This document appears to be a set of final construction plans (635_192070_Final_Construction_Documents.pdf) for the REPLACE FORT PICKENS EAST LIFT STATION federal contract opportunity, Solicitation Number 140P5224B0001.
The key details are:
- The project is to demolish the existing lift station, generator, and control panel at Fort Pickens Park in Escambia County, Florida and install a new lift station with a fiberglass wet well, 15 HP pump, 80 KW propane generator, pump control panel, and automatic transfer switch.
- The estimated price range for the single fixed-price construction contract is between $500,000 and $1,000,000.
- An organized site visit is scheduled for May 29, 2024 at 10 AM CDT.
- Bids must be submitted as sealed bids, with a required bid bond of 20% of the bid price or $3,000,000, whichever is less.
- Bids will be evaluated without discussions, and award will be made to the responsible bidder whose bid is most advantageous to the government, considering only price and price-related factors.
- The cut-off for inquiries or requests for information is COB on June 10, 2024.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFI__1_-_9_CLARIFICATIONS_0003.zip | ZIP file | |
| Sol_140P5224B0001_Amd_0003.pdf | ||
| C4_SHEET_5_OF_11_REVISION_FP-2024-EAST-Lift_Station_Revised_Site_Plan_0003.pdf | ||
| Site_Visit_Sign-In_Sheet_0003.pdf | ||
| Sol_140P5224B0001_Amd_0002.pdf | ||
| Sol_140P5224B0001_Amd_0001.pdf | ||
| Site_Visit_Agenda.pdf | ||
| BID_SCHEDULE.xlsx | XLSX spreadsheet | |
| Engineer_s_Estimated_Quantity.pdf | ||
| Atch_4_-_BID_BOND__SF24-16e.pdf | ||
| Sol_140P5224B0001.pdf | ||
| ReadThisFirst.pdf | ||
| Atch_3_-_WAGE_DETERMINATION_FL20240112.pdf | ||
| B08_Atch_2_-_SPECS_-FP-East_LS-FINAL_Contract_Documents.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RANGER
STATION
QUALITY DESIGN CERTIFICATION
STATEREGION COUNTY
NAME OF PARK
TITLE OF PROJECTREVISION
LOCATION WITHIN PARK
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
UNITED STATES
DEPARTMENT OF THE INTERIOR
RECOMMENDED:
Project Manager
APPROVED:
Superintendent
Date
Date
REPLACE EAST LIFT STATION
FORT PICKENS
SOUTHEAST ESCAMBIA FLORIDA 1 11
303760
XX
XXXXXX
CONSTRUCTION DOCUMENTS
GULF ISLAND NATIONAL SEASHORE
SITE LOCATION
SITE LOCATION
PENSACOLA, FLORIDA NOT TO SCALE
RANGER STATION
PROJECT AREA
TO PENSACOLA BEACH
TO FT PERKINS
CAMPGROUND
INDEX OF DRAWINGS
SHEET SUB SHEET TITLE OF SHEET
1 CS COVER SHEET
2 C1 GENERAL INFORMATION
3 C2 SITE ACCESS PLAN
4 C3 DEMOLITION PLAN
5 C4 SITE PLAN
6 C5 LIFT STATION DETAIL PLAN
7 C6 LIFT STATION LAYOUT
8 C7 DETAILS
9 E001 ELECTRICAL LEGEND
10 E301 EXISTING ELECTRICAL
CONDITIONS
11 E501 ELECTRICAL RISER
AutoCAD SHX Text
GULF ISLAND NATIONAL SEASHORE
AutoCAD SHX Text Sheet
AutoCAD SHX Text Mark
AutoCAD SHX Text Date
AutoCAD SHX Text Initial
AutoCAD SHX Text
DRAWING NO.
AutoCAD SHX Text
PMIS/PKG NO.
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
OF
MATCH LINE MARK
KEYNOTE
DETAIL NUMBER
DRAWING NUMBER
X
XXXX
LEGENDS AND SYMBOLS:
DETAIL
TITLES
SHEET NO. (WHERE SHOWN)
SHEET NO. (WHERE SHOWN) XXXX
X
CENTER LINE
GENERAL NOTES:
1. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE
SUPERVISION AND COORDINATION OF ALL
CONSTRUCTION PROCEDURES.
2. THESE PLANS SHOULD BE STUDIED AND USED IN
THEIR ENTIRETY AS INFORMATION VITAL TO EACH
STAGE OF CONSTRUCTION.
3. ALL WORK SHALL BE PERFORMED IN STRICT
ACCORDANCE WITH THE APPLICABLE CODES AND
ORDINANCES IN EFFECT AT THE TIME OF PERMIT. IN
THE EVENT OF A CONFLICT, THE MORE STRINGENT
REQUIREMENT SHALL GOVERN AND BE MET.
4. ALL DIMENSIONS SHALL BE VERIFIED BY THE
CONTRACTOR AND THE CONTRACTING OFFICER MUST
BE NOTIFIED OF ANY DISCREPANCIES BEFORE
PROCEEDING WITH THE WORK.
5. COORDINATE LOCATIONS AND/OR ELEVATIONS OF
DRAINS, SLABS, GROUND, ELECTRICAL PANELS,
CONTROLS, ALARMS, ETC. WITH MECHANICAL AND
ELECTRICAL CONTRACTORS AND ARCHITECTURAL
DRAWINGS.
6. WHERE A DETAIL IS SHOWN FOR ONE CONDITION, IT
SHALL APPLY TO ALL LIKE OR SIMILAR CONDITIONS,
EVEN THOUGH NOT SPECIFICALLY MARKED ON THE
DRAWINGS.
7. THE GENERAL CONTRACTOR SHALL ENSURE THAT
CONSTRUCTION ENVIRONMENT IS MAINTAINED IN
SUCH A WAY TO INHIBIT EROSION AND SEDIMENT
CONTROL.
8. THE GENERAL CONTRACTOR SHALL REMOVE
PROMPTLY AND LEGALLY ALL ACCUMULATED DEBRIS,
PROTECT ALL EXPOSED PORTIONS OF WORK FROM
ELEMENTS, AVOID OVER- LOADING STRUCTURE, AND
SECURELY STORE ALL ITEMS TO BE USED FOR
CONSTRUCTION.
9. THE GENERAL CONTRACTOR SHALL VERIFY LOCATION
OF ALL EXISTING UNDERGROUND UTILITIES PRIOR TO
EXCAVATION.
10. THE GENERAL CONTRACTOR SHALL TAKE ALL
NECESSARY PRECAUTIONARY MEASURES TO
PROTECT THE PUBLIC AND ADJACENT PROPERTIES
FROM DAMAGE THROUGHOUT CONSTRUCTION.
11. ANY EXISTING UTILITIES TO BE ABANDONED SHALL BE
PROPERLY DISCONNECTED, PLUGGED OR CAPPED, AS
REQUIRED BY CODE OR SOUND CONSTRUCTION
PRACTICE.
12. NO CHANGES, MODIFICATIONS OR DEVIATIONS SHALL
BE MADE FROM THE DRAWINGS OR SPECIFICATIONS
WITHOUT FIRST SECURING WRITTEN PERMISSION
FROM THE CONTRACTING OFFICER.
13. WHERE LACK OF INFORMATION, OR ANY DISCREPANCY
SHOULD APPEAR IN THE DRAWINGS OR
SPECIFICATIONS, REQUEST WRITTEN
INTERPRETATION FROM THE CONTRACTING OFFICER
BEFORE PROCEEDING WITH THAT PORTION OF THE
WORK.
14. WHEN A SYSTEM OR ASSEMBLY IS SPECIFIED, ALL
A
A/E ARCHITECT/ENGINEER
ABV ABOVE
ADJ ADJUSTABLE
ADMIN ADMINISTRATION
AFF ABOVE FINISH FLOOR
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZED
ARCH ARCHITECT (URAL)
AUTO AUTOMATIC
AVG AVERAGE
& AND
@ AT
B
BLDG BUILDING
BD BOARD
B.O. BOTTOM OFF
C
CAB CABINET
CJ CONTROL JOINT
CLG CEILING
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CONTRACTING OFFICER
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS(ATION)
COR CONTRACTING OFFICER
REPRESENTATIVE
D
DBL DOUBLE
DEPT DEPARTMENT
DIA DIAMETER
DIFF DIFFUSER
DIM DIMENSION
DIV DIVISION
DN DOWN
DSC DENVER SERVICE CENTER
DTL DETAIL
DWG DRAWING
E
EA EACH
ELEC ELECTRICAL
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
ELEV ELEVATION
ENTR ENTRANCE
EQ EQUAL
EQUIP EQUIPMENT
EXIST EXISTING
EXP JT EXPANSION JOINT
EXPS EXPOSE(D)
EXT EXTERIOR
F
FAB FABRICATION
FD FLOOR DRAIN
FE FIRE EXTINGUISHER
FFE FINISHED FLOOR
ELEVATION
FFL FINISHED FLOOR LINE
FIN FINISH
FLR FLOOR(ING)
FRP FIBER REINFORCED PANEL
FRT FIRE RETARDANT TREATED
FT FOOT/FEET
FURN FURNITURE
G
GA GAUGE
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GL GLASS
GPM GALLONS PER MINUTE
H
H HIGH
HC HANDICAP
HDWR HARDWARE
HM HOLLOW METAL
HP HORSE POWER
HT HEIGHT
HVAC HEATING, VENTILATION AND
AIR CONDITIONING
I
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J
JAN JANITOR
JT JOINT
L
LAV LAVATORY
L LONG
LVT LUXURY VINYL TILE
M
MAINTENANCE
MAT'L MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEZZ MEZZANINE
MFR MANUFACTURER
MISC MISCELLANEOUS
MIN MINIMUM
MO MASONRY OPENING
MOD MODIFICATION
MTD MOUNTED
MTL METAL
N
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NPS NATIONAL PARK SERVICE
NTS NOT TO SCALE
O
OC ON CENTER
OPNG OPENING(S)
OPP OPPOSITE
OVHD OVERHEAD
P
PL PLATE
PLBG PLUMBING
PLYWD PLYWOOD
PMIS PROJECT MANAGEMENT
INFORMATION SYSTEM
PMIS NO PROJECT PMIS NUMBER
PNL PANEL
PREFAB PREFABRICATED
PREFIN PREFINISHED
PT PRESSURE TREATED
Q
QTY QUANTITY
R
R, RAD RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REINF REINFORCE (D) (ING)
REQD REQUIRED
REV REVISION
RM ROOM
RO ROUGH OPENING
RTU ROOF TOP UNIT
S
SIM SIMILAR
SPEC SPECIFICATION
SPK SPEAKER
SQ SQUARE
SS STAINLESS STEEL
STD STANDARD
STRUCT STRUCTURAL
STL STEEL
STO STORAGE
SUSP SUSPENDED
T
TBD TO BE DETERMINED
TEL TELEPHONE
TEMP TEMPERED
THK THICK
TLT TOILET
T.O. TOP OF
T & G TONGUE AND GROOVE
TYP TYPICAL
TV TELEVISION
U
UNFIN UNFINISHED
UNO UNLESS NOTED OTHERWISE
V
VAR VARIES
VERT VERTICAL
VIF VERIFY IN FIELD
W
W/ WITH
W WIDTH
WC WATER CLOSET
WD WOOD
W/O WITHOUT
WTRPRF WATERPROOFING
ABBREVIATIONS:
DEFINITIONS:
A.
B.
C.
DIMENSIONS NOTED AS "CLEAR" SHALL BE FROM FINISHED
FACE TO FINISHED FACE.
"TYPICAL" MEANS TYPICAL FOR ALL SIMILAR CONDITIONS, UNO.
WHEREVER THE TERM "OR EQUAL" IS USED, IT SHALL MEAN
EQUAL OR BETTER PRODUCT AS APPROVED BY THE
CONTRACTING OFFICER.
WORK.
14. WHEN A SYSTEM OR ASSEMBLY IS SPECIFIED, ALL
NECESSARY PARTS AND MATERIALS REQUIRED FOR A
COMPLETE INSTALLATION/SYSTEM SHALL BE
INSTALLED ACCORDING TO THE MANUFACTURERS
INSTRUCTIONS.
15. COORDINATE WITH ALL TRADES THE LOCATIONS OF
SLEEVES OR OTHER PRESET ACCESSORIES
INVOLVING OTHER TRADES.
16. THE GENERAL CONTRACTOR WILL BE HELD SOLELY
RESPONSIBLE FOR THE COMPLETION OF ALL WORK
SHOWN OR REASONABLY IMPLIED BY THESE
DRAWINGS AND/OR SPECIFICATIONS. THE GENERAL
CONTRACTOR SHALL CONFIRM ALL DIMENSIONS AND
CONDITIONS AT THE SITE AND SHALL IMMEDIATELY
NOTIFY THE CONTRACTING OFFICER IN WRITING OF
ANY DISCREPANCIES.
17. DETAILS TAKE PRECEDENCE OVER PLANS AND
ELEVATIONS - LARGER SCALE DRAWINGS TAKE
PRECEDENCE OVER SMALLER SCALE DRAWINGS.
18. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE
FOR OBTAINING ALL REQUIRED PERMIT APPROVALS
PRIOR TO THE COMMENCEMENT OF ANY WORK.
19. THE GENERAL CONTRACTOR SHALL FURNISH COPIES
OF PERMITS, INSPECTIONS, AND CERTIFICATES TO
THE CONTRACTING OFFICER AS REQUESTED ALONG
WITH FIRST APPLICATION FOR PAYMENT.
20. THE GENERAL CONTRACTOR SHALL PROVIDE ALL
PERMITS AND CLOSE OUT DOCUMENTS TO
CONTRACTING OFFICER UPON COMPLETION OF
PROJECT.
21. THE DESIGN OF THIS PROJECT IS BASED UPON
INFORMATION PROVIDED BY NATIONAL PARK SERVICE
THROUGH EXISTING DRAWINGS AND ON-SITE
OBSERVATION. VERIFY ALL EXISTING DIMENSIONS AND
CONDITIONS PRIOR TO COMMENCING WORK. IF
EXISTING CONDITIONS ARE NOT AS DEPICTED OR
ANTICIPATED, NOTIFY THE CONTRACTING OFFICER
IMMEDIATELY UPON DISCOVERY AND DO NOT
PROCEED WITHOUT APPROVAL. IF CONTRACTOR
PROCEEDS WITHOUT APPROVAL, THE CONTRACTOR
ACCEPTS FULL LIABILITY FOR THAT PORTION OF
CONSTRUCTION.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
OF
TITLE OF PROJECT
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
06/08/2023
J. DOWNEY
K.BATES
L.HALE
303760
XXXXXX
XX
GULF ISLAND NATIONAL SEASHORE
GENERAL INFORMATION
REPLACE EAST LIFT STATION
C1
RANGER
STATION
TO FORT PICKENS
CAMPGROUND
TO PENSACOLA BEACH
SCALE A
SCALE OF FEET
4002000200
06/08/2023
J. DOWNEY
K.BATES
L.HALE
303760
XXXXXX
XX
GULF ISLAND NATIONAL SEASHORE
SITE ACCESS PLAN
REPLACE EAST LIFT STATION
C2
NOTES
1. APPROXIMATE 100'x75' AREA FOR CONTRACTOR LAYDOWN AND STAGING. EXACT LOCATION
TO BE APPROVED BY THE CONTRACTING OFFICER, TEMPORARY FENCE TO BE INSTALLED BY
THE CONTRACTOR FOR PROTECTION OF MATERIALS AND EQUIPMENT. CONTRACTOR SHALL
REPAIR AREA TO ITS ORIGINAL CONDITION AT THE END OF CONSTRUCTION. ACCESS FOR
CONSTRUCTION ACTIVITIES SHALL BE MONITORED BY THE CONTRACTING OFFICER IF THE
GROUND IS WET AND SATURATED.
2. CONTRACTOR EQUIPMENT AND VEHICLES SHALL BE STORED AND PARKED WITHIN THE
LAYDOWN AND STAGING AREA.
3. ALL ON-SITE ROAD SURFACE IS MACADAM UNLESS OTHERWISE STATED ON THE DRAWINGS.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
OF
TITLE OF PROJECT
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
SCALE A
SITE ACCESS PLAN VIEW
C2
RANGERSCALE OF FEET
10505
NOTES
1. EXISTING CHEMICAL FEED LINE TO BE REMOVED, NOT ABANDONED IN PLACE.
2. ALL COMPONENTS BEING REMOVED TO BE DISPOSED OF BY THE CONTRACTOR
UNLESS OTHERWISE INSTRUCTED BY THE CONTRACTING OFFICER.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
OF
TITLE OF PROJECT
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
06/08/2023
J. DOWNEY
K.BATES
L.HALE
303760
XXXXXX
XX
GULF ISLAND NATIONAL SEASHORE
DEMOLITION PLAN
REPLACE EAST LIFT STATION
C3
DEMOLITION PLAN VIEW
C3
AutoCAD SHX Text
EXISTING 1500 GAL. BIOXIDE TANK AND CONCRETE PAD TO BE REMOVED
AutoCAD SHX Text
EXISTING 50 KW GENERATOR WITH SUB FUEL TANK TO BE REMOVED CONCRETE PAD TO REMAIN
AutoCAD SHX Text
EXISTING FIBERGLASS WET WELL AND APPURTENANCES TO BE REMOVED
AutoCAD SHX Text
EXISTING FIBERGLASS VALVE BOX TO BE REMOVED
AutoCAD SHX Text
EXISTING CONTROL PANEL TO BE REMOVED CONCRETE PAD TO REMAIN.
AutoCAD SHX Text
EXISTING 6' HIGH WOODEN FENCE TO BE REMOVED
AutoCAD SHX Text
EXISTING ACCESS GATE TO BE REMOVED
AutoCAD SHX Text EXISTING 3" HDPE FORCEMAIN IN TO REMAIN. CONTRACTOR TO INSTALL BY-PASS VALVING AND RECONNECT TO NEW LIFT STATION.
AutoCAD SHX Text
EXISTING CHEMICAL FEED LINE TO BE REMOVED
AutoCAD SHX Text EXISTING 6" PVC GRAVITY LINE IN TO REMAIN. CONTRACTOR TO RECONNECT TO NEW LIFT STATION.
AutoCAD SHX Text EXISTING 4" HDPE FORCEMAIN OUT TO REMAIN. CONTRACTOR TO RECONNECT TO NEW LIFT STATION.
AutoCAD SHX Text EXISTING 4" PVC GRAVITY LINE IN TO REMAIN. CONTRACTOR TO RECONNECT TO NEW LIFT STATION.
PROPOSED 6' DIAMETER FIBERGLASS WETWELL
CONTRACTOR TO PROVIDE CONNECTIONS TO
EXISTING UTILITIES INCLUDING TWO (2) GRAVITY
CONNECTIONS AND TWO (2) PRESSURE PIPE
CONNECTIONS
NEW 12'x18' CONCRETE
PAD
SEE SHEET C6 FOR LIFT
STATION LAYOUT FOR
APPROXIMATE PIPED
CONNECTIONS
o o o o o o o o o o o o o o o o o o o o o o o o ooooooooooo
NEW 10' WIDE GRAVEL
ACCESS ROAD
oo o o
NEW 12' WIDE CHAIN
LINK GATE
NEW CONTROL PANEL
TO BE PLACED ON
EXISTING CONCRETE
PAD
NEW 50 KW
GENERATOR TO BE
PLACED ON EXISTING
CONCRETE PAD
NEW CHAIN LINK FENCE
NEW 1'x1' CONCRETE
PAD WITH POTABLE
WATER HOSE BIB
CONNECTING LINES SHOWN FOR REFERENCE.
CONTRACTOR TO FIELD LOCATE GRAVITY AND
PRESSURE PIPES TO DETERMINE CONNECTION
POINTS TO NEW WET WELL.
NEW CONCRETE PAD
FOR 250 GALLON
GENERATOR FUEL
STORAGE TANK
SCALE ASCALE A
SITE PLAN
C4
SCALE OF FEET
NOTES
1. 4" PF FLORIDA DEPARTMENT OF TRANSPORTATION (FDOT) #57 STONE, 60 MIL
GEOFABRIC WEED CONTROL LINER UNDER STONE PLACED AT ALL NON-PAVED
AREAS WITHIN CHAIN LINK FENCE
2. SEE SHEETS C5 & C6 FOR LIFT STATION PLAN AND SECTION DETAILS.
3. SEE ELECTRICAL PLANS FOR ELECTRICAL CONNECTIONS
4. CONTRACTOR SHALL BRING IN SAND FILL AS REQUIRED TO MATCH ORIGINAL
GRADE.
5. CONTRACTOR TO PROVIDE TEMPORARY PUMPING OF SANITARY SEWER TO MAINTAIN
OPERATIONS THROUGHOUT CONSTRUCTION. TEMPORARY PUMPING SHALL BE
SUBMITTED AND APPROVED BY THE CONTRACTING OFFICE PRIOR TO USE.
6. APPROXIMATELY 60' IN 1" PVC MAY BE NEEDED FOR WATER LINE EXTENSION.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
OF
TITLE OF PROJECT
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
06/08/2023
Jim Downey
Ken Bates
Lee Hale
303760
XXXXXX
XX
GULF ISLAND NATIONAL SEASHORE
SITE PLAN
REPLACE EAST LIFT STATION
C4
10505
32'-8"
18'-0"
12'-0"
40'-0"
35'-0"
NOT TO SCALE
PUMPS OFF FLOAT SWITCH EL. 4.50 FT
FOUR SST OPTI-FLOAT WEIGHTS
WELDED TO BOTTOM OF POLE
FOR STABILITY
TYPE 316 STAINLESS STEEL
COMMON BASE PLATE SHALL
BE LAMINATED TO BOTTOM
9" THICK FDOT #57 STONE
(COMPACT TO 95% DENSITY
LEAD PUMP ON FLOAT SWITCH EL. 5.50 FT
LAG PUMP ON FLOAT SWITCH EL. 6.50 FT
HIGH LEVEL ALARM FLOAT SWITCH EL. 7.50 FT
FLOAT CABLE/POLE ASSEMBLY
SST SWAY BRACE, TYPICAL
1. THE PUMPS SHALL HAVE A 5 YEAR 100% PARTS AND LABOR WARRENTY AS PROVIDED BY THE PUMP
MANUFACTURER.
2. PRESSURE GAUGE SIZED TO READ NO MORE THAN 1-1/2 TIMES THE MAXIMUM PRESSURE PUMP PROVIDES AT DEAD
HEAD.
3. FLOAT POLE ASSEMBLY CONSISTS OF A 1” SST PIPE WITH SST LIFTING CHAIN MOUNTED TO WELED EYE. CHAIN SHALL BE LONG ENOUGH TO POSITION THE FLOATS AT THE REQUIRED DEPTH. FIBER OPTIC “OPTI-FLOATS” ARE WEIGHTLESS AND MOUNT TO POLE WITH PIPE CLAMPS. ONE SST WEIGHT FOR EACH FLOAT IS WELDED TO BOTTOM
OF FLOAT POLE FOR STABILITY.
4. ALL PIPE AND FITTINGS MUST BE 3” DIAMETER SCH 40 TYPE 316 STAINLESS STEEL W/ MINIMUM 125 LB FLANGES.
5. VALVES MUST BE 316 STAINLESS STEEL.
6. PIPE DISCHARGE PENETRATIONS FROM WET WELL MUST BE VIA INTERGRAL FIBERGLASS SLEEVES WITH RUBBER
LINK SEALS AND SST HARDWARE.
7. KSB PUMP GUIDE RAIL SYSTEM MUST BE UTILIZED AND SHALL INCLUDE: 2”x3” BASE ELBOWS OF CAST “WHITE
CHROMIUM IRON” WITH 5 YEAR ABRASION WARRENTY (STANDARD CAST IRON WILL NOT BE ACCEPTABLE), DUAL 2” SCH 40 TYPE 316 STAINLESS STEEL GUIDE RAILS, PUMP “CLAWS” THAT WRAP AROUND PIPE (RAIL CLAWS THAT FIT
BETWEEN RAIL PIPE WILL NOT BE ACCEPTABLE).
8. KSB MIXER MAST MUST BE INTEGRATED INTO NEW WET WELL AND MUST BE HEAVY-DUTY 2”x2” SQUARE TYPE 316 SST WITH RUBBER COMPRESSION INSERT UPPER MAST BRACKET, AND LOWER BRACKET SECURED TO COMMON
BASE PLATE.
9. HATCH COVERS BY USFF: ODOR REDUCTION GASKETED WET WELL HATCH SHALL BE 1/4” THICK DIAMOND PLATE ALUMINUM, ROUND WITH DOUBLE LEAFS AND SAFETY GRATES. EACH LEAF SHALL HAVE A SLAM LOCK. VALVE BOX SHALL BE 48”x48” SQUARE, DOUBLE-DOOR WITH SLAM LOCK (NO SAFETY GRATES).
10. EXISTING CONTROL PANEL AND ELECTRICAL BACKBOARDS/RACK TO REMAIN.
11. EXISTING PUMPS, MIXER, AND FLOATS SHALL BE SUBMITTED TO CERTIFIED KSB REPAIR SHOP “GULF COAST
ELECTRIC MOTOR” LOCATED IN PENSACOLA, FL OR APPROVED EQUAL TO BE INSEPECTED, CLEANED. PUMPS AND MIXER SHALL BE PRESSURE WASHED HAVE KSB PAINT APPLIED AS NEEDED TO COVER ANY SCRATCHES AND TO MAKE LOOK “LIKE NEW”. AFTER BEING CLEANED PUMPS, MIXER AND FLOTAS SHALL BE SUBMITTED TO NPS FOR
STORAGE.
12. REPAIR KITS AND REPLACEMENT MIXER SHALL BE SUBMITTED TO NPS AS PART OF THE PROJECT.
13. ELEVATIONS SHOWN AS APPROXIMATE. NO SURVEY HAS BEEN PROVIDED. CONTRACTOR TO VERIFY ALL
ELEVATIONS AND FIELD ADJUST TO MEET EXISTING CONDITIONS FOR PIPE PENETRATIONS.
14. FLOAT ELEVATIONS MAY BE ADJUSTED AS NEEDED. THE FOLLOWING HEIGHTS ARE THE REQUIRED FLOAT HEIGHTS
MEASURED FROM THE BOTTOM OF THE WETWELL.
14.1. LEAD PUMP ON: 2'-0"
14.2. LAG PUMP ON: 3'-0"
14.3. HIGH LEVEL ALARM: 4'-0"
14.4. HIGH LEVEL ALARM SHOULD BE AT LEAST 6" BELOW LOWEST GRAVITY INVERT INTO THE WET WELL.
15. UPON FINAL DEPTH DETERMINATION MADE BY CONTRACTOR, CONTRACTOR TO PROVIDE BUOYANCY CALCULATIONS AND MUST INSTALL PROPER COUNTERMEASURES TO PREVENT UPLIFT. DESIGN FOR UPLIFT PREVENTION MUST BE SIGNED AND SEALED BY A STATE OF FLORIDA REGISTERED PE. FOR COST ESTIMATING PURPOSES, AN 8' DIAMETER
CONCRETE SLAB 2.0' THICK AS THE BASED OF THE WET WELL MAY BE CONSIDERED.
S A
FE
TY
G R
A
TE
BOTTOM EL: 2.00 FT.
WETWELL DEPTH
APPROX. 10'
6" DIA. x 12' DEEP FRP WET WELL
WITH 12" [1:1] PITCHED. BENCHED
BOTTOM AND 6" FLANGE
KSB 1.7 HP AMAMIX MIXER
MODEL C222/14DG MOUNTED
ON 2" SQ TYPE 316 SST MAST
SST LIFTING CHAIN
TYPICAL FOR 2 PUMPS
3" SCH 40 TYPE 316 SST
DISCHARGE PIPING (TYP.)
2" SCH 40 TYPE 316 SST
GUIDE RAIL AS PER PUMP
MANFACTURER
SST HANGER BAR FOR
FLOAT AND MIXER
CABLES, AND PUMP
CORDS AND CHAINS (TYP.)
MIXER SHALL HAVE RUBBER
COMPRESSION INSERT
UPPER MAST BRACKET
TOP EL: 6" ABOVE EXISTING GRADE ELEVATION
DOUBLE-DOOR SPLIT HATCH COVER OF
H2O TRAFFIC RATED ALUMINUM
DIAMOND PLATE WITH TYPE 316 SST
HARDWARE, ODOR-CONTROL GASKET,
AND SAFETY GRATES WITH SAFETY
ORANGE POWDER COAT
BANJO VC330
ANTI-VORTEX VENT CAP
WITH BUG SCREEN ON 3"
SST VENT PIPE RISER
3" SS PLUG VALVE
NOTE:
FIBERGLASS WET WELL MUST SHIP COMPLETELY ASSEMBLED AND FOLLOWING ITEMS INTEGRATED: PIPE, FITTINGS, VALVES, PRESSURE BRACES, GAUGES, BRACES, BRACKETS, KSB GUIDE RAIL SYSTEMS, KSB MIXER MAST SYSTEM, ODOR REDUCTION GASKETED HATCH COVERS, 3" SST VENT PIPE WITH PVC "BANJO VENT" WITH SST BUG SCREEN, CONTAINMENT AREA DRAIN CONNECTION. IN ORDER TO ASSURE QUALITY, THE WET WELL AND VALVE BOX MUST BE SUPPLIED BY "FIBERGLASS TANK SOLUTIONS." SUBMITTAL DATA FROM FIBERGLASS TANK SOLUTIONS WILL INCLUDE STRUCTURAL AND ANTI-FLOTATION CALCULATIONS STAMPED BY THIRD PARTY STATE OF FLORIDA LICENSED ENGINEER AND WILL INCLUDE CONCRETE BASIN
DESIGN.
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
OF
TITLE OF PROJECT
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
4" HDPE SANITARY
FORCEMAIN - SEE C6 FOR
FLOW METER AND
EMERGENCY BYPASS PIPING
TWO (2) KSB 15 HP SUBMERSIBLE
WASTEWATER PUMPS
LIFT STATION SECTION VIEW
C5
06/08/2023
J. DOWNEY
K.BATES
L.HALE
303760
XXXXXX
XX
GULF ISLAND NATIONAL SEASHORE
LIFT STATION DETAIL
REPLACE EAST LIFT STATION
C5
3" SS CHECK VALVE
3" SS TEE WITH MOUNTED
PRESSURE GAUGE
4" PLUG VALVE W/
FIBERGLASS REINFORCED
VALVE VAULT AND TRAFFIC
RATED NDS LID.
4" HDPE CLEANOUT
W/ ZURN SST FINISH
COVER
6" THICK 4,000 PSI CONCRETE PAD
REINFORCED WITH W2.9XW2.9, W.W.F, ASTM
GRADE 60 STEEL 2" FROM BOTTOM OF PAD
(SEE SHEET C3 FOR SIZING)
4" HDPE DR 11 WELD ON
STEEL TRANSITION FITTING
EXISTING 3" SST FORCEMAIN
TO REMAIN. CONTRACTOR TO
RECONNECT TO NEW LIFT STATION
EXISTING 6" PVC GRAVITY
PIPE TO REMAIN. CONTRACTOR TO
RECONNECT TO NEW LIFT STATION
EXISTING 4" PVC GRAVITY
PIPE TO REMAIN. CONTRACTOR TO
RECONNECT TO NEW LIFT STATION
3" SS CHECK VALVE
3" SS PLUG VALVE
3" SS TEE MOUNTED PRESSURE GAUGE
4" SST PLUG VALVE
4" SST PLUG VALVE
PROPOSED 3" SST PLUG VALVE
4" HDPE EMERGENCY BYPASS
12'X18' CONCRETE PAD
EXISTING CONTROL PANEL PAD TO REMAIN
(ABOVE GROUND PANEL TO BE REMOVED AND
REPLACED WITH ENTIRELY NEW STRUCTURE)
KSB 15 HP SUBMERSIBLE
WASTEWATER PUMP
KSB 15 HP SUBMERSIBLE
WASTEWATER PUMP
KSB 1.7 HP AMAMIX MIXER
MODEL C222/14DG MOUNTED
ON 2" SQ TYPE 316 SST MAST
DOUBLE-DOOR SPLIT HATCH COVER OF
H2O TRAFFIC RATED ALUMINUM
DIAMOND PLATE WITH TYPE 316 SST
HARDWARE, ODOR-CONTROL GASKET,
AND SAFETY GRATES WITH SAFETY
ORANGE POWDER COAT (SEE DETAIL)
4" MAGNETIC-INDUCTIVE
FLOW METER
RATED FOR 30 GPM-200 GPM MIN.
W/ METER BOX
VALVING ORDER MATCHES
OTHER PUMP ALIGNMENT
4" PLUG VALVE
(BURIED VALVE)
W/ VALVE
BOX
4" SST CLEANOUT
6' DIAMETER FIBERGLASS
WET WELL
1'x1' CONCRETE PAD
24" TALL STEEL HOSE BIB STAND
PIPE WITH STANDARD WATER
HOSE CONNECTION
SST TO HDPE TRANSITION
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
OF
TITLE OF PROJECT
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
06/08/2023
J. DOWNEY
K.BATES
L.HALE
303760
XXXXXX
XX
GULF ISLAND NATIONAL SEASHORE
LIFT STATION LAYOUT
REPLACE EAST LIFT STATION
C6
NOT TO SCALE
LIFT STATION PLAN VIEW
C6
NOTES:
1. EMERGENCY BYPASS IS NOT ABLE TO SUSTAIN FULL DESIGN FLOW. THE FLOW RATE WILL BE REDUCED, BUT COULD PROVIDE RELIEF OF
ALTERNATIVE MEANS OF FLOWING WASTEWATER IN CASE OF EMERGENCY OUTAGE AT THIS LIFT STATION. FLOW METER IS DOWNSTREAM OF
EMERGENCY BYPASS FOR ACCURATE CALCULATION OF FLOW IN EMERGENCY SITUATIONS.
2. ALL VALVE VAULTS AND METER BOX SHALL HAVE TRAFFIC RATED LIDS.
SST OIL-FILLED,
BACK-MOUNT
PRESSURE GAUGE (SEE
NOTE 2)
SST DIAPHRAGM
ASSEMBLY FOR GAUGE
DAMPENING
1/4" SST BALL
VALVE FOR
GAUGE ISOLATION
CHECK VALVE COVER
SHOWN ROTATED WITH
LEFT SIDE COVER AND
SAFETY GRATE OPEN
GRATING SHALL HAVE
SAFETY ORANGE
POWDER COAT FINISH
NOT TO SCALE
PRESSURE GAUGE DETAIL
C6
NOT TO SCALE
WETWELL HATCH DETAIL
C6
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
OF
TITLE OF PROJECT
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
06/08/2023
J. DOWNEY
K.BATES
L.HALE
303760
XXXXXX
XX
GULF ISLAND NATIONAL SEASHORE
DETAILS
REPLACE EAST LIFT STATION
C7
NOTES:
1. BRACING SYMMETRICAL ABOUT CORNER AND INTERMEDIATE POSTS.
2. FASTEN THE BOTTOM TENSION WIRE WITHIN THE BOTTOM 6" OF FABRIC
3. ALL TENSION WIRE SHALL MATCH FENCE FABRIC
4. TENSION WIRE SHALL BE SECURELY FASTENED TO THE CORNER POSTS, AND
SHALL BE TAUT AND FREE OF SAG.
5. FENCE INSTALLER TO PROVIDE DETAIL FOR GROUNDING FENCE FOR
LIGHTING AT ALL FOUR CORNERS.
6. FENCING SHALL PROVIDE 1' WIDE, 4" THICK STRIP OF CONCRETE WITH THE
FENCE CENTERED OVER THE STRIP TO PROVIDE EASIER MAINTENANCE FOR
PARK STAFF. CONCRETE TO BE REINFORCED WITH W2.9XW2.9 W.R.F.
3/8" Ø
TRUSS
ROD
HOOK
BOLT
STRETCHER
BOLT
TRUSS
ROD
TOP
HINGE
GATE
POST
BOTTOM
HINGE
GATE FRAME AND
SOCKET BALL
SLOPE TO
GRADE
1" (TYP.)
GATE
FRAME
FORK
CATCH
LOCK
KEEPER
FOR
PADLOCK
PLUNGER
ROD
GATE
FRAME
UPPER
FORK
LOCK
KEEPER
GUIDE
8" TRUSS
ROD
TRUSS
TIGHTENER
SEE DETAIL
ON THIS
SHEET
STRETCHER
BAR
TRUSS
ROD
END CORNER OR
INTERMEDIATE POST
(SEE NOTE 1)
LINE
POST
WITH
BRACE
LINE POST WITH BRACE
3000 PSI
CONCRETE
(TYP.)
TOP RAIL GATE
POST
PLUNGER
ROD
BOTTOM GATE
HINGE, SEE
DETAIL ON THIS
SHEET
CATCH
BLOCK
10'-0" MAX 10'-0" MAX
7'-0"
FABRIC
HEIGHT
1" MAX
8" DIA. MIN.
2'-0"
MIN
NOT TO SCALE
CHAINLINK FENCE ELEVATION VIEW
C7
NOT TO SCALE
TYPICAL FABRIC TIE DETAIL
C7
NOT TO SCALE
TRUSS TIGHTENER DETAIL
C7
NOT TO SCALE
TYPICAL GATE LOCKING DEVICE
C7
NOT TO SCALE
GATE HINGE DETAIL
C7
TABLE 1
GATE LEAF WIDTHS GATE POST FOOTING SIZE GATE FRAME SIZE
6'-0" WIDE 1'-0" DIA. X 3'-0" DEEP 1.900" O.D., 2.28 LBS/FT
TABLE 2
FABRIC HEIGHT END CORNER OR INTERMEDIATE
POST FOOTING SIZE LINE POSTS FOOTING SIZE
7-0" 1'-0" DIA. X 3'-6" DEEP 10" DIA. X 3'-6" DEEP
OR AS SPECIFIED
FILL MATERIAL IN 12" LIFTS
PLACE AND COMPACT COMMON
4'MIN. FOR SHEETED
4/3 OD+18"
6" BEDDING
PRIMARY ZONE
SECONDARY ZONE
FINAL BACKFILL
SHEETED UNSHEETED
SIDE SLOPE PERSHEETING
AS REQ'D
FINISH GRADE
OSHA REQUIREMENTS
3M MARKER TAPE
OD
(36" MIN.)
SPRINGLINE OF PIPE
24"
MAX DEPTH 18 INCHES
NOTES:
1. BEDDING SHALL BE #57 STONE IF PIPE BEDDING IS YIELDING
2. PRIMARY & SECONDARY ZONES SHALL BE INDIVIDUALLY COMPACTED LAYERS OF CLEAN
FILL
3. COMPACTION OF BACKFILL BENEATH PAVEMENT SHALL BE 98% OF AASHTO T-180, ALL
OTHER AREAS SHALL BE 95% OF AASHTO T-180 UNLESS OTHERWISE REQUIRED BY AN
AUTHORITY HAVING JURISDICTION
4. PLACE APPROVED 3M MARKER TAPE OR EQUAL DIRECTLY ABOVE THE CENTERLINE OF
THE PIPE.
5. SLOPES, BENCHING, OR SHORING SHALL BE PER OSHA REQUIREMENTS
6. SHEETING SHOWN FOR REFERENCE. CONTRACTOR TO FOLLOW ALL OSHA AND OTHER
SAFETY STANDARDS WHEN USING SHEETING.
NOT TO SCALE
TYPICAL PIPE TRENCH
C7
NORMAL EXCAVATION LIMIT FOR
COMPACTED FILL BEDDING
EXCAVATION LIMITS FOR DRY
UNDISTURBED EARTH BEDDING
A AMPS, AMPERES
AB AS-BUILT
AC ALTERNATING CURRENT
AFCI ARC FAULT CIRCUIT
INTERRUPTOR
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
AL ALARM
AM AMMETER
AT ASTRONOMIC TIMER
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
C CONDUIT
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CL CENTER LINE
CLG CEILING
CLR CLEARANCE
COR THE CONTRACTING OFFICER
REPRESENTATIVE
CPVC CHLORINATED POLYVINYL
CHLORIDE
CT CURRENT TRANSFORMER
CTR COUNTER
CU COPPER
DC DIRECT CURRENT
DIA DIAMETER
DS DISCONNECT SWITCH
EA EACH
ELEC ELECTRICAL
EMER EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ES EMERGENCY STOP
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FC FULLY CLOSED
FLA FULL LOAD AMPS
FO FULLY OPEN
FU FUSE
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT
INTERRUPTOR
GND GROUND
HP HORSEPOWER
HZ HERTZ
IMC INTERMEDIATE METAL CONDUIT
JB JUNCTION BOX
KVA KILO-VOLT AMP(S)
KW KILO-WATT
KWH KILO-WATT HOUR(S)
LTG LIGHTING
LTS LIGHTS
LO LOCKOUT
MC METAL-CLAD CABLE
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MFR MANUFACTURER
MLO MAIN LUGS ONLY
MTD MOUNTED
MTG MOUNTING
MTR METER
MTS MANUAL TRANSFER SWITCH
N NEUTRAL
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL
CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATED
NO NORMALLY OPEN
NOM NOMINAL
NTS NOT TO SCALE
OC OVERCURRENT
OCPD OVERCURRENT
PROTECTION DEVICE
OD OUTSIDE DIAMETER
OL OVERLOAD
P POLE
PB PUSHBUTTON
PH PHASE
PNL PANELBOARD
POE POWERED OVER
ETHERNET
PVC POLYVINYL CHLORIDE
QTY QUANTITY
RA REMOTE ANNUNCIATOR
RCC RELAY CONTROL CABINET
REF REFERENCE
REQD REQUIRED
RMC RIGID METAL CONDUIT
SW SWITCH
SWB SWITCHBOARD
SWGR SWITCHGEAR
UC UNDER COUNTER
UL UNDERWRITERS
LABORATORY
UNO UNLESS NOTED
OTHERWISE
V VOLT(S)
VA VOLT-AMPERE(S)
VFD VARIABLE FREQUENCY
DRIVE
VSD VARIABLE SPEED DRIVE
W WATT(S)
WP WATER PROOF
XFMR TRANSFORMER
ABBREVIATIONS:
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/9
/2
:2
:1
P M
ELECTRICAL LEGENDE001
J. SERRADAS
J. SERRADAS
J. MORGAN
9 11
EAST LIFT STATION XX
XXXXXX
GUIS 303760
GULF ISLAND NATIONAL SEASHORE6/8/2023
E001
1 WORK SITE
PROJECT SITE
Jeff Morgan FL Stamp - JKM Simple
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/9
/2
:2
:1
P M
EXISTING ELECTRICAL
CONDITIONSE301
J. SERRADAS
J. SERRADAS
J. MORGAN
10 11
EAST LIFT STATION XX
XXXXXX
GUIS 303760
GULF ISLAND NATIONAL SEASHORE6/8/2023
E301
1 METER,SERVICE DISC, ATS
E301
2 ATS, GEN. DISC, AUTO-DIALER
E301
3 EXISTING DIESEL GENERATOR
E301
4 PUMP CONTROLLER
E301
5 PANEL SERVING AREA
E301
6 PANEL, SPD, PUMP CONTROLLER
NOTE: THIS SHEET IS PROVIDED FOR REFERENCE OF EXISTING CONDITIONS AND EQUIPMENT LAYOUT.
M
ATS
200A
240V/120V 3Ø, 4W
EXISTING
PANEL LP
60A MCB
208/120V 3Ø, 4W
7 8
50KW
GENERATOR
M
5 6
7 9
BELOW GRADE
20 20
EXISTING
CONCRETE PAD
EXISTING STEEL MOUNTING
CHANNEL SYSTEM
6 7
EXISTING
CONCRETE PAD
EXISTING STEEL MOUNTING
CHANNEL SYSTEM
6 7
LIFT STATION PUMP
CONTROL PANEL
120/240V, 1PH, 4W
C O
N T
R O
L S
P
-2 A
P
-1 A
P
-6 A
P
-6 A
P
-1 A
P
-1 A
15 HP
PUMP
15 HP
PUMP
MIXER
11 11 12
TO ATS
LOCATED IN WET WELL
212121
A. REMOVE EXISTING PUMPS AND WELL ASSEMBLIES, ELECTRICAL
CONNECTIONS, CONDUIT, AND WIRING MARKED FOR DEMO BACK TO SOURCE
B. ALL UNDERGROUND CONDUIT TO BE BURIED A MINIMUM OF 24 INCHES
BELOW GRADE.
C. MINIMIZE OUTAGES, COORDINATE ANY REQUIRED OUTAGES WITH
CONTRACTING OFFICER.
D. PRIOR TO DEMOLITION, FIELD VERIFY CONDUITS, CONDUCTORS, AND CABLES
THAT PASS THROUGH AND SERVE AREAS OUTSIDE THE SCOPE OF WORK.
MAINTAIN CONTINUITY OF SYSTEMS. PROTECT OR RELOCATE SYSTEMS TO
PREVENT DAMAGE. RESTORE SYSTEMS TO NORMAL OPERATION.
COORDINATE SYSTEM OUTAGES WITH OWNER.
E. IDENTIFY NONFUNCTIONING EQUIPMENT AND DEVICES TO REMAIN AFTER
DEMOLITION. NOTIFY CONTRACTING OFFICER IN WRITING PRIOR TO
DEMOLITION. UPON COMPLETION OF WORK, ENSURE THAT EXISTING
EQUIPMENT AND DEVICES OPERATE PROPERLY.
F. IN AREAS REQUIRING THE PERFORMANCE OF WORK OF OTHER TRADES,
CAREFULLY DISCONNECT, MAKE SAFE, REMOVE AND STORE ELECTRICAL
ITEMS IN PATH OF WORK. REINSTALL AND RECONNECT AFTER COMPLETION
OF OTHERS TRADE'S WORK.
G. DRAWINGS REFLECT EXISTING CONDITIONS FROM GENERAL OBSERVATIONS
AND ARE NOT INTENDED TO INDICATE DETIALS OR DIMENSIONS. VERIFY
EXISTING CONDITIONS PRIOR TO PERFORMING WORK. NOTIFY CONTRACTING
OFFICER IN WRITING IF CONDITIONS ARE DISCOVERED THAT PREVENT
EXECUTION OF WORK.
H. UPDATE PANELBOARD DIRECTORIES TO INCLUDE MODIFICATIONS BY THIS
PROJECT. TRACE CIRCUITS TO IDENTIFY UNLABELED LOADS.
I. ALL NEW CONDUIT SHALL BE CPVC BELOW GRADE AND PVC-COATED RIGID
METAL CONDUIT ABOVE GRADE.
J. ALL NEW EXTERIOR ENCLOSURES SHALL BE NEMA 4X RATED.
K. ALL WIRING TO BE COPPER THHN/THWN. ANY WIRING DIFFERENT THAN THIS
SPECIFICATION MUST BE APPROVED BY THE CONTRACTING OFFICER PRIOR
TO USE.
GENERAL NOTES:
4000 PSI CONCRETE SLAB
ON GRADE-18"
THICK WITH #4 AT 12"
EACH WAY TOP AND
BOTTOM
6" MIN, TYP
4000 PSI CONCRETE
CONCRETE ANCHOR
FINISH GRADE
STANDARD HOOK,
TYPICAL #4
@ 12" O.C
1'-0", TYP
6", TYP
3" CLR
3" CLR,
TYP UNO
CHAMFER EDGE
GENERATOR
GENERATOR
6" MIN,
TYP
6" MIN,
TYP
DATE:
TECH REVIEW:
DESIGNED: SUB SHEET NO. DRAWING NO.
PMIS/PKG NO.
SHEET
OF
LOCATION WITHIN PARK
TITLE OF SHEET
A/E FIRM
CROFT &
ASSOCIATES
KENNESAW,
GEORGIA
/9
/2
:2
:1
P M
ELECTRICAL RISERE501
J. SERRADAS
J. SERRADAS
J. MORGAN
11 11
EAST LIFT STATION XX
XXXXXX
GUIS 303760
GULF ISLAND NATIONAL SEASHORE6/8/2023
NOT TO SCALEE501
1 ELECTRICAL RISER DEMOLITION
NOT TO SCALEE501
3 ELECTRICAL RISER NEW WORK
NOT TO SCALEE501
2 LIFT STATION - ENLARGED PLAN DEMOLITION
NOT TO SCALEE501
4 LIFT STATION - ENLARGED PLAN NEW WORK
NOT TO SCALEE501
6 LIFT STATION PUMP CONTROL ONE-LINE DIAGRAM
NOT TO SCALEE501
5 GENERATOR PAD DETAIL
RISER SHEET NOTES
SEE MASTER KEY ON E101 FOR COMPLETE LIST
TAG # TAG DESCRIPTION
1 SERVICE METER, EXISTING TO REMAIN.
2 SERVICE DISCONNECT, EXISTING TO REMAIN.
3 DEMO EXISTING AUTOMATIC TRANSFER SWITCH
4 DEMO GENERATOR DISCONNECT SWITCH.
5 RANGER STATION AUTO-DIALER, EXISTING TO REMAIN.
6 EXISTING 60A MCB, 120/240V, 1Ø, 4W, PANEL SERVING AREA TO REMAIN.
7 SURGE PROTECTION DEVICE, EXISTING TO REMAIN.
8 DEMO EXISTING PUMP CONTROLLER, STEEL CHANNEL SYSTEM TO REMAIN.
9 PROVIDE AND INSTALL NEW PUMP CONTROLLER, MOUNT TO EXISTING STEEL
CHANNEL SYSTEM.
10 PROVIDE 2#12 & 1#12G. IN 3/4" CONDUIT FOR GFCI RECEPTACLE.
11 PROVIDE 3#4 & 1#10G. IN 1-1/2" CONDUIT FOR LIFT PUMP MOTOR ROUTED A
MINIMUM OF 24"BELOW GRADE.
12 PROVIDE 3#12 & 1#12G. IN 1" CONDUIT FOR MIXER MOTOR ROUTED A MINIMUM
OF 24"BELOW GRADE.
13 PROVIDE AND INSTALL NEW 200A, 120/240V, 1Ø, 4W, AUTOMATIC TRANSFER
SWITCH.
14 DEMO EXISTING 50KW DIESEL GENERATOR AND CONCRETE HOUSEKEEPING
PAD.
15 PROVIDE AND INSTALL NEW 80KW PROPANE GENERATOR WITH 250 GALLON
PROPANE TANK AND ALUMINUM SOUND ATTENTUATOR ENCLOSURE. REFER
TO 1/C4 FOR MORE INFORMATION ON PROPANE TANK LOCATION.
16 PROVIDE NEW CONCRETE HOUSEKEEPING PAD FOR 80KW GENERATOR. SEE
DETAIL 5/E501 FOR MORE INFROMATION, WIDTH AND LENGTH TO BE
COORDINATED WITH ACTUAL GENSET SIZE.
17 REPLACE CONDUIT AND WIRING ONE FOR ONE, ROUTE UNDERGROUND FROM
PANEL LP TO GENERATOR.
18 DEMO CONDUIT AND FEEDERS BACK TO ATS,
19 REPLACE CONDUIT AND WIRING ONE FOR ONE, ROUTE UNDERGROUND FROM
ATS TO GENERATOR.
20 EXISTING CONDUIT AND WIRING. LEAVE INTACT.
21 PROVIDE AND INSTALL CONDUIT SEALS AS REQUIRED BY N.E.C. CLASS 1
DIVISION 1.
22 INCOMING SERVICE FROM EXISTING UTILITY TRANSFORMER.
23 PROVIDE AND INSTALL (1 SET) 4#3/0, 1#6 GND IN 2" CONDUIT FROM ATS TO
PUMP CONTROLLER.
24 PROVIDE AND INSTALL (1 SET) 4#3/0, 1#6 GND IN 2" CONDUIT FROM ATS TO
GENERATOR ROUTED A MINIMUM OF 24"BELOW GRADE.
25 PROVIDE AND INSTALL CONTROL WIRE FROM ATS TO GENERATOR IN 1"
CONDUIT ROUTED A MINIMUM OF 24"BELOW GRADE.
26 PROVIDE AND INSTALL (1 SET) 3#12 & 1#12G. IN 3/4" CONDUIT ROUTED A
MINIMUM OF 24"BELOW GRADE FOR GENERTATOR BATTERY CHARGER.
27 ENSURE ATS HAS ADEQUATELY SIZED LOAD LUGS TO DOUBLE FEED BOTH
EXISTING PANEL AND NEW PUMP CONTROLLER.
28 ELECTRICAL EQUIPMENT LOCATED INSIDE OF PUMP CONTROLLER
ENCLOSURE.
| C0 - Cover Sheet |
| Sheets and Views |
| Layout1 |
| C1 - General Information |
| Sheets and Views |
| G002 |
| C2 - Site Access Plan |
| Sheets and Views |
| C-1 Access Plan |
| C3 - Demolition Plan |
| Sheets and Views |
| C-2 Demolition Plan |
| C4 - Site Plan |
| Sheets and Views |
| C-3 Site Plan |
| C5 - Lift Station Detail |
| Sheets and Views |
| C-5 Lift Station Detail Plan |
| C6 - Lift Station Layout |
| Sheets and Views |
| C-6 Lift Station Layout |
| C7 - Details |
| Sheets and Views |
| C8 |
| 100% CD FINAL SET - ELECTRICAL.pdf |
| 2022-417 GUIS 303760 Lift Station E22 - Sheet - E001 - ELECTRICAL LEGEND |
| 2022-417 GUIS 303760 Lift Station E22 - Sheet - E301 - EXISTING ELECTRICAL CONDITIONS |
| 2022-417 GUIS 303760 Lift Station E22 - Sheet - E501 - ELECTRICAL RISER |
| 2023-06-09T17:18:00-0400 | |
| Lawrence Hale |
| 2023-06-09T17:19:00-0400 | |
| Lawrence Hale |
| 2023-06-09T17:19:43-0400 | |
| Lawrence Hale |
| 2023-06-09T17:20:28-0400 | |
| Lawrence Hale |
| 2023-06-09T17:21:18-0400 | |
| Lawrence Hale |
| 2023-06-09T17:22:07-0400 | |
| Lawrence Hale |
| 2023-06-09T17:22:58-0400 | |
| Lawrence Hale |
| 2023-06-09T17:23:58-0400 | |
| Lawrence Hale |
File details come from the government source that posted it. Updated .