ATCH 3 - Partial Generator List.xlsx
XLSX spreadsheet 19 KB Posted
- Attached to
- Generator Maintenance Services
- Solicitation number
- FA558727MR001
About this file
This file is a partial generator inventory list maintained by the requesting organization at Royal Air Force (RAF) Lakenheath and RAF Feltwell. The spreadsheet catalogs backup generators across two locations (RPIE and POL classifications) with detailed technical specifications and maintenance records for each unit. The inventory includes 16 generators ranging from 10 KW to 580 KW in capacity, manufactured between 1986 and 2019 by various suppliers including Caterpillar, Cummins, Perkins, FG Wilson, Olympian, Kohler, and Volvo Penta. Each generator entry documents voltage ratings (primarily 240/415V or 230/400V three-phase configurations), current maximum demand loads ranging from 15% to 98%, cumulative run-time hours, alternator specifications, engine models, fuel type (all diesel), and automatic transfer switch (ATS) configurations.
Maintenance frequency for the RPIE emergency generators is documented as semi-monthly, monthly, or semi-annually intervals, while the POL generators operate on monthly, quarterly, or annual maintenance schedules. The data captures critical operational metrics including unit serial numbers, manufacturer stock numbers, and alternator/engine make and model information necessary for parts procurement and service planning. This generator list serves as the baseline equipment inventory for the market research presolicitation (FA558727MR001) issued by the 48th Contracting Squadron seeking vendor capabilities to provide comprehensive backup generator maintenance and routine repair services at both RAF locations.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| SSN FA558727MR001 - Generator Maintenance Services.pdf | ||
| ATCH 2 - UFC 3-540-07.pdf | ||
| ATCH 4 - SSNQ.docx | DOCX document | |
| ATCH 1 - PWS Excerpt.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1
| Classification of Generator | Frequency of Maintenance | KW | Voltage | Phase | RPIE / EAID | Generator Unit Manufacturer | Stock Number | Unit Serial Number | Maximum Demand Load (KW) | Maximum Demand Load (%) | Year | |
| Mfg | Cumulative Run Time Hours | Alternator Make | Alternator Model | Engine Make | Engine Model | Type of Fuel | Auto Transfer Switch Make | Auto Transfer Switch Model | 3 / 4 Pole ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 24 | 240/415 | 3 | RPIE | Perkins | 6115-XX-XXXX | OLY00000HRPT03567 | 10.8 | 45% | 2004 | 224.7 | Olympian | LL1014Q | Perkins | CM51035 | DIESEL | MEM | 43587 | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 26 | 230/400 | 3 | RPIE | Caterpillar | 6115-XX-XXXX | CAT00C33EGF201780 | 15.5 | 59% | 2019 | 101.6 | Caterpillar | LC1514F | Caterpillar | C3.3 | DIESEL | CTI | CTI63 | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 26 | 230/400 | 3 | RPIE | Caterpillar | 6115-XX-XXXX | CAT00C33LGT200271 | 14.3 | 55% | 2015 | 190.3 | Caterpillar | LMF00734 | Caterpillar | C3.3 | DIESEL | Olympian | CTI 100 | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 24 | 240/416 | 3 | RPIE | FG Wilson | 6115-XX-XXXX | FGWPEP03JD0A05757 | 15.0 | 63% | 2002 | 452.66 | FG Wilson | LL2014B | Perkins | AG51041 | DIESEL | Rand | 45879 | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 120 | 240/415 | 3 | RPIE | Olympian | 6115-XX-XXXX | OLY00000CLEH00860 | 18.0 | 15% | 2013 | 164.2 | Olympian | LL3014F | Perkins | GEP150-4 | DIESEL | Olympian | ATI250 | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 580 | 230/400 | 3 | RPIE | Cummins | 6115-XX-XXXX | J04K486830 | 460.0 | 55% | 2004 | 483 | Cummins | A041286779 | Cummins | QST30-G1 | DIESEL | TyCo Electronic | Z3D4K25HIAAA-07 | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 168 | 240/415 | 3 | RPIE | Auto-Diesels | 6115-XX-XXXX | 87390101 | 75.6 | 45% | 1992 | 691.06 | Stamford | UC1274H14 | Volvo-Penta | TMD1010G | DIESEL | Auto-Diesels | 1/1/39 | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 100 | 120/240 | 3 | RPIE | Kohler | 6115-XX-XXXX | PE4045L0892 | 30.0 | 30% | 2009 | 4466.3 | Kohler | 100REOZJD | John Deer | 100RE02JD | DIESEL | Kohler | *********** | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 302 | 240/416 | 3 | RPIE | Perkins | 6115-XX-XXXX | FGB061105U3342K | 45.3 | 15% | 2003 | 325.9 | Morelli Motori | M8B315SB4 | Perkins | 2306CE14RAG2 | DIESEL | Merlin Gerin | 03/1789971 | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 45 | 240/415 | 3 | RPIE | FG Wilson | 6115-XX-XXXX | GABL002611 | 15.8 | 35% | 2001 | 569.4 | FG Wilson | LL2014D | Perkins | AG50757 | DIESEL | RAND | ATY220i | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 280 | 240/415 | 3 | RPIE | Volvo-Pen | 6115-XX-XXXX | W01481-20 | 47.6 | 17% | 2002 | 419.59 | Partner | 471M4C6/4 | Volvo | TWD1211G | DIESEL | Witham Power Engineering | NG242DX | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 10 | 240/415 | 3 | RPIE | Olympian | 6115-XX-XXXX | FAFL001114 | 4.5 | 45% | 2000 | 327.5 | Olympian | LA1014H | Lister | LPW3A | DIESEL | TC | 01078EF | 4 ATS |
| RPIE Emergency | Semi-Monthly, Monthly, Semi-Annually | 24 | 240/416 | 3 | RPIE | SDMD | 6115-XX-XXXX | TM30K | 3.8 | 16% | 2000 | 1333.59 | Panther | 42.2L9C6/4 | SDMO | TM30K | DIESEL | SDMD | AVP93052 | 4 ATS |
| POL RPIE | Monthly, Quarterly, Annually | 83 | 240/416 | 3 | RPIE | Libby | 6115-01-296-1463 | RZ01912 | 81.5 | 98% | 1986 | 180.8 | Military Design | 70-4001 | Caterpillar | 3306 | DIESEL | *********** | ************* | 4 MTS |
| POL RPIE | Monthly, Quarterly, Annually | 200 | 240/416 | 3 | RPIE | Volvo-Pen | 6115-XX-XXXX | 44615 | 63.0 | 32% | 2004 | 159.5 | Marclli Motori | M8B250LB4 | Volvo Penta | TAD740GE | DIESEL | Volvo-Pen | 44615 | 4 ATS |
DRAFT
File details come from the government source that posted it. Updated .