Att 04 - Final Bldg 220 221 223 225 Narrative).pdf
PDF 6 MB Posted
- Attached to
- Large-Tier Electrical Construction IDIQ
- Solicitation number
- 1333ND26RNB190031
About this file
This is a Fire Alarm Replacements Narrative document prepared by CFR Engineering Consultants for Buildings 220, 221, 223, and 225 at the National Institute of Standards and Technology (NIST) in Gaithersburg, Maryland under Contract No. 133ND21DNB190025, Task Order 133ND24FNB190117, dated August 29, 2025.
The narrative specifies the design and installation of new addressable fire alarm systems compliant with NFPA 72 standards to replace existing systems in the four buildings. Each building will receive a Simplex 4100ES Fire Alarm Control Panel (FACP) located at the main entrance (first floor lobby) with a transponder panel in the attic serving upper floors. The systems must be fully installed and operational before demolition of existing equipment. All signaling line circuits, panel-to-panel communications, initiating device circuits, and notification appliance circuits will meet Class A or Class X requirements as appropriate. Notification will utilize speakers and strobes meeting ABA and NFPA standards, with separate circuits provided for each level and spine, and 70V RMS amplifier circuits throughout. Initiating devices will include photoelectric smoke detectors and heat detectors as required by codes, with manual pull stations positioned to ensure all occupants can reach one within 200 feet. The document includes extensive audibility and intelligibility calculations using EASE Evac software for various room types across the buildings, demonstrating compliance with required speech intelligibility standards (CIS values and SPL measurements) for all spaces including labs, offices, basements, sub-basements, and penthouse areas. Design approval from the NIST Authority Having Jurisdiction and an approved NIST-383 form are required before work commencement.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Prepared By:
CFR Engineering Consultants, Inc.
20251 Century Blvd, Suite 120
Germantown, MD 20874
(877) 871-4229
Buildings 220, 221, 223, & 225 – Fire Alarm Replacements
National Institute of Standards and Technology
FA Narrative Final Submission
CFR Project Number: 24049 August 29th, 2025
NIST – Building 220, 221, 223, & 225 Fire Alarm Replacements Contract No. 133ND21DNB190025
Task Order. 133ND24FNB190117
IFC Submission%
August 29, 2025
FIRE ALARM AND MASS NOTIFICATION SYSTEM
The existing fire alarm systems in Buildings 220, 221, 223, and 225 will be demolished. A new, addressable fire alarm system, compliant with NFPA 72, will be installed to notify occupants inside the buildings. This system will be a fully integrated, electrically supervised, addressable, intelligent fire alarm and detection system, featuring both manual and automatic operation, with annunciation throughout the buildings.
Buildings 220, 221, 223, and parts of 225 are not equipped with sprinkler systems. Automatic detection will be provided throughout each building to provide total coverage. The system will notify building occupants through a combination of speakers and strobes. These speakers will meet
NFPA 72 standards, including intelligibility requirements. The mass notification system will provide audible messaging both within the buildings and via exterior speakers located at exits and key outdoor areas where personnel may be present.
A new fire alarm control panel (FACP), specifically the Simplex 4100ES, will be installed at the main entrance of each building. This FACP will be compatible with the existing fire alarm reporting loop. The system will include a battery backup power supply with sufficient capacity to operate under quiescent conditions, and in the event of an emergency, it will maintain functionality during fire or other emergency situations.
FIRE ALARM DESIGN
General
All fire protection devices, equipment, and materials shall be listed for their intended use in accordance with FM Global and/or Underwriters Laboratories (UL) standards. Unless otherwise specified, each floor of every building will be covered by a single fire alarm zone.
The new fire alarm system must be fully installed before the demolition of the existing system. All new fire alarm systems must be approved, tested, and fully operational prior to the removal of the existing systems in each building.
NIST shall be given the option to salvage any existing fire alarm devices slated for demolition before they are disposed of.
Control Panels
All buildings will be provided with a 4100ES FACP located in the first floor lobby (serving circuits within the sub-basement, basement, first floor, and second floor) and a 4100ES transponder panel located in the Attic (serving circuits within the third floor, attic, and penthouse).
August 29, 2025
Circuit Performance
Fire protective signaling systems shall have the following circuit performance in accordance with
NFPA 72:
• All signaling line circuits (SLCs) shall meet Class A requirements.
• All panel-to-panel communication shall meet Class X requirements.
• Initiating device circuits (IDCs) serving more than one device shall meet Class A requirements. IDCs serving only one device, such as an IDC from a monitor module to an adjacent waterflow alarm, may meet Class B requirements.
• All notification appliance circuits (NACs) shall meet Class A requirements. All fire alarm notification circuits shall use a 70 v RMS amplifier circuit.
Fire alarm circuits shall be provided as follows:
• Separate Strobe Circuits for Each Level.
• Separate Strobe Circuits for Each Spine.
• Separate Speaker Circuits for Each Level.
• Separate Speaker Circuits for Each Spine.
• Separate SLC Circuits for Each Level.
• Separate SLC Circuits for Each Spine.
• Separate Exterior Speaker Circuits for Each 1st Level and Penthouse Level.
• Separate Acoustic Hailing Device (Loudspeaker) Circuit for Each 1st Level.
• Separate M&E Circuit for Each Panel.
Notification
Notification shall be via speakers and strobes. Spacing and location of speakers and strobes shall be compliant with the ABA (Architectural Barriers Act), NFPA 72, NIST O/P 7400 and NIST S
7401. The quantity and location of interior speakers shall be determined by the audibility requirements. For voice systems, additional speakers tapped at lower wattage provide greater intelligibility.
Visual signals shall be provided via multi-candela, field selectable strobe lights utilizing high-intensity, white xenon flash tube with a clear plastic lens. The body of the strobe shall be white in color marked “ALERT”. All strobes shall be UL 1971 compliant as well as ABA compliant.
August 29, 2025
Notification devices shall be installed in locations required by NFPA 101 and NFPA 72 and NIST
7401 and meet audibility/intelligibility requirements. See Appendix for audibility and intelligibility calculations. (To be provided at a later submission)
Initiating Devices
Fire alarm initiating devices shall be provided in accordance with NFPA 101 and NFPA 72 except as modified herein.
• Smoke detectors shall only be installed as required by codes. Only photoelectric smoke detectors shall be utilized.
• Heat detectors shall be provided thoughout each building as required by codes.
• Duct detectors shall only be installed as required by codes or referenced herein.
• All automatic detection devices shall be clearly labeled and access shall be provided for testing and maintenance.
• Manual pull stations shall be required at all exits and so that all occupants can reach a pull station within 200ft of travel distance.
PERMITTING REQUIREMENTS
All design must be reviewed and approved by the NIST AHJ, and no work shall be started without an approved NIST-383 form as required by NIST S 7401.01.
CFR Engineering August 29, 2025
Audibility and Intelligibility Calcs
Appendix – A.1
NIST SINGLE
MODULE LAB
Alec Lauterbach Stanton Engineering
Wednesday, May 14, 2025
EASE Evac
Wednesday, May 14, 2025 1/4
Project Information Title: NIST SINGLE MODULE LAB
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary Quantity Type
1 E70 (Cooper Notification)
Layout Overview
Wednesday, May 14, 2025 2/4
Room: Single Module Lab
Label: Single Module Lab
Room Height: 10.00 ft
Dimensions (WxD): 23.81 ft x 10.70 ft
Volume: 2488.3 cb ft (net: 2488.3 cb ft)
Surface Area: 1187.5 sq ft (net: 1187.5 sq ft)
Ear Height: 5.51 ft
Network Voltage: 70.7 V
Power Consumption: 0.3 W
Sound Sources Summary Quantity Type
1 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 248.83 Concrete, Painted, Wall or Floor
Ceiling Main Area 248.83 Concrete, Painted, Wall or Floor
Wall #1 Main Area 224.31 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 41.37 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 13.65 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 65.43 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 238.04 Steel, Wall, Floor, or Ceiling
Wall #6 Main Area 107.00 Steel, Wall, Floor, or Ceiling
Wednesday, May 14, 2025 3/4
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 4.58 3.75 8.00 0.0 0.0 1/4 W (70V)
Mapping and Distribution
Direct SPL (A-Weighted), Broadband
Average: 72.6 dB ±20.1 dB
Average + Std. Dev.: 92.7 dB
Average - Std. Dev.: 52.6 dB
Max. Value: 86.7 dB
Min. Value: -178.3 dB
Data Points: 1993
Area Covered: Direct SPL(A) Average
95% ≥69.1 dB 74.8 dB
90% ≥69.6 dB 75.1 dB
85% ≥70.0 dB 75.4 dB
Wednesday, May 14, 2025 4/4
80% ≥70.5 dB 75.7 dB
Additional Mappings
CIS
Average: 0.73 ±0.01
Average + Std. Dev.: 0.74
Average - Std. Dev.: 0.72
Max. Value: 0.78
Min. Value: 0.72
Data Points: 1993
Area Covered: CIS Average
95% ≥0.72 0.73
90% ≥0.72 0.73
85% ≥0.72 0.73
80% ≥0.72 0.73
NIST FA COMMON
ROOMS
[Your Name] [Your Company]
Wednesday, May 14, 2025 1/5
Project Information Title: NIST FA COMMON ROOMS
Author: [Your Name]
Company: [Your Company]
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary Quantity Type
Wednesday, May 14, 2025 2/5
Room: Single Module Office
Label: Single Module Office
Room Height: 10.00 ft
Dimensions (WxD): 16.03 ft x 10.75 ft
Volume: 1721.5 cb ft (net: 1721.5 cb ft)
Surface Area: 879.7 sq ft (net: 879.7 sq ft)
Ear Height: 6.80 ft
Network Voltage: 70.7 V
Power Consumption: 0.3 W
Sound Sources Summary Quantity Type
1 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 172.15 Concrete, Painted, Wall or Floor
Ceiling Main Area 172.15 Concrete, Painted, Wall or Floor
Wall #1 Main Area 160.29 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 107.40 Concrete, Painted, Wall or Floor
Wednesday, May 14, 2025 3/5
Wall #3 Main Area 160.19 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 107.47 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 0.98 9.59 8.00 0.0 0.0 1/4 W (70V)
Mapping and Distribution
Direct SPL (A-Weighted), Broadband
Average: 76.3 dB ±12.2 dB
Average + Std. Dev.: 88.4 dB
Average - Std. Dev.: 64.1 dB
Max. Value: 92.5 dB
Wednesday, May 14, 2025 4/5
Min. Value: -123.1 dB
Data Points: 1436
Area Covered: Direct SPL(A) Average
95% ≥71.8 dB 77.2 dB
90% ≥72.3 dB 77.5 dB
85% ≥72.7 dB 77.8 dB
80% ≥73.1 dB 78.1 dB
Additional Mappings
CIS
Average: 0.74 ±0.01
Average + Std. Dev.: 0.76
Average - Std. Dev.: 0.73
Wednesday, May 14, 2025 5/5
Max. Value: 0.84
Min. Value: 0.73
Data Points: 1436
Area Covered: CIS Average
95% ≥0.73 0.74
90% ≥0.73 0.74
85% ≥0.73 0.74
80% ≥0.73 0.74
NIST DOUBLE
Alec Lauterbach
Wednesday, May 14, 2025 1/7
Project Information Title: NIST DOUBLE MODULE LAB
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary Quantity Type
Wednesday, May 14, 2025 2/7
Wednesday, May 14, 2025 3/7
Room: Room Nr. 1
Label: Room Nr. 1
Room Height: 10.00 ft
Dimensions (WxD): 23.83 ft x 21.70 ft
Volume: 5042.7 cb ft (net: 5042.7 cb ft)
Surface Area: 1945.7 sq ft (net: 1945.7 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.3 W
Sound Sources Summary
Wednesday, May 14, 2025 4/7
Surfaces Surface Part Area sq ft Material
Floor Main Area 504.27 Concrete, Painted, Wall or Floor
Ceiling Main Area 504.27 Concrete, Painted, Wall or Floor
Wall #1 Main Area 238.15 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 65.89 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 13.47 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 86.08 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 13.77 Steel, Wall, Floor, or Ceiling
Wall #6 Main Area 65.06 Steel, Wall, Floor, or Ceiling
Wall #7 Main Area 238.15 Steel, Wall, Floor, or Ceiling
Wall #8 Main Area 216.56 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 4.09 12.12 8.00 0.0 0.0 1/4 W (70V)
Wednesday, May 14, 2025 5/7
Mapping and Distribution
Direct SPL (A-Weighted), Broadband
Average: 69.7 dB ±27.7 dB
Average + Std. Dev.: 97.4 dB
Average - Std. Dev.: 42.1 dB
Max. Value: 86.9 dB
Min. Value: -178.3 dB
Wednesday, May 14, 2025 6/7
Data Points: 4020
Area Covered: Direct SPL(A) Average
95% ≥68.4 dB 73.7 dB
90% ≥69.1 dB 74.0 dB
85% ≥69.6 dB 74.2 dB
80% ≥70.0 dB 74.5 dB
Additional Mappings
CIS
Wednesday, May 14, 2025 7/7
Average: 0.70 ±0.01
Average + Std. Dev.: 0.72
Average - Std. Dev.: 0.69
Max. Value: 0.80
Min. Value: 0.69
Data Points: 4020
Area Covered: CIS Average
95% ≥0.69 0.70
90% ≥0.69 0.70
85% ≥0.69 0.70
80% ≥0.69 0.70
NIST DOUBLE
MODULE OFFICE
Alec Lauterbach
Project Information Title: NIST DOUBLE MODULE OFFICE
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: Double Module Office
Label: Double Module Office
Room Height: 10.00 ft
Dimensions (WxD): 15.99 ft x 21.74 ft
Volume: 3472.2 cb ft (net: 3472.2 cb ft)
Surface Area: 1448.6 sq ft (net: 1448.6 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.3 W
Sound Sources Summary
1 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 347.22 Concrete, Painted, Wall or Floor
Ceiling Main Area 347.22 Concrete, Painted, Wall or Floor
Wall #1 Main Area 159.86 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 217.22 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 159.70 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 217.41 Concrete, Painted, Wall or Floor
Sound Sources
1 Wall E70 19.89 12.78 8.00 -180.0 0.0 1/4 W (70V)
Mapping and Distribution
Direct SPL (A-Weighted), Broadband
Average: 71.0 dB ±28.6 dB
Average + Std. Dev.: 99.6 dB
Average - Std. Dev.: 42.4 dB
Max. Value: 86.8 dB
Min. Value: -124.3 dB
Data Points: 2767
Area Covered: Direct SPL(A) Average
95% ≥70.8 dB 75.4 dB
90% ≥71.5 dB 75.6 dB
85% ≥72.0 dB 75.9 dB
80% ≥72.3 dB 76.1 dB
Average: 0.71 ±0.01
Average + Std. Dev.: 0.72
Average - Std. Dev.: 0.70
Max. Value: 0.78
Min. Value: 0.70
Data Points: 2767
Area Covered: CIS Average
95% ≥0.70 0.71
90% ≥0.70 0.71
85% ≥0.71 0.71
80% ≥0.71 0.71
NIST TRIPLE
Alec Lauterbach
Project Information Title: NIST TRIPLE MODULE LAB
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: Room Nr. 1
Label: Room Nr. 1
Room Height: 10.00 ft
Dimensions (WxD): 23.80 ft x 32.63 ft
Volume: 7581.6 cb ft (net: 7581.6 cb ft)
Surface Area: 2671.7 sq ft (net: 2671.7 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
1 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 758.16 Concrete, Painted, Wall or Floor
Ceiling Main Area 758.16 Concrete, Painted, Wall or Floor
Wall #1 Main Area 223.70 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 41.35 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 13.78 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 133.69 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 13.67 Steel, Wall, Floor, or Ceiling
Wall #6 Main Area 85.79 Steel, Wall, Floor, or Ceiling
Wall #7 Main Area 13.71 Steel, Wall, Floor, or Ceiling
Wall #8 Main Area 65.62 Steel, Wall, Floor, or Ceiling
Wall #9 Main Area 237.74 Steel, Wall, Floor, or Ceiling
Wall #10 Main Area 326.29 Steel, Wall, Floor, or Ceiling
Sound Sources
1 Wall E70 5.89 17.76 5.65 -0.1 0.0 1/2 W (70V)
Mapping and Distribution
Average: 71.7 dB ±28.9 dB
Average + Std. Dev.: 100.6 dB
Average - Std. Dev.: 42.8 dB
Max. Value: 108.9 dB
Min. Value: -178.3 dB
Data Points: 5904
Area Covered: Direct SPL(A) Average
95% ≥70.7 dB 76.1 dB
90% ≥71.5 dB 76.3 dB
85% ≥71.9 dB 76.6 dB
80% ≥72.3 dB 76.9 dB
Average: 0.69 ±0.03
Average + Std. Dev.: 0.72
Average - Std. Dev.: 0.66
Max. Value: 0.92
Min. Value: 0.68
Data Points: 5904
Area Covered: CIS Average
95% ≥0.68 0.69
90% ≥0.68 0.69
85% ≥0.68 0.69
80% ≥0.68 0.69
NIST TRIPLE
MODULE OFFICE
Alec Lauterbach
Project Information Title: NIST TRIPLE MODULE OFFICE
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: Triple Module Office
Label: Triple Module Office
Room Height: 10.00 ft
Dimensions (WxD): 16.05 ft x 32.79 ft
Volume: 5243.5 cb ft (net: 5243.5 cb ft)
Surface Area: 2024.0 sq ft (net: 2024.0 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
1 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 524.35 Concrete, Painted, Wall or Floor
Ceiling Main Area 524.35 Concrete, Painted, Wall or Floor
Wall #1 Main Area 159.71 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 327.85 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 160.42 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 327.34 Concrete, Painted, Wall or Floor
Sound Sources
1 Wall E70 19.33 18.14 8.00 179.9 0.0 1/2 W (70V)
Mapping and Distribution
Average: 73.7 dB ±24.7 dB
Average + Std. Dev.: 98.4 dB
Average - Std. Dev.: 49.0 dB
Max. Value: 89.9 dB
Min. Value: -178.3 dB
Data Points: 4105
Area Covered: Direct SPL(A) Average
95% ≥71.8 dB 76.9 dB
90% ≥72.5 dB 77.2 dB
85% ≥73.1 dB 77.5 dB
80% ≥73.6 dB 77.7 dB
Average: 0.70 ±0.01
Average + Std. Dev.: 0.71
Average - Std. Dev.: 0.69
Max. Value: 0.79
Min. Value: 0.69
Data Points: 4105
Area Covered: CIS Average
95% ≥0.69 0.70
90% ≥0.69 0.70
NIST QUADRUPLE
Alec Lauterbach
Project Information Title: NIST QUADRUPLE MODULE LAB
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
2 E70 (Cooper Notification)
Room: Room Nr. 1
Label: Room Nr. 1
Room Height: 10.00 ft
Dimensions (WxD): 23.69 ft x 43.55 ft
Volume: 10062.4 cb ft (net: 10062.4 cb ft)
Surface Area: 3412.0 sq ft (net: 3412.0 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
2 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 1006.24 Concrete, Painted, Wall or Floor
Ceiling Main Area 1006.24 Concrete, Painted, Wall or Floor
Wall #1 Main Area 236.88 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 435.45 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 236.54 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 65.41 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 13.81 Steel, Wall, Floor, or Ceiling
Wall #6 Main Area 85.63 Steel, Wall, Floor, or Ceiling
Wall #7 Main Area 13.76 Steel, Wall, Floor, or Ceiling
Wall #8 Main Area 132.62 Steel, Wall, Floor, or Ceiling
Wall #9 Main Area 14.01 Steel, Wall, Floor, or Ceiling
Wall #10 Main Area 85.96 Steel, Wall, Floor, or Ceiling
Wall #11 Main Area 13.97 Steel, Wall, Floor, or Ceiling
Wall #12 Main Area 65.50 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 30.74 23.86 8.00 180.0 0.0 1/4 W (70V)
2 Wall E70 30.72 2.04 8.00 180.0 0.0 1/4 W (70V)
Mapping and Distribution
Average: 74.3 dB ±10.5 dB
Average + Std. Dev.: 84.8 dB
Average - Std. Dev.: 63.9 dB
Max. Value: 86.9 dB
Min. Value: -178.3 dB
Data Points: 7808
Area Covered: Direct SPL(A) Average
95% ≥70.4 dB 75.0 dB
90% ≥71.0 dB 75.2 dB
85% ≥71.4 dB 75.4 dB
80% ≥71.7 dB 75.7 dB
Average: 0.69 ±0.02
Average + Std. Dev.: 0.71
Average - Std. Dev.: 0.67
Max. Value: 0.79
Min. Value: 0.67
Data Points: 7808
Area Covered: CIS Average
95% ≥0.67 0.69
90% ≥0.67 0.69
85% ≥0.68 0.69
80% ≥0.68 0.69
NIST 5 MODULE
LAB
Alec Lauterbach
Project Information Title: NIST 5 MODULE LAB
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: Room Nr. 1
Label: Room Nr. 1
Room Height: 10.00 ft
Dimensions (WxD): 23.95 ft x 55.07 ft
Volume: 13064.7 cb ft (net: 13064.7 cb ft)
Surface Area: 4246.6 sq ft (net: 4246.6 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
2 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 1306.47 Concrete, Painted, Wall or Floor
Ceiling Main Area 1306.47 Concrete, Painted, Wall or Floor
Wall #1 Main Area 15.51 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 225.63 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 550.71 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 239.12 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 92.89 Steel, Wall, Floor, or Ceiling
Wall #6 Main Area 13.35 Steel, Wall, Floor, or Ceiling
Wall #7 Main Area 32.77 Steel, Wall, Floor, or Ceiling
Wall #8 Main Area 13.71 Steel, Wall, Floor, or Ceiling
Wall #9 Main Area 188.20 Steel, Wall, Floor, or Ceiling
Wall #10 Main Area 13.65 Steel, Wall, Floor, or Ceiling
Wall #11 Main Area 33.35 Steel, Wall, Floor, or Ceiling
Wall #12 Main Area 13.38 Steel, Wall, Floor, or Ceiling
Wall #13 Main Area 187.90 Steel, Wall, Floor, or Ceiling
Wall #14 Main Area 13.48 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 30.74 21.02 8.00 180.0 0.0 1/4 W (70V)
2 Wall E70 30.74 -7.04 8.00 180.0 0.0 1/4 W (70V)
Mapping and Distribution
Average: 73.7 dB ±5.5 dB
Average + Std. Dev.: 79.2 dB
Average - Std. Dev.: 68.2 dB
Max. Value: 86.9 dB
Min. Value: -178.3 dB
Data Points: 10078
Area Covered: Direct SPL(A) Average
95% ≥69.7 dB 74.0 dB
90% ≥70.3 dB 74.2 dB
85% ≥70.6 dB 74.4 dB
80% ≥71.0 dB 74.7 dB
Average: 0.68 ±0.02
Average + Std. Dev.: 0.70
Average - Std. Dev.: 0.66
Max. Value: 0.80
Min. Value: 0.66
Data Points: 10078
Area Covered: CIS Average
95% ≥0.67 0.68
90% ≥0.67 0.68
85% ≥0.67 0.69
80% ≥0.67 0.69
NIST PENTHOUSE
TRANSFORMER
VAULT
Alec Lauterbach
Project Information Title: NIST PENTHOUSE TRANSFORMER VAULT
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: PENTHOUSE TRANSFORMER VAULT
Label: PENTHOUSE TRANSFORMER VAULT
Room Height: 10.00 ft
Dimensions (WxD): 37.96 ft x 43.18 ft
Volume: 14192.6 cb ft (net: 14192.6 cb ft)
Surface Area: 4460.2 sq ft (net: 4460.2 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 1.0 W
2 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 1419.26 Concrete, Painted, Wall or Floor
Ceiling Main Area 1419.26 Concrete, Painted, Wall or Floor
Wall #1 Main Area 150.85 Concrete, Painted, Wall or Floor
Wall #2 Main Area 95.17 Concrete, Painted, Wall or Floor
Wall #3 Main Area 228.31 Concrete, Painted, Wall or Floor
Wall #4 Main Area 336.11 Concrete, Painted, Wall or Floor
Wall #5 Main Area 379.51 Concrete, Painted, Wall or Floor
Wall #6 Main Area 431.76 Concrete, Painted, Wall or Floor
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 2.00 31.43 8.00 -0.1 0.0 1/2 W (70V)
2 Wall E70 1.98 14.84 8.00 -0.1 0.0 1/2 W (70V)
Mapping and Distribution
Average: 73.9 dB ±20.2 dB
Average + Std. Dev.: 94.1 dB
Average - Std. Dev.: 53.7 dB
Max. Value: 89.9 dB
Min. Value: -122.4 dB
Data Points: 10917
Area Covered: Direct SPL(A) Average
95% ≥70.5 dB 76.2 dB
90% ≥71.0 dB 76.5 dB
85% ≥71.5 dB 76.8 dB
80% ≥72.0 dB 77.1 dB
Average: 0.67 ±0.02
Average + Std. Dev.: 0.69
Average - Std. Dev.: 0.65
Max. Value: 0.80
Min. Value: 0.65
Data Points: 10917
Area Covered: CIS Average
95% ≥0.65 0.67
90% ≥0.65 0.67
85% ≥0.66 0.67
80% ≥0.66 0.67
NIST STORAGE
ROOM TO LOADING
DOCK
Alec Lauterbach
Project Information Title: NIST STORAGE ROOM TO LOADING DOCK
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: Room Nr. 1
Label: Room Nr. 1
Room Height: 10.00 ft
Dimensions (WxD): 25.21 ft x 29.01 ft
Volume: 7280.5 cb ft (net: 7280.5 cb ft)
Surface Area: 2538.0 sq ft (net: 2538.0 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
1 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 728.05 Concrete, Painted, Wall or Floor
Ceiling Main Area 728.05 Concrete, Painted, Wall or Floor
Wall #1 Main Area 252.14 Concrete, Painted, Wall or Floor
Wall #2 Main Area 290.09 Concrete, Painted, Wall or Floor
Wall #3 Main Area 251.37 Concrete, Painted, Wall or Floor
Wall #4 Main Area 288.30 Concrete, Painted, Wall or Floor
Sound Sources
1 Wall E70 1.40 16.90 8.00 0.1 0.0 1/2 W (70V)
Mapping and Distribution
Average: 74.1 dB ±16.0 dB
Average + Std. Dev.: 90.1 dB
Average - Std. Dev.: 58.1 dB
Max. Value: 89.9 dB
Min. Value: -125.0 dB
Data Points: 5645
Area Covered: Direct SPL(A) Average
95% ≥70.7 dB 75.6 dB
90% ≥71.3 dB 75.9 dB
85% ≥71.7 dB 76.1 dB
80% ≥72.0 dB 76.4 dB
Average: 0.68 ±0.02
Average + Std. Dev.: 0.70
Average - Std. Dev.: 0.66
Max. Value: 0.80
Min. Value: 0.67
Data Points: 5645
Area Covered: CIS Average
95% ≥0.67 0.68
90% ≥0.67 0.68
85% ≥0.67 0.68
80% ≥0.67 0.68
NIST B220
BASEMENT
Alec Lauterbach
Wednesday, May 14, 2025 1/22
Project Information Title: NIST B220 BASEMENT
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
13 E70 (Cooper Notification)
Wednesday, May 14, 2025 2/22
Wednesday, May 14, 2025 3/22
Room: Basement Tunnel
Label: Basement Tunnel
Room Height: 10.00 ft
Dimensions (WxD): 9.04 ft x 129.64 ft
Volume: 11581.0 cb ft (net: 11581.0 cb ft)
Surface Area: 5087.4 sq ft (net: 5087.4 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 1.0 W
Wednesday, May 14, 2025 4/22
4 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 1158.10 Concrete, Painted, Wall or Floor
Ceiling Main Area 1158.10 Concrete, Painted, Wall or Floor
Wall #1 Main Area 88.27 Concrete, Painted, Wall or Floor
Wall #2 Main Area 1296.38 Concrete, Painted, Wall or Floor
Wall #3 Main Area 90.42 Concrete, Painted, Wall or Floor
Wall #4 Main Area 1296.15 Concrete, Painted, Wall or Floor
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 104.43 161.62 8.00 179.9 0.0 1/4 W (70V)
2 Wall E70 104.37 127.10 8.00 179.9 0.0 1/4 W (70V)
3 Wall E70 104.32 93.23 8.00 179.9 0.0 1/4 W (70V)
4 Wall E70 104.26 60.81 8.00 179.9 0.0 1/4 W (70V)
Wednesday, May 14, 2025 5/22
Mapping and Distribution
Average: 73.2 dB ±23.6 dB
Wednesday, May 14, 2025 6/22
Average + Std. Dev.: 96.8 dB
Average - Std. Dev.: 49.6 dB
Max. Value: 87.0 dB
Min. Value: -178.3 dB
Data Points: 9136
Area Covered: Direct SPL(A) Average
95% ≥70.5 dB 76.2 dB
90% ≥71.7 dB 76.5 dB
85% ≥72.7 dB 76.7 dB
80% ≥73.2 dB 77.0 dB
Wednesday, May 14, 2025 7/22
Average: 0.72 ±0.01
Average + Std. Dev.: 0.74
Average - Std. Dev.: 0.71
Max. Value: 0.79
Min. Value: 0.71
Data Points: 9136
Area Covered: CIS Average
95% ≥0.71 0.72
90% ≥0.71 0.72
85% ≥0.71 0.72
80% ≥0.71 0.72
Wednesday, May 14, 2025 8/22
Room: Basement C07
Label: Basement C07
Room Height: 15.00 ft
Dimensions (WxD): 42.23 ft x 55.94 ft
Volume: 25076.2 cb ft (net: 25076.2 cb ft)
Surface Area: 6947.0 sq ft (net: 6947.0 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.8 W
Wednesday, May 14, 2025 9/22
3 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 1671.74 Concrete, Painted, Wall or Floor
Ceiling Main Area 1671.74 Concrete, Painted, Wall or Floor
Wall #1 Main Area 301.34 Concrete, Painted, Wall or Floor
Wall #2 Main Area 838.36 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 300.30 Concrete, Painted, Wall or Floor
Wall #4 Main Area 104.65 Concrete, Painted, Wall or Floor
Wall #5 Main Area 331.59 Concrete, Painted, Wall or Floor
Wall #6 Main Area 429.95 Concrete, Painted, Wall or Floor
Wall #7 Main Area 255.32 Concrete, Painted, Wall or Floor
Wall #8 Main Area 218.56 Concrete, Painted, Wall or Floor
Wall #9 Main Area 61.01 Concrete, Painted, Wall or Floor
Wall #10 Main Area 111.18 Concrete, Painted, Wall or Floor
Wall #11 Main Area 15.85 Concrete, Painted, Wall or Floor
Wall #12 Main Area 635.37 Concrete, Painted, Wall or Floor
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 21.10 -16.58 8.00 179.9 0.0 1/4 W (70V)
2 Wall E70 21.07 -38.11 8.00 179.9 0.0 1/4 W (70V)
3 Wall E70 -21.04 -34.75 8.00 0.1 0.0 1/4 W (70V)
Wednesday, May 14, 2025 10/22
Mapping and Distribution
Average: 71.1 dB ±24.9 dB
Wednesday, May 14, 2025 11/22
Average + Std. Dev.: 96.0 dB
Average - Std. Dev.: 46.2 dB
Max. Value: 87.0 dB
Min. Value: -178.3 dB
Data Points: 12926
Area Covered: Direct SPL(A) Average
95% ≥69.5 dB 74.5 dB
90% ≥70.3 dB 74.7 dB
85% ≥71.1 dB 74.9 dB
80% ≥71.6 dB 75.2 dB
Wednesday, May 14, 2025 12/22
Average: 0.66 ±0.02
Average + Std. Dev.: 0.68
Average - Std. Dev.: 0.63
Max. Value: 0.79
Min. Value: 0.63
Data Points: 12926
Area Covered: CIS Average
95% ≥0.64 0.66
90% ≥0.64 0.66
85% ≥0.64 0.66
80% ≥0.64 0.66
Wednesday, May 14, 2025 13/22
Room: Basement B48
Label: Basement B48
Room Height: 10.00 ft
Dimensions (WxD): 17.57 ft x 44.15 ft
Volume: 7724.4 cb ft (net: 7724.4 cb ft)
Surface Area: 2777.3 sq ft (net: 2777.3 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
Wednesday, May 14, 2025 14/22
2 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 772.44 Concrete, Painted, Wall or Floor
Ceiling Main Area 772.44 Concrete, Painted, Wall or Floor
Wall #1 Main Area 440.76 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 174.52 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 441.49 Concrete, Painted, Wall or Floor
Wall #4 Main Area 175.69 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 -0.03 -9.86 8.00 179.9 0.0 1/4 W (70V)
2 Wall E70 -0.07 -28.17 8.00 179.9 0.0 1/4 W (70V)
Wednesday, May 14, 2025 15/22
Mapping and Distribution
Average: 71.8 dB ±27.6 dB
Wednesday, May 14, 2025 16/22
Average + Std. Dev.: 99.4 dB
Average - Std. Dev.: 44.2 dB
Max. Value: 87.0 dB
Min. Value: -126.6 dB
Data Points: 5978
Area Covered: Direct SPL(A) Average
95% ≥70.7 dB 75.9 dB
90% ≥71.8 dB 76.2 dB
85% ≥72.4 dB 76.4 dB
80% ≥72.9 dB 76.7 dB
Wednesday, May 14, 2025 17/22
Average: 0.69 ±0.02
Average + Std. Dev.: 0.71
Average - Std. Dev.: 0.68
Max. Value: 0.78
Min. Value: 0.68
Data Points: 5978
Area Covered: CIS Average
95% ≥0.68 0.70
90% ≥0.68 0.70
85% ≥0.68 0.70
80% ≥0.68 0.70
Wednesday, May 14, 2025 18/22
Room: Basement B59
Label: Basement B59
Room Height: 10.00 ft
Dimensions (WxD): 48.53 ft x 66.17 ft
Volume: 26585.8 cb ft (net: 26585.8 cb ft)
Surface Area: 7605.7 sq ft (net: 7605.7 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 1.3 W
Wednesday, May 14, 2025 19/22
4 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 2658.58 Concrete, Painted, Wall or Floor
Ceiling Main Area 2658.58 Concrete, Painted, Wall or Floor
Wall #1 Main Area 241.72 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 221.04 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 243.59 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 438.64 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 482.60 Steel, Wall, Floor, or Ceiling
Wall #6 Main Area 76.76 Steel, Wall, Floor, or Ceiling
Wall #7 Main Area 396.40 Steel, Wall, Floor, or Ceiling
Wall #8 Main Area 44.13 Steel, Wall, Floor, or Ceiling
Wall #9 Main Area 143.65 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 0.14 -22.08 8.00 -0.1 0.0 1/2 W (70V)
2 Wall E70 0.09 -55.16 8.00 -0.1 0.0 1/4 W (70V)
3 Wall E70 48.47 -33.19 8.00 179.8 0.0 1/4 W (70V)
4 Wall E70 48.38 -55.16 8.00 179.8 0.0 1/4 W (70V)
Wednesday, May 14, 2025 20/22
Mapping and Distribution
Average: 75.3 dB ±3.3 dB
Wednesday, May 14, 2025 21/22
Average + Std. Dev.: 78.6 dB
Average - Std. Dev.: 72.0 dB
Max. Value: 89.8 dB
Min. Value: 57.8 dB
Data Points: 5189
Area Covered: Direct SPL(A) Average
95% ≥70.9 dB 75.7 dB
90% ≥72.4 dB 75.9 dB
85% ≥73.0 dB 76.1 dB
80% ≥73.6 dB 76.3 dB
Wednesday, May 14, 2025 22/22
Average: 0.66 ±0.02
Average + Std. Dev.: 0.68
Average - Std. Dev.: 0.64
Max. Value: 0.81
Min. Value: 0.64
Data Points: 5189
Area Covered: CIS Average
95% ≥0.65 0.66
90% ≥0.65 0.67
85% ≥0.65 0.67
80% ≥0.65 0.67
NIST B220 SUB-
Alec Lauterbach
Project Information Title: NIST B220 SUB-BASEMENT
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: Sub-Basement
Label: Sub-Basement
Room Height: 10.00 ft
Dimensions (WxD): 30.91 ft x 35.30 ft
Volume: 6199.7 cb ft (net: 6199.7 cb ft)
Surface Area: 2561.5 sq ft (net: 2561.5 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
2 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 619.97 Concrete, Painted, Wall or Floor
Ceiling Main Area 619.97 Concrete, Painted, Wall or Floor
Wall #1 Main Area 103.27 Concrete, Painted, Wall or Floor
Wall #2 Main Area 7.26 Concrete, Painted, Wall or Floor
Wall #3 Main Area 7.31 Concrete, Painted, Wall or Floor
Wall #4 Main Area 89.84 Concrete, Painted, Wall or Floor
Wall #5 Main Area 90.10 Concrete, Painted, Wall or Floor
Wall #6 Main Area 24.36 Concrete, Painted, Wall or Floor
Wall #7 Main Area 114.17 Concrete, Painted, Wall or Floor
Wall #8 Main Area 116.68 Concrete, Painted, Wall or Floor
Wall #9 Main Area 36.63 Concrete, Painted, Wall or Floor
Wall #10 Main Area 70.63 Concrete, Painted, Wall or Floor
Wall #11 Main Area 141.17 Concrete, Painted, Wall or Floor
Wall #12 Main Area 72.13 Concrete, Painted, Wall or Floor
Wall #13 Main Area 211.59 Concrete, Painted, Wall or Floor
Wall #14 Main Area 236.45 Concrete, Painted, Wall or Floor
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 144.33 53.27 8.00 0.0 0.0 1/4 W (70V)
2 Wall E70 140.50 63.97 8.00 89.8 0.0 1/4 W (70V)
Mapping and Distribution
Average: 73.8 dB ±17.3 dB
Average + Std. Dev.: 91.1 dB
Average - Std. Dev.: 56.5 dB
Max. Value: 86.9 dB
Min. Value: -178.3 dB
Data Points: 4928
Area Covered: Direct SPL(A) Average
95% ≥69.1 dB 75.5 dB
90% ≥70.2 dB 75.8 dB
85% ≥71.2 dB 76.1 dB
80% ≥72.1 dB 76.4 dB
Average: 0.71 ±0.01
Average + Std. Dev.: 0.72
Average - Std. Dev.: 0.69
Max. Value: 0.77
Min. Value: 0.70
Data Points: 4928
Area Covered: CIS Average
95% ≥0.70 0.71
90% ≥0.70 0.71
85% ≥0.70 0.71
80% ≥0.70 0.71
NIST B220 THIRD
FLOOR UNIQUE
ROOMS
Alec Lauterbach
Wednesday, May 14, 2025 1/11
Project Information Title: NIST B220 THIRD FLOOR UNIQUE ROOMS
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary Quantity Type
5 E70 (Cooper Notification)
Wednesday, May 14, 2025 2/11
Room: Sub-Basement
Label: Sub-Basement
Room Height: 10.00 ft
Dimensions (WxD): 30.91 ft x 35.30 ft
Volume: 6199.7 cb ft (net: 6199.7 cb ft)
Surface Area: 2561.5 sq ft (net: 2561.5 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
Wednesday, May 14, 2025 3/11
2 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 619.97 Steel, Wall, Floor, or Ceiling
Ceiling Main Area 619.97 Steel, Wall, Floor, or Ceiling
Wall #1 Main Area 103.27 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 7.26 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 7.31 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 89.84 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 90.10 Steel, Wall, Floor, or Ceiling
Wall #6 Main Area 24.36 Steel, Wall, Floor, or Ceiling
Wall #7 Main Area 114.17 Steel, Wall, Floor, or Ceiling
Wall #8 Main Area 116.68 Steel, Wall, Floor, or Ceiling
Wall #9 Main Area 36.63 Steel, Wall, Floor, or Ceiling
Wall #10 Main Area 70.63 Steel, Wall, Floor, or Ceiling
Wall #11 Main Area 141.17 Steel, Wall, Floor, or Ceiling
Wall #12 Main Area 72.13 Steel, Wall, Floor, or Ceiling
Wall #13 Main Area 211.59 Steel, Wall, Floor, or Ceiling
Wall #14 Main Area 236.45 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 144.33 53.27 8.00 0.0 0.0 1/4 W (70V)
2 Wall E70 140.50 63.97 8.00 89.8 0.0 1/4 W (70V)
Wednesday, May 14, 2025 4/11
Mapping and Distribution
Average: 73.8 dB ±17.3 dB
Wednesday, May 14, 2025 5/11
Average + Std. Dev.: 91.1 dB
Average - Std. Dev.: 56.5 dB
Max. Value: 86.9 dB
Min. Value: -178.3 dB
Data Points: 4928
Area Covered: Direct SPL(A) Average
95% ≥69.1 dB 75.5 dB
90% ≥70.2 dB 75.8 dB
85% ≥71.2 dB 76.1 dB
80% ≥72.1 dB 76.4 dB
Wednesday, May 14, 2025 6/11
Average: 0.71 ±0.01
Average + Std. Dev.: 0.72
Average - Std. Dev.: 0.69
Max. Value: 0.77
Min. Value: 0.70
Data Points: 4928
Area Covered: CIS Average
95% ≥0.70 0.71
90% ≥0.70 0.71
85% ≥0.70 0.71
80% ≥0.70 0.71
Wednesday, May 14, 2025 7/11
Room: Third Level Room B341
Label: Third Level Room B341
Room Height: 10.00 ft
Dimensions (WxD): 23.63 ft x 65.35 ft
Volume: 14960.8 cb ft (net: 14960.8 cb ft)
Surface Area: 4845.3 sq ft (net: 4845.3 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.8 W
Wednesday, May 14, 2025 8/11
3 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 1496.08 Concrete, Painted, Wall or Floor
Ceiling Main Area 1496.08 Concrete, Painted, Wall or Floor
Wall #1 Main Area 653.47 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 235.47 Concrete, Painted, Wall or Floor
Wall #3 Main Area 54.92 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 14.20 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 104.48 Steel, Wall, Floor, or Ceiling
Wall #6 Main Area 12.83 Steel, Wall, Floor, or Ceiling
Wall #7 Main Area 113.26 Steel, Wall, Floor, or Ceiling
Wall #8 Main Area 13.54 Steel, Wall, Floor, or Ceiling
Wall #9 Main Area 104.98 Steel, Wall, Floor, or Ceiling
Wall #10 Main Area 12.27 Steel, Wall, Floor, or Ceiling
Wall #11 Main Area 113.24 Steel, Wall, Floor, or Ceiling
Wall #12 Main Area 12.41 Steel, Wall, Floor, or Ceiling
Wall #13 Main Area 104.65 Steel, Wall, Floor, or Ceiling
Wall #14 Main Area 12.78 Steel, Wall, Floor, or Ceiling
Wall #15 Main Area 55.39 Steel, Wall, Floor, or Ceiling
Wall #16 Main Area 235.25 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 48.41 46.58 8.00 0.0 0.0 1/4 W (70V)
2 Wall E70 48.41 66.77 8.00 0.0 0.0 1/4 W (70V)
3 Wall E70 48.40 88.56 8.00 0.0 0.0 1/4 W (70V)
Wednesday, May 14, 2025 9/11
Mapping and Distribution
Average: 74.0 dB ±15.9 dB
Wednesday, May 14, 2025 10/11
Average + Std. Dev.: 90.0 dB
Average - Std. Dev.: 58.1 dB
Max. Value: 87.1 dB
Min. Value: -178.3 dB
Data Points: 11615
Area Covered: Direct SPL(A) Average
95% ≥71.0 dB 75.5 dB
90% ≥71.7 dB 75.7 dB
85% ≥72.1 dB 75.9 dB
80% ≥72.4 dB 76.1 dB
Wednesday, May 14, 2025 11/11
Average: 0.68 ±0.02
Average + Std. Dev.: 0.70
Average - Std. Dev.: 0.67
Max. Value: 0.79
Min. Value: 0.66
Data Points: 11615
Area Covered: CIS Average
95% ≥0.67 0.68
90% ≥0.67 0.69
NIST B221 Basement Unique Rooms
Alec Lauterbach
Wednesday, May 14, 2025 1/11
Project Information Title: NIST B221 Basement Unique Rooms
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
4 E70 (Cooper Notification)
Wednesday, May 14, 2025 2/11
Wednesday, May 14, 2025 3/11
Room: Basement Room C08
Label: Basement Room C08
Room Height: 10.00 ft
Dimensions (WxD): 26.75 ft x 74.66 ft
Volume: 15607.1 cb ft (net: 15607.1 cb ft)
Surface Area: 5206.3 sq ft (net: 5206.3 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 1.5 W
Wednesday, May 14, 2025 4/11
3 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 1560.71 Concrete, Painted, Wall or Floor
Ceiling Main Area 1560.71 Concrete, Painted, Wall or Floor
Wall #1 Main Area 266.99 Concrete, Painted, Wall or Floor
Wall #2 Main Area 706.90 Concrete, Painted, Wall or Floor
Wall #3 Main Area 95.98 Concrete, Painted, Wall or Floor
Wall #4 Main Area 39.13 Concrete, Painted, Wall or Floor
Wall #5 Main Area 121.37 Concrete, Painted, Wall or Floor
Wall #6 Main Area 62.03 Concrete, Painted, Wall or Floor
Wall #7 Main Area 28.77 Concrete, Painted, Wall or Floor
Wall #8 Main Area 461.63 Concrete, Painted, Wall or Floor
Wall #9 Main Area 79.42 Concrete, Painted, Wall or Floor
Wall #10 Main Area 222.69 Concrete, Painted, Wall or Floor
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 28.07 81.41 8.00 0.0 0.0 1/2 W (70V)
2 Wall E70 28.08 111.73 8.00 0.0 0.0 1/2 W (70V)
3 Wall E70 36.08 140.12 8.00 -90.0 0.0 1/2 W (70V)
Wednesday, May 14, 2025 5/11
Mapping and Distribution
Average: 76.9 dB ±15.5 dB
Wednesday, May 14, 2025 6/11
Average + Std. Dev.: 92.3 dB
Average - Std. Dev.: 61.4 dB
Max. Value: 90.0 dB
Min. Value: -178.3 dB
Data Points: 12090
Area Covered: Direct SPL(A) Average
95% ≥72.8 dB 78.1 dB
90% ≥74.2 dB 78.4 dB
85% ≥74.9 dB 78.6 dB
80% ≥75.3 dB 78.8 dB
Wednesday, May 14, 2025 7/11
Average: 0.68 ±0.02
Average + Std. Dev.: 0.70
Average - Std. Dev.: 0.66
Max. Value: 0.79
Min. Value: 0.66
Data Points: 12090
Area Covered: CIS Average
95% ≥0.66 0.68
90% ≥0.67 0.68
Wednesday, May 14, 2025 8/11
Room: Basement C09
Label: Basement C09
Room Height: 10.00 ft
Dimensions (WxD): 36.65 ft x 24.63 ft
Volume: 8101.2 cb ft (net: 8101.2 cb ft)
Surface Area: 2843.5 sq ft (net: 2843.5 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.5 W
Sound Sources Summary Quantity Type
1 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 810.12 Concrete, Painted, Wall or Floor
Ceiling Main Area 810.12 Concrete, Painted, Wall or Floor
Wall #1 Main Area 366.18 Concrete, Painted, Wall or Floor
Wall #2 Main Area 246.08 Concrete, Painted, Wall or Floor
Wednesday, May 14, 2025 9/11
Wall #3 Main Area 272.96 Concrete, Painted, Wall or Floor
Wall #4 Main Area 96.86 Concrete, Painted, Wall or Floor
Wall #5 Main Area 92.81 Concrete, Painted, Wall or Floor
Wall #6 Main Area 148.38 Concrete, Painted, Wall or Floor
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 20.04 -0.06 8.00 -90.0 0.0 1/2 W (70V)
Mapping and Distribution
Direct SPL (A-Weighted), Broadband
Average: 72.0 dB ±24.5 dB
Average + Std. Dev.: 96.5 dB
Wednesday, May 14, 2025 10/11
Average - Std. Dev.: 47.4 dB
Max. Value: 90.0 dB
Min. Value: -126.5 dB
Data Points: 6342
Area Covered: Direct SPL(A) Average
95% ≥70.6 dB 75.2 dB
90% ≥71.2 dB 75.5 dB
85% ≥71.6 dB 75.7 dB
80% ≥71.9 dB 76.0 dB
Additional Mappings
Average: 0.68 ±0.02
Wednesday, May 14, 2025 11/11
Average + Std. Dev.: 0.70
Average - Std. Dev.: 0.67
Max. Value: 0.81
Min. Value: 0.67
Data Points: 6342
Area Covered: CIS Average
95% ≥0.67 0.68
90% ≥0.67 0.68
80% ≥0.67 0.68
NIST B221 FIRST
ROOMS
Alec Lauterbach
Project Information Title: NIST B221 FIRST FLOOR UNIQUE ROOMS
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
3 E70 (Cooper Notification)
Room: Level 1 Room B110
Label: Level 1 Room B110
Room Height: 10.00 ft
Dimensions (WxD): 35.36 ft x 54.41 ft
Volume: 16472.0 cb ft (net: 16472.0 cb ft)
Surface Area: 5087.6 sq ft (net: 5087.6 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.8 W
3 E70 (Cooper Notification)
Surfaces Surface Part Area sq ft Material
Floor Main Area 1647.20 Concrete, Painted, Wall or Floor
Ceiling Main Area 1647.20 Concrete, Painted, Wall or Floor
Wall #1 Main Area 162.23 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 167.22 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 191.48 Concrete, Painted, Wall or Floor
Wall #4 Main Area 543.22 Concrete, Painted, Wall or Floor
Wall #5 Main Area 352.36 Concrete, Painted, Wall or Floor
Wall #6 Main Area 376.69 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 194.77 176.18 8.00 179.9 0.0 1/4 W (70V)
2 Wall E70 194.71 153.61 8.00 179.9 0.0 1/4 W (70V)
3 Wall E70 159.47 153.69 8.00 0.0 0.0 1/4 W (70V)
Mapping and Distribution
Average: 75.2 dB ±3.1 dB
Average + Std. Dev.: 78.3 dB
Average - Std. Dev.: 72.1 dB
Max. Value: 87.0 dB
Min. Value: 63.7 dB
Data Points: 12648
Area Covered: Direct SPL(A) Average
95% ≥70.7 dB 75.5 dB
90% ≥71.7 dB 75.7 dB
85% ≥72.3 dB 75.9 dB
80% ≥72.7 dB 76.1 dB
Average: 0.67 ±0.02
Average + Std. Dev.: 0.69
Average - Std. Dev.: 0.66
Max. Value: 0.78
Min. Value: 0.65
Data Points: 12648
Area Covered: CIS Average
95% ≥0.66 0.68
90% ≥0.66 0.68
85% ≥0.66 0.68
80% ≥0.66 0.68
NIST B221 Sub- Basement
Alec Lauterbach
Project Information Title: NIST B221 Sub-Basement
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: SUB BASEMENT
Label: SUB BASEMENT
Room Height: 10.00 ft
Dimensions (WxD): 23.27 ft x 20.98 ft
Volume: 4870.7 cb ft (net: 4870.7 cb ft)
Surface Area: 1858.1 sq ft (net: 1858.1 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 0.3 W
Sound Sources Summary
Surfaces Surface Part Area sq ft Material
Floor Main Area 487.07 Concrete, Painted, Wall or Floor
Ceiling Main Area 487.07 Concrete, Painted, Wall or Floor
Wall #1 Main Area 232.73 Concrete, Painted, Wall or Floor
Wall #2 Main Area 209.32 Concrete, Painted, Wall or Floor
Wall #3 Main Area 232.17 Concrete, Painted, Wall or Floor
Wall #4 Main Area 209.76 Concrete, Painted, Wall or Floor
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 145.27 41.96 8.00 -0.1 0.0 1/4 W (70V)
Mapping and Distribution
Average: 71.4 dB ±21.3 dB
Average + Std. Dev.: 92.7 dB
Average - Std. Dev.: 50.2 dB
Max. Value: 86.8 dB
Min. Value: -124.0 dB
Data Points: 3758
Area Covered: Direct SPL(A) Average
95% ≥68.9 dB 74.0 dB
90% ≥69.4 dB 74.2 dB
85% ≥69.8 dB 74.5 dB
80% ≥70.2 dB 74.8 dB
Additional Mappings
CIS
Average: 0.70 ±0.01
Average + Std. Dev.: 0.71
Average - Std. Dev.: 0.68
Max. Value: 0.79
Min. Value: 0.68
Data Points: 3758
Area Covered: CIS Average
95% ≥0.69 0.70
90% ≥0.69 0.70
NIST FA B223 FIRST
ROOMS
Alec Lauterbach
Project Information Title: NIST FA B223 FIRST FLOOR UNIQUE ROOMS
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software Version: EASE Evac, Version 2.0.40
Sound Sources Summary
Room: Level 1 Room A158
Label: Level 1 Room A158
Room Height: 10.00 ft
Dimensions (WxD): 36.08 ft x 32.93 ft
Volume: 11159.7 cb ft (net: 11159.7 cb ft)
Surface Area: 4266.1 sq ft (net: 4266.1 sq ft)
Ear Height: 5.58 ft
Network Voltage: 70.7 V
Power Consumption: 1.0 W
Sound Sources Summary
Surfaces Surface Part Area sq ft Material
Floor Main Area 1115.97 Concrete, Painted, Wall or Floor
Ceiling Main Area 1115.97 Concrete, Painted, Wall or Floor
Wall #1 Main Area 110.56 Steel, Wall, Floor, or Ceiling
Wall #2 Main Area 38.38 Steel, Wall, Floor, or Ceiling
Wall #3 Main Area 108.70 Steel, Wall, Floor, or Ceiling
Wall #4 Main Area 104.78 Steel, Wall, Floor, or Ceiling
Wall #5 Main Area 15.14 Concrete, Painted, Wall or Floor
Wall #6 Main Area 30.79 Concrete, Painted, Wall or Floor
Wall #7 Main Area 14.92 Concrete, Painted, Wall or Floor
Wall #8 Main Area 149.85 Steel, Wall, Floor, or Ceiling
Wall #9 Main Area 3.00 Steel, Wall, Floor, or Ceiling
Wall #10 Main Area 149.54 Steel, Wall, Floor, or Ceiling
Wall #11 Main Area 14.93 Concrete, Painted, Wall or Floor
Wall #12 Main Area 31.39 Concrete, Painted, Wall or Floor
Wall #13 Main Area 14.31 Concrete, Painted, Wall or Floor
Wall #14 Main Area 103.24 Steel, Wall, Floor, or Ceiling
Wall #15 Main Area 107.44 Steel, Wall, Floor, or Ceiling
Wall #16 Main Area 358.94 Steel, Wall, Floor, or Ceiling
Wall #17 Main Area 328.17 Steel, Wall, Floor, or Ceiling
Wall #18 Main Area 225.86 Steel, Wall, Floor, or Ceiling
Wall #19 Main Area 14.54 Concrete, Painted, Wall or Floor
Wall #20 Main Area 30.13 Concrete, Painted, Wall or Floor
Wall #21 Main Area 14.47 Concrete, Painted, Wall or Floor
Wall #22 Main Area 65.06 Steel, Wall, Floor, or Ceiling
Sound Sources Nr. Mounting Type X [ft] Y [ft] Z [ft] Hor [°] Ver [°] Tap Settings
1 Wall E70 114.30 106.74 8.00 -0.1 0.0 1/2 W (70V)
2 Wall E70 114.33 123.74 8.00 -0.1 0.0 1/2 W (70V)
Mapping and Distribution
Direct SPL (A-Weighted), Broadband
Average: 71.4 dB ±29.8 dB
Average + Std. Dev.: 101.2 dB
Average - Std. Dev.: 41.7 dB
Max. Value: 89.9 dB
Min. Value: -178.3 dB
Data Points: 8703
Area Covered: Direct SPL(A) Average
95% ≥68.6 dB 75.3 dB
90% ≥69.1 dB 75.7 dB
85% ≥69.6 dB 76.1 dB
80% ≥70.1 dB 76.5 dB
Average: 0.70 ±0.02
Average + Std. Dev.: 0.72
Average - Std. Dev.: 0.68
Max. Value: 0.81
Min. Value: 0.69
Data Points: 8703
Area Covered: CIS Average
95% ≥0.69 0.70
90% ≥0.69 0.70
NIST FA B223 SUB-
Alec Lauterbach
Project Information Title: NIST FA B223 SUB-BASEMENT
Author: Alec Lauterbach
Company: Stanton Engineering
Temperature: 68.0°F
Pressure: Standard (29.8 inHg)
Humidity: Standard (60%)
Input Signal Spectrum: Program (IEC 60268-1)
Input Signal Crest Factor: Sine
Calculation Accuracy: Fast Approximation
STI Standard: IEC 60268-16 (2020)
Software…
This is the start of the file's text. The full file is on GovTribe.