Attachment 03 - Electrical Phase B Drawings.pdf

PDF 9 MB Posted

Attached to
Eielson AFB CHPP Phase B Electrical Panels and Circuits Federal contract opportunity
Solicitation number
FA500422B0008
Issued by
Department of the Air Force Pacific Air Forces

About this file

This document includes a solicitation for electrical panel and lighting replacement work at Eielson Air Force Base's Central Heat and Power Plant, along with attached drawings. The solicitation seeks replacement of light fixtures, conduit, conductors and boxes from the second floor to the roof of the plant and in the cooling pond pump house, along with demolition of existing lighting systems in the same areas. A site visit will be held on June 1st, with questions due by June 7th and electronic bids due by June 23rd to two Air Force contacts. The work has an estimated value between $1-5 million and is set aside for small businesses under NAICS 238210 with a $39.5 million size standard. The performance period is 360 calendar days from notice to proceed. Payment and performance bonds are required in accordance with FAR 28.102.

View the file

Other files for this federal contract opportunity

Other files attached to Eielson AFB CHPP Phase B Electrical Panels and Circuits, newest first.
File Type Posted
Questions and Answers for FTQW 19-0504 Site visit.pdf PDF
Questions and Answers for FTQW 19-0504 Site visit.pdf PDF
Solicitation Amendment FA500422B00080001 SF 30.pdf PDF
Attachment 01 - Electrical Phase B Synopsis of Work.pdf PDF
Attachment 05 - Submittal Register.xlsx XLSX spreadsheet
Attachment 02 - Electrical Phase B Specs.pdf PDF
Attachment 04 - Wage Determination - AK20220001.pdf PDF
Solicitation - FA500422B0008.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

THIS PROJECT

EIELSON AIR FORCE BASE VICINITY MAP

PACIFIC AIR FORCES

354th CE Squadron

Eielson Air Force Base

FTQW 19-0504

REPAIR CENTRAL HEATING & POWER PLANT (CH & PP)

ELECTRICAL PANELS & CIRCUITS, PHASE B

SHEET INDEX

SHEET NUMBER SHEET TITLE

E0.1

TITLE SHEET, INDEX, AND VICINITY MAP

E0.2 LEGEND AND SCHEDULES

E1.2

E1.3

WATER DECK LIGHTING PLAN

E1.4

SCALE DECK LIGHTING PLAN

E1.5

DRUM & CONTACTOR DECK LIGHTING PLAN

E1.6

FAN DECK LIGHTING PLAN

E1.7

H1.0 LOCATION & VICINITY MAP

H2.0 FIRST & SECOND FLOOR SAMPLE LOCATIONS & RESULTS

F500

AREA CLASSIFICATION PLANS (ISSUED FOR REFERENCE)

ER1

EXISTING ELECTRICAL ONE-LINE DIAGRAM

(ISSUED FOR REFERENCE)

TRIPPER / BUNKER LEVEL LIGHTING PLAN

ROOF LEVEL & POND HOUSE LIGHTING PLAN

E2.2

E2.3

WATER DECK LIGHTING DEMOLITION PLAN

E2.4

SCALE DECK LIGHTING DEMOLITION PLAN

E2.5

DRUM & CONTACTOR DECK LIGHTING DEMOLITION PLAN

E2.6

FAN DECK LIGHTING DEMOLITION PLAN

E2.7

TRIPPER / BUNKER LEVEL LIGHTING DEMOLITION PLAN

ROOF LEVEL & POND HOUSE LIGHTING DEMOLITION PLAN

E3.1

E3.2

LIGHTING NEW WORK ONE-LINE DIAGRAM

PANEL SCHEDULES

H3.0

H4.0

H5.0

THIRD & FOURTH FLOOR SAMPLE LOCATIONS & RESULTS

FIFTH & SIXTH FLOOR SAMPLE LOCATIONS & RESULTS

ROOF & POND HOUSE SAMPLE LOCATIONS & RESULTS

David Harr

EE-10223

03/28/2019

REG IS T ER E D PR O FE S S IO NA L ENGINEER

David Harr

EE-10223

Peter Beardsley

CE 10934

First Floor Settled Dust Laboratory Data Surveyed by NORTECH: August 1, 2017

Sample Location Dust Rating (1-5) Asbestos (str/cm²) SD-1 MCC near Turbine 3 3 ND

SD-2 MCC-E 3 ND

SD-6 Near Panel D 2 ND

First Floor Settled Dust Laboratory Data Surveyed by NORTECH: August 1, 2017

Dust Rating Asbestos Total Silica RCRA-8 (µg/m2) Sample Location (1 - 5) (str/cm2) (%) Arsenic Barium Cadmium Chromium Lead Selenium Silver Mercury

SD-1 MCC near Turbine 3 3 ND 29.5 2.9 110 0.88 17 38 1.1 ND 0.073

SD-2 MCC-E 3 ND 16.2 12 380 1.9 23 62 ND 0.71 0.25

SD-6 Coal Thaw Rail Building 4 ND 6.7 6.9 1,500 1.9 60 100 ND ND 1.6

Notes = None detected

Second Floor Lead Content Data Survey Surveyed By NORTECH: August 2018

Niton # Color Description Lead (mg/cm²) 1545 White Wall 5.7

Second Floor Settled Dust Laboratory Data Surveyed By NORTECH: August 2018

Sample Location Asbestos Lead L-1 Panel P-1 & P-1A NA 810 ug/ft²

Dust Rating: 3-4 Note:

NA = Contaminant not analyzed for this sample

Third Floor Settled Dust Laboratory Data Surveyed By NORTECH: August 2018

Sample Location Asbestos Lead A-1 Panel N ND NA

Dust Rating: 2-3 Notes:

ND = None detected NA = Contaminant not analyzed for this sample

Fourth Floor Lead Content Data Survey Surveyed By NORTECH: August 2018

Niton # Color Description Lead (mg/cm²)

1546 White Beam 3.3 1547 White Elec. Panel 0.18 1548 White Beam 4.4 1549 White Wall 1.3 1550 White Wall 0.04

Fourth Floor Settled Dust Laboratory Data Surveyed By NORTECH: August 2018

Sample Location Asbestos Lead L-2 Panel P NA 930 ug/ft²

Dust Rating: 3-4 Note:

NA = Contaminant not analyzed for this sample

Fifth Floor Lead Content Data Survey

Niton # Color

Description

Lead

(mg/cm²)

1551 White Panel F 0.24

1552 White Beam 2.3

1553 White Wall 0.8

Dust Rating: 2-3

Sixth Floor Dust Rating: 2-3

Roof Lead Content Data Survey

Niton # Color Description Lead (mg/cm²) 1554 Gray Wall 1.6 1555 Gray Beam 10.01

Roof Settled Dust Laboratory Data Surveyed By NORTECH: August 2018

Sample Location Asbestos Lead A-2 Lighting Panel ND NA L-3 Lighting Panel NA 570 ug/ft²

Dust Rating: 2 Notes:

ND = None detected NA = Contaminant not analyzed for this sample

POND HOUSE

Lead Sample Results

Number Color Surface Substrate Result (mg/cm²)

3562 white wall hard board 0.05 3563 gray lift collumn metal 0.00 3564 white wall hard board 0.07 3565 white wall hard board 0.06 3566 off white cabinet metal 0.00 3567 off white truss metal 7.8

REFERENCED GRIDLINES

BAGHOUSE

BAGHOUSE

CHEMICAL STORAGE AREA TO

BE INCLUDED IN WP AREA

CLASSIFICATION HOWEVER

DETECTORS INSTALLED SHALL

BE THE SAME TYPE INSTALLED

IN THE CLASS II DIV 1 AREAS

OPEN TO BELOW

ROOF

BAGHOUSE

BAGHOUSE

OPEN TO BELOW

OPEN TO BELOW

BAGHOUSE BAGHOUSE

ROOF

ROOF

ROOF

F500 NO SCALE

F500 NO SCALE

F500 NO SCALE

F500 NO SCALE

F500 NO SCALE

F500 NO SCALE

F500 NO SCALE

F500 NO SCALE

CLASS II DIV 1 GROUP F AREA

UNCLASSIFIED AREA, BUT EQUIPMENT TO BE INSTALLED AS WEATHERPROOF TO

INCLUDE RACEWAYS, BACK BOXES, CONNECTIONS AND SHALL ALSO INCLUDE

SECONDARY ENCLOSURES FOR ANY PACKAGED EQUIPMENT WHICH IS PROVIDED IN

NEMA 1 TYPE ENCLOSURES TO PROVIDE ADDITIONAL PROTECTION FROM DUST

INFILTRATION INTO THESE COMPONENTS, DEVICES AND/OR ANCILLARY SYSTEMS

CLASS I DIV 2 GROUP D AREA

UNCLASSIFIED AREA

EAST

FILTRATION

BUILDING

COAL

THAWING

ROOM

ELEV. 575'-6"

ELEV. 581'-2"

ELEV. 600'-0"

ELEV. 616'-0"

WEST

FILTRATION

BUILDING

ELEV. 578'-3"

ELEV. 543'-9"

ELEV. 636'-0"

B

TRIPPER

ROOM

CRANE

ELEV. 543'-9" ELEV. 543'-9"

ELEV. 556'-2"

ELEV. 581'-2"

ELEV. 600'-0"

ELEV. 616'-0"

TRIPPER

ROOM

EAST

FILTRATION

BUILDING

COAL

THAWING

ROOM

ELEV. 575'-6"

ELEV. 556'-2"

ELEV. 545'-6"

ELEV. 531'-0"

ELEV. 581'-2"

ELEV. 600'-0"

ELEV. 616'-0"

WEST

FILTRATION

BUILDING

ELEV. 571'-3"

ELEV. 575'-6" ELEV. 578'-3"ELEV. 578'-3"

TURBINE

GENERATOR

ROOM

AREA CLASSIFICATION: AREA CLASSIFICATION:

AREA CLASSIFICATION: AREA CLASSIFICATION: AREA CLASSIFICATION:

AREA CLASSIFICATION: AREA CLASSIFICATION:

GENERAL SHEET F500 NOTES

1. COAL HANDLING AREAS ARE AT VARIOUS ELEVATIONS WITH EXTERNAL CONVEYORS ARE NOT LEVEL.

2. AREA CLASSIFICATIONS BASED ON TYPES OF MATERIALS NORMALLY PRESENT AT THE LOCATIONS, i.e. PREDOMINANTLY COAL DUSTS. OTHER NON EXPLOSIVE BASED DUSTS AND DIRT ARE ALSO PRESENT WITHIN THE PLANT AREAS WHERE DEVICES ARE NOTED TO HAVE WEATHERPROOF ENCLOSURES TO PREVENT THIS DUST INFILTRATION INTO THESE SYSTEMS.

3. AREA CLASSIFICATIONS FOR THE SORBENT FACILITIES HAS NOT BEEN VERIFIED AS THESE LOCATIONS ARE STILL NOT COMPLETED AND TURNED OVER TO THE GOVERNMENT AND AS SUCH AS-BUILT INFORMATION IS NOT AVAILABLE.

ISSUED FOR REFERENCE: PROJECT FTQW 19-0504

REPAIR CH&PP ELEC. PANELS, PHASE B

FOR REFERENCE ONLY

EE-10223

File details come from the government source that posted it. Updated .