Atch 2 Steam Trap Inventory Spreadsheet April 16 2024.xlsx

XLSX spreadsheet 34 KB Posted

Attached to
J035--603-24-102 - Repair (Replace) Steam Traps- Robley Rex VAMC - Re-Solicitation
Solicitation number
36C24924R0069
Issued by

About this file

This document is a Statement of Work (SOW) for a federal contract opportunity to replace steam traps at the Robley Rex VA Medical Center in Louisville, KY. The project objectives are to replace 98 failed steam traps and associated assemblies, including all required components such as pipe, nipples, and fittings. For high and medium pressure steam trap assemblies, all components must be cast steel, forged steel, or stainless steel. The contractor is responsible for providing all labor, materials, and equipment to complete the work. The period of performance is 240 days, and some after-hours work will be required to minimize disruptions to medical center operations. The contractor must submit a proposed replacement trap for each inventory item for approval prior to installation. Training for maintenance personnel and a one-year warranty are also required.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1 Robley Rex VA Medical Center - Replace Steam Traps Project - Trap Inventory

16-Apr-24
Line ItemTrap #RouteLocationElevationApplicationUsageExisting MakeExisting ModelTypePMOConnection SizePressure InPressure OutCondensate LiftCheck ValveIsolation InIsolation OutConstant/ModulatingRecommendationsStatusCommentsProposed ManufacturerProposed Model
111Boiler 1 steam piping10'DripHPS SupplyArmstrong800IVBT1500.75110102'XXXConstantReplaceOKNone
221Boiler 2 steam piping10'DripHPS SupplyWatson McDaniel1032IVBT1250.75110102'XXXConstantReplaceOKNone
331Boiler 3 steam piping10'DripHPS SupplyArmstrong800IVBT1500.75110102'XXXConstantReplaceBlow ThruTrap has failed.
4131DA Room - Main PRV StationGLDripHPS SupplyArmstrong811IVBT1250.75110020'XXXConstantReplaceBlow ThruTrap has failed.
5612SB-4 Mechanical Room2'DripHPS SupplyArmstrong800IVBT1250.75110105'XXXConstantReplaceBlow ThruTrap has failed.
6622SB-4 Mechanical Room2'DripHPS SupplyArmstrong800IVBT1250.75110105'XXXConstantInstall a larger capacity, constant pressure, steam trap.Rapid CyclingTrap is undersized.
71022Crawl Space South Stairwell 53'DripHPS SupplyArmstrong800IVBT1250.75110105'XXXConstantReplaceOKNone
81032Crawl Space Southeast Stairwell 53'DripHPS SupplyArmstrong800IVBT1250.75110105'XXXConstantReplaceOKNone
91102Crawl Space - East Side of Telephone Equipment RoomGLDripHPS SupplyArmstrong800IVBT1500.75110105'XXXConstantReplaceOKNone
101222Subbasement Below M0035'DripHPS SupplyArmstrong125A3F&T1250.75110105'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
111232Subbasement Below M0034'DripHPS SupplyArmstrong800IVBT1250.75110105'XXXConstantReplaceOKNone
1225815Basement Mechanical6'DripHPS SupplyArmstrong800IVBT1250.75110100'XXXConstantReplaceBlow ThruTrap has failed.
1327517Basement Mechanical7'DripHPS SupplyArmstrong800IVBT1250.75110100'XXOConstantReplaceOKNone
14101Surge Tank Room - Beside Surge TankGLDripHPS SupplyArmstrong800IVBT1500.7580010'XXXConstantReplaceOKNone
15111Surge Tank Room - Beside Surge TankGLDripHPS SupplyArmstrong800IVBT1500.7580010'XXXConstantReplaceOKNone
16121Surge Tank Room - Beside Surge TankGLDripHPS SupplyArmstrong800IVBT1500.7580010'XXXConstantReplaceOKNone
171383M0035'DripHPS SupplyArmstrong125A3F&T1250.7580102'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
181393M0035'DripHPS SupplyArmstrong125A3F&T1250.7580102'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
191855M302 - Mechanical Penthouse7'DripHPS SupplyArmstrong800IVBT1250.7580104'XXXConstantReplaceOKNone
201865M302 - Mechanical Penthouse7'DripHPS SupplyArmstrong800IVBT1250.7580104'XXXConstantReplaceBlow ThruTrap has failed.
2125114PRV StationGLDripHPS SupplyArmstrong813IVBT125170100'XXXConstantReplaceOKNone
22172Next to Stairwell #24'DripMPS SupplyArmstrong800IVBT800.55000'XXXConstantReplaceOKNone
23182Next to Stairwell #24'DripMPS SupplyArmstrong800IVBT800.55000'XXXConstantReplaceOfflineCheck trap when returned to service.
24192Next to Stairwell #24'DripMPS SupplyArmstrong800IVBT800.55000'XXXConstantReplaceOfflineCheck trap when returned to service.
25222Due East Stairwell 24'DripMPS SupplyArmstrong800IVBT800.55000'XXXConstantReplaceOKNone
26282Due East Stairwell 22'DripMPS SupplyArmstrong800IVBT800.55000'XXXConstantReplaceRapid CyclingTrap has failed.
27292Due East Stairwell 23'DripMPS SupplyArmstrong800IVBT800.55000'XXXConstantReplaceOKNone
28332East of S-5 Elevator Shaft2'DripMPS SupplyArmstrong75A3F&T750.755000'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
29432North Wing - Center Entrance3'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantNoneOKNone
30442North End of main Crawl Space1'DripMPS SupplyArmstrong880IVBT1250.755000'XXXConstantReplaceOKNone
31452North End of main Crawl Space1'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceBlow ThruTrap has failed.
32462North End of main Crawl Space1'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceOKNone
33472North End of main Crawl Space1'DripMPS SupplySpirax-SarcoTD52Disc6000.55000'XXXConstantReplaceColdTrap has failed.
34572AHU 23 Mech Space - Behind AHU 243'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceColdTrap has failed.
35582AHU 23 Mech Space - Behind AHU 233'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceBlow ThruTrap has failed.
36632SB-4 Mechanical Room5'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceOKNone
37722SB-4 Mechanical Room8'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplace with a larger capacity, constant pressure, steam trap.Rapid CyclingTrap is undersized.
38832SB-4 Mechanical Room8'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceOKNone
39842SB-4 Mechanical Room8'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceOKNone
40852SB-6 Mechanical Room - HX Area4'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceOKNone
411082Crawl Space - North Side of Telephone Equipment RoomGLDripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceFloodedTrap has failed. Miss the cap plug and leaking on the ground.
421162Crawl Space - West of Linen Stairwell3'DripMPS SupplyArmstrong800IVBT1250.55095'XXXConstantReplaceOKNone
431242Subbasement Below M0033'DripMPS SupplyArmstrong800IVBT1250.550105'XXXConstantReplaceOKNone
441252Subbasement Below M0036'DripMPS SupplyArmstrong800IVBT1250.550105'XXXConstantReplaceOKNone
451282Subbasement Below M0033'DripMPS SupplyArmstrong800IVBT1250.550105'XXXConstantReplaceOKNone
461684A-236a Kitchen Soup KettlesGLDripMPS SupplyArmstrong800IVBT800.755000'XOOConstantReplaceOKNone
471694A-236a Kitchen Soup Kettles1'DripMPS SupplyUnknownUnknownDisc60015000'XXOConstantReplaceOKNone
481765M301-1 Mechanical Penthouse AHU5A3'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceBlow ThruTrap has failed.
491785M301-1 Mechanical Penthouse AHU4A3'EquipmentHumidifierHoffman601AIVBT1250.755000'XXXConstantReplaceOfflineCheck trap when returned to service.
501795M301-1 Mechanical Penthouse AHU5A3'DripMPS SupplyArmstrong15B3F&T150.755000'XXXConstantReplace with a constant pressure application steam trap.Over PressureBad application for a modulating pressure steam trap.
511805M301-1 Mechanical Penthouse AHU5A5'DripMPS SupplyHoffmanFT015I-3F&T150.755000'XXXConstantReplace with a constant pressure application steam trap.Over PressureBad application for a modulating pressure steam trap.
521815M301-1 Mechanical Penthouse AHU5A3'DripMPS SupplyArmstrong125A3F&T1250.755000'XXXConstantReplaceOKBad application for a modulating pressure steam trap.
531835M301-1 Mechanical Penthouse AHU5A2'DripLPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceOKNone
541845M301-1 Mechanical Penthouse AHU5A2'EquipmentHumidifierArmstrong125A3F&T1250.755000'XXXConstantReplaceOKBad application for a modulating pressure steam trap.
551996M504 AHU16'DripMPS SupplyArmstrong800IVBT800.755000'XXXConstantReplaceOKNone
562106M504 AHU21'DripMPS SupplyArmstrongCD33Disc6000.755000'XXXConstantReplaceOKNone
572126M504 AHU2GLPump TrapAHU1ArmstrongPT104F&T1001.2550010'XXXConstantif steel replacement pump trap cannot be found, replace with a suitable steel trap.OKNone
582136M504 AHU11'DripMPS SupplyArmstrongCD33Disc6000.755000'XXXConstantReplaceOKNone
592236M502 Entrance6'EquipmentUnit HeaterArmstrong800IVBT800.755000'XXXConstantReplaceOKNone
602358Cart Washer6'EquipmentHeat ExchangerSpirax-SarcoFT14HCF&T36315000'OOOModulatingReplaceOKNone
612368Cart Washer6'EquipmentHeat ExchangerSpirax-SarcoFT14HCF&T3630.55000'OOOModulatingReplaceOKNone
6224412100001 Machine Room Cage9'DripMPS SupplyArmstrong800IVBT1250.755000'XXXConstantReplaceBlow ThruTrap has failed.
6324512100001 Machine Room Cage9'DripMPS SupplyArmstrong800IVBT1250.755000'XXXConstantReplaceOKNone
6427817Basement Mechanical2'DripMPS SupplyArmstrong800IVBT1250.755000'XOOConstantReplaceOfflineCheck trap when returned to service.
651504C220 AHU96'DripLPS SupplyArmstrong800IVBT200.752000'XXXConstantReplaceBlow ThruTrap has failed.
661584C220 AHU 6A4'DripLPS SupplyArmstrong800IVBT200.752000'XXXConstantReplaceBlow ThruTrap has failed.
671825M301-1 Mechanical Penthouse Behind AHU4AGLDripLPS SupplyArmstrong811IVBT200.752000'XXXConstantReplaceBlow ThruTrap has failed.
6825715Basement Mechanical7'DripLPS SupplySpirax-SarcoFT125F&T1250.752000'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
6926115Basement MechanicalGLDripTank HeaterArmstrong812IVBT700.752006'OOXConstantReplaceBlow ThruTrap has failed.
7071Chiller Plant - Chiller 18'DripLPS SupplyArmstrong15B4F&T1511500XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
7191Surge Tank Room - Beside Brine TankGLDripLPS SupplyArmstrong800IVBT1500.5151012'XXXConstantReplaceLeakingTrap has failed. Wrong PMO.
721333M0026'DripLPS SupplyArmstrong15B3F&T150.751500'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
732206M502 AHU-106'DripLPS SupplySpirax-SarcoFT15F&T150.751500'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
742216M502 AHU-101'DripHumidifierSpirax-SarcoSIB30/6 (6/64")IVBT150.751500'XXXConstantReplaceBlow ThruTrap has failed.
7525314PRV Station2'DripLPS SupplyMepcoIB12IVBT150.751500'XXXConstantReplaceBlow ThruTrap has failed.
762541419-HX-12'EquipmentHeat ExchangerMepcoIB13IVBT150.751500'XXXConstantReplace with a modulating pressure application steam trap.FloodedBad application for a constant pressure steam trap.
77262Due East Stairwell 23'DripLPS SupplyArmstrong15B3F&T150.751000'OXOConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
78542AHU 23 Mech Space - Condensate Skid7'DripLPS SupplyArmstrong15B3F&T150.751000'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
79552AHU 23 Mech Space - Condensate Skid7'DripLPS SupplyArmstrong125A3F&T150.751000'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
80562AHU 23 Mech Space - AHU 23GLEquipmentSteam CoilArmstrong15B3F&T150.751000'XXXConstantReplaceColdTrap has failed.
81592AHU 23 Mech Space - AHU 237'DripLPS SupplyArmstrong15B3F&T150.751000'OXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
82662SB-4 Mechanical Room6'DripLPS SupplyMepco40-215AF&T150.751000'XXXConstantReplace with a constant pressure application steam trap.ColdBad application for a modulating pressure steam trap.
83762SB-4 Mechanical RoomGLEquipmentWater HeaterNicholsonNFT25-2F&T5021013'XXXModulatingReplaceBlow ThruTrap has failed.
84772SB-4 Mechanical Room1'DripLPS SupplyArmstrong800IVBT200.751000'XXXConstantReplaceBlow ThruTrap has failed.
85782SB-4 Mechanical RoomGLEquipmentWater HeaterNicholsonNFT25-2F&T5021013'XXXModulatingReplaceBlow ThruTrap has failed.
86812SB-4 Mechanical RoomGLEquipmentWater HeaterNicholsonNFT25-2F&T5021013'XXXModulatingReplaceBlow ThruTrap has failed.
87141DA Room - DA PRV Station12'DripLPS SupplyArmstrong15B4F&T151 (.75 pipe)500'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
88902SB-6 Mechanical Room - HX Area7'DripLPS SupplyArmstrong800IVBT200.75500'XXXConstantReplaceBlow ThruTrap has failed.
89982Crawl Space East of SB-62'DripLPS SupplyArmstrong15B3F&T150.75500'OXXConstantReplaceColdTrap has failed. Bad application for a modulating pressure steam trap.
901002Crawl Space Under Stairwell 54'DripLPS SupplyArmstrong800IVBT200.75500'XXXConstantReplaceColdTrap has failed.
911012Crawl Space Under Stairwell 52'DripLPS SupplyArmstrong15B3F&T150.75500'XXXConstantReplaceColdTrap has failed. Bad application for a modulating pressure steam trap.
921042Crawl Space East Stairwell 56'DripLPS SupplyArmstrong800IVBT200.75500'XXXConstantReplaceFloodedTrap has failed.
931062Crawl Space Southeast Stairwell 5 Along the East Wall4'DripLPS SupplyArmstrong800IVBT200.75500'XXXConstantReplaceFloodedTrap has failed.
941072Crawl Space Southeast Stairwell 5 Along the East Wall4'DripLPS SupplyArmstrong800IVBT200.75500'XXXConstantReplaceLeakingTrap has failed.
951092Crawl Space - Northeast Side of Telephone Equipment RoomGLDripLPS SupplyHoffmanFT015H3F&T150.75500'XXXConstantReplaceColdTrap has failed. Bad application for a modulating pressure steam trap.
962046M504 HX-1A6'DripLPS SupplyArmstrong15B3F&T150.75500'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
972256M503 HX5'DripLPS SupplyArmstrong15B3F&T150.75500'XXXConstantReplace with a constant pressure application steam trap.Blow ThruBad application for a modulating pressure steam trap.
982503Dock Unit Heater8'EquipmentUnit HeaterArmstrong800IVBT200.75500'XXXConstantReplaceRapid CyclingTrap has failed.
Note:X - present
O - missing

File details come from the government source that posted it. Updated .