Attachment 03 - Electrical Phase B Drawings.pdf
PDF 9 MB Posted
- Attached to
- Eielson AFB CHPP Phase B Electrical Panels and Circuits Federal contract opportunity
- Solicitation number
- FA500422B0008
About this file
This document includes a solicitation for electrical panel and lighting replacement work at Eielson Air Force Base's Central Heat and Power Plant, along with attached drawings. The solicitation seeks replacement of light fixtures, conduit, conductors and boxes from the second floor to the roof of the plant and in the cooling pond pump house, along with demolition of existing lighting systems in the same areas. A site visit will be held on June 1st, with questions due by June 7th and electronic bids due by June 23rd to two Air Force contacts. The work has an estimated value between $1-5 million and is set aside for small businesses under NAICS 238210 with a $39.5 million size standard. The performance period is 360 calendar days from notice to proceed. Payment and performance bonds are required in accordance with FAR 28.102.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions and Answers for FTQW 19-0504 Site visit.pdf | ||
| Questions and Answers for FTQW 19-0504 Site visit.pdf | ||
| Solicitation Amendment FA500422B00080001 SF 30.pdf | ||
| Attachment 01 - Electrical Phase B Synopsis of Work.pdf | ||
| Attachment 05 - Submittal Register.xlsx | XLSX spreadsheet | |
| Attachment 02 - Electrical Phase B Specs.pdf | ||
| Attachment 04 - Wage Determination - AK20220001.pdf | ||
| Solicitation - FA500422B0008.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
THIS PROJECT
EIELSON AIR FORCE BASE VICINITY MAP
PACIFIC AIR FORCES
354th CE Squadron
Eielson Air Force Base
FTQW 19-0504
REPAIR CENTRAL HEATING & POWER PLANT (CH & PP)
ELECTRICAL PANELS & CIRCUITS, PHASE B
SHEET INDEX
SHEET NUMBER SHEET TITLE
E0.1
TITLE SHEET, INDEX, AND VICINITY MAP
E0.2 LEGEND AND SCHEDULES
E1.2
E1.3
WATER DECK LIGHTING PLAN
E1.4
SCALE DECK LIGHTING PLAN
E1.5
DRUM & CONTACTOR DECK LIGHTING PLAN
E1.6
FAN DECK LIGHTING PLAN
E1.7
H1.0 LOCATION & VICINITY MAP
H2.0 FIRST & SECOND FLOOR SAMPLE LOCATIONS & RESULTS
F500
AREA CLASSIFICATION PLANS (ISSUED FOR REFERENCE)
ER1
EXISTING ELECTRICAL ONE-LINE DIAGRAM
(ISSUED FOR REFERENCE)
TRIPPER / BUNKER LEVEL LIGHTING PLAN
ROOF LEVEL & POND HOUSE LIGHTING PLAN
E2.2
E2.3
WATER DECK LIGHTING DEMOLITION PLAN
E2.4
SCALE DECK LIGHTING DEMOLITION PLAN
E2.5
DRUM & CONTACTOR DECK LIGHTING DEMOLITION PLAN
E2.6
FAN DECK LIGHTING DEMOLITION PLAN
E2.7
TRIPPER / BUNKER LEVEL LIGHTING DEMOLITION PLAN
ROOF LEVEL & POND HOUSE LIGHTING DEMOLITION PLAN
E3.1
E3.2
LIGHTING NEW WORK ONE-LINE DIAGRAM
PANEL SCHEDULES
H3.0
H4.0
H5.0
THIRD & FOURTH FLOOR SAMPLE LOCATIONS & RESULTS
FIFTH & SIXTH FLOOR SAMPLE LOCATIONS & RESULTS
ROOF & POND HOUSE SAMPLE LOCATIONS & RESULTS
David Harr
EE-10223
03/28/2019
REG IS T ER E D PR O FE S S IO NA L ENGINEER
David Harr
EE-10223
Peter Beardsley
CE 10934
First Floor Settled Dust Laboratory Data Surveyed by NORTECH: August 1, 2017
Sample Location Dust Rating (1-5) Asbestos (str/cm²) SD-1 MCC near Turbine 3 3 ND
SD-2 MCC-E 3 ND
SD-6 Near Panel D 2 ND
First Floor Settled Dust Laboratory Data Surveyed by NORTECH: August 1, 2017
Dust Rating Asbestos Total Silica RCRA-8 (µg/m2) Sample Location (1 - 5) (str/cm2) (%) Arsenic Barium Cadmium Chromium Lead Selenium Silver Mercury
SD-1 MCC near Turbine 3 3 ND 29.5 2.9 110 0.88 17 38 1.1 ND 0.073
SD-2 MCC-E 3 ND 16.2 12 380 1.9 23 62 ND 0.71 0.25
SD-6 Coal Thaw Rail Building 4 ND 6.7 6.9 1,500 1.9 60 100 ND ND 1.6
Notes = None detected
Second Floor Lead Content Data Survey Surveyed By NORTECH: August 2018
Niton # Color Description Lead (mg/cm²) 1545 White Wall 5.7
Second Floor Settled Dust Laboratory Data Surveyed By NORTECH: August 2018
Sample Location Asbestos Lead L-1 Panel P-1 & P-1A NA 810 ug/ft²
Dust Rating: 3-4 Note:
NA = Contaminant not analyzed for this sample
Third Floor Settled Dust Laboratory Data Surveyed By NORTECH: August 2018
Sample Location Asbestos Lead A-1 Panel N ND NA
Dust Rating: 2-3 Notes:
ND = None detected NA = Contaminant not analyzed for this sample
Fourth Floor Lead Content Data Survey Surveyed By NORTECH: August 2018
Niton # Color Description Lead (mg/cm²)
1546 White Beam 3.3 1547 White Elec. Panel 0.18 1548 White Beam 4.4 1549 White Wall 1.3 1550 White Wall 0.04
Fourth Floor Settled Dust Laboratory Data Surveyed By NORTECH: August 2018
Sample Location Asbestos Lead L-2 Panel P NA 930 ug/ft²
Dust Rating: 3-4 Note:
NA = Contaminant not analyzed for this sample
Fifth Floor Lead Content Data Survey
Niton # Color
Description
Lead
(mg/cm²)
1551 White Panel F 0.24
1552 White Beam 2.3
1553 White Wall 0.8
Dust Rating: 2-3
Sixth Floor Dust Rating: 2-3
Roof Lead Content Data Survey
Niton # Color Description Lead (mg/cm²) 1554 Gray Wall 1.6 1555 Gray Beam 10.01
Roof Settled Dust Laboratory Data Surveyed By NORTECH: August 2018
Sample Location Asbestos Lead A-2 Lighting Panel ND NA L-3 Lighting Panel NA 570 ug/ft²
Dust Rating: 2 Notes:
ND = None detected NA = Contaminant not analyzed for this sample
POND HOUSE
Lead Sample Results
Number Color Surface Substrate Result (mg/cm²)
3562 white wall hard board 0.05 3563 gray lift collumn metal 0.00 3564 white wall hard board 0.07 3565 white wall hard board 0.06 3566 off white cabinet metal 0.00 3567 off white truss metal 7.8
REFERENCED GRIDLINES
BAGHOUSE
BAGHOUSE
CHEMICAL STORAGE AREA TO
BE INCLUDED IN WP AREA
CLASSIFICATION HOWEVER
DETECTORS INSTALLED SHALL
BE THE SAME TYPE INSTALLED
IN THE CLASS II DIV 1 AREAS
OPEN TO BELOW
ROOF
BAGHOUSE
BAGHOUSE
OPEN TO BELOW
OPEN TO BELOW
BAGHOUSE BAGHOUSE
ROOF
ROOF
ROOF
F500 NO SCALE
F500 NO SCALE
F500 NO SCALE
F500 NO SCALE
F500 NO SCALE
F500 NO SCALE
F500 NO SCALE
F500 NO SCALE
CLASS II DIV 1 GROUP F AREA
UNCLASSIFIED AREA, BUT EQUIPMENT TO BE INSTALLED AS WEATHERPROOF TO
INCLUDE RACEWAYS, BACK BOXES, CONNECTIONS AND SHALL ALSO INCLUDE
SECONDARY ENCLOSURES FOR ANY PACKAGED EQUIPMENT WHICH IS PROVIDED IN
NEMA 1 TYPE ENCLOSURES TO PROVIDE ADDITIONAL PROTECTION FROM DUST
INFILTRATION INTO THESE COMPONENTS, DEVICES AND/OR ANCILLARY SYSTEMS
CLASS I DIV 2 GROUP D AREA
UNCLASSIFIED AREA
EAST
FILTRATION
BUILDING
COAL
THAWING
ROOM
ELEV. 575'-6"
ELEV. 581'-2"
ELEV. 600'-0"
ELEV. 616'-0"
WEST
FILTRATION
BUILDING
ELEV. 578'-3"
ELEV. 543'-9"
ELEV. 636'-0"
B
TRIPPER
ROOM
CRANE
ELEV. 543'-9" ELEV. 543'-9"
ELEV. 556'-2"
ELEV. 581'-2"
ELEV. 600'-0"
ELEV. 616'-0"
TRIPPER
ROOM
EAST
FILTRATION
BUILDING
COAL
THAWING
ROOM
ELEV. 575'-6"
ELEV. 556'-2"
ELEV. 545'-6"
ELEV. 531'-0"
ELEV. 581'-2"
ELEV. 600'-0"
ELEV. 616'-0"
WEST
FILTRATION
BUILDING
ELEV. 571'-3"
ELEV. 575'-6" ELEV. 578'-3"ELEV. 578'-3"
TURBINE
GENERATOR
ROOM
AREA CLASSIFICATION: AREA CLASSIFICATION:
AREA CLASSIFICATION: AREA CLASSIFICATION: AREA CLASSIFICATION:
AREA CLASSIFICATION: AREA CLASSIFICATION:
GENERAL SHEET F500 NOTES
1. COAL HANDLING AREAS ARE AT VARIOUS ELEVATIONS WITH EXTERNAL CONVEYORS ARE NOT LEVEL.
2. AREA CLASSIFICATIONS BASED ON TYPES OF MATERIALS NORMALLY PRESENT AT THE LOCATIONS, i.e. PREDOMINANTLY COAL DUSTS. OTHER NON EXPLOSIVE BASED DUSTS AND DIRT ARE ALSO PRESENT WITHIN THE PLANT AREAS WHERE DEVICES ARE NOTED TO HAVE WEATHERPROOF ENCLOSURES TO PREVENT THIS DUST INFILTRATION INTO THESE SYSTEMS.
3. AREA CLASSIFICATIONS FOR THE SORBENT FACILITIES HAS NOT BEEN VERIFIED AS THESE LOCATIONS ARE STILL NOT COMPLETED AND TURNED OVER TO THE GOVERNMENT AND AS SUCH AS-BUILT INFORMATION IS NOT AVAILABLE.
ISSUED FOR REFERENCE: PROJECT FTQW 19-0504
REPAIR CH&PP ELEC. PANELS, PHASE B
FOR REFERENCE ONLY
EE-10223