This document is an appendix listing fire protection systems for various buildings at the National Institute of Standards and Technology campus in Boulder, Colorado. It provides details on automatic sprinkler systems and standpipe systems for each building, including the riser location, areas protected, system type, presence of fire pumps or backflow preventers. Key buildings include Building 1 with five automatic sprinkler water entry systems and standpipe systems throughout, Building 24 with two interconnected sprinkler systems and standpipe systems on each level, and Building 81 with one sprinkler system including the only fire pump on site. The related federal contract opportunity is for fire protection systems inspection, testing, maintenance, repair and impairment coordinator services for the Boulder and Fort Collins, Colorado locations of the National Institute of Standards and Technology. The solicitation number is 1333ND21QNB150136.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NIST Boulder Automatic Sprinkler Systems Water-Based Fire Protection Systems Appendix B

Building # Automatic Sprinkler System Riser

Location Area Protected System Type Fire Pump

(Y/N) Standpipe

System (Y/N)

Backflow Preventer

(Y/N)

Building 1 Room 1049 - Mechanical Room Fitness Center, Connector to B81, and Spine Standpipe - All Levels Wet N Y Y

Building 1 Wing 1 Wing 1 Room 2142 Wing 1 (Interconnected to Room 1049 System) Wet N N Y Building 1 Wing 1 Wing 1 Janitor Closet 2100 Room 2106 and 2108 Single Interlock Pre-Action N N N Building 1 Wing 2 Wing 2 West Entrance Vestibule Room 2226 Single Interlock Pre-Action N N N Building 1 Wing 3 Wing 3 Service Corridor North Wing 3 - Main Entry Wet N N Y Building 1 Wing 3 Wing 3 Service Corridor North Wing 3 - Level 3 Wet N N N Building 1 Wing 3 Wing 3 Service Corridor North Wing 3 - Clerestory Wet N N N Building 1 Wing 3 Wing 3 Service Corridor North Wing 3 - Dock Canopy Dry N N N Building 1 Wing 5 Wing 5 - Water Entry Room Wing 5 - Main Entry Wet N N Y Building 1 Wing 5 Wing 5 - Water Entry Room Wing 5 - Level 2 Wet N N N Building 1 Wing 5 Wing 5 - Water Entry Room Wing 5 - Level 3 Wet N N N Building 1 Wing 5 Wing 5 - Water Entry Room Wing 5 - Level 4 Wet N N N Building 1 Wing 5 Wing 5 - Water Entry Room Wing 5 - Level 5 Wet N N N Building 1 Wing 6 Wing 6 - Mechanical Room 3671 Wing 6 - Main Entry Wet N N Y Building 1 Wing 6 Wing 6 - Mechanical Room 3671 Wing 6 - Level 3 Wet N N N Building 1 Wing 6 Wing 6 - Mechanical Room 3671 Wing 6 - Level 4 Wet N N N Building 1 Wing 6 Wing 6 - Mechanical Room 4605 Wing 6 - Level 4 Anechoic Chamber 4607 Single Interlock Pre-Action N N N Building 1 Wing 6 Wing 6 - Mechanical Room 3671 Wing 6 - Clerestory Level - Dock Canopy Dry N N N Building 1 Wing 6 Wing 6 - Mechanical Room 3671 Wing 6 - Clerestory Level Wet N N N

Building 1 Annex D Annex D North Closet Near Entry Annex D Wet N N N

Common Components and Valves Summary

Building 1 (B1) has five (5) automatic sprinkler water entry systems identified by fire alarm panel Node as follows:

Node 1: Water Entry in Spine Basement Room 1049 interconnected to water entry in Wing 1 Room 2142. Includes standpipe system throughout B1 Spine all levels (1-5). Includes Spine Fitness Center Room 1006 automatic sprinklers.

Node 2: Water Entry in Wing 1 Room 2142 interconnected to water entry in Basement Room 1049. Includes sprinklers throughout Wing 1 including pre-action automatic sprinklers for Lab 2106 and 2108.

Node 2 includes pre-action sprinklers for Lab 2226 in Wing 2 fed off of standpipe system. Also includes separate water entry for Annex D wet sprinklers.

Node 3: No water entry.

Node 4: No water entry. Includes automatic sprinklers for very west end of Level 4 Spine and B81 connector wet sprinklers fed off of stanpipe system. Also includes automatic sprinklers for Spine Level 5 Penthouse fed off of standpipe system.

Node 13: Dedicated Wing 3 water entry. Automatic sprinklers for all systems feeding Wing 3.

Node 15: Dedicated Wing 5 water entry. Automatic sprinkler for all systems feeding WIng 5.

Node 16: Dedicated Wing 6 water entry. Automatic sprinklers for all systems feeding Wing 6.

Wing 4 and Wing 5 are not provided with automatic sprinkler protection.

The Spine of B1 is without automatic sprinkler protection except in the Fitness Center (Room 1006), a very small area at the west end of Level 4 Corridor to include B81 connector, and the Level 5 Penthouse - All fed from the sandpipe system.

Building 1 has standpipe hose connections throughout the Spine at each exit stairwell (count estimate is 29 hose connection stations).

Automatic Sprinkler System Riser

Location Area Protected System Type Fire Pump

(Y/N) Standpipe

System (Y/N)

Backflow Preventer

(Y/N) Common Components and Valves Summary

Builidng 2 Building 2 - Mechanical Room 0105

Building 2 - Basement, Various Level 1 and 2 Areas, and Mechancial Equipment Tunnel (Main Entry) Wet N N Y

Building 2 Buidling 2 - Mech Room 0105 Building 2 Dock Dry N N N

Builiding 3 Main Entry - Mechanical Room

Entire Building including Standpipe - All Levels North and South Stairwells Wet N Y Y

Building 3 Mechanical Room 1126 Level 1 Wet N N N

Building 3 Mechanical Room 1126 Standpipes (North and South) and Levels above Level 1 Wet N N N

Building 3 South Stair (Stair 02) Level 2 Wet N N N Building 3 South Stair (Stair 02) Lvl 2 -Public Safety Equipment Room 2112 Pre-Action N N N Building 3 South Stair (Stair 02) Level 3 Wet N N N Building 3 Sout Stair (Stair 02) Roof Stair Penthouse - Roof Manifold Wet N Y N

Building 4 Building 4 Room 1310 Building 4 Above and Below Lay-in Ceiling and in Warehouse Dry N N Y

Building 22 Building 22 - Mechanical Room 1122 Building 22 Wet N N Y

Building 23 Building 23 Bathroom Building 23 Wet N N Y Building 24 B24 Basement North - Rm 0300 Building 24 First Level Lab 1300 Single Interlock Pre-Action N N N Building 24 Building 24 Lab 1500 NW Corner Building 24 First Level Lab 1500 Single Interlock Pre-Action N N N

Building 24 B24 Basement North - Rm 0300 Building 24 Basement Wet N Y Y

Building 24 Building 24 Mechanical Room 0114 Building 24 Basement, First Level, Second Level Wet N Y Y

Building 26 Building 26 Room 123 Closet (SW Corner of B26) Building 26 Wet N N Y

Building 42 (CUP) Building 42 Room 106 B42 All Levels Wet N y Y

Building 42 (CUP) Tunnel Building 42 Outside Room 106 Tunnel Wet N N N Building 42 Tunnel West Doghouse

Building 42 Tunnel @ West Doghouse West Tunnel Doghouse Antifreeze N N Y

Building 42 Tunnel Central Doghouse

Building 42 Tunnel @ Central Doghouse Central Tunnel Doghouse Antifreeze N N Y

Building 42 Tunnel East Doghouse

Building 42 Tunnel @ East Doghouse East Tunnel Doghouse Antifreeze N N Y

Building 23 (B23) has one automatic sprinkler water entry monitored by Node 23 protecting all of B23. No hose connecitons in

Building 24 (B24) has two interconnected automatic sprinkler water entries monitored by Node 24 protecting the two pre-action systems for Lab 1300 and Lab 1500.

Building 24 has standpipe hose connections for each level located at exit stairwells. Hose connection count is estimated 11 stations.

Buildign 26 (B26) has one automatic sprinkler water entry monitored by Node 26 protecting all of B26.

Building 42 (B42) has one automatic sprinkler water entry monitored by Node 45 proteting all of B42 including the Tunnel.

Building 42 has standpipe hose connections for each level located in exit paths.

Hose connections are provided one each level, with two (2) on Level 2, three (3) on Level 1, two (2) in the Basement, and three (3) in the B42 Tunnel. A total of (ten) 10 standpipe hose connection stations are provided in B42.

Building 22 (B22) has one automatic sprinkler water entry monitored by Node 22 protecting all of B22.

Hose connections are located at exit paths and estimate is 2.

Building 2 (B2) has one automatic sprinkler water entry monitored by Node 5.

Standpipe hose connections are located at exit paths. Hose connection count estimate is 7 hose connection stations.

Building 3 (B3) has one automatic sprinkler water entry monitored by Node 33.

Standpipe hose connections are located in the north and south exit stairwells. Hose conection count estimate is 8 hose connection stations.

Building 4 (B4) has one automatic sprinkler water entry monitored by Node 30 protecting all of B4.

There are no hose connections in B4.

Automatic Sprinkler System Riser

Location Area Protected System Type Fire Pump

(Y/N) Standpipe

System (Y/N)

Backflow Preventer

(Y/N) Common Components and Valves Summary

Building 81 Main Riser Entry - Mechanical Room 1K112 Entire Building - Main Entry w/ Fire Pump Wet Y N Y

Building 81 West Stair 7 - Level 1 Laboratory North - Level 1 Wet Y N N Building 81 West Stair 7 - Level 1 Laboratory South - Level 1 Wet Y N N Building 81 West Stair 7 - Level 1 Cleanroom Level 1 Wet Y N N Building 81 West Stair 7 - Level 2 Interstitial Level 2 North Wet Y N N Building 81 West Stair 7 - Level 2 Interstitial Level 2 South Wet Y N N Building 81 West Stair 7 - Level 3 Mechanical Level 3 - North Wet Y N N Building 81 West Stair - Level 3 Mechancial Level 3 - South Wet Y N N Building 81 Building 81 Room 2K101 Building 81 Dock Antifreeze Y N N

Building 81 (B81) has one automatic sprinkler water entry that includes the only fire pump on the NIST site, monitored by Node 60.

Building 81 has no hose connection stations.

FY00

Gas Dock added, CW line routed outside dock footprint

Sheet1