Attach 3 - Drawings.pdf
PDF 8 MB Posted
- Attached to
- Replace HVAC Controllers
- Solicitation number
- FA875126Q0009
About this file
These are architectural drawing sheets for a federal construction project at Rome Research Site, New York, detailing the replacement of Johnson Controls N2 temperature control systems with updated BACnet MS/TP devices across multiple buildings (Buildings 2, 3, and 106). The project, numbered ULDF22-0002, is dated April 10, 2026, and was designed by MWF.
The drawings specify comprehensive HVAC control system upgrades including replacement of existing N2 controllers (shown in red) with new BACnet MS/TP devices, removal of the entire N2 communications bus, and installation of new bus wiring and field communication trunks. Key work includes replacing incremental damper actuators with proportional actuators for VAV units, establishing new field busses connected to NAE (Network Automation Engine) nodes, and relocating lighting control network bridges to new BACnet MS/TP trunks. The detailed controller schedules reference over 200 devices across multiple NAE nodes, specifying device replacements, removals, and new installations with associated input/output configurations. All work must comply with the National Electrical Code and Unified Facilities Criteria. The project encompasses multiple floor plans across Buildings 2 (north and south floors), Building 3 (ground floor, mezzanine, and multiple enlarged views), and Building 106 (first floor, second floor, and monitors level), with existing and proposed equipment locations clearly marked using color-coded legends (red for replacement/removal, green for devices to remain, orange for incompatible sensors requiring replacement).
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T
T
T
T
T
T
T
B CORRIDO
B104A B105
B104
B103 B106
B107B108
B109
B102
B100
B101
A H
U -2
VAV 2-1
(NAE-1 UNT-7)
VAV 2-2
(to NAE-1 UNT-7)
VAV 2-3
(to NAE-1 UNT-7)
VAV 2-4
(NAE-1 UNT-8)
VAV 2-5
(to NAE-1 UNT-8)
VAV 2-6
(to NAE-1 UNT-8)
VAV 2-7
(NAE-1 UNT-9)
FTR A1
(NAE-1 UNT-19)
(Above Ceiling)
A H
U -1
B133
B132
B131
B134
B130
B128
B129
B128A
B126
B127
AHU-1
(NAE-1 DX-1)
AHU-2
(NAE-1 DX-2)
NAE-1
(B2)
CHW System
(NAE-1 DX-6)
T
T T T
T
FTR B1
(NAE-1 UNT-21)
(Above Ceiling)
FTR B2
(NAE-1 UNT-22)
(Above Ceiling)
A102
A104
A105
A106
North End AHU
(NAE-1 CGM-65)
AHU-COMSEC
COMSEC AHU
(NAE-1 UNT-16)
T
AHU-5
AHU-5 [Switch Room]
(NAE-1 FEC-64)
Generator Room
(NAE-1 UNT-14)
T
Gen Rm Unit Htr
A107
A108
A109 B143
B142 B141A
B141
B141B
B140
B144
B145
B146
B147
B148
B149
A101
T
Unit Heater
(NAE-1 TEC-11)
T
Unit Heater
(NAE-1 TEC-10)
T
Unit Heater
(NAE-1 TEC-12)
T
Unit Heater
(NAE-1 TEC-8)
T
Unit Heater
(NAE-1 TEC-7)
T
Unit Heater
(NAE-1 TEC-13)
T
Unit Heater
(NAE-1 TEC-6)
T
Unit Heater
(NAE-1 TEC-9)
T
T
T
FTR D1
(NAE-1 UNT-25)
(Above Ceiling)
Comm Rm (former) ACUs
(NAE-1 UNT-15)
Switch Rm Liebert
A-16J
A-16E
B-18E A100
A-08J
B-20E
B-23D
B-25D
B-24E
B-20H
B-24H B-29H
REMOVE CONTROLLER BUT
DO NOT REPLACE.
MOVE EXHAUST FAN POINTS TO
NEW RM B141 FTR CONTROLLER
(NAE-1 CGM-10)
REMOVE CONTROLLER BUT
DO NOT REPLACE.
REMOVE COMMUNICATIONS BUS.
LMBC
LMBC-11
LMBCLMBC-12
LMBC LMBC-13 LMBC
LMBC-14
LMBCLMBC-17
LMBC LMBC-18
AIR COOLED
CHILLER
Chiller Control
(NAE-1 UNT-13)
ABANDON CONTROLLER IN PLAC
DO NOT REPLACE.
REMOVE COMMUNICATIONS BUS
PROVIDE NEW BACNET ROUTER
IN THIS LOCATION
(CONTEMPORARY CONTROLS PART# BASRT-B)
T
A102A
A102B
AHU-NE
BUILDING 2 NOTES:
1. EXECUTE ALL WORK IN ACCORDANCE WITH THE CURRENT EDITIONS OF THE NATIONAL ELECTRICAL CODE
AND UNIFIED FACILITIES CRITERIA.
2. REPLACE OR REMOVE ALL EXISTING N2 DEVICES AS SHOWN ON THIS DRAWING (IN RED) AND ACCORDING TO THE CONTROLLER SCHEDULE ON PAGE TC-501, WITH UP-TO-DATE BACNET MS/TP DEVICES. UTILIZE
EXISTING ENCLOSURES FOR NEW CONTROL DEVICES.
3. CONNECT NEW AND EXISTING TO REMAIN CONTROLLERS (IN GREEN) TO NAE-1 FIELD BUSSES AS DETAILED ON BUS SCHEDULE ON THIS PAGE. PROVIDE AND INSTALL NEW BUS WIRING AS NECESSARY. ADDRESS
NEW AND AFFECTED EXISTING DEVICES AS SHOWN.
4. REMOVE EXISTING N2 COMMUNICATIONS BUS IN ITS ENTIRETY. RE-USE OF N2 BUS CONDUCTORS IS NOT
ALLOWED.
5. REUSE ALL EXISTING END DEVICES UNLESS OTHERWISE NOTED.
6. INCREMENTAL DAMPER ACTUATORS FOR THE OFFICE AREA VAV'S (VAV 2-1 THRU VAV 2-16) SHALL BE REPLACED WITH PROPORTIONAL ACTUATORS. EXISTING DAMPER MOTOR WIRING CAN BE RE-USED.
(TYPICAL FOR 16)
7. BUILDING 2 LIGHTING CONTROL NETWORK BRIDGES (IN VIOLET) RESIDE ON THE EXISTING BACNET MS/TP COMMUNICATIONS TRUNK IN THE BUILDING (NAE-1, FC-2). REMOVE THESE NETWORK BRIDGES FROM THE JOHNSON CONTROLS TRUNK AND PROVIDE AND INSTALL A NEW MS/TP TRUNK TO THESE DEVICES WHICH
WILL BE HOME-RUNNED BACK TO BACNET ROUTER (CONTEMPORARY CONTROLS MODEL BASRT-B)
PROVIDED UNDER THIS PROJECT IN ROOM B148.
COLOR CODE LEGEND:
EXISTING JOHNSON CONTROLS N2 DEVICES TO BE REPLACED OR REMOVED
EXISTING JOHNSON CONTROLS MS/TP DEVICES TO REMAIN. REFER TO BUS SCHEDULE.
EXISTING WATTSTOPPER LIGHTING CONTROL NETWORK BRIDGES TO BE MIGRATED TO NEW
COMMUNICATIONS BUS. REFER TO BUS SCHEDULE AND NOTES.
RED
GREEN
VIOLET
Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
REPLACE JOHNSON CONTROLS
N2 CONTROLLERS, SITE
8 10 APR 2026
MWF
ULDF22-0002
BLDG. 2
TEMPERATURE CONTROL
BLDG. 2 NORTH FLOOR PLAN
TC-101 1
MWF
MWF
N 1/16"=1'-0"BLDG 2
EXISTING FLOOR PLAN - NORTH
JOHNSON CONTROLS FIELD
BUS SCHEDULE
(ALL CONNECTED TO NAE-1)
NCE-2
(B2 Mail Room)
T T
T
T
T
T
T
T
T
T
RRIDOR
C115
C115
C116A
C117A
C116
C117
C118
C126
C119
C120
C122
C121
C123
C125
C124
C128
C129
C130
C131
C132
C133
C161
C164
C160
C162 C163
AHU-4 [Mail Room]
(NCE-2 NCE-4)
A H
U -4
VAV 2-8
(to NAE-1 UNT-9)
VAV 2-15
(to NAE-1 UNT-9)
VAV 2-13
(NAE-1 UNT-10)
VAV 2-14
(to NAE-1 UNT-10)
VAV 2-9
(to NAE-1 UNT-10)
VAV 2-16
(to NAE-1 UNT-10)
VAV 2-10
(NAE-1 UNT-11)
VAV 2-11
(to NAE-1 UNT-11)
VAV 2-12
(to NAE-1 UNT-11)
FTR A2
(NAE-1 UNT-20)
(Above Ceiling)
A H
U -3
T
AHU-3 [CE Shop]
(NAE-1 UNT-18)
T
H V
U -2
H V
U -1
HVU-1
(NAE-1 DX-4)
HVU-2
(NAE-1 DX-5)
D100
C198
C197 C196
C194A
C194
C191
C192
C193
C189
C190
C187
C188
C195
C195A
C250
T
Unit Heater
(NAE-1 TEC-5)
T
Unit Heater
(NAE-1 TEC-14)
T
Unit Heater
(NAE-1 TEC-15)
T
Unit Heater
(NAE-1 TEC-16)
T Unit Heater
(NAE-1 TEC-18)
T Unit Heater (NAE-1 TEC-17) TUnit Heater
(NAE-1 TEC-19)
TUnit Heater
(NAE-1 TEC-20)
C-39K
C-35E
C-47D
D-53B
REMOVE CONTROLLER BUT
DO NOT REPLACE.
REMOVE COMMUNICATIONS BUS.
REMOVE CONTROLLER BUT
DO NOT REPLACE.
REMOVE COMMUNICATIONS BUS.
LMBC
LMBC-15
LMBCLMBC-16
LMBC
LMBC-10
LACE.
US.
Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
REPLACE JOHNSON CONTROLS
N2 CONTROLLERS, SITE
8 10 APR 2026
MWF
ULDF22-0002
BLDG. 2
TEMPERATURE CONTROL
BLDG. 2 SOUTH FLOOR PLAN
TC-102 2
MWF
MWF
N 1/16"=1'-0"BLDG 2
EXISTING FLOOR PLAN - SOUTH
A H
U -A
-1
A H
U -A
-2
A H
U -A
-5
A H
U -A
-3
T
VAV-A1-11
(NAE-3 VMA-15)
VAV-A1-12
(NAE-3 VMA-16)
T
T
A5-H
A5-F
A5-G
B5-K
B5-D
B5-N
CORRIDOR A
A6-AAHU-A-1
(NAE-3 DX-4)
T
AHU-A-5
(NAE-3 DX-6)AHU-A-2
(NAE-3 DX-5)
Emergency Shutdown
(NAE-3 UNT-62)
(Above Ceiling)
CUH-2
(NAE-3 DX-2)
CHWP-A1 VSD
(NAE-3 VND-57)
CHWP-A2 VSD
(NAE-3 VND-58)
AHU-A-3
(NAE-3 FEC-4)
A1-7
3 VMA-11)
C H
W P
-A
C H
W P
-A
NAE-3
(B3 A & B Bays)
AHU-A-8
C8-B C8-C
C8-D
AHU-A-8
(NAE-8 DX-12)
VAV-A8-1
(NAE-8 VMA-21)
T
CORRIDOR 8 AHU-B-1
Z7 Z6
Z5
Z4
Z3
Z2
Z1
T
AHU-B-1
e 3 Sensor
AHU-B-1
(NAE-8 DX-14)
C-Bay HW
(NAE-8 DX-43)
HVU-F8-1
F8-K
F8-i
F8-J
HVU-F8-1
(NAE-8 DX-44)
Chiller 3
Chiller 1
(CH-1)
Chiller 2
(CH-2)
Cooling Tower 1
(CT-1)
P C
H W
P -3
P C
H W
P -1
PCHWP-HX
SCHWP-4
SCHWP-5
SCHWP4 VSD
(NAE-8 VND-55)
SCHWP5 VSD
(NAE-8 VND-56)
CWP-3a CWP-3b
HVU-F8-1 PRV VSD
(NAE-8 VND-61)
CT-3a VSD
(NAE-8 VND-53)
CT-3b VSD
(NAE-8 VND-54)
CHW-HX
PCHWP-2
C W
P -2b
C W
P -2a
C W
P -1
Chiller 1
(NAE-13 FEC-4)
NAE-13
(B3 Chillers)
Chlr 1 Trane Interface
(NAE-13 VND-29)
Chiller 2
(NAE-13 FEC-5)
Chlr 2 York Interface
(NAE-13 VND-7)
Chiller 3
(NAE-13 FEC-6)
AHU-B-4
T/H
T
Chilled Beam
Chilled Beam
Chilled Beam
Chilled Beam hilled eam
Chilled Beam
VAV-C2-1
(NAE-14 VMA-9)
NAE-14
(Extreme Computing)
8-L
G8-P
VMA-26)
2-13 -24)
2-14
4 VMA-25)
A-28)
AHU-C-2
(NAE-14 FEC-4)
CB-27
CB-25
CB-24
CB-23
CB-31
CB-33
VAV-1
VAV-13
AHU-C-2-SF-VFD
(NAE-14 VND-5)
AHU-C-2-HUM-1
(NAE-14 VND-8)
AHU-C-2-HUM-2
(NAE-14 VND-8)
AHU-C-2-RF-VFD
(NAE-14 FEC-6)
G8-O
U P
J4-A
J4-A1
J4-B
FCU-J4-1
(NAE-8 UNT-200)
T
T
CB-1
CB-2
CB-3
CB-4
CB-5
CB-6 CB-10
CB-9
CB-8
CB-7
CB-11 CB-12 CB-13 CB-14 CB-15
CB-16
CB-17
CB-18
CB-19
CB-20 CB-21
CB-22
CB-27
CB-25
CB-24
CB-23CB-30
CB-29
CB-28
CB-26
CB-31
CB-34
CB-32
CB-33
VAV-3
VAV-1
VAV-2
VAV-8
VAV-5
VAV-6
VAV-7
VAV-4
VAV-9
VAV-10
VAV-11 VAV-12
VAV-13
VAV-14
VAV-15
FIL-2
FIL-3
FIL-4
FIL-5
FIL-6
FIL-7
FIL-8
S/N:2010264-01 S/N:2010264-02 S/N:2010264-03
U P
U P
«RAMP»
«RAMP»
R
A M
P»
«RAMP»
U P
COLOR CODE LEGEND:
EXISTING JOHNSON CONTROLS N2 DEVICES TO BE REPLACED OR REMOVED
EXISTING JOHNSON CONTROLS MS/TP DEVICES TO REMAIN. REFER TO BUS SCHEDULE.
EXISTING ZONE SENSOR THAT WILL BE INCOMPATIBLE WITH NEW CONTROLLER - REPLACE WITH NEW DEVICE
RED
GREEN
ORANGE
BUILDING 3 NOTES:
1. EXECUTE ALL WORK IN ACCORDANCE WITH THE CURRENT EDITIONS OF THE NATIONAL ELECTRICAL CODE
AND UNIFIED FACILITIES CRITERIA.
2. REPLACE OR REMOVE ALL EXISTING N2 DEVICES AS SHOWN ON THIS DRAWING (IN RED) AND ACCORDING TO THE CONTROLLER SCHEDULE ON PAGE TC-501, WITH UP-TO-DATE BACNET MS/TP DEVICES. UTILIZE
EXISTING ENCLOSURES FOR NEW CONTROL DEVICES.
3. CONNECT NEW CONTROLLERS TO FIELD COMMUNICATION BUSSES AS SHOWN IN THE SCHEDULE ON THIS PAGE. PROVIDE AND INSTALL NEW BUS WIRING AS NECESSARY. ADDRESS NEW AND AFFECTED EXISTING
DEVICES AS SHOWN.
4. REMOVE EXISTING N2 COMMUNICATIONS BUS IN ITS ENTIRETY. RE-USE OF N2 BUS CONDUCTORS IS NOT
ALLOWED.
5. REUSE ALL EXISTING END DEVICES UNLESS OTHERWISE NOTED.
N 1/64"=1'-0"BLDG 3
GROUND FLOOR KEY PLAN
Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
REPLACE JOHNSON CONTROLS
N2 CONTROLLERS, SITE
8 10 APR 2026
MWF
ULDF22-0002
BLDG. 3
TEMPERATURE CONTROL
BLDG. 3 GROUND FLOOR PLAN
TC-201 3
MWF
MWF
N 1/16"=1'-0"BLDG 3
ENLARGED VIEW 1
N 1/16"=1'-0"BLDG 3
ENLARGED VIEW 2
N 1/16"=1'-0"BLDG 3
ENLARGED VIEW 3
N 1/16"=1'-0"BLDG 3
ENLARGED VIEW 4
JOHNSON CONTROLS FIELD
NAE-2
(B3 DHRF)
C6-R
AHU-B-4 AHU-B-2
AHU-B-3
AHU-B-4
(NAE-6 FEC-18)
CRAC-C6-5
CRAC-C6-6
DHRF SiteLink
(NAE-2 VND-8)
AHU-B-2
(Zone 1) Supply Air
AHU-B-2
(Zone 2) Supply Air
AHU-B-2
(Zone 3) Supply Air
AHU-B-2
(Zone 4) Supply Air
AHU-B-2
(Zone 5) Supply Air
AHU-B-2
(NAE-3 DX-7)
AHU-B-3
(NAE-3 DX-9)
AHU-B-3
Supply Air
U P
AHU-C-4
AHU-C-4
(NAE-3 DX-30)
AHU-C-4 Zones
(NAE-3 UNT-31)
C H
W P
-C
C H
W P
-C
CHWP-C1 VSD
(NAE-8 VND-59)
CHWP-C2 VSD
(NAE-3 VND-57)
A H
U -C
-3
AHU-C-3
Supply Air
NAE-8
(B3 C & D Bays) NAE-6
(B3 RIG Offices, CRDSF)
AHU-C-3
(NAE-6 FEC-4)
D O
W N
D O
W N
U P
U P
U P
D O
W N
U P
UP
U P
UP
PENTHOUSE ON
ROOF LEVEL
PENTHOUSE ON
ROOF LEVEL
C6-R
Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
REPLACE JOHNSON CONTROLS
N2 CONTROLLERS, SITE
8 10 APR 2026
MWF
ULDF22-0002
BLDG. 3
TEMPERATURE CONTROL
BLDG. 3 MEZZANINE FLOOR PLAN
TC-202 4
MWF
MWF
N 1/64"=1'-0"BLDG 3
MEZZANINE KEY PLAN
N 1/16"=1'-0"BLDG 3
ENLARGED VIEW 1
N 1/16"=1'-0"BLDG 3
ENLARGED VIEW 4
N 1/16"=1'-0"BLDG 3
ENLARGED VIEW 3
N 1/16"=1'-0"BLDG 3
ENLARGED VIEW 2
T TTTTT T T T T
T TTT
T
TTT
T
T T
T
T
T
TTT TTTTTTT
T T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T T TT T T TT
DX-101
AI-3, AO-9
VMA-176
Sideloop
DX-102
AI-5, AO-11
DX-102
AI-6, AO-12
DX-102
AI-7, AO-13
DX-102
AI-8, AO-14
DX-103
AI-1, AO-1
DX-103
AI-2, AO-2
DX-103
AI-3, AO-9
DX-101
AI-4, AO-10
DX-101
AI-5, AO-11
DX-101
AI-6, AO-12
DX-101
AI-7, AO-13
DX-101
AI-8, AO-14
DX-102
AI-1, AO-1
DX-102
AI-2, AO-2
DX-102
AI-3, AO-9
DX-102
AI-4, AO-10
VMA-175
Sideloop
DX-101
AI-1, AO-1
DX-107
AI-3, AO-9
DX-107
AI-2, AO-2
VMA-182
SideloopDX-107
AI-1, AO-1
VMA-183
SideloopDX-106
AI-8, AO-14
DX-106
AI-7, AO-13
DX-106
AI-6, AO-12
DX-106
AI-5, AO-11
DX-106
AI-4, AO-10
DX-106
AI-3, AO-9
DX-106
AI-2, AO-2
DX-106
AI-1, AO-1
Duct from RHC-A2-1a
(RHC-7)
DX-105
AI-8, AO-14
DX-105
AI-7, AO-13
VMA-181
Sideloop
DX-105
AI-6, AO-12
DX-105
AI-5, AO-11
DX-105
AI-4, AO-10
DX-105
AI-3, AO-9
DX-105
AI-2, AO-2
DX-105
AI-1, AO-1
CVM-60
Sideloop
DX-104
AI-4, AO-10
DX-104
AI-3, AO-9
DX-104
AI-2, AO-2
DX-104
AI-1, AO-1
VMA-177
Sideloop
DX-103
AI-7, AO-13
DX-103
AI-6, AO-12
T
AHU-A2
RHC-5, 6, 7
T
AHU-P2
RHC-2
T
AHU-A1
RHC-4
T
AHU-B1
RHC-1, 2
T
AHU-B2
RHC-3
T
AHU-P1
RHC-1
T
AHU-E
RHC-4, 5
T
DX-101
AI-2, AO-2
To Valve Upstairs
DX-103
AI-5, AO-11
T T T
T
T T T
T
T
T T
T
Duct from RHC-A2-1b
(RHC-6)
Duct from RHC-A2-1c
(RHC-5)
Duct from
RHC-A1-1
(RHC-4)
Duct from RHC-B1-1b
(RHC-2)
Duct from
RHC-P2-12
(RHC-2)
Duct from
RHC-B2-1
(RHC-3)
Duct from RHC-B1-1a
(RHC-1)
Duct from RHC-E-1a
(RHC-4)
Duct from RHC-E-1b
(RHC-5)
Duct from
RHC-P1-1
(RHC-1)
TTTTT
T
T
T
T T
T
T
T
T
T
TTT
T
TTT
T T
T T
T
T T
T
T
T T
T
T
T TT T TT
T
T T
T
T
T
T
T T
T
T
T
T
T
T
T
T
AHU-F1
VAV-A2-1b-4
(NAE-4 VMA-4)
A101
A105
A107
A115
VAV-A2-1b-3
(NAE-4 VMA-5)
A117 A119
A121
VAV-A2-1b-2
(NAE-4 VMA-6)
A125
B125
VAV-A2-1c-1
(NAE-4 VMA-7)
B126
B127 B127A
B132
A129
CORRIDOR A
VAV-A2-1c-3 (NAE-4 VMA-8)
B122
B120B118
B116
B114
B108
B106
B104
B104A
CORRIDOR B
WEST CORRIDOR
EAST CORRIDOR
VAV-A2-1c-2 (NAE-4 VMA-9)
Stair 4
B101
B109 B113 B115
B117 B119 Stair 5
VAV-A1-1-2
(NAE-4 VMA-10)
C125A C125B C125C
C134
C134A
C140
VAV-A1-1-1
(NAE-4 VMA-11)
C125
C135
C137
EAST CORRIDOR
CORRIDOR C
C128 C130
C131
D132
D132A
D134
C139D C139C
C139 C139B
C139A
CORRIDOR C EAST
CORRIDOR 5
VAV-A1-1-4 (NAE-4 VMA-12)
C114 C118 C122
VAV-A1-1-5 (NAE-4 VMA-13)
CORRIDOR C
C102 C104
C104B C112
WEST CORRIDOR
VAV-A1-1-3 (NAE-4 VMA-14)
C101
C107
C115
C117
C102
VAV-B1-1b-2 (NAE-4 VMA-15)
D105 D107 D109 D117
D121
D100
D119A
CORRIDOR D VAV-B1-1b-1
(NAE-4 VMA-16)
E132
D127 D133
EAST CORRIDOR
CORRIDOR D
VAV-P2-12-3
(NAE-4 VMA-17)
O113
O117
O121
O123
O125
VAV-B2-1-3 (NAE-4 VMA-18)
E106 E110 E120 E122
E120A
VAV-B2-1-2 (NAE-4 VMA-19)
CORRIDOR E
CORRIDOR E
E101
E101A
E103 E105 E107 E115 E117 E119 E121
VAV-B2-1-1
(NAE-4 VMA-20)
E125
EAST CORRIDOR
VAV-B1-1a-2 (NAE-4 VMA-21)CORRIDOR F
CORRIDOR F
F122F102
VAV-B1-1a-1
(NAE-4 VMA-22)
F132 F134 F136
F136AF122A
CORRIDOR 2
VAV-B1-1b-3
(NAE-4 VMA-38)
D116D108
D102
Stair 6 Stair 7
VAV-P2-12-5
(NAE-4 VMA-39)
B102O137A
O133
O137
O141
UPS Room
(NAE-4 FEC-41)
E140
AHU-F1
(NAE-4 FEC-44)
VAV-F1-1 (NAE-4 VMA-45)
VAV-F1-2 (NAE-4 VMA-46) VAV-F1-3
(NAE-4 VMA-47)
F142
F141
F143
F144
F153C
F153
F152C
F153A
F153B
F152
F152F
CORRIDOR F
SNE-2
(B106 Interior VAVs)
VAV-A2-1a-1 (NAE-7 VMA-183) VAV-A2-1b-1 (NAE-7 VMA-182)
VAV-E-1a-1
(NAE-7 VMA-176)
VAV-E-1b-1
(NAE-7 VMA-175)
VAV-P1-1-1 (NAE-7 VMA-177)
VAV-P1-1-2
(NAE-7 VMA-178)
VAV-P2-12-2
(NAE-7 VMA-180)
Electric Baseboard
Electric Baseboard
VAV-P2-12-4
(NAE-7 VMA-181)
FTR Flr-1 [S,W]
(NAE-7 DX-104),
FTR Flr-1 [W]
(NAE-7 DX-105)
FTR Flr-1 [N]
(NAE-7 DX-106),
FTR Ftr-1 [N]
(NAE-7 DX-107)
AHU-Chllr Rm
(NAE-7 DX-17)
VAV-VTC-2
(NAE-7 VMA-6)
T T
T
VAV-VTC-1
(NAE-7 VMA-5)
VAV-VTC-3
(NAE-7 VMA-7)
To Upstairs T-stat
(DX-103 AI-8, AO-14)
F109
F103
Stair 1
G1B-08
G1B-09
G1B-10
G1C-01
F133 F137
F137A
D150
CORRIDOR 4
D140
D153D
D153
D153E
C146
C147A
C147C
C148
C156
C149
C158
C159
C144A
C144
C141C
C141
C141B
C141A
C142
C143
C160
Stair 11
W161 W163 W169 W181A
W181B
W181
W181C
W181D
W181E
W181F
W183
W191 W193
W193A
Stair 12
W188
W184W180W178
W174
W170
W167A
W168
W167
W165B
W165
W165A
W164W162
W162A
W160
D153A D153B
CORRIDOR W
A137
Stair 9
A132
A130 A128A126A124A122
A116 A108
A106
A104A102
Stair 3
A104A A104B
O143O144
O143A
O143B
O144A
O140
O130
O128A
O128
O127
O124
O122
O120
O118
Stair 2
O138
O134
O99B
O99C O99
O99A
O99D
O99E
O99
O99F
O99H
O99G
O97
AHU-Alt BDOC
AHU-Alt BDOC
(NAE-4 FEC-48)
T
From AHU-VTC
C147BC147D
T
VAV-VTC-4
(NAE-7 VMA-10)
NCE-1
(B106 Chillers)
Chiller 1
(CH-1)
Chiller 2
(CH-2)
PCHWP-2
PCHWP-1
SCHW
P-1
SCHW
P-2
CWP-1
CWP-2
B106 Chiller Plant
(NCE-1 NCE-4)
Chlr 1 York Interface
(NCE-1 VND-6)
Chlr 2 York Interface
(NCE-1 VND-7)
T
T
T
T T
T
Duct from
AHU-B3
VAV-B3-1-1
(NAE-4 CVM-52)
VAV-B3-1-2
(NAE-4 CVM-53)
VAV-B3-1-3
(NAE-4 CVM-54)
VAV-B3-1-4
(NAE-4 CVM-55)
VAV-B3-1-6
(NAE-4 CVM-57)
VAV-B3-1-5
(NAE-4 CVM-56)
FTR Flr-1 [W-Corr S]
(NAE-7 DX-101),
FTR Flr-1 [W-Corr N,S]
(NAE-7 DX-102),
FTR Flr-1 [W-Corr N]
(NAE-7 DX-103)
E1D-01
E1D-03
E1D-04
E1D-05
E1D-02D1A-1 D1A-3
D1A-2
D1A-4
D1A-6
T
VAV-P2-12-6
(NAE-4 CVM-58)
VAV-P2-12-7
(NAE-4 CVM-59)
VAV-P2-12-8
(NAE-4 CVM-60)
Boiler 1
(BLR-1)
Boiler 2
(BLR-2)
HVU-BLRM
PHW
P-1
PHW
P-2
Protonode
(NAE-4 VND-61)
HW Control
(NAE-4 CGM-49)
HVU-BLRM
(NAE-4 CGM-62)
BUILDING 106 NOTES:
1. EXECUTE ALL WORK IN ACCORDANCE WITH THE CURRENT EDITIONS OF THE NATIONAL ELECTRICAL CODE
AND UNIFIED FACILITIES CRITERIA.
2. REPLACE OR REMOVE ALL EXISTING N2 DEVICES AS SHOWN ON THIS DRAWING (IN RED) AND ACCORDING TO THE CONTROLLER SCHEDULE ON PAGE TC-501, WITH UP-TO-DATE BACNET MS/TP DEVICES. UTILIZE
EXISTING ENCLOSURES FOR NEW CONTROL DEVICES.
3. CONNECT NEW CONTROLLERS TO FIELD COMMUNICATION BUSSES AS SHOWN IN THE SCHEDULE ON THIS PAGE. RUN NEW CONDUCTORS AS APPROPRIATE. ADDRESS NEW AND AFFECTED EXISTING DEVICES AS
SHOWN.
4. N2 COMMUNICATIONS BUS MUST REMAIN INTACT FOR CONTINUED COMMUNICATION TO THE EXISTING AIR
HANDLERS. ALL UNNECESSARY N2 BUS SHALL BE REMOVED.
COLOR CODE LEGEND:
EXISTING JOHNSON CONTROLS N2 DEVICES TO BE REPLACED OR REMOVED
EXISTING JOHNSON CONTROLS MS/TP DEVICES TO REMAIN. REFER TO BUS SCHEDULE.
EXISTING ZONE SENSOR THAT WILL BE INCOMPATIBLE WITH NEW CONTROLLER - REPLACE W
RED
GREEN
ORANGE
N 1/16"=1'-0"BLDG 106
EXISTING FIRST FLOOR PLAN
Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
REPLACE JOHNSON CONTROLS
N2 CONTROLLERS, SITE
8 10 APR 2026
MWF
ULDF22-0002
BLDG. 106
TEMPERATURE CONTROL
BLDG. 106 FIRST FLOOR PLAN
TC-301 5
MWF
MWF
JOHNSON CONTROLS FIELD BUS SCHEDULE
T DX-103
AI-8, AO-14
T
T
T
T
T
T
T
T
T
T
TTTTTTT
TT
T
T
T
T T
T T
T
DX-202
AI-4, AO-10
DX-202
AI-7, AO-13
DX-203
AI-4, AO-10
DX-203
AI-5, AO-11
DX-203
AI-6, AO-12
DX-203
AI-7, AO-13 DX-203
AI-8, AO-14
VMA-232
Sideloop
VMA-234
Sideloop
DX-204
AI-1, AO-1
DX-204
AI-2, AO-2
DX-201
AI-2, AO-2
DX-201
AI-1, AO-1
Electric Baseboard
T
T T
T
AHU-A2
RHC-8
T
AHU-P2
RHC-2
T
AHU-P1
RHC-3
T
AHU-B2
RHC-10
T
AHU-A1
(RHC-A1-2)
T T
T
T
T
T
T
T
UNT-26
AI-2, AO-2
UNT-26
AI-1, AO-1
VMA-25
Sideloop
VMA-22
Sideloop
VMA-24
Sideloop
T
VMA-23
Sideloop
UNT-27
AI-1, AO-1
UNT-27
AI-2, AO-2
UNT-27
AI-4, AO-4
UNT-27
AI-3, AO-3
T
To Downstairs T-stat
(DX-101 AI-2, AO-2)
UNT-26
AI-4, AO-4
UNT-26
AI-3, AO-3
Duct from
RHC-A2-2
(RHC-8)
Duct from
RHC-A1-2
(RHC-9)
Duct from
RHC-B2-2
(RHC-10)
Duct from
RHC-B1-2
(RHC-11)
Duct from
RHC-P2-12
(RHC-2)
Duct from
RHC-P1-2
(RHC-3)
Duct from RHC-E-2b
(RHC-7)
Duct from RHC-E-2a
(RHC-6)
T T
T
T
T
T
T
T
T
T
T
T
T
T T T T T
T T
TT T
To Downstairs T-stat (VMA-181 Sideloop)
T
T
T
T
T
T
T T T
T
T
T
T T
T
T
VAV-A2-2-4
(NAE-4 VMA-23)
O201
O203
O205
O207
O200A
B200
CORRIDOR B
WEST CORRIDOR
WEST CORRIDOR
B207
B207A
B207B
B211 B213
B215
Stair 4 Stair 5
EAST CORRIDOR
VAV-A2-2-3 (NAE-4 VMA-24) VAV-A2-2-1 (NAE-4 VMA-25)
C218
C220
C222
Stair 9
CORRIDOR B
VAV-A1-2-3 (NAE-4 VMA-26)
C202 C204 C206 C208 C210
C212
VAV-A1-2-2 (NAE-4 VMA-27)
C216
C214 C224
CORRIDOR C CORRIDOR C
VAV-A1-2-4 (NAE-4 VMA-28)
D202
C211
Stair 6 Stair 7
EAST CORRIDOR
VAV-A1-2-1 (NAE-4 VMA-29)
C213
C215
C217
C219
C221
VAV-B2-2-3 (NAE-4 VMA-30)CORRIDOR D
VAV-B2-2-2
(NAE-4 VMA-31)
D212 D216 D233
D233A
D235
Auditorium AHU
AHU-Auditorium
(NAE-4 FEC-42)
AHU-Auditorium SF-VSD
(NAE-4 VND-43)
O200C
Stair 2
Stair 2A
T T
T
T
T
T2
T1
T
T
T
T1
T2
T T T
T
T
T
T
T
T
T T
Duct from
AHU-B3
VAV-B2-2-8
(NAE-12 VMA-14)
VAV-B2-2-9
(NAE-12 VMA-15)
VAV-B2-2-10
(NAE-12 VMA-16)
VAV-B1-2-9
(NAE-12 VMA-13)
VAV-B1-2-10
(NAE-12 VMA-12)
VAV-P1-2-13
(NAE-12 VMA-4)
VAV-P1-2-14
(NAE-12 VMA-6)
VAV-P1-2-15 (NAE-12 VMA-8)
VAV-P1-2-20
(NAE-12 VMA-11)
VAV-P1-2-17
(NAE-12 VMA-5)
VAV-P1-2-18
(NAE-12 VMA-7)
VAV-P1-2-19
(NAE-12 VMA-9)
VAV-B3-2-1
(NAE-12 VMA-24)
VAV-B3-2-2
(NAE-12 VMA-23)
VAV-B3-2-3
(NAE-12 VMA-22)
VAV-B3-2-4
(NAE-12 VMA-21)
VAV-B3-2-5
(NAE-12 VMA-20)
VAV-B3-2-6
(NAE-12 VMA-19)
VAV-B3-2-7
(NAE-12 VMA-17)
VAV-B3-2-8
(NAE-12 VMA-18)
VAV-B3-2-9
(NAE-12 VMA-25)
VAV-B3-2-10
(NAE-12 VMA-26)
VAV-B3-2-11
(NAE-12 VMA-27)
VAV-B3-2-12
(NAE-12 VMA-28)
VAV-B3-2-13
(NAE-12 VMA-29)
VAV-B3-2-14
(NAE-12 VMA-30)
VAV-B3-2-15
(NAE-12 VMA-33)
VAV-B3-2-16
(NAE-12 VMA-32) VAV-B3-2-17
(NAE-12 VMA-31)
VAV-P1-2-16 (NAE-12 VMA-10)
SUITE E2C
SUITE F2C
SUITE F2D
SUITE E2D
SUITE G2C
SUITE G2D
E2C-04 E2C-05
E2C-01
E2C-03
E2C-02
F2C-02
F2C-04
F2C-03
F2C-01
G2C-01
G2C-02 G2C-04
G2C-05
G2C-03
E2D-01
E2D-02
E2D-03
F2D-08
F2D-09 F2D-07
F2D-06
F2D-04
F2D-05
F2D-03
F2D-01 F2D-02
G2D-01
G2D-02
G2D-03
G2D-04
G2D-05
Stair 8
EAST CORRIDOR
CORRIDOR D
AHU-E (NIC)
(NAE-7 DX-5)
NAE-7
(B106 AHU's, Perimeter)
VAV-A2-2-2 (NAE-7 VMA-234)
VAV-A2-2-5 (NAE-7 VMA-232)
VAV-E-2a-1
(NAE-7 VMA-25)
VAV-E-2a-2
(NAE-7 VMA-24)
VAV-E-2b-1
(NAE-7 VMA-22)
VAV-E-2b-2
(NAE-7 VMA-21)
VAV-E-2b-3
(NAE-7 VMA-23)
VAV-B1-2-2
(NAE-12 VMA-8)
VAV-B1-2-3
(NAE-12 VMA-10)
VAV-B1-2-4
(NAE-12 VMA-9)
VAV-B1-2-5
(NAE-12 VMA-14)VAV-B1-2-6
(NAE-12 VMA-11)
VAV-B1-2-7
(NAE-12 VMA-21)
VAV-B1-2-8
(NAE-12 VMA-20)
VAV-B2-2-4
(NAE-12 VMA-6)VAV-B2-2-5
(NAE-12 VMA-5)VAV-B2-2-6
(NAE-12 VMA-4)
VAV-B2-2-7
(NAE-12 VMA-7)
VAV-P1-2-3
(NAE-12 VMA-13)
VAV-P1-2-4
(NAE-12 VMA-19)
VAV-P1-2-5
(NAE-12 VMA-12)
VAV-P1-2-6
(NAE-12 VMA-26)
VAV-P1-2-7
(NAE-12 VMA-22)
VAV-P1-2-8
(NAE-12 VMA-24)
VAV-P1-2-9
(NAE-12 VMA-25)
VAV-P1-2-10
(NAE-12 VMA-18)
VAV-P1-2-11
(NAE-12 VMA-23)
VAV-P1-2-12
(NAE-12 VMA-17)
FTR Flr-2 [W,N]
(NAE-7 DX-203),
FTR Flr-2 [N]
(NAE-7 DX-204)
FTR Flr-2 [E]
(NAE-7 DX-201),
FTR Flr-2 [SW]
(NAE-7 DX-202)
FTR Flr-2 [W-Corr W]
(NAE-7 UNT-26)
FTR Flr-2 [W-Corr E]
(NAE-7 UNT-27)
AHU-RePro
(NAE-7 DX-108)
AHU-VTC
(NAE-7 FEC-4)
AHU-VTC SF-VSD
(NAE-7 VND-8)
AHU-VTC RF-VSD
(NAE-7 VND-9)
To Valve Downstairs
E2B-03
E2B-04
E2B-05
E2B-06
E2B-02
E2B-01
E2B-07
F2B-01
F2B-02
F2B-03
F2B-04 F2B-05
F2B-06
F2B-07
F2B-08
Corridor E
Corridor F
G2B-01 G2B-02
G2B-03
G2B-04
G2B-05
G2B-06
G2B-07
F2B-21
West Corridor
West Corridor
E2B-14 E2B-15
E2B-16
F2B-19
F2B-18
F2B-20
SUITE E2B
SUITE E2B
SUITE F2B
SUITE F2B
Stair 1
O212A
O202
O200
B204
B204A
B206 B208
B210
B212 B214 B216
B218
B220
B241
B240
C240
C241
W2B
W2A
Stair 11
W2C1
W2C
W2D
W2E
W2F W2G
W2H
W2I
Stair 12
W2J
W2K
AHU-E
AHU-VTC
AHU-VTC
Supply Air
AHU-
Repro
AHU-Chllr Rm
T
T
T T
T T
VAV-P12-6
(NAE-12 CVM-27)
VAV-P12-7
(NAE-12 CVM-29)
VAV-P12-8
(NAE-12 CVM-28)
VAV-P12-9
(NAE-12 CVM-30)
VAV-P12-10
(NAE-12 CVM-31)
VAV-P12-11
(NAE-12 CVM-32)
D2A-2
D2A-3D2A-5
D2A-7
D2A-1
D2A-8
D2A-9
D2A-6
D2A-4
N 1/16"=1'-0"BLDG 106
EXISTING SECOND FLOOR PLAN
Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
REPLACE JOHNSON CONTROLS
N2 CONTROLLERS, SITE
8 10 APR 2026
MWF
ULDF22-0002
BLDG. 106
TEMPERATURE CONTROL
BLDG. 106 SECOND FLOOR PLAN
TC-302 6
1st & 2nd Floor Return
Up to EF-P2-1
AHU-P2
RHC-P2-12
(RHC-2)
(AO-10)
To 1st & 2nd Floor VAV's
AHU-P1
Up to EF-P1-1
1st Floor Return
Up to EF-P1-2
To 1st Floor VAV's To 2nd Floor VAV's
RHC-P1-1
(RHC-1)
(AO-10)
RHC-P1-2
(RHC-3)
(AO-11)
2nd Floor Return
1st Floor Return
2nd Floor Return
1st Floor Return
Up to EF-B1-1
AHU-B2
AHU-B1
To 2nd Floor VAV's
Up to EF-B2-1
2nd Floor Return
RHC-B2-1
(RHC-3)
(AO-10)
To 1st Floor VAV's
RHC-B2-2
(RHC-10)
(AO-11)
RHC-B1-1b
(RHC-2)
(AO-11)
To 1st Floor VAV's
RHC-A2-1a
(RHC-7)
(AO-12)
RHC-A2-1b
(RHC-6)
(AO-11)
RHC-A2-2
(RHC-8)
(AO-13)
RHC-A2-1c
(RHC-5)
(AO-10)
To 1st Floor VAV's
To 1st Floor VAV'sTo 2nd Floor VAV's
1st Floor Return2nd Floor Return
1st Floor Return
RHC-A1-2
(RHC-9)
(AO-11)
RHC-A1-1
(RHC-4)
(AO-10)
Up to EF-A2-2
Up to EF-A2-1
AHU-A2
AHU-A1
Up to EF-A1-1
1st & 2nd Floor Return
AHU-B3
VAV-B3-P-1 (NAE-12 VMA-34)
AHU-B3
(NAE-12 FEC-37)
AHU-B3 RF-VSD
(NAE-12 VND-35)
AHU-B3 SF-VSD
(NAE-12 VND-34)
AHU-A1 (NIC)
(NAE-7 DX-8)
AHU-A2 (NIC)
(NAE-7 DX-10)
AHU-P1 (NIC)
(NAE-7 DX-1)
AHU-P2 (NIC)
(NAE-7 DX-12)
NAE-12
(B106 2nd Floor)
AHU-B1
(NAE-12 CGM-38)
AHU-B2
(NAE-12 CGM-39)
To 1st Floor VAV's (Duct B1-1a)
To 2nd Floor VAV's (Duct B1-2)
N 1/16"=1'-0"BLDG 106
MONITOR LEVEL FLOOR PLAN Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
REPLACE JOHNSON CONTROLS
N2 CONTROLLERS, SITE
8 10 APR 2026
MWF
ULDF22-0002
BLDG. 106
TEMPERATURE CONTROL
BLDG. 106 MONITORS FLOOR PLAN
TC-303 7
Air Force Research Laboratory Rome Research Site, New York
ROME RESEARCH SITE
PROJECT MANAGER:
DESIGNER:
DRAFTER:
SHEET TITLE:
PROJECT TITLE:
DATE:SHEET:DRAWING NO: FACILITY NO:
PROJECT NO:
OF
REPLACE JOHNSON CONTROLS
N2 CONTROLLERS, SITE
8 10 APR 2026
MWF
ULDF22-0002
TEMPERATURE CONTROL
DETAILS
TC-501 8
MWF
MWF
JOHNSON CONTROLS FIELD
| TC-101 |
| TC-102 |
| TC-201 |
| TC-202 |
| TC-301 |
| TC-302 |
| TC-303 |
| TC-501 |
| Sheets and Views |
| Details |
File details come from the government source that posted it. Updated .