Atch 2 Steam Trap Inventory Spreadsheet April 16 2024.xlsx
XLSX spreadsheet 34 KB Posted
- Solicitation number
- 36C24924R0069
About this file
This document is a Statement of Work (SOW) for a federal contract opportunity to replace steam traps at the Robley Rex VA Medical Center in Louisville, KY. The project objectives are to replace 98 failed steam traps and associated assemblies, including all required components such as pipe, nipples, and fittings. For high and medium pressure steam trap assemblies, all components must be cast steel, forged steel, or stainless steel. The contractor is responsible for providing all labor, materials, and equipment to complete the work. The period of performance is 240 days, and some after-hours work will be required to minimize disruptions to medical center operations. The contractor must submit a proposed replacement trap for each inventory item for approval prior to installation. Training for maintenance personnel and a one-year warranty are also required.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24924R0069 0001.docx | DOCX document | |
| Atch 8 RFIs Questions and Answers from Previous Solicitation.docx | DOCX document | |
| Atch 7 Construction Past Performance Questionnaire.docx | DOCX document | |
| 36C24924R0069.docx | DOCX document | |
| Atch 5 Construction Pricing Schedule.xlsx | XLSX spreadsheet | |
| Atch 6 Calculation of Contractor Self Performed Work.xlsx | XLSX spreadsheet | |
| Atch 3 Drawing Float and Thermostatic Steam Trap Assembly Detail.pdf | ||
| Atch 4 Drawing Inverted Bucket Steam Trap Assembly.pdf | ||
| Atch 1 WD Jefferson County Building KY20240093 dated 03152024.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet1 Robley Rex VA Medical Center - Replace Steam Traps Project - Trap Inventory
| 16-Apr-24 | |||||||||||||||||||||||
| Line Item | Trap # | Route | Location | Elevation | Application | Usage | Existing Make | Existing Model | Type | PMO | Connection Size | Pressure In | Pressure Out | Condensate Lift | Check Valve | Isolation In | Isolation Out | Constant/Modulating | Recommendations | Status | Comments | Proposed Manufacturer | Proposed Model |
| 1 | 1 | 1 | Boiler 1 steam piping | 10' | Drip | HPS Supply | Armstrong | 800 | IVBT | 150 | 0.75 | 110 | 10 | 2' | X | X | X | Constant | Replace | OK | None | ||
| 2 | 2 | 1 | Boiler 2 steam piping | 10' | Drip | HPS Supply | Watson McDaniel | 1032 | IVBT | 125 | 0.75 | 110 | 10 | 2' | X | X | X | Constant | Replace | OK | None | ||
| 3 | 3 | 1 | Boiler 3 steam piping | 10' | Drip | HPS Supply | Armstrong | 800 | IVBT | 150 | 0.75 | 110 | 10 | 2' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 4 | 13 | 1 | DA Room - Main PRV Station | GL | Drip | HPS Supply | Armstrong | 811 | IVBT | 125 | 0.75 | 110 | 0 | 20' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 5 | 61 | 2 | SB-4 Mechanical Room | 2' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 110 | 10 | 5' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 6 | 62 | 2 | SB-4 Mechanical Room | 2' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 110 | 10 | 5' | X | X | X | Constant | Install a larger capacity, constant pressure, steam trap. | Rapid Cycling | Trap is undersized. | ||
| 7 | 102 | 2 | Crawl Space South Stairwell 5 | 3' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 110 | 10 | 5' | X | X | X | Constant | Replace | OK | None | ||
| 8 | 103 | 2 | Crawl Space Southeast Stairwell 5 | 3' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 110 | 10 | 5' | X | X | X | Constant | Replace | OK | None | ||
| 9 | 110 | 2 | Crawl Space - East Side of Telephone Equipment Room | GL | Drip | HPS Supply | Armstrong | 800 | IVBT | 150 | 0.75 | 110 | 10 | 5' | X | X | X | Constant | Replace | OK | None | ||
| 10 | 122 | 2 | Subbasement Below M003 | 5' | Drip | HPS Supply | Armstrong | 125A3 | F&T | 125 | 0.75 | 110 | 10 | 5' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 11 | 123 | 2 | Subbasement Below M003 | 4' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 110 | 10 | 5' | X | X | X | Constant | Replace | OK | None | ||
| 12 | 258 | 15 | Basement Mechanical | 6' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 110 | 10 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 13 | 275 | 17 | Basement Mechanical | 7' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 110 | 10 | 0' | X | X | O | Constant | Replace | OK | None | ||
| 14 | 10 | 1 | Surge Tank Room - Beside Surge Tank | GL | Drip | HPS Supply | Armstrong | 800 | IVBT | 150 | 0.75 | 80 | 0 | 10' | X | X | X | Constant | Replace | OK | None | ||
| 15 | 11 | 1 | Surge Tank Room - Beside Surge Tank | GL | Drip | HPS Supply | Armstrong | 800 | IVBT | 150 | 0.75 | 80 | 0 | 10' | X | X | X | Constant | Replace | OK | None | ||
| 16 | 12 | 1 | Surge Tank Room - Beside Surge Tank | GL | Drip | HPS Supply | Armstrong | 800 | IVBT | 150 | 0.75 | 80 | 0 | 10' | X | X | X | Constant | Replace | OK | None | ||
| 17 | 138 | 3 | M003 | 5' | Drip | HPS Supply | Armstrong | 125A3 | F&T | 125 | 0.75 | 80 | 10 | 2' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 18 | 139 | 3 | M003 | 5' | Drip | HPS Supply | Armstrong | 125A3 | F&T | 125 | 0.75 | 80 | 10 | 2' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 19 | 185 | 5 | M302 - Mechanical Penthouse | 7' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 80 | 10 | 4' | X | X | X | Constant | Replace | OK | None | ||
| 20 | 186 | 5 | M302 - Mechanical Penthouse | 7' | Drip | HPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 80 | 10 | 4' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 21 | 251 | 14 | PRV Station | GL | Drip | HPS Supply | Armstrong | 813 | IVBT | 125 | 1 | 70 | 10 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 22 | 17 | 2 | Next to Stairwell #2 | 4' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.5 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 23 | 18 | 2 | Next to Stairwell #2 | 4' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.5 | 50 | 0 | 0' | X | X | X | Constant | Replace | Offline | Check trap when returned to service. | ||
| 24 | 19 | 2 | Next to Stairwell #2 | 4' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.5 | 50 | 0 | 0' | X | X | X | Constant | Replace | Offline | Check trap when returned to service. | ||
| 25 | 22 | 2 | Due East Stairwell 2 | 4' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.5 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 26 | 28 | 2 | Due East Stairwell 2 | 2' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.5 | 50 | 0 | 0' | X | X | X | Constant | Replace | Rapid Cycling | Trap has failed. | ||
| 27 | 29 | 2 | Due East Stairwell 2 | 3' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.5 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 28 | 33 | 2 | East of S-5 Elevator Shaft | 2' | Drip | MPS Supply | Armstrong | 75A3 | F&T | 75 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 29 | 43 | 2 | North Wing - Center Entrance | 3' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | None | OK | None | ||
| 30 | 44 | 2 | North End of main Crawl Space | 1' | Drip | MPS Supply | Armstrong | 880 | IVBT | 125 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 31 | 45 | 2 | North End of main Crawl Space | 1' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 32 | 46 | 2 | North End of main Crawl Space | 1' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 33 | 47 | 2 | North End of main Crawl Space | 1' | Drip | MPS Supply | Spirax-Sarco | TD52 | Disc | 600 | 0.5 | 50 | 0 | 0' | X | X | X | Constant | Replace | Cold | Trap has failed. | ||
| 34 | 57 | 2 | AHU 23 Mech Space - Behind AHU 24 | 3' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | Cold | Trap has failed. | ||
| 35 | 58 | 2 | AHU 23 Mech Space - Behind AHU 23 | 3' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 36 | 63 | 2 | SB-4 Mechanical Room | 5' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 37 | 72 | 2 | SB-4 Mechanical Room | 8' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace with a larger capacity, constant pressure, steam trap. | Rapid Cycling | Trap is undersized. | ||
| 38 | 83 | 2 | SB-4 Mechanical Room | 8' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 39 | 84 | 2 | SB-4 Mechanical Room | 8' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 40 | 85 | 2 | SB-6 Mechanical Room - HX Area | 4' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 41 | 108 | 2 | Crawl Space - North Side of Telephone Equipment Room | GL | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | Flooded | Trap has failed. Miss the cap plug and leaking on the ground. | ||
| 42 | 116 | 2 | Crawl Space - West of Linen Stairwell | 3' | Drip | MPS Supply | Armstrong | 800 | IVBT | 125 | 0.5 | 50 | 9 | 5' | X | X | X | Constant | Replace | OK | None | ||
| 43 | 124 | 2 | Subbasement Below M003 | 3' | Drip | MPS Supply | Armstrong | 800 | IVBT | 125 | 0.5 | 50 | 10 | 5' | X | X | X | Constant | Replace | OK | None | ||
| 44 | 125 | 2 | Subbasement Below M003 | 6' | Drip | MPS Supply | Armstrong | 800 | IVBT | 125 | 0.5 | 50 | 10 | 5' | X | X | X | Constant | Replace | OK | None | ||
| 45 | 128 | 2 | Subbasement Below M003 | 3' | Drip | MPS Supply | Armstrong | 800 | IVBT | 125 | 0.5 | 50 | 10 | 5' | X | X | X | Constant | Replace | OK | None | ||
| 46 | 168 | 4 | A-236a Kitchen Soup Kettles | GL | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | O | O | Constant | Replace | OK | None | ||
| 47 | 169 | 4 | A-236a Kitchen Soup Kettles | 1' | Drip | MPS Supply | Unknown | Unknown | Disc | 600 | 1 | 50 | 0 | 0' | X | X | O | Constant | Replace | OK | None | ||
| 48 | 176 | 5 | M301-1 Mechanical Penthouse AHU5A | 3' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 49 | 178 | 5 | M301-1 Mechanical Penthouse AHU4A | 3' | Equipment | Humidifier | Hoffman | 601A | IVBT | 125 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | Offline | Check trap when returned to service. | ||
| 50 | 179 | 5 | M301-1 Mechanical Penthouse AHU5A | 3' | Drip | MPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Over Pressure | Bad application for a modulating pressure steam trap. | ||
| 51 | 180 | 5 | M301-1 Mechanical Penthouse AHU5A | 5' | Drip | MPS Supply | Hoffman | FT015I-3 | F&T | 15 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Over Pressure | Bad application for a modulating pressure steam trap. | ||
| 52 | 181 | 5 | M301-1 Mechanical Penthouse AHU5A | 3' | Drip | MPS Supply | Armstrong | 125A3 | F&T | 125 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | Bad application for a modulating pressure steam trap. | ||
| 53 | 183 | 5 | M301-1 Mechanical Penthouse AHU5A | 2' | Drip | LPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 54 | 184 | 5 | M301-1 Mechanical Penthouse AHU5A | 2' | Equipment | Humidifier | Armstrong | 125A3 | F&T | 125 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | Bad application for a modulating pressure steam trap. | ||
| 55 | 199 | 6 | M504 AHU1 | 6' | Drip | MPS Supply | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 56 | 210 | 6 | M504 AHU2 | 1' | Drip | MPS Supply | Armstrong | CD33 | Disc | 600 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 57 | 212 | 6 | M504 AHU2 | GL | Pump Trap | AHU1 | Armstrong | PT104 | F&T | 100 | 1.25 | 50 | 0 | 10' | X | X | X | Constant | if steel replacement pump trap cannot be found, replace with a suitable steel trap. | OK | None | ||
| 58 | 213 | 6 | M504 AHU1 | 1' | Drip | MPS Supply | Armstrong | CD33 | Disc | 600 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 59 | 223 | 6 | M502 Entrance | 6' | Equipment | Unit Heater | Armstrong | 800 | IVBT | 80 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 60 | 235 | 8 | Cart Washer | 6' | Equipment | Heat Exchanger | Spirax-Sarco | FT14HC | F&T | 363 | 1 | 50 | 0 | 0' | O | O | O | Modulating | Replace | OK | None | ||
| 61 | 236 | 8 | Cart Washer | 6' | Equipment | Heat Exchanger | Spirax-Sarco | FT14HC | F&T | 363 | 0.5 | 50 | 0 | 0' | O | O | O | Modulating | Replace | OK | None | ||
| 62 | 244 | 12 | 100001 Machine Room Cage | 9' | Drip | MPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 63 | 245 | 12 | 100001 Machine Room Cage | 9' | Drip | MPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 50 | 0 | 0' | X | X | X | Constant | Replace | OK | None | ||
| 64 | 278 | 17 | Basement Mechanical | 2' | Drip | MPS Supply | Armstrong | 800 | IVBT | 125 | 0.75 | 50 | 0 | 0' | X | O | O | Constant | Replace | Offline | Check trap when returned to service. | ||
| 65 | 150 | 4 | C220 AHU9 | 6' | Drip | LPS Supply | Armstrong | 800 | IVBT | 20 | 0.75 | 20 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 66 | 158 | 4 | C220 AHU 6A | 4' | Drip | LPS Supply | Armstrong | 800 | IVBT | 20 | 0.75 | 20 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 67 | 182 | 5 | M301-1 Mechanical Penthouse Behind AHU4A | GL | Drip | LPS Supply | Armstrong | 811 | IVBT | 20 | 0.75 | 20 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 68 | 257 | 15 | Basement Mechanical | 7' | Drip | LPS Supply | Spirax-Sarco | FT125 | F&T | 125 | 0.75 | 20 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 69 | 261 | 15 | Basement Mechanical | GL | Drip | Tank Heater | Armstrong | 812 | IVBT | 70 | 0.75 | 20 | 0 | 6' | O | O | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 70 | 7 | 1 | Chiller Plant - Chiller 1 | 8' | Drip | LPS Supply | Armstrong | 15B4 | F&T | 15 | 1 | 15 | 0 | 0 | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 71 | 9 | 1 | Surge Tank Room - Beside Brine Tank | GL | Drip | LPS Supply | Armstrong | 800 | IVBT | 150 | 0.5 | 15 | 10 | 12' | X | X | X | Constant | Replace | Leaking | Trap has failed. Wrong PMO. | ||
| 72 | 133 | 3 | M002 | 6' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 15 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 73 | 220 | 6 | M502 AHU-10 | 6' | Drip | LPS Supply | Spirax-Sarco | FT15 | F&T | 15 | 0.75 | 15 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 74 | 221 | 6 | M502 AHU-10 | 1' | Drip | Humidifier | Spirax-Sarco | SIB30/6 (6/64") | IVBT | 15 | 0.75 | 15 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 75 | 253 | 14 | PRV Station | 2' | Drip | LPS Supply | Mepco | IB12 | IVBT | 15 | 0.75 | 15 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 76 | 254 | 14 | 19-HX-1 | 2' | Equipment | Heat Exchanger | Mepco | IB13 | IVBT | 15 | 0.75 | 15 | 0 | 0' | X | X | X | Constant | Replace with a modulating pressure application steam trap. | Flooded | Bad application for a constant pressure steam trap. | ||
| 77 | 26 | 2 | Due East Stairwell 2 | 3' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 10 | 0 | 0' | O | X | O | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 78 | 54 | 2 | AHU 23 Mech Space - Condensate Skid | 7' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 10 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 79 | 55 | 2 | AHU 23 Mech Space - Condensate Skid | 7' | Drip | LPS Supply | Armstrong | 125A3 | F&T | 15 | 0.75 | 10 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 80 | 56 | 2 | AHU 23 Mech Space - AHU 23 | GL | Equipment | Steam Coil | Armstrong | 15B3 | F&T | 15 | 0.75 | 10 | 0 | 0' | X | X | X | Constant | Replace | Cold | Trap has failed. | ||
| 81 | 59 | 2 | AHU 23 Mech Space - AHU 23 | 7' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 10 | 0 | 0' | O | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 82 | 66 | 2 | SB-4 Mechanical Room | 6' | Drip | LPS Supply | Mepco | 40-215A | F&T | 15 | 0.75 | 10 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Cold | Bad application for a modulating pressure steam trap. | ||
| 83 | 76 | 2 | SB-4 Mechanical Room | GL | Equipment | Water Heater | Nicholson | NFT25-2 | F&T | 50 | 2 | 10 | 1 | 3' | X | X | X | Modulating | Replace | Blow Thru | Trap has failed. | ||
| 84 | 77 | 2 | SB-4 Mechanical Room | 1' | Drip | LPS Supply | Armstrong | 800 | IVBT | 20 | 0.75 | 10 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 85 | 78 | 2 | SB-4 Mechanical Room | GL | Equipment | Water Heater | Nicholson | NFT25-2 | F&T | 50 | 2 | 10 | 1 | 3' | X | X | X | Modulating | Replace | Blow Thru | Trap has failed. | ||
| 86 | 81 | 2 | SB-4 Mechanical Room | GL | Equipment | Water Heater | Nicholson | NFT25-2 | F&T | 50 | 2 | 10 | 1 | 3' | X | X | X | Modulating | Replace | Blow Thru | Trap has failed. | ||
| 87 | 14 | 1 | DA Room - DA PRV Station | 12' | Drip | LPS Supply | Armstrong | 15B4 | F&T | 15 | 1 (.75 pipe) | 5 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 88 | 90 | 2 | SB-6 Mechanical Room - HX Area | 7' | Drip | LPS Supply | Armstrong | 800 | IVBT | 20 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace | Blow Thru | Trap has failed. | ||
| 89 | 98 | 2 | Crawl Space East of SB-6 | 2' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 5 | 0 | 0' | O | X | X | Constant | Replace | Cold | Trap has failed. Bad application for a modulating pressure steam trap. | ||
| 90 | 100 | 2 | Crawl Space Under Stairwell 5 | 4' | Drip | LPS Supply | Armstrong | 800 | IVBT | 20 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace | Cold | Trap has failed. | ||
| 91 | 101 | 2 | Crawl Space Under Stairwell 5 | 2' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace | Cold | Trap has failed. Bad application for a modulating pressure steam trap. | ||
| 92 | 104 | 2 | Crawl Space East Stairwell 5 | 6' | Drip | LPS Supply | Armstrong | 800 | IVBT | 20 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace | Flooded | Trap has failed. | ||
| 93 | 106 | 2 | Crawl Space Southeast Stairwell 5 Along the East Wall | 4' | Drip | LPS Supply | Armstrong | 800 | IVBT | 20 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace | Flooded | Trap has failed. | ||
| 94 | 107 | 2 | Crawl Space Southeast Stairwell 5 Along the East Wall | 4' | Drip | LPS Supply | Armstrong | 800 | IVBT | 20 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace | Leaking | Trap has failed. | ||
| 95 | 109 | 2 | Crawl Space - Northeast Side of Telephone Equipment Room | GL | Drip | LPS Supply | Hoffman | FT015H3 | F&T | 15 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace | Cold | Trap has failed. Bad application for a modulating pressure steam trap. | ||
| 96 | 204 | 6 | M504 HX-1A | 6' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 97 | 225 | 6 | M503 HX | 5' | Drip | LPS Supply | Armstrong | 15B3 | F&T | 15 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace with a constant pressure application steam trap. | Blow Thru | Bad application for a modulating pressure steam trap. | ||
| 98 | 250 | 3 | Dock Unit Heater | 8' | Equipment | Unit Heater | Armstrong | 800 | IVBT | 20 | 0.75 | 5 | 0 | 0' | X | X | X | Constant | Replace | Rapid Cycling | Trap has failed. |
| Note: | X - present |
| O - missing |