Attach 1 - Appendix A Fire Alarm Systems 12-2020 revised.pdf

PDF 1003 KB Posted

Attached to
Fire Protection Systems Inspection, Testing, Maintenance, Repair and Impairment Coordinator Services
Solicitation number
1333ND21QNB150136
Issued by

About this file

This document contains an appendix detailing the fire alarm systems and devices at various National Institute of Standards and Technology buildings in Boulder and Fort Collins, Colorado. The appendix lists 49 nodes across the sites, with details on the make and model of fire alarm panels, as well as initiating devices, notification appliances, and supervisory points for each building. It also provides totals for fire panels, power supplies, signaling line circuits, notification circuits and devices across the portfolio. The related solicitation seeks proposals for fire protection systems inspection, testing, maintenance, repair and impairment coordinator services for the Boulder and Fort Collins sites. Offerors should have experience with the types of fire alarm and suppression systems described in the appendix. The agency is the Department of Commerce National Institute of Standards and Technology.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Appendix A - Fire Alarm Systems 12-2020.xls NIST Boulder FACP Node Number in Order on Fiber Network

12/7/2020

Building # Panel Location Panel Model # FACP Node # DVC Node # NCA Node # Building 1 DOC Police Command Center Room 1007 Work Station 15 N/A N/A

Building 24 North Main Entry Corridor 1200 by Room 1208 NFS2-640 24 124 N/A Building 26 West Main Vestibule 102 NFS2-640 26 126 N/A Building 3 Northeast Main Vestibule NFS2-3030 33 34 N/A Building 3 Room 1A112 (Anechoic Chambers) NFS2-320 35 N/A N/A

Building 22 Southeast Entry Room 1200 by Room 1102 NFS2-640 22 122 N/A Building 23 Riser Room 23-D NFS-320 23 N/A N/A

Building 8/11/12 East Main Entry Room 1000 by Room 1000A NFS2-640 8 9 N/A Building 27 East Entry Open Room Area Room 101 NFS-320 27 N/A N/A Building 25 East Main Entry Corridor 1400 by Room 1408 NFS2-640 25 125 N/A Building 21 East Center Entry Open Area Room 1009 across from Room 1010 NFS2-640 21 121 N/A

Building 4/5/3A/111 Open Office 1200 Impairment Coordinator Cubicle Work Station 50 N/A N/A Building 4/5 East Main Entry Open Area Room 1300 by Room 1003 NFS2-640 30 31 N/A

Building 42 (CUP) 2nd Floor Data Closet Room 210 (NOT Connected) Work Station 19 N/A N/A Building 42/9(CUP) Upper Level Control Room 204 NFS2-640 45 46 N/A

Building 92 North Entry Vestibule LO-A-1 NFS2-3030 92 93 N/A Building 2/2A/91 Center Corridor 1400 by Room 1409 NFS2-640 5 55 N/A

Building 1 4th Floor Wing 6 South Main Entry Corridor by Room 4663 NFS2-3030 16 116 N/A Building 1 4th Floor Wing 5 North Main Entry Corridor by Room 4556 (future) NFS2-3030 15 115 N/A Building 1 4th Floor Spine/Wing "T" Intersection by Room 4502 (next to Node 4) NCA-2 N/A N/A 20 Building 1 4th Floor Spine/Wing "T" Intersection by Room 4502 NFS2-3030 4 104 N/A Building 1 3rd Floor Wing 3 North Main Entry Corridor by Room 3353A NFS2-3030 13 113 N/A Building 1 3rdFloor Spine/Wing Intersection by Room 3061 NFS2-3030 3 103 N/A

Building 81 Building 81 South Entry Corridor by Room 1A102 NFS2-3030 60 61 N/A Building 81 Building 81 Clean Room Conference Room 1A111 NFS2-3030 62 63 N/A Building 1 2nd Floor Spine/Wing Intersection by Room 2029 NFS2-3030 2 102 N/A Building 1 1st Floor Lobby Office Room 1101C NFS2-3030 1 101 N/A Building 1 DOC Police Command Center Room 1007 NCA-2 N/A 105 17

49- Nodes Total Note: WWV and WWVB are not on the Fiber Network

Node Order on Fiber Network Appendix A - Fire Alarm Systems Page 1 of 37

Appendix A - Fire Alarm Systems 12-2020.xls Updated 12/7/2020

Node List by Node Number Appendix A - Fire Alarm Systems Page 2 of 37

Node # Building # Panel Model # Panel Location 1 Building 1 NFS2-3030 1st Floor Lobby Office 1101C 2 Building 1 NFS2-3030 2nd Floor Spine/Wings 1-2 Intersection 3 Building 1 NFS2-3030 3rdFloor Spine/Wing 4 Intersection 4 Building 1 NFS2-3030 4th Floor Spine 5 Building 2/2A/91 NFS2-640 Middle Hallway by Room 1409 8 Building 8/11/12 NFS2-640 East Main Entry Open Area 9 Building 8/11/12 DVC East Main Entry Open Area

13 Building 1 NFS2-3030 3rd Floor Wing 3 North Entry Corridor 15 Building 1 NFS2-3030 4th Floor Wing 5 North Entry Corridor (Future) 16 Building 1 NFS2-3030 4th Floor Wing 6 South Entry Corridor 17 Building 1 NCA-2 DOC Police Room 1007 18 Building 1 Workstation DOC Police Room 1007 IP: 192.168.10.11 Workstation 19 Building 42 Workstation 2nd Floor Data Closet 210 IP: 192.168.10.10 Workstation 20 Building 1 NCA-2 4th Floor Spine/Wing 5 Intersection, next to Node 4 21 Building 21 NFS2-640 East Center Entry Open Area 1009 22 Building 22 NFS2-640 Southeast Entry Warehouse 1200 23 Building 23 NFS-320 Riser Room 24 Building 24 NFS2-640 North Main Entry Corridor 1200 25 Building 25 NFS2-640 East Main Entry Corridor 1400 26 Building 26 NFS2-640 West Main Vestibule 27 Building 27 NFS-320 East Entry Open Area 30 Building 4/5/3A/111 NFS2-640 East Main Entry Open Area 1300 31 Building 4/5/3A/111 DVC East Main Entry Open Area 1300 33 Building 3 NFS2-3030 Northeast Main Vestibule 34 Building 3 DVC Northeast Main Vestibule 35 Building 3 NFS2-320 Room 1A112 (Anechoic Chambers) 45 Building 42/9 NFS2-640 (CUP) 2nd Floor Control Room 204 46 Building 42/9 DVC (CUP) 2nd Floor Control Room 204 50 Building 4 Workstation Open Office 1200 IC Office IP: 192.168.10.9 Workstation 55 Building 2 DVC Middle Hallway by Room 1409 60 Building 81 NFS2-3030 Building 81 (Main) South Corridor by Southeast Entry 61 Building 81 DVC Building 81 (Main) South Corridor by Southeast Entry 62 Building 81 NFS2-3030 Building 81 (Cleanrooms) Office 1A111 63 Building 81 DVC Building 81 (Cleanrooms) Office 1A111 92 Building 92 NFS2-3030 Building (BCF) Entry Vestibule LO-A-1 93 Building 92 DVC Building (BCF) Entry Vestibule LO-A-1

101 Building 1 DVC 1st Floor Lobby Office 1101C 102 Building 1 DVC 2nd Floor Spine/Wings 1-2 Intersection 103 Building 1 DVC 3rdFloor Spine/Wing 4 Intersection 104 Building 1 DVC 4th Floor Spine/Wing 5 Intersection 105 Building 1 DVC DOC Police Room 1007 113 Building 1 DVC 3rd Floor Wing 3 North Entry Corridor 115 Building 1 DVC 4th Floor Wing 5 North Entry Corridor 116 Building 1 DVC 4th Floor Wing 6 South Entry Corridor 121 Building 21 DVC East Center Entry Open Area 1009 122 Building 22 DVC Southeast Entry Warehouse 1200

Appendix A - Fire Alarm Systems 12-2020.xls Updated 12/7/2020

Node List by Node Number Appendix A - Fire Alarm Systems Page 3 of 37

124 Building 24 DVC North Main Entry Corridor 1200 125 Building 25 DVC East Main Entry Corridor 1400

Appendix A - Fire Alarm Systems 12-2020.xls

Boulder/Fort Collins Sites - Total Counts Appendix A - Fire Alarm Systems Page 4 of 37

FIRE ALARM SYSTEM INSPECTION REPORT

NIST Boulder / Fort Collins Sites, Total Device Count 12-2020

Total # of Fire Panels/WS/DVC 49 Total # of Releasing- Sapphire / FM200 12 Total # of Power Supplies 122 Total # of Releasing Panels- CO2 23

Total Number of SLC's 40

Total Number of IDC's 8

Total Number Of Notification Circuits on Entire System 436

Alarm Initiating Devices/Points Batteries Device type Quantity Size Quantity

Manual Pull Station 298 7 AH 106 I-Quad Smoke Acclimate Det. 33 12 AH 93

Photo Smoke Detector 1326 18 AH 12 Heat Detector 75 26 AH 14 Laser Detector 5 35 AH 10

Flow Switch 79 55 AH 14 Flame Detector 36 75 AH 4

Beam Smoke Detector 5

Gas Detection Interface 46 Alarm Notification Appliances Kitchen Hood/Ansul 1 Device type Quantity

AirSense 4 Horns 3 Vesda Fire 1 / 2 146 Horn/Strobe 60

Releasing / Solenoid 47 Strobe 188 Speakers 254

Supervisory Initiating Devices/Points Speaker/Strobes 992 Device Type Quantity Chime 0

Tamper Switch/Valves 132 Panic/Strobe 34 Duct Detectors 175 Bells 0 Low Air Switch 8 Outside Horn/ Strobes 32

AirSense 4

Vesda Alert/Action 136

Releasing 29

Fume Hood Panic 33

AED 25 Panel Types Security Door 18 Device type Quantity

Fire Pump 1 Workstation 3

NCA 2

NFS2-3030 11

NFS2-640 11

Miscellaneous Initiating Devices/Points NFS-320 3 Device Type Quantity DVC 21

Relays/Control Modules 411 LCD-160 2 Trouble Monitors 298 LCD-80 4 Non-Fire Modules 66

Liquid Level 2 Batteries Continued Air Flow 2 APC- RBC 3

Totals From Above= 6007

Building 1 Counts Appendix A - Fire Alarm Systems Page 5 of 37

NIST Bldg. 1, Total Device Count 12-2020 Nodes: 1, 2, 3, 4, 13, 15, 16, 17, 20, 101, 102, 103, 104, 105, 113, 115, 116

Total # of Fire Panels/WS/DVC 18 Total # of Releasing Panels- Sapphire 2 Total # of Power Supplies 22 Total # of Releasing Panels- CO2 0

Total Number of SLC's 14

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 136

** = Estimates only as Node 15 / 115 will be completed in 2022

Alarm Initiating Devices/Points ** Device type Quantity

Manual Pull Station 84 I-Quad Smoke Acclimate Det. 15

Photo Smoke Detector 641 Heat Detector 23 Laser Detector 5

Flow Switch 24 Flame Detector 0

Beam Smoke Detector 3 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 4

Vesda 0 Releasing / Solenoid 4

Batteries ** Size Quantity

7 AH 30

12 AH 10

18 AH 0

26 AH 2

35 AH 0

55 AH 12

75 AH 4

Alarm Notification Appliances **

Device type Quantity Horns 0

Horn/Strobe 0 Strobe 50

Speakers 167 Speaker/Strobes 390

Chime 0 Panic/Strobe 13

Bells 0 Outside Horn/ Strobes 7

Supervisory Initiating Devices/Points ** Device Type Quantity

Tamper Switch/Valves 47 Duct Detectors 85 Low Air Switch 4

AirSense 4 Vesda Alert/Action 0

Releasing 2 Fume Hood Panic 10

AED 5

Security Door 7

Panel Types

Workstation 1

NCA 1

NFS2-3030 7

NFS2-640 0

NFS-320 0

DVC 8

LCD-160 1

LCD-80 0

Miscellaneous Initiating Devices/Points **

Relays/Control Modules 131 Trouble Monitors 59 Non-Fire Modules 15

Liquid Level 0 Air Flow 0

Totals From Above= 1344

Building 1 Counts Appendix A - Fire Alarm Systems Page 6 of 37

NIST Bldg. 1, Device Count 12-2020

Nodes: Node 1, 101, 17, 105

Total # of Fire Panels/WS/DVC 4 Total # of Releasing Panels- Sapphire 1 Total # of Power Supplies 2 Total # of Releasing Panels- CO2 0

Total Number of SLC's 1

Total Number of IDC's

Total Number Of Notification Circuits on Entire System 11

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 14 I-Quad Smoke Acclimate Det. 2

Photo Smoke Detector 76 Heat Detector 14 Laser Detector 0

Flow Switch 1 Flame Detector 0

Beam Smoke Detector 3 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

Releasing / Solenoid 1

Batteries

7 AH 2

12 AH 0

18 AH 0

26 AH 0

35 AH 0

55 AH 4

110 AH 0

Alarm Notification Appliances

Horns

Horn/Strobe Strobe

Speakers Speaker/Strobes

Chime Panic/Strobe

Bells Outside Horn/ Strobes

Supervisory Initiating Devices/Points

Tamper Switch/Valves 1 Duct Detectors 6 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Releasing 1 Fume Hood Panic 0

AED 1

Security Door 1

Workstation 1

NCA 1

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 2

LCD-160 0

Miscellaneous Initiating Devices/Points

Relays/Control Modules 12 Trouble Monitors 9 Non-Fire Modules 3

Totals From Above= 175

Building 1 Counts Appendix A - Fire Alarm Systems Page 7 of 37

Nodes: Node 2, 102

Total # of Fire Panels/WS/DVC 2 Total # of Releasing Panels- Sapphire 1 Total # of Power Supplies 4 Total # of Releasing Panels- CO2 0

Total Number of SLC's 4

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 28

Alarm Initiating Devices/Points Device type Totals

Manual Pull Station 27 I-Quad Smoke Acclimate Det. 4

Photo Smoke Detector 230 Heat Detector 9 Laser Detector 5

Flow Switch 8 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 1

Releasing / Solenoid 3

7 AH 8

12 AH 2

18 AH 0

26 AH 0

35 AH 0

55 AH 2

Horns

Horn/Strobe Strobe

Speakers Speaker/Strobes

Chime Panic/Strobe

Device Type Totals

Tamper Switch/Valves 9 Duct Detectors 3 Low Air Switch 1

AirSense 1 Vesda Alert/Action 0

Fire Pump 1 Fume Hood Panic 5

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 38 Trouble Monitors 13 Non-Fire Modules 2

Totals From Above= 416

Building 1 Counts Appendix A - Fire Alarm Systems Page 8 of 37

Nodes: Node 2, 102

Alarm Initiating Devices/Points Device type SLC 1 SLC 2 SLC 3 SLC 4 Manual Pull Station 5 10 12 0 I-Quad Smoke Accl Det. 2 1 1 0 Photo Smoke Detector 66 83 81 0 Heat Detector 8 0 1 0 Laser Detector 5 0 0 0 Flow Switch 0 1 8 0 Flame Detector 0 0 0 0 Beam Smoke Detector 0 0 0 0 Gas Detection Interface 0 0 0 0 Kitchen Hood/Ansul 0 0 0 0 AirSense 0 1 0 0 Vesda 0 0 0 0 Releasing & Soleniod 1 1 0 0

Device Type SLC 1 SLC 2 SLC 3 SLC 4 Tamper Switch/Valves 0 1 8 0 Duct Detectors 1 0 2 0 Low Air Switch 0 0 1 0 AirSense 0 1 0 0 Vesda Alert/Action 0 0 0 0 Releasing 1 0 0 0 Fume Hood Panic 0 1 4 0

AED 1 0 0 0

Security Door 1 0 0 0

Relays/Control Modules 21 8 9 0 Trouble Monitors 1 2 10 0 Non-Fire Modules 1 1 0 0 Liquid Level 0 0 0 0 Air Flow 0 0 0 0

Building 1 Counts Appendix A - Fire Alarm Systems Page 9 of 37

Nodes: Node 3, 103

Total # of Fire Panels/WS/DVC 2 Total # of Releasing Panels- Sapphire 0 Total # of Power Supplies 3 Total # of Releasing Panels- CO2 0

Total Number of SLC's 4

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 30

Alarm Initiating Devices/Points Device type Totals

Manual Pull Station 12 I-Quad Smoke Acclimate Det. 2

Photo Smoke Detector 201 Heat Detector 0 Laser Detector 0

Flow Switch 0 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 2

Releasing / Solenoid 0

7 AH 6

12 AH 0

18 AH 0

26 AH 0

35 AH 0

Horns

Horn/Strobe Strobe

Speakers Speaker/Strobes

Chime Panic/Strobe

Tamper Switch/Valves 0 Duct Detectors 0 Low Air Switch 0

AirSense 2 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 1

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 5 Trouble Monitors 10 Non-Fire Modules 0

Totals From Above= 286

Building 1 Counts Appendix A - Fire Alarm Systems Page 10 of 37

Nodes: Node 3, 103

Device type SLC 1 SLC 2 SLC 3 SLC 4 Manual Pull Station 4 0 8 0 I-Quad Smoke Accl Det. 2 0 0 0 Photo Smoke Detector 88 0 113 0 Heat Detector 0 0 0 0 Laser Detector 0 0 0 0 Flow Switch 0 0 0 0 Flame Detector 0 0 0 0 Beam Smoke Detector 0 0 0 0

Gas Detection Interface 0 0 0 0 Kitchen Hood/Ansul 0 0 0 0 AirSense 1 0 1 0 Vesda 0 0 0 0 Releasing 0 0 0 0

Tamper Switch/Valves 0 0 0 0 Duct Detectors 0 0 0 0 Low Air Switch 0 0 0 0 AirSense 1 0 1 0 Vesda Alert/Action 0 0 0 0 Releasing 0 0 0 0 Fume Hood Panic 0 0 1 0

AED 1 0 0 0

Security Door 1 0 0 0

Relays/Control Modules 3 0 2 0 Trouble Monitors 9 0 1 0 Non-Fire Modules 0 0 0 0 Liquid Level 0 0 0 0 Air Flow 0 0 0 0

Building 1 Counts Appendix A - Fire Alarm Systems Page 11 of 37

Nodes: Node 4, 104

Total # of Fire Panels/WS/DVC 3 Total # of Releasing Panels- Sapphire 0 Total # of Power Supplies 1 Total # of Releasing Panels- CO2 0

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 4

Alarm Initiating Devices/Points Device type Totals

Manual Pull Station 7 I-Quad Smoke Acclimate Det. 7

Photo Smoke Detector 115 Heat Detector 0 Laser Detector 0

Flow Switch 2 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 1

7 AH 2

12 AH 0

18 AH 0

26 AH 0

35 AH 0

Horns

Horn/Strobe Strobe

Speakers Speaker/Strobes

Chime Panic/Strobe

Tamper Switch/Valves 4 Duct Detectors 1 Low Air Switch 0

AirSense 1 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

AED 2

Workstation 0

NCA 1

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 9 Trouble Monitors 7 Non-Fire Modules 2

Totals From Above= 175

Building 1 Counts Appendix A - Fire Alarm Systems Page 12 of 37

Nodes: Node 4, 104

Device type SLC 1

Manual Pull Station 7 I-Quad Smoke Acclimate Det. 7

Photo Smoke Detector 115 Heat Detector 0 Laser Detector 0

Flow Switch 2 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 1

Releasing 0

Device Type SLC 1 Tamper Switch/Valves 4

Duct Detectors 1 Low Air Switch 0

AirSense 1 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Device Type SLC 1 Relays/Control Modules 9

Trouble Monitors 7 Non-Fire Modules 2

Building 1 Counts Appendix A - Fire Alarm Systems Page 13 of 37

Nodes: Node 13, 113

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 15

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 4 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 3 Heat Detector 0 Laser Detector 0

Flow Switch 4 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 2

12 AH 0

18 AH 0

26 AH 2

35 AH 0

55 AH 0

75 AH 2

Horns

Horn/Strobe Strobe

Speakers Speaker/Strobes

Chime Panic/Strobe

Tamper Switch/Valves 9 Duct Detectors 16 Low Air Switch 1

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 4

AED 0

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 17 Trouble Monitors 5 Non-Fire Modules 2

Totals From Above= 94

Building 1 Counts Appendix A - Fire Alarm Systems Page 14 of 37

Nodes: Node 15 **, 115 **

Total # of Power Supplies ** 8 Total # of Releasing Panels- CO2 0

Total Number of SLC's ** 2

Total Number of IDC's ** 0

Total Number Of Notification Circuits on Entire System ** 36

** = Estimates only as Node 15 / 115 will be completed in 2022

Alarm Initiating Devices/Points ** Device type Quantity

Manual Pull Station ** 10 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector ** 12 Heat Detector 0 Laser Detector 0 Flow Switch ** 6 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 8

12 AH 8

18 AH 0

26 AH 0

35 AH 0

Horns

Horn/Strobe Strobe

Speakers Speaker/Strobes

Chime Panic/Strobe

Supervisory Initiating Devices/Points **

Tamper Switch/Valves ** 16 Duct Detectors ** 40 Low Air Switch ** 1

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Miscellaneous Initiating Devices/Points **

Relays/Control Modules ** 30 Trouble Monitors ** 10 Non-Fire Modules ** 4

Totals From Above= 198

Building 1 Counts Appendix A - Fire Alarm Systems Page 15 of 37

Nodes: Node 16, 116

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 12

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 10 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 4 Heat Detector 0 Laser Detector 0

Flow Switch 3 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 2

12 AH 0

18 AH 0

26 AH 0

35 AH 0

Horns

Horn/Strobe Strobe

Speakers Speaker/Strobes

Chime Panic/Strobe

Tamper Switch/Valves 8 Duct Detectors 19 Low Air Switch 1

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 20 Trouble Monitors 5 Non-Fire Modules 2

Totals From Above= 96

Building 1 Counts Appendix A - Fire Alarm Systems Page 16 of 37

NIST Bldg. 2, Device Count 12-2020 Nodes: 5, 55

Total # of Power Supplies 4 Total # of Releasing Panels- CO2 0

Total Number of SLC's 2

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 32

Alarm Initiating Devices/Points Device type SLC 1 SLC 2 Total

Manual Pull Station 15 15 30 I-Quad Smoke Acclimate Det. 0 1 1

Photo Smoke Detector 121 147 268 Heat Detector 10 0 10 Laser Detector 0 0 0

Flow Switch 3 6 9 Flame Detector 0 0 0

Beam Smoke Detector 0 2 2 Gas Detection Interface 0 0 0

Kitchen Hood/Ansul 0 0 0 AirSense 0 0 0

Vesda 0 0 0 Releasing / Solenoid 0 0 0

7 AH 8

12 AH 0

18 AH 0

26 AH 2

35 AH 0

Horns 0

Horn/Strobe 0 Strobe 8

Speakers 9 Speaker/Strobes 49

Chime 0 Panic/Strobe 18

Outside Horn/ Strobes 2

Device Type SLC 1 SLC 2 Total

Tamper Switch/Valves 2 6 8 Duct Detectors 1 0 1 Low Air Switch 0 1 1

AirSense 0 0 0 Vesda Alert/Action 0 0 0

Fire Pump 0 0 0 Fume Hood Panic 6 12 18

AED 2 1 3

Security Door 1 0 1

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

LCD-80 3

Device Type SLC 1 SLC 2 Total

Relays/Control Modules 3 16 19 Trouble Monitors 1 4 5 Non-Fire Modules 3 6 9

Liquid Level 0 0 0 Air Flow 0 0 0

Totals From Above= 526

Building 1 Counts Appendix A - Fire Alarm Systems Page 17 of 37

NIST Bldg. 3 Main FACP Device Count 12-2020 Nodes:33, 34

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 14

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 11 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 11 Heat Detector 3 Laser Detector 0

Flow Switch 5 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

Vesda 8 Releasing / Solenoid 1

7 AH 6

12 AH 6

18 AH 0

26 AH 2

35 AH 0

Horns 1

Horn/Strobe 0 Strobe 3

Speakers 34 Speaker/Strobes 116

Chime 0 Panic/Strobe 0

Outside Horn/ Strobes 1

Tamper Switch/Valves 9 Duct Detectors 6 Low Air Switch 1

AirSense 0 Vesda Alert/Action 2

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 9 Trouble Monitors 9 Non-Fire Modules 2

Totals From Above= 270 building 3 Anechoic Chamber Counts Appendix A - Fire Alarm Systems Page 18 of 37

NIST Bldg. 3 Anechoic Chambers, Device Count 12-2020 Nodes: 35

Total # of Fire Panels/WS/DVC 1 Total # of Releasing Panels- Sapphire 1

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 9

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 3 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 2 Heat Detector 0 Laser Detector 0

Flow Switch 0 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

Vesda Fire 1 / 2 6 Releasing / Solenoid 3

7 AH 2

12 AH 6

18 AH 2

26 AH 0

35 AH 0

Horns 0

Horn/Strobe 3 Strobe 3

Speakers 0 Speaker/Strobes 0

Chime 0 Panic/Strobe 0

Outside Horn/ Strobes 0

Tamper Switch/Valves 3 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 6

Releasing 0 Fume Hood Panic 0

Security Door 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 0

NFS-320 1

DVC 0

Relays/Control Modules 15 Trouble Monitors 3 Non-Fire Modules 0

Totals From Above= 73

Building 4, 5, 3A, and 11 Counts Appendix A - Fire Alarm Systems Page 19 of 37

NIST Bldg. 4, 5, 3A, and 111 Device Count 12-2020 Nodes: 30, 31, 50

Total # of Power Supplies 1 Total # of Releasing Panels- CO2 0

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 12

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 13 I-Quad Smoke Acclimate Det. 5

Photo Smoke Detector 81 Heat Detector 2 Laser Detector 0

Flow Switch 1 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 2

12 AH 0

18 AH 0

26 AH 0

35 AH 2

Horns 0

Horn/Strobe 0 Strobe 10

Speakers 0 Speaker/Strobes 25

Chime 0 Panic/Strobe 2

Tamper Switch/Valves 1 Duct Detectors 0 Low Air Switch 1

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 2

Workstation 1

NCA 1

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

Relays/Control Modules 13 Trouble Monitors 1 Non-Fire Modules 1

Totals From Above= 186

Buildings 8, 11, and 12 Counts Appendix A - Fire Alarm Systems Page 20 of 37

NIST Bldg. 8, 11, and 12 Device Count 12-2020 Nodes: 8, 9

Total # of Power Supplies 0 Total # of Releasing Panels- CO2 0

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 7

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 7 I-Quad Smoke Acclimate Det. 1

Photo Smoke Detector 9 Heat Detector 1 Laser Detector 0

Flow Switch 0 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 0

12 AH 0

18 AH 0

26 AH 0

35 AH 0

Horns 1

Horn/Strobe 1 Strobe 2

Speakers 0 Speaker/Strobes 3

Chime 0 Panic/Strobe 0

Outside Horn/ Strobes 3

Tamper Switch/Valves 0 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

Relays/Control Modules 0 Trouble Monitors 0 Non-Fire Modules 0

Totals From Above= 43

Building 21 Counts Appendix A - Fire Alarm Systems Page 21 of 37

NIST Bldg. 21, Device Count 12-2020 Nodes: 21, 121

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 10

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 3 I-Quad Smoke Acclimate Det. 1

Photo Smoke Detector 7 Heat Detector 3 Laser Detector 0

Flow Switch 0 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 0

12 AH 0

18 AH 0

26 AH 0

35 AH 2

Horns 0

Horn/Strobe 0 Strobe 3

Speakers 1 Speaker/Strobes 6

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 0 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

Relays/Control Modules 2 Trouble Monitors 0 Non-Fire Modules 1

Totals From Above= 45

Building 22 Counts Appendix A - Fire Alarm Systems Page 21 of 37

NIST Bldg. 22, Device Count 12-2020 Nodes: 22, 122

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 10

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 8 I-Quad Smoke Acclimate Det. 1

Photo Smoke Detector 34 Heat Detector 3 Laser Detector 0

Flow Switch 1 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 0

12 AH 0

18 AH 0

26 AH 0

35 AH 2

Horns 0

Horn/Strobe 0 Strobe 4

Speakers 0 Speaker/Strobes 14

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 1 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

Relays/Control Modules 2 Trouble Monitors 0 Non-Fire Modules 1

Totals From Above= 89

Building 23 Counts Appendix A - Fire Alarm Systems Page 21 of 37

NIST Bldg. 23, Device Count 12-2020 Nodes:23

Total # of Fire Panels/WS/DVC 1 Total # of Releasing Panels- Sapphire 0

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 5

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 4 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 1 Heat Detector 0 Laser Detector 0

Flow Switch 1 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 2

Kitchen Hood/Ansul 0 AirSense 0

7 AH 0

12 AH 0

18 AH 2

26 AH 0

35 AH 0

Horns 1

Horn/Strobe 0 Strobe 0

Speakers 0 Speaker/Strobes 0

Chime 0 Panic/Strobe 1

Tamper Switch/Valves 0 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 1

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 0

NFS-320 1

DVC 0

Relays/Control Modules 1 Trouble Monitors

Non-Fire Modules

Liquid Level 2 Air Flow 2

Totals From Above= 28

Building 24 Counts Appendix A - Fire Alarm Systems Page 21 of 37

NIST Bldg. 24, Device Count 12-2020 Nodes: 24, 124

Total # of Fire Panels/WS/DVC 2 Total # of Releasing Panels- FM-200 2 Total # of Power Supplies 5 Total # of Releasing Panels- CO2 0

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 25

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 20 I-Quad Smoke Acclimate Det. 2

Photo Smoke Detector 105 Heat Detector 6 Laser Detector 0

Flow Switch 5 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

Vesda 8 Releasing / Solenoid 4

7 AH 10

12 AH 0

18 AH 2

26 AH 2

35 AH 0

Horns 0

Horn/Strobe 4 Strobe 15

Speakers 5 Speaker/Strobes 37

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 4 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 8

Releasing 4 Fume Hood Panic 3

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

Relays/Control Modules 27 Trouble Monitors 12 Non-Fire Modules 2

Totals From Above= 326

Building 25 Counts Appendix A - Fire Alarm Systems Page 21 of 37

NIST Bldg. 25, Device Count 12-2020 Nodes: 25, 125

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 10

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 6 I-Quad Smoke Acclimate Det. 2

Photo Smoke Detector 18 Heat Detector 10 Laser Detector 0

Flow Switch 0 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 0

12 AH 0

18 AH 0

26 AH 0

35 AH 2

Horns 0

Horn/Strobe 0 Strobe 2

Speakers 0 Speaker/Strobes 7

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 0 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

Relays/Control Modules 3 Trouble Monitors 0 Non-Fire Modules 0

Totals From Above= 67

Building 26 Counts Appendix A - Fire Alarm Systems Page 21 of 37

NIST Bldg. 26, Device Count 12-2020 Nodes: 26, 126

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 10

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 1 I-Quad Smoke Acclimate Det. 2

Photo Smoke Detector 31 Heat Detector 2 Laser Detector 0

Flow Switch 1 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 1 AirSense 0

7 AH 0

12 AH 0

18 AH 0

26 AH 0

35 AH 2

Horns 0

Horn/Strobe 0 Strobe 12

Speakers 0 Speaker/Strobes 13

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 1 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

Relays/Control Modules 12 Trouble Monitors 0 Non-Fire Modules 1

Totals From Above= 97

Building 27 Counts Appendix A - Fire Alarm Systems Page 21 of 37

NIST Bldg. 27, Device Count 12-2020 Node: 27

Total # of Fire Panels/WS/DVC 1 Total # of Releasing Panels- Sapphire 0

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 4

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 1 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 1 Heat Detector 2 Laser Detector 0

Flow Switch 0 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 0

12 AH 0

18 AH 2

26 AH 0

35 AH 0

Horns 0

Horn/Strobe 1 Strobe 0

Speakers 0 Speaker/Strobes 0

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 0 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 0

NFS-320 1

DVC 0

Relays/Control Modules 0 Trouble Monitors 0 Non-Fire Modules 0

Totals From Above= 16

Building 42, 9, and Tunnel Counts Appendix A - Fire Alarm Systems Page 28 of 37

NIST Bldg. 42/CUP, 9, and Tunnel Device Count 12-2020 Nodes: 45, 46

Total # of Fire Panels/WS/DVC 3 Total # of Releasing Panels- Sapphire 0

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 10

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 15 I-Quad Smoke Acclimate Det. 2

Photo Smoke Detector 25 Heat Detector 3 Laser Detector 0

Flow Switch 8 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

7 AH 6

12 AH 0

18 AH 2

26 AH 0

35 AH 0

Horns 0

Horn/Strobe 0 Strobe 14

Speakers 0 Speaker/Strobes 21

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 10 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Fire Pump 0 Fume Hood Panic 0

Workstation 1

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 1

LCD-80 1

Relays/Control Modules 7 Trouble Monitors 1 Non-Fire Modules 0

Totals From Above= 138

Building 81 Counts Appendix A - Fire Alarm Systems Page 29 of 37

NIST Bldg. 81 Device Count 12-2020 Nodes: 60, 61, 62, 63

Total # of Fire Panels/WS/DVC 4 Total # of Releasing Panels- Sapphire 0 Total # of Power Supplies 76 Total # of Releasing Panels- CO2 23

Total Number of SLC's 9

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 116

Alarm Initiating Devices/Points Device type TOTALS

Manual Pull Station 63 I-Quad Smoke Acclimate Det. 1

Photo Smoke Detector 42 Heat Detector 7 Laser Detector 0

Flow Switch 24 Flame Detector 34

Beam Smoke Detector 0 Gas Detection Interface 44

Kitchen Hood/Ansul 0 AirSense 0

Vesda Fire 1 / 2 112 Releasing / Solenoid 23

7 AH 34

12 AH 63

18 AH 0

26 AH 4

35 AH 0

Horns 0

Horn/Strobe 23 Strobe 27

Speakers 38 Speaker/Strobes 287

Chime 0 Panic/Strobe 0

Device Type TOTALS

Tamper Switch/Valves 40 Duct Detectors 83 Low Air Switch 0

AirSense 0 Vesda Alert/Action 112

Gas Detection Interface 42 Security Door 0

AED 6

Fire Pump 1 Releasing 23

Workstation 0

NCA 0

NFS2-3030 2

NFS2-640 0

NFS-320 0

DVC 2

Relays/Control Modules 149 Trouble Monitors 181 Non-Fire Modules 26

Liquid Level 0

Pendant 3

Totals From Above= 1726

Building 81 Counts Appendix A - Fire Alarm Systems Page 30 of 37

NIST Bldg. 81 Main, Device Count 2-2019 Nodes: 60, 61

Total # of Power Supplies 18 Total # of Releasing Panels- CO2 0

Total Number of SLC's 2

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 98

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 26 I-Quad Smoke Acclimate Det. 1

Photo Smoke Detector 40 Heat Detector 7 Laser Detector 0

Flow Switch 13 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface- O2 3

Kitchen Hood/Ansul 0 AirSense 0

Vesda 2

7 AH 28

12 AH 8

18 AH 0

26 AH 2

35 AH 0

Horns 0

Horn/Strobe 0 Strobe 27

Speakers 38 Speaker/Strobes 237

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 29 Duct Detectors/Smokes 79

Low Air Switch 0 AirSense 0

Vesda Alert/Action 2 Fire Pump Points 4 Fume Hood Panic 0

AED 5

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 86 Trouble Monitors 14 Non-Fire Modules 15

Totals From Above= 790

Building 81 Counts Appendix A - Fire Alarm Systems Page 31 of 37

NIST Bldg. 81 Cleanroom, Device Count 2-2019

Nodes: 62, 63

Total # of Power Supplies 58 Total # of Releasing Panels- CO2 23

Total Number of SLC's 7

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 18

Alarm Initiating Devices/Points Device type TOTALS

Manual Pull Station 37 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 2 Heat Detector 0 Laser Detector 0

Flow Switch 11 Flame Detector 34

Beam Smoke Detector 0 Gas Detection Interface 41

Kitchen Hood/Ansul 0 AirSense 0

Vesda Fire 1 / 2 110

7 AH 6

12 AH 55

18 AH 0

26 AH 2

35 AH 0

Horns 0

Horn/Strobe 23 Strobe 0

Speakers 0 Speaker/Strobes 50

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 11 Duct Detectors 4 Low Air Switch 0

AirSense 0 Vesda Alert/Action 110

Gas Detection Interface 42 Fume Hood Panic 0

AED 1

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 63 Trouble Monitors 167 Non-Fire Modules 11

Liquid Level 0

Pendant 3

Totals From Above= 939

Building 81 Counts Appendix A - Fire Alarm Systems Page 32 of 37

Device type SLC 1 SLC 2 SLC 3

Manual Pull Station 12 10 11 I-Quad Smoke Acclimate Det. 0 0 0

Photo Smoke Detector 1 0 0 Heat Detector 0 0 0 Laser Detector 0 0 0

Flow Switch 3 4 4 Flame Detector 11 13 10

Beam Smoke Detector 0 0 0 Gas Detection Interface 0 0 0

Kitchen Hood/Ansul 0 0 0 AirSense 0 0 0

Vesda Fire 1 / 2 18 12 16 Releasing 9 6 8

Device Type SLC 1 SLC 2 SLC 3 Tamper Switch/Valves 3 4 4

Duct Detectors 0 0 0 Low Air Switch 0 0 0

AirSense 0 0 0 Vesda Alert/Action 18 12 16

Gas Detection Interface 0 0 0 Fume Hood Panic 0 0 0

AED 0 0 1

Security Door 0 0 0

Releasing 9 6 8

Device Type SLC 1 SLC 2 SLC 3

Relays/Control Modules 1 2 1 Trouble Monitors 23 18 24 Non-Fire Modules 3 4 4

Liquid Level 0 0 0

Pendant 0 0 3

Building 81 Counts Appendix A - Fire Alarm Systems Page 33 of 37

Device type SLC 4 SLC 5 SLC 6

Manual Pull Station 0 0 0 I-Quad Smoke Acclimate Det. 0 0 0

Photo Smoke Detector 0 0 0 Heat Detector 0 0 0 Laser Detector 0 0 0

Flow Switch 0 0 0 Flame Detector 0 0 0

Beam Smoke Detector 0 0 0 Gas Detection Interface 33 8 0

Kitchen Hood/Ansul 0 0 0 AirSense 0 0 0

Vesda Fire 1 / 2 0 24 40 Releasing 0 0 0

Device Type SLC 4 SLC 5 SLC 6 Tamper Switch/Valves 0 0 0

Duct Detectors 0 0 0 Low Air Switch 0 0 0

AirSense 0 0 0 Vesda Alert/Action 0 24 40

Gas Detection Interface 34 8 0 Fume Hood Panic 0 0 0

AED 0 0 0

Security Door 0 0 0

Releasing 0 0 0

Device Type SLC 4 SLC 5 SLC 6

Relays/Control Modules 0 1 0 Trouble Monitors 34 16 20 Non-Fire Modules 0 0 0

Liquid Level 0 0 0

Pendant 0 0 0

Building 81 Counts Appendix A - Fire Alarm Systems Page 34 of 37

NIST Bldg. 81 Cleanroom, Full Device Count 2-2019

Device type SLC 7

Manual Pull Station 4

I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 1

Heat Detector 0

Laser Detector 0

Flow Switch 0

Flame Detector 0

Beam Smoke Detector 0

Gas Detection Interface 0

Kitchen Hood/Ansul 0

AirSense 0

Vesda Fire 1 / 2 0

Device Type SLC 7

Tamper Switch/Valves 0

Duct Detectors 4

Low Air Switch 0

AirSense 0

Vesda Alert/Action 0

Gas Detection Interface 0

Fume Hood Panic 0

AED 0

Device Type SLC 7

Relays/Control Modules 58

Trouble Monitors 32

Non-Fire Modules 0

Liquid Level 0

Pendant 0

Building 81 Counts Appendix A - Fire Alarm Systems Page 35 of 37

NIST Bldg. 92, Device Count 12-2020 Nodes: 92, 93

Total # of Fire Panels/WS/DVC 2 Total # of Releasing Systems- Sapphire 3 Total # of Power Supplies 6 Total # of Releasing Panels- CO2 0

Total Number of SLC's 1

Total Number of IDC's 0

Total Number Of Notification Circuits on Entire System 18

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 15 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 2 Heat Detector 0 Laser Detector 0

Flow Switch 0 Flame Detector 0

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

Vesda Fire 1 / 2 12 Releasing / Solenoid 8

7 AH 2

12 AH 14

18 AH 0

26 AH 2

35 AH 0

Horns 0

Horn/Strobe 6 Strobe 6

Speakers 0 Speaker/Strobes 24

Chime 0 Panic/Strobe 0

Outside Horn/ Strobes 8

Tamper Switch/Valves 8 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 8

Releasing 0 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 1

NFS2-640 0

NFS-320 0

DVC 1

Relays/Control Modules 21 Trouble Monitors 15 Non-Fire Modules 8

Totals From Above= 192

Building WWVA Counts Appendix A - Fire Alarm Systems Page 36 of 37

NIST Bldg. WWV, Full Device Count 12-2020 Nodes: N/A

Total # of Fire Panels/WS/DVC 1 Total # of Releasing Panels- Sapphire 2

Total Number of SLC's 1

Total Number of IDC's 4

Total Number Of Notification Circuits on Entire System 4

Alarm Initiating Devices/Points Device type Quantity

Manual Pull Station 7 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 27 Heat Detector 0 Laser Detector 0

Flow Switch 0 Flame Detector 1

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

Releasing / Solenoid 2

7 AH 4

12 AH 0

18 AH 4

26 AH 0

35 AH 0

Horns 0

Horn/Strobe 13 Strobe 16

Speakers 0 Speaker/Strobes 0

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 0 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0

Releasing 2 Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 0

Relays/Control Modules 0 Trouble Monitors 6 Non-Fire Modules 0

Totals From Above= 96

Building WWVB Counts Appendix A - Fire Alarm Systems Page 37 of 37

NIST Bldg. WWVB, Full Device Count 12-2020 Nodes: N/A

Total # of Fire Panels/WS/DVC 1 Total # of Releasing Panels- Sapphire 2

Total Number of SLC's 1

Total Number of IDC's 4

Total Number Of Notification Circuits on Entire System 4

Manual Pull Station 7 I-Quad Smoke Acclimate Det. 0

Photo Smoke Detector 21 Heat Detector 0 Laser Detector 0

Flow Switch 0 Flame Detector 1

Beam Smoke Detector 0 Gas Detection Interface 0

Kitchen Hood/Ansul 0 AirSense 0

Releasing / Solenoid 2

7 AH 4

12 AH 0

18 AH 2

26 AH 0

35 AH 0

Horns 0

Horn/Strobe 9 Strobe 13

Speakers 0 Speaker/Strobes 0

Chime 0 Panic/Strobe 0

Tamper Switch/Valves 0 Duct Detectors 0 Low Air Switch 0

AirSense 0 Vesda Alert/Action 0 Releasing Panel 2

Fume Hood Panic 0

Workstation 0

NCA 0

NFS2-3030 0

NFS2-640 1

NFS-320 0

DVC 0

Relays/Control Modules 0 Trouble Monitors 6 Non-Fire Modules 0

Totals From Above= 81

NIST Bldg. 1, Total Device Count 12-2020
NIST Bldg. 1, Device Count 12-2020
NIST Bldg. 1, Device Count 12-2020
NIST Bldg. 1, Device Count 12-2020
NIST Bldg. 1, Device Count 12-2020
NIST Bldg. 1, Device Count 12-2020
NIST Bldg. 1, Device Count 12-2020
NIST Bldg. 1, Device Count 12-2020
NIST Bldg. 2, Device Count 12-2020
NIST Bldg. 3 Main FACP Device Count 12-2020
NIST Bldg. 3 Anechoic Chambers, Device Count 12-2020
NIST Bldg. 4, 5, 3A, and 111 Device Count 12-2020
NIST Bldg. 8, 11, and 12 Device Count 12-2020
NIST Bldg. 21, Device Count 12-2020
NIST Bldg. 22, Device Count 12-2020
NIST Bldg. 23, Device Count 12-2020
NIST Bldg. 24, Device Count 12-2020
NIST Bldg. 25, Device Count 12-2020
NIST Bldg. 26, Device Count 12-2020
NIST Bldg. 27, Device Count 12-2020
NIST Bldg. 42/CUP, 9, and Tunnel Device Count 12-2020
NIST Bldg. 81 Device Count 12-2020
NIST Bldg. 81 Main, Device Count 2-2019
NIST Bldg. 81 Cleanroom, Device Count 2-2019
NIST Bldg. 81 Cleanroom, Device Count 2-2019
NIST Bldg. 81 Cleanroom, Device Count 2-2019
NIST Bldg. 81 Cleanroom, Full Device Count 2-2019
NIST Bldg. 92, Device Count 12-2020
NIST Bldg. WWV, Full Device Count 12-2020
NIST Bldg. WWVB, Full Device Count 12-2020