Attachment 1 - Troy Lock Electrical One-Line Riser Diagram.pdf
PDF 289 KB Posted
- Attached to
- Troy Lock Automatic Transfer Switch Replacement Federal contract opportunity
- Solicitation number
- W912DS25R0005
About this file
This document is a Solicitation for the Troy Lock Automatic Transfer Switch Replacement at the Albany Field Office in Troy, NY. The work includes removing and replacing the existing 208V, 400A, 3-phase, 4-wire, 35,000 AIC automatic transfer switch (ATS) with a new NEMA 3R rated ATS with a manual actuation handle. The contractor must also conduct a load test on the existing generator and functionally test the new ATS. The period of performance is 30 days after April 15, 2025, and the contractor must coordinate with the local utility, National Grid. The solicitation provides detailed requirements for site access, security, codes and standards, materials, and safety. No government resources will be provided. The solicitation package includes an electrical one-line diagram, ATS specifications, and an O&M manual for the existing ATS.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions and Government Responses for W912DS25R0005_Troy Lock Automatic Transfer Switch Replacement.pdf | ||
| W912DS25R0005 Amendment 1.pdf | ||
| Questions and Government Responses for W912DS25R0005_Troy Lock Automatic Transfer Switch Replacement.pdf | ||
| W912DS25R0005_Troy Lock Automatic Transfer Switch Photos at site.pdf | ||
| W912DS25R0005_Troy Lock Automatic Transfer Switch Replacement Solicitation.pdf | ||
| Attachment 3 - ASCO Series 300 O M Manual.pdf | ||
| Attachment 4 - Generator Data plate.jpg | JPG image | |
| Attachment 2 - ATS Specifications.pdf | ||
| Attachment 5 - Power System Analysis.pdf | ||
| W912DS25R0005_Troy Lock Automatic Transfer Switch Replacement Solicitation.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(3) 50KVA POLE-
MOUNTED XFMRS
TCC 1105
ETCC 2035
TCC 2035
ETCC 2025
TCC 2025
TCC 2095
TCC 1035
TCC 1025
TCC 2080
CU
CU
CU
CU
CUCUCU
CU
CU
CU
CU
CU
CU
CU
AL
AL
CU
CU
CU
CU
CU
CU
CU
CU
CUCU
AL
CU
ID: CBL-2056
Length: 120 ft # Cond. / Phase: 1 Cable Size: 4 AWG/kcmil
ID: 2056 HEATER-2
Nominal: 0.208 kV
ID: 2095 SAND HOUSE
Nominal: 0.208 kV
ID: 2020-06 EMER SH-2 FDR
MFR Name: Siemens Model: ED2 Trip Type: Thermal Magnetic Size: 70 3 Pole
ID: 2065 EMER SH-2
Nominal: 0.208 kV
100A MLO
ID: 2020-05 HEATER-2 FDR
MFR Name: Siemens Model: ED2 Trip Type: Thermal Magnetic Size: 70 3 Pole
ID: CBL-2065
Length: 900 ft # Cond. / Phase: 1 Cable Size: 3 AWG/kcmil
ID: 2020 MDP-2
Nominal: 0.208 kV
ID: CBL-2095
Length: 375 ft # Cond. / Phase: 1 Cable Size: 6 AWG/kcmil
ID: CBL-2003
Length: 325 ft # Cond. / Phase: 1 Cable Size: 750 AWG/kcmil
ID: CBL-2015-2
Length: 40 ft # Cond. / Phase: 1 Cable Size: 4/0 AWG/kcmil
ID: CBL-2015-1
Length: 10 ft # Cond. / Phase: 1 Cable Size: 4/0 AWG/kcmil
ID: 2000 ATS-1
Nominal: 0.208 kV
ID: 2010-02 TX DISC
Manufacturer: Cutler-Hammer Model: DSL-206 Size: 300A
ID: CBL-2045
Length: 25 ft # Cond. / Phase: 1 Cable Size: 3 AWG/kcmil
ID: 2020-01 MDP-2 MAIN
MFR Name: Cutler-Hammer Model: KD Trip Type: Thermal Magnetic Size: 300 3 Pole
ID: 2020-04 LOCK SYS FDR
MFR Name: Siemens Model: ED2 Trip Type: Thermal Magnetic Size: 100 3 Pole
ID: TX
Rating: 75 kVA Pri: 0.208 kV Sec: 0.208 kV %Z: 4.88 % ANSI Pos. X/R: 1.86 Inrush Multiplier: 11.7
ID: 2010 TX DISC
Nominal: 0.208 kV
ID: 2045 LOCK SYS
Nominal: 0.208 kV
100A MLO
ID: 2003-01 MDP-1 MB
MFR Name: Siemens Model: JXD2-A Trip Type: Thermal Magnetic Size: 400 3 Pole
ID: CBL-2010
Length: 40 ft # Cond. / Phase: 1 Cable Size: 4/0 AWG/kcmil
ID: MDP LMP MTR
QTY: 1 HP: 20 HP
PF: 80 %
Xsc 1/2 cyc: 27.833 % Eff: 93.25 %
ID: CBL-1040
Length: 5 ft # Cond. / Phase: 1 Cable Size: 1/0 AWG/kcmil
ID: 1040 POWER PNL DSC
Nominal: 0.208 kV
ID: CBL-1005
Length: 20 ft # Cond. / Phase: 1 Cable Size: 500 AWG/kcmil
ID: CBL-1050
Length: 10 ft # Cond. / Phase: 1 Cable Size: 3/0 AWG/kcmil
ID: 1050 LP-1
Nominal: 0.208 kV
ID: CBL-1045
Length: 100 ft # Cond. / Phase: 1 Cable Size: 1/0 AWG/kcmil
ID: 1005-01 MDP MAIN
Trip: 400
ID: 1045 POWER PNL
Nominal: 0.208 kV
ID: 1005 MDP
Nominal: 0.208 kV
ID: 1040-01 POWER PNL FUSE
Manufacturer: Bussmann Model: FRN-R (10/08) Size: 100A
ID: 1000-02 MAIN FUSE
Manufacturer: Westinghouse Model: DSL-206 Size: 250A
ID: BLDG-2 TROUGH
Nominal: 0.208 kV
ID: CBL-1000
Length: 135 ft # Cond. / Phase: 1 Cable Size: 500 AWG/kcmil
ID: 1000 MAIN DSC
Nominal: 0.208 kV
ID: 1005-04 LP-1 FDR
Trip: 200
ID: 2035-00 NW STAND MAIN
MFR Name: Siemens Model: ED2 Trip Type: Thermal Magnetic Size: 100 3 Pole
ID: 2020-02 SUMP PUMP FDR
MFR Name: Siemens Model: FXD6-A Trip Type: Thermal Magnetic Size: 175 3 Pole
ID: 2020-03 NW XFMR FDR
MFR Name: Siemens Model: ED2 Trip Type: Thermal Magnetic Size: 100 3 Pole
ID: NW XFMR
Rating: 30 kVA Pri: 0.24 kV Sec: 0.208 kV %Z: 2.7 % ANSI Pos. X/R: 1.69 Inrush Multiplier: 12
ID: 2035 NW STAND
Nominal: 0.208 kV
ID: CBL-2035-2
Length: 10 ft # Cond. / Phase: 1 Cable Size: 1/0 AWG/kcmil
ID: CBL-2026
Length: 60 ft # Cond. / Phase: 1 Cable Size: 2/0 AWG/kcmil
ID: CBL-2035-1
Length: 900 ft # Cond. / Phase: 1 Cable Size: 3 AWG/kcmil
ID: SUMP PUMP
QTY: 1 HP: 40 HP
PF: 80 %
Xsc 1/2 cyc: 27.833 % Eff: 93.25 %
ID: CBL-1105
Length: 35 ft # Cond. / Phase: 1 Cable Size: 2 AWG/kcmil
ID: 1105-01 SHACK PNL MB
MFR Name: Square-D Model: QO-VH Trip Type: Thermal Magnetic Size: 100 2 Pole
ID: 1105-02 SHACK PNL LGST
ID: 1100-02 SHACK PNL FDR
MFR Name: Square-D Model: QOM1-VH Trip Type: Thermal Magnetic Size: 100 2 Pole
ID: 1100 MB PNL
Nominal: 0.208 kV
ID: UTILITY XFMR-1
Rating: 150 kVA Pri: 4.16 kV Sec: 0.208 kV %Z: 3.75 % Tolerance: 60 % ANSI Pos. X/R: 3.5 Inrush Multiplier: 12
ID: 1105 SHACK PNL
Nominal: 0.208 kV
ID: 1100-01 MB PNL MB
MFR Name: Cutler-Hammer Model: CSR Trip Type: Thermal Magnetic Size: 200 2 Pole
ID: CBL-1100
Length: 60 ft # Cond. / Phase: 1 Cable Size: 4/0 AWG/kcmil
ID: CBL-1015
Length: 240 ft # Cond. / Phase: 1 Cable Size: 500 AWG/kcmil
ID: 1025 LP-2
Nominal: 0.208 kV
ID: 1035 LP-3
Nominal: 0.208 kV
ID: 1020 LP-2 DSC
Nominal: 0.208 kV
ID: 1030 LP-3 DSC
Nominal: 0.208 kV
ID: CBL-1030
Length: 5 ft # Cond. / Phase: 1 Cable Size: 2 AWG/kcmil
ID: 1005-02 SUB PNL FDR
ID: 1030-01 LP-3 FUSE
Manufacturer: Bussmann Model: FRN-R (10/08) Size: 100A
ID: 1010 SUB PNL
Nominal: 0.208 kV
ID: CBL-1010
Length: 10 ft # Cond. / Phase: 1 Cable Size: 4 AWG/kcmil
ID: CBL-1035
Length: 100 ft # Cond. / Phase: 1 Cable Size: 2 AWG/kcmil
ID: 1005-03 BLDG-2 FDR
Trip: 200
ID: CBL-1020
Length: 5 ft # Cond. / Phase: 1 Cable Size: 3/0 AWG/kcmil
ID: 1020-01 LP-2 FUSE
Manufacturer: Bussmann Model: FRN-R (10/08) Size: 150A
ID: CBL-1025
Length: 55 ft # Cond. / Phase: 1 Cable Size: 3/0 AWG/kcmil
ID: 2090 EMER SH-1
Nominal: 0.208 kV
ID: CBL-2080
Length: 15 ft # Cond. / Phase: 1 Cable Size: 1/0 AWG/kcmil
ID: 2080 LH HOUSE PNL
Nominal: 0.208 kV
150A MLO
ID: 2003-02 LH HOUSE PNL FDR
MFR Name: Siemens Model: FD6-A Trip Type: Thermal Magnetic Size: 150 3 Pole
ID: 2003 MDP-1
Nominal: 0.208 kV
ID: 2090-01 SAND HOUSE FDR
MFR Name: Cutler-Hammer Model: BA Trip Type: Thermal Magnetic Size: 60 2 Pole
ID: CBL-2090
Length: 900 ft # Cond. / Phase: 1 Cable Size: 400 AWG/kcmil
ID: 2003-03 EMER SH-1 FDR
MFR Name: Cutler-Hammer Model: KD Trip Type: Thermal Magnetic Size: 150 3 Pole
ID: 2090-00 EMER SH-1 MAIN
MFR Name: Cutler-Hammer Model: HKD Trip Type: Thermal Magnetic Size: 150 3 Pole
ID: UTILITY MAX
kV: 4.16 kV kAsc 3p: 50 kA 3p MVAsc: 360.267 MVA Pos X/R: 12
ID: 3000-02 ATS-1 EFDR
MFR Name: Square-D Model: LHL Trip Type: Thermal Magnetic Size: 400 3 Pole
ID: 2000-01 ATS-1 MB
MFR Name: Square-D Model: LH Trip Type: Thermal Magnetic Size: 400 3 Pole
ID: CBL-2000E
Length: 100 ft # Cond. / Phase: 1 Cable Size: 750 AWG/kcmil
ID: UTILITY ACT
kV: 4.16 kV kAsc 3p: 3.53 kA 3p MVAsc: 25.42 MVA Pos X/R: 1.78
ID: 3000 GEN-1
Nominal: 0.208 kV
ID: GEN-1
Power: 150 kW Nominal: 0.208 kV Xd'': 7.8 % X/R: 5.65
ID: CBL-2000N
Length: 95 ft # Cond. / Phase: 1 Cable Size: 500 AWG/kcmil
ID: ATS-1