Atch 3 Drawings 614-23-103 Replace Old Roofing Buildings 1 1A 5 and 7.pdf

PDF 15 MB Posted

Attached to
Z2DA--614-23-103 - Replace Old Roofing Buildings 1, 1A, 5 & 7
Solicitation number
36C24926R0044
Issued by

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

N

VICINITY MAP

SCALE: N.T.S.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

N

LOCATION MAP

SCALE: N.T.S.

PROJECT LOCATION:

MEMPHIS VA MEDICAL CENTER

MEMPHIS, TN.

PROJECT LOCATION:

MEMPHIS VA MEDICAL CENTER

MEMPHIS, TN.

REPLACE ROOF BLDG 1, 1A, 5 & 7

Department of Veterans Affairs

REVISED BID SET SUBMISSION

DECEMBER 30, 2024

PROJECT # 614-23-103

MEMPHIS VA MEDICAL CENTER,

1030 JEFFERSON AVENUE MEMPHIS, TN, 38104

COVER SHEET

GI-001

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

AB, DRJ, CFAB

35% SUBMISSION 05 JUNE, 2023

30 DEC 2024

DWG NO DRAWING TITLE

GI-002 GENERAL INFORMATION

AD-101 BUILDING 1 - DEMOLITION ROOF PLAN

GI-001 COVER SHEET

GI-003 GENERAL NOTES

A SEPARATE PROJECT MANUAL (SPECIFICATIONS) IS:

INCLUDED

NOT INCLUDED

AS PART OF THIS PROJECT.

INDEX

AD-102

AD-103

AD-104 BUILDING 1 CONNECTING CORRIDORS & DOCK CANOPY, AND BLDG 1A PENTHOUSE - DEMOLITION ROOF PLAN

BUILDING 1A SECOND FLOOR PATIO ROOF - DEMOLITION ROOF PLAN

BUILDING 1A GENERATOR - DEMOLITION ROOF PLAN

REV. BID SET SUBMISSION

AD-105

AD-106 BUILDING 7 - DEMOLITION ROOF PLAN

AS-101 BUILDING 1 - NEW ROOF PLAN

AS-102

AS-103

AS-104

BUILDING 1A SECOND FLOOR PATIO ROOF - NEW ROOF PLAN

BUILDING 1A GENERATOR - NEW ROOF PLAN

AS-105 BUILDING 5 & COOLING TOWER EQUIPMENT ROOM - NEW ROOF PLAN

AS-106 BUILDING 7 - NEW ROOF PLAN

65% SUBMISSION 15 AUGUST, 2023

AS-501 ROOF DETAILS

AS-502 ROOF DETAILS

AS-503 ROOF DETAILS

AS-504 ROOF DETAILS

AS-505 ROOF DETAILS

95% SUBMISSION 12 DECEMBER, 2023

S-101 BUILDING 1 - WIND ZONE ROOF PLAN

S-102

S-103

S-104

BUILDING 1A SECOND FLOOR PATIO ROOF - WIND ZONE ROOF PLAN

BUILDING 1A GENERATOR - WIND ZONE ROOF PLAN

S-105 BUILDING 5 & COOLING TOWER EQUIPMENT ROOM - WIND ZONE ROOF PLAN

S-106 BUILDING 7 - WIND ZONE ROOF PLAN

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

BUILDING 1 CONNECTING CORRIDORS & DOCK CANOPY, AND BLDG 1A PENTHOUSE - NEW ROOF PLAN

BUILDING 1 CONNECTING CORRIDORS & DOCK CANOPY, AND BLDG 1A PENTHOUSE - WIND ZONE ROOF PLAN

BUILDING 5 & COOLING TOWER EQUIPMENT ROOM - DEMOLITION ROOF PLAN

100% SUBMISSION 8 APRIL, 2024

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

EARTH

CONCRETE MASONRY

CONCRETE

COMPRESSIBLE FILLER

PORTLAND CEMENT

PLASTER OVER METAL LATH

UNIT

PORTLAND

BATT INSULATION

ROOF GYPSUM COVER BOARD

LWIC-LIGHT WEIGHT INSULATED CONCRETE

MEMBERFINISH SYSTEM

PLYWOOD

WOOD BLOCKING

CONTINUOUS WOOD

FINISHED WOOD MEMBER

EXTERIOR INSULATION &

GLASS

GYPSUM BOARD

POLYISOCYANURATE

METAL

A-611

4 2

A-611

MATERIALS LEGEND

SYMBOLS

CEMENT PLASTER

CODE INFORMATION

SECTIONS

TONGUE & GROOVE

HOLLOW METAL

MAX MAXIMUM

INSUL

HM

INSULATION

WOOD

VENT THRU ROOF

TOP OF STEEL

WD

W/ W/O

WITH

WITHOUT

VTR

TYP

TOS

TYPICAL

CONDENSING UNITCU

EXPANSIONEXP

FIELD JOINT

FLASHING

GALVANIZED

GA

GALV

GAUGE

FLASH'G

FIN

FL

FP

FJ

EXST'G

FINISH

FLOOR

EXISTING

FIREPROOF

DIAMETER

DOWN SPOUT

EXPANSION JOINT

DS

EJ

EWC ELECTRIC WATER COOLER

DN

DIA

DOWN

AT

CONCRETE MASONRY UNIT

ABOVE FINISHED FLOOR

ACOUSTICAL CEILING TILE or ACOUSTICAL TREATMENT

AIR CONDITIONING

CONTROL JOINT

CONCRETE

CONTINUOUS

CLG

COL

CONC

CONT

CMU

CJ

BLDG

CEILING

COLUMN

BUILDING

AFF

ACT

A/C

SUSPENDED CEILING

TOP OF MASONRY

STAINLESS STEEL

SQUARE

THICK

TREATED

TOM

TREAT'D

THK

SQ

SUSP. CLG.

REQD REQUIRED

PLASTIC LAMINATE

ROOF DRAIN

RAD

RD

RADIUS

PLYWD

PLAS. LAM.

PL

PLYWOOD

PLATE

OPENING

MECHANICAL

NOT IN CONTRACT

ON CENTER

OPEN'G(OPN'G)

OC

NIC

MIN

MECH

MINIMUM

ABBREVIATIONS

METALMTL

ELEVATIONEL

MASONRY OPENINGMO

BOARDBD

BLK BLOCK

BLK'G BLOCKING

BUR BUILD UP ROOFING

CENTER LINECL

DRAWINGDWG

GLASSGL

JT JOINT

LAVATORYLAV

NOT APPLICABLENA

STEELSTL

VIF VERIFY IN FIELD

PRESSURE TREATEDPT

SUSPENDED ACOUSTICAL TILESAT

LAMINATELAM

LOW POINTLP

SS

SCALE:

TITLE

############ A-501

MODIFIED BITUMEN SYSTEM

COMPONENT AND CLADDING WIND

UPLIFT PRESSURES

ROOF DRAINAGE CALCULATION

REFER TO SHEETS S-101 - S-106 FOR WIND ZONE ROOF PLANS:

S-101 - BUILDING 1 - WIND ZONE ROOF PLAN

S-102 - BUILDING 1 GENERATOR BLDG AND LOW ROOF - WIND ZONE ROOF PLAN

S-103 - BUILDING 1A PATIO ROOF - WIND ZONE ROOF PLAN

S-104 - BUILDING 1A PENTOUSE, CORRIDORS & DOCK CANOPY - WIND ZONE ROOF PLAN

S-105 - BULDING 5.1-5.4 & COOLING TOWER - WIND ZONE ROOF PLAN

S-106 - BUILDING 7 - WIND ZONE ROOF PLAN

CODE: ASCE 7-10; IBC 2012

ROOF AREA DIMENSIONS (FEET): REFER ROOF PLAN

MEAN ROOF HEIGHT: 115' (BUILDING 1A PENTHOUSE), 90' (ALL ROOF AREAS EXCEPT COOLING TOWER AND BUILDING 1A

MECHANICAL PENTHOUSE), 15' (COOLING TOWER)

RISK CATEGORY: IV

EXPOSURE CATEGORY: C

BASIC WIND SPEED (THREE-SECOND PEAK GUST, MPH): 120 MPH

TABLE HEIGHT

ZONE H= 90'-0"

LRFD

ASD*

* ROOFING CONTRACTOR SHALL INSTALL A TESTED ROOF ASSEMBLY TO MEET OR EXCEED ASD

PRESSURES WITH A SAFTEY FACTOR OF 2.

LOAD TYPE

-44.95 PSF

-65.69 PSF

-86.44 PSF

-33.42 PSF

-54.17 PSF

-74.91 PSF

-109.48 PSF

-144.06 PSF

-55.70 PSF

-90.28 PSF

H= 115'-0"

-47.33 PSF

-69.17 PSF

-91.01 PSF

-35.19 PSF

-57.03 PSF

-78.88 PSF

-115.28 PSF

-151.68 PSF

-58.65 PSF

-95.05 PSF

H= 15'-0"

-24.02 PSF

-33.81 PSF

-44.86 PSF

-23.59 PSF

-27.10 PSF

-40.03 PSF

-56.35 PSF

-74.76 PSF

-39.31 PSF

-45.16 PSF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

GI-002

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

GENERAL INFORMATION

AB AB, DRJ, CF

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

30 DEC 2024

REV. BID SET SUBMISSION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

GI-003

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

GENERAL NOTES

CF, AB, DRJ

ROOF DEMOLITION NOTES

GENERAL CONSTRUCTION NOTES

GENERAL SCOPE OF WORK

PROTECTION NOTES

GENERAL NOTES

SCALE: N.T.S.1 SITE PLAN - SCOPE OF WORK

AB

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

DEDUCT ALTERNATES

PRD

PRD PRD

PRD

PRD

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

SVP

SVP

SVP

SVP

ENTRANCE VESTIBULE 1

DS

G

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AD-101

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1 - DEMOLITION ROOF PLAN

BUILDING 1 - DEMOLITION ROOF PLAN 1 SCALE: 1/16" : 1'-0"

KEYPLAN

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET GUTTER (GU)

SOIL VENT PIPE (SVP)

DOWNSPOUT (DS)

TEST CUT1

WATER FLOWPRIMAY ROOF DRAIN (PRD)

ROOF-TO-WALL

EXPANSION JOINT

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.)

ROOF-TO-ROOF

EXPANSION JOINTSKYLIGHT (S)S

ELEVATION CHANGE

LIGHTINING ROD

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

EXISTING ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

STRUCTURAL

DECK

VAPOR

RETARDER INSULATION COVER

BOARD

ROOF

MEMBRANE SURFACING COMMENTS

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

CO

AL

T

AR

P

IT

CH

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

PE

RL

IT

E

BU

ILT

-U P

RO

OF

AG

GR

EG

AT

E

SU

RF

AC

IN

G

ENTRANCE

VESTIBULE 1 ● - - ● ● ● X3/AS-501

ENTRANCE

VESTIBULE 2 ● - - - - - X6/AS-501

ROOF OVER THEATER ● ● ● ● ● ● X2/AS-501

AMBULATORY CARE

MECHANICAL

PENTHOUSE ● - ● ● ● ● X1/AS-501

SPECIFIC ROOF DEMOLITION NOTES

25'-5"±

45'-3"±

9'-3"±

10'-7"± 23'-2"±

6'±

27'-2"±

44'±

67'-4"±

42'-2"±

27'-1"±

23'-7"±

24'-6"±

23'-3"±

5'-4"±

CF, AB, DRJAB

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

EXISTING FALL

PROTECTION

NOT IN SCOPE

NOT IN SCOPE

PRD PRD

PRD

PRD

PRD PRD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AD-102

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1A GENERATOR - DEMOLITION ROOF PLAN1 SCALE: 3/32" : 1'-0"

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET

PRIMARY SCUPPER (PS)

GUTTER (GU)

TAPERED INSULATION

STRUCTURAL RIDGE/HIP

SOIL VENT PIPE (SVP)

OVERFLOW ROOF DRAIN

(ORD)

DOWNSPOUT (DS)

VALLEY

TEST CUT1

WATER FLOW

FALL PROTECTION DAVIT

(FPD)

PRIMAY ROOF DRAIN (PRD)

LIGHTNING PROTECTION

PITCH POCKET (LPS)

PITCH POCKET (PP)

FALL PROTECTION

ANCHOR (FPA)

ROOF-TO-WALL

EXPANSION JOINT

FALL PROTECTION

CABLE (FPC)

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.) WIND ZONE NO. 1

WIND ZONE NO. 3 WIND ZONE NO. 2

ROOF-TO-ROOF

EXPANSION JOINT

OVERFLOW SCUPPER

(OS)

EXHAUST FAN (EF) HEATED VENT STACK

(HVS)

SKYLIGHT (S)S ROOF ACCESS - LADDER

ROOF HATCH ROOF WALKWAY PAD

CONTROL JOINT

ELEVATION CHANGE

KEYPLAN

LIGHTINING ROD

EXISTING ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

STRUCTURAL

DECK INSULATION COVERB

OARD

ROOF

MEMBR

ANE

RECOVER

BOARD

RECOVER

MEMBRANE SURFACING COMMENTS

FL

AT

M

ET

AL

D

EC

K

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

PE

RL

IT

E

MU

LT

I-P

LY

B

UI

LT

U

P

RO

OF

PE

RL

IT

E

MU

LT

I-P

LY

B

UR

GR

AN

UL

ES

GENERATOR

BUILDING ● ● ● ● ● ● ● X7/AS-501

BUILDING 1A GENERATOR - DEMOLITION

ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

8'-11"±

44'-5"±

38'-4"±

12'-11"±

29'-7"±

37'-9"±

15'-6"±

66'-7"±

34'-10"±

1'-11"±

35'-2"±

13'-6"± 1'-9"± 67'-5"±

61'-7"±

12'-1"±

21'-9"±

8'-9"±

9'±

11'-3"±

7'-8"±

106'-4"±

SPECIFIC ROOF DEMOLITION NOTES

CF, AB, DRJAB

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

EXISTING FALL

PROTECTION

NOT IN SCOPE

TPO ROOF TO REMAIN

PATIO ROOF 2

PATIO ROOF 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AD-103

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1A, SECOND FLOOR PATIO ROOFS - DEMOLITION ROOF PLAN1 SCALE: 3/32" : 1'-0"

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET GUTTER (GU)

SOIL VENT PIPE (SVP)

DOWNSPOUT (DS)

TEST CUT1

WATER FLOWPRIMAY ROOF DRAIN (PRD)

ROOF-TO-WALL

EXPANSION JOINT

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.)

ROOF-TO-ROOF

EXPANSION JOINTSKYLIGHT (S)S

ELEVATION CHANGE

KEYPLAN

LIGHTINING ROD

BUILDING 1A, SECOND FLOOR PATIO

ROOF - DEMOLITION ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

26'-2"±

61'±

72'-6"±

14'-5"±

33'-10"±

39'-2"±

32'-11"±

46'-9"±

11'-5"±

EXISTING ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

STRUCTURAL

DECK

ROOF

MEMBRANE PAVERS COMMENTS

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

BU

ILT

-U P

RO

OF

PE

DE

ST

AL

S

PA

VE

RS

BLDG 1A PATIO

ROOFS ● ● ● X5/AS-501

SPECIFIC ROOF DEMOLITION NOTES

CF, AB, DRJAB

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

PRD

PRD

PRD PRD

DS

DS

AN

PRD

PRD

PRD

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AD-104

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1, CONNECTING CORRIDORS - DEMOLITION ROOF PLAN1 SCALE: 1/8" : 1'-0"

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET

PRIMARY SCUPPER (PS)

GUTTER (GU)

TAPERED INSULATION

STRUCTURAL RIDGE/HIP

SOIL VENT PIPE (SVP)

OVERFLOW ROOF DRAIN

(ORD)

DOWNSPOUT (DS)

VALLEY

TEST CUT1

WATER FLOW

FALL PROTECTION DAVIT

(FPD)

PRIMAY ROOF DRAIN (PRD)

LIGHTNING PROTECTION

PITCH POCKET (LPS)

PITCH POCKET (PP)

FALL PROTECTION

ANCHOR (FPA)

ROOF-TO-WALL

EXPANSION JOINT

FALL PROTECTION

CABLE (FPC)

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.) WIND ZONE NO. 1

WIND ZONE NO. 3 WIND ZONE NO. 2

ROOF-TO-ROOF

EXPANSION JOINT

OVERFLOW SCUPPER

(OS)

EXHAUST FAN (EF) HEATED VENT STACK

(HVS)

SKYLIGHT (S)S ROOF ACCESS - LADDER

ROOF HATCH ROOF WALKWAY PAD

CONTROL JOINT

ELEVATION CHANGE

KEYPLAN

LIGHTINING ROD

EXISTING ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

DECK INSULATION COVER BOARD ROOF

MEMBRANE SURFACING COMMENTS

FL

AT

M

ET

AL

D

EC

K

TA

PE

RE

D

LIG

HT

W

EI

GH

T

CO

NC

RE

TE

O

VE

R

FL

AT

M

ET

AL

DE

CK

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

DE

CK

FL

AT

P

OL

YI

SO

CY

AN

UR

AT

E

TA

PE

RE

D

PE

RL

IT

E

FL

AT

P

ER

LIT

E

BU

ILT

-U P

RO

OF

GR

AN

UL

E

SU

RF

AC

IN

G

CONNECTING

CORRIDOR 1 ● - - ● ● - ● ● X8/AS-501

CONNECTING

CORRIDOR 2 - ● - - - ● ● ● X9/AS-501

DOCK CANOPY - - ● - - - - - X6/AS-501

BUILDING 1A

PENTHOUSE ● - - ● ● - ● ● X8/AS-501

SPECIFIC ROOF DEMOLITION NOTES

BUILDING 1 CONNECTING CORRIDORS,

DOCK CANOPY, & BLDG 1A PENTHOUSE -

DEMOLITION ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

BUILDING 1A, PENTHOUSE3 SCALE: 1/8" : 1'-0"

ANTENNAAN

BUILDING 1, DOCK CANOPY - DEMOLITION ROOF PLAN2 SCALE: 1/8" : 1'-0"

17'-6"±

132'-11"±

2'-10"±

11'-5"±

14'-5"± 55'-2"± 8'-9"± 17'-6"±

13'-10"±

40'-4"±

55'-5"±25'-11"±

10'-4"±

4'-3"±

2'-11"± 14'-6"±

22'-1"±

15'-6"±

33'-9"±

13'-2"±

42'-4"±

31'-3"±

27'-6"±

1'-8"±

29'-7"±

47°±

41'-9"±

CONNECTING

CORRIDOR 1

CONNECTING

CORRIDOR 2

CF, AB, DRJAB

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172 30 DEC 2024

PRD PRD

PRD

PRD

PRD

BUILDING 5

MECHANICAL

PENTHOUSE

(5.2)

BUILDING 5

ROOF EAST

OF WOMEN'S

CLINIC

RENOVATION

(5.1)

NOT IN SCOPE

NOT IN SCOPE

PRD

PRD

PRD

PRD

PRD

LOADING

DOCK

CANOPY (5.4)

BUILDING 5

LOW ROOF

(5.3)

COOLING

TOWER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AD-105

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

2 SCALE: 1/16" : 1'-0"

KEYPLAN

LEGEND

ROOFTOP UNIT

GUTTER (GU)

SOIL VENT PIPE (SVP)

DOWNSPOUT (DS)

WATER FLOW

PRIMAY ROOF DRAIN (PRD)

ROOF-TO-WALL

EXPANSION JOINT

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.)

CONTROL JOINT

ELEVATION CHANGE

STRUCTURAL RIDGE/HIP

VALLEY

EXISTING ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

DECK INSULATION COVER

BOARD

ROOF

MEMBRANE SURFACING COMMENTS

TA

PE

RE

D

LIG

HT

W

EI

GH

T

CO

NC

RE

TE

O

VE

R

ME

TA

L D

EC

K

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

DE

CK

SL

OP

ED

M

ET

AL

D

EC

K

PO

LY

IS

O

IN

SU

LA

TI

ON

, F

LA

T

PE

RL

IT

E

BU

ILT

-U P

RO

OF

GR

AN

UL

AT

ED

C

AP

S

HE

ET

BUILDING 5 ROOF

EAST OF WOMEN'S

CLINIC

RENOVATION (5.1)

● - - - - ● ● X1/AS-502

BUILDING 5

MECHANICAL

PENTHOUSE (5.2) ● - - - - ● ● X1/AS-502

BUILDING 5 LOW

ROOF (5.3) ● - - - - ● ● X1/AS-502

BUILDING 5

LOADING DOCK

CANOPY (5.4)

- ● - - ● ● ● X4/AS-501

COOLING TOWER - - ● ● ● ● ● X2/AS-502

SPECIFIC ROOF DEMOLITION NOTES

BUILDING 5 - DEMOLITION ROOF PLAN

1 SCALE: 1/8" : 1'-0"

BUILDING 5 - DEMOLITION ROOF PLAN

3 SCALE: 1/4" : 1'-0"

COOLING TOWER EQUIPMENT ROOM - DEMOLITION ROOF PLAN

BUILDING 5 & COOLING TOWER EQUIPMENT

ROOM - DEMOLITION ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

75'-7"±

7'-2"± 8'±

59'-6"±

18'-11"±

7'-2"±

9'-10"±

113°±

133°±

5'-1"±

42'-1"±

15'-10"± 18'± 29'-2"±

42'-5"±

27'-9"± 17'-2"±

5'-8"±

17'-11"±

21'-5"±

9'-2"± 17'-11"± 10'±

22'-7"± 17'-3"± 17'-5"± 12'-6"± 10'-1"±

59'±

10'-1"±

15'±

43'-4"±10'-8"±

6'-11"±

21'-1"±9'-7"±

8'-1"±

45'-8"±31'-11"±19'-6"±

64'-10"±

47'-5"±

13'-11"±

CF, AB, DRJAB

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

EXISTING FALL

PROTECTION

PRD PRD

PRD

PRD

PRD

PRD

PRD

PRD PRD

PRD

ORD

PRD PRD

PRD PRD PRD

PRD

PRD

PRD

PRD

PRD

PRD

PRD

PRD PRD

PRD

PRD

PRD PRD

PRD PRD PRD

PRD PRD

PRD

PRD

PRD

PRD

PRD

PRD

NOT IN SCOPE

NOT IN SCOPE

CONC. PATIO

NOT IN SCOPE

CONC. PATIO

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

BUILDING 7.6

SL

SL SL

SL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AD-106

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 7 - DEMOLITION ROOF PLAN

BUILDING 7 - DEMOLITION ROOF PLAN1 SCALE: 1/32" : 1'-0"

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET

PRIMARY SCUPPER (PS)

GUTTER (GU)

TAPERED INSULATION

SOIL VENT PIPE (SVP)

OVERFLOW ROOF DRAIN

(ORD)

DOWNSPOUT (DS)

TEST CUT1

WATER FLOW

FALL PROTECTION DAVIT

(FPD)

PRIMAY ROOF DRAIN (PRD)

LIGHTNING PROTECTION

PITCH POCKET (LPS)

PITCH POCKET (PP)

FALL PROTECTION

ANCHOR (FPA)

ROOF-TO-WALL

EXPANSION JOINT

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.)

WIND ZONE NO. 1

WIND ZONE NO. 3

WIND ZONE NO. 2

ROOF-TO-ROOF

EXPANSION JOINT

OVERFLOW SCUPPER

(OS)

EXHAUST FAN (EF)

HEATED VENT STACK

(HVS)

SKYLIGHT (S)S

ROOF ACCESS - LADDER

ROOF HATCH

ROOF WALKWAY PAD

CONTROL JOINT

ELEVATION CHANGE

KEYPLAN

LIGHTINING ROD

EXISTING ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

DECK INSULATION COVER

BOARD

ROOF

MEMBRANE SURFACING COMMENTS

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

PE

RL

IT

E

BU

ILT

-U P

RO

OF

AG

GR

EG

AT

E

BUILDINGS

7.1 - 7.9 ● ● ● ● ● X1/AS-501

SPECIFIC ROOF DEMOLITION NOTES

STRUCTURAL RIDGE/HIP

VALLEY

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

22'±

19'±17'-5"±

49'-1"±

21'-7"± 20'-8"±

136°±

93'-10"±

80'-1"± 15'-7"±

105'-11"±

2'-7"± 23'-5"±

17'-9"±

140°±

21'-9"± 6'-8"±

118'-1"± 116'-10"±

6'-8"±

21'-4"±

17'-9"±

131°± 23'-5"±

2'-8"±

92'-10"±

17'-10"±

5'-9"±

18'-11"±

36'-2"±

134°±

30'-6"±

66'-8"±

13'-7"±

100'-7"±

61'-10"±

71'-4"±

97'-3"±

48'-10"±

45°±

12'-8"±

125'-9"±

91'-11"±

4'-10"± 24'-10"±

17'-11"±

136°±

20'-3"±

2'-8"±

119'-3"±

31'±

30'-9"±

55'±

28'-7"±

39'-3"±

59'-4"±

33'-7"±

9'-2"± 24'-9"±

133°±

16'-10"±

26'-1"±

9'±

13'-1"±

24'-10"±

BUILDING 7.4

BUILDING 7.1

BUILDING 7.2

BUILDING 7.3

BUILDING 7.5

BUILDING 7.6

BUILDING

7.9

BUILDING 7.7

BUILDING 7.8

5'-0"±

5'-0"±

22'-0"±

22'-0"±

CF, AB, DRJAB

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

EXTENT OF COURTYARD

EXISTING FALL

PROTECTION

BUILDING 7.10

PRD PRD

PRD

PRD

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

ENTRANCE

VESTIBULE 2

ENTRANCE

VESTIBULE 1

ROOF OVER

THEATER

AMBULATORY CARE

MECHANICAL

PENTHOUSE

NOT IN SCOPE

NOT IN SCOPE

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

SVP

SVP

SVP

SVP

ENTRANCE VESTIBULE 1

DS

G 0.25:12

TAPER

KEYPLAN

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET GUTTER (GU)

SOIL VENT PIPE (SVP)

DOWNSPOUT (DS)

TEST CUT1

WATER FLOWPRIMAY ROOF DRAIN (PRD)

ROOF-TO-WALL

EXPANSION JOINT

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.)

ROOF-TO-ROOF

EXPANSION JOINTSKYLIGHT (S)S

ELEVATION CHANGE

LIGHTINING ROD

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

NEW ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

STRUCTURAL

DECK UNDERLAYMENT INSULATION COVER

BOARD

ROOF

MEMBRANE SURFACING COMMENTS

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

MO

DI

FI

ED

B

IT

UM

EN

B

AS

E

SH

EE

T, TO

RC

H

AP

PL

IE

D

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

AD

HE

RE

D

AP

PR

OV

ED

C

OV

ER

B

OA

RD

AD

HE

RE

D

2 P

LY

M

OD

IF

IE

D

BI

TU

ME

N W

IT

H

GR

AN

UL

AT

ED

C

AP

S

HE

ET

, T

OR

CH

AP

PL

IE

D

GR

AN

UL

ES

M

EE

TI

NG

C

OO

L R

OO

F

RA

TI

NG

C

OU

NC

IL

RE

QU

IR

EM

EN

TS

FO

R

LO

W

-S

LO

PE

R

OO

FS

ENTRANCE

VESTIBULE 1 ● ● ● ● ● ● 1/AS-502

ENTRANCE

VESTIBULE 2 ● ● ● ● ● ● 1/AS-502

ROOF OVER THEATER ● ● ● ● ● ● 1/AS-502

AMBULATORY CARE

MECHANICAL

PENTHOUSE ● ● ● ● ● ● 1/AS-502

SPECIFIC ROOF CONSTRUCTION NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AS-101

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1 - NEW ROOF PLAN

BUILDING 1 - NEW ROOF PLAN 1 SCALE: 1/16" : 1'-0"

CF, AB, DRJAB

SIM.

SIM.

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

EXISTING FALL

PROTECTION

NOT IN SCOPE

PRD PRD

PRD

0.

:1

TA

PE

R 0.

:1

TA

PE

R

PRD

PRD PRD

0.25:12

TAPER

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AS-102

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1A GENERATOR - NEW ROOF PLAN1 SCALE: 3/32" : 1'-0"

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET

PRIMARY SCUPPER (PS)

GUTTER (GU)

TAPERED INSULATION

STRUCTURAL RIDGE/HIP

SOIL VENT PIPE (SVP)

OVERFLOW ROOF DRAIN

(ORD)

DOWNSPOUT (DS)

VALLEY

TEST CUT1

WATER FLOW

FALL PROTECTION DAVIT

(FPD)

PRIMAY ROOF DRAIN (PRD)

LIGHTNING PROTECTION

PITCH POCKET (LPS)

PITCH POCKET (PP)

FALL PROTECTION

ANCHOR (FPA)

ROOF-TO-WALL

EXPANSION JOINT

FALL PROTECTION

CABLE (FPC)

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.) WIND ZONE NO. 1

WIND ZONE NO. 3 WIND ZONE NO. 2

ROOF-TO-ROOF

EXPANSION JOINT

OVERFLOW SCUPPER

(OS)

EXHAUST FAN (EF) HEATED VENT STACK

(HVS)

SKYLIGHT (S)S ROOF ACCESS - LADDER

ROOF HATCH ROOF WALKWAY PAD

CONTROL JOINT

ELEVATION CHANGE

KEYPLAN

LIGHTINING ROD

NEW ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

STRUCTURAL

DECK INSULATION COVER

BOARD

ROOF

MEMBRANE SURFACING COMMENTS

FL

AT

M

ET

AL

D

EC

K

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

AP

PR

OV

ED

C

OV

ER

B

OA

RD

2 P

LY

M

OD

IF

IE

D

BI

TU

ME

N W

IT

H

GR

AN

UL

AT

ED

C

AP

S

HE

ET

, T

OR

CH

AP

PL

IE

D

GR

AN

UL

ES

M

EE

TI

NG

C

OO

L R

OO

F

RA

TI

NG

C

OU

NC

IL

RE

QU

IR

EM

EN

TS

FO

R

LO

W

-S

LO

PE

R

OO

FS

GENERATOR

BUILDING ● ● ● ● ● 3/AS-502

BUILDING 1A GENERATOR - NEW

ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

CF, AB, DRJAB

SPECIFIC ROOF CONSTRUCTION NOTES

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

EXISTING FALL

PROTECTION

NOT IN SCOPE

TPO ROOF TO REMAIN

PATIO ROOF 2

PATIO ROOF 1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AS-103

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1A, SECOND FLOOR PATIO ROOF - NEW ROOF PLAN1 SCALE: 3/32" : 1'-0"

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET GUTTER (GU)

SOIL VENT PIPE (SVP)

DOWNSPOUT (DS)

TEST CUT1

WATER FLOWPRIMAY ROOF DRAIN (PRD)

ROOF-TO-WALL

EXPANSION JOINT

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.)

ROOF-TO-ROOF

EXPANSION JOINTSKYLIGHT (S)S

ELEVATION CHANGE

KEYPLAN

LIGHTINING ROD

BUILDING 1A, SECOND FLOOR PATIO

ROOF - NEW ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

26'-2"±

61'±

72'-6"±

14'-5"±

33'-10"±

39'-2"±

32'-11"±

46'-9"±

11'-5"±

NEW ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

STRUCTURAL

DECK UNDERLAYMENT INSULATION COVER

BOARD ROOF MEMBRANE SURFACING COMMENTS

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

MO

DI

FI

ED

B

IT

UM

EN

B

AS

E

SH

EE

T, TO

RC

H

AP

PL

IE

D

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

AD

HE

RE

D (V

.I.F

AP

PR

OV

ED

C

OV

ER

B

OA

RD

AD

HE

RE

D

2 P

LY

M

OD

IF

IE

D

BI

TU

ME

N W

IT

H

GR

AN

UL

AT

ED

C

AP

S

HE

ET

, T

OR

CH

AP

PL

IE

D

M

IL

FU

LL

Y

AD

HE

RE

D

TP

O

ME

MB

RA

NE

PE

DE

ST

AL

S

AN

D

PA

VE

RS

PATIO ROOF 1 ● ● ● ● ● ● 4/AS-502

PATIO ROOF 2 ● ● ● ● ● 4A/AS-502

CF, AB, DRJAB

SPECIFIC ROOF CONSTRUCTION NOTES

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

PRD

PRD

PRD PRD

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.2 5:1

TAPER

0.2 5:1

TAPER

0.2 5:1

TAPER

0.2 5:1

TAPER

AN

DS DS

DS DS

DS

DSDS

DSDS

DS

DS DS

0.25:12

TAPER

0.

:1

TA

PE

R

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.

:1

TA

PE

R

PRD

PRD

PRD

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AS-104

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1, CONNECTING CORRIDORS - NEW ROOF PLAN1 SCALE: 1/8" : 1'-0"

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET

PRIMARY SCUPPER (PS)

GUTTER (GU)

TAPERED INSULATION

STRUCTURAL RIDGE/HIP

SOIL VENT PIPE (SVP)

OVERFLOW ROOF DRAIN

(ORD)

DOWNSPOUT (DS)

VALLEY

TEST CUT1

WATER FLOW

FALL PROTECTION DAVIT

(FPD)

PRIMAY ROOF DRAIN (PRD)

LIGHTNING PROTECTION

PITCH POCKET (LPS)

PITCH POCKET (PP)

FALL PROTECTION

ANCHOR (FPA)

ROOF-TO-WALL

EXPANSION JOINT

FALL PROTECTION

CABLE (FPC)

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.) WIND ZONE NO. 1

WIND ZONE NO. 3 WIND ZONE NO. 2

ROOF-TO-ROOF

EXPANSION JOINT

OVERFLOW SCUPPER

(OS)

EXHAUST FAN (EF) HEATED VENT STACK

(HVS)

SKYLIGHT (S)S ROOF ACCESS - LADDER

ROOF HATCH ROOF WALKWAY PAD

CONTROL JOINT

ELEVATION CHANGE

KEYPLAN

LIGHTINING ROD

NEW ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

DECK UNDERLAYMENT INSULATION COVER

BOARD

ROOF

MEMBRANE SURFACING COMMENTS

FL

AT

M

ET

AL

D

EC

K

TA

PE

RE

D

LIG

HT

W

EI

GH

T

CO

NC

RE

TE

O

VE

R

FL

AT

M

ET

AL

DE

CK

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

DE

CK

AP

PR

OV

ED

U

ND

ER

LA

YM

EN

T

BO

AR

D, A

DH

ER

ED

MO

DI

FI

ED

B

IT

UM

EN

B

AS

E

SH

EE

T, TO

RC

H

AP

PL

IE

D

FL

AT

P

OL

YI

SO

CY

AN

UR

AT

E

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

AP

PR

OV

ED

C

OV

ER

B

OA

RD

2 P

LY

M

OD

IF

IE

D

BI

TU

ME

N W

IT

H

GR

AN

UL

AT

ED

C

AP

S

HE

ET

, T

OR

CH

AP

PL

IE

D

GR

AN

UL

ES

M

EE

TI

NG

C

OO

L R

OO

F

RA

TI

NG

C

OU

NC

IL

RE

QU

IR

EM

EN

TS

FO

R

LO

W

-S

LO

PE

R

OO

FS

CONNECTING

CORRIDOR 1 ● - - - - - ● ● ● ● 3/AS-502

CONNECTING

CORRIDOR 2 - ● - ● ● ● - ● ● ● 2/AS-502

DOCK CANOPY - - ● - ● - ● ● ● ● 1/AS-502

BUILDING 1A

PENTHOUSE ● - - - - - ● ● ● ● 3/AS-502

BUILDING 1 CONNECTING CORRIDORS, DOCK

CANOPY & BLDG 1A PENTHOUSE -

NEW ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

BUILDING 1A, PENTHOUSE - NEW ROOF PLAN3 SCALE: 1/8" : 1'-0"

CONNECTING

CORRIDOR 2

ANTENNAAN

BUILDING 1, DOCK CANOPY - NEW ROOF PLAN2 SCALE: 1/8" : 1'-0"

CONNECTING

CORRIDOR 1

CF, AB, DRJAB

SPECIFIC ROOF CONSTRUCTION NOTES

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

PRD PRD

PRD

PRD

PRD

BUILDING 5

MECHANICAL

PENTHOUSE

(5.2)

BUILDING 5

ROOF EAST

OF WOMEN'S

CLINIC

RENOVATION

(5.1)

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U

C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U

C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U

C

TU

R

AL

NOT IN SCOPE

NOT IN SCOPE

PRD

PRD

PRD

PRD

PRD

LOADING

DOCK

CANOPY (5.4)

BUILDING 5

LOW ROOF

(5.3)

0.25:12

TAPER

0.25:12

TAPER

0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL 0.25:12

STR

U C

TU

R

AL

0.25:12

STR

U C

TU

R

AL

COOLING

TOWER

0.25:12

STRUCTURAL

DS

DS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AS-105

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

2 SCALE: 1/16" : 1'-0"

KEYPLAN

LEGEND

ROOFTOP UNIT

GUTTER (GU)

SOIL VENT PIPE (SVP)

DOWNSPOUT (DS)

WATER FLOW

PRIMAY ROOF DRAIN (PRD)

ROOF-TO-WALL

EXPANSION JOINT

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.)

CONTROL JOINT

ELEVATION CHANGE

STRUCTURAL RIDGE/HIP

VALLEY

NEW ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

DECK UNDERLAYMENT INSULATION COVER

BOARD

ROOF

MEMBRANE SURFACING COMMENTS

TA

PE

RE

D

LIG

HT

W

EI

GH

T

CO

NC

RE

TE

O

VE

R

ME

TA

L D

EC

K

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

DE

CK

SL

OP

ED

M

ET

AL

D

EC

K

AP

PR

OV

ED

U

ND

ER

LA

YM

EN

T

BO

AR

D, A

DH

ER

ED

MO

DI

FI

ED

B

IT

UM

EN

B

AS

E

SH

EE

T, TO

RC

H

AP

PL

IE

D

FL

AT

P

OL

YI

SO

CY

AN

UR

AT

E

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

AP

PR

OV

ED

C

OV

ER

B

OA

RD

2 P

LY

M

OD

IF

IE

D

BI

TU

ME

N W

IT

H

GR

AN

UL

AT

ED

C

AP

S

HE

ET

, T

OR

CH

AP

PL

IE

D

GR

AN

UL

ES

M

EE

TI

NG

C

OO

L R

OO

F

RA

TI

NG

C

OU

NC

IL

RE

QU

IR

EM

EN

TS

FO

R

LO

W

-S

LO

PE

R

OO

FS

BUILDING 5 ROOF

EAST OF WOMEN'S

CLINIC

RENOVATION (5.1)

● - - ● ● ● - ● ● ● 2/AS-502

BUILDING 5

MECHANICAL

PENTHOUSE (5.2) ● - - ● ● ● - ● ● ● 2/AS-502

BUILDING 5 LOW

ROOF (5.3) ● - - ● ● ● - ● ● ● 2/AS-502

BUILDING 5

LOADING DOCK

CANOPY (5.4)

- ● - - ● - ● ● ● ● 1/AS-502

COOLING TOWER - - ● - - ● - ● ● ● 3/AS-502

BUILDING 5 - NEW ROOF PLAN

1 SCALE: 1/8" : 1'-0"

BUILDING 5 - NEW ROOF PLAN

3 SCALE: 1/4" : 1'-0"

COOLING TOWER EQUIPMENT ROOM - NEW ROOF PLAN

BUILDING 5 & COOLING TOWER EQUIPMENT

ROOM - NEW ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

CF, AB, DRJAB

SPECIFIC ROOF CONSTRUCTION NOTES

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

EXISTING FALL

PROTECTION

PRD PRD

PRD

PRD

PRD

PRD

PRD

PRD PRD

PRD

ORD

PRD PRD

PRD PRD PRD

PRD

PRD

PRD

PRD

PRD

PRD

PRD

PRD PRD

PRD

PRD

PRD PRD

PRD PRD PRD

PRD PRD

PRD

PRD

PRD

PRD

PRD

PRD

NOT IN SCOPE

NOT IN SCOPE

CONC. PATIO

NOT IN SCOPE

CONC. PATIO

NOT IN SCOPE

NOT IN SCOPE

NOT IN SCOPE

BUILDING 7.6

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.25:12

TAPER

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R 0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R 0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R 0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.

:1

TA

PE

R

0.25:12

TAPER

SL

SL SL

SL

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AS-106

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 7 - NEW ROOF PLAN

BUILDING 7 - NEW ROOF PLAN1 SCALE: 1/32" : 1'-0"

LEGEND

ROOFTOP UNIT

ROOF OUTLINE/PARAPET

PRIMARY SCUPPER (PS)

GUTTER (GU)

TAPERED INSULATION

SOIL VENT PIPE (SVP)

OVERFLOW ROOF DRAIN

(ORD)

DOWNSPOUT (DS)

TEST CUT1

WATER FLOW

FALL PROTECTION DAVIT

(FPD)

PRIMAY ROOF DRAIN (PRD)

LIGHTNING PROTECTION

PITCH POCKET (LPS)

PITCH POCKET (PP)

FALL PROTECTION

ANCHOR (FPA)

ROOF-TO-WALL

EXPANSION JOINT

ROOF OUTLINE/

GRAVE-STOP FASCIA

ROOF AREA NOT-IN-

CONTRACT (N.I.C.)

WIND ZONE NO. 1

WIND ZONE NO. 3

WIND ZONE NO. 2

ROOF-TO-ROOF

EXPANSION JOINT

OVERFLOW SCUPPER

(OS)

EXHAUST FAN (EF)

HEATED VENT STACK

(HVS)

SKYLIGHT - MIN 8" BASE

FLASHING HEIGHTSL

ROOF ACCESS - LADDER

ROOF HATCH

ROOF WALKWAY PAD

CONTROL JOINT

ELEVATION CHANGE

KEYPLAN

LIGHTINING ROD

STRUCTURAL RIDGE/HIP

VALLEY

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

BUILDING 7.4

BUILDING 7.1

BUILDING 7.2

BUILDING 7.3

BUILDING 7.5

BUILDING 7.6

BUILDING

7.9

BUILDING 7.7

BUILDING 7.8

NEW ROOF ASSEMBLY CHART

RO

OF

D

ES

IG

NA

TI

ON

STRUCTURAL

DECK UNDERLAYMENT INSULATION COVER

BOARD

ROOF

MEMBRANE SURFACING COMMENTS

FL

AT

S

TR

UC

TU

RA

L C

ON

CR

ET

E

MO

DI

FI

ED

B

IT

UM

EN

B

AS

E

SH

EE

T, TO

RC

H

AP

PL

IE

D

TA

PE

RE

D

PO

LY

IS

OC

YA

NU

RA

TE

AD

HE

RE

D

AP

PR

OV

ED

C

OV

ER

B

OA

RD

AD

HE

RE

D

2 P

LY

M

OD

IF

IE

D

BI

TU

ME

N W

IT

H

GR

AN

UL

AT

ED

C

AP

S

HE

ET

, T

OR

CH

AP

PL

IE

D

GR

AN

UL

ES

M

EE

TI

NG

C

OO

L R

OO

F

RA

TI

NG

C

OU

NC

IL

RE

QU

IR

EM

EN

TS

FO

R

LO

W

-S

LO

PE

R

OO

FS

BUILDINGS 7.1-7.10 ● ● ● ● ● ● 1/AS-502

CF, AB, DRJAB

SPECIFIC ROOF CONSTRUCTION NOTES

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

OFFICE: 901 523 8990 EXT 4172

EXTENT OF COURTYARD

EXISTING FALL

PROTECTION

BUILDING 7.10

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

NOT IN

SCOPE

ENTRANCE

VESTIBULE

15'±

ENTRANCE

VESTIBULE 1

15'±

ROOF

OVER

THEATER

40'±

AMBULATORY

CARE

MECHANICAL

PENTHOUSE

28'±

NOT IN

SCOPE

NOT IN SCOPE

3 3

KEYPLAN

35% SUBMISSION 05 JUNE, 2023

TAB12 DEC 2024

BID SET SUBMISSION REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103 Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201 S-101

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/1 3/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 1 - WIND ZONE ROOF PLAN

CF, ABTAB

BUILDING 1 - WIND ZONE ROOF PLAN 1 SCALE: 1/16" : 1'-0"

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

LEGEND

ZONE 1 - FIELD

ZONE 2 - PERIMETER

ZONE 3 - CORNER

22'-0"

TYP

22'-0"

TYP

11'-3"

TYP

11'-3"

TYP

11'-3"

TYP

WIND UPLIFT PRESSURES

ASCE 7-10; IBC 2012

ROOF AREA DIMENSIONS (FEET): REFER ROOF PLAN

RISK CATEGORY: IV

EXPOSURE CATEGORY: C

BASIC WIND SPEED (THREE-SECOND PEAK GUST, MPH): 120 MPH

ASD*

ZONE 1 -44.95 PSF

ZONE 2 -65.69 PSF

ZONE 3 -86.44 PSF

ROOFING CONTRACTOR SHALL INSTALL TESTED ROOF ASSEMBLY w/ 2.0

SAFETY FACTOR TO MEET OR EXCEED THESE PRESSURES.

100 SUBMISSION 08 APRIL, 2024

BID SET 12/12/2024

NOT IN

SCOPE

NOT IN

SCOPE

3 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201 S-102

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/1 3/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

TAB

BUILDING 1A GENERATOR - WIND ZONE ROOF PLAN1 SCALE: 3/32" : 1'-0"

KEYPLAN

CF, AB, DRJ

35% SUBMISSION 05 JUNE, 2023

TAB

BUILDING 1A GENERATOR - WIND ZONE ROOF

PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

LEGEND

ZONE 1 - FIELD

6'-0"

6'-0"

WIND UPLIFT PRESSURES

ASCE 7-10; IBC 2012

ROOF AREA DIMENSIONS (FEET): REFER ROOF PLAN

RISK CATEGORY: IV

EXPOSURE CATEGORY: C

BASIC WIND SPEED (THREE-SECOND PEAK GUST, MPH): 120 MPH

ASD*

ZONE 1 -44.95 PSF

ZONE 2 -65.69 PSF

ZONE 3 -86.44 PSF

ROOFING CONTRACTOR SHALL INSTALL TESTED ROOF ASSEMBLY w/ 2.0

SAFETY FACTOR TO MEET OR EXCEED THESE PRESSURES.

6'-0"

TYP

100% SUBMISSION 08 APRIL, 2024

BID SET 12 DECEMBER, 2024

BID SET

12 DEC 2024

NOT IN

SCOPE

NOT IN

SCOPE

TPO ROOF TO REMAIN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201 S-103

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/1 3/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

CF, ABTAB

BUILDING 1A, SECOND FLOOR PATIO ROOF - WIND ZONE ROOF PLAN1 SCALE: 3/32" : 1'-0"

KEYPLAN

35% SUBMISSION 05 JUNE, 2023

TAB

BUILDING 1A, SECOND FLOOR PATIO

ROOF - WIND ZONE ROOF PLAN

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

LEGEND

ZONE 1 - FIELD

WIND UPLIFT PRESSURES

ASCE 7-10; IBC 2012

ROOF AREA DIMENSIONS (FEET): REFER ROOF PLAN

RISK CATEGORY: IV

EXPOSURE CATEGORY: C

BASIC WIND SPEED (THREE-SECOND PEAK GUST, MPH): 120 MPH

ASD*

ZONE 1 -44.95 PSF

ZONE 2 -65.69 PSF

ZONE 3 -86.44 PSF

ROOFING CONTRACTOR SHALL INSTALL TESTED ROOF ASSEMBLY w/ 2.0

SAFETY FACTOR TO MEET OR EXCEED THESE PRESSURES.

100% SUBMISSION 08 APRIL, 2024

BID SET 12 DECEMBER, 2024

3 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201 S-104

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/1 3/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

TAB

BUILDING 1, CONNECTING CORRIDORS - WIND ZONE ROOF PLAN1 SCALE: 1/8" : 1'-0"

KEYPLAN

CF, AB, DRJ

35% SUBMISSION 05 JUNE, 2023

TAB

BUILDING 1 CONNECTING CORRIDORS,

DOCK CANOPY, & BUILDING 1A PENTHOUSE

- WIND ZONE ROOF PLANS

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

BUILDING 1A, PENTHOUSE - WIND ZONE NEW ROOF PLAN3 SCALE: 1/8" : 1'-0"

CONNECTING

CORRIDOR 2

BUILDING 1, DOCK CANOPY - WIND ZONE ROOF PLAN2 SCALE: 1/8" : 1'-0"

CONNECTING

CORRIDOR 1

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

LEGEND

ZONE 1 - FIELD

3'-0"

3'-0"

TYP 3'-0"

TYP

3'-0"

TYP

5'-3"

TYP

WIND UPLIFT PRESSURES

ASCE 7-10; IBC 2012

ROOF AREA DIMENSIONS (FEET): REFER ROOF PLAN

RISK CATEGORY: IV

EXPOSURE CATEGORY: C

BASIC WIND SPEED (THREE-SECOND PEAK GUST, MPH): 120 MPH

BUILDING 1A PENTHOUSE

ASD*

ZONE 1 -47.33 PSF

ZONE 2 -69.17 PSF

ZONE 3 -91.01 PSF

BUILDING 1 CORRIDORS

ASD*

ZONE 1 -44.95 PSF

ZONE 2 -65.69 PSF

ZONE 3 -86.44 PSF

BUILDING 1 DOCK CANOPY

ASD*

ZONE 1 -40.03 PSF

ZONE 2 -56.35 PSF

ZONE 3 -74.76 PSF

ROOFING CONTRACTOR SHALL INSTALL TESTED ROOF ASSEMBLY w/ 2.0

SAFETY FACTOR TO MEET OR EXCEED THESE PRESSURES.

10'-6"

TYP

10'-6"

TYP

100% SUBMISSION 08 APRIL, 2024

BID SET 12 DECEMBER, 2024

NOT IN

SCOPE

BUILDING 5

MECHANICAL

PENTHOUSE (5.2)

BUILDING 5

ROOF EAST OF

WOMEN'S CLINIC

RENOVATION (5.1)

2 2

33 2

2 2

2 2

3 3 3 3 3

NOT IN SCOPE

NOT IN SCOPE

LOADING

DOCK

CANOPY (5.4)

BUILDING 5

LOW ROOF (5.3)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201 S-105

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/1 3/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

TAB

2 SCALE: 1/16" : 1'-0"

KEYPLAN

CF, AB, DRJ

BUILDING 5 - WIND ZONE ROOF PLAN

1 SCALE: 1/8" : 1'-0"

BUILDING 5 - WIND ZONE ROOF PLAN

3 SCALE: 1/4" : 1'-0"

COOLING TOWER EQUIPMENT ROOM - WIND ZONE ROOF PLAN

35% SUBMISSION 05 JUNE, 2023 BUILDING 5 & COOLING TOWER EQUIPMENT

ROOM - WIND ZONE ROOF PLANS

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

LEGEND

ZONE 1 - FIELD

3'-0"

3'-0"

TYP

3'-0"

TYP

3'-0"

TYP

16'-0"

TYP 16'-0"

TYP

WIND UPLIFT PRESSURES

ASCE 7-10; IBC 2012

ROOF AREA DIMENSIONS (FEET): REFER ROOF PLAN

RISK CATEGORY: IV

EXPOSURE CATEGORY: C

BASIC WIND SPEED (THREE-SECOND PEAK GUST, MPH): 120 MPH

COOLING TOWER EQUIPMENT ROOM

ASD*

ZONE 1 -24.50 PSF

ZONE 2 -37.15 PSF

ZONE 3 -52.95 PSF

BUILDING 5

ASD*

ZONE 1 -44.95 PSF

ZONE 2 -65.69 PSF

ZONE 3 -86.44 PSF

BUILDING 5 LOADING DOCK CANOPY

ASD*

ZONE 1 -40.03 PSF

ZONE 2 -56.35 PSF

ZONE 3 -74.76 PSF

ROOFING CONTRACTOR SHALL INSTALL TESTED ROOF ASSEMBLY w/ 2.0

SAFETY FACTOR TO MEET OR EXCEED THESE PRESSURES.

100% SUBMISSION 08 APRIL, 2024

BID SET 12 DECEMBER, 2024

NOT

IN

SCOPE

NOT

IN

SCOPE

CONC.

PATIO

NOT

IN

SCOPE

CONC.

PATIO

NOT

IN

SCOPE

NOT

IN

SCOPE

NOT

IN

SCOPE

BUILDING

7.6

3 3 3

3 32

NOT

IN

SCOPE

NOT

IN

SCOPE

CONC.

PATIO

NOT

IN

SCOPE

CONC.

PATIO

NOT

IN

SCOPE

NOT

IN

SCOPE

NOT

IN

SCOPE

BUILDING

7.6

3 3 3

3 32

NOT

IN

SCOPE

NOT

IN

SCOPE

CONC.

PATIO

NOT

IN

SCOPE

CONC.

PATIO

NOT

IN

SCOPE

NOT

IN

SCOPE

NOT

IN

SCOPE

BUILDING

7.6

3 3 3

3 32

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201 S-106

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/1 3/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

BUILDING 7 - WIND ZONE ROOF PLAN

TAB

BUILDING 7 - WIND ZONE ROOF PLAN1 SCALE: 1/32" : 1'-0"

KEYPLAN

CF, AB, DRJ

35% SUBMISSION 05 JUNE, 2023

TAB

REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

BUILDING 7.4

BUILDING 7.1

BUILDING 7.2

BUILDING 7.5

BUILDING 7.6

BUILDING

7.9

BUILDING 7.7

BUILDING 7.8

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

LEGEND

ZONE 1 - FIELD

125'-9"±125'-9"±

16'-0"

TYP

16'-0"

TYP

WIND UPLIFT PRESSURES

ASCE 7-10; IBC 2012

ROOF AREA DIMENSIONS (FEET): REFER ROOF PLAN

RISK CATEGORY: IV

EXPOSURE CATEGORY: C

BASIC WIND SPEED (THREE-SECOND PEAK GUST, MPH): 120 MPH

SPINAL CHORD INJURY BUILDING

ASD*

ZONE 1 -44.95 PSF

ZONE 2 -65.69 PSF

ZONE 3 -86.44 PSF

ROOFING CONTRACTOR SHALL INSTALL TESTED ROOF ASSEMBLY w/ 2.0

SAFETY FACTOR TO MEET OR EXCEED THESE PRESSURES.

100% SUBMISSION 07 MARCH, 2024

BUILDING 7.10

BID SET 12 DECEMBER, 2024

STRUCTURAL CONCRETE DECK, FLAT

POLYISOCYANURATE FOAM BOARD

INSULATION, TAPERED

PERLITE

COAL TAR PITCH

STRUCTURAL CONCRETE DECK, FLAT

EX. METAL DECK

EX. ISOCYANURATE

INSULATION

EX. PERLITE

EX. B.U.R. FELTS

EX. AGGREGATE

STRUCTURAL CONCRETE DECK, FLAT

PERLITE

STRUCTURAL CONCRETE DECK, FLAT

STRUCTURAL CONCRETE DECK, FLAT

STRUCTURAL CONCRETE DECK

PERLITE

METAL DECK, FLAT

PERLITE (RE-COVER BOARD)

METAL DECK, FLAT

TAPRED PERLITE

LWC OVER METAL DECK,

TAPERED

PERLITE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

WWW.RAYMOND.GLOBAL

FULL-SERVICE ARCHITECTURE & ENGINEERING

CONYERS, GA | SAVANNAH, GA | GREER, SC | RALEIGH, NC

ORLANDO, FL | MIAMI, FL | RICHMOND, VA

1035 GREEN ST., STE A

CONYERS, GA 30012

404-345-8201

35% SUBMISSION 05 JUNE, 2023

65% SUBMISSION 15 AUGUST, 2023

95% SUBMISSION 12 DECEMBER, 2023

BID SET 4 OCTOBER, 2024

REVISED BID SET 30 DECEMBER, 2024

AS-501

AR

C

H F

U

LL

B

LE

ED

E

(3

0.

X

2.

IN

C

H

ES

/3 0/

:1

PM

PA

PE

R S

IZ

E

LA

ST

S

AV

ED

ROOF DETAILS REPLACE ROOF BLDG 1, 1A, 5 & 7

VA MEDICAL CENTER - MEMPHIS, TN

614-23-103

CF, AB, DRJAB

PAUL S. BROWN II

PROJECT ENGINEER, FAC-COR II, FE-C

LT. COL. LUKE J. WEATHERS, JR. VA MEDICAL CENTER

ADMIN BLDG 1, AEG28

1030 JEFFERSON AVE

MEMPHIS, TN 38104

APPROVED FIRE RETARDANT CANT

ROOFING FASTENERS AT 8" O.C

ROOF MEMBRANE (2-PLY) FLASHING SYSTEM PER

MANUFACTURER.

NOTE:

1. ALTERNATE DETAIL SHOULD ONLY BE USED UPON WRITTEN APPROVAL FROM THE DESIGNER OF RECORD AND ROOF SYSTEM MANUFACTURER AT LOCATIONS WHERE 8"

BASE FLASHING HEIGHT IS NOT POSSIBLE.

2. COUNTERFLASHING NOT SHOWN FOR CLARITY. REFER TO INDIVIDUAL DETAIL DRAWINGS FOR COUNTERFLASHING INFORMATION. INSTALL BASE WALL FLASHING SYSTEM

PER MANUFACTURER REQUIREMENTS. ALL FLASHINGS SHALL BE WARRANTED BY ROOF SYSTEM MANUFACTURER.

APPROVED FIRE RETARDANT CANT

REINFORCED LIQUID APPLIED FLASHING

SYSTEM

ROOF MEMBRANE (2-PLY) FLASHING SYSTEM PER

MANUFACTURER.

ROOFING FASTENERS

AT 8" O.C

ALTERNATE DETAIL: 4-6" MINIMUM BASE FLASHING HEIGHTSTANDARD DETAIL: 8" MINIMUM BASE FLASHING HEIGHT

DECK TO STRUCTURE ATTACHMENT PER

APPROVAL.

ROOF MEMBRANE BASE FLASHING (2-PLY MIN.)

AT VERTICAL MASONRY WALL

EXISTING MASONRY SURFACE SHALL BE SCRAPED,

CLEANED AND PRIMED

AT WOOD WALLS

MECHANICALLY FASTEN APPROVED

MANUFACTURER BASE FLASHING PLY TO

MASONRY/WOOD SURFACE @ 12" O.C ALL

DIRECTION PRIOR TO INSTALLATION OF TWO PLY

BASE FLASHING.

MASONRY/ STRUCTURAL CONCRETE: INSTALL 14" DIAMETER ANCHOR 300 SS

BY AGGRE-GATOR, 2 ROWS STAGGERED CONNECTING WOOD BLOCKING TO

MASONRY/ STRUCTURAL CONCRETE. ANCHORS TO BE STAGGERED AND

COUNTER SUNK. (FOR OTHER SUBSTRATE, NOTIFY ENGINEER OF RECORD TO

OBTAIN FASTENER TYPE AND PATTERN SECUREMENT)

MINIMUM DISTANCE FROM THE EDGE 2 INCHES

MINIMUM EMBEDMENT 1.25 INCHES

3 INCHES

9 INCHES

8 INCHES

MINIMUM SPACING

SPACING AT PERIMETER

SPACING AT CORNER

WOOD BLOCKING (PRESSURE TREATED) SECUREMENT OF WOOD

MEMBER TO WOOD NAILER: INSTALL MINIMUM NO. 8 SCREWS IN

TWO STAGGERED ROWS SPACING AT 6" O.C.

WOOD BLOCKING MIN. 2X6 (PRESSURE TREATED)

STEEL DECK

STEEL ANGLE/ BEAM

POLYISOCYANURATE FOAM BOARD

INSULATION, R-30, SLOPED OR FLAT

- REFER NEW ROOF ASSEMBLY

CHART ON NEW ROOF PLAN.

ADHERED (STAGGER JOINTS), 4'X4'

BOARD, MIN. 2 LAYERS

APPROVED COVER BOARD, ADHERED

MEMBRANE ROOFING SYSTEM

MEMBRANE…