Att 6 - Brand Name Justification - Bronx BP 7-1-25.pdf
PDF 162 KB Posted
- Attached to
- 526-22-900 Replace Boiler Plant Construction - Bronx VAMC Federal contract opportunity
- Solicitation number
- 36C77625B0028
About this file
This document is a Justification and Approval (J&A) for Other Than Full and Open Competition for a boiler plant replacement project at the Bronx VA Medical Center. The procurement, valued between $20-50 million, will be a firm-fixed price contract set aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The project requires 14 specific brand-name items from manufacturers like Cleaver Brooks, Caterpillar, Schneider Electric, and others, which are critical for maintaining system compatibility, standardization, and operational integrity of the medical center's infrastructure.
The justification details the specific requirements for each brand-name component, including boilers, deaerators, emergency generators, transformers, electrical panels, circuit breakers, fire alarm systems, building automation systems, and security monitoring equipment. Each item is justified based on its unique interface with existing systems, potential operational risks of using alternative manufacturers, and the need to ensure patient and staff safety. The document also confirms Buy American Act compliance for most items, with some manufactured in the United States and one transformer manufactured in Canada but considered compliant under trade agreements.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project No. 526-22-900 Project Title: Replace Boiler Plant Construction – Bronx VAMC
VHAPG Part 806.3 OFOC Page 1 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450
DEPARTMENT OF VETERANS AFFAIRS
Justification and Approval (J&A) for Other Than Full and Open Competition
Acquisition Plan Action ID: 36C776-25-AP-1450
1. Contracting Activity:
Veterans Health Administration (VHA), Program Contracting Activity Central (PCAC) The proposed procurement, Invitation for Bid (IFB) 36C77625B0028, is for the Replace Boiler Plant Construction project at the Bronx VA Medical Center (VAMC) in Bronx, NY.
2. Nature and/or Description of the Action Being Processed:
This justification is to support the Replace Boiler Plant Construction project at the Bronx VAMC, that will be awarded as a firm-fixed price contract. This justification is for other than full and open competition for the procurement of certain construction materials. The use of a particular brand name for the items listed below accommodate standardization of these items throughout the facility.
a. Boilers with Economizers, Model NB-200D-40 with E6-ST-SER-5 with Boiler Controls
i. Cleaver Brooks
b. Deaerator (DUO TMV-70-3500-ADAC Pressurized tray type deaerator with 3500-gallon storage tank) and Condensate Storage Tank – 3,000 Gallons (SRG-300)
i. Cleaver Brooks
c. Emergency Generator
i. Caterpillar
d. Transformers - Ultra Efficiency Low-Loss Transformers
i. Powersmiths
e. Automatic Transfer Switch (ATS)
i. ASCO
f. Electrical Panel Boards
i. Schneider Electric USA/Square D
g. Circuit Breakers
i. Schneider Electric USA/Square D
h. Receptacles
i. Schneider Electric USA/Square D
i. Disconnect Switches
i. Schneider Electric USA/Square D
j. Fire Alarm System/Devices
i. Johnson Controls (JCI) Simplex
k. Building Automation System (Tridium-based JCI FX system)
i. Independent Temperature Control Inc. (ITC)
l. Security Camera and Monitoring System
i. Motorola Avigilon
m. Fuel Tank Monitoring System
i. Veeder-Root
n. Mortar Flooring System
i. Stonhard
3. Description of Supplies/Services Required to Meet the Agency’s Needs:
VHAPG Part 806.3 OFOC Page 2 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450
This procurement is for the Replace Boiler Plant Construction project at the Bronx VAMC.
The scope includes everything necessary to complete the project that meets the requirements of the Department of Veterans Affairs. There are fourteen (14) brand name items listed for which the VA is not able to accept equal or alternate items. The value of the items are listed below. The VAAR Construction magnitude for the entire project is between $20,000,000 and $50,000,000.
a. Boilers with Economizers, Model NB-200D-40 with E6-ST-SER-5, and Boiler Controls
i. Cleaver Brooks ii.
iii. Description: Complete installation of three 40,000 lbs/hr water-tube boilers in the same location as the existing boilers supplying heat for the entire facility with each boiler being installed with an exhaust stack economizer to provide greater efficiency for boiler performance and Complete programming of new boiler direct digital controls (DDC) shall be applied to the new boilers and associated equipment maintaining compatibility with the existing DDC building automation system throughout the facility.
b. Deaerator (DUO TMV-70-3500-ADAC Pressurized tray type deaerator with 3500-gallon storage tank) and Condensate Tank – 3000 Gallons (SRG-3000)
i. Cleaver Brooks ii.
iii. Description: Complete installation of a deaerator in approximately the same location as the existing deaerator, providing 20 minutes storage from overflow level at peak boiler plant output requirements and new condensate storage (surge) tank in the same location as the existing condensate storage tank to prevent overflow and ensuring efficient condensate recycling from the boiler heating system.
c. Emergency Generator
i. Caterpillar ii.
iii. Description: Complete installation and programming of a new 480-volt, 350-kW emergency standby generator that will accommodate the new boiler electrical requirements in the case of an emergency power incident to the facility.
d. Transformers - Ultra Efficiency Low-Loss Transformers
i. Powersmiths ii.
iii. Description: Complete installation of transformers to provide efficient transitions from higher to lower voltages
e. Automatic Transfer Switch (ATS)
i. ASCO ii.
iii. Description: Complete installation, and programming of a new transfer switch
(ATS) shall be provided acting as a switch between the emergency generator and the existing power serving the boilers.
f. Electrical Panel Boards
i. Schneider Electric USA/Square D ii.
VHAPG Part 806.3 OFOC Page 3 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450
iii. Description: Complete installation of electrical panelboards to matching existing to ensure and maintain proper power for the new boiler plant equipment.
g. Circuit Breakers
i. Schneider Electric USA/Square D ii.
iii. Description: Complete installation of new circuit breakers shall be installed
h. Receptacles
i. Leviton ii.
iii. Description: Complete installation of new receptacles to ensure and maintain proper operation of the existing powered equipment and to support boiler plant operations.
i. Disconnect Switches
i. Schneider Electric USA/Square D ii.
iii. Description: Complete installation of disconnect switches for all new installed equipment that require accessible, line-of-sight safety shut off in event of emergencies or regular maintenance.
j. Fire Alarm System
i. Johnson Controls (JCI) Simplex ii.
iii. Description: Complete installation and programming of fire alarm initiating and notification appliances matching existing to ensure and maintain proper operation of the existing fire alarm system.
k. Building Automation System (Tridium-based JCI FX system)
i. Independent Temperature Control Inc. (ITC) ii.
iii. Description: Complete installation and programming of an extension to the building automation system compatible with existing to ensure and maintain proper operation of the boiler plant and provide notifications and alerts.
l. Security Camera and Monitoring System
i. Motorola Avigilon ii.
iii. Description: Complete installation, programming, and licensing of digital video capture and recording equipment matching existing to ensure and maintain proper operation of the video surveillance system.
m. Fuel Tank Monitoring System
i. Veeder-Root ii.
iii. Description: Complete installation and programming of a new fuel oil maintenance system to filter and remove moisture from the stored fuel oil in the fuel oil tanks.
n. Mortar Flooring System
i. Stonhard ii.
iii. Description: Robust, impact resistant, and durable flooring for that can withstand heavy foot traffic, high heat, increased humidity and doesn’t chip easily.
VHAPG Part 806.3 OFOC Page 4 of 12 Revision: 03 Effective Date: 04/15/24
4. Statutory Authority Permitting Other than Full and Open Competition:
(X) Only One Responsible Source and No Other Supplies or Services Will Satisfy Agency Requirements per 41 USC §3304(a)(1) as implemented by FAR 6.302-1;
( ) Unusual and Compelling Urgency per 41 USC §3304(a)(2) as implemented by FAR 6.302-2;
( ) Industrial Mobilization, Engineering, Developmental or Research Capability or Expert Services per 41 USC §3304(a)(3) as implemented by FAR 6.302-3;
( ) International Agreement per 41 USC §3304(a)(4) as implemented by FAR 6.302-4
( ) Authorized or Required by Statute per 41 USC §3304(a)(5) as implemented by FAR 6.302-5;
( ) National Security per 41 USC §3304(a)(6) as implemented by FAR 6.302-6;
( ) Public Interest per 41 USC §3304(a)(7) as implemented by FAR 6.302-7;
5. Demonstration that the Contractor’s Unique Qualifications or Nature of the
Acquisition Requires the Use of the Authority Cited Above (applicability of authority):
These items have been standardized throughout the Bronx VAMC. Installing a different manufacturers’ systems will create significant duplication in costs for the facility, and in most cases the equipment will not function properly. The specific impact for not using the brand name items is listed below:
a. Boilers with Economizers, Model NB-200D-40 with E6-ST-SER-5 with Boiler Controls
i. Cleaver Brooks
ii. Impact: The current design is contingent on the basis of the boiler type. There are key differences between boilers based on size and type that have knock-on effects for the entirety of the system design. The boiler heating system is vital for providing a safe environment for patients, visitors, staff, and the facility. Modifications of the boiler type, brand or sizing without the proper design intent can compromise the integrity of the entire system. Factory trained and authorized service must be located and supported by OEM within a limited travel time to provide emergency service support. Using non- Cleaver Brooks components or systems may result in operational failure or incompatibility with the entirety of the boiler plant system design.
Unauthorized modifications risk compromising the reliability and code compliance of the boiler heating system, including integration with temperature controls, HVAC maintenance, and emergency notification systems.
b. Deaerator (DUO TMV-70-3500-ADAC Pressurized tray type deaerator with 3500-gallon storage tank) and Condensate Storage Tank – 3,000 Gallons (SRG-3000)
i. Cleaver Brooks
ii. Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with the designed boiler system. The boiler plant heating system is critical for the environment patients, visitors, and staff. Replacement of the boiler heating system without the correct OEM components and service can compromise the integrity of the entire system.
Factory trained and authorized service must be located and supported by OEM within a limited travel time to provide emergency service support. Using non-Cleaver Brooks components or systems may result in operational failure or incompatibility with the new boiler heating infrastructure. The heating system is vital for safety, providing adequate environment for patient staff and
VHAPG Part 806.3 OFOC Page 5 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450 visitors. Unauthorized modifications risk compromising the reliability and code compliance of the boiler plant heating system..
c. Emergency Generator
i. Caterpillar
ii. Impact: Any other equipment not of the existing manufacturer may not provide correct interface and operability with the existing electrical system.
The emergency backup generator system is critical for safeguarding patients, visitors, staff, and the facility. Modifications of the existing without the correct OEM components and service can compromise the integrity of the entire system. Factory trained and authorized service must be located and supported by OEM within a limited travel time to provide emergency service support. Using non-Caterpillar components or systems may result in operational failure or incompatibility with the existing emergency infrastructure. The emergency generator system is vital for safety, providing automatic backup responses to protect patients, staff, and visitors.
Unauthorized modifications risk compromising the reliability and code compliance of the electrical system and boiler plant.
d. Transformers - Ultra Efficiency Low-Loss Transformers
i. Powersmiths
ii. Impact: Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with our existing electrical system. The existing electrical system utilizes mainly Powersmiths transformers. The electrical system is critical for providing power for patient care, visitors, staff, and the facility. Modifications of the existing electrical system without the correct OEM components and service can compromise the integrity of our entire system. Standardization is crucial. Using non- Schneider Electric/Square D components or systems may result in delayed maintenance, operational failure or even incompatibility with the existing electrical infrastructure. The electrical system is vital for life safety, providing power and automatic system responses to protect patients, staff, and visitors.
Unauthorized modifications risk compromising the reliability and code compliance of the electrical system.
e. Automatic Transfer Switch (ATS)
i. ASCO
ii. Impact: Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with our existing electrical system. The electrical system is critical for providing power for patient care, visitors, staff, and the facility. Modifications of the existing electrical system without the correct OEM components and service can compromise the integrity of our entire system. Standardization is crucial. Using non-ASCO components or systems may result in delayed maintenance, operational failure or even incompatibility with the existing electrical infrastructure. The electrical system is vital for life safety, providing power and automatic system responses to protect patients, staff, and visitors. Unauthorized modifications risk compromising the reliability and code compliance of the electrical system.
f. Electrical Panel Boards
i. Schneider Electric USA/Square D
ii. Impact: Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with our existing electrical system. The existing electrical system utilizes mainly Square D electrical
VHAPG Part 806.3 OFOC Page 6 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450 panel boards. The electrical system is critical for providing power for patient care, visitors, staff, and the facility. Modifications of the existing electrical system without the correct OEM components and service can compromise the integrity of our entire system. Standardization is crucial. Using non- Schneider Electric/Square D components or systems may result in delayed maintenance, operational failure or even incompatibility with the existing electrical infrastructure. The electrical system is vital for life safety, providing power and automatic system responses to protect patients, staff, and visitors.
Unauthorized modifications risk compromising the reliability and code compliance of the electrical system.
g. Circuit Breakers
i. Schneider Electric USA/Square D
ii. Impact: Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with our existing electrical system and maintenance operations. The existing electrical system utilizes mainly Square D circuit breakers. The electrical system is critical for providing power for patient care, visitors, staff, and the facility. Modifications of the existing electrical system without the correct OEM components can compromise the integrity of our entire system. Standardization is crucial.
Using non-Schneider Electric/Square D components or systems may result in delayed maintenance, operational failure or even incompatibility with the existing electrical infrastructure. The electrical system is vital for life safety, providing power and automatic system responses to protect patients, staff, and visitors. Unauthorized modifications risk compromising the reliability and code compliance of the electrical system.
h. Receptacles
i. Leviton
ii. Impact: Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with our existing electrical system and maintenance operations. The existing electrical system utilizes mainly Leviton receptacles. The electrical system is critical for providing power for patient care, visitors, staff, and the facility. Modifications of the existing electrical system without the correct OEM components can compromise the integrity of our entire system. Standardization is crucial.
Using non-Leviton components or systems may result in delayed maintenance, operational failure or even incompatibility with the existing electrical infrastructure. The electrical system is vital for life safety, providing power and automatic system responses to protect patients, staff, and visitors.
Unauthorized modifications risk compromising the reliability and code compliance of the electrical system.
i. Disconnect Switches
i. Schneider Electric USA/Square D
ii. Impact: Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with our existing electrical system and maintenance operations. The existing electrical system utilizes mainly Square D disconnect switches. The electrical system is critical for providing power for patient care, visitors, staff, and the facility. Modifications of the existing electrical system without the correct OEM components can compromise the integrity of our entire system. Standardization is crucial.
Using non-Schneider Electric/Square D components or systems may result in
VHAPG Part 806.3 OFOC Page 7 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450 delayed maintenance, operational failure or even incompatibility with the existing electrical infrastructure. The electrical system is vital for life safety, providing power and automatic system responses to protect patients, staff, and visitors. Unauthorized modifications risk compromising the reliability and code compliance of the electrical system.
j. Fire alarm system
i. Johnson Controls (JCI) Simplex
ii. Impact: Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with the existing fire protection system. The fire protection system is critical for safeguarding patients, visitors, staff, and the facility. Modifications of the existing without the correct OEM components and service can compromise the integrity of the entire system. Factory trained and authorized service must be located and supported by OEM within a limited travel time to provide emergency service support. Using non-Simplex components or systems may result in operational failure or incompatibility with the existing fire alarm infrastructure. The fire alarm system is vital for life safety, providing early warning and automatic system responses to protect patients, staff, and visitors. Unauthorized modifications risk compromising the reliability and code compliance of the fire protection system, including integration with elevator recall, HVAC shutdown, and emergency notification systems.
k. Building Automation System (Tridium-based JCI FX system)
i. Independent Temperature Control Inc. (ITC)
ii. Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with the existing building automation system (BAS). The BAS is a specialty system critical for providing a safe environment for patients, visitors, and staff. Modifications to the existing system without the correct OEM components and service can compromise the integrity of the entire system. Trained specialists and authorized service must be located and supported by OEM within a limited travel time to provide emergency service support. Using non-Tridium-based JCI components or systems may result in operational failure or incompatibility with the existing fire alarm infrastructure. The BAS is vital for patient and staff safety, providing early warning and automatic system responses to protect patients, staff, and visitors from unsafe cold environmental conditions. Unauthorized modifications risk compromising the reliability and code compliance of the HVAC system.
l. Security Camera and Monitoring System
i. Motorola Avigilon
ii. Impact: Installing video surveillance devices and equipment not manufactured by Motorola Avigilon may result in loss of interface compatibility with the existing monitoring, recording, and control infrastructure. Any other devices and equipment not of the existing manufacturer may not provide correct interface and operability with existing monitoring, recording, and control equipment. The video surveillance system is crucial for safeguarding patients, visitors, staff, and the facility against unlawful and unauthorized activities. Modifications of the existing system without the correct original equipment manufacturer (OEM) components and service can compromise the integrity of the entire system. Factory trained
VHAPG Part 806.3 OFOC Page 8 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450 and authorized service must be located and supported by OEM within a limited travel time to provide emergency service support.
m. Fuel Tank Monitoring System
i. Veeder-Root
ii. Impact: Using any other devices and equipment not of the existing manufacturer will require redesign by the architectural/engineering firm as the fuel tank monitoring system parameters are contingent on the system design.
The fuel tank monitoring system is critical for monitoring for any fuel leaks which are dependent on pressure, piping, and environmental conditions.
Modifications of the new fuel monitoring systems without A/E redesign could compromise the integrity of the existing fuel monitoring system.
n. Mortar Flooring System
i. Stonhard
ii. Impact: Using any other material not of the existing manufacturer will risk poor quality and more frequent maintenance than necessary and impacts operational effectiveness of the facility. The flooring provided by this manufacturer meets a specific need for the critical area that is the boiler plant. Due to the intense heat, high humidity and frequent traffic only a limited few can meet those conditions in terms of durability. It is imperative that as the flooring is laid down that it lasts as long as the newly installed boilers if not longer due to maintenance difficulties and operational impacts once the boiler plant job is completed. Changes to the flooring material and manufacturer could compromise the integrity of the existing flooring so an impact resistant long-lasting flooring material must be used.
6. Description of Efforts Made to ensure that offers are solicited from as many potential sources as deemed practicable:
In accordance with the Competition in Contracting Act (CICA), the components listed above are identified as brand name; however, the overall procurement will be competed as a Service-Disabled Veteran-Owned Small-Business (SDVOSB) set-aside. This Justification for Other Than Full and Open Competition will be posted to Contract Opportunities with the solicitation.
7. Determination by the CO that the Anticipated Cost to the Government will be Fair and Reasonable:
The Government estimate was prepared by the VA team and confirmed by the Contracting Officer’s Representative (COR). The anticipated price to the Government for the items requested to be brand name is approximately .
The items for which brand name approval is being requested are subsequent components to the overall construction project. This procurement will be competed and based on competition; the CO will make a determination of fair and reasonable pricing prior to award.
8. Description of the Market Research Conducted and the Results, or a Statement of the Reasons Market Research Was Not Conducted:
The market research for the required brand name items was conducted and prepared by the COR and A/E. This information was then shared with the CO for further review. The CO was in concurrence with information provided that supported these brand name items. Approval
VHAPG Part 806.3 OFOC Page 9 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450 of the items as brand name only is critical for the overall efficiency of the completed project and the entire Bronx VAMC.
The market research concerning the required brand name items was previously conducted when the procurement of these items were originally purchased. The manufacturers and products are exclusively acceptable for reasons outlined in this J&A.
An additional purpose of the market research was to ensure requirements of the Buy American Act (BAA) has been met for each of the brand name items identified. The A/E team reviewed each of the compliance standards for the BAA and compared it with the components in each of the brand name items. After their thorough review, they have concluded that each item is in compliance with the BAA. See an overview below for each item:
a. Boilers with Economizers, Model NB-200D-40 with E6-ST-SER-5 with Boiler Controls
i. Cleaver Brooks
ii. Based on discussions with customer service and extensive research online, it has been confirmed that these items are manufactured in Lincoln, Nebraska.
Therefore, there are no concerns regarding the “Buy American” compliance.
b. Deaerator (DUO TMV-70-3500-ADAC Pressurized tray type deaerator with 3500-gallon storage tank) and Condensate Storage Tank – 3,000 Gallons (SRG-3000)
i. Cleaver Brooks
ii. Based on discussions with customer service and extensive research online, it has been confirmed that these items are manufactured in Lincoln, Nebraska.
Therefore, there are no concerns regarding the “Buy American” compliance.
c. Emergency Generator
i. Caterpillar
ii. Based on extensive research online, it has been confirmed that these items are manufactured in Newberry, South Carolina. Therefore, there are no concerns regarding the “Buy American” compliance.
d. Transformers - Ultra Efficiency Low-Loss Transformers
i. Powersmiths
ii. Based on extensive research online, it has been confirmed that these items are manufactured in Brampton, Canada. However, Canada is one of the countries recognized in FAR 52.225-11 Buy American-Construction Materials under Trade Agreements, as a “Designated Country” or World Trade Organization Government Procurement Agreement (WTO GPA) country. The solicitation issued for this project will contain this clause.
e. Automatic Transfer Switch (ATS)
i. ASCO
ii. Based on discussions with customer service and extensive research online, it has been confirmed that this product is manufactured in United States of America. Therefore, there are no concerns regarding the “Buy American” compliance.
f. Electrical Panel Boards
VHAPG Part 806.3 OFOC Page 10 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450
i. Schneider Electric USA/Square D
ii. Based on discussions with customer service and extensive research online, it has been confirmed that this product is manufactured in United States of
g. Circuit Breakers
ii. Based on discussions with customer service and extensive research online, it has been confirmed that this product is manufactured in United States of America (USA). Therefore, there are no concerns regarding the “Buy American” compliance.
h. Receptacles
i. Leviton
ii. Based on discussions with customer service and extensive research online, it has been confirmed that this product is manufactured in United States of
i. Disconnect Switches
ii. Based on discussions with customer service and extensive research online, it has been confirmed that this product is manufactured in United States of
j. Mortar Flooring System
i. Stonhard
ii. Based on extensive research online, it has been confirmed that this item is manufactured in Maple Shade, New Jersey. Therefore, there are no concerns regarding the “Buy American” compliance.
9. Any Other Facts Supporting the Use of Other than Full and Open Competition:
The new components (software and servers) must be able to tie into the existing and operational systems including the use of existing hardware. At this time, there are no competing vendors who have the programming rights to the systems, and products must be fully compatible with the existing systems being used at the Bronx VAMC.
10. Listing of Sources that Expressed, in Writing, an Interest in the Acquisition:
Not applicable. It is the responsibility of the offerors and the general contractor awarded the project to locate suppliers and obtain pricing for all materials and components, including the items listed in this justification.
11. A Statement of the Actions, if any, the Agency May Take to Remove or Overcome any
Barriers to Competition before Making subsequent acquisitions for the supplies or services required:
There will be competition for the overall procurement. It will be the responsibility of the offerors to obtain pricing from the suppliers of the items and to submit a competitive proposal for the project.
VHAPG Part 806.3 OFOC Page 11 of 12 Revision: 03 Effective Date: 04/15/24
12. Requirements Certification: I certify that the requirement outlined in this justification is a
Bona Fide Need of the Department of Veterans Affairs and that the supporting data under my cognizance, which are included in the justification, are accurate and complete to the best of my knowledge and belief.
David Ng Date Supervisor General Engineer Bronx VAMC
13. Approvals in accordance with the VHAPM Part 806.3 OFOC SOP:
a. Contracting Officer Certification (required): I certify that the foregoing justification is accurate and complete to the best of my knowledge and belief.
Joseph Rossano Date Contracting Officer Program Contracting Activity Central
b. One Level Above the Contracting Officer (Required over SAT but not exceeding $750K): I certify the justification meets requirements for other than full and open competition.
Donald A. Marsh III Date
Supervisory Contracting Officer Program Contracting Activity Central
c. Director of Contracting (If HCA review/signature is required): I certify the justification meets requirements for other than full and open competition.
Richard C. Dahmen Date
Director of Contracting, PCAC
d. VHA RPO HCA Review and Approval: I have reviewed the foregoing justification and find it to be complete and accurate to the best of my knowledge and belief and
06/30/2025
DAVID NG
Digitally signed by DAVID
NG
Date: 2025.06.30 15:24:05 -04'00'
JOSEPH
ROSSANO
Digitally signed by JOSEPH
ROSSANO
Date: 2025.06.30 16:07:21 -04'00'
DONALD
MARSH
Digitally signed by
DONALD MARSH
Date: 2025.07.01 06:52:34 -04'00'
RICHARD DAHMEN Digitally signed by RICHARD DAHMEN Date: 2025.07.02 07:06:25 -04'00'
VHAPG Part 806.3 OFOC Page 12 of 12 Revision: 03 Effective Date: 04/15/24 Acquisition ID#: 36C776-25-AP-1450 recommend approval (if over $75 million) or approve ($750K to $75 million) for other than full and open competition.
Daryl A. Berg Date Executive Director, Regional Procurement Office Central Head of Contracting Activity