Attachment 1 - Building 19 Drawings.pdf
PDF 11 MB Posted
- Solicitation number
- SP470325B0002
- Issued by
-
Defense Logistics Agency
About this file
This file contains 45 pages of technical drawings for the Building 19 partial demolition project at the Defense Supply Center Richmond (DSCR) facility located at 6090 Strathmore Road in Richmond, VA. The drawings include architectural, civil, structural, mechanical, electrical, fire alarm, and telecommunications demolition and new work plans.
The drawings detail the demolition scope for Building 19, which includes removing portions of the building while maintaining and protecting the remaining structure that will stay in place. Key elements include demolition of concrete slabs, CMU walls, roofing, utilities and building systems within the demolition area; relocation of emergency fuel pump shut-off controls; reworking of electrical services; installation of new CMU infill walls; and protection of adjacent facilities and utilities that are to remain. The drawings provide detailed specifications for new mechanical systems including split system heat pumps, plumbing modifications, electrical work, and fire alarm system modifications. The work requires careful phasing and coordination to maintain operation of critical systems serving the remaining building areas and adjacent facilities during construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Abstract of Offers DSCR B19 Demo.pdf | ||
| Attachment 7 - Questions and Answers.xlsx | XLSX spreadsheet | |
| DoD SAFE-Au83gAsYCbgPPCHQ.zip | ZIP file | |
| DoD SAFE-Dhe7bWsjTjGVba2T.zip | ZIP file | |
| Site Visit Attendance.pdf | ||
| Attachment 6 - Bldg. 19 Asbestos Survey.xlsx | XLSX spreadsheet | |
| Attachment 5 - B19 Location.pdf | ||
| SF30_SP470325B0002.PDF | ||
| Attachment 4 - Continuation Page.pdf | ||
| Attachment 3 - Wage Determination.pdf | ||
| Attachment 2 - Building 19 Specifications.pdf | ||
| Attachment 4 - Continuation Page.pdf | ||
| SF1442_SP470325B0002.pdf |
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT LOCATION
PROJECT LOCATION
BLDG. 19
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
DLA INSTALLATION MANAGEMENT BLDG 19 DEMOLITION
DEFENSE LOGISTICS AGENCY
6090 STRATHMORE ROAD
RICHMOND VA, 23297
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
R. WHITE
K. LE
C. HABY
J. JANOTA
J. CORONADO
1 2 3 4 5
D
C
B
A
6090 Strathmore Road Richmond, VA 23237
DSCR BLDG 19 DEMOLITION
IFC SUBMITTAL
JW
KH
31 JULY 2024
10356006
G-001
COVER SHEET
DSCR BUILDING 19 DEMOLITION
31 JULY 2024
NTSA2
VICINITY MAP
NTSB4
LOCATION MAP
TRUE NORTH
H ROAD
3RD STREET
L R
O A
D
G R
O A
D
J ROAD
H ROAD
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
R. WHITE
K. LE
C. HABY
J. JANOTA
J. CORONADO
1 2 3 4 5
D
C
B
A
JW
KH
31 JULY 2024
10356006
G-002
SHEET INDEX
DSCR BUILDING 19 DEMOLITION
31 JULY 2024
SHEET LIST
SHEET NUMBER SHEET NAME
65%
05/13/2024 95%
06/18/2024 100%
07/31/2024
GENERAL
G-001 COVER SHEET X
G-002 SHEET INDEX X
G-003 GENERAL NOTES, ABBREVIATIONS X
G-004 CODE ANALYSIS X
G-101 LIFE SAFETY PLAN X
CIVIL
C-001 CIVIL ABBREVIATIONS, NOTES, AND LEGEND X
C-002 EXISTING CONDITIONS AND DEMOLITION PLAN X
C-003 SITE AND EROSION CONTROL PLAN X
C-004 CIVIL SITE DETAILS X
STRUCTURAL
S-001 GENERAL STRUCTURAL NOTES X
S-002 TYPICAL CONCRETE DETAILS 1 X
S-003 TYPICAL CONCRETE DETAILS 2 X
S-004 TYPICAL CMU DETAILS 1 X
SD101 OVERALL FIRST FLOOR FRAMING DEMOLITION PLAN X
SD101A PARTIAL FIRST FLOOR FRAMING DEMOLITION PLAN X
SD104 OVERALL ROOF FRAMING DEMOLITION PLAN X
SD104A PARTIAL ROOF FRAMING DEMOLITION PLAN X
SD101B PARTIAL FIRST FLOOR FRAMING DEMOLITION PLAN X
SD104B PARTIAL ROOF FRAMING DEMOLITION PLAN X
S-101 FIRST FLOOR FRAMING PLAN X
S-501 TYPICAL STRUCTURAL DETAILS X
ARCHITECTURAL
AD101 FIRST FLOOR DEMO PLAN X
AD104 ROOF PLAN DEMOLITION X
A-101 FIRST FLOOR PLAN X
A-104 ROOF PLAN X
A-310 WALL SECTIONS X
FIRE PROTECTION
F-001 FIRE ALARM GENERAL NOTES X
FD101 FIRE ALARM AND MASS NOTIFICATION PLAN - DEMOLITION X
FA101 FIRE ALARM AND MASS NOTIFICATION PLAN - NEW WORK X
FA501 FIRE ALARM AND MASS NOTIFICATION DETAILS X
FA601 FIRE ALARM AND MASS NOTIFICATION MATRIX X
MECHANICAL
M-001 MECHANICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS X
M-101 MECHANICAL AND PLUMBING PLAN X
M-501 HVAC AND PLUMBING DETAILS I X
M-502 HVAC AND PLUMBING DETAILS II X
M-601 HVAC SCHEDULES AND PLUMBING MATERIAL LIST X
ELECTRICAL
E-100 ELECTRICAL SYMBOLS AND LEGEND X
ED101 ELECTRICAL PLAN - DEMOLITION X
ED601 ELECTRICAL ONE-LINE DIAGRAMS - DEMOLITION X
E-101 ELECTRICAL PLAN - NEW WORK X
E-501 ELECTRICAL DETAILS X
E-601 ELECTRICAL ONE-LINE DIAGRAMS AND PANEL SCHEDULES X
ES101 ELECTRICAL SITE PLAN X
TELECOMMUNICATIONS
TD101 TELECOMMUNICATIONS DEMO PLAN X
DRAWING ABBREVIATIONS
INDEX OF DRAWINGS
STRUCTURAL ABBREVIATIONS
NUMBERING SYSTEM:
XX100
DISCIPLINE:
C - CIVIL
F - FIREPROTECTION
A - ARCHITECTURE
M - MECHANICAL
E - ELECTRICAL
P - PLUMBING
S - STRUCTURAL
T - TELECOMMUNICATIONS
DISCIPLINE MODIFIER
ANNOTATION CALLOUTS/DRAWING SYMBOLS
STRUCTURAL ABBREVIATIONS
A ---------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AW ARCHITECTURAL WOODWORK
AWT ACOUSTICAL WALL TREATMENT
B ---------------------
B LABEL CLASS B DOOR
BALC BALCONY
BB BASEBOARD
BC BOOKCASE
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE
MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BUILDING PAPER
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER) BOARD
CD CONSTRUCTION DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR
FURNISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HTCEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE
COORDCOORDINATE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE BOARD
(INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GREXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAS BD FASCIA BOARD
FC BRKFACE BRICK
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLRFINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
FRTW FIRE RETARDANT TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED
CONTRACTOR INSTALLED
GFGI GOVERNMENT INSTALLED
GOVERNMENT INSTALLED
GFRG GLASS-FIBER-REINFORCED GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GUT GUTTER
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H ---------------------
HB HOSE BIBB
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR
(FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HORIZ HORIZONTAL
HT HEIGHT
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WATERPROOFING
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTI
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER AND
RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REC ROOM RECREATION ROOM
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV ROOF VENT
RVL REVEAL
REFER TO A/E/C CAD STANDARD FOR
SHEET NUMBERINGSTANDARDS
REVISION
TAG
NORTH ARROW w/
TRUE NORTH
INDICATION
ROOM TAG
ELEVATION NUMBER
SECTION
EXTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
LEVEL NAME
SHEET NUMBER
SHEET NUMBER
SHEET NUMBER
SHEET KEYNOTE
INTERIOR ELEVATION
SHEET NUMBER
S --------------------
SB SPLASH BLOCK
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHT MTL FLASH SHEET METAL
(FLASHING)
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SKLT SKYLIGHT
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STD STANDARD
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STOR STORAGE
STR STRINGERS
STRB/HRN STROBE/HORN
SUB FL SUBFLOOR
SV SHEET VINYL
SW SIDEWALK
T --------------------
T TREAD
T/S TUB/SHOWER
TC TERRA COTTA
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TFF TOP OF FINISH FLOOR
THK THICKNESS
TK BD TACKBOARD
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TRANS TRANSOM
TRTD TREATED
TV TELEVISION
SHEET NUMBER WITHIN SERIES
A201
A204
A301
A401
ROOM
100'
LEVEL 01
100'
A
PLAN NORTH
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
R. WHITE
K. LE
C. HABY
J. JANOTA
J. CORONADO
1 2 3 4 5
D
C
B
A
JW
BK
31 JULY 2024
10356006
G-003
GENERAL NOTES, ABBREVIATIONS
DSCR BUILDING 19 DEMOLITION
31 JULY 2024
STRUCTURAL ABBREVIATIONS
ABBREVIATION ABBREVIATION NAME
# NUMBER
& AND
= EQUAL, EQUALS
@ AT
A/C AIR CONDITIONING
AB ANCHOR BOLT
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
AFF ABOVE FINISEHD FLOOR
AH, AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
APA AMERICAN PLYWOOD ASSOCIATION
APPROX APPROXIMATELY
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AT/FP ANTI-TERRORISM/ FORCE PROTECTION
AWS AMERICAN WELDING SOCIETY
BET BETWEEN
BLW BELOW
BM BEAM
BN BOUNDARY NAIL
BOF BOTTOM OF FOOTING
BOT BOTTOM
BRG BEARING
C CHANNEL
CE CARBON EQUIVALENT
CENT CENTERED
CFMF COLD-FORMED METAL FRAMING
CFS COLD-FORMED STEEL
CIP CAST IN PLACE
CJ CONTROL JOINT/CEILING JOIST
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
COND CONDITION
CONN CONNECT, CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CORNER
CWB CAPILLARY WATERBARRIER
D DEEP, DEPTH
DEG DEGREE
DEM DEMOLISH, DEMOLITION
DEP DEPRESSED
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DL DEADLOAD
DO DITTO
DT DRAG TRUSS
DWG(S) DRAWINGS
DWL DOWEL
EA EACH
EF EACHFACE
ELEC ELECTRICAL
ELEV ELEVATION
EN EDGE NAIL
EQN EQUATION
EQUIP EQUIPMENT
ES EACH SIDE
EW EACH WAY
EXIST EXISTING
EXT EXTERNAL, EXTERIOR
FF FAR FACE
FFE FINISH FLOOR ELEVATION
FG FINISH GRADE
FJ FLOOR JOIST
FMG FRAMING
FN FIELD NAIL
FND FOUNDATION
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
FS FAR SIDE
FT, ' FOOT
FTG FOOTING
Fy YIELD STRESS
GA GAUGE
GLB GLUED LAMINATED BEAM
GT GIRDER TRUSS
GUSS GUSSET
GYP BD GYPSUM BOARD
HD HOLD DOWN
HDR HEADER
HGR HANGER
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HT HEIGHT
HVAC HEATNG/ VENTILATING/ AIR CONDITIONING
I MOMENT OF INERTIA
IBC INTERNATIONAL BUILDING CODE
ICF INSULATED CONCRETE FORM
ID INSIDE DIAMETER
IN, " INCH
INCL INCLUDE
STRUCTURAL ABBREVIATIONS
ABBREVIATION ABBREVIATION NAME
INFO INFORMATION
INS INSULATED, INSULATION
JST JOIST
K, KIPS THOUSAND POUNDS
L LENGTH, ANGLE
LB POUND
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LOC LOCATE, LOCATION
LONG LONGITUDINAL
LP LOW POINT
LW LIGHT WEIGHT
MAS MASONRY
MB MACHINE BOLT
MBR MEMBER
MECH MECHANICAL
MED MEDIUM
MEZZ MEZZANINE
MF MOMENT FRAM
MFG MANUFACTURING
MIN MINIMUM
MO MASONRY OPENING
MOD MODIFY, MODIFIED
MRF MANUFACTURER
NF NEAR FACE
NOM NOMINAL
NS NEAR SIDE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OPPOSITE HAND, OVERHEAD
OWSJ OPEN WEB STEEL JOIST
P/C PIN CONNECTED
PAR PARALLEL
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PEN PENETRATION
PFJ PERIMETER FELT JOINT
PL PLATE
PLYWD PLYWOOD
PNL PANEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PRESSURE TREATED, POINT, PRETENSIONED
REINF REINFORCING, REINFORCED
REQ REQUIRED
RET RETURN, RETAINING
REV REVISION, REVISED
RF ROOF
RFT RAFTERS
RPM REVOLUTIONS PR MINUTE
RS ROUGH SAWN
RT ROOF TRUSS
S SECTION MODULUS
SC SLIP CRITICAL
SCBRW SEGMENTAL CONCRETE BLOCK RETAINING WALL
SCHED SCHEDULE
SDI STEEL DECK INSTITUTE
SECT SECTION
SEIS SEISMIC
SEP SEPARATION
SHT SHEET
SIM SIMILAR
SJI STEEL JOIST INSTITUTE
SMS SHEET METAL SCREW
SPEC(S) SPECIFICATION(S)
SPRT SUPPORT
SQ SQUARE
SS STAINLESS STEEL
ST SNUG TIGHT
STD STANDARD
STIF/STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL, STRUCTURE
SUSP SUSPENDED
SYM SYMMETRICAL
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TGB TOP OF GRADE BEAM
THK THICK, THICKNESS
TL TOTAL LOAD
TN TOE NAIL
TOB TOP OF BEAM
TOC TOP OF CONCRETE
TOF TOP OF FOOTING
TOS TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
UFC UNITED FACILITES CRITERIA
UNO UNLESS NOTED OTHERWISE
UON UNLESS OTHERWISE NOTED
VB VAPOR BARRIER
VERT VERTICAL
W WIDTH, WEST, WIDE FLANGE
w/ WITH
WF WIDE FLANGE
WPT WORKING POINT
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
x BY, TIMES
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond VA, 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
R. WHITE
K. LE
C. HABY
J. JANOTA
J. CORONADO
D
C
B
A
1 2 3 4 5
RM
RD
31 JULY 2024
10356006
G-004
CODE ANALYSIS
BLDG 19 DEMOLITION
31 JULY 2024
• THERE WILL BE NO ALTERATION TO THE EXISTING FIRE HYDRANT PLACMENT AND COVERGE AS PART OF THE OF THIS PROJECT'S SCPOPE OF WORK.
FIRE HYDRANT PLACEMENT AND COVERAGE (SEE CODE COMPLIANCE SITE PLAN)
• THERE WILL BE NO ALTERATION TO THE EXISTING SERVICE MAINS AND LATERALS AS PART OF THE OF THIS PROJECT'S SCPOPE OF WORK.
SERVICE MAINS AND LATERALS
• FIRE FLOW IS INDEPENDENT OF SPRINKLER SYSTEM DEMAND. UFC -600-01 § 9-2.1
• FIRE FLOW FOR SPRINKLERED FACILITIES MUST BE A MINIMUM OF 1,000 GPM AT 20 PSI. UFC -600-01 § 9-2.1
• THERE IS NO EXTERIOR RENOVATION AS PART OF THIS SCOPE OF WORK. THE BUILDING'S FIRE FLOW WILL NOT BE ALTURED.
FIRE FLOW FOR FACILITIES
• THERE IS NO EXTERIOR RENOVATION AS PART OF THIS SCOPE OF WORK.
FIRE DEPARTMENT VEHICLE ACCESS
USE UFC 3-600-01 IN LIEU OF IBC CHAPTER 9. UFC 1-200-01 § 2-9
FIRE PROTECTION SYSTEMS:
NEW BUSINESS A OR B A OR B A,B, OR C CLASS I OR II
EXITS
EXIT ACCESS CORRIDORS OTHER SPACES
INTERIOR FINISH
FLOOR
GROUP
WITH SPRINKLER SYSTEM
INTERIOR WALL, CEILING, AND FLOOR FINISHES: NFPA 101 CHAPTER 10 TABLE A.10.2.2
SPRINKLER PROTECTION IS PROVIDED.
HAZARD GREATER THAN THAT NORMAL TO THE GENERAL OCCUPANCY WHERE AUTOMATIC
• A SMOKE PARTITON WILL BE PROVIDED TO SEPARATE AN AREA HAVING A DEGREE OF NFPA 101 § 8,7,1,2 (1), 38.3.2.1, PROTECTION FROM HAZARDS - APPLIES TO JANITORIAL CLOSETS (SEE LIFE SAFETY PLAN)
• THERE IS NO EXTERIOR RENOVATION AS PART OF THIS SCOPE OF WORK.
FIRE WALL FOR BUILDING SEPARATION
SPECIFICALLY REFERENCE IBC CHAPTER 7.
CONFORM TO THE REQUIRMENTS OF NFPA 101 CHAPTER 8, EXCEPT WHERE IBC CHAPTERS 5 AND 6 UFC 3-600-01 § 7-1
IBC CHAPTER 7 AND UFC 3-600-01 APPLY. UFC 1-200-01 § 2-7
FIRE AND SMOKE PROTECTION FEATURES:
NOTE 1: FIRE RATING MAYBE INCREASED DUE TO OTHER CRITERIA SUCH AS FIRE AREA SEPARATION.
• ROOF CONSTRUCTION (INCLUDING SUPPORTING BEAMS AND JOISTS): 0 HOUR
• FLOOR CONSTRUCTION (INCLUDING SUPPORTING BEAMS AND JOISTS): 0 HOUR
• NON-BEARING WALLS & PARTITIONS - INTERIOR: 0 HOUR (NOTE 1)
• NON-BEARING WALLS - EXTERIOR SEPARATION DISTANCE >30 FT: 0 HOUR
• BEARING WALLS - INTERIOR: 0 HOUR
• BEARING WALLS - EXTERIOR SEPARATION DISTANCE >30 FT: 0 HOUR
• STRUCTURAL FRAME (INCLUDING COLUMNS, GIRDERS, AND TRUSSES): 0 HOUR
IBC 601 & TABLE 602 ALL ALLOWABLE COMBUSTIBLE
MATERIALS AS DEFINED IN SECTION 603
REQUIRED STRUCTURAL ELEMENTS:
• TYPE IIB CONSTRUCTION (IBC) - (000) PER NFPA 220 IBC § 602 & TABLE 601
IBC CHAPTER 6 AND UFC 3-600-01 APPLY. UFC 1-200-01 § 2-6
TYPES OF CONSTRUCTION:
• ACTUAL BUILDING HEIGHT AND STORIES: 15 FT 0 IN AND ONE (1) STORIES IBC § 502 BUILDING HEIGHT
• ALLOWABLE HEIGHT: UNLIMITED FOR HANGARS IBC § 504.1 & UFC 4-211-01 § 3-3.1.7
• ALLOWABLE HEIGHT: 55 FT AND 3 STORIES FOR FULLY NON-SPRINKLED GROUP B BUILDINGS IBC § 504.1 TABLE 504.3/504.4
DEFINITION
• ACTUAL TOTAL BUILDING AREA: 2,000 SF IBC § 502 BUILDING AREA
IBC CHAPTER 5 AND UFC 3-600-01 APPLY. UFC 1-200-01 § 2-5
GENERAL BUILDING HEIGHTS AND AREAS:
• THERE ARE NO SPECIAL DETAILED REQUIREMENTS BASED ON USE
USE UFC 3-600-01 CHAPTER 4 IN LIEU OF IBC CHAPTER 4. UFC 1-200-01 § 2-4
SPECIAL DETAILED REQUIREMENTS BASED ON USE:
NEW BUSINESS OCCUPANCIES NFPA 101 CHAPTER 38
• NFPA OCCUPANCY CLASSIFICATIONS - SINGLE OCCUPANCY: NFPA 101 § 6.1.14.3
FINISH, FIRE PROTECTION FEATURES AND MEANS OF EGRESS.
RATING OF INTERIOR LOAD-BEARING PARTITIONS (OTHER THAN OCCUPANCY SEPARATION), INTERIOR
NFPA 101 APPLIES TO OCCUPANCY CLASSIFICATION AS IT RELATES TO FIRE/SMOKE RESISTANCE UFC 3-600-01 § 3-3.1.2
GROUP B BUSINESS IBC § 304 (BUSINESS)
• IBC OCCUPANCY CLASSIFICATIONS - MIXED USE AND OCCUPANCY - NON-SEPARATED OCCUPANCY: IBC § 508.3
AREA, BUILDING SEPARATION AND OCCUPANCY SEPARATION.
IBC APPLIES TO OCCUPANCY CLASSIFICATION AS IT RELATES TO BUILDING HEIGHT, BUILDING UFC 3-600-01 § 3-2.1.2
IBC CHAPTER 3 AND UFC 3-600-01 APPLY. UFC 1-200-01 § 2-3
PROJECT USE AND OCCUPANCY CLASSIFICATION:
EXISTING BUSINESS OCCUPANCIES NFPA 101 CHAPTER 39
NEW BUSINESS OCCUPANCIES NFPA 101 CHAPTER 38
• NFPA OCCUPANCY CLASSIFICATIONS - MIXED USE AND OCCUPANCY - NON-SEPARATED OCCUPANCY: NFPA 101 § 6.1.14.3
FINISH, FIRE PROTECTION FEATURES AND MEANS OF EGRESS.
RATING OF INTERIOR LOAD-BEARING PARTITIONS (OTHER THAN OCCUPANCY SEPARATION), INTERIOR
NFPA 101 APPLIES TO OCCUPANCY CLASSIFICATION AS IT RELATES TO FIRE/SMOKE RESISTANCE UFC 3-600-01 § 3-3.1.2
GROUP B BUSINESS IBC § 304 (BUSINESS)
• IBC OCCUPANCY CLASSIFICATIONS - MIXED USE AND OCCUPANCY - NON-SEPARATED OCCUPANCY: IBC § 508.3
AREA, BUILDING SEPARATION AND OCCUPANCY SEPARATION.
IBC APPLIES TO OCCUPANCY CLASSIFICATION AS IT RELATES TO BUILDING HEIGHT, BUILDING UFC 3-600-01 § 3-2.1.2
IBC CHAPTER 3 AND UFC 3-600-01 APPLY. UFC 1-200-01 § 2-3
BUILDING USE AND OCCUPANCY CLASSIFICATION:
WITH UFC 3-600-01 AND NFPA 101 THAN BEFORE THE MODIFICATION PROJECT WAS UNDERTAKEN.
REQUIREMENTS IN THIS UFC 3-600-01 AND NFPA 101 FOR NEW CONSTRUCTION. ADDITIONALLY, THE WORK MUST NOT MAKE THE BUILDING AREAS LOCATED OUTSIDE OF THE WORK AREA LESS CONFORMING
RECONSTRUCTION: REQUIRES NEWLY CONSTRUCTED ELEMENTS, COMPONENTS AND SYSTEMS TO COMPLY WITH NEW CONSTRUCTION
GENERAL REQUIREMENTS:
AREA IS NOT PERMITTED TO BE OCCUPIED BECAUSE EXISTING MEANS OF EGRESS AND FIRE PROTECTION SYSTEMS, OR THEIR EQUIVALENT, ARE NOT IN PLACE OR CONTINUOUSLY MAINTAINED.
THE RECONFIGURATION OF A SPACE THAT AFFECTS AN EXIT OR A CORRIDOR SHARED BY MORE THAN ONE OCCUPANT SPACE; OR THE RECONFIGURATION OF A SPACE SUCH THAT THE REHABILITATION...
NFPA 101 - RECONSTRUCTION: NFPA 101 § 43.2.2.1.4
WINDOW, THE RECONFIGURATION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.
AN ALTERATION - LEVEL 2 INCLUDES THE RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR...
IEBC - ALTERATION LEVEL 2: IEBC § 603.1
PROJECT DESCRIPTION (IEBC AND NFPA 101):
THIS PROJECT CONSISTS OF DEMOLISHING THE UNOCCUPIED AREA OF BUILDING 19.
PROJECT DESCRIPTION:
INTERNATIONAL CODE COUNCIL, INTERNATIONAL EXISTING BUILDING CODE (IEBC), 2021 EDITION. (AS AMENDED BY UFC 1-200-01).
INTERNATIONAL CODE COUNCIL, INTERNATIONAL BUILDING CODE (IBC), 2021 EDITION. (AS AMENDED BY UFC 1-200-01).
OTHER REFERENCES
NFPA 241, STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, 2022 EDITION.
NFPA 170, STANDARD FOR FIRE SAFETY AND EMERGENCY SYMBOLS, 2024 EDITION.
NFPA 101, LIFE SAFETY CODE, 2024 EDITION.
NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2022 EDITION.
NFPA 70, NATIONAL ELECTRIC CODE, 2023 EDITION.
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) - LATEST EDITIONS
UFC 3-601-02, FIRE PROTECTION SYSTEMS INSPECTION, TESTING, AND MAINTENANCE, 07 OCT 2021
UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES, CHANGE 6, 06 MAY 2021
UFC 1-200-01 DOD BUILDING CODE (1 SEPTEMBER 2022 WITH CHANGE 3, 26 FEBRUARY 2024)
UNIFIED FACILITIES CRITERIA (UFC)
REFERENCED CODES AND STANDARDS:
CODE ANALYSIS
• EVERY EXIT OR DIRECTIONAL SIGN WILL BE ILLUMINATED BY A RELIABLE LIGHT SOURCE. NFPA 101 § 7.10.5.1
LOCATION WHERE DIRECTION OF TRAVEL TO REACH THE NEAREST EXIT IS NOT APPARENT.
• A SIGN WITH DIRECTIONAL INDICATOR SHOWING DIRECTION OF TRAVEL WILL BE PLACED IN EVERY NFPA 101 § 7.10.2.1
THE EXIT OR WAY TO REACH EXITIS NOT READILY APPARENT TO OCCUPANTS.
• ACCESS TO EXITS WILL BE MARKED BY APPROVED, READILY VISIBLE SIGNS IN ALL CASES WHERE NFPA 101 § 7.10.1.5.1
EXITS, WILL BE MARKED BY APPROVED SIGNS.
• EXITS OTHER THAN MAIN EXTERIOR EXIT DOORS THAT ARE OBVIOUSLY AND CLEARLY IDENTIFIED AS NFPA 101 § 7.10.1.2.1
MARKING MEANS OF EGRESS
• MINIMUM ILLUMINATION FOR FLOORS AND OTHER WALKING SURFACES WILL BE AT LEAST 1 FC. NFPA 101 § 7.8.1.3 (2)
WALKING SURFACE).
• MINIMUM ILLUMINATION FOR MEANS OF EGRESS WILL BE AT LEAST 10 FC (MEASURED FROM NFPA 101 § 7.8.1.3 (1)
ILLUMINATION OF MEANS OF EGRESS
• EXISTING BUSINESS (NON-SPRINKLERED): 20 FEET NFPA 101 § 39.2.5.3.2
DEAD END CORRIDOR
• NEW BUSINESS (NON-SPRINKLERED OR OCCUPANT LOAD > 30 PERSONS): 75 FEET NFPA 101 § 38.2.5.2.3
COMMON PATH OF TRAVEL
• NEW BUSINESS (NON-SPRINKLERED): 200 FEET NFPA 101 § 38.2.6.2
TRAVEL DISTANCE TO AN EXIT
• IT EQUIPMENT ROOMS OR TELOCOMMUNICATIONS ROOMS 300 SQ FT/PERSON GROSS FLOOR AREA UCF 3-600-01 § 10-3.1, TABLE 10-1
• MECHANICAL, ELECTRICAL, OTHER BUILDING EQUIPMENT... 500 SQ FT/PERSON GROSS FLOOR AREA UCF 3-600-01 § 10-3.1, TABLE 10-1
• BUSINESS - OTHER 150 SQ FT/PERSON GROSS FLOOR AREA NFPA 101 TABLE 7.3.1.2
PROJECT OCCUPANCY LOAD FACTORS
OF THE REQUIRED EGRESS WIDTH.
• DOORS LEAVES SWINGING INTO THE THE MEANS OF EGRESS WILL LEAVE NOT LESS THAN ON HALF NFPA 101 § 7.2.1.4.3.1
DOOR LEAF ENCROACHMENT
• DOORS WILL SWING IN THE DIRECTION OF TRAVEL WHERE SERVING MORE THAN 50 PERSONS. NFPA 101 § 7.2.1.4.2 (1)
DOOR LEAF SWING DIRECTION
LIGHTING IN ACCORDANCE WITH NFPA 101 § 7.9.
• THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS WILL BE PROVIDED WITH EMERGENCY NFPA 101 § 7.2.1.6.2(7)
FIRE PROTECTIVE SIGNALLING SYSTEM IS MANUALLY RESET.
UNLOCK THE EGRESS DOORS IN THE DIRECTION OF EGRESS AND THEY WILL REMAIN UNLOCKED UNTIL THE
• ACTIVATION OF THE BUILDING SPRINKLER SYSTEM OR FIRE PROTECTION SIGNALING SYSTEM WILL NFPA 101 § 7.2.1.6.2(6)
THE LOCK, INDEPENDENT OF LOCKING SYSTEM ELECTRONICS.
• WHEN OPERATED, THE MANUAL RELEASE DEVICE WILL RESULT IN DIRECT INTERRUPTION OF POWER TO
READS "PUSH TO EXIT".
• THE MANUAL RELEASE DEVICE WILL BE READILY ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT
AND WITHIN 60 IN. OF THE SECURED DOOR OPENING.
• MANUAL RELEASE DEVICE WILL BE LOCATED ON THE EGRESS SIDE 40 IN TO 48 IN ABOVE THE FLOOR
DEVICE COMPLYING WITH THE FOLLOWING:
• DOOR LOCKS WILL BE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS FROM A MANUAL RELEASE NFPA 101 § 7.2.1.6.2(3)
THE SENSOR OR TO THE PART OF THE SYSTEM THAT LOCKS THE DOOR.
• DOOR LEAVE WILL AUTOMATICALLY UNLOCK IN THE DIRECTION OF TRAVEL UPON LOSS OF POWER TO NFPA 101 § 7.2.1.6.2(2)
OF EGRESS UPON DETECTION OF APPROACHING OCCUPANT.
• SENSOR WILL BE PROVIDED ON THE EGRESS SIDE, ARRANGED TO UNLOCK THE DOOR IN THE DIRECTION NFPA 101 § 7.2.1.6.2(1)
LOCKING HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT THE FOLLOWING ARE MET:
• DOOR ASSEMBLIES IN THE MEANS OF EGRESS WILL BE PERMITTED TO BE EQUIPPED WITH ELECTRICAL NFPA 101 § 7.2.1.6.2
ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES
CORRIDORS NEED NOT BE PROTECTED WITH FIRE RATED CONSTRUCTION. 38.3.6.1 (3), 42.3.6
• WHERE AN APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IS PROVIDED THROUGHOUT, NFPA 101 § 7.1.3.1 (2), 12.3.6 (2), NFPA 101 EXIT ACCESS CORRIDORS
OF THE 2015 IBC ARE ACCPETABLE.
• WHERE ABA STANDARDS REFERENCES PREVIOUS VERSIONS OF IBC, THE APPLICABLE REQUIRMENTS
ACT (ABA) STANDARDS.
• DO NOT USE IBC CHAPTER 10, EXCEPT WHERE REFERENCED BY ARCHITECTURAL BARRIERS
USE UFC 3-600-01 IN LIEU OF IBC CHAPTER 10. UFC 1-200-01 § 2-10
MEANS OF EGRESS (SEE LIFE SAFETY PLANS):
• BUILDING TO BE INHABITED (ROUTINELY OCCUPIED BY 11 OR MORE 11 OCCUPANTS). UFC 4-011 § 1-8
• MASS NOTIFICIATION SYSTEM IS REQUIRED THROUGHOUT.
OR WITH MORE THAN 50 OCCUPANTS ABOVE OR BELOW LEVEL OF EXIT DISCHARGE.
• BUSINESS OCCUPANCY - FIRE ALARM REQUIRED FOR OCCUPANT LOAD > 300 PERSONS. NFPA 101 § 38.3.4.1
• FIRE ALARM SYSTEM IS REQUIRED THROUGHOUT.
FIRE ALARM AND MASS NOTIFICATION SYSTEM (MNS)
• MECHANICAL ROOMS WILL HAVE BRACKET MOUNTED FIRE EXTINGUISHERS. UFC 3-600-01 § 9-17.3.2
• RECESSED OR SEMI-RECESSED CABINETS TO BE PROVIDED IN FINISHED SPACES. UFC 3-600-01 § 9-17.3.1
ELECTRONICS (EG: CLEAN AGENT).
• EXTINGUISHERS FOR ELECTRONIC EQUIPMENT AREAS SPACES WILL BE SUITABLE FOR UFC 3-600-01 § 9-17.2.2
• PORTABLE FIRE EXTINGUISHERS WILL BE LOCATED IN ACCORDANCE WITH NFPA 10. UFC 3-600-01 § 9-17.2.1
EXCEPT FOR SPECIAL USES.
• GENERAL PURPOSE FIRE EXTINGUISHERS ARE NOT REQUIRED FOR FULLY SPRINKLERED BUILDINGS, UFC 3-600-01 § 9-17.1
PORTABLE FIRE EXTINGUISHERS
• THE DISTANCE FROM EXTERIOR DOORS TO ANY PORTION OF THE BUILDING DOES NOT EXCEED 450 FT. UFC 3-600-01 § 9-10.2.2
• THE BUILDING DOES NOT EXCEED 4 STORIES. UFC 3-600-01 § 9-10.2.1
• STANDPIPE SYSTEMS IS NOT REQUIRED.
STANDPIPE SYSTEMS
EXCEEDING 15,000 SQFT.
• AUTOMATIC SPRINKLER PROTECTION IS REQUIRED FOR SINGLE STORY TYPE I OR II CONSTRUCTION UFC 3-600-01 § 9-7.2.1.1
• AUTOMATIC SPRINKLER PROTECTION IS NOT REQUIRED THROUGHOUT.
AUTOMATIC SPRINKLER PROTECTION
ATTS
XEE FO
SA
T
LI DEC NE S
P R
ESS
NIO AL
O F
I
ENG
N
EE
R
RUSSELL P. MILLER
139919
07/31/2024
DN
TD-1 TD-1
TD-1 TD-1TD-1
TD-2 TD-2
TD-2 TD-2
CP-1 CP-1
CP-1 CP-1
C P
-1 C
P -1
RESTROOM
106 SF
WORK ROOM
44 SF
BREAK ROOM
261 SF
LOBBY
455 SF
OFFICE
102 SF
OFFICE
102 SF
I.T.
18 SF
CORRIDOR
88 SF
ELEC / MECH
110 SFCORRIDOR
264 SF
VESTIBULE
88 SF
A
B
1 2 3 4
32" 0.2
32" 0.2
61" 0.3
EXIT WIDTH [INCHES]
EXIT DOOR TAG
LINE TYPES FOR MEANS OF EGRESS:
TRAVEL DISTANCE
COMMON PATH
COMPONENT SYMBOL
LIFE SAFETY SYMBOLS:
TD
CP
EXIT DISCHARGE ARROW
EXIT DISCHARGE
A
B
C
CAPACITY FACTOR [INCHES PER OCCUPANT]
EXIT CAPACITY [OCCUPANTS]
FIRE EXTINGUISHER
(ABC EXTINGUISHER)
(CA DENOTES CLEAN AGENT EXTINGUISHER)
(CO2 DENOTES CARBON MONOXIDE)
1 HOUR FIRE RATED BARRIER
1. FOR EXIT LIGHT AND EMERGENCY LIGHTING, SEE
ELECTRICAL LIGHTING DRAWINGS (E SERIES).
LIFE SAFETY NOTES:
EXISTING EXIT SIGN
Key Plan
1 2 3 4 5
D
C
B
A
NO. REVISIONS DATE
Defense Supply Center Richmond
DLA Installation Management Richmond
6090 Strathmore Road
Richmond VA, 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
AS NOTED
SHEET NAME.
BUILDING NAME.
GENERAL SHEET NOTES
PLAN NORTH
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
R. WHITE
K. LE
C. HABY
J. JANOTA
J. CORONADO
AREA TO BE
DEMOLISHED
EXIST. TO
REMAIN
D
C
B
A
1 2 3 4 5
RM
RD
31 JULY 2024
10356006
G-101
LIFE SAFETY PLAN
BLDG 19 DEMOLITION
31 JULY 2024
3/16" = 1'-0"A1
LIFE SAFETY PLAN
LEGEND
MEANS OF EGRESS
EGRESS
PATH ID OCCUPANCY SPRINKLER PROVIDED
MAXIMUM
PERMITTED
CP-1 NEW BUSINESS NO 56' - 6" 75' - 0"
TD-1 EXISTING BUSINESS NO 66' - 6" 200' - 0"
TD-2 EXISTING BUSINESS NO 56' - 0" 200' - 0"
TOTAL 59
123 CORRIDOR BUSINESS (GROSS) 264 150 2
110 CORRIDOR BUSINESS (GROSS) 88 150 1
109 IT IT EQUIPMENT ROM 18 300 1
108 ELEC/MECH
MECHANICAL/ELECTRICAL
ROOM
110 500 1
106 RESTROOM BUSINESS (GROSS) 106 150 1
105 BREAK ROOM ASSEMBLY USE 261 15 18
104 WORK ROOM BUSINESS (GROSS) 44 150 1
103 OFFICE BUSINESS (GROSS) 102 150 1
102 OFFICE BUSINESS (GROSS) 102 150 1
101 LOBBY ASSEMBLY USE 455 15 31
100 VESTIBULE BUSINESS (GROSS) 88 150 1
ROOM # ROOM DESCRIPTION OCCUPANT USE TYPE
AREA
(SQ SF)
OCCUPANT
LOAD FACTOR
(SQ SF/PERSON)
OCCUPANT
LOAD
OCCUPANT LOAD SCHEDULE
ATTS
XEE FO
SA
T
LI DEC NE S
P R
ESS
NIO AL
O F
I
ENG
N
EE
R
RUSSELL P. MILLER
139919
FLAG POLE
SANITARY SEWER CLEANOUT
AIR CONDITIONER UNIT
SPRINKLER VALVE
SPRINKLER HEAD
TRAFFIC/ELECTRIC PULL BOX
TELEPHONE MANHOLE
SIGN
COMMERCIAL SIGN
UNDERGROUND CABLE TV LINE
WATER LINE
GAS LINE
OVERHEAD ELECTRIC LINE
GAS VALVE
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
TRANSFORMER POLE
TELEPHONE RISER
FIRE HYDRANT
LIGHT POLE
GAS METER
POWER POLE
FENCE
ELECTRIC UNDERGROUND LINE
ELECTRIC MANHOLE
GROUND TRANSFORMER
SANITARY SEWER LINE
GAS VENT
PAY PHONE
GUARD POST
MONUMENT FOUND
MONUMENT SET
EXISTING CONCRETE
EXISTING ASPHALT
G
STORM DRAIN LINE
UNDERGROUND TELEPHONE LINE
CO
GROUND SURFACE CONTOUR
CURB AND GUTTER
SURFACE DRAINAGE FLOWLINE
UNDERGROUND FIBER OPTIC LINE
WATER LINE (ATLAS)
SANITARY SEWER LINE (ATLAS)
GUY POLE
DOWN GUY
COMMUNICATIONS VAULT
OVERHEAD TELEPHONE LINECOMM
MARKED PIPELINE
UNKNOWN UNDERGROUND UTILITY
WATER LINE (IRRIGATION)
Ex
TREE LINE
CHAINLINK FENCE
STOCKADE FENCE
SECURITY FENCE
ELECTRIC FENCE
HOG WIRE FENCE
GAS LINE (ATLAS)
BUILDING/ FOUNDATION DEMO
PAVEMENT DEMO
MONITORING WELL
WATER VALVE BOX
WATER METER
UST FUEL FILL PORT
GROUND LIGHT
HANDHOLE, ELECTRIC
EM ELECTRIC METER
HOSE BIB
WATER VENT
TRAFFIC DETECTOR LOOP
TRAFFIC SIGNAL POLE
TRAFFIC CONTROL BOX
PARKING METER
BORE HOLE LOCATION
GEO PROBE
DOUBLE PARKING METER
PROPOSED ASPHALT
PROPOSED CONCRETE
XXX.XX
LIMITS OF CONSTRUCTION
TREE DRIP LINE
SHRUB LINE
EXISTING GRAVEL/ RIPRAP
LEGEND NOTES
1. ALL SYMBOLS ARE NOT NECESSARILY USED
ON THIS PROJECT.
2. SCREENING OR SHADING OF WORK IS USED
TO INDICATE EXISTING COMPONENTS OR TO
DE-EMPHASIZE PROPOSED IMPROVEMENTS
TO HIGHLIGHT SELECTED TRADE WORK.
REFER TO CONTEXT OF EACH SHEET FOR
USAGE .
GUTTER ELEVATION, UNLESS
OTHERWISE NOTED
AC ASPHALTIC CONCRETE
ACFT AIRCRAFT
AREA DRAINAD
ADJ ADJACENT
A/G ABOVEGROUND
APPROX APPROXIMATE
ARCHITECTURALARCH
ASPHALTASPH
AVERAGEAVG
BARR BARRIER
BH BOILER HOUSE
BKS BARRACKS
BUILDING(S)BLDG(S)
BOT OR B BOTTOM
BS BOTH SIDES
C CONDUIT
CAPACITYCAP
CAST IRON PIPECI-CIP
CJ CONSTRUCTION JOINT
CENTER LINECL OR
CLJ CONTROL JOINT
CORRUGATED METAL PIPECMP
CMU CEMENT MASONRY UNIT
COL COLUMN
CONCRETECONC
CONN CONNECTION
CONTINUOUSCONT
CORNERCOR
CORRUGATEDCORR
CONCRETE PIPECP
C TO C CENTER TO CENTER
CTRJ CONTRACTION JOINT
CHECK VALVECV
COLD WATERCW
CONSTR CONSTRUCTION
EACHEA
E EAST
DWG(S) DRAWING(S)
DSGN DESIGN
DR DRAIN OR DOOR
DOWNDN
DISTR DISTRIBUTION
DI-DIP DUCTILE IRON PIPE
DIM DIMENSION
DIA DIAMETER
DETAIL(S)DET(S)
EXTERIOREXT
EXIST EXISTING
EXPANSION JOINTEXP JT
EST ESTIMATE
ENCLOSUREENCL
ELECTRICAL MANHOLEEMH
ELEC ELECTRICAL
ELEVATIONEL
U/G ELECTRICAL CABLE LINEECL
FIRE WATER
FINISH
FLOOR LEVEL
FIRE HYDRANT
FOUNDATION
FLOOR DRAINFD
FDN
FHY
FIN
FL
FW
GV
GS-GSP
GND
GL
GFP(M)
GEN GENERATOR
GOVERNMENT FURNISHED PROPERTY
GRADE LINE
GROUND
GALVANIZED STEEL PIPE
GATE VALVE
GR
GALV
GRADE
GALVANIZED
HGT HEIGHT
HORIZ HORIZONTAL
HP HIGH POINT
HEADWALL OR HOT WATERHW
INSIDE DIAMETERID
INVERT ELEVATIONIE
ISOLATION JOINTIJ
INL INLET
INVERTINVT
JB JUNCTION BOX
MECHANICALMECH
MDL MIDDLE
MAX MAXIMUM
MATL MATERIAL
LONGITUDINALLONG
L LONG
MINIMUMMIN
MISC MISCELLANEOUS
N NORTH
MECHANICAL JOINTMJ
OPTIONALOPTL
OPNG OPENING
O/H OVERHEAD
OVERALLOA
ON CENTEROC
OD OUTSIDE DIAMETER
ORIGINALORIG
O TO O OUT TO OUT
OUTLETOUTL
PCC PORTLAND CEMENT CONCRETE
PAVT PAVEMENT
OVERHEAD PRIMARY POWER LINEPP
PERMANENTPERM
QUANTITYQ
POWERPWR
PVC POLYVINYL CHLORIDE
REPAIRRPR
REQUIREDREQ'D
REPLACEREPL
RELOCATEDRELOC
REF REFERENCE
RECTANGULARRECT
REINFORCING BARRE-BAR
ROADRD
RAD OR R RADIUS
REINFORCED CONCRETERC
RCP REINFORCED CONCRETE PIPE
SECTIONSECT
SDL SADDLE
SURFACE CLEAN OUTSCO
SCALESC
SOUTHS
SHT SHEET
SHLDR SHOULDER
SLP,S SLOPE
SQUARESQ
SMH SEWER MANHOLE
SP STEEL PIPE OR OVERHEAD SECONDARY
SPEC(S) SPECIFICATION(S)
SST
STA
STAINLESS STEEL
STATION
UNIFORMUNIF
UNDERGROUNDU/G
VAR VARIOUS
VB VALVE BOX
VEL VELOCITY
VERTICALVERT
W WEST, WIDTH
W/ WITH
TEMPORARYTEMP
TEL TELEPHONE
UNDERGROUND TELEPHONE CABLE LINETCL
TITLE BLOCKT/B
THRU THROUGH
TYP TYPICAL
SYSTEMSYS
SUSPEND(ED)SUSP
STD STANDARD
STL STEEL
STOR STORAGE
CENTER LINE
SAME AS ABOVE OR DITTO
PLUS OR MINUS
PLATE
C
P
NUMBER#
EQUAL
AT@
AND&
% PERCENT
TRANSFORMERXFMR
W/O WITHOUT
WATERWTR
WWM WELDED WIRE MESH
TOT TOTAL
WELDED
WIRE MESH
AIR COOLED CONDENSING UNITACCU
WLD
WM
CL
U/C UNDER CONSTRUCTION
BW BOTTOM OF WALL
DRAIN LINEDL
FINISH GRADEFG
T TOP OF CURB OR STRUCTURE
B BOTTOM OF CURB OR STRUCTURE
TW TOP OF WALL
JT JOINT
CI CURB INLET
CLEARANCECLR
EW EACH WAY
NATURAL GAS LINENGL
NUMBERNO OR #
NTS NOT TO SCALE
W
(X 23.60) 23.60
W
EL XX.XX
XX
TREE
SPOT ELEVATION
EXISTING U/G PIPE
(TO BE ABANDONED)
NORTH DIRECTIONAL ARROW
LOCATION OF SOIL BORING W/BORING NUMBER
AND EXISTING GROUND ELEVATION
W W W U/G PIPE & STRUCTURE
FENCE
EXIST REMOVAL NEW
BUILDING
CONC SLAB & CONC SIDEWALK
CONC STEPS W/ HANDRAILS
ASPHALT ROAD W/CURB
CONCRETE PAVEMENT
SAWCUT
GENERAL NOTES:
1. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AS SHOWN ON THE DRAWINGS PRIOR TO
THE START OF CONSTRUCTION. ANY DISCREPANCIES MUST BE BROUGHT IMMEDIATELY TO
THE ATTENTION OF THE CONTRACTING OFFICER.
2. THE CONTRACTOR SHALL PROVIDE, INSTALL, AND MAINTAIN ALL NECESSARY SIGNS, LIGHTS, FLARES, BARRICADES, MARKERS, CONES AND OTHER PROTECTIVE FACILITIES AND SHALL
TAKE ALL NECESSARY PRECAUTIONS FOR THE PROTECTION AND SAFETY OF THE PUBLIC
AND/OR MILITARY TRAFFIC AND OPERATIONS.
3. THE EXISTING TOPOGRAPHIC INFORMATION SHOWN ON THE DRAWINGS IS FROM VARIOUS
AS-BUILT DRAWINGS FOR FACILITIES AND IS NOT COMPLETE. THEREFORE THE CONTRACTOR
SHALL PERFORM A COMPLETE SURVEY OF ALL UTILITY LINE ROUTES TO VERIFY EXISTING
CONDITIONS AND ELEVATIONS. MAJOR DISCREPANCIES SHALL BE BROUGHT TO THE
ATTENTION OF THE CONTRACTING OFFICER.
4. VERIFY ALL DEPTHS AND LOCATIONS OF EXISTING UTILITIES PRIOR TO ANY CONSTRUCTION
STAGING AND DEMOLITION. ALL UTILITIES MAY NOT BE SHOWN. CONTACT UTILITY SERVICE
PROVIDERS AT LEAST 48 HOURS PRIOR TO TRENCHING OR EXCAVATION, AND REQUEST
FIELD LOCATION OF UTILITIES. ONE-CALL LOCATOR SERVICES MAY NOT COVER ALL UTILITIES
IN THIS AREA.
5. PRIOR TO BEGINNING ANY CONSTRUCTION, FIELD VERIFY AND PROTECT THE LOCATIONS
AND ELEVATIONS OF ALL EXISTING FACILITIES (UTILITIES, PIPING, EQUIPMENT, STRUCTURES, FENCING, BARRIERS, PAVEMENT, SIDEWALKS, SIGNAGE, ETC.) WHICH PERTAIN TO AND/OR
AFFECT CONSTRUCTION OF THIS PROJECT.
6. THE CONTRACTOR SHALL COORDINATE ALL PHASES OF WORK WITH THE CONTRACTING
OFFICER.
7. REMOVE AND REPLACE ALL EXISTING PAVEMENTS, CURBS, DRIVEWAYS, SIDEWALKS,
GRAVEL ROADWAYS, PIPE CULVERTS, FENCES, SIGNS, AND MISCELLANEOUS ITEMS WHERE
NOTED IN PLANS TO COMPLETE THE CONSTRUCTION.
8. REPAIR TO ORIGINAL CONDITION ANY DAMAGE INCURRED DURING CONSTRUCTION AT NO
EXPENSE TO OWNER.
9. ANY EXISTING FACILITIES THAT ARE DAMAGED OR REMOVED SHALL BE REPAIRED OR
REPLACED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL CONDITIONS AT NO
ADDITIONAL COSTS.
10. RESTORE ALL DRIVEWAYS, CULVERTS, LANDSCAPING, AND OTHER IMPROVEMENTS
(REGARDLESS OF WHETHER THEY WERE CONSTRUCTED OR INSTALLED BY PUBLIC
AGENCIES, UTILITIES, OR INDIVIDUALS) THAT ARE DISTURBED BY CONSTRUCTION TO A
CONDITION EQUAL TO OR BETTER THAN ORIGINAL CONDITIONS.
11. ALL AREAS DISTURBED OR EXPOSED DURING CONSTRUCTION SHALL BE REVEGETATED AND
RESTORED TO ORIGINAL CONDITIONS IN ACCORDANCE WITH THE PLANS AND
SPECIFICATIONS.
12. IMMEDIATELY NOTIFY THE CONTRACTING OFFICER OF ANY UNREPORTED OBSTACLES THAT
MAY IMPEDE OR PREVENT THE CONSTRUCTION OF THE WORK.
13. ANY PORTION OF THE PROJECT IMPROPERLY PLACED AND/OR CONFLICTING WITH ANY
EXISTING STRUCTURE SHALL BE REMOVED, CORRECTLY PLACED AND NO SEPARATE PAY
SHALL BE APPROVED FOR ASSOCIATED COSTS.
14. CONSTRUCTION OPERATIONS SHALL BE CONDUCTED IN SUCH A MANNER AS TO PROTECT
EXISTING FACILITIES AT ALL TIMES.
15. RECORD AND SUPPLY TO THE CONTRACTING OFFICER THE FOLLOWING INFORMATION:
A. LOCATION AND ELEVATION OF ALL SUPPLEMENTARY CONNECTIONS.
B. "AS-BUILT" INVERTS AND PROFILE OF CONSTRUCTED PIPELINE.
C. THE NEW LOCATION AND DEPTH OF ALL RELOCATED AND/OR ADJUSTED UTILITIES.
D. LOCATION AND ELEVATION OF ALL UTILITIES ENCOUNTERED.
13. ALL HOLES, TRENCHES, AND OTHER HAZARDOUS AREAS SHALL BE ADEQUATELY
PROTECTED BY PROTECTIVE DEVICES.
14. ALL TRENCHES SHALL BE BACKFILLED WITHIN SEVEN (7) DAYS OF INITIAL EXCAVATION
UNLESS APPROVED IN WRITING BY CONTRACTING OFFICER.
15. ANY DEWATERING SHALL BE INCLUDED IN THE CONTRACT PRICE.
16. ALL SPOIL AND EXCESS MATERIAL NOT USED IN CONSTRUCTION SHALL BE REMOVED FROM
THE SITE AND PROPERLY DISPOSED OF, AS COORDINATED WITH THE CONTRACTING
OFFICER.
17. CONFINE WORK AREAS TO WITHIN THE PROJECT BOUNDARY. PRIOR TO FINAL ACCEPTANCE, REMOVE ALL TRASH AND DEBRIS WITHIN THE PROJECT LIMITS.
18. FIELD CHANGES TO THE HORIZONTAL AND VERTICAL DESIGN MAY BE ALLOWED SUBJECT TO
THE APPROVAL OF THE ENGINEER. FIELD CHANGES SHALL COMPLY WITH THE DESIGN
INTENT AS NOTED ON THE DRAWINGS AND SPECIFICATIONS.
19. ALL CONSTRUCTION SHALL FOLLOW USACE SPECIFICATIONS, STANDARDS, AND MATERIAL
ITEM NUMBERS.
20. THE TERM 'CONSTRUCTION' WITHIN THESE NOTES IS REPRESENTATIVE OF ALL
CONSTRUCTION ACTIVITIES, INCLUDING BUT NOT LIMITED TO CONSTRUCTION STAGING,
DEMOLITION AND NEW CONSTRUCTION.
PROJECT LOCATION:
1. PROJECT LIMITS SHOWN ARE APPROXIMATE. FOR THE PURPOSES OF DEFINING THE
PROJECT LIMIT TO DETERMINE LOCATIONS OF TEMPORARY FENCING OR BARRICADES THE
CONTRACTOR SHALL PREPARE A WORK PLAN SHOWING THE PROPOSED PROJECT LIMIT FOR
APPROVAL BY THE CONTRACTING OFFICER AND THE USING AGENCY.
UTILITY NOTES:
1. THE EXISTENCE AND LOCATION OF UNDERGROUND UTILITIES, APPURTENANCES AND
STRUCTURES SHOWN ARE BASED ON AVAILABLE RECORDS, AND APPLICABLE UTILITY MAPS.
HOWEVER THIS INFORMATION MAY NOT BE COMPLETE AND ACCURATE. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION, SIZE AND INVERTS OF ALL EXISTING
UTILITIES AND SHALL PROTECT ALL SUCH UTILITIES AT ALL TIMES, UNLESS OTHERWISE
INDICATED. EXISTING UTILITIES WHETHER SHOWN ON THE DRAWINGS OR NOT WHICH HAVE
BEEN DAMAGED AS A RESULT OF THE CONSTRUCTION WORK, SHALL BE RESTORED
IMMEDIATELY TO THEIR ORIGINAL OR BETTER CONDITION AND SHALL BE PAID FOR BY THE
CONTRACTOR.
2. WHENEVER CONNECTIONS TO EXISTING UTILITIES OR WHERE NEW UTILITIES CROSS
EXISTING UTILITIES ARE SHOWN, THE CONTRACTOR SHALL CAREFULLY EXPOSE THE UTILITY
BY HAND EXCAVATION TO VERIFY THEIR LOCATIONS AND DEPTHS PRIOR TO EXCAVATING
TRENCHES FOR THE NEW UTILITY LINES.
3. WHENEVER ANY CHANGE IN ALIGNMENT OR GRADE FOR THE PROPOSED UTILITIES ARE
REQUIRED DUE TO UNFORESEEN CONFLICT WITH OTHER UTILITIES, THE CONTRACTOR
SHALL INFORM THE CONTRACTING OFFICER IMMEDIATELY FOR REMEDIAL ACTION.
4. INTERRUPTION OF UTILITY SERVICE AND/OR OPERATIONS OF ADJACENT FACILITIES WILL BE
KEPT TO A MINIMUM. ANY INTERRUPTION OF UTILITY SERVICE AND/OR OPERATIONS WILL BE
COORDINATED WITH THE CONTRACTING OFFICER AND THE AFFECTED USING AGENCIES.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROTECTION OF ALL WATER LINES
DURING CONSTRUCTION. THE CONTRACTOR SHALL BE ESPECIALLY CAREFUL WHEN
EXCAVATING BEHIND WATER LINES, TEES AND BENDS WHEREVER THERE IS A POSSIBILITY
OF WATER LINE MOVEMENT DUE TO REMOVAL OF THE SUPPORTING EARTH BEYOND THE
EXISTING REACTION BLOCKS. THE CONTRACTOR SHALL TAKE WHATEVER MEASURES IS
NECESSARY TO PROTECT THE WATER LINES, SUCH AS CONSTRUCTING SPECIAL REACTION
BLOCKS AND/OR MODIFYING HIS/HER CONSTRUCTION METHOD, WITH THE APPROVAL OF THE
CONTRACTING OFFICER.
6. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ANY SEWAGE SPILLS CAUSED DURING
CONSTRUCTION. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER AND
UTILIZE APPROPRIATE MEASURES TO CONTAIN AND ADEQUATELY CLEANUP THE SPILL. THE
CONTRACTING OFFICER SHALL OVERSEE THE CLEANUP EFFORT AND RENDER THE SITE ALL
COSTS INCURRED FOR SPILL CONTAINMENT AND CLEANUP SHALL BE THE RESPONSIBILITY
OF THE CONTRACTOR.
7. ALL WATER LINES (INCLUDING FIRE SERVICE LINE) COVERING DEPTH WILL BE AT LEAST 1
FEET BELOW FROST DEPTH.
8. USE 1.5 FEET FOR THE FROST DEPTH.
9. ALL WATER LINE AND SEWER FORCE MAIN PIPE INSTALLED SHALL HAVE RESTRAINED
JOINTS. PROVIDE CONCRETE THRUST BLOCKS ONLY WHERE APPROVED.
GRADING NOTES:
1. THE FINISH GROUND ELEVATION AT THE BUILDING LINE SHALL BE A MINIMUM OF 6 INCHES
BELOW FINISH FLOOR ELEVATION, UNLESS OTHERWISE SHOWN.
2. ALL EXPOSED AREA SHALL BE SODDED. SODDING SHALL BE PLACED WITH NO GAPS, AS
SOON AS FINAL GRADES HAVE BEEN ESTABLISHED. SODDING SHALL NOT BE DELAYED UNTIL
ALL GRADING WORK HAS BEEN COMPLETED. GRADING TO FINAL GRADE SHALL BE
CONTINUOUS, AND ANY AREA WITHIN WHICH WORK HAS BEEN INTERRUPTED OR DELAYED,
SHALL BE SODDED.CONTRACTOR IS RESPONSIBLE FOR THE INSTALLATION AND
MAINTENANCE OF THE SOD UNTIL PROJECT CLOSEOUT. THIS INCLUDES ENSURING THE SOD
IS PROPERLY LAID, MAINTAINED, AND IN GOOD CONDITION THROUGHOUT THE DURATION OF
CONSTRUCTION. ALL NEWLY GRADED AREAS SHALL BE TOP SOILED 4 INCHES THICK PRIOR
TO SODDING.
3. CONTRACTOR TO ENSURE POSITIVE DRAINAGE AWAY FROM BUILDINGS. PROVIDE A SMOOTH
RIDING CONNECTION TO EXISTING PAVEMENT.
4. TOPS OF MANHOLES TO BE RETAINED SHALL BE ADJUSTED TO MATCH FINISH GRADE
ELEVATION.
5. THE CONTRACTOR SHALL REMOVE ALL SILT AND DEBRIS RESULTING FROM DRAINAGE
FACILITIES, ROADWAYS AND OTHER AREAS DURING CONSTRUCTION. THE COSTS INCURRED
FOR ANY NECESSARY REMEDIAL ACTION BY THE CONTRACTING OFFICER SHALL BE PAYABLE
BY THE CONTRACTOR.
DEMOLITION NOTES:
1. ALL DEMOLITION WORK SHALL BE CONFINED WITHIN THE PROJECT LIMITS INDICATED,
UNLESS OTHERWISE NOTED.
2. ALL STRUCTURES WITHIN THE PROJECT BOUNDARY SHALL REMAIN, UNLESS OTHERWISE
INDICATED.
3. EXISTING ASPHALTIC CONCRETE PAVEMENT WITHIN THE PROJECT LIMITS SHALL REMAIN,
UNLESS OTHERWISE INDICATED.
4. SIDEWALKS, CONCRETE PADS, CURBING AND OTHER ITEMS WITHIN THE PROJECT LIMITS
SHALL REMAIN, UNLESS OTHERWISE INDICATED.
5. WATER AND SEWER LINES WITHIN THE PROJECT LIMITS SHALL REMAIN, UNLESS OTHERWISE
INDICATED. PITS MAY BE ABANDONED AND SHALL BE FILLED WITH STRUCTURAL BACKFILL.
TOP OF PITS SHALL BE DEMOLISHED WITHIN 3 FEET OF THE FINAL GRADE.
6. EXISTING DRAIN LINES AND DRAINAGE STRUCTURES WITHIN THE PROJECT LIMITS SHALL
REMAIN, UNLESS OTHERWISE INDICATED.
7. ALL UTILITIES, STRUCTURES AND/OR IMPROVEMENTS IDENTIFIED AS TO REMAIN SHALL BE
MAINTAINED IN GOOD CONDITION TO RECEIVE THE PROPOSED UTILITIES, STRUCTURES
AND/OR IMPROVEMENTS. SHOULD THESE ITEMS BECOME DAMAGED DUE TO CONTRACTOR'S
NEGLIGENCE OR CONSTRUCTION OPERATIONS, THE CONTRACTOR SHALL RESTORE THESE
ITEMS TO THEIR ORIGINAL OR BETTER CONDITION AT NO ADDITIONAL COST TO THE
GOVERNMENT AND TO THE SATISFACTION OF THE CONTRACTING OFFICER.
8. ALL DISPOSAL WORK, SHALL BE IN ACCORDANCE WITH APPLICABLE LOCAL ENVIRONMENTAL
LAWS.
ENVIRONMENTAL QUALITY NOTES:
1. PRIOR TO COMMENCING CONSTRUCTION, ALL TEMPORARY EROSION AND SEDIMENTATION
(E&S) CONTROL MEASURES SHALL BE PROPERLY SELECTED AND INSTALLED. ALL
TEMPORARY E&S CONTROL MEASURES SHALL BE MAINTAINED IN ACCORDANCE WITH THE
MANUFACTURER'S SPECIFICATIONS AND GOOD ENGINEERING PRACTICES. THE CONTROLS
SHALL REMAIN IN PLACE UNTIL DISTURBED AREAS ARE REVEGETATED AND THE AREAS HAVE
BECOME PERMANENTLY STABILIZED.
2. IF SEDIMENT ESCAPES THE CONSTRUCTION SITE, OFF-SITE ACCUMULATIONS OF SEDIMENT
MUST BE REMOVED AT A FREQUENCY SUFFICIENT TO MINIMIZE OFFSITE IMPACTS TO WATER
QUALITY (E.G., FUGITIVE SEDIMENT IN STREET BEING WASHED INTO SURFACE STREAMS OR
SENSITIVE FEATURES BY THE NEXT RAIN).
3. SEDIMENT MUST BE REMOVED FROM SEDIMENT TRAPS OR SEDIMENTATION PONDS NOT
LATER THAN WHEN DESIGN CAPACITY HAS BEEN REDUCED BY 50%. A PERMANENT STAKE
MUST BE PROVIDED THAT CAN INDICATE WHEN THE SEDIMENT OCCUPIES 50% OF THE BASIN
VOLUME.
4. LITTER, CONSTRUCTION DEBRIS, AND CONSTRUCTION CHEMICALS EXPOSED TO
STORMWATER SHALL BE PREVENTED FROM BECOMING A POLLUTANT SOURCE FOR
STORMWATER DISCHARGES (E.G., SCREENING OUTFALLS, PICKED UP DAILY).
5. ALL SPOILS (EXCAVATED MATERIAL) GENERATED FROM THE PROJECT SITE AND STORED
ON-SITE MUST HAVE PROPER E&S CONTROLS INSTALLED.
6. STABILIZATION MEASURES SHALL BE INITIATED AS SOON AS PRACTICABLE IN PORTIONS OF
THE SITE WHERE CONSTRUCTION ACTIVITIES HAVE TEMPORARILY OR PERMANENTLY
CEASED, AND CONSTRUCTION ACTIVITIES WILL NOT RESUME WITHIN 21 DAYS. WHEN THE
INITIATION OF STABILIZATION MEASURES BY THE 14TH DAY IS PRECLUDED BY WEATHER
CONDITIONS, STABILIZATION MEASURES SHALL BE INITIATED AS SOON AS PRACTICABLE.
7. THESE GENERAL CONSTRUCTION NOTES SHALL BE PROVIDED TO ALL SUBCONTRACTORS.
EROSION AND SEDIMENT CONTROL NOTES:
1. ALL EROSION AND SEDIMENTATION CONTROLS SHALL BE IMPLEMENTED BEFORE
CONSTRUCTION COMMENCES AND SHALL BE MAINTAINED UNTIL SITE IS STABILIZED AFTER
COMPLETION OF WORK IN EACH WORK AREA.
2. EROSION CONTROL MEASURES, SITE WORK AND RESTORATION WORK SHALL BE IN
ACCORDANCE WITH THE CONTRACT.
3. SILT FENCE AND SIMILARLY RECOGNIZED TECHNIQUES AND MATERIALS SHALL BE
EMPLOYED DURING CONSTRUCTION TO PREVENT POINT SOURCE SEDIMENTATION LOADING
OF DOWNSTREAM FACILITIES. SUCH INSTALLATION SHALL BE REGULARLY INSPECTED FOR
EFFECTIVENESS. ADDITIONAL MEASURES MAY BE REQUIRED IF, IN THE OPINION OF THE
ENGINEER, THEY ARE WARRANTED.
4. MAINTAIN ALL TEMPORARY EROSION CONTROL STRUCTURES.
TRENCH SAFETY NOTES:
1. ALL WORK PERTAINING TO OPEN TRENCHING SHALL COMPLY WITH THE U. S. OCCUPATIONAL
SAFETY AND HEALTH ADMINISTRATION (OSHA) REGULATIONS.
2. CONFORM TO THE APPLICABLE FEDERAL REGULATIONS REGARDING TRENCH SAFETY.
PREPARE A TRENCH SAFETY PLAN FOR ALL EXCAVATIONS EXCEEDING 4-FEET IN DEPTH AND
4-FEET IN WIDTH, TO BE INCLUDED IN HEALTH AND SAFETY PLAN.
3. THE CONTRACTOR AND/OR CONTRACTOR'S INDEPENDENTLY RETAINED EMPLOYEE OR
STRUCTURAL DESIGN/GEOTECHNICAL/SAFETY/ EQUIPMENT CONSULTANT, IF ANY, SHALL
REVIEW THESE PLANS AND AVAILABLE GEOTECHNICAL INFORMATION AND THE
INSTALLATION SITE(S) WITHIN THE PROJECT WORK AREA IN ORDER TO IMPLEMENT
CONTRACTOR'S TRENCH EXCAVATION SAFETY PROTECTION SYSTEM, PROGRAMS AND/OR
PROCEDURES. THE CONTRACTOR'S IMPLEMENTATION OF THE SYSTEMS, PROGRAMS
AND/OR PROCEDURES SHALL PROVIDE FOR ADEQUATE TRENCH EXCAVATION SAFETY
PROTECTION THAT COMPLIES WITH OSHA STANDARDS FOR TRENCH EXCAVATION.
SPECIFICALLY, CONTRACTOR AND/OR CONTRACTOR'S INDEPENDENTLY RETAINED
EMPLOYEE OR SAFETY CONSULTANT SHALL IMPLEMENT A TRENCH SAFETY PROGRAM IN
ACCORDANCE WITH OSHA STANDARDS GOVERNING THE PRESENCE OF ACTIVITIES OF
INDIVIDUALS WORKING IN AND AROUND TRENCH EXCAVATION.
COORDINATION AND COMMUNICATION DURING CONSTRUCTION:
1. MARK ALL CONSTRUCTION EQUIPMENT AND VEHICLES WITH COMPANY PAINT DESIGNS,
INSIGNIAS OR OTHER COMPANY MARKINGS WHICH ARE CLEARLY VISIBLE.
2. CONSTRUCTION EQUIPMENT SHALL HAVE AUTOMATIC SIGNALING DEVICES TO SOUND AN
ALARM WHEN MOVING IN REVERSE.
3. ONLY RUBBER TIRED VEHICLES WILL BE ALLOWED ON EXISTING PAVEMENT WHICH IS TO
REMAIN.
VEHICLE ACCESS AND PARKING:
1. IF AFTER HOURS OR WEEKEND WORK IS REQUIRED, THE CONTRACTING OFFICER SHALL BE
NOTIFIED 14 CALENDAR DAYS PRIOR TO DAY OF NEED. AFTER HOURS OR WEEKEND WORK
ARE SUBJECT TO GOVERNMENT APPROVAL AND AVAILABILITY OF ESCORTS.
2. ALL PERSONNEL ARE RESPONSIBLE FOR OBTAINING PROPER PASS PRIOR TO ENTERING
SITE. COORDINATE WITH CONTRACTING OFFICER ON SUBMITTING ACCESS REQUESTS A
MINIMUM OF 14 CALENDAR DAYS PRIOR (ACCESS REQUIREMENTS ARE SUBJECT TO SUDDEN
CHANGES TO MEET SECURITY REQUIREMENTS).
3. KEEP ALL ROADS CLEAN OF CONSTRUCTION DEBRIS, MUD, ETC. AT ALL TIMES. PROVIDE
EQUIPMENT AND PERSONNEL TO CLEAN ROADS AS REQUESTED BY CONTRACTING OFFICER.
4. VIDEO DOCUMENT CONDITION OF STREETS, PARKING AREAS, ETC. PRIOR TO
CONSTRUCTION AND REPAIR DUE TO DAMAGE CAUSED BY CONSTRUCTION AND/OR
DEMOLITION ACTIVITIES AT NO ADDITIONAL COST TO THE GOVERNMENT AS REQUESTED BY
CONTRACTING OFFICER.
PERIMETER FENCE NOTES:
1. PERIMETER FENCE IS NOT NECESSARILY COINCIDENTAL WITH PROPERTY LINE.
TREE REPLACEMENT NOTES:
1. CONTRACTOR TO REPLACE REMOVED TREES AT A RATIO OF 2:1 AT A LOCATION
DETERMINED BY THE CONTRACTING OFFICER AND BASE ENVIRONMENTAL. CONTRACTOR TO
COORDINATE WITH CONTRACTING OFFICER AND BASE ENVIRONMENTAL.
ENCOUNTERED SPECIES:
1. THE CONTRACTOR SHALL AT ALL TIMES TAKE SUCH STEPS REQUIRED TO PREVENT ANY
INTERFERENCE OF OR DISTURBANCE TO FISH AND WILDLIFE. CONSULT THE CURRENT DLA
RICHMOND INTEGRATED NATURAL RESOURCES MANAGEMENT PLAN (INRMP) FOR
IDENTIFICATION AND MAPPING OF THESE RESOURCES. REFER TO SPECIFICATION 00 72 00
GENERAL CONDITIONS FOR MORE INFORMATION.
GR 10356006
NT
AS NOTED
1 2 3 4 5
D
C
B
A
CONTROLLED UNCLASSIFIED INFORMATION
NO. REVISIONS DATE
DLA Installation Management Richmond
6090 Strathmore Road Richmond, VA 23237
DESIGNED BY:
DRAWN BY:
SCALE:
CHECKED BY:
CIVIL
ELECTRICAL
MECHANICAL
ARCHITECTURAL
STRUCTURAL
PROJECT NO.
DRAWING NO.
DATE
SHEET NAME.
BUILDING NAME.
GENERAL SHEET NOTES
Engineer Of Record Info
613 NW LOOP 410, STE 700
SAN ANTONIO, TX 78216
(210) 841-2800
HDR ENGINEERING, INC
TEXAS P.E. FIRM
REGISTRATION NO. F-754
R. WHITE
K. LE
C. HABY
J. CORONADO
J. JANOTA
1 2 3 4 5
D
C
B
A
31 JULY 2024
31 JULY 2024
DEFENSE SUPPLY CENTER RICHMOND
DSCR BLDG 19 DEMOLITION
CIVIL ABBREVIATIONS, NOTES, AND LEGEND
C-001
STATE OF TEXAS
L I CENS ED
PROF ES S I ONA L E NG I NEER
07/31/24
COMM
COMM
COMM COMM
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
CO
M
M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
C O
M M
COMM
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
SD
D
JB
SD
SD
SD
SD
SD
SD
SD
SD
SD
SAN
SAN
SAN
SAN
SAN
SAN
SAN
SAN
SAN
SANSANSANSANSANSAN
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
CB
W W W W
S
S
S
S
S
W
W W
W
W
WWWWWWWWW
WWWW
W W W W W W W W W
W
W
E
E E E E
E E
E E
E
E
E
E E
E
E
E
E
E E
E
E E
E
E E
E
E
E
E
E
E
E
D
D
Ex
Ex Ex
Ex Ex Ex
Ex Ex Ex Ex
Ex Ex
Ex Ex
H RD
S 3RD ST
4TH ST
PARKING
AREA
BLDG NO. 20
B38
FUEL
PUMPS
STORM GRATE
INLET TO REMAIN
12" CONC. PIPE
TO REMAIN
STORM MANHOLE
TO REMAIN
12" CONC. PIPE
TO REMAIN
HYDRANT AND
BOLLARDS TO REMAIN
SANITARY SEWER TO REMAIN
This is the start of the file's text. The full file is on GovTribe.