Engineers Architects
Revisions: Date
Drawing Title
Location
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
Approved
Project Title VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
Date Checked Drawn
/1
/2
:1
:3
P
M C
U s e rs \c k u rk u l\ D o c u m e n ts
\A
-3
-V A
H o u s to n -E
H R
M
M A
S T
E R c k u rk u lG V
Y
H .r v t
COVER VOLUME 4
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BLVD.
HOUSTON, TX 77030
BID DOCUMENTS
21-313
EHRM INFRASTRUCTURE UPGRADES
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BLVD.
HOUSTON, TX 77030
VA PROJECT #: 580-22-700
1 1CMK
EHRM INFRASTRUCTURE
UPGRADES
JANUARY 14, 2025
580-22-700
WVS
000 G-001.4
VOLUME 4
VOLUME 4 OF 4
DRAWING LIST - VOLUME 4
GENERAL
000 G-001.4 COVER VOLUME 4 1 1
ELECTRICAL
000 ET001 ELECTRICAL GENERAL NOTES, SYMBOL LEGENDS, AND ABBREVIATIONS 1 107
000 ET002 TECHNOLOGY GENERAL NOTES, SYMBOL LEGEND, AND ABBREVIATIONS 2 107
000 ET501 TYPICAL TELECOM ROOM DETAILS 3 107
000 ET502 ELECTRICAL AND TECHNOLOGY DETAILS 4 107
000 ET503 ELECTRICAL AND TECHNOLOGY DETAILS 5 107
000 ET504 TECHNOLOGY DETAILS 6 107
000 ET505 CHANNEL RACK POWER AND TE DETAILS 7 107
000 ET506 TR RACK DETAIL, MAIN DISTRIBUTION AREA DETAILS, AND SCHEDULES 8 107
000 ET507 TECHNOLOGY DETAILS 9 107
000 ES101 SITE FIBER BACKBONE ROUTING PLAN 10 107
100 ET100 BUILDING 100, OVERALL BASEMENT FLOOR ELECTRICAL PLAN 11 107
100 ET110 BUILDING 100, OVERALL FIRST FLOOR ELECTRICAL PLAN 12 107
100 ET120 BUILDING 100, OVERALL SECOND FLOOR ELECTRICAL PLAN 13 107
100 ET130 BUILDING 100, OVERALL THIRD FLOOR ELECTRICAL PLAN 14 107
100 ET140 BUILDING 100, OVERALL FOURTH FLOOR ELECTRICAL PLAN 15 107
100 ET150 BUILDING 100, OVERALL FIFTH FLOOR ELECTRICAL PLAN 16 107
100 ET160 BUILDING 100, OVERALL SIXTH FLOOR ELECTRICAL PLAN 17 107
103 ET110 BUILDING 103, OVERALL FIRST FLOOR ELECTRICAL PLAN 18 107
104 ET110 BUILDING 104, OVERALL FIRST FLOOR ELECTRICAL PLAN 19 107
108 ET110 BUILDING 108, OVERALL FIRST FLOOR ELECTRICAL PLAN 20 107
108A ET110 BUILDING 108A, OVERALL FIRST AND SECOND FLOOR ELECTRICAL PLAN 21 107
109 ET100 BUILDING 109, OVERALL BASEMENT FLOOR ELECTRICAL PLAN 22 107
109 ET110 BUILDING 109, OVERALL FIRST FLOOR ELECTRICAL PLAN 23 107
109 ET120 BUILDING 109, OVERALL SECOND FLOOR ELECTRICAL PLAN 24 107
110 ET100 BUILDING 110, OVERALL BASEMENT FLOOR ELECTRICAL PLAN 25 107
110 ET110 BUILDING 110, OVERALL FIRST FLOOR ELECTRICAL PLAN 26 107
110 ET120 BUILDING 110, OVERALL SECOND FLOOR ELECTRICAL PLAN 27 107
110 ET130 BUILDING 110, OVERALL THIRD FLOOR ELECTRICAL PLAN 28 107
120 ET110 BUILDING 120, OVERALL FIRST FLOOR ELECTRICAL PLAN 29 107
123 ET110 BUILDING 123, OVERALL FIRST FLOOR ELECTRICAL PLAN 30 107
125 ET110 BUILDIING 125, OVERALL FIRST AND SECOND FLOOR ELECTRICAL PLAN 31 107
100T ET311 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-101 SECTIONS 32 107
100T ET312 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-102 SECTIONS 33 107
100T ET313 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-103 SECTIONS 34 107
100T ET320 BUILDING 100, TYPICAL TOWER, SECTIONS - FLOORS 2 THRU 5 35 107
100T ET360 BUILDING 100, SIXTH FLOOR, TOWER TR SECTIONS 36 107
100T ET400 BUILDING 100, TYPICAL TOWER, TELECOM ROOM PLANS 37 107
100 ET401 BUILDING 100, BASEMENT FLOOR, TELECOM ROOM BA-450B PLANS 38 107
100 ET402 BUILDING 100, BASEMENT FLOOR, TELECOM AND ENTRANCE ROOM B ROOM BB-221 PLANS 39 107
100 ET403 BUILDING 100, BASEMENT FLOOR, TELECOM ROOM BC-209A PLANS 40 107
100 ET404 BUILDING 100, BASEMENT FLOOR, MAIN COMPUTER ROOM BC-301 PLANS 41 107
100 ET405 BUILDING 100, BASEMENT FLOOR, TELECOM ROOM ZB-E03A PLANS 42 107
100 ET406 BUILDING 100, BASEMENT FLOOR, TELECOM ROOM ZB-L06A PLANS 43 107
100T ET411 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-101 PLANS 44 107
100T ET412 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-102 PLANS 45 107
100T ET413 BUILDING 100, FIRST FLOOR, TELECOM ROOM T-103 PLANS 46 107
100 ET414 BUILDING 100, FIRST FLOOR, TELECOM ROOM 1A-314 PLANS 47 107
100 ET415 BUILDING 100, FIRST FLOOR, TELECOM ROOM 1A-660A 48 107
100 ET416 BUILDING 100, FIRST FLOOR, TELECOM ROOM 1B-204B PLANS 49 107
100 ET417 BUILDING 100, FIRST FLOOR, TELECOM ROOM 1C-356A PLANS 50 107
100T ET421 BUILDING 100, SECOND FLOOR, TELECOM ROOM T-201 PLANS 51 107
100T ET422 BUILDING 100, SECOND FLOOR, TELECOM ROOM T-202 PLANS 52 107
100T ET423 BUILDING 100, SECOND FLOOR, TELECOM ROOM T-203 PLANS 53 107
100 ET424 BUILDING 100, SECOND FLOOR, TELECOM ROOM 2A-114 PLANS 54 107
100 ET425 BUILDING 100, SECOND FLOOR, TELECOM ROOM 2B-340A PLANS 55 107
100 ET426 BUILDING 100, SECOND FLOOR, TELECOM ROOM 2C-420A PLANS 56 107
100T ET431 BUILDING 100, THIRD FLOOR, TELECOM ROOM T-301 PLANS 57 107
100T ET432 BUILDING 100, THIRD FLOOR, TELECOM ROOM T-302 PLANS 58 107
100T ET433 BUILDING 100, THIRD FLOOR, TELECOM ROOM T-303 PLANS 59 107
100 ET434 BUILDING 100, THIRD FLOOR, TELECOM ROOM 3A-100A PLANS 60 107
100 ET435 BUILDING 100, THIRD FLOOR, TELECOM ROOM 3B-310M PLANS 61 107
100 ET436 BUILDING 100, THIRD FLOOR, TELECOM ROOM 3C-204A PLANS 62 107
100T ET441 BUILDING 100, FOURTH FLOOR, TELECOM ROOM T-401 PLANS 63 107
100T ET442 BUILDING 100, FOURTH FLOOR, TELECOM ROOM T-402 PLANS 64 107
100T ET443 BUILDING 100, FOURTH FLOOR, TELECOM ROOM T-403 PLANS 65 107
100 ET444 BUILDING 100, FOURTH FLOOR, TELECOM ROOM 4A-136 PLANS 66 107
100 ET445 BUILDING 100, FOURTH FLOOR, TELECOM ROOM 4B-204A PLANS 67 107
100 ET446 BUILDING 100, FOURTH FLOOR, TELECOM ROOM 4C-204A PLANS 68 107
100T ET451 BUILDING 100, FIFTH FLOOR, TELECOM ROOM T-501 PLANS 69 107
100T ET452 BUILDING 100, FIFTH FLOOR, TELECOM ROOM T-502 PLANS 70 107
100T ET453 BUILDING 100, FIFTH FLOOR, TELECOM ROOM T-503 PLANS 71 107
100 ET454 BUILDING 100, FIFTH FLOOR, TELECOM ROOM 5A-174 PLANS 72 107
100 ET455 BUILDING 100, FIFTH FLOOR, TELECOM ROOM 5B-358A PLANS 73 107
100 ET456 BUILDING 100, FIFTH FLOOR, TELECOM ROOM 5C-320A PLANS 74 107
100T ET461 BUILDING 100, SIXTH FLOOR, TELECOM ROOM T-601 PLANS 75 107
100T ET462 BUILDING 100, SIXTH FLOOR, TELECOM ROOM T-602 PLANS 76 107
100T ET463 BUILDING 100, SIXTH FLOOR, TELECOM ROOM T-603 PLANS 77 106
100 ET464 BUILDING 100, SIXTH FLOOR, TELECOM ROOM 6B-392A PLANS 78 107
100 ET465 BUILDING 100, BASEMENT AND FIRST FLOOR POWER ENLARGEMENTS 79 106
100 ET466 BUILDING 100, SECOND AND THIRD FLOOR POWER ENLARGEMENTS 80 107
100 ET467 BUILDING 100, THIRD AND FOURTH FLOOR POWER ENLARGEMENTS 81 107
100 ET468 BUILDING 100, FIFTH AND SIXTH FLOOR POWER ENLARGEMENTS 82 107
103 ET411 BUILDING 103, FIRST FLOOR, TELECOM ROOM 4A-113A PLANS 83 107
104 ET411 BUILDING 104, FIRST FLOOR, TELECOM ROOM 109 PLANS 84 107
108 ET411 BUILDING 108, FIRST FLOOR, TELECOM ROOM 102G PLANS 85 107
108A ET411 BUILDING 108A, FIRST FLOOR, TELECOM ROOM 125 PLANS 86 107
108A ET421 BUILDING 108A, SECOND FLOOR, TELECOM ROOM 232 PLANS 87 107
109 ET401 BUILDING 109, BASEMENT FLOOR, TELECOM ROOM B-43 PLANS 88 106
109 ET411 BUILDING 109, FIRST FLOOR, TELECOM ROOM 141 PLANS 89 106
109 ET421 BUILDING 109, SECOND FLOOR, TELECOM ROOM 238A PLANS 90 107
110 ET411 BUILDING 110, FIRST FLOOR, TELECOM ROOM 125 PLANS 91 107
110 ET412 BUILDING 110, FIRST FLOOR, TELECOM ROOM 136 PLANS 92 107
110 ET421 BUILDING 110, SECOND FLOOR, TELECOM ROOM 228 PLANS 93 107
110 ET422 BUILDING 110, SECOND FLOOR, TELECOM ROOM 235A PLANS 94 107
110 ET431 BUILDING 110, THIRD FLOOR, TELECOM ROOM 302B PLANS 95 107
DRAWING LIST - VOLUME 4
120 ET411 BUILDING 120, FIRST FLOOR, TELECOM ROOM 114 PLANS 96 107
123 ET411 BUILDING 123, FIRST FLOOR, TELECOM ROOM PLANS 97 107
125 ET411 BUILDING 125, FIRST FLOOR, TELECOM ROOM 116 PLANS 98 107
125 ET421 BUILDING 125, SECOND FLOOR, TELECOM ROOM 216 PLANS 99 107
000 ET601 FIBER RISER DIAGRAMS 100 107
100 ET602 BUILDING 100, BONDING RISER 101 107
100 ET603 BUILDING 100, SINGLE LINE POWER DIAGRAM 102 107
100 ET604 BUILDING 100, SINGLE LINE POWER DIAGRAM 103 107
103 ET601 BUILDING 103, SINGLE LINE DIAGRAM 104 107
104 ET601 BUILDING 104, SINGLE LINE DIAGRAM 105 107
108 ET601 BUILDING 108, SINGLE LINE DIAGRAM 106 107
108A ET601 BUILDING 108A, SINGLE LINE DIAGRAM 107 107
100, 103, 104A, 108, 108A, 109, 110, 120, 121, 122, 123, 124, 125, FISHER HOUSE
(1, 2, AND 3), VA REGIONAL OFFICEW
AL
TE
R DAVID VAN SCOTER
REG. NO. 9953
Docusign Envelope ID: 4347F947-D407-40B0-BEA8-3B760489F051
1/14/2025
120V DUPLEX RECEPTACLE
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
120V DUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
JUNCTION BOX, WALL MOUNTED, PURPOSE AS NOTED
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
SINGLE POLE WALL SWITCH: 48" AFF STANDARD UNO
SYMBOL HEIGHT DESCRIPTION
18"
18"
18"
18"
AS
NOTED
72" TOP
72" TOP
SWITCH MODIFIERS:
M: MOTOR-RATED
48"
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SPECIAL RECEPTACLE, REFER TO ET501 FOR NEMA
TYPE
EQUIPMENT CONNECTION
AS
NOTED
E
18"
120V DUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V QUADUPLEX RECEPTACLE EMERGENCY
FLOOR BOX OUTLET AND COVER PLATE SHALL BE
RED IN COLOR
CLNG
J
J
J
JUNCTION BOX, CEILING MOUNTED, PURPOSE AS
NOTED
JUNCTION BOX, FLOOR MOUNTED, PURPOSE AS
NOTED
120V SIMPLEX RECEPTACLE18"
2' X 2' RECESSED ARCHITECTURAL TROFFER
2' X 4' RECESSED ARCHITECTURAL TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT LENS TROFFER
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
VS: VACANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY
DR: DUAL RELAY
VSD: VACANCY SENSOR, LINE VOLTAGE, DIMMER
OSD: OCCUPANCY SENSOR, LINE VOLTAGE, DIMMER
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
4: 4 WAY
48"
CENTER
OCCUPANCY SENSOR, LOW VOLTAGE,
DUAL TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, LOW VOLTAGE, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
OS
OS
LS
4' LINEAR STRIP - SUSPENDED---
L L
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
UPS UNINTERUPTABLE POWER
SUPPLY
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MSBD MAIN SWITCHBOARD
MT MOUNT
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BIPHENYL
PC PHOTOELECTRIC CELL
PDU POWER DISTRIBUTION UNIT
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
R RELOCATE/RELOCATED
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
2W TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCT CORRELATED COLOR TEMPERATURE
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
D DEMOLITION
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FU FUSE
FUDS FUSED SAFETY DISCONNECT
SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEC GROUND ELECTRODE CONDUCTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HW HARD WIRED
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER
CASE LETTER AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b'.
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING
MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES
DIRECTIONAL ARROW ON ILLUMINATED FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER
FOLLOWING THE UPPER CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR
THE SINGLE LINE DIAGRAM FOR THE TRANSFORMER DESCRIPTION AND
REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING
SIDE OF RECESSED PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR
DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE
NUMBER INDICATED IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT
DESIGNATION ARE SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL
SCHEDULE WITH THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE
A UNIT TYPE. SEE APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE
AND DIRECTIONAL ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE
FACE AND DIRECTIONAL ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE
NOTE NUMBER INDICATED IN THE SQUARE.
A. PRIOR TO SUBMITTING PROPOSAL, BIDDER SHALL EXAMINE ALL GENERAL CONSTRUCTION DRAWINGS.
B. CERTAIN REMODELING OF ELECTRICAL FACILITIES WILL BE REQUIRED IN THE EXISTING BUILDING. EXISTING CONDUIT RUNS ARE GENERALLY NOT SHOWN. ALTHOUGH A FULL ATTEMPT HAS BEEN MADE TO SHOW SOME EXISTING CONDITIONS, OF WHICH INFORMATION HAS BEEN TAKEN FROM EXISTING RECORD DRAWINGS OF THIS PROJECT. THE DRAWINGS SHOWING LOCATION OF EXISTING EQUIPMENT, OUTLETS, FIXTURES, ETC., IN EXISTING AREAS ARE
APPROXIMATE ONLY (FIELD VERIFY).
C. BRANCH CIRCUITS SHALL BE REUSED WHERE PRACTICAL AND SHALL, IN ADDITION, BE REMODELED AS REQUIRED. THE
CONTRACTOR SHALL CONCEAL ALL WORK WHERE POSSIBLE.
D. EXISTING ELECTRICAL WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO OPERATING CONDITION, AS REQUIRED AND/OR DIRECTED. WHERE REQUIRED, SHOWN AND/OR DIRECTED, OUTLETS AND CONDUIT RUNS SHALL BE RELOCATED. IN SOME CASES IT MAY BE NECESSARY TO EXTEND CONDUITS AND PULL IN NEW WIRING OR INSTALL
JUNCTION BOXES AND SPLICE IN NEW WIRING OR REPLACE OLD WIRING WITH NEW.
E. OUTLETS FROM WHICH FIXTURES, SWITCHES, RECEPTACLES, AND/OR OTHER ELECTRICAL DEVICES ARE MOVED AND WHICH ARE NOT REPLACED OR REUSED SHALL BE REMOVED OR, IF IT IS NOT POSSIBLE TO REMOVE, PLACE A BLANK COVER ON THE OUTLET BOX. WHERE OUTLETS, BOXES, ETC., ARE COMPLETELY REMOVED, THE CONTRACTOR SHALL
CUT OFF CONDUITS AND REMOVE WIRING.
F. WHERE EXISTING LIGHT FIXTURES ARE TO BE REUSED, THE ELECTRICAL CONTRACTOR SHALL CLEAN AND REPLACE
LAMPS, REPAIR OR REPLACE DEFECTIVE PARTS, LENS, BALLAST, ETC. AS REQUIRED.
G. WHERE CONDUITS EXTENDING THROUGH FLOORS ARE TO BE ABANDONED, THE CONTRACTOR SHALL CUT AND CAP OR
PLUG CONDUIT, THAT IT WILL NOT PROTRUDE ABOVE THE FLOOR.
H. WHERE EXISTING CONDUIT IS TO BE ABANDONED, THE CONDUIT SHALL BE REMOVED IF IT IS EXPOSED, IN A CRAWL SPACE OR IN AN ACCESSIBLE CEILING. WHERE IT IS IMPOSSIBLE TO REMOVE THE CONDUIT, IT SHALL BE CUT OFF AND
CAPPED OR PLUGGED.
I. THE CONTRACTOR SHALL BE HELD FULLY RESPONSIBLE FOR THE PROPER RESTORATION OF ALL EXISTING SURFACES REQUIRED PATCHING, PLASTERING, PAINTING AND/OR OTHER REPAIR DUE TO THE INSTALLATION OF ELECTRICAL WORK UNDER THE TERMS OF THIS SPECIFICATION. CLOSE ALL OPENINGS, REPAIR ALL SURFACES, ETC., AS REQUIRED. THE CONTRACTOR SHALL EMPLOY QUALIFIED AND EXPERIENCED WORKMEN FOR THIS WORK. ALL RESTORATION WORK
SHALL BE SUBJECT TO THE APPROVAL OF THE ARCHITECT AND/OR THE COR/VA.
J. ALL TEMPORARY AND REMODELING WORK SHALL BE CONSIDERED A PART OF THIS CONTRACT AND NO EXTRA CHARGES WILL BE ALLOWED. THIS SHALL INCLUDE MINOR ITEMS OF MATERIAL OR EQUIPMENT NECESSARY TO MEET THE
REQUIREMENTS AND INTENT OF THE PROJECT.
K. EXAMINE ARCHITECTURAL, STRUCTURAL, AND MECHANICAL DRAWINGS AND SPECIFICATIONS TO DETERMINE THE SEQUENCE OF CONSTRUCTION THROUGHOUT THE PROJECT, INCLUDING EXISTING, TEMPORARY, REMODELED AND NEW
AREAS.
L. ALL ELECTRICAL CONNECTIONS REQUIRING AN OUTAGE SHALL BE MADE DURING AN APPROVED TIME LIMIT.
CHANGEOVERS SHALL BE AS SHORT A DURATION AS POSSIBLE AND SHALL NOT INTERFERE WITH NORMAL OPERATION OF THE COR/VA FACILITIES. NOTIFY COR/VA NO LESS THAN 14 DAYS (TWO WEEKS) IN ADVANCE OF A SHUTDOWN OF ANY ELECTRICAL CIRCUIT FOR CHANGEOVER, AND SUCH A CHANGEOVER SHALL BE DONE DURING HOURS AS DIRECTED BY COR/VA. WORK SHALL BE SCHEDULED SO THAT AT NO TIME WILL ANY EMERGENCY FEEDER, CIRCUIT, OR FIRE ALARM ZONE BE OUT OF SERVICE. PROVIDE NECESSARY TEMPORARY FEEDERS TO ACCOMPLISH THIS REQUIREMENT.
M. EXISTING LOW VOLTAGE WIRING WHICH WILL NOT BE MADE OBSOLETE AND WHICH WILL BE DISTURBED DUE TO CONSTRUCTION CHANGES REQUIRED BY THIS CONTRACT SHALL BE RESTORED TO CONDITION, OR POSITION, AS REQUIRED. PROPERLY RE-SECURE CABLE IN CHASES, CRAWL SPACES, TUNNELS, AND CEILING SPACES AS REQUIRED BY NEC. IN SOME CASES IT MAY BE NECESSARY TO ADD SUPPORTING HARDWARE TO ACCOMPLISH THIS REQUIREMENT.
N. IF POSSIBLE, ALL NEWLY INSTALLED RECEPTACLES SHALL BE INSTALLED IN SEPARATE STUD SPACES, TO AVOID SOUND TRANSMISSION AND WALL INTEGRITY ISSUES. ALL NEWLY INSTALLED RECEPTACLES LOCATED IN COMMON STUD SPACES OF FIRE-RESISTANT WALLS SHALL BE EQUIPPED WITH FIRE-RESISTANT PUTTY PADS AT THE BACK OF EACH BOX IN ACCORDANCE WITH NEC 300.21. DEVICES SHALL HAVE A MINIMUM OF 24" CENTER TO CENTER LATERAL SPACING.
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA
STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE BUILDING
CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE WITH THE REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE, UL LISTING REQUIREMENT AND THE APPLICABLE BUILDING CODES.
4. VERIFY CEILING SYSTEMS AND PROVIDE MOUNTING ACCESSORIES, TRIMS AND ALL REQUIRED MOUNTING HARDWARE TO
SUIT THE PARTICULAR INSTALLATION.
5. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
6. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
7. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO AVOID CONFLICT DURING
CONSTRUCTION.
8. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR SPARE, OR SPACE.
9. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
10. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR EQUIPMENT
MANUFACTURER'S SPECIFICATIONS.
11. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE DEVICE'S SCREW
TERMINALS.
12. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
13. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
14. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
15. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND CONDUIT OR WHERE CONCRETE- ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE, LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR
FINAL CONNECTIONS.
16. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN APPROVED THIRD
PARTY TESTING AGENCY.
17. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS.
PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
18. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS DETERMINED BY THE GOVERNMENT, SHALL BE
PROVIDED.
19. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
20. MINIMUM CONDUIT SIZE TO BE USED IS 3/4".
21. FEEDER TAGS APPENDED WITH 'VD' ARE UPSIZED IN AMPACITY DUE TO VOLTAGE DROP.
22. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT, SUCH AS DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED
PENETRATION.
A. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. MATERIALS DEEMED NOT SALVAGEABLE SHALL BE
REMOVED FROM THE PREMISES.
B. ALL EXISTING CONDITIONS, INCLUDING BUT NOT LIMITED TO EQUIPMENT, DEVICES, FIXTURES, CONDUIT AND CIRCUITS, ARE BASED ON THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
C. THE DRAWINGS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL HARMONIZE HIS WORK SO THAT EACH PIECE OF EQUIPMENT WILL BE INSTALLED AS TO FUNCTION PROPERLY. THE CONTRACTOR SHALL COOPERATE WITH OTHER
TRADES.
D. REMOVE ALL EXISTING WIRING DEVICES, LIGHT FIXTURES, WIRE, CONDUIT, ETC., AS NOTED OR INDICATED WITHIN DEMOLITION AREA. (ALL ITEMS MAY NOT BE SHOWN). REWORK AS NECESSARY CIRCUITING WHICH REQUIRES
CONTINUATION THROUGH THE AREA.
E. ELECTRICAL CONTRACTOR TO PROVIDE ALL NECESSARY LABOR, CONDUIT, WIRE, CONNECTIONS, ETC., FOR DEVICES, FIXTURES, ETC., NOTED AS "EXISTING TO REMAIN" SUCH THAT EXISTING CIRCUIT CONTINUITY IS MAINTAINED.
F. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK REQUIRED TO REMOVE/RELOCATE ANY EXISTING ELECTRICAL EQUIPMENT SUCH THAT ELECTRIC SHOCK HAZARDS TO WORKMEN ARE ELIMINATED DURING DEMOLITION AND
NEW CONSTRUCTION.
G. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL WORK IN REMOVING AND REPLACING "EXISTING TO REMAIN" FIXTURES, DEVICES, ETC., AS REQUIRED SO THAT THESE DEVICES ARE NOT DAMAGED DURING DEMOLITION. RELOCATED TO NEAREST APPROPRIATE LOCATION TO AVOID CONFLICTS WITH OTHER TRADES' WORK. REPLACE WITH NEW ANY "EXISTING
TO REMAIN" FIXTURE, DEVICE, ETC., NOT DEEMED SALVAGEABLE BY THE COR.
H. REMOVED OR DAMAGED CONDUIT, WIRE, AND FITTINGS SHALL NOT BE REUSED FOR RELOCATED OR NEW DEVICES.
I. MAKE AS-BUILTS WITH NEW TYPED DIRECTORIES FOR ALL PANELBOARDS, INDICATING CIRCUIT DESCRIPTION (USED OR
SPARE), CIRCUIT BREAKERS AND CIRCUIT LOAD.
J. WORK REQUIRED FOR EXISTING EQUIPMENT NOTED AS "EXISTING TO BE REMOVED" SHALL INCLUDE:
A. REMOVAL OF FEEDER FROM EQUIPMENT TO POINT OF FEED.
B. REMOVAL OR RE-CIRCUITING OF ALL BRANCH CIRCUITING.
C. REMOVAL OF ALL FITTINGS, SUPPORTS, BRACKETS, ETC.
D. PATCHING OF WALLS, FLOORS AND CEILINGS PER ARCHITECT'S INSTRUCTIONS.
E. CAPPING OF FEEDER CONDUIT AT 6" ABOVE OR BELOW FLOOR/CEILING AS REQUIRED AND MARKING LOCATION OF POINT
OF FEED WITH AN ENGRAVED BRASS TAG.
F. REMOVAL OF FEEDER CONDUIT IF FOUND TO BE UNSALVAGEABLE BY ARCHITECT, ENGINEER OR THE COR.
K. EXISTING EQUIPMENT NOT IMPLICITLY SHOWN ON THE DRAWINGS IS INTENDED TO BE "EXISTING TO REMAIN UNCHANGED", UNLESS NOTED OTHERWISE.
IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING COMPOSED OF MINERAL WOOL SHALL BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED
PENETRATION.
SHORT CIRCUIT CURRENT CALCULATIONS SHALL BE PERFORMED ON THE ELECTRICAL SYSTEM USING A BOLTED THREE PHASE FAULT CONDITION FOR CALCULATIONS TO ACHIEVE MAXIMUM THERMAL AND MECHANICAL STRESS TO THE SYSTEM FOR CALCULATIONS PURPOSES. EXISTING SHORT CIRCUIT VALUES WILL BE USED OUTSIDE THE WORK
AREA, FOR THE STARTING POINT OF THE CALCULATIONS.
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:1
:4
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts
\T R
R o o m
D e ta ils ls ta rn e s C
B U
M B
.r v t
ELECTRICAL GENERAL NOTES,
SYMBOL LEGENDS, AND
ABBREVIATIONS
1 107ADR
EHRM INFRASTRUCTURE
UPGRADES
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BLVD.
HOUSTON, TX 77030 JANUARY 14, 2025
BID DOCUMENTS
580-22-70021-313
JDM
000 ET001
ELECTRICAL SYMBOL LEGEND
LIGHTING SYMBOL LEGEND ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES
GENERAL ELECTRICAL REMODELING NOTES
ELECTRICAL GENERAL NOTES
GENERAL ELECTRICAL DEMO NOTES
TEMPORARY FIRESTOPPING
METHOD OF SHORT CIRCUIT CURRENT CALCULATIONS
Docusign Envelope ID: 2B86FD95-F687-4E04-BBB2-F6FA4A59EBAA
1/14/2025 1/14/2025
TECHNOLOGY SYMBOL LEGEND
DATA OUTLET - N-4 PR UTP
SYMBOL HEIGHT DESCRIPTION
18"
WIRELESS ACCESS POINT - N-4 PR UTP
WALL MOUNT PHONE VOIP OUTLET
W
N
48"
N
CEILING
(N - QUANTITY)
(N - QUANTITY)
ELECTRIC STRIKE
CARD READER
(K - KEYPAD)
48"CR
EL DOOR
PHYSICAL ACCESS CONTROL SYSTEMPACS 6' TO TOP
DOOR CONTACT
REQUEST FOR EXIT SENSOR
DC
RX
DOOR
ABOVE
DOOR
DO DOOR OPERATORDOOR
48" EMERGENCY EXIT BUTTON TO RELEASE DOOR (EEB)
CCTV DOME CAMERA FIXED
CCTV DOME CAMERA PAN/TILT/ZOOM
FOUR POST CHANNEL RACK
OIT EQUIPMENT CABINET
FLOOR
FLOOR
FLOOR 6", 12" VERTICAL WIRE MANAGEMENT
CEILING
CEILING
CCTV EQUIPMENT CABINETCCTV
BASKET CABLE TARY
GROUND BUS
FLOOR
ABOVE
CEILING
12", 18", 20"
4'x8'x3/4" FIRE RATED TTB8"
CABLE LADDERABOVE
CEILING
CEILING MOUNTED SPEAKERSCEILING
WALL MOUNTED SPEAKERS96"
S
S
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
SEE DRAWINGS FOR MORE INFORMATION.
NOTE: NOT ALL SYMBOLS ARE USED.
CABLES AND CONNECTORS COLOR LEGEND
DESCRIPTION
ITEM JACK CABLE PATCH CABLES I.D. NOTES
DATA/COMPUTER
WIRELESS
ACCESS POINT
FIBER - MULTI-MODE
FIBER - SINGLE-MODE
CCTV - IP
BLUE
N/A
N/A
N/A
N/A
BLUE
GREEN
AQUA
YELLOW
WHITE
BLUE
GREEN
AQUA
YELLOW
WHITE
C
WAP
FO
FO
CCTV 4 PAIR UTP CABLE
4 PAIR UTP CABLE
4 PAIR UTP CABLE
6/12/24
6/12/24
PACS N/A GRAY N/A PACS MULTI-PAIR
CONDUCTORS
ADO AUTOMATIC DOOR OPERATOR
AFF ABOVE FINISH FLOOR
BOD BASIS OF DESIGN
CCTV CLOSED CIRCUIT TELEVISION
COAX COAXIAL CABLE
COMM COMMUNICATION
COR CONTRACTING OFFICER REPRESENTATIVE
DC DOOR CONTACT SWITCH
DN DOWN
DO DOOR OPERATOR
DVC DIGITAL VOICE COMMAND
DVR DIGITAL VIDEO RECORDER
E EXISTING DEVICES
EEB EMERGENCY EXIT BUTTON
EL ELECTRICAL STRIKE
ETR EXISTING TO REMAIN
FO FIBER OPTIC
IT INFORMATION AND TECHNOLOGY ROOM
MATV MASTER ANTENNA TELEVISION
MDA MAIN DISTRIBUTION AREA
MM MULTI MODE FIBER
NAC NETWORK APPLIANCE CIRCUIT PANEL
N NEW DEVICES
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
NVR NETWORK VIDEO RECORDER
TECHNOLOGY ABBREVIATIONS LIST
OC ON CENTER
OIT OFFICE OF INFORMATION TECHNOLOGY
PACS PHYSICAL ACCESS CONTROL SYSTEM
PAMN PUBLIC ADDRESS AND MASS NOTIFICATION SYSTEM
PB PUSH BUTTON
PBB PRIMARY BONDING BUSBAR
PDU POWER DISTRIBUTION UNIT
POE POWER OVER ETHERNET
PR PAIR
RBB RACK BONDING BUSBAR
rPDU RACK POWER DISTRIBUTION UNIT
RX REQUEST TO EXIT
SBB SECONDARY BONDING BUSBAR
SEP SERVICE ENTRANCE PROTECTION
SLC SIGNALING LINE CIRCUIT
SM SINGLE MODE FIBER
TBB TELECOM BONDING BACKBONE
TEBC TELECOMMUNICATIONS EQUIPMENT BONDING
CONDUCTOR
TEL TELEPHONE
TGB TELECOM GROUND BUS BAR
TM TELEMONITORING
TMGB TELECOM MAIN GROUND BUS BAR
TP TWISTED PAIR
TR TELECOM ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
WM WIRE MANAGEMENT
WAP WIRELESS ACCESS POINT
WAO WORK AREA OUTLET
UL UNDERWRITERS LABORATORY
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
TECHNOLOGY GENERAL NOTES
1. PROVIDE COMMUNICATIONS DEVICES AND EQUIPMENT IN ACCORDANCE WITH THE CONTRACT DOCUMENTS, MANUFACTURER'S RECOMMENDED PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT, LATEST EDITION OF THE NATIONAL ELECTRICAL CODE, BICSI STANDARDS, AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES AND EQUIPMENT WHERE BUILDING CONSTRUCTION IS NOT SUITABLE FOR
DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP OR PROTECT ANNULAR SPACE AROUND PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILINGS, AND ROOF IN ACCORDANCE WITH REQUIREMENTS OF NFPA 70, UL LISTING
REQUIREMENT, SPECIFICATIONS, AND APPLICABLE BUILDING CODES.
4. PROVIDE CABLING THAT COMPLIES WITH THE LATEST EDITION OF TELECOMMUNICATIONS DISTRIBUTION METHOD
MANUAL AND ANSI/TIA/EIA PUBLICATIONS.
5. COMPLY WITH THE LATEST ANSI/TIA/EIA 758 AND 607 - GROUNDING AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS IN COMMERCIAL BUILDING.
6. COMPLY WITH THE LATEST ANSI/TIA-568-SET, COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD.
7. COMPLY WITH THE LATEST ANSI/TIA/EIA 569 - COMMERCIAL BUILDING STANDARD FOR TELECOMMUNICATIONS
PATHWAYS AND SPACES.
8. COMPLY WITH THE LATEST NFPA 70 NATIONAL ELECTRICAL CODE.
9. COMPLY WITH THE LATEST NFPA 99 HEALTHCARE FACILITIES CODE.
10. COMPLY WITH THE LATEST NFPA 101 LIFE SAFETY CODE.
11. COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
12. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES TO INDICATE A QUALITY STANDARD AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE COR WILL BE ACCEPTABLE. COMPLY WITH "BUY AMERICAN ACT".
13. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, BOXES, OUTLET, OR EQUIPMENT UNLESS NOTED
OTHERWISE.
14. PROVIDE RGS OR EMT CONDUIT UNLESS OTHERWISE NOTED.
15. PROVIDE MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT LABEL LISTED BY APPROVED THIRD PARTY TESTING
AGENCY.
16. NOTIFY COR REGARDING DISCREPANCY BETWEEN PLANS AND SPECIFICATIONS FOR CLARIFICATION. THE MORE
STRINGENT OF THE THEM SHALL TAKE PRECEDENCE.
17. PROVIDE TIA/EIA CAT 6A COPPER OUTLETS AND CONNECTORS.
18. ALL WORK AREA OUTLETS SHALL BE 8 PIN, CAT 6A KEYSTONE JACK WIRED PER T568B.
19. LABEL DEVICES IN ACCORDANCE WITH LATEST ANSI/TIA 606 AS WELL AS THE STANDARDS SET FORTH BY THE VA
HOSPITAL OIT.
20. PROVIDE A MINIMUM OF 12" CLEARANCE ABOVE THE CABLE TRAY IN ACCORDANCE WITH LATEST TIA/EIA 569.
21. VA WILL CONDUCT A WAP SURVEY AND PROVIDE THE SURVEY TO THE CONTRACTOR. INSTALL CABLING AND
EQUIPMENT IN ACCORDANCE WITH THE SURVEY. COORDINATE WITH COR/OIT.
22. ALL CABLING INSTALLED ABOVE CEILING SHALL BE PLENUM RATED.
23. MINIMUM CONDUIT SIZE TO BE USED IS 1-1/4" EMT.
24. WALL MOUNTED DEVICES PLACED IN TELECOM ROOM SHALL BE MOUNTED ON FIRE RETARDANT PLYWOOD.
25. PROVIDE OUTDOOR AND INDOOR CONDUITS, INNERDUCTS, TELECOM HANDHOLES, TELECOM MANHOLES, HANDHOLE COVERS, CABLING BOTH FIBER AND COPPER, SUPPORTS, TESTING, AND ALL RELATED MATERIALS FOR A COMPLETE
SYSTEM AS SHOWN HEREIN AND DESCRIBED IN THE SPECIFICATIONS.
26. PROVIDE CABLE TRAY, LADDER TRAY J-HOOKS, CONDUITS, JUNCTION BOXES, SUPPORTS, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, FLOOR SLEEVES, CORE DRILLING, CABLING (BOTH FIBER AND COPPER), JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, CHANNEL RACKS, VERTICAL AND HORIZONTAL WIRE MANAGEMENT, BONDING BUS BARS, RACK MOUNTED BONDING BUS, BONDING CABLING, BONDING TO THE GROUNDING SYSTEM, BONDING CABLE IN THE CABLE AND LADDER TRAY, POWER STRIPS, UPS'S, TESTING AND RELATED MATERIALS FOR A COMPLETE CABLING SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
27. PROVIDE J-HOOKS OR FLEXIBLE CONDUITS WHERE CABLE TRAY IS NOT SHOWN, OR IF THE PATH OF THE CABLE TRAY IS OBSTRUCTED. PROVIDE JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, AND COVER PLATES AS NEEDED OR WHERE REQUIRED BY CODE. LABEL AND SUPPORT J-HOOKS, CABLE TRAY, AND CONDUIT AS SHOWN
HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
28. PROVIDE 12 PORT, WALL MOUNTED, COPPER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, COPPER PATCH PANEL IN EACH NEW TR AND RUN 12 CAT 6A CABLE BETWEEN THESE TELECOM
ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.
29. PROVIDE 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN THE EXISTING TR/FACILITY ROOM AND ANOTHER 12 PORT, WALL MOUNTED, FIBER PATCH PANEL IN EACH NEW TR AND RUN 12 STRAND FIBER CABLE BETWEEN THESE TELECOM
ROOMS. TERMINATE AND TEST EACH CABLE. LABEL EACH PORT ON THE NEW PATCH PANELS.
30. PROVIDE MULTI-SENSOR PANORAMIC SECURITY SURVEILLANCE TELEVISION (SSTV) CAMERAS, DVRS/NVRS, STORAGE, SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, PATCH PANELS, PATCH CORDS, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL SSTV SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
CAMERAS SHALL MEET THE NATIONAL DEFENSE AUTHORIZATION ACT-NDAA.
31. PROVIDE CARD READERS, DOOR CONTROLLERS, TR KEYPADS FOR PHYSICAL ACCESS AND CONTROL SYSTEM (PACS), SOFTWARE, LICENSES, CONDUITS, JUNCTION BOXES, FIRE AND SMOKE RATED SLEEVE ASSEMBLIES, CABLING, COVER, JACKS, TERMINATIONS, COVER PLATES, LABELING, TESTING AND RELATED MATERIALS FOR A COMPLETE OPERATIONAL
PACS SYSTEM AS SHOWN HEREIN AND AS DESCRIBED IN THE SPECIFICATIONS.
32. CONTRACTOR IS RESPONSIBLE FOR PROVIDING RECORD/AS-BUILT DRAWINGS AS PART OF CLOSEOUT SUBMITTALS
SHOWING ALL NEW WORK AREA OUTLET LOCATIONS ON THE MOST UP-TO-DATE FLOOR PLAN.
33. PROVISION OF MULTI-SENSOR SSTV CAMERAS AS WELL AS ASSOCIATED NVR'S, STORAGE, SOFTWARE, AND LICENSES
SHALL BE COORDINATED WITH AVIGILON. CONTACT LOCAL AVIGILON REPRESENTATIVE.
34. PROVISION OF CARD READERS AND ASSOCIATED DOOR SECURITY HARDWARE AS WELL AS ASSOCIATED HEAD END EQUIPMENT SHALL BE COORDINATED WITH OPEN OPTIONS. CONTACT LOCAL OPEN SOURCE REPRESENTATIVE.
35. PROVIDE 6 CISCO C9K-PWR-CAB-AC-US POWER CORDS FOR CISCO CATALYST 9300 SWITCHES PER TR.
36. WHERE THERE ARE HARD LID CEILINGS, PROVIDE FLEXIBLE CONDUIT FROM THE WORK AREA OUTLET TO THE CABLE
TRAY.
37. COORDINATE DOOR HARDWARE WITH THE EXISTING ELECTRIC KEY SYSTEM EMPLOYED BY THE VA. ALL DOOR
SECURITY HARDWARE SHALL INTEGRATE WITH THE ELECTRIC KEY SYSTEM.
38. TEN (10) SWITCHES WILL BE PROVIDED TO THE SITE TO ACCOMMODATE TRANSITIONING TELECOMMUNICATIONS
ROOMS.
39. IT IS THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE AND INSTALL COPPER PATCH CABLES IN ALL TELECOMMUNICATIONS ROOMS. ONE COPPER PATCH CABLE IS REQUIRED TO SERVE EVERY WORK AREA OUTLET, WIRELESS ACCESS POINT, AND ALL OTHER CONNECTION POINTS SERVED BY OIT NETWORK SWITCHES. THE APPROXIMATE AMOUNT OF PATCH CABLES NEEDED IS 10,000 (VARYING LENGTHS OF 2, 4, AND 8 FEET) TO REACH FROM
THE SWITCH TO THE PATCH PANELS.
GENERAL TECHNOLOGY DEMOLITION AND REMODEL NOTES
A. ALL EXISTING CONDITIONS - INCLUDING EQUIPMENT, CABINETS, CABLE TRAY, DEVICES, AND CONDUIT - ARE BASED ON
THE BEST AVAILABLE INFORMATION AT THE TIME OF SURVEY AND VISUAL INSPECTION.
B. RETURN REMOVED MATERIAL DEEMED SALVAGEABLE BY THE COR. ALL OTHER MATERIAL SHALL BE REMOVED FROM THE PREMISES (E.G., PATCH PANELS, CABLES, COVER PLATES, PATCH CORDS, AND RELATED MATERIAL).
C. EXISTING CABLE TRAY SHALL REMAIN. REMOVE EXISTING CABLING SERVING WORK AREA OUTLETS (WAO). NO ABANDONED CABLING WILL BE ALLOWED TO REMAIN ABOVE THE CEILING. INSTALL NEW CABLE TRAY NEXT TO THE
EXISTING CABLE TRAY.
D. EXISTING CONDUIT AND SURFACE RACEWAY MAY BE REUSED FOR NEW WAO. COORDINATE LOCATION WITH THE COR.
E. EXISTING TR: ONCE ALL ACTIVE CONNECTIONS TO AN EXISTING TR HAVE BEEN REPLACED BY CONNECTIONS TERMINATED IN THE NEW TR - AND OIT HAS CONFIRMED THAT THERE ARE NO LONGER ANY ACTIVE CONNECTIONS FROM THE EXISTING TR - COORDINATE REMOVAL OF ALL VA OWNED NETWORK SWITCHES. REMOVE PATCH PANELS AND ALL ASSOCIATED CABLING. BID DEMOLITION AND DISPOSAL OF THE RACKS IN THE TR UNLESS THERE ARE REMAINING NON-NETWORK COMPONENTS WHICH SHALL REMAIN IN PLACE WITH THE UPS AND POWER SOURCE IN
TACT.
F. EXISTING TR IDENTIFIED TO BE RENOVATED: PROTECT NETWORK RACK, EQUIPMENT, AND CABLING FROM DAMAGE, DUST, AND DEBRIS. MAINTAIN EXISTING PHYSICAL SECURITY DURING RENOVATION. NOTIFY THE COR AND VA POLICE A
MINIMUM OF 14 DAYS PRIOR TO ANY PHYSICAL SECURITY OUTAGES.
1. CONTRACTOR TO REFER TO TELECOM ROOM PHASING NOTES, SHEETS A-001, FOR ADDITIONAL INFOMATION.
FIRE ALARM PULL STATION
SYMBOL HEIGHT DESCRIPTION
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERSEDE THOSE LISTED HERE.
F
F
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM SPEAKER AND STROBE
FIRE ALARM PHOTOELECTRIC SMOKE DETECTOR
42"-48"
90"
90"
90"
XX - CANDELA
XX - CANDELA
XX - WATTAGEF
S
F
S
SD CEILING
ACC ACCESSIBLE
ACLG ABOVE CEILING
A/E ARCHITECT/ENGINEER
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPRX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
BOD BASIS OF DESIGN
C CONDUIT
CAB CABINET
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICE
COR CONTRACTING OFFICER
REPRESENTATIVE
dB DECIBEL
DN DOWN
DVC DIGITAL VOICE COMMAND
E EXISTING DEVICES
ELEV ELEVATOR
ETR EXISTING TO REMAIN
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAGAP FIRE ALARM GRAPHIC
ANNUNCIATOR PANEL
FO FIBER OPTIC
J-BOX JUNCTION BOX
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MT MOUNT
N NEW DEVICES
NAC NETWORK APPLIANCE CIRCUIT
PANEL
NCA NETWORK CONTROL ANNUNCIATOR
NS NO SCALE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PIV POST INDICATING VALVE
PVC POLYVINYL CHLORIDE (CONDUIT)
QTY QUANTITY
R REMOVE AND REPLACE IN NEW
LOCATION
RCP REFLECTED CEILING PLAN
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
SC SURFACE CONDUIT
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
SPEC SPECIFICATION
SPKR SPEAKER
SR SURFACE RACEWAY
SS STAINLESS STEEL
STD STANDARD
SURF SURFACE MOUNTED
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
TYP TYPICAL
UL UNDERWRITER'S LABORATORY
UTP UNSHIELDED TWISTED PAIR
FIRE ALARM ABBREVIATIONS LIST
1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:
A. NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
B. NFPA 70 NATIONAL ELECTRICAL CODE.
C. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.
D. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.
E. NFPA 101 LIFE SAFETY CODE.
F. VA FIRE PROTECTION DESIGN MANUAL.
G. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.
2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).
3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.
4. BEFORE STARTING WORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.
6. CONTRACTOR TO ENSURE THAT ALL NEW FIRE ALARM SPEAKERS, TONES, AND STROBES ARE IN-SYNC WITH ALL ADJACENT AREAS BEYOND THE AREA OF WORK. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN
WORK AREA AND ADJACENT AREAS.
7. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.
8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE ALARM
DEVICES. COORDINATE WITH COR.
9. THE OPERABLE PART OF A MANUAL ACTUATED ALARM INITIATING DEVICE SHALL BE NOT LESS THAN 42" (1.07M) AND
NOT MORE THAN 48" (1.22M) FROM FINISH FLOOR.
10. FOR LOCATION (CORRIDOR, ROOM OR ADJACENT SPACE) WITH TWO OR MORE VISIBLE FIRE ALARM NOTIFICATION APPLIANCES WITHIN THE FIELD OF VIEW, PROGRAM VISIBLE TO FLASH IN SYNCHRONIZATION.
11. PROGRAM ALL NEW A/V APPLIANCES. COORDINATE ZONING WITH EXISTING FIRE ALARM AND LIFE SAFETY PLANS.
FIRE ALARM GENERAL NOTES
CHANNEL RACK FRAME WHERE
EQUIPMENT IS MOUNTED.
CABLE WATERFALL
ATTACHED TO THE
TOP OF THE
CHANNEL RACK.
REAR EQUIPMENT
RAIL AT THE TOP OF
THE RACK.
6" VERTICAL WIRE MANAGEMENT. THE REAR
OF THE WIRE MANAGEMENT MOUNTS TO THE
FRONT OF THE CHANNEL RACK. THE CABLE
WATERFALL DIRECTS CABLING INTO THE
VERTICAL WIRE MANAGEMENT FROM THE TOP.
CHANNEL RACK SYMBOL NOTES
Engineers Architects
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:1
:4
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts
\T R
R o o m
D e ta ils ls ta rn e s C
B U
M B
.r v t
TECHNOLOGY GENERAL NOTES,
SYMBOL LEGEND, AND
ABBREVIATIONS
2 107ADR
EHRM INFRASTRUCTURE
UPGRADES
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BLVD.
HOUSTON, TX 77030 JANUARY 14, 2025
BID DOCUMENTS
580-22-70021-313
JDM
000 ET002
CONDITIONAL NOTE
FIRE ALARM SYMBOL
E
CR
DC ES RX J
M
10 10
PANEL 'A' PANEL 'B'
ET5016
A-7,9,11
B-7,9,11
SBB
K
A-2
B-2
A-2
A-2 N
GFIB-2
B-2
A-2
B-2
W
A
B
A
B
A
A-1,3,5
B-1,3,5
A-13,15,17
B-13,15,17BA
6FIRE RATED PATHWAYS
A-4
A
AA
FIRE RATED PATHWAYS6
PANEL A
FIRE RATED
PATHWAYS
SSB
CABLE TRAY
RECEPTACLE NEMA 5-20R
MOTOR-RATED
SWITCH
17 17
"B" PANEL"A" PANEL
CABLE TRAY
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R SSB
DATA PORT
LIGHT SWITCH
RECEPTACLE
NEMA 5-20R
RECEPTACLE
NEMA 5-20R
"B" PANEL
SBB
NEC REQUIRED WORKING
CLEARANCE, 30" WIDE BY
36" DEEP BY 72" HIGH
17 17
16 16
RECEPTACLE NEMA 5-20R
Engineers Architects
# KEY NOTES:
Revisions: Date
Drawing Title
Approved
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/1
/2
:1
:4
P
M C
U s e rs
\l s ta rn e s \D o c u m e n ts
\T R
R o o m
D e ta ils ls ta rn e s C
B U
M B
.r v t
TYPICAL TELECOM ROOM DETAILS
3 107ADR
EHRM INFRASTRUCTURE
UPGRADES
MICHAEL E. DEBAKEY VAMC
2002 HOLCOMBE BLVD.
HOUSTON, TX 77030 JANUARY 14, 2025
BID DOCUMENTS
580-22-70021-313
JDM
000 ET501
1 ROOMS ARE COOLED WITH EITHER FAN COIL
UNITS (FCU) OR DUCTLESS MINI-SPLITS. FOR
FCUS, PROVIDE A 20A/1P CIRCUIT FROM
PANEL 'A' TO A MOTOR-RATED TOGGLE
SWITCH WITH A CONNECTION TO THE UNIT.
DUCTLESS MINI-SPLIT UNITS SHALL BE
POWERED FROM THEIR ASSOCIATED
OUTDOOR CONDENSING UNITS. PROVIDE A
CIRCUIT TO THE CONDENSING UNIT,
INCLUDING RACEWAYS AND CONDUCTORS
TO POWER THE INDOOR UNITS.
2 TELECOMMUNICATIONS CHANNEL RACK,
23.75" WIDE (19" RAILS) SQUARE HOLE
PATTERN, 30 INCHES DEEP (MINIMUM), 84
INCHES HIGH, 45RU, WHITE. PROVIDE
ORTRONICS (LEGRAND) MM2073038-W, OR
APPROVED EQUIVALENT. CONTRACTOR
SHALL COORDINATE ADDITIONAL DETAILS
INCLUDING BUT NOT LIMITED TO GROUNDING
AND BONDING DETAILS, DATA ELEVATIONS
AND POWER ELEVATIONS IN THE DRAWINGS.
3 VERTICAL CABLE MANAGEMENT CAGE WITH
DOOR, 6 INCHES WIDE, 84 INCHES HIGH,
45RU, WHITE. PROVIDE ORTRONICS
(LEGRAND) MM20VMD706-W, OR APPROVED
EQUIVALENT.
4 RACK POWER CONNECTION MOUNTED TO
THE CHANNEL STEEL ABOVE THE RACKS
MINIMUM 12" AWAY FROM CABLE TRAY. FOR
EACH RACK, PROVIDE L21-20R RECEPTACLE.
PROVIDE (4) 12 AWG AND (1) 12 AWG GND IN
3/4" CONDUIT. REFER TO RACK POWER
ELEVATION AND SCHEMATIC DIAGRAMS ON
SHEET 000 ET505.
5 SECONDARY BONDING BUSBAR.
TELECOMMUNICATIONS EQUIPMENT SHALL
BE BONDED ACCORDING TO THE
GROUNDING AND BONDING DETAILS. REFER
TO DETAILS 3 AND 4 ON SHEET 000 ET503
FOR MORE INFORMATION.
6 FIRE/SMOKE SLEEVE ASSEMBLIES. PROVIDE
UL LISTED ASSEMBLIES, STI EZ-PATH, SERIES
44 FIRE-RATED PATHWAY, OR APPROVED
EQUIVALENT. INSTALL SLEEVES ABOVE
DOOR HEADER AT AN ELEVATION
COORDINATED TO BE ABOVE THE EXISTING
CEILING HEIGHT IN THE ADJACENT
COORIDOR. REFER TO 400 SERIES ET
SHEETS FOR QUANTITIES.
7 PROVIDE NEW WIRE MESH TRAY AROUND
THE ROOM AND ABOVE THE CHANNEL
RACKS, WITH WATERFALL DROPOUTS INTO
EACH RACK, 90 DEGREE CORNERS AND ALL
RELATED FITTINGS. SEE WIRE MESH TRAY
DETAIL ON 000.ET504 FOR MORE INFO.
B.O.D.: CABLEOFIL CF105/600 AND CF150/600
SERIES OR EQUIVALENT.
8 RECEPTACLES, PROVIDE TWO RECEPTACLE
ON EACH WALL, AS SHOWN, ONE FED FROM
PANEL A THE OTHER FROM PANEL B.
9 FIRE RETARDANT PLYWOOD BACKBOARD.
SEE ARCHITECTURAL.
10 LIGHTING AND APPLIANCE PANELBOARDS.
PROVIDE PANELS MOUNTED ON CHANNEL
STEEL SUPPORTS. UNLESS NOTED
OTHERWISE ON THE 400 SERIES ET SHEETS,
PANEL 'A' SHALL BE FED FROM A SOURCE
WITH GENERATOR BACKUP, AND PANEL 'B'
SHALL BE FED FROM A NORMAL UTILITY
SOURCE.
11 PROVIDE JUNCTION BOX WITH EMERGENCY
POWER TO THE PACS DOOR CONTROLLER.
12 PROVIDE FIXED, MULTI SENSOR CAMERA
WITH 90 DEGREE FIELD OF VIEW AND
CONNECT TO EXISTING CAMERA SYSTEM.
LOCATION SHOULD BE COORDINATED WITH
THE CHANNEL RACK LAYOUT AND OIT.
13 PROVIDE CABLING FOR VA FURNISHED
WIRELESS ACCESS POINT.
14 PROVIDE RECEPTACLE NEAR DOOR, WITH
POWER EXTENDED FROM AN EXISTING
CONVENIENCE OUTLET CIRCUIT
ORIGINATING FROM A PANEL NOT IN THE
ROOM.
15 PROVIDE WALL PHONE OUTLET IN EVERY
TELECOM ROOM.
16 FIRE-RATED PATHWAY WILL GO UP INTO THE
INTERSTITIAL SPACE IN BUILDING 100.
PROVIDE UL LISTED ASSEMBLY WITH A T
RATING THAT IS A MINIMUM OF 1 HOUR. FOR
ALL OTHER BUILDINGS, THE FIRE RATED
PATHWAY WILL GO HORIZONTALLY INTO
ADJACENT SPACE ABOVE CEILINGS.
17 BASKET CABLE TRAY IS SHOWN OFFSET
FROM WALL FOR…
This is the start of the file's text. The full file is on GovTribe.