Main Report Summary - Page 1 of 4
438 New Karner Road Albany, New York 12205 Phone: (518) 250-4047
REPORT OF LIMITED ASBESTOS INSPECTION
Location of Inspection: Building 12 Roof
Stratton Air National Guard
Ronald Reagan Way
Glenville, New York
Client: Stratton Air National Guard
1220 Washington Avenue
Albany, New York
Alpine Project #: 20-25594-A
Material or Area Inspected: Building #12 Roofs
Asbestos Materials Tested: Tar on deck (Roofs 3 & 4), roof ply (Roof 4)
Non-Asbestos Containing
Materials: Tar on deck (Roofs 1 & 2), roof ply (Roof 3)
Date(s) of Inspection: May 1, 2020
Report Date: May 8, 2020
Inspection Performed By: Alpine Environmental Services, Inc.
438 New Karner Road
Albany, New York 12205
Inspector(s): Paul Van Zandt: NYSDOL Cert.#AH95-0281
NYS Department of Labor Certified Asbestos Inspector
May 2020 Stratton ANG - Building #12
Main Report Summary - Page 2 of 4
438 New Karner Road, Albany, New York 12205 - Phone: (518) 250-4047
Scope and Purpose
This report is intended to document the limited asbestos inspection of the building #12 roof of the Stratton Air Nation Guard base located at Ronald Reagan Way, Glenville, New York.
“Asbestos containing materials”, as defined by the United States Environmental Protection
Agency (EPA), is any material containing greater than 1% by weight of asbestos. Friable samples
(samples easily crushed/pulverized by hand pressure), were analyzed via Polarized Light
Microscopy (PLM) and Non-Friable samples (samples not easily crushed/pulverized by hand pressure), were analyzed via Transmission Electron Microscopy (TEM) by EMSL Laboratory of
New York, New York, a New York State Department of Health Approved Laboratory (ELAP
#11506).
Description
The building was a single-story block military structure. There were two roof levels. On each level half of the roof was on a metal deck and the other half was a concrete deck. The roofing consisted of a rubber membrane over multiple layers of rigid foam board insulation. There were roofing plies attached to the metal decks of roofs 3 and 4.
Limitations
Quantities of asbestos containing materials were estimated and the user must field verify all quantities. Only the four roofs shown by the client were inspected.
Results of Asbestos Inspection
Bulk samples were collected, as prescribed by US EPA ASHARA protocols for the number and types of samples. The following asbestos containing materials were found at the Building 12 roofs of the Stratton Air National Guard base in Glenville, New York:
ACM
(Sample #s) Location Quantity Substrate Friability Condition
Roofs
Tar on Deck
(1-03) Roof #3 770 sq. ft. Metal
Non-
Friable Good
Tar on Deck, Roof
Ply
(1-04, 3-01)
Roof #4 2,300 sq.
ft.
Metal
Non-
Friable Good
*Quantities are estimates only and should be field verified by the user.
Main Report Summary - Page 3 of 4
The following materials were sampled and determined not to contain asbestos:
Non-Asbestos
Material Locations Sample #s
Roofs
Tar on Deck Roofs #1 & #2 1-01, 1-02
Roof Ply Roof #3 2-01, 2-02
Conclusion & Recommendations
Any materials not sampled during this inspection should be considered suspect unless sampled and determined to be non-asbestos. All asbestos containing materials must be abated prior to the demolition/renovation of any of the structures unless performed under a variance issued by the NYS Department of Labor. Disturbance/Abatement of any asbestos containing materials, as well as necessary air monitoring, must be performed by a NYS DOL licensed contractor, in accordance with state and federal regulations (NYS DOL ICR 56 and US EPA 40 CFR).
If Alpine Environmental Services can be of further assistance on this matter, please contact Craig
Petreikis at either (518) 250-4047 ext. 313 or craigp@alpineenv.com.
Sincerely, Alpine Environmental Services, Inc.
Paul Van Zandt
NYS Dept. of Labor Asbestos Inspector
Enclosures: Results, NYSDOL Handling License(s), NYSDOL Handling Certificate(s), NYSDOH ELAP
License(s)
Main Report Summary - Page 4 of 4
Roof Diagram Building #12
Roof #2 Roof #1
Roof #4
Roof #3
EMSL Analytical, Inc.
307 West 38th Street New York, NY 10018
Tel/Fax: (212) 290-0051 / (212) 290-0058 http://www.EMSL.com / manhattanlab@emsl.com
032007404EMSL Order:
Customer ID: ALPI50
Customer PO:
Project ID:
Attention: Phone:Alpine Environmental Services (518) 250-4047
Fax:438 New Karner Road
Received Date:Albany, NY 12205 05/02/2020 10:55 AM
Analysis Date: 05/06/2020
Collected Date: 05/01/2020
Project: 20-25594-A/ STRATTON AIR NATION GUARD / GLENVILLE NY
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 1-01 Description BUILDING 12 ROOF # 1 - TAR ON DECK
032007404-0001 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Gray/ Black Inconclusive: None Detected05/06/2020 100.00% Other
TEM NYS 198.4 NOB Gray/ Black None Detected05/06/2020 100.00% Other
Sample ID 1-02 Description BUILDING 12 ROOF # 2 - TAR ON DECK
032007404-0002 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black Inconclusive: None Detected05/06/2020 100.00% Other
TEM NYS 198.4 NOB Black05/06/2020 None 100.00% Other <1% Chrysotile
Sample ID 1-03 Description BUILDING 12 ROOF # 3 - TAR ON DECK
032007404-0003 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black05/06/2020 None 91.80% Other 8.20% Chrysotile
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/06/2020
Sample ID 1-04 Description BUILDING 12 ROOF # 4 - TAR ON DECK
032007404-0004 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black05/06/2020 1.00% Glass 94.80% Other 4.20% Chrysotile
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/06/2020
Sample ID 2-01 Description BUILDING 12 ROOF # 3 - ROOF PLY
032007404-0005 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black Inconclusive: None Detected05/06/2020 <1.00% Glass 100.00% Other
TEM NYS 198.4 NOB Black05/06/2020 None 100.00% Other <1% Chrysotile
Initial report from: 05/06/2020 20:02:33
Page 1 of 3ASB_198x_0009_0001 Printed 5/6/2020 8:35:24PM
Tel/Fax: (212) 290-0051 / (212) 290-0058 http://www.EMSL.com / manhattanlab@emsl.com
032007404EMSL Order:
Customer ID: ALPI50
Customer PO:
Project ID:
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 2-02 Description BUILDING 12 ROOF # 3 - ROOF PLY
032007404-0006 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black Inconclusive: None Detected05/06/2020 100.00% Other
Final Residue <1% of original subsample.
TEM NYS 198.4 NOB Black05/06/2020 None 100.00% Other <1% Chrysotile
Sample ID 3-01 Description BUILDING 12 ROOF # 4 - ROOF PLY
032007404-0007 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black05/06/2020 None 95.00% Other 5.00% Chrysotile
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/06/2020
Sample ID 3-02 Description BUILDING 12 ROOF # 4 - ROOF PLY
032007404-0008 Homogeneity
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Positive Stop (Not Analyzed)05/06/2020
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/06/2020
Page 2 of 3ASB_198x_0009_0001 Printed 5/6/2020 8:35:24PM
Tel/Fax: (212) 290-0051 / (212) 290-0058 http://www.EMSL.com / manhattanlab@emsl.com
032007404EMSL Order:
Customer ID: ALPI50
Customer PO:
Project ID:
Test Report:Asbestos Analysis of Bulk Material
The samples in this report were submitted to EMSL for analysis by Asbestos Analysis of Bulk Materials via NYS ELAP Approved Methods. The reference number for these samples is the EMSL Order ID above. Please use this reference number when calling about these samples.
Report Comments:
Sample Receipt Date:
Analysis Completed Date: Analysis Completed Time:
Sample Receipt Time:5/4/2020 10:55 AM
5/6/2020 8:09 PM
Analyst(s):
Kerrie Gibson PLM NYS 198.6 NOB (7) Ted Lam TEM NYS 198.4 NOB (4)
Samples reviewed and approved by:
James Hall, Laboratory Manager or Other Approved Signatory
NOB = Non Friable Organically Bound N/A = Not Applicable VCM = Vermiculite Containing Material
-In New York State, TEM is currently the only method that can be used to determine if NOB materials can be considered or treated as non-asbestos containing.
All samples examined for the presence of vermiculite when analyzed via NYS 198.1.
-NYS Guidelines for Vermiculite containing samples are available at http://www.wadsworth.org/labcert/elapcert/forms/VermiculiteInterimGuidance_Rev070913.pdf EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by
EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client.
Samples were received in good condition unless otherwise noted.
This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. This report may contain data that is not covered by the NVLAP accreditation.
Samples analyzed by EMSL Analytical, Inc. New York, NY NYS ELAP 11506
Page 3 of 3ASB_198x_0009_0001 Printed 5/6/2020 8:35:24PM
OrderID: 032007404
New York State – Department of Labor Division of Safety and Health License and Certificate Unit State Campus, Building 12
Albany, NY 12240
ASBESTOS HANDLING LICENSE
Alpine Environmental Services, Inc.
438 New Karner Road
Albany, NY 12205
FILE NUMBER: 00-0320
LICENSE NUMBER: 29095
LICENSE CLASS: RESTRICTED
DATE OF ISSUE: 07/10/2019
EXPIRATION DATE: 07/31/2020
Duly Authorized Representative – Craig Petreikis:
This license has been issued in accordance with applicable provisions of Article 30 of the Labor Law of New York State and of the New York State Codes, Rules and Regulations (12 NYCRR Part 56). It is subject to suspension or revocation for a (1) serious violation of state, federal or local laws with regard to the conduct of an asbestos project, or (2) demonstrated lack of responsibility in the conduct of any job involving asbestos or asbestos material.
This license is valid only for the contractor named above and this license or a photocopy must be prominently displayed at the asbestos project worksite. This license verifies that all persons employed by the licensee on an asbestos project in New York State have been issued an Asbestos Certificate, appropriate for the type of work they perform, by the New York State Department of Labor.
Eileen M. Franko, Director SH 432 (8/12) For the Commissioner of Labor
NEW YORK STATE DEPARTMENT OF HEALTH
WADSWORTH CENTER
Expires ] 2:01 AM April ()1 ·~2b21 Issued April 01, 2020
CERTIFICATE OF APPROVAL FOR LABORATORY SERVICE
Issued in accordance with and pursuant to section 502 Public Health Law of f\tew~York State
MR. JAMES HALL
EMSL ANALYTICAL, INC
--307 WEST 38TH_STREET
- NEWYORK, NY 10()18
NY Lab ld No: 1_1506 · is hereby APPROVED as an Environmental Laboratory for the category
ENVIRONMENTAL ANALYSES SOLID AND HAZARDOUS WASTE -
All approved subcategories and/or analytes are listed below:
Asbestos in _Friable Material
Asbestos in !'Jon-Friable Materiai-PLM
Asbestos in Non-Friable Materiai-TEM
Item 198.1 of Manual
EPA 600/M4/82/020
Item 198.6 of Manual (NOB by PLM)
Item 198.4 of Manual
Asbestos-Vermiculite-Containing Material Item 198.8 of Manual
Serial No.: 61413 ProReJ1Y of the New York State Department of-Healfh. Ce[tificates are valid only at the address shown._must be conspicu(')_usJy posted;cand are pdnte_d_-o_n:SeeJ,Jre gaper. Continued accreditation depends