This is a solicitation for infrastructure upgrades at a Veterans Affairs medical facility in Columbus, Ohio. The project involves upgrading electrical, IT, and fiber optic infrastructure to support a new electronic health records modernization system. The solicitation is set aside for service-disabled veteran-owned small businesses. Bids are due by 2:00 PM on August 5th and will be evaluated for responsiveness and responsibility. The apparent low bidder must provide documentation of safety, environmental, and insurance records for a responsibility determination. The work includes upgrading fiber throughout buildings to IT closets, a redundant fiber run, a new main fiber line, additional outlets in IT closets, and power distribution upgrades. Buildings in the scope are the main ambulatory care center, engineering building, and energy center.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AUTHORIZED STAMPS

THIS PROJECT CONSISTS OF DESIGN UPGRADES TO THE FACILITIES ELECTRICAL AND IT INFRASTRUCTURE TO ALLOW FOR THE NEW ELECTRONIC HEALTH RECORD MODERNIZATION (EHRM) SYSTEM. THE PROJECT SHALL INCLUDE, BUT IS NOT LIMITED TO, UPGRADING THE FACILITIES FIBER THROUGHOUT THE BUILDINGS TO EACH IT CLOSET, PROVIDE A REDUNDANT FIBER RUN THROUGHOUT THE FACILITY TO EACH IT CLOSET, PROVIDE A NEW MAIN FIBER LINE COMING INTO THE BUILDING FROM THE PROVIDER POINT, PROVIDE ADDITIONAL OUTLETS IN EACH IT CLOSET AND UPGRADE

FACILITY POWER DISTRIBUTION AS REQUIRED.

BUILDINGS INCLUDED IN THE SCOPE OF THE PROJECT INCLUDE THE MAIN AMBULATORY CARE CENTER (ACC), ENGINEERING BUILDING (A), AND THE ENERGY CENTER (EC). THE WORK IN ENGINEERING BUILDING (A) AND THE ENERGY CENTER (EC) IS LIMITED TO THE TELECOM ROOMS. THE WORK IN THE MAIN AMBULATORY CARE CENTER (ACC) INCLUDES THE TELECOM ROOMS, ONE DATA ROOM, AND THE SERVER / MAIN TELECOM ROOM ON LEVEL 4.

ARCHITECTURAL INTERIOR FINISHES ARE LIMITED TO PATCH AND REPAIR AS REQUIRED.

PROJECT DISCRIPTION

Seth A. Cavin

ARCHITECT

Ryan V. Jeppson

CIVIL ENGINEER

AUTHORIZED SIGNATURE APPROVAL

SERVICE/TITLE:

Nicholas E. Roach

REGISTERED COMMUNICATIONS DISTRIBUTION DESIGNER

Benjamin E. Noe

ELECTRICAL ENGINEER

X

SERVICE/TITLE:

X

SERVICE/TITLE:

X

SERVICE/TITLE:

X

SERVICE/TITLE:

X

SERVICE/TITLE:

X

CHRISTOPHER YINGLING

AMBULATORY CARE CENTER ASSOCIATE DIRECTOR

X

M. ALLISON ARENSMAN, M.D.

CHIEF OF STAFF

X

SUSAN WILLIAMS

ASSOCIATE DIRECTOR OF PATIENT CARE SERVICES

X

MARK COOPERMAN, M.D.

AMBULATORY CARE CENTER INTERIM DIRECTOR

X

FARID MEHR, PR

CHIEF, ENGINEERING SERVICES

X

ANDREW BLANFORD, MS, BS, CHTM

CHIEF, HEALTHCARE TECHNOLOGY MANAGEMENT SERVICE (BIOMEDICAL ENGINEERING)

X

SERVICE/TITLE:

X

CHRIS PANNELL

COR/PROJECT ENGINEER

X th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

U.S. DEPARTMENT OF VETERANS AFFAIRS

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. EXP. 06/23/2021

ENGR REG. NO. EXP. 06/30/2021

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

ELEC ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

OH 20314270,

OH 06253,

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, SUITE 1415,

PANAMA CITY BEACH, FL 32407

(502) 836-4232

/9

/2

:3

:3

P

M

COVER SHEET

ECO 1 39BKM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE

UPGRADES

COLUMBUS, OH – TIER 1

VA PROJECT NUMBER: 757-21-701

EHRM INFRASTRUCTURE UPGRADES

COLUMBUS, OH – TIER 1

06/28/2021

757-21-701

Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219

Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219

FINAL BID DOCUMENTS

GI-000

SHEET INDEX

SEQUENCE NUMBER SHEET NAME

[01] GENERAL

1 GI-000 COVER SHEET

2 GI-001 GENERAL INFORMATION

3 GI-011 LIFE SAFETY PLANS

4 GI-012 LIFE SAFETY PLANS

5 GI-013 LIFE SAFETY PLANS

[02] CIVIL

6 GS-001 GENERAL LAYOUT

7 GS-002 SITE PLAN

8 GS-003 GRADING PLAN

9 GS-004 DETAILS

[03] ARCHITECTURAL

10 AS-001 ARCHITECTURAL SITE PLAN

[04] ELECTRICAL

11 E-000 ELECTRICAL LEGEND

12 E-101 REFERENCE PLAN - ACC - LEVEL 1

13 E-101A REFERENCE PLAN - ACC - LEVEL 1 - AREA A

14 E-101B REFERENCE PLAN - ACC - LEVEL 1 - AREA B

15 E-101C REFERENCE PLAN - ENGINEERING BUILDING (A) - LEVEL 1

16 E-101D REFERENCE PLAN - ENERGY CENTER (EC) - LEVEL 1

17 E-102 REFERENCE PLAN - ACC - LEVEL 2

18 E-102A REFERENCE PLAN - ACC - LEVEL 2 - AREA A

19 E-102B REFERENCE PLAN - ACC - LEVEL 2 - AREA B

20 E-103A REFERENCE PLAN - ACC - LEVEL 3 - AREA A

21 E-104A REFERENCE PLAN - ACC - LEVEL 4 - AREA A

22 E-401A ENLARGED PLANS - ACC - LEVEL 1 - AREA A

23 E-401B ENLARGED PLANS - ACC - LEVEL 1 - AREA B

24 E-402A ENLARGED PLANS - ACC - LEVEL 2 - AREA A

25 E-402B ENLARGED PLANS - ACC - LEVEL 2 - AREA B

26 E-403A ENLARGED PLANS - ACC - LEVEL 3 - AREA A

27 E-404A ENLARGED PLANS - ACC - LEVEL 4 - AREA A

28 E-501 ELECTRICAL DETAILS

29 E-502 ELECTRICAL DETAILS

30 E-601 ELECTRICAL SCHEDULES

31 E-602 ELECTRICAL SCHEDULES

[05] TECHNOLOGY

32 T-000 TECHNOLOGY LEGEND

33 T-101 TELECOM - ACC - LEVELS 1, 2, 3, & 4

34 T-101A TELECOM - ACC - LEVEL 1 - AREA A

35 T-101B TELECOM - ACC - LEVEL 1 - AREA B

36 T-102A TELECOM - ACC - LEVEL 2 - AREA A

37 T-102B TELECOM - ACC - LEVEL 2 - AREA B

38 T-103 TELECOM - ACC - LEVELS 3 & 4 - AREA A

39 T-104 TELECOM - ENERGY CENTER (EC) & ENGINEERING BUILDING (A)

TOTAL SHEETS: 39

LOCATION MAP

No. REVISION DESCRIPTION DATE

ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS

PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN

VOLUNTARY STANDARD BODIES.

GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS

SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:

• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL

INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).

• 2021 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)

• 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)

• 2021 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)

• 2021 INTERNATIONAL FIRE CODE

• 2021 NFPA 5000 BUILDING CONSTRUCTION AND SAFETY CODE

• 2019 NFPA 900 BUILDING ENERGY CODE

• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.

• 2020 VA SEISMIC DESIGN REQUIREMENTS, H-18-8

• 2020 NATIONAL ELECTRICAL CODE (NEC), NFPA 70

• 2021 INTERNATIONAL PLUMBING CODE (IPC)

• 2016 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.

• 2015 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)

• 2017 ANSI ICC A117.1 ACCESIBLE AND USABLE BUILDINGS AND FACILITIES

• 2019 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)

• 2017 STEEL CONSTRUCTION MANUAL (15TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)

• ENERGY POLICY ACT OF 2005 (EPACT)

• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND

NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.

• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)

• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS

• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION

SPECIFICATION.

• 2019 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1

• 2019 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15

LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.

NOTES:

1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT

NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN.

DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES

EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).

2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.

1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL

CONFIRM ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF THE

ENTIRE DOCUMENT SET.

2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING ANY

WORK, TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY

DISCREPANCIES TO THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD VERIFY

ALL DIMENSIONS AND EXISTING STRUCTURAL CONDITIONS.

3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE KEPT

CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.

4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF THE

CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO SEPARATE WORK

AREAS FROM THE EXISTING FACILITIES.

5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.

6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO REMAIN IN

PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR, PATCH AND

REPAIR ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.

7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE REPAIRED

OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL COST TO THE

OWNER.

8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO PREVENT

PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING SPACES.

9. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH OTHER

DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS. DRAWINGS, AS A

WHOLE, REPRESENT A COMPLETE SET AND DEPICT REQUIREMENTS FOR COMPLETE

AND OPERATIONAL SYSTEMS. INDIVIDUAL DRAWINGS MAY NOT DEPICT COMPLETE AND

ACCURATE INFORMATION TO COORDINATE COMPLETE AND OPERATIONAL SYSTEMS,

BUT DO SO AS AN ENTIRE DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL

DRAWINGS. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE

OTHER SHEETS AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION

DOCUMENTS THAT REFLECT WORK REQUIRED TO ACHIEVE A COMPLETE AND

OPERATIONAL GOAL. LACK OF COORDINATION AND REVIEW OF DRAWINGS AND

SPECIFICATIONS AS AN ENTIRE DOCUMENT TO INSTALL COMPLETE AND OPERATIONAL

SYSTEMS, BEING OBVIOUS AND TYPICAL INDUSTRY STANDARD, IDENTIFIED IN THE

DRAWINGS AND SPECIFICATIONS, SHALL NOT BE IN ANY WAY AN ADDITIONAL COST TO

THE GOVERNMENT.

10. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SUCH

SERVICES TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 7 CALENDAR DAYS IN

ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE,

EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR

INTERRUPTIONS OF ANY SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 60

CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE PERFORMED AS

DIRECTED BY THE COR. MAJOR INTERRUPTIONS SHALL BE COORDINATED WITH OTHER

MAJOR INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE DISCIPLINE MORE

THAN TWICE THROUGHOUT THE OVERALL CONSTRUCTION SCHEDULE UNLESS

REQUESTED IN WRITING AND APPROVED BY THE COR. CONTRACTOR WILL BE ADVISED,

IN WRITING, OF APPROVAL OF REQUEST, OR OF WHICH OTHER DATE AND/OR TIME

SUCH INTERRUPTION WILL CAUSE THE LEAST INCONVENIENCE TO OPERATIONS OF

THE MEDICAL CENTER. INTERRUPTION TIME APPROVED BY THE MEDICAL CENTER MAY

OCCUR AT TIMES OTHER THAN CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE

INTERRUPTION MAY BE ON WEEKENDS OR LATE HOURS AND MAY NOT BE AN

ADDITIONAL COST TO THE GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT MAY

AFFECT THE NORMAL OPERATION OF THE FACILITY WITH THE COR WHEN SUBMITTING

THE CONSTRUCTION SCHEDULE OR UPDATES TO THE CONSTRUCTION SCHEDULE.

11. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT. SPUR

DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS CONTAINING

BUILDING MATERIALS (ACBM) OR LEAD BASED PAINT (LBP) PRODUCTS WERE

DESIGNED/SPECIFIED AS BUILDING MATERIAL IN ANY OF THE CONSTRUCTION

DOCUMENTS.

14. FIRESTOPPING SHALL BE IN PLACE WITHIN 24 HOURS OF CREATION OF PENETRATION.

GENERAL NOTES

A

ACST ACOUSTIC

ADA AMERICANS WITH DISABILITIES ACT

ACT ACOUSTICAL CEILING TILE

ADDL ADDITIONAL

ADDN ADDITION

ADJ ADJACENT, ADJOINING, OR

ADJUSTABLE

ADMIN ADMINISTRATION

AE ARCHITECT/ENGINEER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHJ AUTHORITY HAVING JURISDICTION

AIA AMERICAN INSTITUTE OF

ARCHITECTS

ALT ALTERNATE

ALT NO ALTERNATE NUMBER

AMT AMOUNT

APPROX APPROXIMATE

ARCH ARCHITECT

ASC ABOVE SUSPENDED CEILING

AVG AVERAGE

B

BD BOARD

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BOS BOTTOM OF STEEL

BOT BOTTOM

BRKT BRACKET

BTWN BETWEEN

C

CAB CABINET

CAV CAVITY

CD CONSTRUCTION DOCUMENTS

CFM CUBIC FEET PER MINUTE

CFS CUBIC FEET PER SECOND

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLG HT CEILING HEIGHT

CLR COLOR

CO CONTRACTING OFFICER

COL COLUMN

COMM COMMUNICATION

CONC CONCRETE

CONT CONTINUOUS

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTRACTOR PROVIDED

CP/CI CONTRACTOR PROVIDED /

CONTRACTOR INSTALLED

CSWK CASEWORK

CTR CENTER

CU FT CUBIC FEET

D

DBL DOUBLE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DIR DIRECTION

DIST DISTANCE

DOC DOCUMENT

DR DOOR

DS DOWNSPOUT

DWG DRAWING

E

EA EACH

EJ EXPANSION JOINT

EL ELEVATION

ELEV ELEVATOR

ENTR ENTRANCE

EQ EQUAL

EX EXISTING

EXP EXPOSED

EXT EXTERIOR

F

FED FEDERAL

FF FINISH FACE

FF EL FINISH FLOOR ELEVATION

FIN FINISH

FIN BS FINISH BOTH SIDES

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIXT FIXTURE

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLMT FLUSH MOUNT

FLR FLOOR

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FR FIRE RESISTANT

FT FEET

FTG FOOTING

FV FIELD VERIFY

G

GR FL GROUND FLOOR

H

HDW HARDWARE

HEPA HIGH EFFICIENCY

PARTICULATE AIR (FILTER)

HORIZ HORIZONTAL

HT HEIGHT

I

IBC INTERNATIONAL BUILDING CODE

INSUL INSULATION

INT INTERIOR

ILO IN LIEU OF

J

J-BOX JUNCTION BOX

L

LAV LAVATORY

LBS POUND

LDG LANDING

LF LINEAR FEET (FOOT)

LIN LINEAR

LOC LOCATION

LT LIGHT

LVR LOUVER

M

MATL MATERIAL

MAX MAXIMUM

MECH MECHANICAL

MEMB MEMBRANE

MFR MANUFACTURER

MID MIDDLE

MIL STD MILITARY STANDARD

MIN MINIMUM

MISC MISCELLANEOUS

MO MASONRY OPENING

MOD MODIFY

MTG MOUNTING

MTL METAL

MVBL MOVABLE

N

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

P

PA PUBLIC ADDRESS

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PERF PERFORATED

PERIM PERIMETER

PERP PERPENDICULAR

PL PROPERTY LINE

PLBG PLUMBING

PNL PANEL

PR PAIR

PRKG PARKING

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PWR POWER

Q

QA QUALITY ASSURANCE

QC QUALITY CONTROL

QTY QUANTITY

R

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RFG ROOFING

RM ROOM

RO ROUGH OPENING

RV ROOF VENT

S

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT (FEET)

SGL SINGLE

SIM SIMILAR

SJ SCORED JOINT

SLNT SEALANT

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

STD STANDARD

STOR STORAGE

T

TEL TELEPHONE

TEMP TEMPORARY

TOF TOP OF FOOTING/ FOUNDATION

TOM TOP OF MASONRY

TOS TOP OF SLAB/ STEEL

U

UNO UNLESS NOTED OTHERWISE

UTIL UTILITY

V

VAR VARIES

VC VA PROVIDED / CONTRACTOR

INSTALLED

VV VA PROVIDED / VA INSTALLED

W

W/ WITH

W/O WITHOUT

W/C WATER CLOSET

WC WHEELCHAIR

WPM WATERPROOF MEMBRANE

X

X BRACE CROSS BRACE

NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.

th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. EXP. 06/23/2021

ENGR REG. NO. EXP. 06/30/2021

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

ELEC ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

OH 20314270,

OH 06253,

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, SUITE 1415,

PANAMA CITY BEACH, FL 32407

(502) 836-4232

/9

/2

:3

:3

P

M

GENERAL INFORMATION

ECO 2 39BKM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

COLUMBUS, OH – TIER 1

06/28/2021

757-21-701

Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219

GI-001

FACP

FEC

AED

FIRE ALARM CONTROL PANEL

FIRE EXTINGUISHER CABINET

AUTOMATED EXTERNAL DEFIBRILLATOR, GC TO

COORDINATE ROUGH-IN CONDITION WITH VA

PROVIDED EQUIPMENT

EXIT LIGHT / SIGN

SPACE NOT OCCUPIED

PROTECTED AREA ENCLOSED WITH SMOKE

PARTITIONS

EGRESS PATH

BUILDING EXIT

OCCUPANT LOAD

NFPA 101-2021 EDITION

BUILDING HEIGHT:

2 STORIES, 36'-0" HEIGHT

BUILDING AREA:

AREA LIMITATION: 37,500 SF PER FLOOR (2012 IBC TABLE 503)

FIRST FLOOR 9,907 SF

SECOND FLOOR 8,931 SF

TOTAL 18,838 SF

BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT

CONSTRUCTION TYPE: (TABLE A.8.2.1.2): TYPE II (000)

FIRE RESISTANCE RATINGS (TABLE A.8.2.1.2):

• COLUMNS: 0 HR

• BEAM, GIRDERS, TRUSSES: 0 HR

• FLOOR/CEILING ASSEMBLIES: 0 HR

• ROOF/CEILING ASSEMBLIES: 0 HR

• EXTERIOR NON-BEARING WALLS: 0 HR

• INTERIOR NON-BEARING WALLS: 0 HR

FIRE-RESISTIVE REQUIREMENTS:

• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR

NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)

CHAPTER 38: NEW BUSINESS OCCUPANCY

OCCUPANT LOADS (TABLE 7.3.1.2):

• FIRST FLOOR BUSINESS USE = 100 SF/PERSON

• SECOND FLOOR BUSINESS USE = 100 SF/PERSON

• FIRST FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON

• SECOND FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON

SHAFTS MINIMUM 1-HOUR RATING (8.6.5)

DEAD END CORRIDOR MAXIMUM DISTANCE: 50' (38.2.5.2.1)

MAXIMUM COMMON PATH OF TRAVEL: 100' (38.2.5.3.1)

MAXIMUM TRAVEL DISTANCE: 300' (38.2.6.3)

CORRIDOR MINIMUM FIRE RATING: 0 HR (38.3.6.1 EXCEPTION 3)

ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR EXIT WIDTH.

- 15"/PERSON (IBC 1005.3.2, EXCEPTION 1) ALLOWS 226 OCCUPANT LOAD PER DOOR MAX.

STAIR WIDTH PROVIDED IS 44 1/4" AT STAIR 1 (SOUTH) AND 42 1/2" AT STAIR 2 (WEST)

- .3"/PERSON (IBC 1005.3.1) ALLOWS 146 OCCUPANT LOAD AT STAIR 1 MAX.

- .3"/PERSON (IBC 1005.3.1) ALLOWS 141 OCCUPANT LOAD AT STAIR 2 MAX.

PROTECTED AREAS:

- STORAGE ROOMS/CLEAN/SOILED - REQUIRED VA FIRE PROTECTION DESIGN MANUAL 3.1.A AND PER NFPA 101: 38.3.2.1 AND 8.7 SMOKE PARTITIONS WITH SPRINKLER PROTECTION, PROVIDED.

-MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION DESIGN MANUAL SECTION 3.1.B.

SMOKE COMPARTMENTALIZATION:

- NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.

FIRE ALARM SYSTEM:

- REQUIRED/PROVIDED MANUAL SYSTEM.

STANDPIPES:

- NOT REQUIRED / NOT PROVIDED.

FIRE - 1 HOUR

FIRE - 2 HOUR

TELECOM

1A457

TELECOM

1A024

TELECOM

1A014

TELECOM

1A106

TELECOM

1B002

DATA

1B609

TELECOM

1B006

TELECOM

2A004

TELECOM

2A143

TELECOM

2B102

TELECOM

2B310

TELECOM

2A018

TELECOM

2B003 th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. EXP. 06/23/2021

ENGR REG. NO. EXP. 06/30/2021

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

ELEC ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

OH 20314270,

OH 06253,

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, SUITE 1415,

PANAMA CITY BEACH, FL 32407

(502) 836-4232

/9

/2

:3

:0

P

M

LIFE SAFETY PLANS

ECO 3 39BKM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

COLUMBUS, OH – TIER 1

06/28/2021

757-21-701

Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219

GI-011

LIFE SAFETY LEGEND

LIFE SAFETY REQUIREMENTS

RATED PARTITIONS & BARRIERS

1/32" = 1'-0"

CPW AMBULATORY CARE CENTER - LEVEL 1 - LIFE SAFETY PLAN1

1/32" = 1'-0"

CPW AMBULATORY CARE CENTER - LEVEL 2 - LIFE SAFETY PLAN2

DN

TELECOM

3A004

TELECOM

3A015

TELECOM

3A063

SERVER / MAIN

TELECOM

4A201

TELECOM

4A041

ELECT. ROOM

4A012

NFPA 101-2021 EDITION

BUILDING HEIGHT:

2 STORIES, 36'-0" HEIGHT

BUILDING AREA:

AREA LIMITATION: 37,500 SF PER FLOOR (2012 IBC TABLE 503)

FIRST FLOOR 9,907 SF

SECOND FLOOR 8,931 SF

TOTAL 18,838 SF

BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT

CONSTRUCTION TYPE: (TABLE A.8.2.1.2): TYPE II (000)

FIRE RESISTANCE RATINGS (TABLE A.8.2.1.2):

• COLUMNS: 0 HR

• BEAM, GIRDERS, TRUSSES: 0 HR

• FLOOR/CEILING ASSEMBLIES: 0 HR

• ROOF/CEILING ASSEMBLIES: 0 HR

• EXTERIOR NON-BEARING WALLS: 0 HR

• INTERIOR NON-BEARING WALLS: 0 HR

FIRE-RESISTIVE REQUIREMENTS:

• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR

NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)

CHAPTER 38: NEW BUSINESS OCCUPANCY

OCCUPANT LOADS (TABLE 7.3.1.2):

• FIRST FLOOR BUSINESS USE = 100 SF/PERSON

• SECOND FLOOR BUSINESS USE = 100 SF/PERSON

• FIRST FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON

• SECOND FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON

SHAFTS MINIMUM 1-HOUR RATING (8.6.5)

DEAD END CORRIDOR MAXIMUM DISTANCE: 50' (38.2.5.2.1)

MAXIMUM COMMON PATH OF TRAVEL: 100' (38.2.5.3.1)

MAXIMUM TRAVEL DISTANCE: 300' (38.2.6.3)

CORRIDOR MINIMUM FIRE RATING: 0 HR (38.3.6.1 EXCEPTION 3)

ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR EXIT WIDTH.

- 15"/PERSON (IBC 1005.3.2, EXCEPTION 1) ALLOWS 226 OCCUPANT LOAD PER DOOR MAX.

STAIR WIDTH PROVIDED IS 44 1/4" AT STAIR 1 (SOUTH) AND 42 1/2" AT STAIR 2 (WEST)

- .3"/PERSON (IBC 1005.3.1) ALLOWS 146 OCCUPANT LOAD AT STAIR 1 MAX.

- .3"/PERSON (IBC 1005.3.1) ALLOWS 141 OCCUPANT LOAD AT STAIR 2 MAX.

PROTECTED AREAS:

- STORAGE ROOMS/CLEAN/SOILED - REQUIRED VA FIRE PROTECTION DESIGN MANUAL 3.1.A AND PER NFPA 101: 38.3.2.1 AND 8.7 SMOKE PARTITIONS WITH SPRINKLER PROTECTION, PROVIDED.

-MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION DESIGN MANUAL SECTION 3.1.B.

SMOKE COMPARTMENTALIZATION:

- NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.

FIRE ALARM SYSTEM:

- REQUIRED/PROVIDED MANUAL SYSTEM.

STANDPIPES:

- NOT REQUIRED / NOT PROVIDED.

FACP

FEC

AED

FIRE ALARM CONTROL PANEL

FIRE EXTINGUISHER CABINET

AUTOMATED EXTERNAL DEFIBRILLATOR, GC TO

COORDINATE ROUGH-IN CONDITION WITH VA

PROVIDED EQUIPMENT

EXIT LIGHT / SIGN

SPACE NOT OCCUPIED

PROTECTED AREA ENCLOSED WITH SMOKE

PARTITIONS

EGRESS PATH

BUILDING EXIT

OCCUPANT LOAD

FIRE - 1 HOUR

FIRE - 2 HOUR

th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. EXP. 06/23/2021

ENGR REG. NO. EXP. 06/30/2021

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

ELEC ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

OH 20314270,

OH 06253,

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, SUITE 1415,

PANAMA CITY BEACH, FL 32407

(502) 836-4232

/9

/2

:3

:1

P

M

LIFE SAFETY PLANS

ECO 4 39BKM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

COLUMBUS, OH – TIER 1

06/28/2021

757-21-701

Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219

GI-012

1/32" = 1'-0"

CPW AMBULATORY CARE CENTER - LEVEL 3 - LIFE SAFETY PLAN1

1/32" = 1'-0"

CPW AMBULATORY CARE CENTER - LEVEL 4 - LIFE SAFETY PLAN2

LIFE SAFETY REQUIREMENTS

LIFE SAFETY LEGEND

RATED PARTITIONS & BARRIERS

UP

NFPA 101-2021 EDITION

BUILDING HEIGHT:

2 STORIES, 36'-0" HEIGHT

BUILDING AREA:

AREA LIMITATION: 37,500 SF PER FLOOR (2012 IBC TABLE 503)

FIRST FLOOR 9,907 SF

SECOND FLOOR 8,931 SF

TOTAL 18,838 SF

BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT

CONSTRUCTION TYPE: (TABLE A.8.2.1.2): TYPE II (000)

FIRE RESISTANCE RATINGS (TABLE A.8.2.1.2):

• COLUMNS: 0 HR

• BEAM, GIRDERS, TRUSSES: 0 HR

• FLOOR/CEILING ASSEMBLIES: 0 HR

• ROOF/CEILING ASSEMBLIES: 0 HR

• EXTERIOR NON-BEARING WALLS: 0 HR

• INTERIOR NON-BEARING WALLS: 0 HR

FIRE-RESISTIVE REQUIREMENTS:

• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR

NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)

CHAPTER 38: NEW BUSINESS OCCUPANCY

OCCUPANT LOADS (TABLE 7.3.1.2):

• FIRST FLOOR BUSINESS USE = 100 SF/PERSON

• SECOND FLOOR BUSINESS USE = 100 SF/PERSON

• FIRST FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON

• SECOND FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON

SHAFTS MINIMUM 1-HOUR RATING (8.6.5)

DEAD END CORRIDOR MAXIMUM DISTANCE: 50' (38.2.5.2.1)

MAXIMUM COMMON PATH OF TRAVEL: 100' (38.2.5.3.1)

MAXIMUM TRAVEL DISTANCE: 300' (38.2.6.3)

CORRIDOR MINIMUM FIRE RATING: 0 HR (38.3.6.1 EXCEPTION 3)

ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR EXIT WIDTH.

- 15"/PERSON (IBC 1005.3.2, EXCEPTION 1) ALLOWS 226 OCCUPANT LOAD PER DOOR MAX.

STAIR WIDTH PROVIDED IS 44 1/4" AT STAIR 1 (SOUTH) AND 42 1/2" AT STAIR 2 (WEST)

- .3"/PERSON (IBC 1005.3.1) ALLOWS 146 OCCUPANT LOAD AT STAIR 1 MAX.

- .3"/PERSON (IBC 1005.3.1) ALLOWS 141 OCCUPANT LOAD AT STAIR 2 MAX.

PROTECTED AREAS:

- STORAGE ROOMS/CLEAN/SOILED - REQUIRED VA FIRE PROTECTION DESIGN MANUAL 3.1.A AND PER NFPA 101: 38.3.2.1 AND 8.7 SMOKE PARTITIONS WITH SPRINKLER PROTECTION, PROVIDED.

-MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION DESIGN MANUAL SECTION 3.1.B.

SMOKE COMPARTMENTALIZATION:

- NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.

FIRE ALARM SYSTEM:

- REQUIRED/PROVIDED MANUAL SYSTEM.

STANDPIPES:

- NOT REQUIRED / NOT PROVIDED.

FACP

FEC

AED

FIRE ALARM CONTROL PANEL

FIRE EXTINGUISHER CABINET

AUTOMATED EXTERNAL DEFIBRILLATOR, GC TO

COORDINATE ROUGH-IN CONDITION WITH VA

PROVIDED EQUIPMENT

EXIT LIGHT / SIGN

SPACE NOT OCCUPIED

PROTECTED AREA ENCLOSED WITH SMOKE

PARTITIONS

EGRESS PATH

BUILDING EXIT

OCCUPANT LOAD

FIRE - 1 HOUR

FIRE - 2 HOUR

DATA RM

NO RATED WALLS

1 2 3 4

A.2

B

D

C

F

E

G

1.8

B.4

A

2.72.6

DATA RM

th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t

00 00

11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t

00 00

22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t

00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t

00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t

00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

00 00 44 44

88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t

00 00 44 44

88 88

A

B

C

D

E

F

Veterans Health

Administration

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project Number

CONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. EXP. 06/23/2021

ENGR REG. NO. EXP. 06/30/2021

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

ELEC ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

FULLY SPRINKLERED

INDUSTRIAL HYGENIST

RSH

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

STAMP:

OH 20314270,

OH 06253,

Drawing Number

Building Number

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, SUITE 1415,

PANAMA CITY BEACH, FL 32407

(502) 836-4232

/9

/2

:3

:1

P

M

LIFE SAFETY PLANS

ECO 5 39BKM

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES

COLUMBUS, OH – TIER 1

06/28/2021

757-21-701

Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219

GI-013

LIFE SAFETY REQUIREMENTS

LIFE SAFETY LEGEND

RATED PARTITIONS & BARRIERS

No. REVISION DESCRIPTION DATE

3/32" = 1'-0"

ENGINEERING BUILDING - LEVEL 1 - LIFE SAFETY PLAN33/32" = 1'-0"

BOILER PLANT - LEVEL 1 - LIFE SAFETY PLAN4

N N

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. EXP. 06/23/2021

ENGR REG. NO. EXP. 06/30/2021

STAMP:

OH 20314270,

OH 06253,

Drawing Number

Building Number

CRW 39RGH

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES -

COLUMBUS, OH - TIER 1

6/28/2021

757-21-701

CHALMERS P. WYLIE VA AMBULATORY CARE CENTER

420 NORTH JAMES ROAD

COLUMBUS, OH 43219

ACC

No. REVISION DESCRIPTION DATE

FULLY SPRINKLERED

Veterans Health

Administration

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

ELEC ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

INDUSTRIAL HYGENIST

RSH

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, SUITE 1415,

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 ASI-0001 1/26/2022

LEGEND

GENERAL LAYOUT

GS-001

GENERAL NOTES:

CALL 811 SEVENTY-TWO HOURS PRIOR TO

DIGGING, GRADING OR EXCAVATING FOR THE

MARKING OF UNDERGROUND MEMBER UTILITIES.

Know what's below.

before you dig.CallR

KEYNOTES:

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. EXP. 06/23/2021

ENGR REG. NO. EXP. 06/30/2021

STAMP:

OH 20314270,

OH 06253,

Drawing Number

Building Number

CRW 39RGH

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES -

COLUMBUS, OH - TIER 1

6/28/2021

757-21-701

CHALMERS P. WYLIE VA AMBULATORY CARE CENTER

420 NORTH JAMES ROAD

COLUMBUS, OH 43219

ACC

No. REVISION DESCRIPTION DATE

FULLY SPRINKLERED

Veterans Health

Administration

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

ELEC ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

INDUSTRIAL HYGENIST

RSH

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, SUITE 1415,

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 ASI-0001 1/26/2022

LEGEND

GENERAL NOTES:

PAVEMENT MARKING NOTES:

KEYNOTES:

DEMOLITION NOTES:

CALL 811 SEVENTY-TWO HOURS PRIOR TO

DIGGING, GRADING OR EXCAVATING FOR THE

MARKING OF UNDERGROUND MEMBER UTILITIES.

Know what's below.

before you dig.CallR

SITE PLAN

GS-002

A

B

C

D

E

F

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Drawing Title Project Title

Location

Date Checked Drawn

Project NumberCONSULTANTS:

Drawing # OF

VA Health Care System Approval:

ARCHITECT:

SPUR DESIGN, LLC

312 SW 25TH STREET

Oklahoma City, OK 73109

(405) 842-6100

ARCH REG. NO. EXP. 06/23/2021

ENGR REG. NO. EXP. 06/30/2021

STAMP:

OH 20314270,

OH 06253,

Drawing Number

Building Number

CRW 39RGH

FINAL BID DOCUMENTS

EHRM INFRASTRUCTURE UPGRADES -

COLUMBUS, OH - TIER 1

6/28/2021

757-21-701

CHALMERS P. WYLIE VA AMBULATORY CARE CENTER

420 NORTH JAMES ROAD

COLUMBUS, OH 43219

ACC

No. REVISION DESCRIPTION DATE

FULLY SPRINKLERED

Veterans Health

Administration

TELECOM

ASPEN ENGINEERING & CONTRACTING

7 KIJI-DAVA CIRCLE

PRESCOTT, AZ 86301

(928) 774-0992

ELEC ENGINEER

SPUR DESIGN

11020 KING STREET, SUITE 350

OVERLAND PARK, KS 66210

(405) 842-6100

INDUSTRIAL HYGENIST

RSH

1225 N. LOOP WEST, SUITE 800

HOUSTON, TX 77008

(713) 864-2900

CIVIL ENGINEER

OLSSON

550 ST. LOUIS ST.

SPRINGFIELD, MO 65806

(417) 885-1736

PHYSICAL SECURITY

FORCE PROTECT

10901 FRONT BEACH ROAD, SUITE 1415,

PANAMA CITY BEACH, FL 32407

(502) 836-4232

1 ASI-0001 1/26/2022

LEGEND

GRADING NOTES: GENERAL NOTES:

CALL 811 SEVENTY-TWO HOURS PRIOR TO

DIGGING, GRADING OR EXCAVATING FOR THE

MARKING OF UNDERGROUND MEMBER UTILITIES.

Know what's below.

before you dig.CallR

GRADING PLAN

GS-003

01_GI-000 COVER SHEET
02_GI-001 GENERAL INFORMATION
Sheets
GI-001 - GENERAL INFORMATION
03_GI-011 LIFE SAFETY PLANS
Sheets
GI-011 - LIFE SAFETY PLANS
04_GI-012 LIFE SAFETY PLANS
Sheets
GI-012 - LIFE SAFETY PLANS
05_GI-013 LIFE SAFETY PLANS
Sheets
GI-013 - LIFE SAFETY PLANS
06_GS-001 GENERAL LAYOUT
Sheets and Views
GS-001 GENERAL LAYOUT
07_GS-002 SITE PLAN
Sheets and Views
GS-002 SITE PLAN
08_GS-003 GRADING PLAN
Sheets and Views
GS-003 GRADING PLAN

File details come from the government source that posted it. Updated .