This document is a federal specification section (Section 09 90 00) for Paints and Coatings from the USDA B1392 Addition project, dated February 2021. The comprehensive specification provides detailed requirements for painting and coating various surfaces, including metal, concrete, and other substrates, both for exterior and interior applications. Key requirements include using environmentally friendly, low-VOC materials with specific performance standards, applying coatings in accordance with MPI (Master Painters Institute) guidelines, and following strict surface preparation and application procedures.
The specification outlines specific coating systems for different surface types, with precise requirements for primer, intermediate, and topcoat applications. For exterior metal surfaces, the specification prescribes alkyd and waterborne coating systems with a minimum dry film thickness of 4.5-5.25 mils, depending on the surface type. Interior metal surfaces require high-performance architectural latex systems with a 5-mil dry film thickness. The document also includes detailed environmental and safety requirements, such as restrictions on toxic materials, proper ventilation during application, and waste management protocols, emphasizing the use of green-certified painting materials with low environmental impact.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 12639525R0018-0001.pdf | ||
| RFI 5.docx | DOCX document | |
| RFI 4.docx | DOCX document | |
| 09_90_00 Paints and Coatings.pdf | ||
| RFI 3.docx | DOCX document | |
| WH2.jpg | JPG image | |
| WH1.jpg | JPG image | |
| Contractor Sign In 13AUG25.pdf | ||
| PPQ S and T FPML Geotechnical Report.pdf | ||
| Geotechnical Engineering Report_Proposed Building Addition_USDA ARS.pdf | ||
| RFI 2.docx | DOCX document | |
| RFI and response.docx | DOCX document | |
| Atch 3_specifications.pdf | ||
| Atch 2_Federal Construction Wage Rates_Barnstable County.pdf | ||
| Atch 1_SOW Warehouse Addition .doc | DOC document | |
| 12639525R0018.pdf | ||
| Atch 5_drawings_2 of 2.pdf | ||
| Atch 4_drawings_1 of 2.pdf |
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA B1392 Addition 2424A
SECTION 09 90 00
PAINTS AND COATINGS
02/21
PART 1 GENERAL
1.1 RELATED REQUIREMENTS
1.1.1 Painting Included
Where a space or surface is indicated to be painted, include the following unless indicated otherwise.
a. Surfaces behind portable objects and surface mounted articles readily detachable by removal of fasteners, such as screws and bolts.
b. New factory finished surfaces that require identification or color coding and factory finished surfaces that are damaged during performance of the work.
c. Existing coated surfaces that are damaged during performance of the work.
1.1.1.1 Exterior Painting
Includes new surfaces of the building appurtenances.
1.1.1.2 Interior Painting
Includes new surfaces of the building and appurtenances as indicated.
Where a space or surface is indicated to be painted, include the following items, unless indicated otherwise.
a. Exposed columns, girders, beams, joists, and metal deck; and
b. Other contiguous surfaces.
1.1.2 Painting Excluded
Do not paint the following unless indicated otherwise.
a. Surfaces concealed and made inaccessible by panelboards, fixed ductwork, machinery, and equipment fixed in place.
b. Surfaces in concealed spaces. Concealed spaces are defined as enclosed spaces above suspended ceilings, furred spaces, attic spaces, crawl spaces, elevator shafts and chases.
c. Steel to be embedded in concrete.
d. Copper, stainless steel, aluminum, anodized aluminum, brass, and lead except existing coated surfaces.
e. Hardware, fittings, and other factory finished items.
1.1.3 Mechanical and Electrical Painting
Includes field coating of interior and exterior new surfaces.
SECTION 09 90 00 Page 1
a. Where a space or surface is indicated to be painted, include the following items unless indicated otherwise.
(1) Exposed piping, conduit, and ductwork;
(2) Supports, hangers, air grilles, and registers;
(3) Miscellaneous metalwork and insulation coverings.
b. Do not paint the following, unless indicated otherwise:
(1) New zinc-coated, aluminum, and copper surfaces under insulation
(2) New aluminum jacket on piping
(3) New interior ferrous piping under insulation.
1.1.4 Exterior Painting of Site Work Items
Field coat the following items:
New Surfaces
a. Bollards
b. Handrails
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN CONFERENCE OF GOVERNMENTAL INDUSTRIAL HYGIENISTS (ACGIH)
ACGIH 0100 (2017; Suppl 2020) Documentation of the Threshold Limit Values and Biological Exposure Indices
ASTM INTERNATIONAL (ASTM)
ASTM D235 (2022) Standard Specification for Mineral Spirits (Petroleum Spirits) (Hydrocarbon Dry Cleaning Solvent)
ASTM D523 (2014; R 2018) Standard Test Method for Specular Gloss
ASTM D6386 (2022) Standard Practice for Preparation of Zinc (Hot-Dip Galvanized) Coated Iron and Steel Product and Hardware Surfaces for Painting
CENTERS FOR DISEASE CONTROL AND PREVENTION (CDC)
Intelligence Bulletin 65 (2013) Occupational Exposure to Carbon Nanotubes and Nanofibers
SECTION 09 90 00 Page 2
MASTER PAINTERS INSTITUTE (MPI)
MPI 9 (2016) Alkyd, Exterior Gloss (MPI Gloss Level 6)
MPI 23 (2015) Primer, Metal, Surface Tolerant
MPI 72 (2016) Polyurethane, Two-Component, Pigmented, Gloss (MPI Gloss Level 6-7)
MPI 76 (2016) Primer, Alkyd, Quick Dry, for Metal
MPI 79 (2016) Primer, Alkyd, Anti-Corrosive for Metal
MPI 94 (2016) Alkyd, Exterior, Semi-Gloss (MPI Gloss Level 5)
MPI 95 (2015) Primer, Quick Dry, for Aluminum
MPI 101 (2016) Primer, Epoxy, Anti-Corrosive, for Metal
MPI 107 (2016) Primer, Rust-Inhibitive, Water Based
MPI 134 (2015) Primer, Galvanized, Water Based
MPI 141 (2016) Latex, Interior, High Performance Architectural, Semi-Gloss (MPI Gloss Level 5)
MPI 163 (2016) Light Industrial Coating, Exterior, Water Based, Semi-Gloss (MPI Gloss Level 5)
MPI ASM (2019) Architectural Painting Specification Manual
MPI GPS-1-14 (2014) Green Performance Standard GPS-1-14
MPI GPS-2-14 (2014) Green Performance Standard GPS-2-14
MPI MRM (2015) Maintenance Repainting Manual
SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC Glossary (2011) SSPC Protective Coatings Glossary
SSPC PA 1 (2024) Shop, Field, and Maintenance Coating of Metals
SSPC QP 1 (2019) Standard Procedure for Evaluating the Qualifications of Industrial/Marine Painting Contractors (Field Application to Complex Industrial Steel Structures and Other Metal Components)
SSPC SP 1 (2015) Solvent Cleaning
SSPC SP 2 (2018) Hand Tool Cleaning
SECTION 09 90 00 Page 3
SSPC SP 3 (2024) Power Tool Cleaning
SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning
SSPC SP 10/NACE No. 2 (2015) Near-White Blast Cleaning
SSPC VIS 3 (2004) Guide and Reference Photographs for Steel Surfaces Prepared by Hand and Power Tool Cleaning
SSPC-SP WJ-3/NACE WJ-3 (2012) Thorough Cleaning, Waterjet Cleaning of Metals
U.S. ARMY CORPS OF ENGINEERS (USACE)
EM 385-1-1 (2024) Safety -- Safety and Occupational Health (SOH) Requirements
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-STD-101 (2014; Rev C) Color Code for Pipelines and for Compressed Gas Cylinders
U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)
EPA Method 24 (2000) Determination of Volatile Matter Content, Water Content, Density, Volume Solids, and Weight Solids of Surface Coatings
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
FED-STD-313 (2018) Material Safety Data, Transportation Data and Disposal Data for Hazardous Materials Furnished to Government Activities
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.1000 Air Contaminants
1.3 DEFINITIONS
1.3.1 Qualification Testing
Qualification testing is the performance of all test requirements listed in the product specification. This testing is accomplished by MPI to qualify each product for the MPI Approved Product List, and may also be accomplished by Contractor's third-party testing lab if an alternative to Batch Quality Conformance Testing by MPI is desired.
1.3.2 Batch Quality Conformance Testing
Batch quality conformance testing determines that the product provided is the same as the product qualified to the appropriate product specification. This testing must be accomplished by an MPI testing lab.
SECTION 09 90 00 Page 4
1.3.3 Coating
SSPC Glossary ; (1) A liquid, liquefiable, or mastic composition that is converted to a solid protective, decorative, or functional adherent film after application as a thin layer; (2) Generic term for paint, lacquer, enamel.
1.3.4 DFT or dft
Dry film thickness, the film thickness of the fully cured, dry paint or coating.
1.3.5 DSD
Degree of Surface Degradation, the MPI system of defining degree of surface degradation. Five levels are generically defined under the Assessment sections in the MPI MRM, MPI Maintenance Repainting Manual.
1.3.6 EXT
MPI short term designation for an exterior coating system.
1.3.7 INT
MPI short term designation for an interior coating system.
1.3.8 Loose Paint
Paint or coating that can be removed with a dull putty knife.
1.3.9 mil / mils
The English measurement for 0.001 in or one one-thousandth of an inch.
1.3.10 MPI Gloss Levels
MPI system of defining gloss. Seven gloss levels (G1 to G7) are generically defined under the Evaluation sections of the MPI Manuals.
Traditionally, Flat refers to G1/G2, Eggshell refers to G3, Semigloss refers to G5, and Gloss refers to G6.
Gloss levels are defined by MPI as follows:
Gloss Level Description Units at 60 degree angle
Units at 80 degree angle
G1 Matte or Flat 0 to 5 10 max
G2 Velvet 0 to 10 10 to 35
G3 Eggshell 10 to 25 10 to 35
G4 Satin 20 to 35 35 min
G5 Semi-Gloss 35 to 70
G6 Gloss 70 to 85
SECTION 09 90 00 Page 5
Gloss Level Description Units at 60 degree angle
Units at 80 degree angle
G7 High Gloss
Gloss is tested in accordance with ASTM D523. Historically, the Government has used Flat (G1 / G2), Eggshell (G3), Semi-Gloss (G5), and Gloss (G6).
1.3.11 MPI System Number
The MPI coating system number in each MPI Division found in either the MPI Architectural Painting Specification Manual or the Maintenance Repainting Manual and defined as an exterior (EXT/REX) or interior system (INT/RIN).
1.3.12 Paint
SSPC Glossary ; (1) Any pigmented liquid, liquefiable, or mastic composition designed for application to a substrate in a thin layer that is converted to an opaque solid film after application. Used for protection, decoration, identification, or to serve some other functional purposes; (2) Application of a coating material.
1.3.13 REX
MPI short term designation for an exterior coating system used in repainting projects or over existing coating systems.
1.3.14 RIN
MPI short term designation for an interior coating system used in repainting projects or over existing coating systems.
1.4 SCHEDULING
Allow paint, polyurethane, varnish, and wood stain installations to cure prior to the installation of materials that adsorb VOCs.
1.5 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
Samples of specified materials may be taken and tested for compliance with specification requirements.
SD-02 Shop Drawings
Piping Identification
SD-03 Product Data
Coating; G
Product Data Sheets
SD-04 Samples
SECTION 09 90 00 Page 6
Color; G
SD-07 Certificates
Qualification Testing laboratory for coatings; G
Indoor Air Quality for Paints and Primers
Indoor Air Quality for Consolidated Latex Paints
SD-08 Manufacturer's Instructions
Mixing
Manufacturer's Safety Data Sheets
SD-10 Operation and Maintenance Data
Coatings, Data Package 1; G
1.6 QUALITY ASSURANCE
1.6.1 Regulatory Requirements
1.6.1.1 Environmental Protection
In addition to requirements specified elsewhere for environmental protection, provide coating materials that conform to the restrictions of the local Air Pollution Control District and regional jurisdiction.
Notify Contracting Officer of any paint specified herein which fails to conform.
1.6.1.2 Lead Content
Do not use coatings having a lead content over 0.06 percent by weight of nonvolatile content.
1.6.1.3 Chromate Content
Do not use coatings containing zinc-chromate or strontium-chromate.
1.6.1.4 Asbestos Content
Provide asbestos-free materials.
1.6.1.5 Mercury Content
Provide materials free of mercury or mercury compounds.
1.6.1.6 Silica
Provide abrasive blast media containing no free crystalline silica.
1.6.1.7 Human Carcinogens
Provide materials that do not contain ACGIH 0100 confirmed human carcinogens (A1) or suspected human carcinogens (A2).
SECTION 09 90 00 Page 7
1.6.1.8 Carbon Based Fibers / Tubes
Materials must not contain carbon based fibers such as carbon nanotubes or carbon nanofibers. Intelligence Bulletin 65 ranks toxicity of carbon nanotubes on a par with asbestos.
1.6.2 SSPC QP 1 Certification
Contractors that perform surface preparation or coating application on steel substrates must be certified by the Society for Protective Coatings (formerly Steel Structures Painting Council) (SSPC) to the requirements of SSPC QP 1 prior to Contract award, and must remain certified while accomplishing any surface preparation or coating application. If a Contractor's certification expires, the firm will not be allowed to perform any work until the certification is reissued. Requests for extension of time for any delay to the completion of the project due to an inactive certification will not be considered. Notify the Contracting Officer of any change in Contractor certification status. Notify the Contracting Officer of all scheduled and unannounced on-site audits from SSPC and furnish a copy of all audit reports.
1.6.3 Approved Products List
The current MPI, "Approved Product List" which lists paint by brand, label, product name and product code as of the date of Contract award, will be used to determine compliance with the submittal requirements of this specification. The Contractor may choose to use a subsequent MPI "Approved Product List", however, only one list may be used for the entire Contract and each coating system is to be from a single manufacturer.
Provide all coats on a particular substrate from a single manufacturer.
No variation from the MPI Approved Products List is acceptable.
1.6.4 Paints and Coatings Indoor Air Quality Certifications
Provide paint and coating products certified to meet indoor air quality requirements by MPI GPS-1-14 , MPI GPS-2-14 or provide certification by other third-party programs. Provide current product certification documentation from certification body.
Provide certification of Indoor Air Quality for Paints and Primers.
Submit required indoor air quality certifications in one submittal package.
1.6.5 Field Samples and Tests
The Contracting Officer may choose up to two coatings that have been delivered to the site to be tested at no cost to the Government. Take samples of each chosen product as specified in the paragraph SAMPLING PROCEDURE. Test each chosen product as specified in the paragraph TESTING PROCEDURE. Remove products from the job site which do not conform, and replace with new products that conform to the referenced specification.
Test replacement products that failed initial testing as specified in the paragraph TESTING PROCEDURE at no cost to the Government.
1.6.5.1 Sampling Procedure
Select paint at random from the products that have been delivered to the job site for sample testing. The Contractor must provide one quart samples of the selected paint materials. Take samples in the presence of the Contracting Officer, and label, and identify each sample. Provide
SECTION 09 90 00 Page 8 labels in accordance with the paragraph PACKAGING, LABELING, AND STORAGE.
1.6.5.2 Testing Procedure
Provide Batch Quality Conformance Testing for specified products, as defined by and performed by MPI. As an alternative to Batch Quality Conformance Testing, the Contractor may provide Qualification Testing for specified products above to the appropriate MPI product specification, using the third-party laboratory approved under the paragraph QUALIFICATION TESTING laboratory for coatings. Include the backup data and summary of the test results within the qualification testing lab report. Provide a summary listing of all the reference specification requirements and the result of each test. Clearly indicate in the summary whether the tested paint meets each test requirement. Note that Qualification Testing may take 4 to 6 weeks to perform, due to the extent of testing required.
Submit name, address, telephone number, FAX number, and e-mail address of the independent third party laboratory selected to perform testing of coating samples for compliance with specification requirements. Submit documentation that laboratory is regularly engaged in testing of paint samples for conformance with specifications, and that employees performing testing are qualified. If MPI is chosen to perform the Batch Quality Conformance testing, the above submittal information is not required, only a letter is required from the Contractor stating that MPI will perform the testing.
1.7 PACKAGING, LABELING, AND STORAGE
Provide paints in sealed containers that legibly show the Contract specification number, designation name, formula or specification number, batch number, color, quantity, date of manufacture, manufacturer's formulation number, manufacturer's directions including any warnings and special precautions, and name and address of manufacturer. Furnish pigmented paints in containers not larger than 5 gallons. Store paints and thinners in accordance with the manufacturer's written directions, and as a minimum, stored off the ground, under cover, with sufficient ventilation to prevent the buildup of flammable vapors, and at temperatures between 40 to 95 degrees F. Do not store paint, polyurethane, varnish, or wood stain products with materials that have a high capacity to absorb VOC emissions. Do not store paint, polyurethane, varnish, or wood stain products in occupied spaces.
1.8 SAFETY AND HEALTH
Comply with applicable Federal, State, and local laws and regulations, and with the ACCIDENT PREVENTION PLAN, including the Activity Hazard Analysis as specified in Section 01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS and in Appendix A of EM 385-1-1 . Include in the Activity Hazard Analysis the potential impact of painting operations on painting personnel and on others involved in and adjacent to the work zone.
1.8.1 Toxic Materials
To protect personnel from overexposure to toxic materials, conform to the most stringent guidance of:
a. The applicable manufacturer's Safety Data Sheets (SDS) or local regulation.
SECTION 09 90 00 Page 9
b. 29 CFR 1910.1000 .
c. ACGIH 0100 , threshold limit values.
Submit manufacturer's Safety Data Sheets for coatings, solvents, and other potentially hazardous materials, as defined in FED-STD-313 .
1.9 ENVIRONMENTAL REQUIREMENTS
Comply, at minimum, with manufacturer recommendations for space ventilation during and after installation.
1.9.1 Coatings
Do not apply coating when air or substrate conditions are:
a. Less than 5 degrees F above dew point;
b. Below 50 degrees F or over 95 degrees F, unless specifically pre-approved by the Contracting Officer and the product manufacturer.
Do not, under any circumstances, violate the manufacturer's application recommendations.
1.9.2 Post-Application
Vacate space for as long as possible after application. Wait a minimum of 48 hours before occupying freshly painted rooms. Maintain one of the following ventilation conditions during the curing period, or for 72 hours after application:
a. Supply 100 percent outside air 24 hours a day.
b. Supply airflow at a rate of 6 air changes per hour, when outside temperatures are between 55 degrees F and 85 degrees F and humidity is between 30 percent and 60 percent.
c. Supply airflow at a rate of 1.5 air changes per hour, when outside air conditions are not within the range stipulated above.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to the coating specifications and standards referenced in PART 3.
Submit Product Data Sheets for specified coatings and solvents. Provide preprinted cleaning and maintenance instructions for all coating systems.
Submit Manufacturer's Instructions on Mixing: Detailed mixing instructions, minimum and maximum application temperature and humidity, pot life, and curing and drying times between coats.
2.2 COLOR SELECTION OF FINISH COATS
Provide colors of finish coats as indicated or specified. Allow Contracting Officer to select colors not indicated or specified.
Manufacturers' names and color identification are used for the purpose of color identification only. Named products are acceptable for use only if they conform to specified requirements. Products of other manufacturers are acceptable if the colors are approximately the colors indicated and
SECTION 09 90 00 Page 10 the product conforms to specified requirements.
Provide color, texture, and pattern of wall coating systems as indicated.
Submit manufacturer's samples of paint colors. Cross reference color samples to color scheme as indicated. Submit color stencil codes. Tint each coat progressively darker to enable confirmation of the number of coats.
PART 3 EXECUTION
3.1 PROTECTION OF AREAS AND SPACES NOT TO BE PAINTED
Prior to surface preparation and coating applications, remove, mask, or otherwise protect hardware, hardware accessories, machined surfaces, radiator covers, plates, lighting fixtures, public and private property, and other such items not to be coated that are in contact with surfaces to be coated. Following completion of painting, reinstall removed items by workmen skilled in the trades. Restore surfaces contaminated by coating materials, to original condition and repair damaged items.
3.2 SURFACE PREPARATION
Remove dirt, splinters, loose particles, grease, oil, and other foreign matter and substances deleterious to coating performance as specified for each substrate before application of paint or surface treatments. Remove oil and grease prior to mechanical cleaning. Schedule cleaning so that dust and other contaminants will not fall on wet, newly painted surfaces.
Spot-prime exposed ferrous metals such as nail heads on or in contact with surfaces to be painted with water-thinned paints, with a suitable corrosion-inhibitive primer capable of preventing flash rusting and compatible with the coating specified for the adjacent areas. Refer to MPI ASM and MPI MRM for additional more specific substrate preparation requirements.
3.3 PREPARATION OF METAL SURFACES
3.3.1 New Ferrous Surfaces
a. Ferrous Surfaces including Shop-coated Surfaces and Small Areas That Contain Rust, Mill Scale and Other Foreign Substances: Solvent clean or detergent wash in accordance with SSPC SP 1 to remove oil and grease. Where shop coat is missing or damaged, clean according to SSPC SP 2 , SSPC SP 3 , SSPC SP 6/NACE No.3 , or SSPC SP 10/NACE No. 2 .
Protect shop-coated ferrous surfaces from corrosion by treating and touching up corroded areas immediately upon detection.
b. Surfaces With More Than 20 Percent Rust, Mill Scale, and Other Foreign Substances: Clean entire surface in accordance with SSPC SP 6/NACE No.3 / SSPC-SP WJ-3/NACE WJ-3 .
3.3.2 Final Ferrous Surface Condition:
3.3.2.1 Tool Cleaned Surfaces
Comply with SSPC SP 2 and SSPC SP 3 . Use as a visual reference, photographs in SSPC VIS 3 for the appearance of cleaned surfaces.
SECTION 09 90 00 Page 11
3.3.3 Galvanized Surfaces
a. New Galvanized Surfaces With Only Dirt and Zinc Oxidation Products:
Clean with solvent, or non-alkaline detergent solution in accordance with SSPC SP 1 . Completely remove coating by brush-off abrasive blast if the galvanized metal has been passivated or stabilized. Do not "passivate" or "stabilize" new galvanized steel to be coated. If the absence of hexavalent stain inhibitors is not documented, test as described in ASTM D6386, Appendix X2, and remove by one of the methods described therein.
3.3.4 Non-Ferrous Metallic Surfaces
Aluminum and aluminum-alloy, lead, copper, and other nonferrous metal surfaces.
Surface Cleaning: Solvent clean in accordance with SSPC SP 1 and wash with mild non-alkaline detergent to remove dirt and water soluble contaminants.
3.3.5 Terne-Coated Metal Surfaces
Solvent clean surfaces with mineral spirits, ASTM D235. Wipe dry with clean, dry cloths.
3.4 APPLICATION
3.4.1 Coating Application
a. Comply with applicable federal, state and local laws enacted to ensure compliance with Federal Clean Air Standards. Apply coating materials in accordance with SSPC PA 1 . SSPC PA 1 methods are applicable to all substrates, except as modified herein.
b. At the time of application, paint must show no signs of deterioration. Maintain uniform suspension of pigments during application.
c. Unless otherwise specified or recommended by the paint manufacturer, paint may be applied by brush, roller, or spray. Use trigger operated spray nozzles for water hoses. Use rollers for applying paints and enamels of a type designed for the coating to be applied and the surface to be coated. Wear protective clothing and respirators when applying oil-based paints or using spray equipment with any paints.
d. Only apply paints, except water-thinned types, to surfaces that are completely free of moisture as determined by sight or touch.
e. Thoroughly work coating materials into joints, crevices, and open spaces. Pay special attention to ensure that all edges, corners, crevices, welds, and rivets receive a film thickness equal to that of adjacent painted surfaces.
f. Apply each coat of paint so that dry film is of uniform thickness and free from runs, drops, ridges, waves, pinholes or other voids, laps, brush marks, and variations in color, texture, and finish. Completely hide all blemishes.
g. Touch up damaged coatings before applying subsequent coats. Broom
SECTION 09 90 00 Page 12 clean and clear dust from interior areas before and during the application of coating material.
h. Piping in Finished Areas: Provide primed surfaces with two coats of paint to match adjacent surfaces, except provide valves and operating accessories with one coat of red alkyd gloss enamel ( MPI 9 ) applied to a minimum dry film thickness of 1.0 mil or two component gloss polyurethane ( MPI 72 ) in exterior applications.
i. Primers, and Intermediate Coats: Do not allow primers or intermediate coats to dry more than 30 days, or longer than recommended by manufacturer, before applying subsequent coats. Follow manufacturer's recommendations for surface preparation if primers or intermediate coats are allowed to dry longer than recommended by manufacturers of subsequent coatings. Cover each preceding coat or surface completely by ensuring visually perceptible difference in shades of successive coats.
j. Finished Surfaces: Provide finished surfaces free from runs, drops, ridges, waves, laps, brush marks, and variations in colors.
3.4.2 Mixing and Thinning of Paints
Reduce paints to proper consistency by adding fresh paint, except when thinning is mandatory to suit surface, temperature, weather conditions, application methods, or for the type of paint being used. Obtain written permission from the Contracting Officer to use thinners. Verify that the written permission includes quantities and types of thinners to use.
When thinning is allowed, thin paints immediately prior to application with not more than one pint of suitable thinner per gallon. The use of thinner does not relieve the Contractor from obtaining complete hiding, full film thickness, or required gloss. Thinning cannot cause the paint to exceed limits on volatile organic compounds. Do not mix paints of different manufacturers.
3.4.3 Coating Systems
a. Systems by Substrates: Apply coatings that conform to the respective specifications listed in the following Tables:
Table for Exterior Applications
MPI Division Substrate Application
MPI Division 5 Exterior Metal, Ferrous and Non-Ferrous Paint Table
Table for Interior Applications
MPI Division Substrate Application
MPI Division 5 Interior Metal, Ferrous and Non-Ferrous Paint Table
b. Minimum Dry Film Thickness (DFT): Apply paints, primers, varnishes, enamels, undercoats, and other coatings to a minimum dry film thickness of 1.5 mil each coat unless specified otherwise in the Tables. Coating thickness, where specified, refers to the minimum dry
SECTION 09 90 00 Page 13 film thickness.
c. Coatings for Surfaces Not Specified Otherwise: Coat unspecified surfaces the same as surfaces having similar conditions of exposure.
d. Existing Surfaces Damaged During Performance of the Work, Including New Patches In Existing Surfaces: Coat surfaces with the following:
(1) One coat of primer.
(2) One coat of undercoat or intermediate coat.
(3) One topcoat to match adjacent surfaces.
3.5 COATING SYSTEMS FOR METAL
Apply coatings of Tables in MPI Division 5 for Exterior and Interior.
a. Apply specified ferrous metal primer to steel surfaces on the same day that surface is cleaned, to surfaces that meet all specified surface preparation requirements at time of application.
b. Inaccessible Surfaces: Prior to erection, use one coat of specified primer on metal surfaces that will be inaccessible after erection.
c. Shop-primed Surfaces: Touch up exposed substrates and damaged coatings to protect from rusting prior to applying field primer.
d. Surface Previously Coated with Epoxy or Urethane: Apply MPI 101 , 1.5 mils DFT immediately prior to application of epoxy or urethane coatings.
e. Pipes and Tubing: The semitransparent film applied to some pipes and tubing at the mill is not to be considered a shop coat. Overcoat these items with the specified ferrous-metal primer prior to application of finish coats.
f. Exposed Nails, Screws, Fasteners, and Miscellaneous Ferrous Surfaces.
On surfaces to be coated with water thinned coatings, spot prime exposed nails and other ferrous metal with latex primer MPI 107 .
3.6 COATING SYSTEMS FOR CONCRETE AND CEMENTITIOUS SUBSTRATES
Apply coatings of Tables in MPI Division 3, 4 and 9 for Exterior and Interior.
3.7 PIPING IDENTIFICATION
Piping Identification, Including Surfaces In Concealed Spaces: Provide in accordance with MIL-STD-101 . Place stenciling in clearly visible locations. On piping not covered by MIL-STD-101 , stencil approved names or code letters, in letters a minimum of 1/2 inch high for piping and a minimum of 2 inches high elsewhere. Stencil arrow-shaped markings on piping to indicate direction of flow using black stencil paint.
3.8 INSPECTION AND ACCEPTANCE
In addition to meeting previously specified requirements, demonstrate mobility of moving components, including swinging and sliding doors, SECTION 09 90 00 Page 14 cabinets, and windows with operable sash, for inspection by the Contracting Officer. Perform this demonstration after appropriate curing and drying times of coatings have elapsed and prior to invoicing for final payment.
3.9 WASTE MANAGEMENT
As specified in the Waste Management Plan and as follows. Do not use kerosene or any such organic solvents to clean up water based paints.
Properly dispose of paints or solvents in designated containers. Close and seal partially used containers of paint to maintain quality as necessary for reuse. Store in protected, well-ventilated, fire-safe area at moderate temperature. Place materials defined as hazardous or toxic waste in designated containers.
3.10 PAINT TABLES
All DFT's are minimum values. Use only materials with a MPI GPS-1-14 green check mark having a minimum MPI "Environmentally Friendly" E1 rating based on VOC ( EPA Method 24 ) content levels. Acceptable products are listed in the MPI Green Approved Products List, available at https://www.mpi.net/APL/index.asp .
3.10.1 Exterior Paint Tables
3.10.1.1 MPI Division 5: Exterior Metal, Ferrous and Non-Ferrous Paint Table
A. Steel / Ferrous Surfaces
(1) New Steel that has been hand or power tool cleaned to SSPC SP 2 or
SSPC SP 3
Alkyd
New Existing, uncoated Primer Intermediate Topcoat System DFT
MPI EXT 5.1Q-G5
(Semigloss
MPI REX 5.1D-G5
(Semigloss)
MPI 23 MPI 94 MPI 94 5.25 mils
Topcoat: Coating to match adjacent surfaces.
(2) New Steel that has been blast-cleaned to SSPC SP 6/NACE No.3
Alkyd
New Existing, uncoated Primer Intermediate Topcoat System DFT
MPI EXT 5.1D-G5
(Semigloss)
MPI REX 5.1D-G5
(Semigloss)
MPI 79 MPI 94 MPI 94 5.25 mils
Topcoat: Coating to match adjacent surfaces.
B. Exterior Galvanized Surfaces
SECTION 09 90 00 Page 15
(1) New Galvanized surfaces
Waterborne Primer / Waterborne Light Industrial Coating
New Galvanized Surfaces
Primer Intermediate Topcoat System DFT
MPI EXT 5.3J-G5
(Semigloss)
MPI 134 MPI 163 MPI 163 4.5 mils
Topcoat: Coating to match adjacent surfaces.
C. Exterior Surfaces, Other Metals (Non-Ferrous)
(1) Aluminum, aluminum alloy and other miscellaneous non-ferrous metal items not otherwise specified except hot metal surfaces, roof surfaces, and new prefinished equipment
Waterborne Light Industrial Coating
New Galvanized Surfaces
Primer Intermediate Topcoat System DFT
MPI EXT 5.4F-G5
(Semigloss)
MPI 95 MPI 163 MPI 163 5 mils
Topcoat: Coating to match adjacent surfaces.
3.10.2 Interior Paint Tables
3.10.2.1 MPI Division 5: Interior Metal, Ferrous and Non-Ferrous Paint Table
A. Interior Steel / Ferrous Surfaces
(1) Metal, Mechanical, Electrical, Surfaces adjacent to painted surfaces (Match surrounding finish), and miscellaneous metal items not otherwise specified except floors, hot metal surfaces, and new prefinished equipment
High Performance Architectural Latex
New, uncoated Existing Primer Intermediate Topcoat System DFT
MPI INT 5.1R-G5
(Semigloss)
MPI 76 MPI 141 MPI 141
5 mils
Topcoat: Coating to match adjacent surfaces.
(2) Miscellaneous non-ferrous metal items not otherwise specified except floors, hot metal surfaces, and new prefinished equipment. Match surrounding finish
SECTION 09 90 00 Page 16
High Performance Architectural Latex
New, uncoated Existing Primer Intermediate Topcoat System DFT
MPI INT 5.4F-G5
(Semigloss)
MPI 95 MPI 141 MPI 141
5 mils
Topcoat: Coating to match adjacent surfaces.
-- End of Section --
SECTION 09 90 00 Page 17
THIS PAGE INTENTIONALLY LEFT BLANK
SECTION 09 90 00 Page 18
| 09 90 00 - PAINTS AND COATINGS |
| PART 1 GENERAL |
| 1.1 RELATED REQUIREMENTS |
| 1.1.1 Painting Included |
| 1.1.1.1 Exterior Painting |
| 1.1.1.2 Interior Painting |
| 1.1.2 Painting Excluded |
| 1.1.3 Mechanical and Electrical Painting |
| 1.1.4 Exterior Painting of Site Work Items |
| 1.2 REFERENCES |
| 1.3 DEFINITIONS |
| 1.3.1 Qualification Testing |
| 1.3.2 Batch Quality Conformance Testing |
| 1.3.3 Coating |
| 1.3.4 DFT or dft |
| 1.3.5 DSD |
| 1.3.6 EXT |
| 1.3.7 INT |
| 1.3.8 Loose Paint |
| 1.3.9 mil / mils |
| 1.3.10 MPI Gloss Levels |
| 1.3.11 MPI System Number |
| 1.3.12 Paint |
| 1.3.13 REX |
| 1.3.14 RIN |
| 1.4 SCHEDULING |
| 1.5 SUBMITTALS |
| 1.6 QUALITY ASSURANCE |
| 1.6.1 Regulatory Requirements |
| 1.6.1.1 Environmental Protection |
| 1.6.1.2 Lead Content |
| 1.6.1.3 Chromate Content |
| 1.6.1.4 Asbestos Content |
| 1.6.1.5 Mercury Content |
| 1.6.1.6 Silica |
| 1.6.1.7 Human Carcinogens |
| 1.6.1.8 Carbon Based Fibers / Tubes |
| 1.6.2 SSPC QP 1 Certification |
| 1.6.3 Approved Products List |
| 1.6.4 Paints and Coatings Indoor Air Quality Certifications |
| 1.6.5 Field Samples and Tests |
| 1.6.5.1 Sampling Procedure |
| 1.6.5.2 Testing Procedure |
| 1.7 PACKAGING, LABELING, AND STORAGE |
| 1.8 SAFETY AND HEALTH |
| 1.8.1 Toxic Materials |
| 1.9 ENVIRONMENTAL REQUIREMENTS |
| 1.9.1 Coatings |
| 1.9.2 Post-Application |
| PART 2 PRODUCTS |
| 2.1 MATERIALS |
| 2.2 COLOR SELECTION OF FINISH COATS |
| PART 3 EXECUTION |
| 3.1 PROTECTION OF AREAS AND SPACES NOT TO BE PAINTED |
| 3.2 SURFACE PREPARATION |
| 3.3 PREPARATION OF METAL SURFACES |
| 3.3.1 New Ferrous Surfaces |
| 3.3.2 Final Ferrous Surface Condition: |
| 3.3.2.1 Tool Cleaned Surfaces |
| 3.3.3 Galvanized Surfaces |
| 3.3.4 Non-Ferrous Metallic Surfaces |
| 3.3.5 Terne-Coated Metal Surfaces |
| 3.4 APPLICATION |
| 3.4.1 Coating Application |
| 3.4.2 Mixing and Thinning of Paints |
| 3.4.3 Coating Systems |
| 3.5 COATING SYSTEMS FOR METAL |
| 3.6 COATING SYSTEMS FOR CONCRETE AND CEMENTITIOUS SUBSTRATES |
| 3.7 PIPING IDENTIFICATION |
| 3.8 INSPECTION AND ACCEPTANCE |
| 3.9 WASTE MANAGEMENT |
| 3.10 PAINT TABLES |
| 3.10.1 Exterior Paint Tables |
| 3.10.1.1 MPI Division 5: Exterior Metal, Ferrous and Non-Ferrous Paint |
| 3.10.2 Interior Paint Tables |
| 3.10.2.1 MPI Division 5: Interior Metal, Ferrous and Non-Ferrous Paint |