Attachment 10 - Drawings Electrical.pdf

PDF 18 MB Posted

Attached to
Z2DA--580-22-700 | Construct EHRM Infrastructure Upgrades | Houston, TX | Federal contract opportunity
Solicitation number
36C77625R0058
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--580-22-700 | Construct EHRM Infrastructure Upgrades | Houston, TX |, newest first.
File Type Posted
Amendment 0005.pdf PDF
Drawings Architectural to Scale.pdf PDF
Amendment 0004.pdf PDF
Drawings Civil to Scale.pdf PDF
Updated Wage Determination.pdf PDF
SECTION 01 45 35 Statement of SI Template.xlsx XLSX spreadsheet
ACM 2019 Inspection Update.xlsx XLSX spreadsheet
Amendment 0003.pdf PDF
Technical Questions Responses.docx DOCX document
Section 01 45 35 Schedule of Special Inspections Template.docx DOCX document
Geotechnical Report - Duct Bank Loop and Pavement.pdf PDF
Geotechnical Report - 3 Tower Addition.pdf PDF
Sign-in Sheet Page 1.jpeg JPEG file
Sign-in Sheet Page 2.jpeg JPEG file
Amendment 0002.pdf PDF
Drawings Structural.pdf PDF
Amendment 0001.pdf PDF
Attachment 4 - Drawings Architectural Part I.pdf PDF
Attachment 7 - Drawings Architectural Part IV.pdf PDF
Attachment 12 - Wage Determination Harris County.pdf PDF
Attachment 5 - Drawings Architectural Part II.pdf PDF
36C77625R0058.pdf PDF
Attachment 2 - Drawings General.pdf PDF
Attachment 8 - Drawings Architectural Part V.pdf PDF
Attachment 9 - Drawings Mechanical.pdf PDF
Attachment 1 - Specifications.pdf PDF
Attachment 3 - Drawings Civil.pdf PDF
Attachment 6 - Drawings Architectural Part III.pdf PDF
Attachment 11 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 13 - Spec 01 31 00.01 Project Management and Coordination.pdf PDF
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Engineers Architects

Revisions: Date

Drawing Title

Location

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

Approved

Project Title VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

Date Checked Drawn

/1

/2

:1

:3

P

M C

U s e rs \c k u rk u l\ D o c u m e n ts

\A

-3

-V A

H o u s to n -E

H R

M

M A

S T

E R c k u rk u lG V

Y

H .r v t

COVER VOLUME 4

MICHAEL E. DEBAKEY VAMC

2002 HOLCOMBE BLVD.

HOUSTON, TX 77030

BID DOCUMENTS

21-313

EHRM INFRASTRUCTURE UPGRADES

MICHAEL E. DEBAKEY VAMC

2002 HOLCOMBE BLVD.

HOUSTON, TX 77030

VA PROJECT #: 580-22-700

1 1CMK

EHRM INFRASTRUCTURE

UPGRADES

JANUARY 14, 2025

580-22-700

WVS

000 G-001.4

VOLUME 4

VOLUME 4 OF 4

DRAWING LIST - VOLUME 4

GENERAL

000 G-001.4 COVER VOLUME 4 1 1

ELECTRICAL

000 ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 107

000 ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 107

000 ET501 TYPICAL TELECOM ROOM DETAILS 3 107

000 ET502 ELECTRICAL AND TECHNOLOGY DETAILS 4 107

000 ET503 ELECTRICAL AND TECHNOLOGY DETAILS 5 107

000 ET504 TECHNOLOGY DETAILS 6 107

000 ET505 CHANNEL RACK POWER AND TE DETAILS 7 107

000 ET506 TR RACK DETAIL, MAIN DISTRIBUTION AREA DETAILS, AND SCHEDULES 8 107

000 ET507 TECHNOLOGY DETAILS 9 107

000 ES101 SITE FIBER BACKBONE ROUTING PLAN 10 107

100 ET100 BUILDING 100, OVERALL BASEMENT FLOOR ELECTRICAL PLAN 11 107

100 ET110 BUILDING 100, OVERALL FIRST FLOOR ELECTRICAL PLAN 12 107

100 ET120 BUILDING 100, OVERALL SECOND FLOOR ELECTRICAL PLAN 13 107

100 ET130 BUILDING 100, OVERALL THIRD FLOOR ELECTRICAL PLAN 14 107

100 ET140 BUILDING 100, OVERALL FOURTH FLOOR ELECTRICAL PLAN 15 107

100 ET150 BUILDING 100, OVERALL FIFTH FLOOR ELECTRICAL PLAN 16 107

100 ET160 BUILDING 100, OVERALL SIXTH FLOOR ELECTRICAL PLAN 17 107

103 ET110 BUILDING 103, OVERALL FIRST FLOOR ELECTRICAL PLAN 18 107

104 ET110 BUILDING 104, OVERALL FIRST FLOOR ELECTRICAL PLAN 19 107

108 ET110 BUILDING 108, OVERALL FIRST FLOOR ELECTRICAL PLAN 20 107

108A ET110 BUILDING 108A, OVERALL FIRST AND SECOND FLOOR ELECTRICAL PLAN 21 107

109 ET100 BUILDING 109, OVERALL BASEMENT FLOOR ELECTRICAL PLAN 22 107

109 ET110 BUILDING 109, OVERALL FIRST FLOOR ELECTRICAL PLAN 23 107

109 ET120 BUILDING 109, OVERALL SECOND FLOOR ELECTRICAL PLAN 24 107

110 ET100 BUILDING 110, OVERALL BASEMENT FLOOR ELECTRICAL PLAN 25 107

110 ET110 BUILDING 110, OVERALL FIRST FLOOR ELECTRICAL PLAN 26 107

110 ET120 BUILDING 110, OVERALL SECOND FLOOR ELECTRICAL PLAN 27 107

110 ET130 BUILDING 110, OVERALL THIRD FLOOR ELECTRICAL PLAN 28 107

120 ET110 BUILDING 120, OVERALL FIRST FLOOR ELECTRICAL PLAN 29 107

123 ET110 BUILDING 123, OVERALL FIRST FLOOR ELECTRICAL PLAN 30 107

125 ET110 BUILDIING 125, OVERALL FIRST AND SECOND FLOOR ELECTRICAL PLAN 31 107

100T ET311 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-101 SECTIONS 32 107

100T ET312 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-102 SECTIONS 33 107

100T ET313 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-103 SECTIONS 34 107

100T ET320 BUILDING 100, TYPICAL TOWER, SECTIONS - FLOORS 2 THRU 5 35 107

100T ET360 BUILDING 100, SIXTH FLOOR, TOWER TR SECTIONS 36 107

100T ET400 BUILDING 100, TYPICAL TOWER, TELECOM ROOM PLANS 37 107

100 ET401 BUILDING 100, BASEMENT FLOOR, TELECOM ROOM BA-450B PLANS 38 107

100 ET402 BUILDING 100, BASEMENT FLOOR, TELECOM AND ENTRANCE ROOM B ROOM BB-221 PLANS 39 107

100 ET403 BUILDING 100, BASEMENT FLOOR, TELECOM ROOM BC-209A PLANS 40 107

100 ET404 BUILDING 100, BASEMENT FLOOR, MAIN COMPUTER ROOM BC-301 PLANS 41 107

100 ET405 BUILDING 100, BASEMENT FLOOR, TELECOM ROOM ZB-E03A PLANS 42 107

100 ET406 BUILDING 100, BASEMENT FLOOR, TELECOM ROOM ZB-L06A PLANS 43 107

100T ET411 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-101 PLANS 44 107

100T ET412 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-102 PLANS 45 107

100T ET413 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-103 PLANS 46 107

100 ET414 BUILDING 100, FIRST FLOOR, TELECOM ROOM 1A-314 PLANS 47 107

100 ET415 BUILDING 100, FIRST FLOOR, TELECOM ROOM 1A-660A 48 107

100 ET416 BUILDING 100, FIRST FLOOR, TELECOM ROOM 1B-204B PLANS 49 107

100 ET417 BUILDING 100, FIRST FLOOR, TELECOM ROOM 1C-356A PLANS 50 107

100T ET421 BUILDING 100, SECOND FLOOR, TELECOM ROOM T-201 PLANS 51 107

100T ET422 BUILDING 100, SECOND FLOOR, TELECOM ROOM T-202 PLANS 52 107

100T ET423 BUILDING 100, SECOND FLOOR, TELECOM ROOM T-203 PLANS 53 107

100 ET424 BUILDING 100, SECOND FLOOR, TELECOM ROOM 2A-114 PLANS 54 107

100 ET425 BUILDING 100, SECOND FLOOR, TELECOM ROOM 2B-340A PLANS 55 107

100 ET426 BUILDING 100, SECOND FLOOR, TELECOM ROOM 2C-420A PLANS 56 107

100T ET431 BUILDING 100, THIRD FLOOR, TELECOM ROOM T-301 PLANS 57 107

100T ET432 BUILDING 100, THIRD FLOOR, TELECOM ROOM T-302 PLANS 58 107

100T ET433 BUILDING 100, THIRD FLOOR, TELECOM ROOM T-303 PLANS 59 107

100 ET434 BUILDING 100, THIRD FLOOR, TELECOM ROOM 3A-100A PLANS 60 107

100 ET435 BUILDING 100, THIRD FLOOR, TELECOM ROOM 3B-310M PLANS 61 107

100 ET436 BUILDING 100, THIRD FLOOR, TELECOM ROOM 3C-204A PLANS 62 107

100T ET441 BUILDING 100, FOURTH FLOOR, TELECOM ROOM T-401 PLANS 63 107

100T ET442 BUILDING 100, FOURTH FLOOR, TELECOM ROOM T-402 PLANS 64 107

100T ET443 BUILDING 100, FOURTH FLOOR, TELECOM ROOM T-403 PLANS 65 107

100 ET444 BUILDING 100, FOURTH FLOOR, TELECOM ROOM 4A-136 PLANS 66 107

100 ET445 BUILDING 100, FOURTH FLOOR, TELECOM ROOM 4B-204A PLANS 67 107

100 ET446 BUILDING 100, FOURTH FLOOR, TELECOM ROOM 4C-204A PLANS 68 107

100T ET451 BUILDING 100, FIFTH FLOOR, TELECOM ROOM T-501 PLANS 69 107

100T ET452 BUILDING 100, FIFTH FLOOR, TELECOM ROOM T-502 PLANS 70 107

100T ET453 BUILDING 100, FIFTH FLOOR, TELECOM ROOM T-503 PLANS 71 107

100 ET454 BUILDING 100, FIFTH FLOOR, TELECOM ROOM 5A-174 PLANS 72 107

100 ET455 BUILDING 100, FIFTH FLOOR, TELECOM ROOM 5B-358A PLANS 73 107

100 ET456 BUILDING 100, FIFTH FLOOR, TELECOM ROOM 5C-320A PLANS 74 107

100T ET461 BUILDING 100, SIXTH FLOOR, TELECOM ROOM T-601 PLANS 75 107

100T ET462 BUILDING 100, SIXTH FLOOR, TELECOM ROOM T-602 PLANS 76 107

100T ET463 BUILDING 100, SIXTH FLOOR, TELECOM ROOM T-603 PLANS 77 106

100 ET464 BUILDING 100, SIXTH FLOOR, TELECOM ROOM 6B-392A PLANS 78 107

100 ET465 BUILDING 100, BASEMENT AND FIRST FLOOR POWER ENLARGEMENTS 79 106

100 ET466 BUILDING 100, SECOND AND THIRD FLOOR POWER ENLARGEMENTS 80 107

100 ET467 BUILDING 100, THIRD AND FOURTH FLOOR POWER ENLARGEMENTS 81 107

100 ET468 BUILDING 100, FIFTH AND SIXTH FLOOR POWER ENLARGEMENTS 82 107

103 ET411 BUILDING 103, FIRST FLOOR, TELECOM ROOM 4A-113A PLANS 83 107

104 ET411 BUILDING 104, FIRST FLOOR, TELECOM ROOM 109 PLANS 84 107

108 ET411 BUILDING 108, FIRST FLOOR, TELECOM ROOM 102G PLANS 85 107

108A ET411 BUILDING 108A, FIRST FLOOR, TELECOM ROOM 125 PLANS 86 107

108A ET421 BUILDING 108A, SECOND FLOOR, TELECOM ROOM 232 PLANS 87 107

109 ET401 BUILDING 109, BASEMENT FLOOR, TELECOM ROOM B-43 PLANS 88 106

109 ET411 BUILDING 109, FIRST FLOOR, TELECOM ROOM 141 PLANS 89 106

109 ET421 BUILDING 109, SECOND FLOOR, TELECOM ROOM 238A PLANS 90 107

110 ET411 BUILDING 110, FIRST FLOOR, TELECOM ROOM 125 PLANS 91 107

110 ET412 BUILDING 110, FIRST FLOOR, TELECOM ROOM 136 PLANS 92 107

110 ET421 BUILDING 110, SECOND FLOOR, TELECOM ROOM 228 PLANS 93 107

110 ET422 BUILDING 110, SECOND FLOOR, TELECOM ROOM 235A PLANS 94 107

110 ET431 BUILDING 110, THIRD FLOOR, TELECOM ROOM 302B PLANS 95 107

DRAWING LIST - VOLUME 4

120 ET411 BUILDING 120, FIRST FLOOR, TELECOM ROOM 114 PLANS 96 107

123 ET411 BUILDING 123, FIRST FLOOR, TELECOM ROOM PLANS 97 107

125 ET411 BUILDING 125, FIRST FLOOR, TELECOM ROOM 116 PLANS 98 107

125 ET421 BUILDING 125, SECOND FLOOR, TELECOM ROOM 216 PLANS 99 107

000 ET601 FIBER RISER DIAGRAMS 100 107

100 ET602 BUILDING 100, BONDING RISER 101 107

100 ET603 BUILDING 100, SINGLE LINE POWER DIAGRAM 102 107

100 ET604 BUILDING 100, SINGLE LINE POWER DIAGRAM 103 107

103 ET601 BUILDING 103, SINGLE LINE DIAGRAM 104 107

104 ET601 BUILDING 104, SINGLE LINE DIAGRAM 105 107

108 ET601 BUILDING 108, SINGLE LINE DIAGRAM 106 107

108A ET601 BUILDING 108A, SINGLE LINE DIAGRAM 107 107

100, 103, 104A, 108, 108A, 109, 110, 120, 121, 122, 123, 124, 125, FISHER HOUSE

(1, 2, AND 3), VA REGIONAL OFFICEW

AL

TE

R DAVID VAN SCOTER

REG. NO. 9953

Docusign Envelope ID: 4347F947-D407-40B0-BEA8-3B760489F051

1/14/2025

120V DUPLEX RECEPTACLE

RECEPTACLE MODIFIERS:

AC: 3" ABOVE COUNTERTOP/BACKSPLASH

GFI: GROUND FAULT CURRENT INTERRUPTER

WP: WEATHERPROOF ENCLOSURE

DED: DEDICATED CIRCUIT

120V DUPLEX RECEPTACLE EMERGENCY OUTLET

AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE

120V QUADRUPLEX RECEPTACLE EMERGENCY

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED

DISCONNECT SWITCH NON-FUSED

DISCONNECT SWITCH FUSED

SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO

SYMBOL HEIGHT DESCRIPTION

18"

18"

18"

18"

AS

NOTED

72" TOP

72" TOP

SWITCH MODIFIERS:

M: MOTOR-RATED

48"

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SPECIAL RECEPTACLE, REFER TO ET501 FOR NEMA

TYPE

EQUIPMENT CONNECTION

AS

NOTED

E

18"

120V DUPLEX RECEPTACLE FLOOR BOX

120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX

OUTLET AND COVER PLATE SHALL BE RED IN COLOR

120V QUADRUPLEX RECEPTACLE FLOOR BOX

120V QUADUPLEX RECEPTACLE EMERGENCY

FLOOR BOX OUTLET AND COVER PLATE SHALL BE

RED IN COLOR

CLNG

J

J

J

JUNCTION BOX, CEILING MOUNTED, PURPOSE AS

NOTED

JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS

NOTED

120V SIMPLEX RECEPTACLE18"

2' X 2' RECESSED ARCHITECTURAL TROFFER

2' X 4' RECESSED ARCHITECTURAL TROFFER

SYMBOL

HEIGHT

AFF * DESCRIPTION

--- 2' X 4' RECESSED FLAT LENS TROFFER

2' LINEAR - WALL MOUNTED

7'-0"

CENTER

4' LINEAR - WALL MOUNTED

7'-0"

CENTER

WALL SCONCE

6'-0"

CENTER

6" DIAMETER RECESSED DOWNLIGHT---

EXIT SIGN - WALL MOUNTED

EXIT SIGN - CEILING MOUNTED---

7'-5"

BOTTOM

SINGLE POLE WALL SWITCH

SWITCH MODIFIERS:

OS: OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

VS: VACANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY

DR: DUAL RELAY

VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER

OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER

LV: LOW VOLTAGE

LVD: LOW VOLTAGE DIMMER

D: LINE VOLTAGE DIMMER

T: DIGITAL TIMER

K: KEYED

3: 3 WAY

4: 4 WAY

48"

CENTER

OCCUPANCY SENSOR, LOW VOLTAGE,

DUAL TECHNOLOGY - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL DEVICE

OCCUPANCY SENSOR, LOW VOLTAGE, DUAL

TECHNOLOGY - WALL/CORNER MOUNTED

EMERGENCY LIGHT BATTERY

OPERATED - WALL MOUNTED

7'-6"

CENTER

RC

* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

LIGHT LEVEL SENSOR, SINGLE ZONE

DIMMING CLOSED LOOP - CEILING MOUNTED

--- LOW VOLTAGE LIGHTING CONTROL

DEVICE WITH 0-10V DIMMING

RCD

OS

OS

LS

4' LINEAR STRIP - SUSPENDED---

L L

SPKR SPEAKER

SP SPARE

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TEL/DATA TELEPHONE/DATA

TERM TERMINAL

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

T-STAT THERMOSTAT

TTB TELEPHONE TERMINAL BOARD

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER'S LABORATORY

UT UNDERGROUND TELEPHONE

UTP UNSHIELDED TWISTED PAIR

UTIL UTILITY

UV UNIT VENTILATOR OR

ULTRAVIOLET

UPS UNINTERUPTABLE POWER

SUPPLY

V VOLT

VA VOLT-AMPERES

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

ANGLE

@ AT

DELTA

' FEET

" INCHES

# NUMBER

Φ PHASE

C CENTER LINE

P PLATE

MSBD MAIN SWITCHBOARD

MT MOUNT

MTR MOTOR, MOTORIZED

MTS MANUAL TRANSFER SWITCH

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURER'S ASSOCIATION

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PBPU PREFABRICATED BEDSIDE PATIENT

UNIT

PCB POLYCHLORINATED BIPHENYL

PC PHOTOELECTRIC CELL

PDU POWER DISTRIBUTION UNIT

PED PEDESTAL

PEND PENDANT

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

POE POWER-OVER-ETHERNET

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

R RELOCATE/RELOCATED

RCP REFLECTED CEILING PLAN

RCPT RECEPTACLE

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

RMS ROOT MEAN SQUARE

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

S/N SOLID NEUTRAL

SPEC SPECIFICATION

1P 1 POLE (2P, 3P, 4P, ETC.)

1PH 1 PHASE

2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)

2W TWO-WIRE (3W, 4W, ETC.)

3PH 3 PHASE

A AMPERE

AAP ALARM ANNUNCIATOR PANEL

AC ABOVE COUNTER

AIR CONDITIONER

ALTERNATING CURRENT

ACC ACCESSIBLE

ACLG ABOVE CEILING

ADO AUTOMATIC DOOR OPENER

A/E ARCHITECT/ENGINEER

AF AMP FRAME

AFC AVAILABLE FAULT CURRENT (KILOAMPS)

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMPERE INTERRUPTING CAPACITY

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPROX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AT AMP TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BC BARE COPPER

BD BOARD

BFF BELOW FINISHED FLOOR

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

BYP BYPASS

C CONDUIT

CAB CABINET

CALC CALCULATED

CAP CAPACITY

CAT CATALOG, CATEGORY

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CCR CONTROL CONTACTOR

CCT CORRELATED COLOR TEMPERATURE

CCTV CLOSED CIRCUIT TELEVISION

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICER

COAX COAXIAL CABLE

COMM COMMUNICATION

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CTR CENTER

CU COPPER

CU FT CUBIC FEET

D DEMOLITION

dB DECIBEL

DB DIRECT BURIAL

DC DIRECT CURRENT

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLISH/DEMOLITION

DEPT DEPARTMENT

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

ESMT EASEMENT

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WALL HEATER

ELECTRIC WATER HEATER

EX EXISTING

EXP EXPLOSION PROOF

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FU FUSE

FUDS FUSED SAFETY DISCONNECT

SWITCH

FVR FULL VOLTAGE REVERSING

FVNR FULL VOLTAGE NON-REVERSING

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEC GROUND ELECTRODE CONDUCTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

GRS GALVANIZED RIGID STEEL (CONDUIT)

GYP BD GYPSUM BOARD

HID HIGH-INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

HW HARD WIRED

IES ILLUMINATION ENGINEERING SOCIETY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

IR INFRARED

I/W INTERLOCK WITH

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LED LIGHT-EMITTING DIODE

LF LINEAR FEET/FOOT

LM LUMEN

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTNG LIGHTNING

LV LOW VOLTAGE

MATV MASTER ANTENNA TELEVISION SYSTEM

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MOA MULTIOUTLET ASSEMBLY

A1 b

E1 c d

T1

'LPN'

THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER

CASE LETTER AND NUMBER.

THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.

EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.

EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING

MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES

DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.

TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER

FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR

THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND

REQUIREMENTS.

PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING

SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR

DESIGNATION CODES.

SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE

NUMBER INDICATED IN THE HEXAGON.

HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT

DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.

CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL

SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.

SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE

A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.

'LPN'-1,3,5

EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE

AND DIRECTIONAL ARROW.

EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE

FACE AND DIRECTIONAL ARROWS.

E2

EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS

CONTROLLED BY SWITCH 'c'.

EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.

EXAMPLE: TRANSFORMER TYPE 'T1'.

EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.

# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE

NOTE NUMBER INDICATED IN THE SQUARE.

A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.

B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE

APPROXIMATE ONLY (FIELD VERIFY).

C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE

CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.

D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL

JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.

E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL

CUT OFF CONDUITS AND REMOVE WIRING.

F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE

LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.

G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR

PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.

H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND

CAPPED OR PLUGGED.

I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK

SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE COR/VA.

J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO MEET THE

REQUIREMENTS AND INTENT OF THE PROJECT.

K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW

AREAS.

L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.

CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.

M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS REQUIREMENT.

N. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC 300.21. DEVICES SHALL HAVE A MINIMUM OF 24" CENTER TO CENTER LATERAL SPACING.

1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA

STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING

CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL

ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.

4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO

SUIT THE PARTICULAR INSTALLATION.

5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.

6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.

7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING

CONSTRUCTION.

8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.

9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".

10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT

MANUFACTURER'S SPECIFICATIONS.

11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW

TERMINALS.

12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.

14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.

15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR

FINAL CONNECTIONS.

16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD

PARTY TESTING AGENCY.

17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.

PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.

PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.

18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE

PROVIDED.

19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.

20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".

21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.

22. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT, SUCH AS DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED

PENETRATION.

A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE

REMOVED FROM THE PREMISES.

B. ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.

C. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH OTHER

TRADES.

D. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES

CONTINUATION THROUGH THE AREA.

E. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.

F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND

NEW CONSTRUCTION.

G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING

TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.

H. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.

I. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR

SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.

J. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:

A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.

B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.

C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.

D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.

E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT

OF FEED WITH AN ENGRAVED BRASS TAG.

F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.

K. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.

IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED

PENETRATION.

SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK

AREA, FOR THE STARTING POINT OF THE CALCULATIONS.

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

/2

:1

:4

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts

\T R

R o o m

D e ta ils ls ta rn e s C

B U

M B

.r v t

ELECTRICAL GENERAL NOTES,

SYMBOL LEGENDS, AND

ABBREVIATIONS

1 107ADR

EHRM INFRASTRUCTURE

UPGRADES

MICHAEL E. DEBAKEY VAMC

2002 HOLCOMBE BLVD.

HOUSTON, TX 77030 JANUARY 14, 2025

BID DOCUMENTS

580-22-70021-313

JDM

000 ET001

ELECTRICAL SYMBOL LEGEND

LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST

ELECTRICAL SYMBOL NOTES

GENERAL ELECTRICAL REMODELING NOTES

ELECTRICAL GENERAL NOTES

GENERAL ELECTRICAL DEMO NOTES

TEMPORARY FIRESTOPPING

METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS

Docusign Envelope ID: 2B86FD95-F687-4E04-BBB2-F6FA4A59EBAA

1/14/2025 1/14/2025

TECHNOLOGY SYMBOL LEGEND

DATA OUTLET - N-4 PR UTP

SYMBOL HEIGHT DESCRIPTION

18"

WIRELESS ACCESS POINT - N-4 PR UTP

WALL MOUNT PHONE VOIP OUTLET

W

N

48"

N

CEILING

(N - QUANTITY)

(N - QUANTITY)

ELECTRIC STRIKE

CARD READER

(K - KEYPAD)

48"CR

EL DOOR

PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP

DOOR CONTACT

REQUEST FOR EXIT SENSOR

DC

RX

DOOR

ABOVE

DOOR

DO DOOR OPERATORDOOR

48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)

CCTV DOME CAMERA FIXED

CCTV DOME CAMERA PAN/TILT/ZOOM

FOUR POST CHANNEL RACK

OIT EQUIPMENT CABINET

FLOOR

FLOOR

FLOOR 6", 12" VERTICAL WIRE MANAGEMENT

CEILING

CEILING

CCTV EQUIPMENT CABINETCCTV

BASKET CABLE TARY

GROUND BUS

FLOOR

ABOVE

CEILING

12", 18", 20"

4'x8'x3/4" FIRE RATED TTB8"

CABLE LADDERABOVE

CEILING

CEILING MOUNTED SPEAKERSCEILING

WALL MOUNTED SPEAKERS96"

S

S

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

SEE DRAWINGS FOR MORE INFORMATION.

NOTE: NOT ALL SYMBOLS ARE USED.

CABLES AND CONNECTORS COLOR LEGEND

DESCRIPTION

ITEM JACK CABLE PATCH CABLES I.D. NOTES

DATA/COMPUTER

WIRELESS

ACCESS POINT

FIBER - MULTI-MODE

FIBER - SINGLE-MODE

CCTV - IP

BLUE

N/A

N/A

N/A

N/A

BLUE

GREEN

AQUA

YELLOW

WHITE

BLUE

GREEN

AQUA

YELLOW

WHITE

C

WAP

FO

FO

CCTV 4 PAIR UTP CABLE

4 PAIR UTP CABLE

4 PAIR UTP CABLE

6/12/24

6/12/24

PACS N/A GRAY N/A PACS MULTI-PAIR

CONDUCTORS

ADO AUTOMATIC DOOR OPERATOR

AFF ABOVE FINISH FLOOR

BOD BASIS OF DESIGN

CCTV CLOSED CIRCUIT TELEVISION

COAX COAXIAL CABLE

COMM COMMUNICATION

COR CONTRACTING OFFICER REPRESENTATIVE

DC DOOR CONTACT SWITCH

DN DOWN

DO DOOR OPERATOR

DVC DIGITAL VOICE COMMAND

DVR DIGITAL VIDEO RECORDER

E EXISTING DEVICES

EEB EMERGENCY EXIT BUTTON

EL ELECTRICAL STRIKE

ETR EXISTING TO REMAIN

FO FIBER OPTIC

IT INFORMATION AND TECHNOLOGY ROOM

MATV MASTER ANTENNA TELEVISION

MDA MAIN DISTRIBUTION AREA

MM MULTI MODE FIBER

NAC NETWORK APPLIANCE CIRCUIT PANEL

N NEW DEVICES

NCA NETWORK CONTROL ANNUNCIATOR

NS NO SCALE

NTS NOT TO SCALE

NVR NETWORK VIDEO RECORDER

TECHNOLOGY ABBREVIATIONS LIST

OC ON CENTER

OIT OFFICE OF INFORMATION TECHNOLOGY

PACS PHYSICAL ACCESS CONTROL SYSTEM

PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM

PB PUSH BUTTON

PBB PRIMARY BONDING BUSBAR

PDU POWER DISTRIBUTION UNIT

POE POWER OVER ETHERNET

PR PAIR

RBB RACK BONDING BUSBAR

rPDU RACK POWER DISTRIBUTION UNIT

RX REQUEST TO EXIT

SBB SECONDARY BONDING BUSBAR

SEP SERVICE ENTRANCE PROTECTION

SLC SIGNALING LINE CIRCUIT

SM SINGLE MODE FIBER

TBB TELECOM BONDING BACKBONE

TEBC TELECOMMUNICATIONS EQUIPMENT BONDING

CONDUCTOR

TEL TELEPHONE

TGB TELECOM GROUND BUS BAR

TM TELEMONITORING

TMGB TELECOM MAIN GROUND BUS BAR

TP TWISTED PAIR

TR TELECOM ROOM

TTB TELEPHONE TERMINAL BOARD

TV TELEVISION

WM WIRE MANAGEMENT

WAP WIRELESS ACCESS POINT

WAO WORK AREA OUTLET

UL UNDERWRITERS LABORATORY

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

TECHNOLOGY GENERAL NOTES

1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA STANDARDS.

2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT SUITABLE FOR

DIRECT MOUNTING.

3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL LISTING

REQUIREMENT, SPECIFICATIONS, AND APPLICABLE BUILDING CODES.

4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION METHOD

MANUAL AND ANSI/TIA/EIA PUBLICATIONS.

5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607 - GROUNDING AND BONDING REQUIREMENTS FOR

TELECOMMUNICATIONS IN COMMERCIAL BUILDING.

6. COMPLY WITH THE LATEST ANSI/TIA-568-SET, COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD.

7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569 - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS

PATHWAYS AND SPACES.

8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.

9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.

10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.

11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.

12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN ACT".

13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED

OTHERWISE.

14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.

15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY TESTING

AGENCY.

16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE MORE

STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.

17. PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.

18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568B.

19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606 AS WELL AS THE STANDARDS SET FORTH BY THE VA

HOSPITAL OIT.

20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY IN ACCORDANCE WITH LATEST TIA/EIA 569.

21. VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING AND

EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.

22. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.

23. MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4" EMT.

24. WALL MOUNTED DEVICES PLACED IN TELECOM ROOM SHALL BE MOUNTED ON FIRE RETARDANT PLYWOOD.

25. PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS FOR A COMPLETE

SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.

26. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING (BOTH FIBER AND COPPER), JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, BONDING BUS BARS, RACK MOUNTED BONDING BUS, BONDING CABLING, BONDING TO THE GROUNDING SYSTEM, BONDING CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

27. PROVIDE J-HOOKS OR FLEXIBLE CONDUITS WHERE CABLE TRAY IS NOT SHOWN, OR IF THE PATH OF THE CABLE TRAY IS OBSTRUCTED. PROVIDE JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, AND COVER PLATES AS NEEDED OR WHERE REQUIRED BY CODE. LABEL AND SUPPORT J-HOOKS, CABLE TRAY, AND CONDUIT AS SHOWN

HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

28. PROVIDE 12 PORT, WALL MOUNTED, COPPER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, COPPER PATCH PANEL IN EACH NEW TR AND RUN 12 CAT 6A CABLE BETWEEN THESE TELECOM

ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.

29. PROVIDE 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN EACH NEW TR AND RUN 12 STRAND FIBER CABLE BETWEEN THESE TELECOM

ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.

30. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

CAMERAS SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION ACT-NDAA.

31. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL

PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.

32. CONTRACTOR IS RESPONSIBLE FOR PROVIDING RECORD/AS-BUILT DRAWINGS AS PART OF CLOSEOUT SUBMITTALS

SHOWING ALL NEW WORK AREA OUTLET LOCATIONS ON THE MOST UP-TO-DATE FLOOR PLAN.

33. PROVISION OF MULTI-SENSOR SSTV CAMERAS AS WELL AS ASSOCIATED NVR'S, STORAGE, SOFTWARE, AND LICENSES

SHALL BE COORDINATED WITH AVIGILON. CONTACT LOCAL AVIGILON REPRESENTATIVE.

34. PROVISION OF CARD READERS AND ASSOCIATED DOOR SECURITY HARDWARE AS WELL AS ASSOCIATED HEAD END EQUIPMENT SHALL BE COORDINATED WITH OPEN OPTIONS. CONTACT LOCAL OPEN SOURCE REPRESENTATIVE.

35. PROVIDE 6 CISCO C9K-PWR-CAB-AC-US POWER CORDS FOR CISCO CATALYST 9300 SWITCHES PER TR.

36. WHERE THERE ARE HARD LID CEILINGS, PROVIDE FLEXIBLE CONDUIT FROM THE WORK AREA OUTLET TO THE CABLE

TRAY.

37. COORDINATE DOOR HARDWARE WITH THE EXISTING ELECTRIC KEY SYSTEM EMPLOYED BY THE VA. ALL DOOR

SECURITY HARDWARE SHALL INTEGRATE WITH THE ELECTRIC KEY SYSTEM.

38. TEN (10) SWITCHES WILL BE PROVIDED TO THE SITE TO ACCOMMODATE TRANSITIONING TELECOMMUNICATIONS

ROOMS.

39. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INSTALL COPPER PATCH CABLES IN ALL TELECOMMUNICATIONS ROOMS. ONE COPPER PATCH CABLE IS REQUIRED TO SERVE EVERY WORK AREA OUTLET, WIRELESS ACCESS POINT, AND ALL OTHER CONNECTION POINTS SERVED BY OIT NETWORK SWITCHES. THE APPROXIMATE AMOUNT OF PATCH CABLES NEEDED IS 10,000 (VARYING LENGTHS OF 2, 4, AND 8 FEET) TO REACH FROM

THE SWITCH TO THE PATCH PANELS.

GENERAL TECHNOLOGY DEMOLITION AND REMODEL NOTES

A. ALL EXISTING CONDITIONS - INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, AND CONDUIT - ARE BASED ON

THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.

B. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER MATERIAL SHALL BE REMOVED FROM THE PREMISES (E.G., PATCH PANELS, CABLES, COVER PLATES, PATCH CORDS, AND RELATED MATERIAL).

C. EXISTING CABLE TRAY SHALL REMAIN. REMOVE EXISTING CABLING SERVING WORK AREA OUTLETS (WAO). NO ABANDONED CABLING WILL BE ALLOWED TO REMAIN ABOVE THE CEILING. INSTALL NEW CABLE TRAY NEXT TO THE

EXISTING CABLE TRAY.

D. EXISTING CONDUIT AND SURFACE RACEWAY MAY BE REUSED FOR NEW WAO. COORDINATE LOCATION WITH THE COR.

E. EXISTING TR: ONCE ALL ACTIVE CONNECTIONS TO AN EXISTING TR HAVE BEEN REPLACED BY CONNECTIONS TERMINATED IN THE NEW TR - AND OIT HAS CONFIRMED THAT THERE ARE NO LONGER ANY ACTIVE CONNECTIONS FROM THE EXISTING TR - COORDINATE REMOVAL OF ALL VA OWNED NETWORK SWITCHES. REMOVE PATCH PANELS AND ALL ASSOCIATED CABLING. BID DEMOLITION AND DISPOSAL OF THE RACKS IN THE TR UNLESS THERE ARE REMAINING NON-NETWORK COMPONENTS WHICH SHALL REMAIN IN PLACE WITH THE UPS AND POWER SOURCE IN

TACT.

F. EXISTING TR IDENTIFIED TO BE RENOVATED: PROTECT NETWORK RACK, EQUIPMENT, AND CABLING FROM DAMAGE, DUST, AND DEBRIS. MAINTAIN EXISTING PHYSICAL SECURITY DURING RENOVATION. NOTIFY THE COR AND VA POLICE A

MINIMUM OF 14 DAYS PRIOR TO ANY PHYSICAL SECURITY OUTAGES.

1. CONTRACTOR TO REFER TO TELECOM ROOM PHASING NOTES, SHEETS A-001, FOR ADDITIONAL INFOMATION.

FIRE ALARM PULL STATION

SYMBOL HEIGHT DESCRIPTION

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.

F

F

FIRE ALARM SPEAKER

FIRE ALARM STROBE

FIRE ALARM SPEAKER AND STROBE

FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR

42"-48"

90"

90"

90"

XX - CANDELA

XX - CANDELA

XX - WATTAGEF

S

F

S

SD CEILING

ACC ACCESSIBLE

ACLG ABOVE CEILING

A/E ARCHITECT/ENGINEER

AFF ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING JURISDICTION

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

APPRX APPROXIMATELY

ARCH ARCHITECT, ARCHITECTURAL

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

BOD BASIS OF DESIGN

C CONDUIT

CAB CABINET

cd CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR-FURNISHED

CKT CIRCUIT

CLG CEILING

CO CONTRACTING OFFICE

COR CONTRACTING OFFICER

REPRESENTATIVE

dB DECIBEL

DN DOWN

DVC DIGITAL VOICE COMMAND

E EXISTING DEVICES

ELEV ELEVATOR

ETR EXISTING TO REMAIN

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

FAAP FIRE ALARM ANNUNCIATOR PANEL

FAGAP FIRE ALARM GRAPHIC

ANNUNCIATOR PANEL

FO FIBER OPTIC

J-BOX JUNCTION BOX

MAX MAXIMUM

MC MECHANICAL CONTRACTOR

METAL-CLAD (CONDUIT)

MECH MECHANICAL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MT MOUNT

N NEW DEVICES

NAC NETWORK APPLIANCE CIRCUIT

PANEL

NCA NETWORK CONTROL ANNUNCIATOR

NS NO SCALE

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PIV POST INDICATING VALVE

PVC POLYVINYL CHLORIDE (CONDUIT)

QTY QUANTITY

R REMOVE AND REPLACE IN NEW

LOCATION

RCP REFLECTED CEILING PLAN

REQD REQUIRED

RGS RIGID GALVANIZED STEEL

RM ROOM

SC SURFACE CONDUIT

SF SQUARE FEET/FOOT

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SIM SIMILAR

SPEC SPECIFICATION

SPKR SPEAKER

SR SURFACE RACEWAY

SS STAINLESS STEEL

STD STANDARD

SURF SURFACE MOUNTED

SYM SYMMETRICAL

SYS SYSTEM

TC TIMECLOCK

TEL TELEPHONE

TP TWISTED PAIR

TPS TWISTED PAIR SHIELDED

TR TAMPER RESISTANT

TYP TYPICAL

UL UNDERWRITER'S LABORATORY

UTP UNSHIELDED TWISTED PAIR

FIRE ALARM ABBREVIATIONS LIST

1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:

A. NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.

B. NFPA 70 NATIONAL ELECTRICAL CODE.

C. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.

D. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.

E. NFPA 101 LIFE SAFETY CODE.

F. VA FIRE PROTECTION DESIGN MANUAL.

G. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.

2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).

3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.

4. BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.

5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.

6. CONTRACTOR TO ENSURE THAT ALL NEW FIRE ALARM SPEAKERS, TONES, AND STROBES ARE IN-SYNC WITH ALL ADJACENT AREAS BEYOND THE AREA OF WORK. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN

WORK AREA AND ADJACENT AREAS.

7. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.

8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE ALARM

DEVICES. COORDINATE WITH COR.

9. THE OPERABLE PART OF A MANUAL ACTUATED ALARM INITIATING DEVICE SHALL BE NOT LESS THAN 42" (1.07M) AND

NOT MORE THAN 48" (1.22M) FROM FINISH FLOOR.

10. FOR LOCATION (CORRIDOR, ROOM OR ADJACENT SPACE) WITH TWO OR MORE VISIBLE FIRE ALARM NOTIFICATION APPLIANCES WITHIN THE FIELD OF VIEW, PROGRAM VISIBLE TO FLASH IN SYNCHRONIZATION.

11. PROGRAM ALL NEW A/V APPLIANCES. COORDINATE ZONING WITH EXISTING FIRE ALARM AND LIFE SAFETY PLANS.

FIRE ALARM GENERAL NOTES

CHANNEL RACK FRAME WHERE

EQUIPMENT IS MOUNTED.

CABLE WATERFALL

ATTACHED TO THE

TOP OF THE

CHANNEL RACK.

REAR EQUIPMENT

RAIL AT THE TOP OF

THE RACK.

6" VERTICAL WIRE MANAGEMENT. THE REAR

OF THE WIRE MANAGEMENT MOUNTS TO THE

FRONT OF THE CHANNEL RACK. THE CABLE

WATERFALL DIRECTS CABLING INTO THE

VERTICAL WIRE MANAGEMENT FROM THE TOP.

CHANNEL RACK SYMBOL NOTES

Engineers Architects

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

/2

:1

:4

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts

\T R

R o o m

D e ta ils ls ta rn e s C

B U

M B

.r v t

TECHNOLOGY GENERAL NOTES,

SYMBOL LEGEND, AND

ABBREVIATIONS

2 107ADR

EHRM INFRASTRUCTURE

UPGRADES

MICHAEL E. DEBAKEY VAMC

2002 HOLCOMBE BLVD.

HOUSTON, TX 77030 JANUARY 14, 2025

BID DOCUMENTS

580-22-70021-313

JDM

000 ET002

CONDITIONAL NOTE

FIRE ALARM SYMBOL

E

CR

DC ES RX J

M

10 10

PANEL 'A' PANEL 'B'

ET5016

A-7,9,11

B-7,9,11

SBB

K

A-2

B-2

A-2

A-2 N

GFIB-2

B-2

A-2

B-2

W

A

B

A

B

A

A-1,3,5

B-1,3,5

A-13,15,17

B-13,15,17BA

6FIRE RATED PATHWAYS

A-4

A

AA

FIRE RATED PATHWAYS6

PANEL A

FIRE RATED

PATHWAYS

SSB

CABLE TRAY

RECEPTACLE NEMA 5-20R

MOTOR-RATED

SWITCH

17 17

"B" PANEL"A" PANEL

CABLE TRAY

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R SSB

DATA PORT

LIGHT SWITCH

RECEPTACLE

NEMA 5-20R

RECEPTACLE

NEMA 5-20R

"B" PANEL

SBB

NEC REQUIRED WORKING

CLEARANCE, 30" WIDE BY

36" DEEP BY 72" HIGH

17 17

16 16

RECEPTACLE NEMA 5-20R

Engineers Architects

# KEY NOTES:

Revisions: Date

Drawing Title

Approved

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

SHEET NOTES:

Date Checked Drawn

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

/1

/2

:1

:4

P

M C

U s e rs

\l s ta rn e s \D o c u m e n ts

\T R

R o o m

D e ta ils ls ta rn e s C

B U

M B

.r v t

TYPICAL TELECOM ROOM DETAILS

3 107ADR

EHRM INFRASTRUCTURE

UPGRADES

MICHAEL E. DEBAKEY VAMC

2002 HOLCOMBE BLVD.

HOUSTON, TX 77030 JANUARY 14, 2025

BID DOCUMENTS

580-22-70021-313

JDM

000 ET501

1 ROOMS ARE COOLED WITH EITHER FAN COIL

UNITS (FCU) OR DUCTLESS MINI-SPLITS. FOR

FCUS, PROVIDE A 20A/1P CIRCUIT FROM

PANEL 'A' TO A MOTOR-RATED TOGGLE

SWITCH WITH A CONNECTION TO THE UNIT.

DUCTLESS MINI-SPLIT UNITS SHALL BE

POWERED FROM THEIR ASSOCIATED

OUTDOOR CONDENSING UNITS. PROVIDE A

CIRCUIT TO THE CONDENSING UNIT,

INCLUDING RACEWAYS AND CONDUCTORS

TO POWER THE INDOOR UNITS.

2 TELECOMMUNICATIONS CHANNEL RACK,

23.75" WIDE (19" RAILS) SQUARE HOLE

PATTERN, 30 INCHES DEEP (MINIMUM), 84

INCHES HIGH, 45RU, WHITE. PROVIDE

ORTRONICS (LEGRAND) MM2073038-W, OR

APPROVED EQUIVALENT. CONTRACTOR

SHALL COORDINATE ADDITIONAL DETAILS

INCLUDING BUT NOT LIMITED TO GROUNDING

AND BONDING DETAILS, DATA ELEVATIONS

AND POWER ELEVATIONS IN THE DRAWINGS.

3 VERTICAL CABLE MANAGEMENT CAGE WITH

DOOR, 6 INCHES WIDE, 84 INCHES HIGH,

45RU, WHITE. PROVIDE ORTRONICS

(LEGRAND) MM20VMD706-W, OR APPROVED

EQUIVALENT.

4 RACK POWER CONNECTION MOUNTED TO

THE CHANNEL STEEL ABOVE THE RACKS

MINIMUM 12" AWAY FROM CABLE TRAY. FOR

EACH RACK, PROVIDE L21-20R RECEPTACLE.

PROVIDE (4) 12 AWG AND (1) 12 AWG GND IN

3/4" CONDUIT. REFER TO RACK POWER

ELEVATION AND SCHEMATIC DIAGRAMS ON

SHEET 000 ET505.

5 SECONDARY BONDING BUSBAR.

TELECOMMUNICATIONS EQUIPMENT SHALL

BE BONDED ACCORDING TO THE

GROUNDING AND BONDING DETAILS. REFER

TO DETAILS 3 AND 4 ON SHEET 000 ET503

FOR MORE INFORMATION.

6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE

UL LISTED ASSEMBLIES, STI EZ-PATH, SERIES

44 FIRE-RATED PATHWAY, OR APPROVED

EQUIVALENT. INSTALL SLEEVES ABOVE

DOOR HEADER AT AN ELEVATION

COORDINATED TO BE ABOVE THE EXISTING

CEILING HEIGHT IN THE ADJACENT

COORIDOR. REFER TO 400 SERIES ET

SHEETS FOR QUANTITIES.

7 PROVIDE NEW WIRE MESH TRAY AROUND

THE ROOM AND ABOVE THE CHANNEL

RACKS, WITH WATERFALL DROPOUTS INTO

EACH RACK, 90 DEGREE CORNERS AND ALL

RELATED FITTINGS. SEE WIRE MESH TRAY

DETAIL ON 000.ET504 FOR MORE INFO.

B.O.D.: CABLEOFIL CF105/600 AND CF150/600

SERIES OR EQUIVALENT.

8 RECEPTACLES, PROVIDE TWO RECEPTACLE

ON EACH WALL, AS SHOWN, ONE FED FROM

PANEL A THE OTHER FROM PANEL B.

9 FIRE RETARDANT PLYWOOD BACKBOARD.

SEE ARCHITECTURAL.

10 LIGHTING AND APPLIANCE PANELBOARDS.

PROVIDE PANELS MOUNTED ON CHANNEL

STEEL SUPPORTS. UNLESS NOTED

OTHERWISE ON THE 400 SERIES ET SHEETS,

PANEL 'A' SHALL BE FED FROM A SOURCE

WITH GENERATOR BACKUP, AND PANEL 'B'

SHALL BE FED FROM A NORMAL UTILITY

SOURCE.

11 PROVIDE JUNCTION BOX WITH EMERGENCY

POWER TO THE PACS DOOR CONTROLLER.

12 PROVIDE FIXED, MULTI SENSOR CAMERA

WITH 90 DEGREE FIELD OF VIEW AND

CONNECT TO EXISTING CAMERA SYSTEM.

LOCATION SHOULD BE COORDINATED WITH

THE CHANNEL RACK LAYOUT AND OIT.

13 PROVIDE CABLING FOR VA FURNISHED

WIRELESS ACCESS POINT.

14 PROVIDE RECEPTACLE NEAR DOOR, WITH

POWER EXTENDED FROM AN EXISTING

CONVENIENCE OUTLET CIRCUIT

ORIGINATING FROM A PANEL NOT IN THE

ROOM.

15 PROVIDE WALL PHONE OUTLET IN EVERY

TELECOM ROOM.

16 FIRE-RATED PATHWAY WILL GO UP INTO THE

INTERSTITIAL SPACE IN BUILDING 100.

PROVIDE UL LISTED ASSEMBLY WITH A T

RATING THAT IS A MINIMUM OF 1 HOUR. FOR

ALL OTHER BUILDINGS, THE FIRE RATED

PATHWAY WILL GO HORIZONTALLY INTO

ADJACENT SPACE ABOVE CEILINGS.

17 BASKET CABLE TRAY IS SHOWN OFFSET

FROM WALL FOR…