Attachment 1 - Salient Characteristics.docx
DOCX document 42 KB Posted
- Attached to
- Refrigerant Recovery System Federal contract opportunity
- Solicitation number
- FA466124Q0099
About this file
This document is the Attachment 1 - Salient Characteristics for a federal contract opportunity. It specifies the requirements for a refrigerant reclaimer and related equipment, including a high capacity 1200 cfm air-cooled condenser with a minimum 120-gallon tank, tools, and a mini purge unit. The equipment must meet ASME standard regulations and performance may exceed minimum requirements. The related federal contract opportunity is for a Refrigerant Recovery System to be used for maintaining aerospace ground equipment at Dyess AFB. The solicitation is from the Department of the Air Force Global Strike Command and requires the salient characteristics described in this attachment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 4. Attachment 4. Questions Document.docx | DOCX document | |
| 4. Attachment 1 - Salient Characteristics.docx | DOCX document | |
| 4. 1. COMBO Refrigerant Recovery System (Amend 3).docx | DOCX document | |
| 3. Attachment 4. Questions Document.docx | DOCX document | |
| 3. 1. COMBO Refrigerant Recovery System (Amend 2).rtf | RTF text file | |
| 3. Attachment 1 - Salient Characteristics.docx | DOCX document | |
| COMBO Refrigerant Recovery System (Mod 1).rtf | RTF text file | |
| COMBO Refrigerant Recovery System.rtf | RTF text file | |
| Attachment 3 - FA466124Q0099 FAR 52.212-5.docx | DOCX document | |
| Attachment 2 - FA466124Q0099 FAR Provisions and Clauses.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications for refrigerant reclaimer and related equipment.
1. The Contractor shall provide one (1 each) Recovery/Recycle/Reclaim high pressure refrigerant unit for the recovery, compatible with R134a, R410A and other High Pressure Refrigerants. System must include a min 120 gallon tank, tools, and mini purge unit. All the following items must meet American Society of Mechanics (ASME) standard regulation requirements. Performance may exceed any minimum requirement.
ITEM
NUMBER
| Description |
| QUANTITY |
| UNIT |
| 0001 |
| High capacity 1200 cfm air cooled condenser w/attachments |
Recycle/recovery unit 230V/60HZ/3Ph/3HP with a minimum 120 gallon tank, To include the following Min /max specifications:
Push/Pull Rates (R22) 81-lbs/min Vapor Rates (R22) 2.14-lbs/min Float Connection 3-pin BH Connections 1/2” flare Low Pressure Switch 15” Hg Liquid and Vapor ports: 1/2” threaded connect
Quantity for Tool/Attachments QTY 2 – 48 cubic inch drier core QTY 1 – 80% Tank Float Cable QTY 1 – 10 ft. 1/2” hose with isolation valves QTY 2 – 20 ft. 1/2” hoses with isolation valves QTY 1 – 50’ power cable QTY 2 – 1/2 to 5/8 adapters QTY 2 – 5/8 to 3/4 Adapters
| 1 |
| EA |
| 0002 |
| Tank Scale |
For use with all the 120, 250 and 500 Gallon Must be attached in line to the tank (not a separate unit)
| 1 |
| EA |
| 0003 |
| Portable Refrigerant Purge Unit |
Discharge efficiency within +/- .02 of 0.08 lb-refg/lb non-condensibles
| 1 |
| EA |