ATTACHMENT 10 EHRM Tier 1 Design Drawings - 1 of 3.pdf
PDF 6 MB Posted
- Attached to
- Y1BG--757-22-1-344-0002 EHRM Infrastructure Upgrades - Columbus, OH - Tier 1 (VA-21-00085439)
- Solicitation number
- 36C77622B0048
About this file
This is a solicitation for infrastructure upgrades at a Veterans Affairs medical facility in Columbus, Ohio. The project involves upgrading electrical, IT, and fiber optic infrastructure to support a new electronic health records modernization system. The solicitation is set aside for service-disabled veteran-owned small businesses. Bids are due by 2:00 PM on August 5th and will be evaluated for responsiveness and responsibility. The apparent low bidder must provide documentation of safety, environmental, and insurance records for a responsibility determination. The work includes upgrading fiber throughout buildings to IT closets, a redundant fiber run, a new main fiber line, additional outlets in IT closets, and power distribution upgrades. Buildings in the scope are the main ambulatory care center, engineering building, and energy center.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AUTHORIZED STAMPS
THIS PROJECT CONSISTS OF DESIGN UPGRADES TO THE FACILITIES ELECTRICAL AND IT INFRASTRUCTURE TO ALLOW FOR THE NEW ELECTRONIC HEALTH RECORD MODERNIZATION (EHRM) SYSTEM. THE PROJECT SHALL INCLUDE, BUT IS NOT LIMITED TO, UPGRADING THE FACILITIES FIBER THROUGHOUT THE BUILDINGS TO EACH IT CLOSET, PROVIDE A REDUNDANT FIBER RUN THROUGHOUT THE FACILITY TO EACH IT CLOSET, PROVIDE A NEW MAIN FIBER LINE COMING INTO THE BUILDING FROM THE PROVIDER POINT, PROVIDE ADDITIONAL OUTLETS IN EACH IT CLOSET AND UPGRADE
FACILITY POWER DISTRIBUTION AS REQUIRED.
BUILDINGS INCLUDED IN THE SCOPE OF THE PROJECT INCLUDE THE MAIN AMBULATORY CARE CENTER (ACC), ENGINEERING BUILDING (A), AND THE ENERGY CENTER (EC). THE WORK IN ENGINEERING BUILDING (A) AND THE ENERGY CENTER (EC) IS LIMITED TO THE TELECOM ROOMS. THE WORK IN THE MAIN AMBULATORY CARE CENTER (ACC) INCLUDES THE TELECOM ROOMS, ONE DATA ROOM, AND THE SERVER / MAIN TELECOM ROOM ON LEVEL 4.
ARCHITECTURAL INTERIOR FINISHES ARE LIMITED TO PATCH AND REPAIR AS REQUIRED.
PROJECT DISCRIPTION
Seth A. Cavin
ARCHITECT
Ryan V. Jeppson
CIVIL ENGINEER
AUTHORIZED SIGNATURE APPROVAL
SERVICE/TITLE:
Nicholas E. Roach
REGISTERED COMMUNICATIONS DISTRIBUTION DESIGNER
Benjamin E. Noe
ELECTRICAL ENGINEER
X
SERVICE/TITLE:
X
SERVICE/TITLE:
X
SERVICE/TITLE:
X
SERVICE/TITLE:
X
SERVICE/TITLE:
X
CHRISTOPHER YINGLING
AMBULATORY CARE CENTER ASSOCIATE DIRECTOR
X
M. ALLISON ARENSMAN, M.D.
CHIEF OF STAFF
X
SUSAN WILLIAMS
ASSOCIATE DIRECTOR OF PATIENT CARE SERVICES
X
MARK COOPERMAN, M.D.
AMBULATORY CARE CENTER INTERIM DIRECTOR
X
FARID MEHR, PR
CHIEF, ENGINEERING SERVICES
X
ANDREW BLANFORD, MS, BS, CHTM
CHIEF, HEALTHCARE TECHNOLOGY MANAGEMENT SERVICE (BIOMEDICAL ENGINEERING)
X
SERVICE/TITLE:
X
CHRIS PANNELL
COR/PROJECT ENGINEER
X th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t
00 00
11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t
00 00
22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t
00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t
00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
00 00 44 44
88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t
00 00 44 44
88 88
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
U.S. DEPARTMENT OF VETERANS AFFAIRS
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. EXP. 06/23/2021
ENGR REG. NO. EXP. 06/30/2021
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
ELEC ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
OH 20314270,
OH 06253,
Drawing Number
Building Number
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, SUITE 1415,
PANAMA CITY BEACH, FL 32407
(502) 836-4232
/9
/2
:3
:3
P
M
COVER SHEET
ECO 1 39BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE
UPGRADES
COLUMBUS, OH – TIER 1
VA PROJECT NUMBER: 757-21-701
EHRM INFRASTRUCTURE UPGRADES
COLUMBUS, OH – TIER 1
06/28/2021
757-21-701
Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219
Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219
FINAL BID DOCUMENTS
GI-000
SHEET INDEX
SEQUENCE NUMBER SHEET NAME
[01] GENERAL
1 GI-000 COVER SHEET
2 GI-001 GENERAL INFORMATION
3 GI-011 LIFE SAFETY PLANS
4 GI-012 LIFE SAFETY PLANS
5 GI-013 LIFE SAFETY PLANS
[02] CIVIL
6 GS-001 GENERAL LAYOUT
7 GS-002 SITE PLAN
8 GS-003 GRADING PLAN
9 GS-004 DETAILS
[03] ARCHITECTURAL
10 AS-001 ARCHITECTURAL SITE PLAN
[04] ELECTRICAL
11 E-000 ELECTRICAL LEGEND
12 E-101 REFERENCE PLAN - ACC - LEVEL 1
13 E-101A REFERENCE PLAN - ACC - LEVEL 1 - AREA A
14 E-101B REFERENCE PLAN - ACC - LEVEL 1 - AREA B
15 E-101C REFERENCE PLAN - ENGINEERING BUILDING (A) - LEVEL 1
16 E-101D REFERENCE PLAN - ENERGY CENTER (EC) - LEVEL 1
17 E-102 REFERENCE PLAN - ACC - LEVEL 2
18 E-102A REFERENCE PLAN - ACC - LEVEL 2 - AREA A
19 E-102B REFERENCE PLAN - ACC - LEVEL 2 - AREA B
20 E-103A REFERENCE PLAN - ACC - LEVEL 3 - AREA A
21 E-104A REFERENCE PLAN - ACC - LEVEL 4 - AREA A
22 E-401A ENLARGED PLANS - ACC - LEVEL 1 - AREA A
23 E-401B ENLARGED PLANS - ACC - LEVEL 1 - AREA B
24 E-402A ENLARGED PLANS - ACC - LEVEL 2 - AREA A
25 E-402B ENLARGED PLANS - ACC - LEVEL 2 - AREA B
26 E-403A ENLARGED PLANS - ACC - LEVEL 3 - AREA A
27 E-404A ENLARGED PLANS - ACC - LEVEL 4 - AREA A
28 E-501 ELECTRICAL DETAILS
29 E-502 ELECTRICAL DETAILS
30 E-601 ELECTRICAL SCHEDULES
31 E-602 ELECTRICAL SCHEDULES
[05] TECHNOLOGY
32 T-000 TECHNOLOGY LEGEND
33 T-101 TELECOM - ACC - LEVELS 1, 2, 3, & 4
34 T-101A TELECOM - ACC - LEVEL 1 - AREA A
35 T-101B TELECOM - ACC - LEVEL 1 - AREA B
36 T-102A TELECOM - ACC - LEVEL 2 - AREA A
37 T-102B TELECOM - ACC - LEVEL 2 - AREA B
38 T-103 TELECOM - ACC - LEVELS 3 & 4 - AREA A
39 T-104 TELECOM - ENERGY CENTER (EC) & ENGINEERING BUILDING (A)
TOTAL SHEETS: 39
LOCATION MAP
No. REVISION DESCRIPTION DATE
ABBREVIATIONS CODES STANDARDS AND EXECUTIVE ORDERS
PURPOSE: THE PUBLIC BUILDINGS AMENDMENT ACT OF 1988, PUBLIC LAW (PUB. L.) 100-678 REQUIRES FEDERAL AGENCIES TO FOLLOW NATIONAL RECOGNIZED "MODEL" BUILDING CODES. THE FEDERAL PARTICIPATION IN THE DEVELOPMENT AND USE OF VOLUNTARY STANDARDS, OFFICE OF MANAGEMENT AND BUDGET (OMB) CIRCULAR A-119, REQUIRES ALL EXECUTIVE AGENCIES TO RELY ON VOLUNTARY STANDARDS, BOTH DOMESTIC AND INTERNATIONAL, WHENEVER FEASIBLE, AND TO PARTICIPATE IN
VOLUNTARY STANDARD BODIES.
GENERAL: VA HAS ADOPTED THE LATEST EDITION OF THE FOLLOWING CODES AND STANDARDS AS A MINIMUM FOR ALL PROJECTS PERFORMED IN THE MODERNIZATION, ALTERATION, ADDITION, OR IMPROVEMENT OF ITS REAL PROPERTY AND THE CONSTRUCTION OF NEW STRUCTURES. VA DESIGN MANUALS AND MASTER SPECIFICATIONS
SPECIFY OTHER CODES AND STANDARDS THAT VA FOLLOWS ON ITS PROJECTS:
• VA DIRECTIVES, DESIGN MANUALS, MASTER SPECIFICATIONS, VA NATIONAL CAD STANDARD APPLICATION GUIDE, AND OTHER GUIDANCE ON THE TECHNICAL
INFORMATION LIBRARY (TIL) (HTTP://WWW.CFM.VA.GOV/TIL/).
• 2021 INTERNATIONAL BUILDING CODE (IBC) (ONLY WHEN SPECIFICALLY REFERENCED IN VA DESIGN DOCUMENTS, SEE NOTES BELOW)
• 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) (IF APPLICABLE)
• 2021 NFPA 101 LIFE SAFETY CODE (SEE NOTES BELOW)
• 2021 INTERNATIONAL FIRE CODE
• 2021 NFPA 5000 BUILDING CONSTRUCTION AND SAFETY CODE
• 2019 NFPA 900 BUILDING ENERGY CODE
• OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION (OSHA) STANDARDS.
• 2020 VA SEISMIC DESIGN REQUIREMENTS, H-18-8
• 2020 NATIONAL ELECTRICAL CODE (NEC), NFPA 70
• 2021 INTERNATIONAL PLUMBING CODE (IPC)
• 2016 SAFETY CODE FOR ELEVATORS AND ESCALATORS, AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME) A 17.1.
• 2015 ARCHITECTURAL BARRIERS ACT (ABA) STANDARDS INCLUDING VA SUPPLEMENT, VA BARRIER FREE DESIGN STANDARD (PG-18-13)
• 2017 ANSI ICC A117.1 ACCESIBLE AND USABLE BUILDINGS AND FACILITIES
• 2019 BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE AND COMMENTARY, AMERICAN CONCRETE INSTITUTE AND COMMENTARY (ACI 318-19)
• 2017 STEEL CONSTRUCTION MANUAL (15TH EDITION), AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
• ENERGY POLICY ACT OF 2005 (EPACT)
• 2007 DOE INTERIM FINAL RULE: ENERGY CONSERVATION STANDARDS FOR NEW FEDERAL, COMMERCIAL AND MULTI-FAMILY HIGH-RISE RESIDENTIAL BUILDINGS AND
NEW LOW-RISE RESIDENTIAL BUILDINGS, 10 CFR PARTS 433, 434 AND 435.
• 2006 FEDERAL LEADERSHIP IN HIGH PERFORMANCE AND SUSTAINABLE BUILDINGS: MEMORANDUM OF UNDERSTANDING (MOU)
• 2018 EXECUTIVE ORDER 13834: EFFICIENT FEDERAL OPERATIONS
• 2021 THE PROVISIONS FOR CONSTRUCTION AND SAFETY SIGNS. STATED IN THE GENERAL REQUIREMENTS SECTION 010000 OF THE VA MASTER CONSTRUCTION
SPECIFICATION.
• 2019 VENTILATION FOR ACCEPTABLE INDOOR AIR QUALITY – ASHRAE STANDARD 62.1
• 2019 SAFETY STANDARD FOR REFRIGERATION SYSTEMS – ASHRAE STANDARD 15
LOCAL CODES: AS AN AGENCY OF THE FEDERAL GOVERNMENT, VA IS NOT SUBJECT TO LOCAL IMPOSITION OF CODE ENFORCEMENT PROCEDURES (DRAWING REVIEWS, BUILDING PERMITS, INSPECTIONS, FEES, ETC.). VA MUST FUNCTION AS THE AUTHORITY HAVING JURISDICTION (AHJ) AND THUS HAS THE RESPONSIBILITY TO GUARD PUBLIC HEALTH AND SAFETY THROUGH ENFORCING ITS ADOPTED CODES. HOWEVER, LOCAL AUTHORITIES SHOULD BE NOTIFIED ABOUT PLANNED PROJECTS AND GIVEN OPPORTUNITY TO REVIEW DRAWINGS PROVIDED THAT VA DOES NOT PAY FOR REVIEW OR INSPECTION FEES.
NOTES:
1. NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT
NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN.
DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED ABOVE IN THIS PROGRAM GUIDE. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES
EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT).
2. CONFLICTS BETWEEN NATIONALLY RECOGNIZED CODES AND STANDARDS AND VA REQUIREMENTS – SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION FOR VA TO ENSURE A CONSISTENCY SYSTEM WIDE.
1. DRAWINGS ARE PART OF A COMPLETE DOCUMENTS SET. CONTRACTOR SHALL
CONFIRM ALL ITEMS REQUIRED BASED UPON THE OVERALL DESIGN INTENT OF THE
ENTIRE DOCUMENT SET.
2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS, PRIOR TO BEGINNING ANY
WORK, TO CONFIRM THE ACCURACY OF THE DRAWINGS AND REPORT ANY
DISCREPANCIES TO THE ARCHITECT. DO NOT SCALE THE DRAWINGS. FIELD VERIFY
ALL DIMENSIONS AND EXISTING STRUCTURAL CONDITIONS.
3. ALL AREAS NOT INVOLVED IN THE SCOPE OF WORK FOR THIS PROJECT SHALL BE KEPT
CLEAN AND FREE OF OBSTRUCTIONS AT ALL TIMES.
4. ERECT BARRICADES AND WARNING SIGNS TO DIVERT AND WARN PASSERS-BY OF THE
CONSTRUCTION WORK. PROVIDE DUST PROOFING ENCLOSURES TO SEPARATE WORK
AREAS FROM THE EXISTING FACILITIES.
5. ALL TRASH AND DEBRIS TO BE REMOVED ON A DAILY BASIS.
6. PROVIDE PROTECTION FOR ALL EXISTING SURFACES AND CONDITIONS TO REMAIN IN
PLACE DURING THE SCOPE OF WORK. SHOULD ANY DAMAGE OCCUR, PATCH AND
REPAIR ANY DAMAGE TO ADJACENT FINISHES TO MATCH EXISTING.
7. ANY DAMAGE CAUSED TO THE BUILDING OR OWNER EQUIPMENT SHALL BE REPAIRED
OR REPLACED BACK TO ITS ORIGINAL CONDITIONS AT NO ADDITIONAL COST TO THE
OWNER.
8. COVER ALL RETURN AIR GRILLES WITHIN THE AREA OF CONSTRUCTION TO PREVENT
PARTICULATE MATERIAL FROM EXHAUSTING INTO SURROUNDING SPACES.
9. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO COORDINATE WITH OTHER
DISCIPLINES TO INSTALL COMPLETE AND OPERATIONAL SYSTEMS. DRAWINGS, AS A
WHOLE, REPRESENT A COMPLETE SET AND DEPICT REQUIREMENTS FOR COMPLETE
AND OPERATIONAL SYSTEMS. INDIVIDUAL DRAWINGS MAY NOT DEPICT COMPLETE AND
ACCURATE INFORMATION TO COORDINATE COMPLETE AND OPERATIONAL SYSTEMS,
BUT DO SO AS AN ENTIRE DOCUMENT TO BE REFERENCED WITH OTHER INDIVIDUAL
DRAWINGS. CONTRACTOR AND SUBCONTRACTORS ARE REQUIRED TO REFERENCE
OTHER SHEETS AND SPECIFICATIONS AS AN ENTIRE SET OF CONSTRUCTION
DOCUMENTS THAT REFLECT WORK REQUIRED TO ACHIEVE A COMPLETE AND
OPERATIONAL GOAL. LACK OF COORDINATION AND REVIEW OF DRAWINGS AND
SPECIFICATIONS AS AN ENTIRE DOCUMENT TO INSTALL COMPLETE AND OPERATIONAL
SYSTEMS, BEING OBVIOUS AND TYPICAL INDUSTRY STANDARD, IDENTIFIED IN THE
DRAWINGS AND SPECIFICATIONS, SHALL NOT BE IN ANY WAY AN ADDITIONAL COST TO
THE GOVERNMENT.
10. CONTRACTOR SHALL SUBMIT A REQUEST, IN WRITING, TO INTERRUPT ANY SUCH
SERVICES TO COR (CONTRACTING OFFICER’S REPRESENTATIVE) 7 CALENDAR DAYS IN
ADVANCE OF PROPOSED INTERRUPTION. REQUEST SHALL STATE REASON, DATE,
EXACT TIME OF, AND APPROXIMATE DURATION OF SUCH INTERRUPTION. MAJOR
INTERRUPTIONS OF ANY SYSTEM MUST BE REQUESTED, IN WRITING, AT LEAST 60
CALENDAR DAYS PRIOR TO THE DESIRED TIME AND SHALL BE PERFORMED AS
DIRECTED BY THE COR. MAJOR INTERRUPTIONS SHALL BE COORDINATED WITH OTHER
MAJOR INTERRUPTIONS AND MAY NOT BE SCHEDULED FOR ONE DISCIPLINE MORE
THAN TWICE THROUGHOUT THE OVERALL CONSTRUCTION SCHEDULE UNLESS
REQUESTED IN WRITING AND APPROVED BY THE COR. CONTRACTOR WILL BE ADVISED,
IN WRITING, OF APPROVAL OF REQUEST, OR OF WHICH OTHER DATE AND/OR TIME
SUCH INTERRUPTION WILL CAUSE THE LEAST INCONVENIENCE TO OPERATIONS OF
THE MEDICAL CENTER. INTERRUPTION TIME APPROVED BY THE MEDICAL CENTER MAY
OCCUR AT TIMES OTHER THAN CONTRACTOR'S NORMAL WORKING HOURS. SCHEDULE
INTERRUPTION MAY BE ON WEEKENDS OR LATE HOURS AND MAY NOT BE AN
ADDITIONAL COST TO THE GOVERNMENT. COORDINATE ALL INTERRUPTIONS THAT MAY
AFFECT THE NORMAL OPERATION OF THE FACILITY WITH THE COR WHEN SUBMITTING
THE CONSTRUCTION SCHEDULE OR UPDATES TO THE CONSTRUCTION SCHEDULE.
11. NO ASBESTOS CONTAINING MATERIALS ARE TO BE USED ON THIS PROJECT. SPUR
DESIGN, THE A/E OF RECORD, CAN CERTIFY THAT NO ASBESTOS CONTAINING
BUILDING MATERIALS (ACBM) OR LEAD BASED PAINT (LBP) PRODUCTS WERE
DESIGNED/SPECIFIED AS BUILDING MATERIAL IN ANY OF THE CONSTRUCTION
DOCUMENTS.
14. FIRESTOPPING SHALL BE IN PLACE WITHIN 24 HOURS OF CREATION OF PENETRATION.
GENERAL NOTES
A
ACST ACOUSTIC
ADA AMERICANS WITH DISABILITIES ACT
ACT ACOUSTICAL CEILING TILE
ADDL ADDITIONAL
ADDN ADDITION
ADJ ADJACENT, ADJOINING, OR
ADJUSTABLE
ADMIN ADMINISTRATION
AE ARCHITECT/ENGINEER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIA AMERICAN INSTITUTE OF
ARCHITECTS
ALT ALTERNATE
ALT NO ALTERNATE NUMBER
AMT AMOUNT
APPROX APPROXIMATE
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
AVG AVERAGE
B
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BOS BOTTOM OF STEEL
BOT BOTTOM
BRKT BRACKET
BTWN BETWEEN
C
CAB CABINET
CAV CAVITY
CD CONSTRUCTION DOCUMENTS
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG HT CEILING HEIGHT
CLR COLOR
CO CONTRACTING OFFICER
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONT CONTINUOUS
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CONTRACTOR PROVIDED
CP/CI CONTRACTOR PROVIDED /
CONTRACTOR INSTALLED
CSWK CASEWORK
CTR CENTER
CU FT CUBIC FEET
D
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
DWG DRAWING
E
EA EACH
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EQ EQUAL
EX EXISTING
EXP EXPOSED
EXT EXTERIOR
F
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FT FEET
FTG FOOTING
FV FIELD VERIFY
G
GR FL GROUND FLOOR
H
HDW HARDWARE
HEPA HIGH EFFICIENCY
PARTICULATE AIR (FILTER)
HORIZ HORIZONTAL
HT HEIGHT
I
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J
J-BOX JUNCTION BOX
L
LAV LAVATORY
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIN LINEAR
LOC LOCATION
LT LIGHT
LVR LOUVER
M
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MOD MODIFY
MTG MOUNTING
MTL METAL
MVBL MOVABLE
N
NA NOT APPLICABLE
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT TO SCALE
O
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPP OPPOSITE
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P
PA PUBLIC ADDRESS
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PERP PERPENDICULAR
PL PROPERTY LINE
PLBG PLUMBING
PNL PANEL
PR PAIR
PRKG PARKING
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PWR POWER
Q
QA QUALITY ASSURANCE
QC QUALITY CONTROL
QTY QUANTITY
R
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RFG ROOFING
RM ROOM
RO ROUGH OPENING
RV ROOF VENT
S
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT (FEET)
SGL SINGLE
SIM SIMILAR
SJ SCORED JOINT
SLNT SEALANT
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
STD STANDARD
STOR STORAGE
T
TEL TELEPHONE
TEMP TEMPORARY
TOF TOP OF FOOTING/ FOUNDATION
TOM TOP OF MASONRY
TOS TOP OF SLAB/ STEEL
U
UNO UNLESS NOTED OTHERWISE
UTIL UTILITY
V
VAR VARIES
VC VA PROVIDED / CONTRACTOR
INSTALLED
VV VA PROVIDED / VA INSTALLED
W
W/ WITH
W/O WITHOUT
W/C WATER CLOSET
WC WHEELCHAIR
WPM WATERPROOF MEMBRANE
X
X BRACE CROSS BRACE
NOTE: NOT ALL ABBREVIATIONS OR SYMBOLS WILL BE UTILIZED FOR THIS PROJECT.
th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t
00 00
11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t
00 00
22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t
00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t
00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
00 00 44 44
88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t
00 00 44 44
88 88
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. EXP. 06/23/2021
ENGR REG. NO. EXP. 06/30/2021
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
ELEC ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
OH 20314270,
OH 06253,
Drawing Number
Building Number
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, SUITE 1415,
PANAMA CITY BEACH, FL 32407
(502) 836-4232
/9
/2
:3
:3
P
M
GENERAL INFORMATION
ECO 2 39BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
COLUMBUS, OH – TIER 1
06/28/2021
757-21-701
Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219
GI-001
FACP
FEC
AED
FIRE ALARM CONTROL PANEL
FIRE EXTINGUISHER CABINET
AUTOMATED EXTERNAL DEFIBRILLATOR, GC TO
COORDINATE ROUGH-IN CONDITION WITH VA
PROVIDED EQUIPMENT
EXIT LIGHT / SIGN
SPACE NOT OCCUPIED
PROTECTED AREA ENCLOSED WITH SMOKE
PARTITIONS
EGRESS PATH
BUILDING EXIT
OCCUPANT LOAD
NFPA 101-2021 EDITION
BUILDING HEIGHT:
2 STORIES, 36'-0" HEIGHT
BUILDING AREA:
AREA LIMITATION: 37,500 SF PER FLOOR (2012 IBC TABLE 503)
FIRST FLOOR 9,907 SF
SECOND FLOOR 8,931 SF
TOTAL 18,838 SF
BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT
CONSTRUCTION TYPE: (TABLE A.8.2.1.2): TYPE II (000)
FIRE RESISTANCE RATINGS (TABLE A.8.2.1.2):
• COLUMNS: 0 HR
• BEAM, GIRDERS, TRUSSES: 0 HR
• FLOOR/CEILING ASSEMBLIES: 0 HR
• ROOF/CEILING ASSEMBLIES: 0 HR
• EXTERIOR NON-BEARING WALLS: 0 HR
• INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR
NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)
CHAPTER 38: NEW BUSINESS OCCUPANCY
OCCUPANT LOADS (TABLE 7.3.1.2):
• FIRST FLOOR BUSINESS USE = 100 SF/PERSON
• SECOND FLOOR BUSINESS USE = 100 SF/PERSON
• FIRST FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON
• SECOND FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON
SHAFTS MINIMUM 1-HOUR RATING (8.6.5)
DEAD END CORRIDOR MAXIMUM DISTANCE: 50' (38.2.5.2.1)
MAXIMUM COMMON PATH OF TRAVEL: 100' (38.2.5.3.1)
MAXIMUM TRAVEL DISTANCE: 300' (38.2.6.3)
CORRIDOR MINIMUM FIRE RATING: 0 HR (38.3.6.1 EXCEPTION 3)
ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR EXIT WIDTH.
- 15"/PERSON (IBC 1005.3.2, EXCEPTION 1) ALLOWS 226 OCCUPANT LOAD PER DOOR MAX.
STAIR WIDTH PROVIDED IS 44 1/4" AT STAIR 1 (SOUTH) AND 42 1/2" AT STAIR 2 (WEST)
- .3"/PERSON (IBC 1005.3.1) ALLOWS 146 OCCUPANT LOAD AT STAIR 1 MAX.
- .3"/PERSON (IBC 1005.3.1) ALLOWS 141 OCCUPANT LOAD AT STAIR 2 MAX.
PROTECTED AREAS:
- STORAGE ROOMS/CLEAN/SOILED - REQUIRED VA FIRE PROTECTION DESIGN MANUAL 3.1.A AND PER NFPA 101: 38.3.2.1 AND 8.7 SMOKE PARTITIONS WITH SPRINKLER PROTECTION, PROVIDED.
-MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION DESIGN MANUAL SECTION 3.1.B.
SMOKE COMPARTMENTALIZATION:
- NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.
FIRE ALARM SYSTEM:
- REQUIRED/PROVIDED MANUAL SYSTEM.
STANDPIPES:
- NOT REQUIRED / NOT PROVIDED.
FIRE - 1 HOUR
FIRE - 2 HOUR
TELECOM
1A457
TELECOM
1A024
TELECOM
1A014
TELECOM
1A106
TELECOM
1B002
DATA
1B609
TELECOM
1B006
TELECOM
2A004
TELECOM
2A143
TELECOM
2B102
TELECOM
2B310
TELECOM
2A018
TELECOM
2B003 th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t
00 00
11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t
00 00
22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t
00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t
00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
00 00 44 44
88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t
00 00 44 44
88 88
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. EXP. 06/23/2021
ENGR REG. NO. EXP. 06/30/2021
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
ELEC ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
OH 20314270,
OH 06253,
Drawing Number
Building Number
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, SUITE 1415,
PANAMA CITY BEACH, FL 32407
(502) 836-4232
/9
/2
:3
:0
P
M
LIFE SAFETY PLANS
ECO 3 39BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
COLUMBUS, OH – TIER 1
06/28/2021
757-21-701
Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219
GI-011
LIFE SAFETY LEGEND
LIFE SAFETY REQUIREMENTS
RATED PARTITIONS & BARRIERS
1/32" = 1'-0"
CPW AMBULATORY CARE CENTER - LEVEL 1 - LIFE SAFETY PLAN1
1/32" = 1'-0"
CPW AMBULATORY CARE CENTER - LEVEL 2 - LIFE SAFETY PLAN2
DN
TELECOM
3A004
TELECOM
3A015
TELECOM
3A063
SERVER / MAIN
TELECOM
4A201
TELECOM
4A041
ELECT. ROOM
4A012
NFPA 101-2021 EDITION
BUILDING HEIGHT:
2 STORIES, 36'-0" HEIGHT
BUILDING AREA:
AREA LIMITATION: 37,500 SF PER FLOOR (2012 IBC TABLE 503)
FIRST FLOOR 9,907 SF
SECOND FLOOR 8,931 SF
TOTAL 18,838 SF
BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT
CONSTRUCTION TYPE: (TABLE A.8.2.1.2): TYPE II (000)
FIRE RESISTANCE RATINGS (TABLE A.8.2.1.2):
• COLUMNS: 0 HR
• BEAM, GIRDERS, TRUSSES: 0 HR
• FLOOR/CEILING ASSEMBLIES: 0 HR
• ROOF/CEILING ASSEMBLIES: 0 HR
• EXTERIOR NON-BEARING WALLS: 0 HR
• INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR
NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)
CHAPTER 38: NEW BUSINESS OCCUPANCY
OCCUPANT LOADS (TABLE 7.3.1.2):
• FIRST FLOOR BUSINESS USE = 100 SF/PERSON
• SECOND FLOOR BUSINESS USE = 100 SF/PERSON
• FIRST FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON
• SECOND FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON
SHAFTS MINIMUM 1-HOUR RATING (8.6.5)
DEAD END CORRIDOR MAXIMUM DISTANCE: 50' (38.2.5.2.1)
MAXIMUM COMMON PATH OF TRAVEL: 100' (38.2.5.3.1)
MAXIMUM TRAVEL DISTANCE: 300' (38.2.6.3)
CORRIDOR MINIMUM FIRE RATING: 0 HR (38.3.6.1 EXCEPTION 3)
ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR EXIT WIDTH.
- 15"/PERSON (IBC 1005.3.2, EXCEPTION 1) ALLOWS 226 OCCUPANT LOAD PER DOOR MAX.
STAIR WIDTH PROVIDED IS 44 1/4" AT STAIR 1 (SOUTH) AND 42 1/2" AT STAIR 2 (WEST)
- .3"/PERSON (IBC 1005.3.1) ALLOWS 146 OCCUPANT LOAD AT STAIR 1 MAX.
- .3"/PERSON (IBC 1005.3.1) ALLOWS 141 OCCUPANT LOAD AT STAIR 2 MAX.
PROTECTED AREAS:
- STORAGE ROOMS/CLEAN/SOILED - REQUIRED VA FIRE PROTECTION DESIGN MANUAL 3.1.A AND PER NFPA 101: 38.3.2.1 AND 8.7 SMOKE PARTITIONS WITH SPRINKLER PROTECTION, PROVIDED.
-MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION DESIGN MANUAL SECTION 3.1.B.
SMOKE COMPARTMENTALIZATION:
- NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.
FIRE ALARM SYSTEM:
- REQUIRED/PROVIDED MANUAL SYSTEM.
STANDPIPES:
- NOT REQUIRED / NOT PROVIDED.
FACP
FEC
AED
FIRE ALARM CONTROL PANEL
FIRE EXTINGUISHER CABINET
AUTOMATED EXTERNAL DEFIBRILLATOR, GC TO
COORDINATE ROUGH-IN CONDITION WITH VA
PROVIDED EQUIPMENT
EXIT LIGHT / SIGN
SPACE NOT OCCUPIED
PROTECTED AREA ENCLOSED WITH SMOKE
PARTITIONS
EGRESS PATH
BUILDING EXIT
OCCUPANT LOAD
FIRE - 1 HOUR
FIRE - 2 HOUR
th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t
00 00
11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t
00 00
22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t
00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t
00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
00 00 44 44
88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t
00 00 44 44
88 88
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. EXP. 06/23/2021
ENGR REG. NO. EXP. 06/30/2021
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
ELEC ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
OH 20314270,
OH 06253,
Drawing Number
Building Number
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, SUITE 1415,
PANAMA CITY BEACH, FL 32407
(502) 836-4232
/9
/2
:3
:1
P
M
LIFE SAFETY PLANS
ECO 4 39BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
COLUMBUS, OH – TIER 1
06/28/2021
757-21-701
Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219
GI-012
1/32" = 1'-0"
CPW AMBULATORY CARE CENTER - LEVEL 3 - LIFE SAFETY PLAN1
1/32" = 1'-0"
CPW AMBULATORY CARE CENTER - LEVEL 4 - LIFE SAFETY PLAN2
LIFE SAFETY REQUIREMENTS
LIFE SAFETY LEGEND
RATED PARTITIONS & BARRIERS
UP
NFPA 101-2021 EDITION
BUILDING HEIGHT:
2 STORIES, 36'-0" HEIGHT
BUILDING AREA:
AREA LIMITATION: 37,500 SF PER FLOOR (2012 IBC TABLE 503)
FIRST FLOOR 9,907 SF
SECOND FLOOR 8,931 SF
TOTAL 18,838 SF
BUILDING IS EQUIPPED WITH A FULLY AUTOMATIC FIRE SPRINKLER SYSTEM THROUGHOUT
CONSTRUCTION TYPE: (TABLE A.8.2.1.2): TYPE II (000)
FIRE RESISTANCE RATINGS (TABLE A.8.2.1.2):
• COLUMNS: 0 HR
• BEAM, GIRDERS, TRUSSES: 0 HR
• FLOOR/CEILING ASSEMBLIES: 0 HR
• ROOF/CEILING ASSEMBLIES: 0 HR
• EXTERIOR NON-BEARING WALLS: 0 HR
• INTERIOR NON-BEARING WALLS: 0 HR
FIRE-RESISTIVE REQUIREMENTS:
• NON COMBUSTIBLE MATERIALS FOR STRUCTURAL FRAME, FLOORS, ROOF DECK, EXTERIOR
NON-BEARING WALLS, INTERIOR NON-BEARING WALLS (U.N.O. AT EXTERIOR)
CHAPTER 38: NEW BUSINESS OCCUPANCY
OCCUPANT LOADS (TABLE 7.3.1.2):
• FIRST FLOOR BUSINESS USE = 100 SF/PERSON
• SECOND FLOOR BUSINESS USE = 100 SF/PERSON
• FIRST FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON
• SECOND FLOOR WAITING AREAS WITHOUT FIXED SEATING = 15 SF/PERSON
SHAFTS MINIMUM 1-HOUR RATING (8.6.5)
DEAD END CORRIDOR MAXIMUM DISTANCE: 50' (38.2.5.2.1)
MAXIMUM COMMON PATH OF TRAVEL: 100' (38.2.5.3.1)
MAXIMUM TRAVEL DISTANCE: 300' (38.2.6.3)
CORRIDOR MINIMUM FIRE RATING: 0 HR (38.3.6.1 EXCEPTION 3)
ALL EXIT DOORS PROVIDED ARE 36" LEAF MINIMUM YIELDING 34" CLEAR EXIT WIDTH.
- 15"/PERSON (IBC 1005.3.2, EXCEPTION 1) ALLOWS 226 OCCUPANT LOAD PER DOOR MAX.
STAIR WIDTH PROVIDED IS 44 1/4" AT STAIR 1 (SOUTH) AND 42 1/2" AT STAIR 2 (WEST)
- .3"/PERSON (IBC 1005.3.1) ALLOWS 146 OCCUPANT LOAD AT STAIR 1 MAX.
- .3"/PERSON (IBC 1005.3.1) ALLOWS 141 OCCUPANT LOAD AT STAIR 2 MAX.
PROTECTED AREAS:
- STORAGE ROOMS/CLEAN/SOILED - REQUIRED VA FIRE PROTECTION DESIGN MANUAL 3.1.A AND PER NFPA 101: 38.3.2.1 AND 8.7 SMOKE PARTITIONS WITH SPRINKLER PROTECTION, PROVIDED.
-MEDICAL RECORDS STORAGE - 1 HR PER VA FIRE PROTECTION DESIGN MANUAL SECTION 3.1.B.
SMOKE COMPARTMENTALIZATION:
- NOT REQUIRED FOR BUSINESS OCCUPANCIES, NOT PROVIDED.
FIRE ALARM SYSTEM:
- REQUIRED/PROVIDED MANUAL SYSTEM.
STANDPIPES:
- NOT REQUIRED / NOT PROVIDED.
FACP
FEC
AED
FIRE ALARM CONTROL PANEL
FIRE EXTINGUISHER CABINET
AUTOMATED EXTERNAL DEFIBRILLATOR, GC TO
COORDINATE ROUGH-IN CONDITION WITH VA
PROVIDED EQUIPMENT
EXIT LIGHT / SIGN
SPACE NOT OCCUPIED
PROTECTED AREA ENCLOSED WITH SMOKE
PARTITIONS
EGRESS PATH
BUILDING EXIT
OCCUPANT LOAD
FIRE - 1 HOUR
FIRE - 2 HOUR
DATA RM
NO RATED WALLS
1 2 3 4
A.2
B
D
C
F
E
G
1.8
B.4
A
2.72.6
DATA RM
th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t
00 00
11 11 o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t o n e in c h o n e fo o t
00 00
22 22 th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t
00 00 22 22 o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t o n e h a lf in c h o n e fo o t
00 00 44 44 th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t th re e e ig h th s in c h o n e fo o t
00 00 44 44 o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t
00 00 44 44
88 88 o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t o n e e ig h th in c h o n e fo o t
00 00 44 44
88 88
A
B
C
D
E
F
Veterans Health
Administration
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project Number
CONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. EXP. 06/23/2021
ENGR REG. NO. EXP. 06/30/2021
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
ELEC ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
FULLY SPRINKLERED
INDUSTRIAL HYGENIST
RSH
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
STAMP:
OH 20314270,
OH 06253,
Drawing Number
Building Number
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, SUITE 1415,
PANAMA CITY BEACH, FL 32407
(502) 836-4232
/9
/2
:3
:1
P
M
LIFE SAFETY PLANS
ECO 5 39BKM
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES
COLUMBUS, OH – TIER 1
06/28/2021
757-21-701
Chalmers P. Wylie VA Ambulatory Care Center 420 North James Road Columbus, OH 43219
GI-013
LIFE SAFETY REQUIREMENTS
LIFE SAFETY LEGEND
RATED PARTITIONS & BARRIERS
No. REVISION DESCRIPTION DATE
3/32" = 1'-0"
ENGINEERING BUILDING - LEVEL 1 - LIFE SAFETY PLAN33/32" = 1'-0"
BOILER PLANT - LEVEL 1 - LIFE SAFETY PLAN4
N N
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. EXP. 06/23/2021
ENGR REG. NO. EXP. 06/30/2021
STAMP:
OH 20314270,
OH 06253,
Drawing Number
Building Number
CRW 39RGH
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES -
COLUMBUS, OH - TIER 1
6/28/2021
757-21-701
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
420 NORTH JAMES ROAD
COLUMBUS, OH 43219
ACC
No. REVISION DESCRIPTION DATE
FULLY SPRINKLERED
Veterans Health
Administration
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
ELEC ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
INDUSTRIAL HYGENIST
RSH
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, SUITE 1415,
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 ASI-0001 1/26/2022
LEGEND
GENERAL LAYOUT
GS-001
GENERAL NOTES:
CALL 811 SEVENTY-TWO HOURS PRIOR TO
DIGGING, GRADING OR EXCAVATING FOR THE
MARKING OF UNDERGROUND MEMBER UTILITIES.
Know what's below.
before you dig.CallR
KEYNOTES:
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. EXP. 06/23/2021
ENGR REG. NO. EXP. 06/30/2021
STAMP:
OH 20314270,
OH 06253,
Drawing Number
Building Number
CRW 39RGH
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES -
COLUMBUS, OH - TIER 1
6/28/2021
757-21-701
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
420 NORTH JAMES ROAD
COLUMBUS, OH 43219
ACC
No. REVISION DESCRIPTION DATE
FULLY SPRINKLERED
Veterans Health
Administration
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
ELEC ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
INDUSTRIAL HYGENIST
RSH
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, SUITE 1415,
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 ASI-0001 1/26/2022
LEGEND
GENERAL NOTES:
PAVEMENT MARKING NOTES:
KEYNOTES:
DEMOLITION NOTES:
CALL 811 SEVENTY-TWO HOURS PRIOR TO
DIGGING, GRADING OR EXCAVATING FOR THE
MARKING OF UNDERGROUND MEMBER UTILITIES.
Know what's below.
before you dig.CallR
SITE PLAN
GS-002
A
B
C
D
E
F
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Drawing Title Project Title
Location
Date Checked Drawn
Project NumberCONSULTANTS:
Drawing # OF
VA Health Care System Approval:
ARCHITECT:
SPUR DESIGN, LLC
312 SW 25TH STREET
Oklahoma City, OK 73109
(405) 842-6100
ARCH REG. NO. EXP. 06/23/2021
ENGR REG. NO. EXP. 06/30/2021
STAMP:
OH 20314270,
OH 06253,
Drawing Number
Building Number
CRW 39RGH
FINAL BID DOCUMENTS
EHRM INFRASTRUCTURE UPGRADES -
COLUMBUS, OH - TIER 1
6/28/2021
757-21-701
CHALMERS P. WYLIE VA AMBULATORY CARE CENTER
420 NORTH JAMES ROAD
COLUMBUS, OH 43219
ACC
No. REVISION DESCRIPTION DATE
FULLY SPRINKLERED
Veterans Health
Administration
TELECOM
ASPEN ENGINEERING & CONTRACTING
7 KIJI-DAVA CIRCLE
PRESCOTT, AZ 86301
(928) 774-0992
ELEC ENGINEER
SPUR DESIGN
11020 KING STREET, SUITE 350
OVERLAND PARK, KS 66210
(405) 842-6100
INDUSTRIAL HYGENIST
RSH
1225 N. LOOP WEST, SUITE 800
HOUSTON, TX 77008
(713) 864-2900
CIVIL ENGINEER
OLSSON
550 ST. LOUIS ST.
SPRINGFIELD, MO 65806
(417) 885-1736
PHYSICAL SECURITY
FORCE PROTECT
10901 FRONT BEACH ROAD, SUITE 1415,
PANAMA CITY BEACH, FL 32407
(502) 836-4232
1 ASI-0001 1/26/2022
LEGEND
GRADING NOTES: GENERAL NOTES:
CALL 811 SEVENTY-TWO HOURS PRIOR TO
DIGGING, GRADING OR EXCAVATING FOR THE
MARKING OF UNDERGROUND MEMBER UTILITIES.
Know what's below.
before you dig.CallR
GRADING PLAN
GS-003
| 01_GI-000 COVER SHEET |
| 02_GI-001 GENERAL INFORMATION |
| Sheets |
| GI-001 - GENERAL INFORMATION |
| 03_GI-011 LIFE SAFETY PLANS |
| Sheets |
| GI-011 - LIFE SAFETY PLANS |
| 04_GI-012 LIFE SAFETY PLANS |
| Sheets |
| GI-012 - LIFE SAFETY PLANS |
| 05_GI-013 LIFE SAFETY PLANS |
| Sheets |
| GI-013 - LIFE SAFETY PLANS |
| 06_GS-001 GENERAL LAYOUT |
| Sheets and Views |
| GS-001 GENERAL LAYOUT |
| 07_GS-002 SITE PLAN |
| Sheets and Views |
| GS-002 SITE PLAN |
| 08_GS-003 GRADING PLAN |
| Sheets and Views |
| GS-003 GRADING PLAN |
File details come from the government source that posted it. Updated .