Atch 5_drawings_2 of 2.pdf
PDF 9 MB Posted
- Attached to
- Construct Warehouse Addition, Buzzards Bay, MA Federal contract opportunity
- Solicitation number
- 12639525R0018
About this file
The file is a set of detailed electrical, architectural, and systems design drawings for a warehouse addition project at the USDA Forest Pest Management Laboratory in Buzzards Bay, Massachusetts. The drawings comprehensively document the electrical, lighting, power, equipment, and special systems plans for a 1,600-square-foot warehouse storage addition, including floor plans, elevations, demolition plans, and technical details. Key design elements include a pre-engineered metal building with metal wall and roof panels, a 14-foot eave height, new electrical infrastructure, LED lighting fixtures, fire alarm systems, and access control components.
The electrical designs specify a new 112.5 KVA transformer, a 400-amp main circuit breaker panel, underground feeder lines, new receptacles, lighting circuits, and grounding systems. The drawings show provisions for existing equipment like overhead doors and refrigeration units, and new installations including salamander heaters, cord reels, and exterior lighting. The design integrates with the existing warehouse storage building, maintaining consistent architectural and electrical standards. The project includes detailed specifications for electrical safety, grounding, receptacle configurations, and special systems like fire alarms and access control, with careful attention to mounting heights, circuit loads, and compliance with electrical codes.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 12639525R0018-0001.pdf | ||
| RFI 5.docx | DOCX document | |
| RFI 4.docx | DOCX document | |
| 09_90_00 Paints and Coatings.pdf | ||
| RFI 3.docx | DOCX document | |
| WH1.jpg | JPG image | |
| WH2.jpg | JPG image | |
| Contractor Sign In 13AUG25.pdf | ||
| PPQ S and T FPML Geotechnical Report.pdf | ||
| Geotechnical Engineering Report_Proposed Building Addition_USDA ARS.pdf | ||
| 09 90 00 Paints and Coatings.pdf | ||
| RFI 2.docx | DOCX document | |
| RFI and response.docx | DOCX document | |
| Atch 3_specifications.pdf | ||
| Atch 4_drawings_1 of 2.pdf | ||
| Atch 1_SOW Warehouse Addition .doc | DOC document | |
| 12639525R0018.pdf | ||
| Atch 2_Federal Construction Wage Rates_Barnstable County.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AD101
1 EAST ELEVATION
SCALE: 1/4"= 1'-0"
AD101
2 SOUTH ELEVATION
SCALE: 1/4"= 1'-0"
REMOVE EXISTING METAL
DOWNSPOUT FOR INSTALLATION
OF EXPANSION JOINT COVER
EXISTING TRANSLUCENT
WALL PANELS
EXISTING METAL
WALL PANELS
EXISTING METAL OUTSIDE
CORNER TRIM TO REMAIN
EXISTING METAL
WALL PANELS
EXISTING CONCRETE
STEM WALL
EXISTING METAL
WALL PANELS
EXISTING METAL
WALL PANELS
REMOVE EXISTING LIGHT
SEE ELECTRICALEXISTING TRANSLUCENT
WALL PANELS EXISTING METAL OUTSIDE
CORNER TRIM TO REMAIN
'-0
" E
AV
E
HE
IG
HT
(E
XI
ST
IN
G)
'-0
" E
AV
E
HE
IG
HT
(E
XI
ST
IN
G)
EXISTING CONCRETE
STEM WALL
EXISTING METAL OUTSIDE
CORNER TRIM TO REMAIN
EXISTING OVERHEAD
DOOR TO REMAIN
EXISTING OVERHEAD
DOOR TO REMAIN
REMOVE EXISTING RAKE
TRIM--PROVIDE WEATHER
PROTECTION
PPM
REVISIONS
DESCRIPTION
SHEET
DATE
c P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA / APHIS
250 MARQUETTE AVENUE
MINNEAPOLIS, MN 55401
SUITE 410
BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
BUZZARDS BAY, MASSACHUSETTS
DEMOLITION ELEVATIONS
AD101
17 313/10/2025
RPP
RPP
FEJ
XXX
2424-A
T. MITCHELL
M. RADLOFF
T. SNIDOW
T. OTTEN
10-1-2 2 3 4 5
10-1-2 2
A-101
1 WAREHOUSE FLOOR PLAN
SCALE: 3/16"= 1'-0"
EXISTING WAREHOUSE STORAGE
FINISH FLOOR ELEVATION 100.00
EXISTING EXTERIOR
WALL
'-0
M
AT
CH
E
XI
ST
IN
G
WAREHOUSE STORAGE ADDITION
FINISH FLOOR ELEVATION 98.0
NORTH
MANUALLY OPERATED
RIDGE VENT AT ROOF
CONCRETE LANDING & STEP
CURBED CONCRETE
VEHICULAR RAMP
SLOPE 10% MAXIMUM
PPM
REVISIONS
DESCRIPTION
SHEET
DATE
c P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA / APHIS
250 MARQUETTE AVENUE
MINNEAPOLIS, MN 55401
SUITE 410
BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
BUZZARDS BAY, MASSACHUSETTS
FLOOR PLAN & ROOF PLAN
A-101 18 313/10/2025
RPP
T. MITCHELL
M. RADLOFF
T. SNIDOW
T. OTTEN
4'-9"
3'- 0"
DN
. 4
R
IS
ER
S
1 12" Ø STEEL
PIPE HANDRAIL
A-101
2 PARTIAL WAREHOUSE FLOOR PLAN
SCALE: 3/16"= 1'-0"
NORTH
MANUALLY OPERATED
RIDGE VENT AT ROOF
6" METAL GUTTER WITH
GUTTER BRACKETS 24" O.C.
4"x 5" METAL
DOWNSPOUT
METAL RAKE TRIM
DIE FORMED
RIDGE CAP
6" METAL GUTTER WITH
GUTTER BRACKETS 24" O.C.
4"x 5" METAL
DOWNSPOUT
EXISTING METAL PANEL
WAREHOUSE ROOF
END WALL FLASHING
EXTEND UP EXISTING
WAREHOUSE WALL AND
PROVIDE RAKE TRIM AT
EXISTING WAREHOUSE
PROVIDE REPLACEMENT
4"x 5" METAL DOWNSPOUT
AT EXISTING GUTTER
1" E.J.
ST
EE
L L
IN
E
STEEL LINE
STEEL LINE
4'- 7"
8'-
GENERAL NOTES
1. CONFIRM OVERALL EXISTING BUILDING DIMENSIONS AND
FRAME LOCATIONS. SECONDARY PRE-ENGINEERED METAL
BUILDING SYSTEM IS BASED ON BYPASS ZEE GIRTS. VERIFY
DIMENSIONS IN FIELD. "STEEL LINE" REFERS TO OUTSIDE FACE
OF GIRT.
2. PROVIDE 10# CLASS A DRY CHEMICAL TYPE SURFACE MOUNTED
FIRE EXTINGUISHER WITH BRACKETS CONFORMING TO NFPA10,
UL 299
3 I N
3 I
N
A-301
A-301
A-301
A-301
A-101
3 DOOR SCHEDULE
SCALE: 3/8"= 1'-0"
1 2 3
7'- 0"
2"
2"3'-0"2"
'-0
10'-0"
1-3/4" THICK HOLLOW CORE
METAL DOOR AND FRAME
POWER ACTUATED NON-INSULATED
OVERHEAD DOOR AND CHANNEL FRAME
SCALE: 3/8"=1'-0"
0 1' 2' 4' 8'
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
" 11
CONCRETE FILLED
STEEL PIPE BOLLARD
CONCRETE FILLED
STEEL PIPE BOLLARDS
FLEXIBLE DOWNSPOUT
CONNECT AT PVC PIPE
FLEXIBLE DOWNSPOUT
CONNECT AT PVC PIPE
EXPOSED 5"Ø PVC
DRAIN FROM D.S.
5"Ø PVC DRAIN
LINE UNDER
RAMP & LANDING
5"Ø PVC DRAIN
LINE UNDER LANDING
5'W x 4'D METAL
DOOR CANOPY
BY PEMB MFR.
1 IN 12
2'-9"
5'-1"16'-11"16'-11"1'-0" 1'-0"
FIRE EXTINGUISHER
ON WALL BRACKET.
SEE GENERAL NOTE 2.
FIRE EXTINGUISHER
ON WALL BRACKET.
SEE GENERAL NOTE 2.
10.90.50
1 0.9 0.5 0
A-201
1 EAST ELEVATION
SCALE: 3/16"= 1'-0"
METAL ROOF PANEL--
MATCH EXISTING
5' HIGH TRANSLUCENT
WALL PANELS
METAL WALL PANELS
40' LONG ADDITION EXISTING 80' LONG STORAGE BUILDING
A-201
2 SOUTH ELEVATION
SCALE: 3/16"= 1'-0"
TRANSLUCENT
WALL PANELS
METAL WALL PANELS
10'x10' OVER-
HEAD DOOR
METAL GUTTER
' E
AV
E
HE
IG
HT
METAL DOWNSPOUT
END WALL OF EXISTING
METAL STORAGE BUILDING
BEYOND
END WALL FLASHING (SEE 3/A-301)
CONCRETE STEM WALL
CONCRETE STEM WALL
BOTTOM OF EXISTING CONCRETE FOOTING
MANUALLY OPERATED
RIDGE VENT
MANUALLY OPERATED
RIDGE VENT
PROVIDE 3 'x 7'
PERSONNEL DOOR
METAL WALL PANELS
CONCRETE CURBED
VEHICULAR RAMP
CONCRETE LANDING
AND STEP
PPM
REVISIONS
DESCRIPTION
SHEET
DATE
c P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA / APHIS
250 MARQUETTE AVENUE
MINNEAPOLIS, MN 55401
SUITE 410
BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
BUZZARDS BAY, MASSACHUSETTS
EXTERIOR ELEVATIONS
A-201 19 313/10/2025
RPP
T. MITCHELL
M. RADLOFF
T. SNIDOW
T. OTTEN
TIE DOWNSPOUT IN TO
DRAIN PIPE BELOW
STOOP---SEE CIVIL DWGS.
4'- 0"
5'- 0"
5'- 0"3'
3'
3'
4'- 0"
5'- 0"
PROVIDE METAL DOWN-
SPOUT AT EXISTING
LOCATION
METAL CORNER TRIM
A-201
3 WEST ELEVATION
SCALE: 3/16"= 1'-0"
4'- 0"
5'- 0"
5'- 0"
METAL GUTTER
METAL DOWNSPOUT
MANUALLY OPERATED
RIDGE VENT
3'
TRANSLUCENT
WALL PANELS
METAL WALL PANELS
CONCRETE
SPLASHBLOCK
EXISTING 80' LONG STORAGE BUILDING 40' LONG ADDITION
0 4' 8' 16'
SCALE: 3/16"= 1'-0"
2'
F.F.E. 100.00 (EXISTING BUILDING)
F.F.E. 98.00
(ADDITION)
F.F.E. 98.00
(ADDITION)
F.F.E. 98.00
(ADDITION)
5'W x 4'D METAL
DOOR CANOPY
BY PEMB MFR.
5'W x 4'D METAL
DOOR CANOPY
BY PEMB MFR.
8'
STEEL PIPE
BOLLARD
FASTEN FENCING END TENSION
BAR TO FACE OF BUILDING
10.90.50
A B C
EXISTING WAREHOUSE STORAGE
WAREHOUSE STORAGE ADDITION
A-301
1 PARTIAL BUILDING SECTION
SCALE: 1/4"= 1'-0"
EXISTING METAL
PANEL ROOF
"CONCRETE STEM
WALL
PPM
REVISIONS
DESCRIPTION
SHEET
DATE
c P.A.
FIRM
U
NO.
DEPM
SAFETY & HEALTH
REAL PROPERTY
A
DATE
PROJECT NO.
SUSDA
BY
OF
THE
DESIGNER
PROJECT MANAGER
JOB #
CHECKED BY
A-E FIRM
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
Johnson M Adams
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
USDA / APHIS
250 MARQUETTE AVENUE
MINNEAPOLIS, MN 55401
SUITE 410
BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
BUZZARDS BAY, MASSACHUSETTS
SECTIONS & DETAILS
A-301 20 313/10/2025
RPP
T. MITCHELL
M. RADLOFF
T. SNIDOW
T. OTTEN
4'- 0"
4'- 8"
2'- 8"
2'- 4"
VA
RI
ES
TRAPEZOIDAL METAL
ROOF PANEL--MATCH
EXISTING PROFILE
10' LONG MANUALLY
OPERATED RIDGE VENT
8" BY-PASS ZEE
GIRT--TYPICAL
BASE ANGLE
CONCRETE STEM
WALL
4'- 0"
4'- 8"
2'- 8"
'-0
" E
AV
E
HE
IG
HT
EXISTING WALL
PANELS TO
REMAIN
8" BY-PASS ZEE
GIRT--TYPICAL
BASE ANGLE
TRANSLUCENT
WALL PANEL
METAL WALL
PANEL
MIN. 4" PANEL
LAP
METAL GUTTER
TRANSLUCENT
WALL PANEL
METAL WALL
PANEL
MIN. 6" PANEL
LAP--TYPICAL
METAL RAKE TRIM
METAL WALL
PANEL
A-301
2 BUILDING CROSS SECTION
SCALE: 1/4"= 1'-0"
6" THICK SEALED
CONCRETE SLAB
ON GRADE
WAREHOUSE STORAGE ADDITION
6" THICK SEALED
CONCRETE SLAB
ON GRADE
PRE-ENGINEERED METAL
BUILDING PRIMARY FRAME
8" METAL ZEE
PURLINS
8'0 2' 4' 12'
SCALE: 1/4"= 1'-0"
EXISTING TRAPEZOIDAL
METAL ROOF PANEL
PROVIDE METAL RAKE TRIM
AT EXISTING ENDWALL
AFTER INSTALLATION OF
ENDWALL FLASHING
EXISTING ENDWALL
PANEL TO REMAIN
ENDWALL FLASHING
EXTEND TO RAKE
TRIM ABOVE
CONTINUOUS FLASHING
SUPPORT
2'- 0"
RIGID FRAME
PURLIN
A-301
3 FLASHING DETAIL
SCALE: 1-1/2"= 1'-0"
A-301
SCALE: 1 1/2"=1'-0"
0 6" 1' 2'
PROVIDE FOAM WALL
PANEL CLOSURE AT
EXISTING PANEL
TRAPEZOIDAL METAL
ROOF PANEL--MATCH
EXISTING PROFILE
EAVE STRUT
112" Ø STEEL
PIPE HANDRAIL
(PAINTED) AT
STEPS BEYOND
A-301
4 BASE PANEL FLASHING DETAIL
SCALE: 6"= 1'-0"
PRE-ENGINEERED BUILDING
BASE ANGLE PANEL SUPPORT
REINFORCED CONCRETE
STEM WALL--SEE STRUCTURAL
METAL WALL
PANEL
BASE PANEL
FLASHING
BACKER ROD
AND SEALANT
2"
1"
A-301
SCALE: 6"=1'-0"
1 1/2" 3" 6"
U
D A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
ELECTRICAL LEGEND
E-001
ELECTRICAL GENERAL NOTES:
1. THE WORK MUST CONFORM WITH ALL REQUIREMENTS OF:
· NFPA 70, NATIONAL ELECTRICAL CODE (NEC) (2023)
· NFPA 101, LIFE SAFETY CODE (2024)
· NFPA 780, STANDARDS FOR INSTALLATION OF LIGHTNING PROTECTION SYSTEMS (2023)
· IEEE C2, NATIONAL ELECTRICAL SAFETY CODE (NESC) (2023)
· UFC 1-200-01, DOD BUILDING CODE (GENERAL BUILDING REQUIREMENTS),
· UFC 1-200-02, HIGH PERFORMANCE AND SUSTAINABLE BUILDING REQUIREMENTS
· UFC 3-501-01, ELECTRICAL ENGINEERING
· UFC 3-520-01 INTERIOR ELECTRICAL SYSTEMS
· UFC 3-530-01, INTERIOR AND EXTERIOR LIGHTING AND CONTROLS
· UFC 3-550-01, EXTERIOR ELECTRICAL POWER DISTRIBUTION
· UFC 3-560-01, OPERATION AND MAINTENANCE: ELECTRICAL SAFETY
· UFC 3-575-01, LIGHTNING AND STATIC ELECTRICITY PROTECTION SYSTEMS
· UFC 3-580-01, TELECOMMUNICATIONS BUILDING CABLING SYSTEMS PLANNING AND DESIGN
· UFC 4-010-01, DOD ANTITERRORISM STANDARDS FOR BUILDINGS
· UFC 4-011-06, CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
· ASHRAE 90.1, ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS (2013)
*CRITERIA AND STANDARDS LISTED ALSO INCLUDE SPECIFIED STANDARDS AND RELATED SECTIONS AS PART OF THE DESIGN.
2. MINIMUM RACEWAY SIZE MUST BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL FOR FEEDERS
AND 20% FOR BRANCH CIRCUITS IAW CNIFR REQUIREMENTS.
3. THE ELECTRICAL CONTRACTOR MUST CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND MUST BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND CORRECT ROUGH-IN
LOCATIONS OF ELECTRICAL CONNECTIONS.
4. VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL SWITCHES. SWITCHES IN THE SAME LOCATION MUST BE GANGED
TOGETHER IN ONE COMMON BACKBOX AND MUST HAVE ONE COMMON FACE PLATE.
5. ALL FEEDERS AND BRANCH CIRCUITS MUST INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
6. VERIFY LUMINAIRE, CEILING MOUNTED OCCUPANCY SENSOR LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE ROUGHING-IN.
7. EXISTING ELECTRICAL WORK (NOT SHOWN) MUST REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER MUST BE RESTORED TO WORKING CONDITION. THE RESTORATION MUST INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED MUST BE INCLUDED IN THE CONTRACT AND NO EXTRA COMPENSATION
WILL BE GRANTED.
8. NEW WORK MUST BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK MUST BE CHECKED AGAINST EXISTING
WORK
9. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
10. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
11. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.
12. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.
13. CONTRACTOR MUST FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY MATERIALS AND
DEVELOPMENT OF ANY SHOP DRAWINGS OR SUBMITTALS.
14. PROVIDE LABELS ON ALL RECEPTACLES, WALL MOUNTED LIGHT SWITCHES/OCCUPANCY SENSORS AND JUNCTION BOXES INDICATING THE SOURCE PANEL & CIRCUIT(S). TEXT MUST BE BLACK, 1/4" IN HEIGHT PRINTED ON A CLEAR LABEL. HANDWRITTEN LABELS ARE NOT PERMITTED EXCEPT FOR JUNCTION BOXES LOCATED ABOVE FINISHED CEILING WHICH CAN BE HANDWRITTEN WITH AN INDELIBLE MARKER.
15. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT MUST BE FLUSH WITH FRONT SIDE OF EQUIPMENT AND EXTEND AT LEAST 2" BEYOND
THE FOOTPRINT OF THE EQUIPMENT ON ALL OTHER SIDES.
ELECTRICAL ABBREVIATIONS:
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
BMGB
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CMS
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
ECB
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
HWRP
HWSP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
BUILDING MASTER GROUNDING BUSBAR
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS MANHOLE
COMBINATION MOTOR STARTER
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
ENCLOSED CIRCUIT BREAKER
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT SYSTEM HEAT PUMP, USE CU FOR STANDARD
DX OUTDOOR UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY SYSTEM
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM
HWUH
HZ
IAW
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LM
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NL
NO
NTS
P
PA
PBB
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RBB
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SBB
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TEBC
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
WPIU
XFMR
Z
HOT WATER UNIT HEATER
HERTZ
IN ACCORDANCE WITH
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LOCKHEED MARTIN
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
PRIMARY BONDING BUSBAR
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH PARALLEL OR SERIES FAN (PRIMARY INDUCTION UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RACK BONDING BUSBAR
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SECONDARY BONDING BUSBAR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
WEATHERPROOF IN USE
TRANSFORMER
IMPEDANCE
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
OF
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
USDA / APHIS
AutoCAD SHX Text
250 MARQUETTE AVENUE
AutoCAD SHX Text
MINNEAPOLIS, MN 55401
AutoCAD SHX Text
SUITE 410
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
THE
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
BUZZARDS BAY, MASSACHUSETTS
AutoCAD SHX Text 21 31
AutoCAD SHX Text 3/10/2025
AutoCAD SHX Text
RPP
AutoCAD SHX Text
RPP
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
XXX
AutoCAD SHX Text 2424-A
AutoCAD SHX Text
T. MITCHELL
AutoCAD SHX Text
M.RADLOFF
AutoCAD SHX Text
T. SNIDOW
AutoCAD SHX Text
T. OTTEN
Emilie Oakes
DLME31025
A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
ELECTRICAL LEGEND
E-002
LA-1
LA-1
ELECTRICAL LEGEND
1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED.
2. DEVICES NOTED AS "GFI" MUST BE GROUND FAULT CIRCUIT
INTERRUPTING DEVICES.
3. DEVICES NOTED AS "WP" MUST BE GFI AND WEATHERPROOF.
4.
DEVICES NOTED AS "DL" MUST BE RATED FOR DAMP LOCATION.5.
DEVICES NOTED AS "NL" MUST BE NIGHT LIGHTS. PROVIDE
UNSWITCHED POWER TO FIXTURE.
6.
DEVICES NOTED AS "WG" MUST BE PROVIDED AND INSTALLED WITH
A WIRE GUARD.
7.
DEVICES NOTED AS "TR" MUST BE TAMPER RESISTANT.8.
PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY
PACKS.
SINGLE-POLE, SINGLE-THROW SWITCH. MOUNT CENTERLINE
OF BOX AT 45"A.F.F. UNLESS NOTED OTHERWISE.
RELAY PACK MOUNTED ABOVE CEILING. ACUITY CONTROLS
#nPP16-D OR APPROVED EQUAL.
SITE POLE TOP LIGHT
FIXTURE.
PP
PLUG LOAD RELAY PACK MOUNTED ABOVE CEILING TO SWITCH
RECEPTACLES. EQUAL TO ACUITY CONTROLS nPP20-PL OR APPROVED
EQUAL.
PE
PASSIVE INFRARED AND ULTRASONIC DUAL TECHNOLOGY
OCCUPANCY SENSOR WITH A 25' RADIAL COVERAGE. CEILING
MOUNTED.
os
DF
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18" A.F.F. TO
CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, ONE COVER
PLATE, MOUNTED 18" A.F.F. TO CENTERLINE OF BOX UNLESS
NOTED OTHERWISE.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, ONE COVER
PLATE, MOUNTED WITH BOTTOM OF BOX 2" ABOVE COUNTER
BACKSPLASH. WHERE THERE IS NO BACKSPLASH MOUNT 6"
ABOVE COUNTER. WHERE RECEPTACLE IS SHOWN IN AN AREA
WITH NO COUNTER, MOUNT 45"A.F.F. TO CENTERLINE OF BOX.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED WITH BOTTOM
OF BOX 2" ABOVE COUNTER BACKSPLASH. WHERE THERE IS
NO BACKSPLASH MOUNT 6" ABOVE COUNTER. WHERE
RECEPTACLE IS SHOWN IN AN AREA WITH NO COUNTER,
MOUNT 45"A.F.F. TO CENTERLINE OF BOX.
DUPLEX RECEPTACLE, NEMA 5-20R, FOR DRINKING FOUNTAIN
FED FROM GFCI BREAKER. MOUNTED IN ACCORDANCE WITH
MANUFACTURER'S ROUGH-IN REQUIREMENTS. VERIFY
CONNECTION TYPE PRIOR TO BID. RECEPTACLE MUST BE
MOUNTED, CONCEALED BEHIND THE SHROUD OF THE DRINKING
FOUNTAIN.
FLOOR BOX. PROVIDE WITH NEMA 5-20R DUPLEX RECEPTACLE
AND DATA OUTLET AS SHOWN ON COMMUNICATIONS PLANS.
DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED IN A
FLOOR BOX.
CONTACTOR.
PHOTOCELL.
CEILING MOUNTED JUNCTION BOX.
WALL MOUNTED JUNCTION
BOX.
FLEXIBLE CONNECTION TO
EQUIPMENT.
2'X2' RECESSED
FIXTURE.
2'X4' RECESSED
FIXTURE.
SURFACE MOUNTED/SUSPENDED LINEAR
FIXTURE.
2'X2' RECESSED EMERGENCY
FIXTURE.
2'X4' RECESSED EMERGENCY
FIXTURE.
RECESSED CEILING
FIXTURE.
CEILING MOUNTED EXIT SIGN. PROVIDE CHEVRONS AS
INDICATED BY ARROWS.
WALL MOUNTED EXIT SIGN. PROVIDE CHEVRONS AS
INDICATED BY ARROWS.
WALL MOUNTED
FIXTURE.
RECESSED EMERGENCY CEILING
FIXTURE.
SINGLE RECEPTACLE, NEMA 6-50R. PROVIDE 6' CORD AND
MATCHING PLUG WHERE REQUIRED. MOUNTING DETERMINED
BY NEC FOR TYPE OF EQUIPMENT BEING CONNECTED.
HALF CONTROLLED DUPLEX RECEPTACLE, NEMA5-20R. MOUNTED
18"A.F.F. TO CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
LEVITON 16252 SERIES OR APPROVED EQUAL.
SINGLE RECEPTACLE, NEMA 6-30R, MOUNTED 18" A.F.F. TO
CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
SINGLE RECEPTACLE, NEMA 14-30R, MOUNTED 36" A.F.F. TO
CENTERLINE OF BOX UNLESS NOTED OTHERWISE. PROVIDE
6' CORD AND MATCHING PLUG WHERE REQUIRED.
CONDUIT AND WIRING RECEPTACLESSWITCHES
NOTE: THE NUMBER BESIDE THE SYMBOL IS THE CIRCUIT NUMBER. THE LETTER
BESIDE THE SYMBOL IS THE FIXTURE TYPE DESCRIBED IN THE LIGHT FIXTURE
SCHEDULE.
LUMINAIRES (SEE LIGHT FIXTURE SCHEDULE)
LEGEND GENERAL NOTES
MISCELLANEOUS
CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR
CEILING. TIC MARKS INDICATE NUMBER OF
CONDUCTORS. THE EQUIPMENT GROUNDING CONDUCTOR
IS NOT SHOWN, BUT MUST BE PROVIDED. SIZE THE
EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT
PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES
THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE
MARKINGS TO THE LEFT SIGNIFY THAT THREE
CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED.
CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR
FLOOR. TIC MARKS INDICATE NUMBER OF CONDUCTORS.
THE EQUIPMENT GROUNDING CONDUCTOR IS NOT
SHOWN, BUT MUST BE PROVIDED. SIZE THE EQUIPMENT
GROUNDING CONDUCTOR AND THE CONDUIT PER THE
NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO
CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS TO
THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN
EQUIPMENT GROUNDING CONDUCTOR SHOULD BE
PROVIDED.
THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF
THE CONDUCTORS THAT MUST BE RUN IN THE CONDUIT.
THE ABSENCE OF TEXT SIGNIFIES THAT THE
CONDUCTORS SHOULD BE #12 AWG.
CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES
EXPOSED SURFACE-MOUNTED RACEWAY (SEE
SPECIFICATIONS).
HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH
CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS
LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT
NUMBERS AT THE HOMERUN ARROWS.
PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL
PARTIAL HOMERUNS THAT ARE ON THE SAME CIRCUIT IN
A JUNCTION BOX PRIOR TO ENTERING THE PANELBOARD.
LOW VOLTAGE CONDUCTORS USED FOR MOTION DETECTOR
CIRCUITRY. SEE MANUFACTURER'S RECOMMENDATIONS
FOR CONDUCTOR REQUIREMENTS.
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED FLUSH IN THE
CEILING UNLESS NOTED OTHERWISE.
C
PL
PASSIVE INFRARED AND ULTRASONIC DUAL TECHNOLOGY
WALL SWITCH WITH INTEGRAL 0-10V DIMMER. MOUNT CENTERLINE OF BOX
AT 45"A.F.F. UNLESS NOTED OTHERWISE.
D
J
J
SURFACE MOUNTED/SUSPENDED EMERGENCY FIXTURE.
SINGLE RECEPTACLE, NEMA L6-30R, MOUNTED IN A FLOOR BOX.
LED HIGH BAY LIGHT
DEVICES NOTED AS "WPIU" MUST BE GFI AND WEATHERPROOF IN USE.
9.
50A WELDING RECEPTACLE, NON-NEMA FEMALE PIN-SLEEVE,
MOUNTED 48" A.F.F. UNLESS NOTED OTHERWISE. PROVIDE WITH DUST
COVER FLAP TO COVER THE RECEPTACLE WHEN NOT IN USE.
RECEPTACLE IS TO BE OF TYPE WHERE GROUND MAKES BEFORE
CONDUCTORS AND BREAKS AFTER CONDUCTORS. REFER TO D1/EP103.
SINGLE RECEPTACLE, NEMA 8-50R, WALL MOUNTED 48" A.F.F.
UNLESS NOTED OTHERWISE. LABEL "400HZ 120/208V". REFER TO
D2/EP103.
LED EMERGENCY
LIGHTING UNIT
LONG TIC MARK IDENTIFIES CONDUCTOR. SHORT TICK MARK
IDENTIFIES NEUTRAL. HOOKED TIC MARK IDENTIFIES GROUND.
SINGLE RECEPTACLE, NEMA 15-50R. PROVIDE 6' CORD AND
MATCHING PLUG WHERE REQUIRED. MOUNTING DETERMINED
BY NEC FOR TYPE OF EQUIPMENT BEING CONNECTED.
RECEPTACLE, NEMA L5-20R, MOUNTED AT CEILING, DEDICATED
CIRCUIT.
FURNITURE WHIP SINGLE POLE. PROVIDE POWER TO BASE OF FURNITURE
SYSTEM.
J F
FURNITURE WHIP DOUBLE POLE. PROVIDE POWER TO BASE OF
FURNITURE SYSTEM.
J G
FURNITURE WHIP THREE POLE. PROVIDE POWER TO BASE OF FURNITURE
SYSTEM.
J H
OVERHEAD COLUMN POWER SINGLE POLE. PROVIDE POWER TO BASE OF
FURNITURE SYSTEM.
J C1
OVERHEAD COLUMN POWER SINGLE POLE. PROVIDE POWER TO BASE OF
FURNITURE SYSTEM.
J C2
PASSIVE INFRARED AND ULTRASONIC DUAL TECHNOLOGY
WALL SWITCH. MOUNT CENTERLINE OF BOX AT 45"A.F.F. UNLESS NOTED
OTHERWISE.
O
SINGLE-POLE, THREE-WAY SWITCH. MOUNT CENTERLINE
OF BOX AT 45"A.F.F. UNLESS NOTED OTHERWISE.
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
OF
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
USDA / APHIS
AutoCAD SHX Text
250 MARQUETTE AVENUE
AutoCAD SHX Text
MINNEAPOLIS, MN 55401
AutoCAD SHX Text
SUITE 410
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
THE
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
BUZZARDS BAY, MASSACHUSETTS
AutoCAD SHX Text 22 31
AutoCAD SHX Text 3/10/2025
AutoCAD SHX Text
RPP
AutoCAD SHX Text
RPP
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
XXX
AutoCAD SHX Text 2424-A
AutoCAD SHX Text
T. MITCHELL
AutoCAD SHX Text
M. RADLOFF
AutoCAD SHX Text
T. SNIDOW
AutoCAD SHX Text
T. OTTEN
W-EX
WP-EX
L1-2
L1-5
L1-EX SD-1-EX
PANEL
L1-EX
200A
MCB
208Y/120V 3P 4W
PANEL
SD-1-EX
200A
208Y/120V 3P 4W
XFMR UT-1-EX
75 KVA
208Y/120V
TO 208Y/120V
200J
DEMOLITION KEYED NOTES1
GRAPHIC SCALE
GENERAL NOTES
U
D A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
ELECTRICAL DEMOLITION
ED101
EXISTING WAREHOUSE STORAGE
1. UNLESS CALLED OUT BY KEYED NOTE, ALL EXISTING
ELECTRICAL EQUIPMENT, FIXTURES, AND
INFRASTRUCTURE IS EXISTING TO REMAIN.
2. THIS DEMOLITION DRAWING AND SCOPE APPLIES FOR
BOTH SCHEMES.
3. REPAIR OPENINGS IN SURFACES TO REMAIN RESULTING
FROM DEMOLITION. MATCH EXISTING SURFACE.
1. DEMOLISH EXISTING LIGHT FIXTURE. DEMO CONDUIT,
CIRCUITRY BACK TO NEAREST EXISTING JUNCTION BOX.
CONTRACTOR SHALL MAKE-UP WIRING AS REQUIRED TO
MAINTAIN FUNCTIONAL CIRCUIT FOR EXISTING TO REMAIN
ELECTRICAL DEVICES IN EXISTING CIRCUIT.
2. REMOVE EXISTING DISCONNECT. REMOVE ALL CONDUIT
AND WIRE BACK TO ELECTRIC POWER POLE.
3. REMOVE EXISTING PANEL. MAINTAIN CONDUIT AND WIRE
OF BRANCH CIRCUITS FOR RE-USE. REMOVE FEEDER
CONDUIT AND WIRE SUPPLYING THE PANEL.
4. EXISTING TRANSFORMER IS UTILITY OWNED.
5. FEEDER IS FROM AN EXISTING OVERHEAD TO
UNDERGROUND RISER. CUT AND TRENCH THE ASPHALT.
REMOVE THE CONDUIT AND WIRE.
6. REMOVE ELECTRICAL EQUIPMENT.
7. REMOVE EXISTING FEEDER.
8. DEMOLISH EXISTING EXTERIOR RECEPTACLE. DEMO
CONDUIT, CIRCUITRY BACK TO NEAREST EXISTING
JUNCTION BOX. CONTRACTOR SHALL MAKE-UP WIRING AS
REQUIRED TO MAINTAIN FUNCTIONAL CIRCUIT FOR
EXISTING TO REMAIN ELECTRICAL DEVICES IN EXISTING
CIRCUIT.
ED101
1 ELECTRICAL DEMOLITION
SCALE: 3/16"= 1'-0"
NORTH
3 2
ED101
2 EXISTING POWER RISER
RISER NOTE:
EQUIPMENT SHOWN IS EXISTING.
NOT TO SCALE
AutoCAD SHX Text 1'-0'
AutoCAD SHX Text
AutoCAD SHX Text 6'
AutoCAD SHX Text 6'
AutoCAD SHX Text 3'
AutoCAD SHX Text
SCALE: 3/16"=
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
OF
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
USDA / APHIS
AutoCAD SHX Text
250 MARQUETTE AVENUE
AutoCAD SHX Text
MINNEAPOLIS, MN 55401
AutoCAD SHX Text
SUITE 410
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
THE
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
BUZZARDS BAY, MASSACHUSETTS
AutoCAD SHX Text 23 31
AutoCAD SHX Text 3/10/2025
AutoCAD SHX Text
RPP
AutoCAD SHX Text
RPP
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
XXX
AutoCAD SHX Text 2424-A
AutoCAD SHX Text
T. MITCHELL
AutoCAD SHX Text
M. RADLOFF
AutoCAD SHX Text
T. SNIDOW
AutoCAD SHX Text
T. OTTEN
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
XXXXXXX
X
X X
X X
X X
X X
X X
X X
X X
X X
XXX
X X
XXXXXXXXXXX
GAS
GAS
GAS
GAS
GAS
GAS
GAS
GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS
GAS
GAS
GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS GAS
T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T
OP
OP OP OP OP OP OP OP OP OP OP OP
T
KEYED NOTES
GRAPHIC SCALE
GENERAL NOTES
U
D A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
ELECTRICAL SITE PLAN
ES101
EXISTING WAREHOUSE STORAGE
1. UNLESS CALLED OUT BY KEYED NOTE, ALL EXISTING
ELECTRICAL EQUIPMENT, FIXTURES, AND
INFRASTRUCTURE IS EXISTING TO REMAIN.
2. THIS DEMOLITION DRAWING AND SCOPE APPLIES FOR
BOTH SCHEMES.
3. REPAIR OPENINGS IN SURFACES TO REMAIN RESULTING
FROM DEMOLITION.
1. UPGRADE POWER TO OVERHEAD POWER POLE.
ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
PROVIDING AND INSTALLING RISER AND CABLING. UTILITY
TO MAKE CONNECTIONS WITH TRANSFORMER.
COORDINATE WITH UTILITY PRIOR TO WORK.
2. SAW CUT AND REMOVE PAVEMENT, AND REMOVE
EXISTING BURIED ELECTRICAL PATHWAY IN ASPHALT.
INSTALL NEW CONDUIT AND WIRE. SEE 2/E-101 FOR SIZING
AND CONFIGURATION. PROVIDE SPARE CONDUIT. SEE
2/E-501 AND CIVIL FOR DETAILS.
3. REPLACE EXISTING DISCONNECT WITH NEW DISCONNECT.
SEE 2/E-101 FOR SIZING.
4. REPLACE EXISTING ELECTRICAL PANEL. INTERCEPT AND
EXTEND EXISTING CIRCUITRY TO NEW ELECTRICAL PANEL.
SEE 2/E-101 AND PANEL SCHEDULE FOR SIZE AND
CONFIGURATION. INSTALL GROUNDING SYSTEM PER
DETAIL 3/E-501 AND 4/E-501.
ES101
1 ELECTRICAL SITE
SCALE: 3/32"= 1'-0"
NORTH
WAREHOUSE STORAGE ADDITION
UT-1
AutoCAD SHX Text 1'-0'
AutoCAD SHX Text
AutoCAD SHX Text 10'
AutoCAD SHX Text 10'
AutoCAD SHX Text 5'
AutoCAD SHX Text
SCALE: 3/32"=
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
OF
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
USDA / APHIS
AutoCAD SHX Text
250 MARQUETTE AVENUE
AutoCAD SHX Text
MINNEAPOLIS, MN 55401
AutoCAD SHX Text
SUITE 410
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
THE
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
BUZZARDS BAY, MASSACHUSETTS
AutoCAD SHX Text 24 31
AutoCAD SHX Text 3/10/2025
AutoCAD SHX Text
RPP
AutoCAD SHX Text
RPP
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
XXX
AutoCAD SHX Text 2424-A
AutoCAD SHX Text
T. MITCHELL
AutoCAD SHX Text
M. RADLOFF
AutoCAD SHX Text
T. SNIDOW
AutoCAD SHX Text
T. OTTEN
L1
REF-1
7.5HP,208V3P4W
L1-7,9,11 1"C,3#6,#6N,#10G
REF-2
7.5HP,208V3P4W
L1-13,15,17 1"C,3#6,#6N,#10G
EX
EX
EX
WP-EX
WP-EX
WP-EX
L1-2
L1-2
L1-2
L1-4
L1-4
L1-4
L1-25
WP
L1-27 48"
48"
L1-23
L1-21
L1-19
L1-14
L1-16
SD-1
36" 36"36"36"
L1-28 L1-26
NOTE
NEUTRAL
BUS AMPS
VOLTS AIC
MAIN BKR
LUGSFED FROM
MOUNTING
ROOM
CBCIRCUIT DESCRIPTION
LOAD KVA
CKT
CIRCUIT DESCRIPTION
CKT
BKR#
CKTCKT
BKR A CB
LOAD KVA
A
STANDARD
10,000
208Y/120V 3P 4W
"EX" IS EXISTING. "(NEW ADDITION)" IS NEW CIRCUITS. ALL BREAKERS ARE NEW.
FLUSH
L1
SD-1 100%
20/1 0.48 20/1 0.7221 20/120/1 43 0.540.6 20/120/1 65 1.180.12
50/3 3.05 20/1 1.1887 20/1 | 109 1.183.05 20/1 | 1211 0.773.05
50/3 3.05 20/1 0.51413 20/1 | 1615 0.53.05 20/1 | 1817 03.05
20/1 1.5 50/3 52019
|20/1 2221 51.5
|20/1 2423 51.08 20/1 0.9 20/1 0.722625
20/120/1 2827 0.720.9 20/150/3 3029 05
| 5 20/1 03231 20/1 | 3433 05 20/120/1 3635 00
20/1 0 20/1 03837 20/120/1 4039 00 20/120/1 4241 00
TOTAL CONNECTED KVA BY PHASE 22.1 22 19.2
CONN KVA CONN KVA CALC KVACALC KVA
LIGHTING 1.97 2.46 (125%)
LARGEST MOTOR 1.18 0.294 (25%)
MOTORS 3.53 3.53 (100%)
RECEPTACLES 9.58 9.58 (50%>10)
NONCONTINUOUS 18.3 18.3 (100%)
HEATING 30 30 (100%)
TOTAL LOAD 64.2
BALANCED 3-PHASE LOAD 178 A
EX LIGHTING
EX LIGHTING
EX- EXTERIOR LIGHTING
EX REF-1
EX REF-2
LANDSCAPE CHARGER (NEW
ADDITION)
LANDSCAPE CHARGER (NEW
ADDITION)
RECEPTACLE (NEW ADDITION)
RECEPTACLE (NEW ADDITION)
RECEPTACLE (NEW ADDITION)
SAL-1 (NEW ADDITION)
SPACE
SPACE
SPACE
SPACE
EX RECEPTACLE
EX RECEPTACLE
EX OHD-1
EX OHD-2
OHD-3 (NEW ADDITION)
LIGHTING (NEW ADDITION)
CORD REEL (NEW ADDITION)
CORD REEL (NEW ADDITION)
SPACE
SAL-2 (NEW ADDITION)
RECEPTACLE
RECEPTACLE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
PANEL L1
400A
MCB
208Y/120V 3P 4W
PANEL
SD-1
400A
208Y/120V 3P 4W
XFMR UT-1
112.5 KVA
208Y/120V
TO 208Y/120V
400J
200J
400J
FEEDER SCHEDULE
ID FEEDER AMPS CONDUIT AND FEEDER
200 2"C,3#3/0,#3/0N,#6G
200 2"C,3#3/0,#3/0N,#4G
400 3-1/2"C,3#600kcmil,#600kcmil N,#2G
400 3-1/2"C,3#600kcmil,#600kcmil N,#1/0G
SIZING METHOD: COPPER, 60°C #12 THROUGH #1, 75°C 1/0 AND ABOVE
FAULT CURRENT SCHEDULE
DEVICE FAULT AIC RATING L-L VOLTS FEEDER
SIZE LENGTH
TRANSFORMER
KVA Z% FAULT AT
PRIMARY
MOTOR FAULT
UT-1 15,663 22,000 208V 112.5 2 UTILITY 39
SD-1 7,685 10,000 208V #600kcmil 182' 39
L1 7,099 10,000 208V #600kcmil 29' 39
KEYED NOTES
GRAPHIC SCALE
GENERAL NOTES
U
D A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
POWER PLAN
E-101
EXISTING WAREHOUSE STORAGE
WAREHOUSE STORAGE ADDITION
LOADING DOCK
1. UNLESS CALLED OUT BY KEYED NOTE, ALL EXISTING
ELECTRICAL EQUIPMENT, FIXTURES, AND
INFRASTRUCTURE IS EXISTING TO REMAIN.
2. ALL WORK IN WAREHOUSE STORAGE ADDITION IS NEW
WORK.
3. DASHED LINES FOR ELECTRICAL FIXTURES INDICATE
EXISTING TO REMAIN.
1. PROVIDE NEW ELECTRICAL FIXTURES IN THIS SPACE.
2. NEW UTILITY TRANSFORMER.
3. NEW UNDERGROUND FEEDER. SEE 1/ES-101 FOR MORE
INFORMATION.
4. NEW MAIN CIRCUIT BREAKER PANEL. INTERCEPT AND
EXTEND EXISTING ELECTRICAL BRANCH CIRCUITS TO NEW
PANEL.
5. WEATHERPROOF RECEPTACLE. PROTECTIVE COVER WITH
IN-USE . MOUNT 48" ABOVE GRADE.
6. QUADRUPLEX RECEPTACLE FOR FIRE ALARM PANEL(S).
MOUNT AT ELEVATION AS SHOWN ON PLANS.
COORDINATE WITH FIRE ALARM CONTRACTOR PRIOR TO
ROUGH-IN.
E-101
1 POWER PLAN
SCALE: 3/16"= 1'-0"
NORTH
E-101
2 POWER RISER
AutoCAD SHX Text 1'-0'
AutoCAD SHX Text
AutoCAD SHX Text 6'
AutoCAD SHX Text 6'
AutoCAD SHX Text 3'
AutoCAD SHX Text
SCALE: 3/16"=
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
OF
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
USDA / APHIS
AutoCAD SHX Text
250 MARQUETTE AVENUE
AutoCAD SHX Text
MINNEAPOLIS, MN 55401
AutoCAD SHX Text
SUITE 410
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
THE
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
BUZZARDS BAY, MASSACHUSETTS
AutoCAD SHX Text 25 31
AutoCAD SHX Text 3/10/2025
AutoCAD SHX Text
RPP
AutoCAD SHX Text
RPP
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
XXX
AutoCAD SHX Text 2424-A
AutoCAD SHX Text
T. MITCHELL
AutoCAD SHX Text
M. RADLOFF
AutoCAD SHX Text
T. SNIDOW
AutoCAD SHX Text
T. OTTEN
W-EX
W-EX
W-EX
OSOS OS
B-EXB-EXB-EXB-EXB-EXB-EXB-EXB-EXB-EX
B-EX B-EX B-EX B-EX B-EX B-EX B-EX B-EX B-EX
B-EXB-EXB-EXB-EXB-EXB-EXB-EXB-EXB-EX
L1-3L1-3L1-3L1-3L1-3
L1-3 L1-3 L1-3 L1-3 L1-3
L1-3L1-3L1-3L1-3L1-3
L1-1L1-1L1-1L1-1
L1-1 L1-1 L1-1 L1-1
L1-1L1-1L1-1L1-1
EXIT-EX
EXIT-EX
C4C4EC4C4C4
C4C4C4C4E
C4
C4C4EC4C4C4E
OS
W1
W2
W1
L1-5
L1-5
L1-5
X1
SD-1
W1
OS OS
X1
W1
W1
L1-12
9'-6"
KEYED NOTES
GRAPHIC SCALE
GENERAL NOTES
U
D A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
LIGHTING PLAN
E-201
EXISTING WAREHOUSE STORAGE
WAREHOUSE STORAGE ADDITION
1. UNLESS CALLED OUT BY KEYED NOTE, ALL EXISTING
ELECTRICAL EQUIPMENT, FIXTURES, AND
INFRASTRUCTURE IS EXISTING TO REMAIN.
2. ALL WORK IN WAREHOUSE STORAGE ADDITION IS NEW
WORK.
3. DASHED LINES FOR ELECTRICAL FIXTURES INDICATE
EXISTING TO REMAIN.
4. EXTERIOR LIGHTING TO BE CONTROLLED INDEPENDENTLY
OF INTERIOR LIGHTING. CONTRACTOR MUST MAKE-UP
ANY ADDITIONAL WIRING NECESSARY FOR THIS
OPERATION.
1. PROVIDE NEW ELECTRICAL FIXTURES IN THIS SPACE.
2. NEW 3-WAY LIGHT SWITCH.
E-201
1 LIGHTING PLAN
SCALE: 3/16"= 1'-0"
NORTH
E-201
2 LIGHTING ELEVATION
SCALE: 3/16"= 1'-0" E-201
3 LIGHTING ELEVATION
SCALE: 3/16"= 1'-0"
8'- 6"
W1
'-0
W2
6'- 0"
W1
E-201
4 LIGHTING ELEVATION
SCALE: 3/16"= 1'-0"
'-0
W1
W1 W1
26'-6 3/4"
E-201
E-201
E-201
AutoCAD SHX Text 1'-0'
AutoCAD SHX Text
AutoCAD SHX Text 6'
AutoCAD SHX Text 6'
AutoCAD SHX Text 3'
AutoCAD SHX Text
SCALE: 3/16"=
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
OF
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
USDA / APHIS
AutoCAD SHX Text
250 MARQUETTE AVENUE
AutoCAD SHX Text
MINNEAPOLIS, MN 55401
AutoCAD SHX Text
SUITE 410
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
THE
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
BUZZARDS BAY, MASSACHUSETTS
AutoCAD SHX Text 26 31
AutoCAD SHX Text 3/10/2025
AutoCAD SHX Text
RPP
AutoCAD SHX Text
RPP
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
XXX
AutoCAD SHX Text 2424-A
AutoCAD SHX Text
T. MITCHELL
AutoCAD SHX Text
M. RADLOFF
AutoCAD SHX Text
T. SNIDOW
AutoCAD SHX Text
T. OTTEN
LUMINAIRE SCHEDULE
CALLOUT SYMBOL DESCRIPTION MOUNTING INPUT WATTS VOLTS NOTES
B-EX EXISTING PENDANT INDUSTRIAL FIXTURE. EXISTING TO
REMAIN.
CEILING 40 120V 1P 2W EXISTING
C4 PENDANT LED INDUSTRIAL FIXTURE. CEILING 40 120V 1P 2W 80 CRI.
C4E PENDANT LED INDUSTRIAL FIXTURE WITH INTEGRAL
BATTERY BACKUP.
CEILING 40 120V 1P 2W 80 CRI. PROVIDE WITH
SELF-TESTING BATTERY
BACKUP.
EXIT-EX EXIT SIGN. EXISTING TO REMAIN. CEILING 64 120V 1P 2W EXISTING
W1 WALLPACK FIXTURE. MOUNT AT 12' A.F.F. UNLESS
OTHERWISE SPECIFIED.
WALL 30 120V 1P 2W PROVIDE WITH INTEGRAL
PHOTOCELL.
W2 EXTERIOR WALL SCONCE. WALL 10 120V 1P 2W PROVIDE WITH INTEGRAL
PHOTOCELL.
W-EX EXISTING WALLPACK FIXTURE. EXISTING TO REMAIN. WALL 30 120V 1P 2W EXISTING
X1 EXIT SIGN WITH INTEGRAL BATTERY. CEILING 5 120V 1P 2W
U
D A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
LIGHTING SCHEDULES
E-202
LED SUSPENDED INDUSTRIAL
FIXTURE TYPE: C4, C4E
LUMINAIRE REQUIREMENTS:
1. HOUSING - IMPACT RESISTANT ENGINEERING-GRADE THERMOPLASTIC
HOUSING, SCRATCH RESISTANT, CORROSION PROOF. UNIVERSAL
DIRECTIONAL CHEVRONS. REINFORCED, IMPACT-RESISTANT COLOR PANELS.
2. LIGHT SOURCE - LED'S MOUNTED ON PRINTED CIRCUIT BOARD. 10 YEARS
WARRANTY.
3. LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. GREEN LETTERS
AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR
BOTH DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH
HOUSING AS REQUIRED.
4. EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY
CHARGER WITH MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON
INDICATOR LAMP AND TEST SWITCH.
5. MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-
FIXTURE MOUNTING.
6. ILLUMINATION - PROVIDED BY RED HIGH-OUTPUT LEDS INSIDE OF FIXTURE
HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH
FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM LED LIGHT
OUTPUT.
7. VOLTAGE - OPERATING VOLTAGE OF 120-277V.
LED EXIT SIGN
FIXTURE TYPE: X1
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-CAST ALUMINUM WITH INTEGRAL PASSIVE COOLING MECHANISM.
HEAT SINK MUST BE INCORPORATED DIRECTLY INTO HOUSING OR DRIVER
COMPARTMENT TO ENSURE MAXIMUM HEAT TRANSFER AND DISSIPATION.
2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON POLYESTER
POWDER COAT. IP66 RATED. FINISH IS DARK BRONZE.
3. POWER SUPPLY/LED DRIVER - CLASS 1 DRIVER MUST OPERATE AT 120/277 VOLTS,
50/60 HZ, POWER FACTOR GREATER THAN 0.9 AND THD LESS THAN 20% AT FULL LOAD.
MINIMUM EFFICACY MUST BE 60 LM/W AT MAXIMUM 600mA OPERATING CURRRENT.
4. LED OPTICAL ASSEMBLY - PRECISION MOLDED ACRYLIC LENS PROVIDED FOR MULTIPLE
HIGH-POWERED LEDS. BUG UPLIGHT RATING OF U0. MINIMUM COLOR RENDERING
INDEX(CRI) MUST BE 70 FORCORRELATED COLOR TEMPERATURE OF 4000K.
5. CERTIFICATION - UL AND/OR ETL LISTED FOR DAMP OR WET LOCATIONS (FOR EXTERIOR
WALL MOUNT) AND RoHS COMPLIANT.
6. OPTIONS - VARIOUS LUMEN OUTPUT RATINGS AS INDICATED.
7. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A LUMINAIRE
THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT INTENDED TO INDICATE
A CERTAIN MANUFACTURER OR PREFERENCE.
8. INCLUDE EMERGENCY BATTERY PACK OPTION.
LED WALL MOUNTED FIXTURE
FIXTURE TYPE: W1
LUMINAIRE REQUIREMENTS:
1. HOUSING - PRECISION FORMED USING COLD ROLLED STEEL. LENSING
MANUFACTURED FROM A DIFFUSED ACRYLIC POLYMER.
2. LIGHT SOURCE - 4000K COLOR TEMPERATURE , EFFICACY OF 143-146
LUMENS/WATT, WITH A MINIMUM CRI OF 80.
4. DRIVER - OPERATING VOLTAGE OF 120-277V. DIMMABLE TO 10%. (0-10 VOLT
DIMMING)
5. CERTIFICATION - UL 1598, DLC QUALIFIED, AND ROHS COMPLIANT. COMPLIES
WITH LM79, LM80 AND TM21 TESTING STANDARDS. UL 924 WHEN EQUIPPED
WITH EMERGENCY BATTERY BACK-UP. IC RATED WHEN INDICATED.
6. MOUNTING - SUSPENDED/SURFACE MOUNTED.
7. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A
LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT
INTENDED TO INDICATE A CERTAIN MANUFACTURER OR PREFERENCE.
8. NOM. DIMENSIONS: (L=48"" X W=9 7/8" X D=4 3/8"")
1.
2.
3.
4.
5.
6.
7.
DEVICE REQUIREMENTS:
FEATURES: COMPATIBLE WITH LED.
HOUSING: IMPACT RESISTANT INJECTION MOLDED ABS
MOUNTING: WALL MOUNTED (SINGLE GANG SWITCH BOX)
INPUT RATING: 120/277 VAC.
TECHNOLOGY: MANUAL ON/OFF
FINISH: WHITE
NOM. DIMENSIONS: 2.74"H X 1.68"W X 1.63"D
MANUAL ON/OFF
LUMINAIRE REQUIREMENTS:
1. HOUSING ALUMINUM HOUSING WITH DARK BRONZE FINISH.
2. OPTICS - DIFFUSE VANDAL-RESISTANT ACRYLIC LENS. BUG UPLIGHT RATING OF
U0, WITH GLARE RATING AS DETERMINED BY LIGHTING ZONE INSTALLED.
3. LIGHT SOURCE - SOLID STATE LEDS, 4000K CCT UON, MINIMUM 80 CRI UON, AND
MINIMUM EFFICACY OF 50 LUMENS/WATT UON. INITIAL LUMEN OUTPUT AS
INDICATED IN LUMINAIRE SCHEDULE.
4. DRIVER - REPLACEABLE, INTEGRAL, HIGH-EFFICIENCY DRIVER WITH MINIMUM
0.9 PF, OPERATING VOLTAGE OF 120 OR 277V, THERMAL MANAGEMENT, AND
<20% THD. ON-OFF CONTROL AS INDICATED IN LUMINAIRE SCHEDULE.
5. CERTIFICATION - UL LISTED FOR WET LOCATION, ROHS COMPLIANT. COMPLIES
WITH IES LM79, LM80 AND TM21 TESTING STANDARDS.
6. MOUNTING - SURFACE MOUNTED WITH STAINLESS STEEL MOUNTING
HARDWARE.
7. OPTIONS - VARIOUS PROFILES AND SHAPES. OPTIONAL UPLIGHT COMPONENT IF
MOUNTED UNDER CANOPY.
8. THIS SKETCH IS A NON-PROPRIETARY GRAPHIC REPRESENTATION OF A
LUMINAIRE THAT MAY MEET THE SPECIFICATION REQUIREMENTS. IT IS NOT
INTENDED TO INDICATE A CERTAIN MANUFACTURER OR REFERENCE.
9. NOM. DIMENSIONS: ( L=4 5/16" D=3 11/16" H=9 1/4")
LED CYLINDER WALL MOUNTED FIXTURE
FIXTURE TYPE: W2
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
OF
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
USDA / APHIS
AutoCAD SHX Text
250 MARQUETTE AVENUE
AutoCAD SHX Text
MINNEAPOLIS, MN 55401
AutoCAD SHX Text
SUITE 410
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
THE
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
BUZZARDS BAY, MASSACHUSETTS
AutoCAD SHX Text 27 31
AutoCAD SHX Text 3/10/2025
AutoCAD SHX Text
RPP
AutoCAD SHX Text
RPP
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
XXX
AutoCAD SHX Text 2424-A
AutoCAD SHX Text
T. MITCHELL
AutoCAD SHX Text
M. RADLOFF
AutoCAD SHX Text
T. SNIDOW
AutoCAD SHX Text
T. OTTEN
OHD-1
1/2HP,120V1P2W
OHD-2
1/2HP,120V1P2W
L1-6L1-8
OHD-3
1/2HP,120V1P2W
SAL-1
15KVA,208V3P4WSAL-2
15KVA,208V3P4W
L1-10
SD-1
L1-20,22,24 1"C,3#6,#6N,#10G
L1-29,31,33 1"C,3#6,#6N,#10G
EQUIPMENT CONNECTIONS SCHEDULE
CALLOUT DESCRIPTION CIRCUIT VOLTS AMPS BREAKER HP KVA WIRE SIZE DISCONNECT WIRE LENGTH NOTE 1
OHD-1 OVERHEAD DOOR MOTOR L1-6 120V 1P 2W 9.8 20/1 1/2 HP 1.18 #12 HARDWIRED CONNECTION 46' EXISTING TO REMAIN.
OHD-2 OVERHEAD DOOR MOTOR L1-8 120V 1P 2W 9.8 20/1 1/2 HP 1.18 #10 HARDWIRED CONNECTION 71' EXISTING TO REMAIN.
OHD-3 OVERHEAD DOOR MOTOR L1-10 120V 1P 2W 9.8 20/1 1/2 HP 1.18 #10 HARDWIRED CONNECTION 123'
REF-1 CONNEX COOLER L1-7,9,11 208V 3P 4W 25.38 50/3 7.5 HP 9.15 #6 NON-FUSED 56' EXISTING TO REMAIN.
REF-2 CONNEX COOLER L1-13,15,17 208V 3P 4W 25.38 50/3 7.5 HP 9.15 #6 NON-FUSED 57' EXISTING TO REMAIN.
SAL-1 SALAMANDER HEATER OUTLET L1-29,31,33 208V 3P 4W 41.64 50/3 15 #6 SPECIAL RECEPTACLE 101' PROVIDE 14-50R RECEPTACLE.
SAL-2 SALAMANDER HEATER OUTLET L1-20,22,24 208V 3P 4W 41.64 50/3 15 #6 SPECIAL RECEPTACLE 138' PROVIDE 14-50R RECEPTACLE.
KEYED NOTES
GRAPHIC SCALE
GENERAL NOTES
U
D A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
EQUIPMENT PLAN
E-301
EXISTING WAREHOUSE STORAGE
WAREHOUSE STORAGE ADDITION
LOADING DOCK
1. UNLESS CALLED OUT BY KEYED NOTE, ALL EXISTING
ELECTRICAL EQUIPMENT, FIXTURES, AND
INFRASTRUCTURE IS EXISTING TO REMAIN.
2. ALL WORK IN WAREHOUSE STORAGE ADDITION IS NEW
WORK.
3. DASHED LINES FOR ELECTRICAL FIXTURES INDICATE
EXISTING TO REMAIN.
1. PROVIDE NEW ELECTRICAL CONNECTIONS IN THIS SPACE.
E-301
1 EQUIPMENT PLAN
SCALE: 3/16"= 1'-0"
NORTH
AutoCAD SHX Text 1'-0'
AutoCAD SHX Text
AutoCAD SHX Text 6'
AutoCAD SHX Text 6'
AutoCAD SHX Text 3'
AutoCAD SHX Text
SCALE: 3/16"=
AutoCAD SHX Text
PPM
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DATE
AutoCAD SHX Text
NO.
AutoCAD SHX Text
EPM
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
USDA
AutoCAD SHX Text
BY
AutoCAD SHX Text
OF
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
JOB #
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
USDA / APHIS
AutoCAD SHX Text
250 MARQUETTE AVENUE
AutoCAD SHX Text
MINNEAPOLIS, MN 55401
AutoCAD SHX Text
SUITE 410
AutoCAD SHX Text c
AutoCAD SHX Text P.A.
AutoCAD SHX Text
FIRM
AutoCAD SHX Text
THE
AutoCAD SHX Text
P.O. BOX 513, GREENWOOD, MISSISSIPPI - (662) 455-4943
AutoCAD SHX Text Johnson M Adams
AutoCAD SHX Text
ARCHITECTS/ENGINEERS PLANNING SURVEYING MANAGEMENT
AutoCAD SHX Text
BUZZARDS BAY, MASSACHUSETTS
AutoCAD SHX Text 28 31
AutoCAD SHX Text 3/10/2025
AutoCAD SHX Text
RPP
AutoCAD SHX Text
RPP
AutoCAD SHX Text
FEJ
AutoCAD SHX Text
XXX
AutoCAD SHX Text 2424-A
AutoCAD SHX Text
T. MITCHELL
AutoCAD SHX Text
M. RADLOFF
AutoCAD SHX Text
T. SNIDOW
AutoCAD SHX Text
T. OTTEN
A
S BUILDING 1392 WAREHOUSE ADDITION
FOREST PEST MANAGEMENT LABORATORY
1398 WEST TRUCK ROAD
ELECTRICAL DETAILS
E-501
CONVENTIONAL
RECEPTACLE
ISOLATED GROUND
RECEPTACLE
N Ø
N
ØEG
EG
EG
E-501
1 RECEPTACLE WIRING DETAIL
E-501
2 2-WAY DUCTBANK DETAIL
NOT USED.
4/0 AWG BARE COPPER GROUND CONDUCTOR.
INDICATES BOLTED CONNECTION.
19mm x 3050mm (3/4" x 10'-0") LONG COPPER-CLAD GROUND ROD DRIVEN WITH
INDICATES EXOTHERMIC WELD CONNECTION, COMPATIBLE WITH MATERIALS
4/0 AWG INSULATED COPPER GROUND CONDUCTOR IN 30mm CONDUIT.
LEGEND:
T
G G
E-501
3 BUILDING GROUNDING ELECTRODE SYSTEM
TOP 300mm (12") BELOW GRADE. REFER TO BUILDING GROUNDING ELECTRODE SYSTEM DETAIL FOR
NOTES:
1.
FRONT ELEVATION
A
A
SECTION "A-A"
E-501
4 BUILDING ELECTRICAL SYSTEM GROUND BUS
NOTES:
A. 3.5" C. POWER
B. 3.5" C. POWER
A B
7.5-IN MIN
3-
IN
M
IN
3-
IN
M
IN
-IN
M
IN 12
-IN
SAND
CONTINUOUS STRIP OF METALLIC
UTILITY WARNING TAPE
COMPACTED EARTH FILL BACKFILL
IN 6" LIFTS, COMPACT. FINAL
COMPACTION SHALL BE 95% THAT
OF ADJACENT EARTH.
MOUNTING STRAP
GREEN HEX HEAD
GROUND SCREW
CONNECTION
CONDUIT
BONDING
JUMPER
OUTLET
BOX
MOUNTING STRAP
GREEN HEX HEAD
GROUND SCREW
CONNECTION
OUTLET
BOX
NORMAL "COMMON"
BUILDING GROUND (EG)
EG BUS
IG BUS
ISOLATED
GROUND
MAIN PANELBOARD
NEUTRAL BUS
MAIN BONDING
JUMPER
PANELBOARD
GROUND BUS
BUILDING
STRUCTURAL STEEL
BUILDING SERVICE
TRANSFORMER
TRANSFORMER
GROUND BUS
TIE INTO EXISTING BUILDING
GROUND RING (IF APPLICABLE)
INSTALL NEW BUILDING
SUPPLEMENTAL GROUND ROD
AT THE SERVICE DISCONNECT
BUILDING
EXTERIOR
WALL
WATER SERVICE AT STREET
SIDE OF WATER METER.
UNDERGROUND METAL
WATER PIPE GREATER THAN
3.05 METERS LONG.
INSTALL BUILDING SYSTEM GROUND
BUS. SEE DETAIL.
GROUNDING CLAMP WITHIN 5
FEET OF ENTRANCE POINT
OF PIPE.
TYP. 2
POLYESTER/FIBERGLASS INSULATOR.
45MM (1-3/4") DIA. X 50 MM (2") LONG.
RED IN COLOR.
COPPER GROUND BUS.
10MM (3/8") MOUNTING BOLT.
BONDING CONDUCTOR
SIZED TO THE LARGEST
GROUND CONDUCTOR
IN GROUP (TYPICAL).
GROUNDING BUSHING (TYPICAL).
EXOTHERMIC WELD
CONNECTION, (TYPICAL).
INSULATED COPPER
GROUNDING CONDUCTOR.
BARE COPPER
GROUNDING
CONDUCTOR.
INSULATED GROUNDING
CONDUCTOR IN CONDUIT.
SEE BUILDING
GROUNDING DETAIL FOR
ADDITIONAL
INFORMATION.
6MM X50MM (1/4" X 2") LONG COPPER
GROUND BUS. MOUNTED TO WALL WITH
INSULATORS.
BEING JOINED.
MI
N.
m m (2
50mm (2") 6mm (1/4")
EXACT CONFIGURATION.
SEE CIVIL FOR ADDITIONAL INFORMATION.
MATCH…