This appears to be an asbestos inspection report attachment to a Statement of Work for EHRM Infrastructure Upgrades at the VA Loch Raven facility in Maryland. However, the file extension indicates it is a Microsoft Excel spreadsheet format, and without access to the actual contents of the file, I cannot provide specific details about the asbestos findings or inspection results. The file is related to a Department of Veterans Affairs Technology Acquisition Center solicitation (36C77624R0114_1) for construction services supporting Electronic Health Record Modernization (EHRM) infrastructure upgrades.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LR1
| Campus Site | Area Designation | Building Number | Floor | Room Number | Category (AHERA Class) | Material Type | Location | Quantity | Unit of Measure | Condition | Comments | Asbestos Content | Access | Hazard Ranking | Response Action | Drawing Number | Photo Number | Number |
| Loch Raven | 01 | CLC | Ext | West side of extension | Miscellaneous | White exterior window caulk | West wall | 2 @6'x12' | Count | Good | No asbestos detected | High | N/a | N/A | 1 | |||
| Loch Raven | 01 | CLC | Ext | West side of extension | Miscellaneous | White exterior window caulk | West wall | 8 @6'x18' | Count | Good | No asbestos detected | High | N/a | N/A | 2 | |||
| Loch Raven | 01 | CLC | Ext | West side of extension | Miscellaneous | Stone wall paneling caulk | West wall | 175 | LF | Good | No asbestos detected | High | N/a | N/A | 3 | |||
| Loch Raven | 02 | CLC | Ext | North wall | Miscellaneous | White exterior window caulk | North wall | 1 @6'x15' | Count | Good | No asbestos detected | High | N/a | N/A | 4 | |||
| Loch Raven | 02 | CLC | Ext | North wall | Miscellaneous | White exterior door system caulk | North wall | 1 @8'x9' | Count | Good | No asbestos detected | High | N/a | N/A | 5 | |||
| Loch Raven | 03 | CLC | Ext | East wall North side exterior | Miscellaneous | White exterior window caulk | East wall | 44 @3'x6' | Count | Good | No asbestos detected | High | N/a | N/A | 6 | |||
| Loch Raven | 03 | CLC | Ext | East wall North side exterior | Miscellaneous | Exterior door caulk | East wall | 1 @4'x7' | Count | Good | No asbestos detected | High | N/a | N/A | 7 | |||
| Loch Raven | 03 | CLC | Ext | East wall North side exterior | Miscellaneous | Stone wall paneling caulk | East wall | 2 @150 | LF | Good | No asbestos detected | High | N/a | N/A | 8 | |||
| Loch Raven | 04 | CLC | Ext | North side of extension | Miscellaneous | Stone wall paneling caulk | North wall at stone paneling | 80 | LF | Good | No asbestos detected | High | N/a | N/A | 9 | |||
| Loch Raven | 04 | CLC | Ext | North side of extension | Miscellaneous | Door system caulk | North wall | 1 @4'x7' | Count | Good | No asbestos detected | High | N/a | N/A | 10 | |||
| Loch Raven | 04 | CLC | Ext | North side of extension | Miscellaneous | White window system caulk | North wall | 1 @3'x5' | Count | Good | No asbestos detected | High | N/a | N/A | 11 | |||
| Loch Raven | 05 | CLC | Ext | East side extension | Miscellaneous | White door system caulk | Northeast wall | 1 @10'x10' | Count | Good | No asbestos detected | High | N/a | N/A | 12 | |||
| Loch Raven | 05 | CLC | Ext | East side extension | Miscellaneous | White exterior window caulk | Northeast wall | 11 @3'x4' | Count | Good | No asbestos detected | High | N/a | N/A | 13 | |||
| Loch Raven | 05 | CLC | Ext | East side extension | Miscellaneous | White exterior window caulk | Northeast wall | 23 @2'x3' | Count | Good | No asbestos detected | High | N/a | N/A | 14 | |||
| Loch Raven | 05 | CLC | Ext | East side extension | Miscellaneous | White stone wall paneling caulk | Northeast wall | 2 @1451 | LF | Good | No asbestos detected | High | N/a | N/A | 15 | |||
| Loch Raven | 05 | CLC | Ext | Southeast Main Entry | Miscellaneous | White exterior window caulk | East wall | 6 @4'x5' | Count | Good | No asbestos detected | High | N/a | N/A | 16 | |||
| Loch Raven | 05 | CLC | Ext | Southeast Main Entry | Miscellaneous | White exterior door caulk | East wall | 1 @8'x7' | Count | Good | No asbestos detected | High | N/a | N/A | 17 | |||
| Loch Raven | 05 | CLC | Ext | Southeast Main Entry | Miscellaneous | White stone wall paneling caulk | Southeast wall | 3 @150 | LF | Good | No asbestos detected | High | N/a | N/A | 18 | |||
| Loch Raven | CLC | Ext | Southeast Main Entry | Miscellaneous | Good | No asbestos detected | N/a | N/A | 19 | |||||||||
| Loch Raven | 05 | CLC | Ext | Southeast Main Entry | Miscellaneous | White exterior window caulk | Southeast wall | 25 @3'x6' | Count | Good | No asbestos detected | High | N/a | N/A | 20 | |||
| Loch Raven | 06 | CLC | Ext | South Wing | Miscellaneous | White exterior window caulk | East and South wall | 65 @6'x3' | Count | Good | No asbestos detected | High | N/a | N/A | 21 | |||
| Loch Raven | 06 | CLC | Ext | South Wing | Miscellaneous | White exterior door caulk | East and South wall | 2 @8'x7' | Count | Good | No asbestos detected | High | N/a | N/A | 22 | |||
| Loch Raven | 06 | CLC | Ext | South Wing | Miscellaneous | White exterior door caulk | East and South wall | 1 @4'x7' | Count | Good | No asbestos detected | High | N/a | N/A | 23 | |||
| Loch Raven | 06 | CLC | Ext | South Wing | Miscellaneous | White stone paneling caulk | East and South wall | 3 @290 | LF | Good | No asbestos detected | High | N/a | N/A | 24 | |||
| Loch Raven | 06 | CLC | Ext | South Wing | Miscellaneous | White exterior window caulk | South wall | 12 @3'x6' | Count | Good | No asbestos detected | High | N/a | N/A | 25 | |||
| Loch Raven | 06 | CLC | Ext | South Wing | Miscellaneous | White exterior door caulk | South wall | 1 @3'x7' | Count | Good | No asbestos detected | High | N/a | N/A | 26 | |||
| Loch Raven | 07 | CLC | Ext | West side of old building | Miscellaneous | White exterior window caulk system | South and West wall | 118 @3'x6' | Count | Good | No asbestos detected | High | N/a | N/A | 27 | |||
| Loch Raven | 07 | CLC | Ext | West side of old building | Miscellaneous | White exterior door caulk | South and West wall | 5 @8'x9' | Count | Good | No asbestos detected | High | N/a | N/A | 28 | |||
| Loch Raven | 07 | CLC | Ext | West side of old building | Miscellaneous | White stone paneling caulk | South and West wall | 3 @300 | LF | Good | No asbestos detected | High | N/a | N/A | 29 | |||
| Loch Raven | 08 | CLC | Ext | Northwest side of old building | Miscellaneous | White exterior window caulk | North wall and East wall | 28 @3'x6' | Count | Good | No asbestos detected | High | N/a | N/A | 30 | |||
| Loch Raven | 08 | CLC | Ext | Northwest side of old building | Miscellaneous | White exterior door caulk | East wall and North wall | 2 @4'x7' | Count | Good | No asbestos detected | High | N/a | N/A | 31 | |||
| Loch Raven | 08 | CLC | Ext | Northwest side of old building | Miscellaneous | White stone paneling caulk | Throughout | 3 @300 | LF | Good | No asbestos detected | High | N/a | N/A | 32 | |||
| Loch Raven | 08 | CLC | Ext | Throughout roof | Miscellaneous | Roof shingles | Throughout | 45,000 | SF | Good | Assumed ACM | Low | 1 | N/A | 33 | |||
| Loch Raven | 08 | CLC | Ext | Northwest side of old building | Miscellaneous | White exterior window caulk | East wall | 89 @3'x6' | Count | Good | No asbestos detected | High | N/a | N/A | 34 | |||
| Loch Raven | 01 | CLC | Ext | Upper Mechanical Room | Miscellaneous | Tan duct pin mastic | Throughout | 50 | SF | Good | No asbestos detected | Low | N/a | H-CLC-4 | 35 | |||
| Loch Raven | M-01 | CLC | Ext | Upper Mechanical Room | Miscellaneous | White pipe seam sealant | Throughout | 2200 | LF | Good | No asbestos detected | Low | N/a | H-CLC-4 | 36 | |||
| Loch Raven | M-01 | CLC | Ext | Upper Mechanical Room | Surfacing | Spray-on fireproofing | Throughout I-beams | 750 | SF | Good | No asbestos detected | Low | N/a | H-CLC-4 | 37 | |||
| Loch Raven | M-01 | CLC | Ext | Upper Mechanical Room | Miscellaneous | Gray duct seam caulk | Throughout 2'x6' duct | 100 | LF | Good | No asbestos detected | Low | N/a | H-CLC-4 | 38 | |||
| Loch Raven | M-01 | CLC | Ext | Upper Mechanical Room | Miscellaneous | Transite paneling | Throughout ceiling | 5600 | SF | Good | No asbestos detected | Low | N/a | H-CLC-4 | 39 | |||
| Loch Raven | M-01 | CLC | Ext | Upper Mechanical Room | Miscellaneous | Drywall | Throughout | 1000 | SF | Good | No asbestos detected | High | N/a | H-CLC-4 | 40 | |||
| Loch Raven | M-01 | CLC | Ext | Upper Mechanical Room | Miscellaneous | Joint Compound | Throughout | 1000 | SF | Good | No asbestos detected | High | N/a | H-CLC-4 | 41 | |||
| Loch Raven | M-01 | CLC | Ext | Upper Mechanical Room | Miscellaneous | White duct seam sealant on canvas | Throughout | 640 | LF | Good | No asbestos detected | Low | N/a | H-CLC-4 | 42 | |||
| Loch Raven | M-01 | CLC | Ext | Upper Mechanical Room | Miscellaneous | Red fire stop | Throughout | 30 | SF | Good | No asbestos detected | Low | N/a | H-CLC-4 | 43 | |||
| Loch Raven | B-01 | CLC | B | CG-2/3 Hallway | Miscellaneous | 12"x12" Pink with pink and blue specks floor tile | Throughout floor | 840 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 44 | |||
| Loch Raven | B-01 | CLC | B | CG-2/3 Hallway | Miscellaneous | 12"x12" Red mottled floor tile | Throughout floor | 280 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 45 | |||
| Loch Raven | B-01 | CLC | B | CG-2/3 Hallway | Miscellaneous | Tan floor tile mastic | Throughout floor | 1120 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 46 | |||
| Loch Raven | B-01 | CLC | B | CG-2/3 Hallway | Miscellaneous | Tan baseboard mastic | All walls | 296 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 47 | |||
| Loch Raven | B-01 | CLC | B | CG-2/3 Hallway | Miscellaneous | 2'x4' Fissured pinhole ceiling | Throughout ceiling | 1120 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 48 | |||
| Loch Raven | B-01 | CLC | B | CG-2/3 Hallway | Surfacing | Spray-on fireproofing | Above drop ceiling | 250 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 49 | |||
| Loch Raven | B-01 | CLC | B | CG-2/3 Hallway | Miscellaneous | White pipe seam sealant | Above drop ceiling | 200 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 50 | |||
| Loch Raven | B-01 | CLC | B | CG-2/3 Hallway | Miscellaneous | White pipe seam sealant | Above drop ceiling | 30 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 51 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | 12"x12" Pink with pink and blue specks floor tile | Throughout floor | 912 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 52 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | 12"x12" Red mottled floor tile | Throughout floor | 1216 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 53 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | Tan floor tile mastic | Throughout floor | 1216 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 54 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | Tan baseboard mastic | All walls | 320 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 55 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | 2'x4' Fissured pinhole ceiling | Throughout ceiling | 1216 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 56 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Surfacing | Spray-on fireproofing | Above drop ceiling | 300 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 57 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | Gray interior window caulk | North wall | 4 @4'x6' | Window | Good | No asbestos detected | High | N/a | H-CLC-1 | 58 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 300 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 59 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | Brown duct seam sealant | Above drop ceiling | 325 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 60 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | White pipe seam sealant | Above drop ceiling | 180 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 61 | |||
| Loch Raven | B-02 | CLC | B | CG-5/4/7/8 Hallway | Miscellaneous | White duct penetration caulk | Above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 62 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Miscellaneous | Ceramic tile grout | Throughout floor | 552 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 63 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Miscellaneous | Ceramic tile grout | Throughout floor | 552 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 64 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Miscellaneous | 2'x4' Fissured pinhole ceiling | Throughout ceiling | 280 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 65 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Miscellaneous | Drywall | All walls | 816 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 66 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Miscellaneous | Joint Compound | All walls | 816 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 67 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Surfacing | Spray-on fireproofing | Above drop ceiling | 70 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 68 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Miscellaneous | White pipe seam sealant | Above drop ceiling | 30 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 69 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 25 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 70 | |||
| Loch Raven | B-03 | CLC | B | Room G-18 | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 71 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Miscellaneous | Ceramic tile grout | Throughout floor | 552 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 72 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Miscellaneous | Ceramic tile grout | Throughout floor | 552 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 73 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Miscellaneous | 2'x4' Fissured pinhole ceiling | Throughout ceiling | 280 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 74 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Miscellaneous | Drywall | All walls | 816 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 75 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Miscellaneous | Joint Compound | All walls | 816 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 76 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Surfacing | Spray-on fireproofing | Above drop ceiling | 70 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 77 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Miscellaneous | White pipe seam sealant | Above drop ceiling | 30 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 78 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 25 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 79 | |||
| Loch Raven | B-04 | CLC | B | Room G-20 | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 80 | |||
| Loch Raven | B-05 | CLC | B | Utility Room 003 | Surfacing | Spray-on fireproofing | Throughout ceiling deck | 192 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 81 | |||
| Loch Raven | B-05 | CLC | B | Utility Room 003 | Miscellaneous | Drywall | At bulkhead | 150 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 82 | |||
| Loch Raven | B-05 | CLC | B | Utility Room 003 | Miscellaneous | Joint Compound | At bulkhead | 150 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 83 | |||
| Loch Raven | B-05 | CLC | B | Utility Room 003 | Miscellaneous | White pipe seam sealant | Throughout room | 60 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 84 | |||
| Loch Raven | B-05 | CLC | B | Utility Room 003 | Miscellaneous | Gray metal duct seam sealant | Throughout room | 30 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 85 | |||
| Loch Raven | B-05 | CLC | B | Utility Room 003 | Miscellaneous | Red fire stop | Throughout room | 10 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 86 | |||
| Loch Raven | B-06 | CLC | B | Extension Storage Room 006 | Miscellaneous | Good | N/a | H-CLC-1 | 87 | |||||||||
| Loch Raven | B-06 | CLC | B | Extension Storage Room 006 | Miscellaneous | Gray pipe breaching | South wall | 2 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 88 | |||
| Loch Raven | B-06 | CLC | B | Extension Storage Room 006 | Miscellaneous | White pipe seam sealant | Throughout room | 25 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 89 | |||
| Loch Raven | B-06 | CLC | B | Extension Storage Room 006 | Miscellaneous | Red fire stop | Throughout room | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 90 | |||
| Loch Raven | B-07 | CLC | B | Lobby 001 | Miscellaneous | 2'x2' Gray with brown specks floor tile | Throughout floor | 320 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 91 | |||
| Loch Raven | B-07 | CLC | B | Lobby 001 | Miscellaneous | Tan floor tile mastic | Throughout floor | 320 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 92 | |||
| Loch Raven | B-07 | CLC | B | Lobby 001 | Miscellaneous | Tan baseboard mastic | All walls | 96 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 93 | |||
| Loch Raven | B-07 | CLC | B | Lobby 001 | Miscellaneous | 2'x2' Crater pinhole ceiling tile | Throughout ceiling | 320 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 94 | |||
| Loch Raven | B-07 | CLC | B | Lobby 001 | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 95 | |||
| Loch Raven | B-07 | CLC | B | Lobby 001 | Surfacing | Spray-on fireproofing | Above drop ceiling | 320 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 96 | |||
| Loch Raven | B-07 | CLC | B | Lobby 001 | Miscellaneous | Red fire stop | Above drop ceiling | 10 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 97 | |||
| Loch Raven | B-08 | CLC | B | Electrical 004 | Surfacing | Spray-on fireproofing | Throughout | 288 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 98 | |||
| Loch Raven | B-08 | CLC | B | Electrical 004 | Miscellaneous | Red fire stop | Throughout | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 99 | |||
| Loch Raven | B-09 | CLC | B | Elevator Machine 007 | Surfacing | Spray-on fireproofing | Throughout | 346 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 100 | |||
| Loch Raven | B-09 | CLC | B | Elevator Machine 007 | Miscellaneous | Red fire stop | Throughout | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 101 | |||
| Loch Raven | B-09 | CLC | B | Elevator Machine 007 | Miscellaneous | Gray pipe breaching | North wall | 2 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 102 | |||
| Loch Raven | B-10 | CLC | B | Storage 005 | Surfacing | Spray-on fireproofing | Throughout | 325 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 103 | |||
| Loch Raven | B-10 | CLC | B | Storage 005 | Miscellaneous | Gray metal duct seam sealant | Throughout | 50 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 104 | |||
| Loch Raven | B-10 | CLC | B | Storage 005 | Miscellaneous | White pipe seam sealant | Throughout | 40 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 105 | |||
| Loch Raven | B-10 | CLC | B | Storage 005 | Miscellaneous | Red fire stop | Throughout | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 106 | |||
| Loch Raven | B-11 | CLC | B | Room G-9 | Miscellaneous | White duct seam sealant on foil | Throughout room | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 107 | |||
| Loch Raven | B-11 | CLC | B | Room G-9 | Miscellaneous | Red fire stop | Throughout room | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 108 | |||
| Loch Raven | B-11 | CLC | B | Room G-9 | Surfacing | Spray-on fireproofing | Throughout room | 50 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 109 | |||
| Loch Raven | B-11 | CLC | B | Room G-9 | Miscellaneous | Gray metal duct seam sealant | Throughout room | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 110 | |||
| Loch Raven | B-11 | CLC | B | Room G-9 | Miscellaneous | Brown duct seam sealant | Throughout room | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 111 | |||
| Loch Raven | B-12 | CLC | B | Room G-10E | Miscellaneous | Tan baseboard mastic | All walls | 44 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 114 | |||
| Loch Raven | B-12 | CLC | B | Room G-10E | Miscellaneous | 2'x4' Drywall ceiling tile | Throughout ceiling | 117 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 115 | |||
| Loch Raven | B-12 | CLC | B | Room G-10E | Miscellaneous | Drywall | All walls | 528 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 116 | |||
| Loch Raven | B-12 | CLC | B | Room G-10E | Miscellaneous | Joint Compound | All walls | 528 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 117 | |||
| Loch Raven | B-12 | CLC | B | Room G-10E | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 15 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 118 | |||
| Loch Raven | B-12 | CLC | B | Room G-10E | Miscellaneous | White pipe seam sealant | Above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 119 | |||
| Loch Raven | B-12 | CLC | B | Room G-10E | Surfacing | Spray-on fireproofing | Above drop ceiling | 50 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 120 | |||
| Loch Raven | B-13 | CLC | B | Room G-10C | Miscellaneous | Ceramic tile grout | Throughout floor | 430 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 121 | |||
| Loch Raven | B-13 | CLC | B | Room G-10C | Miscellaneous | Ceramic tile grout | Throughout walls | 430 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 122 | |||
| Loch Raven | B-13 | CLC | B | Room G-10C | Miscellaneous | 2'x4' Fissured pinhole ceiling tile | Throughout ceiling | 50 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 123 | |||
| Loch Raven | B-13 | CLC | B | Room G-10C | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 5 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 124 | |||
| Loch Raven | B-13 | CLC | B | Room G-10C | Surfacing | Spray-on fireproofing | Above drop ceiling | 20 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 125 | |||
| Loch Raven | B-14 | CLC | B | Room G-10D | Miscellaneous | Ceramic tile grout | Throughout floor | 96 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 126 | |||
| Loch Raven | B-14 | CLC | B | Room G-10D | Miscellaneous | Ceramic tile grout | Throughout walls | 96 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 127 | |||
| Loch Raven | B-14 | CLC | B | Room G-10D | Miscellaneous | 2'x2' Textured ceiling tile | Throughout ceiling | 96 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 128 | |||
| Loch Raven | B-14 | CLC | B | Room G-10D | Miscellaneous | Red fire stop | East wall and above drop ceiling | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 129 | |||
| Loch Raven | B-14 | CLC | B | Room G-10D | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 130 | |||
| Loch Raven | B-14 | CLC | B | Room G-10D | Surfacing | Spray-on fireproofing | Above drop ceiling | 30 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 131 | |||
| Loch Raven | B-14 | CLC | B | Room G-10D | Miscellaneous | Drywall | East column above drop ceiling | 16 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 132 | |||
| Loch Raven | B-14 | CLC | B | Room G-10D | Miscellaneous | Joint Compound | East column above drop ceiling | 16 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 133 | |||
| Loch Raven | B-15 | CLC | B | Room G-10A | Miscellaneous | Ceramic tile grout | Throughout floor | 144 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 134 | |||
| Loch Raven | B-15 | CLC | B | Room G-10A | Miscellaneous | Ceramic tile grout | Throughout walls | 144 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 135 | |||
| Loch Raven | B-15 | CLC | B | Room G-10A | Miscellaneous | 2'x4' Fissured pinhole ceiling tile | Throughout ceiling | 40 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 136 | |||
| Loch Raven | B-15 | CLC | B | Room G-10A | Surfacing | Spray-on fireproofing | Above drop ceiling | 20 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 137 | |||
| Loch Raven | B-15 | CLC | B | Room G-10A | Miscellaneous | White pipe seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 138 | |||
| Loch Raven | B-15 | CLC | B | Room G-10A | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 139 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Miscellaneous | Ceramic tile grout | Throughout floor | 72 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 140 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Miscellaneous | 2'x4' Fissured pinhole ceiling tile | Throughout ceiling | 72 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 141 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Miscellaneous | Drywall | All walls | 432 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 142 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Miscellaneous | Joint Compound | All walls | 432 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 143 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Surfacing | Spray-on fireproofing | Above drop ceiling | 30 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 144 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Miscellaneous | Tan baseboard mastic | All walls | 36 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 145 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Miscellaneous | Brown duct seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 146 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Miscellaneous | White pipe seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 147 | |||
| Loch Raven | B-16 | CLC | B | West Kitchen Office | Miscellaneous | Gray duct seam caulk | Above drop ceiling | 5 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 148 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Miscellaneous | Ceramic tile grout | Throughout floor and walls | 792 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 149 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Miscellaneous | Ceramic tile grout | Throughout floor and walls | 792 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 150 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Miscellaneous | 2'x4' Drywall ceiling tile | Throughout ceiling | 168 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 151 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Surfacing | Spray-on fireproofing | Above drop ceiling | 50 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 152 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Miscellaneous | Brown duct seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 153 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 15 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 154 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 155 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Miscellaneous | White pipe seam sealant | Above drop ceiling | 50 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 156 | |||
| Loch Raven | B-17 | CLC | B | Room G-10F | Miscellaneous | Red fire stop | Above drop ceiling | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 157 | |||
| Loch Raven | B-18 | CLC | B | Walk-in Cart Storage Freezer | Miscellaneous | Ceramic tile grout | Throughout floor | 264 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 158 | |||
| Loch Raven | B-18 | CLC | B | Walk-in Cart Storage Freezer | Miscellaneous | White pipe seam sealant (assumed) | Above freezer insulation | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 159 | |||
| Loch Raven | B-18 | CLC | B | Walk-in Cart Storage Freezer | Surfacing | Spray-on fireproofing (assumed) | Above freezer insulation | 40 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 160 | |||
| Loch Raven | B-18 | CLC | B | Walk-in Cart Storage Freezer | Miscellaneous | Red fire stop (assumed) | Above freezer insulation | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 161 | |||
| Loch Raven | B-19 | CLC | B | Walk-in Freezer | Miscellaneous | Ceramic tile grout | Throughout floor | 264 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 162 | |||
| Loch Raven | B-19 | CLC | B | Walk-in Freezer | Miscellaneous | White pipe seam sealant (assumed) | Above freezer insulation | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 163 | |||
| Loch Raven | B-19 | CLC | B | Walk-in Freezer | Surfacing | Spray-on fireproofing (assumed) | Above freezer insulation | 40 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 164 | |||
| Loch Raven | B-19 | CLC | B | Walk-in Freezer | Miscellaneous | Red fire stop (assumed) | Above freezer insulation | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 165 | |||
| Loch Raven | B-20 | CLC | B | Kitchen Room G-10 | Miscellaneous | Ceramic tile grout | Throughout floor | 6548 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 166 | |||
| Loch Raven | B-20 | CLC | B | Kitchen Room G-10 | Miscellaneous | Ceramic tile grout | Throughout walls | 6548 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 167 | |||
| Loch Raven | B-20 | CLC | B | Kitchen Room G-10 | Miscellaneous | 2'x4' Smooth ceiling panels | Throughout ceiling | 3148 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 168 | |||
| Loch Raven | B-20 | CLC | B | Kitchen Room G-10 | Surfacing | Spray-on fireproofing | Above drop ceiling | 1425 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 169 | |||
| Loch Raven | B-20 | CLC | B | Kitchen Room G-10 | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 250 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 170 | |||
| Loch Raven | B-20 | CLC | B | Kitchen Room G-10 | Miscellaneous | White pipe seam sealant | Above drop ceiling | 300 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 171 | |||
| Loch Raven | B-21 | CLC | B | Room G-12 | Miscellaneous | 2'x4' Fissured pinhole ceiling tile | Throughout ceiling | 80 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 172 | |||
| Loch Raven | B-21 | CLC | B | Room G-12 | Surfacing | Spray-on fireproofing | Above drop ceiling | 60 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 173 | |||
| Loch Raven | B-21 | CLC | B | Room G-12 | Miscellaneous | Red fire stop | Above drop ceiling | 2 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 174 | |||
| Loch Raven | B-21 | CLC | B | Room G-12 | Miscellaneous | Tan baseboard mastic | All walls | 36 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 175 | |||
| Loch Raven | B-22 | CLC | B | Room G-11 | Miscellaneous | 12"x12" Pink with pink and blue streaks floor tile | Throughout floor | 160 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 176 | |||
| Loch Raven | B-22 | CLC | B | Room G-11 | Miscellaneous | Tan floor tile mastic | Throughout floor | 160 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 177 | |||
| Loch Raven | B-22 | CLC | B | Room G-11 | Miscellaneous | Tan baseboard mastic | All walls | 52 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 178 | |||
| Loch Raven | B-22 | CLC | B | Room G-11 | Miscellaneous | 2'x4' Crater pinhole ceiling tile | Throughout ceiling | 160 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 179 | |||
| Loch Raven | B-22 | CLC | B | Room G-11 | Surfacing | Spray-on fireproofing | Above drop ceiling | 50 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 180 | |||
| Loch Raven | B-22 | CLC | B | Room G-11 | Miscellaneous | Red fire stop | Above drop ceiling | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 181 | |||
| Loch Raven | B-22 | CLC | B | Room G-11 | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 182 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Miscellaneous | 12"x12" Pink with pink and blue streaks floor tile | Throughout floor | 192 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 183 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Miscellaneous | Tan floor tile mastic | Throughout floor | 192 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 184 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Miscellaneous | Tan baseboard mastic | All walls | 56 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 185 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Miscellaneous | 2'x4' Drywall ceiling tile | Throughout ceiling | 192 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 186 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Surfacing | Spray-on fireproofing | Above drop ceiling | 50 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 187 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling and linen shoot | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 188 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 5 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 189 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Miscellaneous | Red fire stop | Above drop ceiling | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 190 | |||
| Loch Raven | B-23 | CLC | B | Room G-13 | Miscellaneous | Fire door | West wall | 1 @4'x7' | Door | Good | Assumed ACM | Low | 1 | O&M | H-CLC-1 | 191 | ||
| Loch Raven | B-24 | CLC | B | Room G-14 | Surfacing | Spray-on fireproofing | Above drop ceiling | 10 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 193 | |||
| Loch Raven | B-24 | CLC | B | Room G-14 | Miscellaneous | Red fire stop | Above drop ceiling | 2 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 194 | |||
| Loch Raven | B-25 | CLC | B | Room G-16 | Miscellaneous | 12'x12' Pink with pink and blue streaks floor tile | Throughout floor | 120 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 195 | |||
| Loch Raven | B-25 | CLC | B | Room G-16 | Miscellaneous | Tan floor tile mastic | Throughout floor | 120 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 196 | |||
| Loch Raven | B-25 | CLC | B | Room G-16 | Miscellaneous | Tan baseboard mastic | All walls | 44 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 197 | |||
| Loch Raven | B-25 | CLC | B | Room G-16 | Miscellaneous | 2'x4' Crater pinhole ceiling tile | Throughout ceiling | 120 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 198 | |||
| Loch Raven | B-25 | CLC | B | Room G-16 | Surfacing | Spray-on fireproofing | Above drop ceiling | 40 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 199 | |||
| Loch Raven | B-25 | CLC | B | Room G-16 | Miscellaneous | Red fire stop | Above drop ceiling | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 200 | |||
| Loch Raven | B-25 | CLC | B | Room G-16 | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 201 | |||
| Loch Raven | B-25 | CLC | B | Room G-16 | Miscellaneous | Fire door | At entrance | 1 | Door | Good | 1 @ 3'x7' | Assumed ACM | Low | |||||
| Loch Raven | B-26 | CLC | B | Room G-15 | Surfacing | Spray-on fireproofing | At ceiling deck throughout | 75 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 202 | |||
| Loch Raven | B-26 | CLC | B | Room G-15 | Miscellaneous | Gray metal duct seam sealant | At ceiling deck throughout | 30 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 203 | |||
| Loch Raven | B-26 | CLC | B | Room G-15 | Miscellaneous | Red fire stop | At ceiling deck throughout | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 204 | |||
| Loch Raven | B-27 | CLC | B | Room G-17 | Surfacing | Spray-on fireproofing | Throughout ceiling deck | 75 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 205 | |||
| Loch Raven | B-27 | CLC | B | Room G-17 | Miscellaneous | Red fire stop | Throughout walls | 5 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 206 | |||
| Loch Raven | B-27 | CLC | B | Room G-17 | Miscellaneous | Gray pipe penetration caulk | North wall | 2 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 207 | |||
| Loch Raven | B-27 | CLC | B | Room G-17 | Miscellaneous | Tan baseboard mastic | All walls | 80 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 208 | |||
| Loch Raven | B-28 | CLC | B | Room G-19 | Surfacing | Spray-on fireproofing | Throughout ceiling deck | 350 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 209 | |||
| Loch Raven | B-28 | CLC | B | Room G-19 | Miscellaneous | White pipe seam sealant | Throughout | 780 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 210 | |||
| Loch Raven | B-28 | CLC | B | Room G-19 | Miscellaneous | Red fire stop | Throughout all walls | 10 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 211 | |||
| Loch Raven | B-28 | CLC | B | Room G-19 | Miscellaneous | Rope gaskets | On boilers | 4 | Units | Good | No asbestos detected | Low | N/a | H-CLC-1 | 212 | |||
| Loch Raven | B-28 | CLC | B | Room G-19 | Miscellaneous | Tan baseboard mastic | All walls | 140 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 213 | |||
| Loch Raven | B-29 | CLC | B | Room G-22 | Miscellaneous | 12"x12" Pink with pink and blue streaks floor tile | Throughout floor | 320 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 214 | |||
| Loch Raven | B-29 | CLC | B | Room G-22 | Miscellaneous | Tan floor tile mastic | Throughout floor | 320 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 215 | |||
| Loch Raven | B-29 | CLC | B | Room G-22 | Miscellaneous | Tan baseboard mastic | All walls | 72 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 216 | |||
| Loch Raven | B-29 | CLC | B | Room G-22 | Miscellaneous | 2'x4' Crater pinhole ceiling tile | Throughout ceiling | 320 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 217 | |||
| Loch Raven | B-29 | CLC | B | Room G-22 | Surfacing | Spray-on fireproofing | Above drop ceiling | 40 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 218 | |||
| Loch Raven | B-29 | CLC | B | Room G-22 | Miscellaneous | Red fire stop | Above drop ceiling | 2 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 219 | |||
| Loch Raven | B-29 | CLC | B | Room G-22 | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 15 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 220 | |||
| Loch Raven | B-29 | CLC | B | Room G-22 | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 15 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 221 | |||
| Loch Raven | B-30 | CLC | B | Room G-10E | Miscellaneous | Ceramic tile grout | Throughout walls and floor | 496 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 222 | |||
| Loch Raven | B-30 | CLC | B | Room G-10E | Miscellaneous | 2'x4' Smooth paneling ceiling tile | Throughout ceiling | 96 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 223 | |||
| Loch Raven | B-30 | CLC | B | Room G-10E | Surfacing | Spray-on fireproofing | Above drop ceiling | 30 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 224 | |||
| Loch Raven | B-30 | CLC | B | Room G-10E | Miscellaneous | White duct seam sealant on foil | Above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 225 | |||
| Loch Raven | B-30 | CLC | B | Room G-10E | Miscellaneous | White pipe seam sealant | Above drop ceiling | 15 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 226 | |||
| Loch Raven | B-31 | CLC | B | Loading Dock | Miscellaneous | Textured ceiling | Throughout loading dock ceiling | 500 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 227 | |||
| Loch Raven | B-31 | CLC | B | Loading Dock | Miscellaneous | Red fire stop | Above textured ceiling | 10 | SF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 228 | |||
| Loch Raven | B-31 | CLC | B | Loading Dock | Miscellaneous | Exterior window caulk | North/East walls | 4 @4'x6' | Window | Good | No asbestos detected | High | N/a | H-CLC-1 | 229 | |||
| Loch Raven | B-31 | CLC | B | Loading Dock | Miscellaneous | White base caulk | Floor and ceiling lining | 40 | LF | Good | No asbestos detected | Low | N/a | H-CLC-1 | 230 | |||
| Loch Raven | B-32 | CLC | B | Elevator 1 | Miscellaneous | 12"x12" Red terrazo tile | Throughout floor | 70 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 231 | |||
| Loch Raven | B-32 | CLC | B | Elevator 1 | Miscellaneous | Elevator cab insulation | Throughout elevator | 376 | SF | Good | Assumed ACM | High | 1 | O&M | H-CLC-1 | 232 | ||
| Loch Raven | B-32 | CLC | B | Elevator 1 | Miscellaneous | Elevator door insulation | North wall | 1 @4'x7' | Door | Good | Assumed ACM | Low | 1 | O&M | H-CLC-1 | 233 | ||
| Loch Raven | B-33 | CLC | B | Elevator 2 | Miscellaneous | 12"x12" Red terrazo tile | Throughout floor | 70 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 234 | |||
| Loch Raven | B-33 | CLC | B | Elevator 2 | Miscellaneous | Elevator cab insulation | Throughout elevator | 376 | SF | Good | Assumed ACM | Low | 1 | O&M | H-CLC-1 | 235 | ||
| Loch Raven | B-33 | CLC | B | Elevator 2 | Miscellaneous | Elevator door insulation | North wall | 1 @4'x7' | Door | Good | Assumed ACM | High | 1 | O&M | H-CLC-1 | 236 | ||
| Loch Raven | B-34 | CLC | B | Elevator 3 | Miscellaneous | 2'x2' White with brown specks floor tile | Throughout floor | 40 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 237 | |||
| Loch Raven | B-34 | CLC | B | Elevator 3 | Miscellaneous | Elevator cab insulation | Throughout elevator | 274 | SF | Good | Assumed ACM | Low | 1 | O&M | H-CLC-1 | 238 | ||
| Loch Raven | B-34 | CLC | B | Elevator 3 | Miscellaneous | Elevator door insulation | East wall | 1 @4'x7' | Door | Good | Assumed ACM | Low | 1 | O&M | H-CLC-1 | 239 | ||
| Loch Raven | B-35 | CLC | B | Elevator 4 | Miscellaneous | 2'x2' White with brown specks floor tile | Throughout floor | 40 | SF | Good | No asbestos detected | High | N/a | H-CLC-1 | 240 | |||
| Loch Raven | B-35 | CLC | B | Elevator 4 | Miscellaneous | Elevator cab insulation | Throughout elevator | 274 | SF | Good | Assumed ACM | Low | 1 | O&M | H-CLC-1 | 241 | ||
| Loch Raven | B-35 | CLC | B | Elevator 4 | Miscellaneous | Elevator door insulation | East wall | 1 @4'x7' | Door | Good | Assumed ACM | Low | 1 | O&M | H-CLC-1 | 242 | ||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | 2'x2' Textured ceiling tile | Throughout drop ceiling at center shop area | 180 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 243 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | 2'x4' Crater pinhole paneling ceiling | Throughout drop ceiling at perimeter of shop | 80 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 244 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Surfacing | Spray-on fireproofing | On ceiling deck | 75 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 245 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | White duct seam sealant on foil | Throughout above drop ceiling | 30 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 246 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | Drywall | All walls & ceiling | 1252 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 247 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | Joint Compound | All walls & ceiling | 1252 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 248 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | 2'x4' White smooth ceiling panels | Throughout canteen kitchen drop ceiling | 180 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 249 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | Interior white window caulk | Along South wall | 1 @3'x6' | Window | Good | No asbestos detected | High | N/a | H-CLC-2 | 250 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | Interior white window caulk | Along South wall | 1 @8'x6' | Window | Good | No asbestos detected | High | N/a | H-CLC-2 | 251 | |||
| Loch Raven | 1-01 | CLC | 1st | Canteen Storage Room 1A-29 | Miscellaneous | Gray sink undercoating | North wall at kitchenette | 1 @1'x2' | Count | Good | No asbestos detected | Medium | N/a | H-CLC-2 | 252 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | 2'x2' Textured ceiling tile | Throughout drop ceiling | 348 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 253 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | Brown streaked linoleum sheeting | Throughout flooring | 348 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 254 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | Drywall | All walls | 416 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 255 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | Joint Compound | All walls | 416 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 256 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Surfacing | Spray-on fireproofing | On ceiling deck | 70 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 257 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | Gray metal duct seam sealant | Above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 258 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | Tan baseboard mastic | All walls | 100 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 259 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | Good | No asbestos detected | High | N/a | H-CLC-2 | 260 | |||||||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | White pipe seam sealant | Throughout above drop ceiling | 20 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 261 | |||
| Loch Raven | 1-02 | CLC | 1st | Canteen Storage | Miscellaneous | Tan floor tile mastic | Throughout | 348 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 262 | |||
| Loch Raven | 1-03 | CLC | 1st | Canteen Office | Miscellaneous | 2'x2' Textured ceiling tile | Throughout drop ceiling | 60 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 263 | |||
| Loch Raven | 1-03 | CLC | 1st | Canteen Office | Miscellaneous | Brown streaked linoleum sheeting | Throughout floor | 60 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 264 | |||
| Loch Raven | 1-03 | CLC | 1st | Canteen Office | Miscellaneous | Drywall | All walls | 364 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 265 | |||
| Loch Raven | 1-03 | CLC | 1st | Canteen Office | Miscellaneous | Joint Compound | All walls | 364 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 266 | |||
| Loch Raven | 1-03 | CLC | 1st | Canteen Office | Miscellaneous | Gray metal duct seam sealant | Throughout above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 267 | |||
| Loch Raven | 1-03 | CLC | 1st | Canteen Office | Surfacing | Spray-on fireproofing | On ceiling deck | 40 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 268 | |||
| Loch Raven | 1-03 | CLC | 1st | Canteen Office | Miscellaneous | Tan baseboard mastic | All walls | 32 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 269 | |||
| Loch Raven | 1-03 | CLC | 1st | Canteen Office | Miscellaneous | Tan floor tile mastic | Throughout floor | 60 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 270 | |||
| Loch Raven | 1-04 | CLC | 1st | Office | Miscellaneous | 2'x2' Textured ceiling tile | Throughout drop ceiling | 112 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 271 | |||
| Loch Raven | 1-04 | CLC | 1st | Office | Miscellaneous | Yellow carpet mastic | Throughout floor | 112 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 272 | |||
| Loch Raven | 1-04 | CLC | 1st | Office | Miscellaneous | Drywall | All walls | 512 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 273 | |||
| Loch Raven | 1-04 | CLC | 1st | Office | Miscellaneous | Joint Compound | All walls | 512 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 274 | |||
| Loch Raven | 1-04 | CLC | 1st | Office | Surfacing | Spray-on fireproofing | On ceiling deck | 35 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 275 | |||
| Loch Raven | 1-04 | CLC | 1st | Office | Miscellaneous | Gray metal duct seam sealant | Throughout above drop ceiling | 30 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 276 | |||
| Loch Raven | 1-04 | CLC | 1st | Office | Miscellaneous | Tan baseboard mastic | All walls | 43 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 277 | |||
| Loch Raven | 1-05 | CLC | 1st | Computer Lab | Miscellaneous | 2'x2' Textured ceiling tile | Throughout drop ceiling | 320 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 278 | |||
| Loch Raven | 1-05 | CLC | 1st | Computer Lab | Miscellaneous | Yellow carpet mastic | Throughout floor | 320 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 279 | |||
| Loch Raven | 1-05 | CLC | 1st | Computer Lab | Miscellaneous | Drywall | All walls | 720 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 280 | |||
| Loch Raven | 1-05 | CLC | 1st | Computer Lab | Miscellaneous | Joint Compound | All walls | 720 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 281 | |||
| Loch Raven | 1-05 | CLC | 1st | Computer Lab | Surfacing | Spray-on fireproofing | On ceiling deck | 40 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 282 | |||
| Loch Raven | 1-05 | CLC | 1st | Computer Lab | Miscellaneous | Gray metal duct seam sealant | Throughout above drop ceiling | 35 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 283 | |||
| Loch Raven | 1-05 | CLC | 1st | Computer Lab | Miscellaneous | White duct seam sealant on foil | Throughout above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 284 | |||
| Loch Raven | 1-05 | CLC | 1st | Computer Lab | Miscellaneous | Tan baseboard mastic | All walls | 70 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 285 | |||
| Loch Raven | 1-06 | CLC | 1st | Restroom | Miscellaneous | Drywall | All walls & ceiling | 420 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 286 | |||
| Loch Raven | 1-06 | CLC | 1st | Restroom | Miscellaneous | Joint Compound | All walls & ceiling | 420 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 287 | |||
| Loch Raven | 1-06 | CLC | 1st | Restroom | Surfacing | Spray-on fireproofing | On ceiling deck | 15 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 288 | |||
| Loch Raven | 1-06 | CLC | 1st | Restroom | Miscellaneous | Gray metal duct seam sealant | Throughout above drop ceiling on structural steel | 5 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 289 | |||
| Loch Raven | 1-06 | CLC | 1st | Restroom | Miscellaneous | White pipe seam sealant | Throughout above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 290 | |||
| Loch Raven | 1-07 | CLC | 1st | Office Space | Miscellaneous | 2'x2' Textured ceiling tile | Throughout drop ceiling | 276 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 291 | |||
| Loch Raven | 1-07 | CLC | 1st | Office Space | Miscellaneous | Yellow carpet mastic | Throughout floor | 276 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 292 | |||
| Loch Raven | 1-07 | CLC | 1st | Office Space | Miscellaneous | Tan baseboard mastic | All walls | 85 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 293 | |||
| Loch Raven | 1-07 | CLC | 1st | Office Space | Miscellaneous | Drywall | All walls | 1110 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 294 | |||
| Loch Raven | 1-07 | CLC | 1st | Office Space | Miscellaneous | Joint Compound | All walls | 1110 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 295 | |||
| Loch Raven | 1-07 | CLC | 1st | Office Space | Surfacing | Spray-on fireproofing | On ceiling deck | 60 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 296 | |||
| Loch Raven | 1-07 | CLC | 1st | Office Space | Miscellaneous | Gray metal duct seam sealant | Throughout above drop ceiling on structural steel | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 297 | |||
| Loch Raven | 1-07 | CLC | 1st | Office Space | Miscellaneous | White pipe seam sealant | Throughout above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 298 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Miscellaneous | 2'x2' Textured ceiling tile | Throughout drop ceiling | 416 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 299 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Miscellaneous | Brown streaked linoleum sheeting | Throughout floor | 416 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 300 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Miscellaneous | Tan baseboard mastic | All walls | 80 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 301 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Miscellaneous | Drywall | All walls | 900 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 302 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Miscellaneous | Joint Compound | All walls | 900 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 303 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Surfacing | Spray-on fireproofing | On ceiling deck | 75 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 304 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Miscellaneous | Gray metal duct seam sealant | Throughout above drop ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 305 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Miscellaneous | White pipe seam sealant | Throughout above drop ceiling | 40 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 306 | |||
| Loch Raven | 1-08 | CLC | 1st | Supply Room | Miscellaneous | Tan floor tile mastic | Throughout | 416 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 307 | |||
| Loch Raven | 1-09 | CLC | 1st | Corridor | Miscellaneous | 2'x2' Textured ceiling tile | Throughout drop ceiling | 205 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 308 | |||
| Loch Raven | 1-09 | CLC | 1st | Corridor | Miscellaneous | Gray with brown and black linoleum | Throughout floor | 205 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 309 | |||
| Loch Raven | 1-09 | CLC | 1st | Corridor | Miscellaneous | Drywall | All walls | 1200 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 310 | |||
| Loch Raven | 1-09 | CLC | 1st | Corridor | Miscellaneous | Joint Compound | All walls | 1200 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 311 | |||
| Loch Raven | 1-09 | CLC | 1st | Corridor | Miscellaneous | Tan baseboard mastic | All walls | 100 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 312 | |||
| Loch Raven | 1-09 | CLC | 1st | Corridor | Surfacing | Spray-on fireproofing | On ceiling deck | 60 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 313 | |||
| Loch Raven | 1-09 | CLC | 1st | Corridor | Miscellaneous | Gray metal duct seam sealant | Throughout above drop ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 314 | |||
| Loch Raven | 1-09 | CLC | 1st | Corridor | Miscellaneous | Tan floor tile mastic | Throughout | 205 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 315 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Miscellaneous | 2'x2' Textured ceiling tile | Throughout | 395 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 316 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Miscellaneous | Yellow carpet mastic | Throughout floor | 396 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 317 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Miscellaneous | Drywall | All walls | 960 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 318 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Miscellaneous | Joint Compound | All walls | 960 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 319 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Surfacing | Spray-on fireproofing | On ceiling deck | 160 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 320 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Miscellaneous | Tan baseboard mastic | All walls | 42 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 321 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Miscellaneous | Gray metal duct seam sealant | Above ceiling throughout | 30 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 322 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Miscellaneous | White duct seam sealant on foil | Throughout above drop ceiling | 60 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 323 | |||
| Loch Raven | 1-10 | CLC | 1st | Pharmacy 1A-25 | Miscellaneous | White pipe seam sealant | Above ceiling throughout | 50 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 324 | |||
| Loch Raven | 1-11 | CLC | 1st | Storage 1A-28A | Miscellaneous | Drywall | All walls & ceiling | 520 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 325 | |||
| Loch Raven | 1-11 | CLC | 1st | Storage 1A-28A | Miscellaneous | Joint Compound | All walls & ceiling | 520 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 326 | |||
| Loch Raven | 1-11 | CLC | 1st | Storage 1A-28A | Surfacing | Spray-on fireproofing | On ceiling deck | 40 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 327 | |||
| Loch Raven | 1-11 | CLC | 1st | Storage 1A-28A | Miscellaneous | Tan baseboard mastic | All walls | 38 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 328 | |||
| Loch Raven | 1-11 | CLC | 1st | Storage 1A-28A | Miscellaneous | Yellow carpet mastic | Throughout floor | 88 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 329 | |||
| Loch Raven | 1-11 | CLC | 1st | Storage 1A-28A | Miscellaneous | Gray metal duct seam sealant | Above fixed ceiling | 10 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 330 | |||
| Loch Raven | 1-12 | CLC | 1st | Office 1A-28 | Miscellaneous | 2'x2' Textured ceiling tile | Throughout | 168 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 331 | |||
| Loch Raven | 1-12 | CLC | 1st | Office 1A-28 | Miscellaneous | Yellow carpet mastic | Throughout floor | 168 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 332 | |||
| Loch Raven | 1-12 | CLC | 1st | Office 1A-28 | Surfacing | Spray-on fireproofing | On ceiling deck | 40 | SF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 333 | |||
| Loch Raven | 1-12 | CLC | 1st | Office 1A-28 | Miscellaneous | Drywall | All walls | 312 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 334 | |||
| Loch Raven | 1-12 | CLC | 1st | Office 1A-28 | Miscellaneous | Joint Compound | All walls | 312 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 335 | |||
| Loch Raven | 1-12 | CLC | 1st | Office 1A-28 | Miscellaneous | Tan baseboard mastic | All walls | 26 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 336 | |||
| Loch Raven | 1-12 | CLC | 1st | Office 1A-28 | Miscellaneous | Gray metal duct seam sealant | Above ceiling | 20 | LF | Good | No asbestos detected | Low | N/a | H-CLC-2 | 337 | |||
| Loch Raven | 1-113 | CLC | 1st | Activity Center Room 138 | Miscellaneous | 2'x2' Crater pinhole ceiling tile | Throughout | 1656 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 338 | |||
| Loch Raven | 1-113 | CLC | 1st | Activity Center Room 138 | Miscellaneous | Light brown wood patterned linoleum sheeting | Throughout interior floor | 1104 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 339 | |||
| Loch Raven | 1-113 | CLC | 1st | Activity Center Room 138 | Miscellaneous | Dark brown wood patterned linoleum sheeting | Throughout perimeter of floor | 552 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 340 | |||
| Loch Raven | 1-113 | CLC | 1st | Activity Center Room 138 | Miscellaneous | Drywall | All walls | 1700 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 341 | |||
| Loch Raven | 1-113 | CLC | 1st | Activity Center Room 138 | Miscellaneous | Joint Compound | All walls | 1700 | SF | Good | No asbestos detected | High | N/a | H-CLC-2 | 342 |