Attachment 02 - Bldg 1130 I.R Scan Report.pdf
PDF 4 MB Posted
- Attached to
- B1130 ROOF REPLACEMENT
- Solicitation number
- VLSB260069
About this file
This is a Roof Diagnostic Survey report prepared for United States Air Force Shaw Air Force Base, specifically for Building 1130 located at 420 Chapin Street, Shaw AFB, South Carolina 29152. The survey was conducted by Tremco Incorporated and Weatherproofing Technologies, Inc. (WTI) on December 23, 2024, under project number 9851183, with diagnostic technician M. Sporcic. The report documents a comprehensive infrared thermography and moisture analysis of the building's roof system to identify wet insulation and potential structural concerns.
The survey identifies wet insulation across eight distinct roof sections, totaling 5,175 square feet of wet area out of 34,392 square feet surveyed (15.09% wet). Roof section 2 shows the highest moisture concentration at 100.00% wet (153 square feet), while sections 4 and 5 have minimal to no wet insulation. The inspection methodology employed mid-wave infrared cameras with spectral range 2.5-5.6, moisture meter readings, and core cuts to verify findings. Thermograms, photographs, and construction data for each roof section document insulation types (primarily polyisocyanurate and EPS foam insulation), roof deck construction (concrete decks with various protective layers), and specific moisture percentage measurements. The report includes detailed drawings with wet insulation areas marked in red, dry core locations, moisture grid measurements, and dimensional analysis of affected areas for remediation planning purposes.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ROOF DIAGNOSTIC SURVEY FOR UNITED STATES AIR FORCE
420 CHAPIN STREET SHAW AFB, SOUTH CAROLINA 29152
SHAW AFB BUILDING 1130
DRAWINGS
TITLE PAGE
SHEET A
SHEET B
MOISTURE SURVEY
SHEET C THERMOGRAMS, PHOTOS & ROOF DATA,
WET DIMENSIONS & SQ. FT.
N
ROOF PLAN
SCALE: NO SCALE
© 2024 BY TREMCO INCORPORATED, ALL RIGHTS RESERVED. NO PART OF THIS DOCUMENT MAY BE
REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL,
PHOTOCOPYING, RECORDING OR OTHERWISE WITHOUT THE EXPRESS PRIOR WRITTEN CONSENT
OF TREMCO INCORPORATED. THE INFORMATION PROVIDED IN THIS DRAWING IS CURRENT AS OF THE DATE OF INSPECTION BY TREMCO INCORPORATED, WEATHERPROOFING TECHNOLOGIES, INC.
OR THEIR DESIGNATED CONTRACTOR. ROOFING SYSTEM AND/OR BUILDING CONDITIONS CAN
CHANGE AT ANY TIME, INCLUDING BUT NOT LIMITED TO THE AMOUNT OF WET INSULATION IN THE
ROOFING SYSTEM, AND CAUSE THE INFORMATION PROVIDED IN THIS DRAWING TO CHANGE OR
BECOME OUT OF DATE.
TREMCO'S INFRARED INSPECTIONS ARE PERFORMED BY CERTIFIED (EXPERIENCED) INFRARED
THERMOGRAPHERS UTILIZING STATE-OF-THE-ART EQUIPMENT. ALL WORK CONFORMS WITH CURRENT INDUSTRY BEST PRACTICES, AND IS PERFORMED IN ACCORDANCE WITH STANDARDS PUBLISHED BY ASTM
INTERNATIONAL AND INFRASPECTION INSTITUTE.
How An Infrared Survey Works:
Wet roof insulation absorbs more solar energy from the sun during the day than dry insulation. As the sun sets, the nighttime cools the roof surface. Wet insulation retains more solar energy than dry insulation. These temperature differences are detected by the infrared camera. All full service scans are performed using a mid-wave IR camera with a 2.5 - 5.6 spectral range.
Suspected wet insulation is verified through core cuts and/or a Roof Moisture Meter. Core cuts are taken to establish acceptable levels of moisture. Confirmed wet areas are marked out on the roof surface with paint.
How A Moisture Meter Works:
During the daytime, readings are taken and recorded in random locations and at wet areas found by the infrared camera.
Fast neutrons are emitted from the source in the Roof Moisture Meter into the roof system. The presence of hydrogen in the roof system slows the neutrons. These slowed neutrons as well as the fast neutrons are detected by the Roof Moisture Meter. A reading is displayed in the digital readout and gets recorded.
Core cuts are taken to determine a baseline for dry roof materials. Wet areas of insulation are marked on the roof surface with paint.
THIS IS A WTI BRANDED REPORT. THE TEMPLATE AND OR
REPORT CAN NOT BE REPRODUCED IN ANY MANNER.
A
UNITED STATES AIR FORCE - SHAW AFB
BUILDING 1130
420 CHAPIN STREET
SHAW AFB, SOUTH CAROLINA 29152
R.L.
9851183
STANDARD KEY OF SYMBOLS
ROOF SECTION
DRY CORE THERMOGRAM
R.I.M. (RANDOM
INTERMITTENT MOISTURE) MOISTURE READING
WET CORE
PHOTO
MOISTURE GRID
N.A.F. (NO ANOMALIES
WET INSULATION
# P-#
T-#
© 2024 BY TREMCO INCORPORATED, ALL RIGHTS RESERVED. NO PART OF THIS DOCUMENT MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE WITHOUT THE EXPRESS PRIOR WRITTEN CONSENT OF TREMCO INCORPORATED. THE INFORMATION PROVIDED IN THIS DRAWING IS CURRENT AS OF THE DATE OF INSPECTION BY TREMCO INCORPORATED, WEATHERPROOFING TECHNOLOGIES, INC. OR THEIR DESIGNATED CONTRACTOR. ROOFING SYSTEM AND/OR BUILDING CONDITIONS CAN CHANGE AT ANY TIME, INCLUDING BUT NOT LIMITED TO THE AMOUNT OF WET INSULATION IN THE ROOFING SYSTEM, AND CAUSE THE INFORMATION PROVIDED IN THIS DRAWING TO CHANGE OR BECOME OUT OF DATE.
N.I.C.
PROJECT NO.:
DATE:
DRAWN BY: SHEET NO.:
DIAGNOSTIC TECHNICIAN:
TRACE CORE
FOUND)
N
ROOF PLAN
SCALE: NO SCALE
M. Sporcic
N
KEY PLAN
SCALE: NO SCALE
AREA OF SURVEY
1-A
30 31
2-A
12 11
20 23
T-07
P-01
27 30T-09
T-08 29 30 30 32 28 25 26
7-A
6-A
12 11
T-03
T-04
T-05
T-06
8-A
T-01 22 26 20 21
8-C
2511 12
101011
10 10
12 12
10 10
111111
8-B
12/23/2024
T-02
B12/23/2024
UNITED STATES AIR FORCE - SHAW AFB
BUILDING 1130
420 CHAPIN STREET
SHAW AFB, SOUTH CAROLINA 29152
R.L.
9851183
STANDARD KEY OF SYMBOLS
ROOF SECTION
DRY CORE THERMOGRAM
R.I.M. (RANDOM
INTERMITTENT MOISTURE) MOISTURE READING
WET CORE
PHOTO
MOISTURE GRID
N.A.F. (NO ANOMALIES
WET INSULATION
# P-#
T-#
© 2024 BY TREMCO INCORPORATED, ALL RIGHTS RESERVED. NO PART OF THIS DOCUMENT MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE WITHOUT THE EXPRESS PRIOR WRITTEN CONSENT OF TREMCO INCORPORATED. THE INFORMATION PROVIDED IN THIS DRAWING IS CURRENT AS OF THE DATE OF INSPECTION BY TREMCO INCORPORATED, WEATHERPROOFING TECHNOLOGIES, INC. OR THEIR DESIGNATED CONTRACTOR. ROOFING SYSTEM AND/OR BUILDING CONDITIONS CAN CHANGE AT ANY TIME, INCLUDING BUT NOT LIMITED TO THE AMOUNT OF WET INSULATION IN THE ROOFING SYSTEM, AND CAUSE THE INFORMATION PROVIDED IN THIS DRAWING TO CHANGE OR BECOME OUT OF DATE.
N.I.C.
PROJECT NO.:
DATE:
DRAWN BY: SHEET NO.:
DIAGNOSTIC TECHNICIAN:
TRACE CORE
FOUND)
N
ROOF PLAN
SCALE: NO SCALE
M. Sporcic
N
KEY PLAN
SCALE: NO SCALE
AREA OF SURVEY
P-01
939 SQ. FT.
153 SQ. FT.
45 SQ. FT.
1,330
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
SQ. FT.
168 SQ. FT.
AutoCAD SHX Text 8'
AutoCAD SHX Text 74'
AutoCAD SHX Text 9'
AutoCAD SHX Text 38'
AutoCAD SHX Text 5'
AutoCAD SHX Text 17'
AutoCAD SHX Text 9'
AutoCAD SHX Text 18'
AutoCAD SHX Text 37'
AutoCAD SHX Text 31'
AutoCAD SHX Text 13'
AutoCAD SHX Text 16'
AutoCAD SHX Text 14'
AutoCAD SHX Text 95'
AutoCAD SHX Text 13'
AutoCAD SHX Text 1'
AutoCAD SHX Text 38'
AutoCAD SHX Text 3'
AutoCAD SHX Text 8'
AutoCAD SHX Text 6'
AutoCAD SHX Text 17'
AutoCAD SHX Text 14'
AutoCAD SHX Text 22'
AutoCAD SHX Text 15'
AutoCAD SHX Text 5'
AutoCAD SHX Text 27'
AutoCAD SHX Text 46'
AutoCAD SHX Text 9'
AutoCAD SHX Text 8'
AutoCAD SHX Text 13'
AutoCAD SHX Text 11'
AutoCAD SHX Text 20'
AutoCAD SHX Text 10'
AutoCAD SHX Text 7'
AutoCAD SHX Text 21'
AutoCAD SHX Text 44'
AutoCAD SHX Text 24'
AutoCAD SHX Text 24'
AutoCAD SHX Text 7'
AutoCAD SHX Text 1' brand Rectangle
STANDARD KEY OF SYMBOLS
ROOF SECTION
DRY CORE THERMOGRAM
R.I.M. (RANDOM
INTERMITTENT MOISTURE) MOISTURE READING
WET CORE
PHOTO
MOISTURE GRID
N.A.F. (NO ANOMALIES
WET INSULATION
# P-#
T-#
© 2024 BY TREMCO INCORPORATED, ALL RIGHTS RESERVED. NO PART OF THIS DOCUMENT MAY BE REPRODUCED OR TRANSMITTED IN ANY FORM OR BY ANY MEANS, ELECTRONIC, MECHANICAL, PHOTOCOPYING, RECORDING OR OTHERWISE WITHOUT THE EXPRESS PRIOR WRITTEN CONSENT OF TREMCO INCORPORATED. THE INFORMATION PROVIDED IN THIS DRAWING IS CURRENT AS OF THE DATE OF INSPECTION BY TREMCO INCORPORATED, WEATHERPROOFING TECHNOLOGIES, INC. OR THEIR DESIGNATED CONTRACTOR. ROOFING SYSTEM AND/OR BUILDING CONDITIONS CAN CHANGE AT ANY TIME, INCLUDING BUT NOT LIMITED TO THE AMOUNT OF WET INSULATION IN THE ROOFING SYSTEM, AND CAUSE THE INFORMATION PROVIDED IN THIS DRAWING TO CHANGE OR BECOME OUT OF DATE.
N.I.C.
PROJECT NO.:
DATE:
DRAWN BY: SHEET NO.:
DIAGNOSTIC TECHNICIAN:
TRACE CORE
FOUND)
NOTE: THE MOISTURE PERCENTAGES ARE INTENDED TO BE USED AS A QUALITATIVE MEASUREMENT RATHER THAN AN EXACT READING.
Photograph P-01Thermogram T-01
Thermogram T-02
Thermogram T-03
Thermogram T-04
Thermogram T-05
Thermogram T-06
Thermogram T-07
Thermogram T-08
Thermogram T-09
C12/23/2024
UNITED STATES AIR FORCE - SHAW AFB
BUILDING 1130
420 CHAPIN STREET
SHAW AFB, SOUTH CAROLINA 29152
R.L.
9851183M. Sporcic