This hazardous materials survey report documents the findings of an asbestos and lead inspection conducted at the Syracuse Hancock International Airport VOR facility in preparation for a planned roof and counterpoise replacement project. The inspection identified asbestos-containing black tar sealants between the flashing and roof deck and between joints of the outermost layer of flashing. Additionally, white caulking around the roof-mounted structure contained asbestos. Lead was also detected above reporting limits in all six paint chip samples collected. The report provides location and quantity details of the identified hazardous materials and recommends abatement of asbestos-containing materials and lead-based paint prior to commencement of the roof replacement project to comply with environmental regulations.
View the file
Other files
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LIMITED HAZARDOUS
MATERIALS SURVEY
REPORT
SYR VOR Facility FAA – Roof-Mounted Teepee Replacement Project
Syracuse Hancock International Airport 1000 Colonel Eileen Collins Boulevard, Syracuse, NY 13212
Prepared for:
Ms. Caitlin (Dixon) Escorcia Safety Engineer
Engineering Services, AJW-2E16E
Federal Aviation Administration 800 Independence Avenue SW
Washington, DC 20591
Report Date: May 24, 2023
Prepared By:
4747 North 7th Street, Suite 422 Phoenix, AZ 85014
TRC Project: 545895
TABLE OF CONTENTS
EXECUTIVE SUMMARY ............................................................................................................. i
INTRODUCTION
BACKGROUND
Asbestos-Containing Materials
Asbestos Bulk Sampling Procedures
Paint Chip Sampling
Laboratory Analysis
FINDINGS
Negative Materials (No Asbestos Detected)
Paint Chip Sampling Results
RECOMMENDATIONS
DISCLAIMER
Appendices
Appendix A – Sample Location Diagram(s)
Appendix B – Representative Photographs
Appendix C – Laboratory Results and Chain of Custody
Appendix D – Certification(s)
Limited Hazardous Materials Survey Report May 24, 2023 SYR VOR Facility TRC Project: 545895
- i -
EXECUTIVE SUMMARY
The Federal Aviation Administration (FAA) contracted TRC Environmental Corporation (TRC) to conduct a limited scope hazardous materials survey of the roof-mounted teepee structure and adjoining materials at the very high frequency omnirange station (VOR) facility at the Syracuse Hancock Internation Airport (SYR) in Syracuse, New York. The survey activities were initiated on April 28, 2023, by Dmitriy Khimich, a New York State Department of Labor Asbestos Inspector and United States Environmental Protection Agency Lead Risk Assessor.
Asbestos-Containing Materials
Laboratory results of the bulk sampling indicated that asbestos was present in the black tar sealant between the flashing and roof deck, the black tar sealant between the joints of the outermost layer of flashing, and the white caulking around the roof-mounted teepee structure. The remaining samples analyzed by the laboratory based on the PLM and TEM methods were negative for asbestos. Any materials uncovered during renovation or demolition activities that are not addressed in this survey report, or presumed asbestos-containing materials (PACM), must be sampled by an accredited asbestos inspector and/or investigator prior to any disturbance, or they must be treated as asbestos-containing materials (ACM).
Lead-Containing Paint Sampling Results
Laboratory results of the paint chip sampling indicated that lead was present above the reporting limits in six (6) of the six (6) samples that were collected and analyzed. Lead-based paint (LBP) is defined as paint containing greater than or equal to 0.5 percent lead by weight (≥0.5%) or greater than or equal to 5,000 parts per million (≥5,000 ppm). Any paint containing less than 0.5% by weight (<0.5%), but greater than the laboratory detection limit is considered to be lead-containing paint (LCP). For any paint in which lead was detected, TRC recommends that any renovation activities that may disturb painted surfaces be conducted according to the Occupational Safety and Heath Administration (OSHA) requirements regarding lead in construction (29 CFR 1926.62).
- 1 -
INTRODUCTION
The Federal Aviation Administration (FAA) contracted TRC Environmental Corporation (TRC) to conduct a limited scope hazardous materials survey of the roof-mounted teepee structure and adjoining materials at the very high frequency omnirange station (VOR) facility at the Syracuse Hancock Internation Airport (SYR) in Syracuse, New York. The survey activities were initiated on April 28, 2023, by Dmitriy Khimich, a New York State Department of Labor Asbestos Inspector and United States Environmental Protection Agency Lead Risk Assessor.
BACKGROUND
Asbestos-Containing Materials
The Occupational Safety and Health Administration (OSHA) defines asbestos-containing material(s) (ACM) as any material containing more than one percent (>1%) asbestos.
The U.S. Environmental Protection Agency (EPA) defines ACM as follows:
1. Friable asbestos-containing material (ACM) is defined by the Asbestos NESHAP as any material containing more than one percent (>1%) asbestos as determined using the method specified in Appendix A, Subpart F, 40 CFR Part 763, Section 1, Polarized Light Microscopy (PLM), that, when dry, can be crumbled, pulverized or reduced to powder by hand pressure.
2. Nonfriable ACM is any material containing more than one percent (>1%) asbestos as determined using the PLM method that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure. The EPA further defines two categories of nonfriable
ACM:
a. Category I (Cat I) - Category I nonfriable ACM is any asbestos-containing packing, gasket, resilient floor covering or asphalt roofing product which contains more than one percent (>1%) asbestos as determined using PLM according to the method specified in Appendix A, Subpart F, 40 CFR Part 763, and
b. Category II (Cat II) - Category II nonfriable ACM is any material, excluding Category I nonfriable ACM, containing more than one percent (>1%) asbestos as determined using PLM according to the methods specified in Appendix A, Subpart F, 40 CFR Part 763 that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.
3. Regulated Asbestos-Containing Material (RACM) is (a) friable asbestos material, (b) Category I nonfriable ACM that has become friable, (c) Category I nonfriable ACM that will be or has been subjected to sanding, grinding, cutting or abrading, or (d) Category II nonfriable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations.
Asbestos Bulk Sampling Procedures
The survey was conducted in accordance with the sample collection protocols established in Environmental Protection Agency (EPA) Asbestos Hazard Emergency Response Act (AHERA)
- 2 -
40 CFR Part 763, Subpart E, National Emissions Standards for Hazardous Air Pollutants (NESHAP) 40 CFR Part 61, Subpart M, and applicable state and local regulations. A summary of survey activities is provided below.
Survey activities began with visual observation of the project area to identify homogeneous areas of suspect ACM. A homogeneous area consists of building materials that appear similar throughout in terms of color and texture that does not extend to other buildings. Visual assessments were conducted in accessible areas of the building. Building materials identified as glass, wood or metal were not considered suspect ACM.
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. Friability was assessed by physically touching suspect materials.
Based on results of the visual observation, bulk samples of suspect ACM were collected in accordance with AHERA, NYSDOL, and/or NYCDEP protocols. Samples of suspect materials were collected in each homogeneous area. Bulk samples were collected using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Field information was organized as per the AHERA concept of homogenous area. That is, suspect ACM with similar age, appearance, and texture was grouped together, sampled, and assessed for condition.
Bulk samples of suspect ACM were analyzed by Polarized Light Microscopy (PLM) with dispersion staining, as described in 40 CFR Part 763 and the National Emissions Standard for Hazardous Air Pollutants (NESHAP).
The New York State Department of Health revised the PLM Stratified Point Counting Method. The new method, "Polarized Light Microscopy Methods for Identifying and Quantitating Asbestos in Bulk Samples" can be found as item 198.1 in the ELAP Certification manual. The State of New York ELAP has determined that analysis of non-friable organically bound materials (NOB's) is not reliably performed by PLM. Therefore, if PLM yields negative results for a non-friable material, it must be confirmed by Transmission Electron Microscopy (TEM).
All samples were initially analyzed by Polarized Light Microscopy. Samples which yielded a negative PLM result, and which are classified as a "non-friable" organically bound material were then reanalyzed utilizing Transmission Electron Microscopy (TEM) methodology.
As per the April 1, 2011 ELAP directive, Item Numbers 198.6/198.4, ceiling tiles with cellulose must now also be confirmed non-ACM via TEM analysis.
As per the July 9, 2013 ELAP directive, for thermal system insulation (TSI) or other presumed ACM (PACM) or miscellaneous suspect ACM which contains 10% vermiculite or less, ELAP method 198.1 can be used to determine the asbestos content of the material. Where TSI or other PACM or miscellaneous suspect ACM contain greater than 10% vermiculite, method 198.6 may be used to evaluate the asbestos content of the material; provided, however, that any test results using this method must be reported with the following conspicuous disclaimer: "This method does not remove vermiculite and may underestimate the level of asbestos present in a sample containing greater than 10% vermiculite."
- 3 -
As per the July 22, 2014 ELAP directive, item numbers 198.6/198.1, sprayed-on fireproofing (SOFV) must now also be analyzed for vermiculite content via ELAP method for SOF-V 198.8 or LAB.055.1, effective November 1, 2014.
In addition, as per the May 6, 2016 ELAP directive, surfacing materials analyzed via items 198.1 or 198.6, as applicable, which contain any amount of vermiculite, must be analyzed by either item
198.8 or LAB.055.1 to confirm asbestos concentration. Per ELAP, negative results for surfacing materials via 198.8 or LAB.055.1 can be reported without any attached disclaimers underestimating the actual asbestos concentrations.
All asbestos bulk samples were submitted under proper chain-of-custody (COC) documentation to the laboratory. Bulk samples were analyzed by PLM utilizing the EPA's Method for the Determination of Asbestos in Bulk Building Materials, EPA 600/M4-82-020. Analysis by PLM was performed by visual observation of the bulk sample and slides prepared of the bulk sample for microscopic examination and identification. The samples were analyzed for asbestos (chrysotile, amosite, crocidolite, anthophyllite, and actinolite/tremolite), fibrous non-asbestos constituents (mineral wool, cellulose, etc.) and non-fibrous constituents. Using a stereoscope, the microscopist visually estimated the relative amounts of each constituent by determining the estimated area of the asbestos compared with the area estimate of the total sample.
Paint Chip Sampling
TRC conducted a limited lead coating survey to identify lead-based paint (LBP) and/or lead-containing paint (LCP). The lead paint survey was performed to identify representative testing combinations of suspect LBP/LCP on painted surfaces that made up the majority of the coatings in each area assessed that would present a hazard during renovation or demolition activities.
The general purpose of this investigation was to confirm the presence, and determine the location of LBP and/or LCP coatings and components that will be disturbed in association with the renovation or demolition of the Site. TRC has documented the general condition of such painted building surfaces, characterized the composition of painted surfaces with regard to lead content, and quantified areas/components to define the magnitude to which deteriorated LBP and/or LCP is present, where encountered. Information derived from this survey may be used in communicating potential lead exposure hazards to workers performing abatement and/or demolition. The scope of work associated with this investigation included the following elements:
Visual inspection of painted surfaces and components;
Testing of select painted surfaces and components using paint chip analysis; and
Assess condition and approximate quantities of LBP/LCP for reporting purposes.
Lead-based paint (LBP) is defined by the United States Department of House and Urban Development (HUD) as any paint, varnish, stain, or other applied coating that has one mg/cm2 or more of lead or 0.5% by weight (5,000 micrograms per gram [ug\g] or 5,000 parts of lead per million [ppm]). According the OSHA Program Directive, Lead: Exposure in Construction, "For all occupational exposure to lead occurring in the course of construction work, the standard (1926.62) does not specify a minimum amount or concentration of lead that triggers a determination that lead is present and the potential for occupational exposure exists." Therefore any paint containing less than 0.5% by weight, but greater than the laboratory detection limit is considered to be LCP.
- 4 -
Paint chip samples were collected from painted surfaces to determine total lead content and assist in determining Occupational Safety and Health Administration (OSHA) requirements with respect to construction activities which may disturb LCP.
All paint chip samples were submitted under proper COC documentation to the laboratory.
Samples were analyzed by flame AAS utilizing the Environmental Protection Agency (EPA) Test Method for Evaluating Solid Waste, Physical/Chemical Methods, EPA SW-846 Method 7000B.
Laboratory Analysis
Laboratory services were provided by two EMSL Analytical, Inc. locations: a New York State Department of Health (NYSDOH) Environmental Laboratory Accreditation Program (ELAP) accredited laboratory (ELAP #11469) located in Carle Place, NY, and a National Voluntary Laboratory Accreditation Program (NVLAP) certified laboratory (NVLAP #101048-9) located in Long Island City, NY.
FINDINGS
Asbestos-Containing Materials (ACM) – Positive (>1%)
Laboratory results of the bulk sampling indicated the following materials sampled contained asbestos in concentrations greater than 1% (>1%), based on the PLM and/or TEM methods:
Sample(s) Material Location(s) Percentage /
Type Approx.
Quantity
Condition / Material Type /
NESHAP Category
Black Tar Sealant between
Flashing and Roof Deck
VOR Roof- Mounted Teepee
Structure and Adjoining Materials
1.6% Chrysotile
60 SF
Good Misc.
Cat I
Black Tar Sealant between Joints of Outermost
Layer of Flashing
VOR Roof- Mounted Teepee
Structure and Adjoining Materials
1.2% Chrysotile
60 SF
Good Misc.
Cat I
Non-ACM - Trace Asbestos (<1%)
Laboratory results of the bulk sampling indicated the following materials sampled contained asbestos in concentrations less than one percent (<1%) but greater than 0.1 percent (>0.1%), based on the PLM and/or TEM methods:
Sample(s) Material Location(s) Percentage /
Type Approx.
Quantity
Condition / Material Type /
NESHAP Category
White Caulking around Teepee
Structure
VOR Roof- Mounted Teepee
Structure and Adjoining Materials
<1% Chrysotile 22 SF Good Misc.
Cat II
- 5 -
Negative Materials (No Asbestos Detected)
Laboratory results of the bulk sampling indicated the following sampled materials did not contain detectable levels of asbestos, based on the PLM and/or TEM methods:
Sample(s) Material Description Location(s) Estimated Quantity
Condition
Outermost Layer of Flashing
VOR Roof-Mounted Teepee Structure and Adjoining Materials
60 SF Good
Brown Insulative Gasket around Access Door to
Teepee Structure
VOR Roof-Mounted Teepee Structure
1 SF Damaged
White/Yellow Fiberglass/Vinyl Walls of
Teepee Structure
VOR Roof-Mounted Teepee Structure
260 SF Good
Paint Chip Sampling Results
Sample Number Location Description % Lead
(by weight)
Lead-Based Paint / Lead- Containing
Paint
LCP - 01
Engine Generator
Room Ceiling White Paint on Wood 0.49 LCP
LCP - 02
Roof-Mounted
Teepee Structure Base Access Hatch
White Paint on Wood 0.36 LCP
LCP - 03
Engine Generator
Room Ceiling White Paint on
Fiberboard
0.73 LBP
LCP - 04
Roof-Mounted
Teepee Structure Floor
Dark Gray Paint on Wood
4.1 LBP
LCP - 05
Roof-Mounted
Teepee Structure Floor
Light Gray Paint on Wood
2.8 LBP
LCP - 06
Roof-Mounted
Teepee Structure Exterior
White Paint on Fiberglass/Vinyl
0.024 LCP
Laboratory results of the paint chip sampling indicated that lead was detected in six (6) of the six
(6) samples that were collected and analyzed as part of this survey.
RECOMMENDATIONS
Asbestos-Containing Materials
Laboratory results of the bulk sampling indicated that asbestos was present in the black tar sealant between the flashing and roof deck, the black tar sealant between the joints of the outermost layer of flashing, and the white caulking around the roof-mounted teepee structure. The remaining samples analyzed by the laboratory based on the PLM and TEM methods were
- 6 -negative for asbestos. Any materials uncovered during renovation or demolition activities that are not addressed in this survey report, or presumed asbestos-containing materials (PACM), must be sampled by an accredited asbestos inspector and/or investigator prior to any disturbance, or they must be treated as asbestos-containing materials (ACM).
Lead-Containing Paint Sampling Results
Laboratory results of the paint chip sampling indicated that lead was present above the reporting limits in six (6) of the six (6) samples that were collected and analyzed. Lead-based paint (LBP) is defined as paint containing greater than or equal to 0.5 percent lead by weight (≥0.5%) or greater than or equal to 5,000 parts per million (≥5,000 ppm). Any paint containing less than 0.5% by weight (<0.5%), but greater than the laboratory detection limit is considered to be lead-containing paint (LCP). For any paint in which lead was detected, TRC recommends that any renovation activities that may disturb painted surfaces be conducted according to the Occupational Safety and Heath Administration (OSHA) requirements regarding lead in construction (29 CFR 1926.62).
DISCLAIMER
The content presented in this report is based on data collected during the survey, review of pertinent regulations, requirements, guidelines and commonly followed industry standards, and information provided by Client and their clients, agents, and representatives.
The work has been conducted in an objective and unbiased manner and in accordance with generally accepted professional practice for this type of work. TRC believes the data and analysis to be accurate and relevant, but cannot accept responsibility for the accuracy or completeness of available documentation or possible withholding of information of other parties.
This limited hazardous materials survey report is designed to aid the property owner, architect, construction manager, general contractor, and asbestos abatement contractor in locating ACM and LBP or LCP.
Sincerely, TRC Environmental Corporation
Aaron Monto Adam Carity, CIEC, CFSAT Staff Industrial Hygienist Office Practice Leader
Appendix A – Sample Location Diagram(s)
LIMITED HAZARDOUS MATERIALS SURVEY
TRC Project No.: 545895 Figure: 1
Drawn by: AM Date: May 2023Reviewed by: AC
4747 North 7th Street, Suite 422 Phoenix, AZ 85014
Phone: (602) 266-8288 Fax: (602) 266-9355
SYR VOR FACILITY – TEEPEE REPLACEMENT PROJECT
SYRACUSE HANCOCK INTERNATIONAL AIRPORT
1000 COLONEL EILEEN COLLINS BOULEVARD, SYRACUSE, NY 13212
LEGEND
- Asbestos-Containing Sample Location
- Non-Asbestos Sample Location
LIMITED HAZARDOUS MATERIALS SURVEY
TRC Project No.: 545895 Figure: 2
Drawn by: AM Date: May 2023Reviewed by: AC
4747 North 7th Street, Suite 422 Phoenix, AZ 85014
Phone: (602) 266-8288 Fax: (602) 266-9355
SYR VOR FACILITY – TEEPEE REPLACEMENT PROJECT
SYRACUSE HANCOCK INTERNATIONAL AIRPORT
1000 COLONEL EILEEN COLLINS BOULEVARD, SYRACUSE, NY 13212
LEGEND
- Lead-Containing Paint Sample Location
LCP - 02
LCP - 06
LCP - 05
LCP - 04
LCP - 03
LCP - 01
Appendix B – Representative Photographs
SYR VOR FACILITY
FAA – ROOF-MOUNTED TEEPEE REPLACEMENT PROJECT
SYRACUSE HANCOCK INTERNATIONAL AIRPORT
OVERVIEW PHOTOGRAPHIC LOG
SYRACUSE HANCOCK INTERNATIONAL AIRPORT
SUSPECT ASBESTOS-CONTAINING MATERIALS PHOTOGRAPHIC LOG
Sample Numbers: 01, 02, 03
Material Description: Black Tar Sealant between Flashing and Roof Deck
Material Color: Black
Accessible Material: Accessible
Reason Inaccessible: N/A
Asbestos Detected: Positive
Asbestos Type: 1.6% Chrysotile
Homogeneous Area: VOR Roof-Mounted Teepee Structure and Adjoining Materials
Total Approximate Quantity: 60 SF
Condition: Good
Material Type: Misc.
NESHAP Category: Cat I
Notes: Not Applicable
Sample Numbers: 04, 05, 06
Material Description: Outermost Layer of Flashing
Material Color: Black
Accessible Material: Accessible
Reason Inaccessible: N/A
Asbestos Detected: Negative
Asbestos Type: No Asbestos Detected
Homogeneous Area: VOR Roof-Mounted Teepee Structure and Adjoining Materials
Total Approximate Quantity: 60 SF
Condition: Good
Material Type: Misc.
NESHAP Category: N/A
Notes: Not Applicable Sample Numbers: 07, 08, 09
Material Description: Black Tar Sealant between Joints of Outermost Layer of Flashing
Material Color: Black
Accessible Material: Accessible
Reason Inaccessible: N/A
Asbestos Detected: Positive
Asbestos Type: 1.2% Chrysotile
Homogeneous Area: VOR Roof-Mounted Teepee Structure and Adjoining Materials
Total Approximate Quantity: 60 SF
Condition: Good
Material Type: Misc.
NESHAP Category: Cat I
Notes: Not Applicable
SYRACUSE HANCOCK INTERNATIONAL AIRPORT
SUSPECT ASBESTOS-CONTAINING MATERIALS PHOTOGRAPHIC LOG
Sample Numbers: 10, 11, 12
Material Description: White Caulking around Teepee Structure
Material Color: White
Accessible Material: Accessible
Reason Inaccessible: N/A
Asbestos Detected: Positive
Asbestos Type: <1% Chrysotile
Homogeneous Area: VOR Roof-Mounted Teepee Structure and Adjoining Materials
Total Approximate Quantity: 22 SF
Condition: Good
Material Type: Misc.
NESHAP Category: Cat II
Notes: Not Applicable
Sample Numbers: 13, 14, 15
Material Description: Brown Insulative Gasket around Access Door to Teepee Structure
Material Color: Brown
Accessible Material: Accessible
Reason Inaccessible: N/A
Asbestos Detected: Negative
Asbestos Type: No Asbestos Detected
Homogeneous Area: VOR Roof-Mounted Teepee Structure
Total Approximate Quantity: 1 SF
Condition: Damaged
Material Type: Misc.
NESHAP Category: N/A
Notes: Not Applicable Sample Numbers: 16, 17, 18
Material Description: White/Yellow Fiberglass/Vinyl Walls of Teepee Structure
Material Color: White Yellow
Accessible Material: Accessible
Reason Inaccessible: N/A
Asbestos Detected: Negative
Asbestos Type: No Asbestos Detected
Homogeneous Area: VOR Roof-Mounted Teepee Structure
Total Approximate Quantity: 260 SF
Condition: Good
Material Type: Misc.
NESHAP Category: N/A
Notes: Not Applicable
SYRACUSE HANCOCK INTERNATIONAL AIRPORT
LEAD-CONTAINING PAINT PHOTOGRAPHIC LOG
Sample Numbers: LCP - 01
Sample Location: Engine Generator Room Ceiling
Description: White Paint
Laboratory Result (%): 0.49
Substrate: Wood
Paint Locations: Throughout
Quantity of Deteriorated Paint (SF): TBD
Sample Numbers: LCP - 02
Sample Location: Roof-Mounted Teepee Structure Base Access Hatch
Description: White Paint
Laboratory Result (%): 0.36
Substrate: Wood
Sample Numbers: LCP - 03
Sample Location: Engine Generator Room Ceiling
Description: White Paint
Laboratory Result (%): 0.73
Substrate: Fiberboard
SYRACUSE HANCOCK INTERNATIONAL AIRPORT
LEAD-CONTAINING PAINT PHOTOGRAPHIC LOG
Sample Numbers: LCP - 04
Sample Location: Roof-Mounted Teepee Structure Floor
Description: Dark Grey Paint
Laboratory Result (% wt.): 4.1
Substrate: Wood
Sample Numbers: LCP - 05
Floor
Description: Light Grey Paint
Laboratory Result (%): 2.8
Substrate: Wood
Sample Numbers: LCP - 06
Exterior
Description: White Paint
Laboratory Result (%): 0.024
Substrate: Fiberglass/Vinyl
Appendix C – Laboratory Results and Chain of Custody
EMSL Analytical, Inc.
10-39 45th Road Long Island City, NY 11101
Tel/Fax: (212) 290-0051 / (212) 290-0058 http://www.EMSL.com / manhattanlab@emsl.com
032304554EMSL Order:
Customer ID: TRCE51
Customer PO: 545895
Project ID:
Attention: Phone:Dmitriy Khimich (212) 221-7822
Fax:TRC Environmental Corporation (212) 221-7840
Received Date:1430 Broadway 04/28/2023 8:32 PM
Analysis Date:10th Floor 05/14/2023 - 05/16/2023
Collected Date:New York, NY 10018 04/28/2023
Project: 545895 / FAA - SYR VOR Facility Room-Mounted Tee-pee Replacement, FAA - Syracuse Hancock
International Airport - VOR Facility, Syracuse, New York
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 01 Description SYR VOP Tee-Pee on the Top - Roof Flashing Bottom Tar, Black
032304554-0001 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black05/14/2023 <1.00% Glass 100.00% Other Inconclusive : <1% Chrysotile
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/14/2023
Sample ID 02 Description SYR VOP Tee-Pee on the Top - Roof Flashing Bottom Tar, Black
032304554-0002 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black05/14/2023 None 98.40% Other 1.60% Chrysotile
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/14/2023
Sample ID 03 Description SYR VOP Tee-Pee on the Top - Roof Flashing Bottom Tar, Black
032304554-0003 Homogeneity
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Positive Stop (Not Analyzed)05/14/2023
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/14/2023
Sample ID 04 Description SYR VOP Tee-Pee on the Top - Roof Flashing Top Layer , Black
032304554-0004 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black Inconclusive: None Detected05/14/2023 <1.00% Glass 100.00% Other
TEM NYS 198.4 NOB Black None Detected05/16/2023 100.00% Other
Sample ID 05 Description SYR VOP Tee-Pee on the Top - Roof Flashing Top Layer , Black
032304554-0005 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black Inconclusive: None Detected05/14/2023 1.70% Glass 98.30% Other
TEM NYS 198.4 NOB Black None Detected05/16/2023 100.00% Other
Initial report from: 05/14/2023 17:36:19
Page 1 of 5ASB_198x_0009_0001 Printed 5/16/2023 11:32:59PM
Tel/Fax: (212) 290-0051 / (212) 290-0058 http://www.EMSL.com / manhattanlab@emsl.com
032304554EMSL Order:
Customer ID: TRCE51
Customer PO: 545895
Project ID:
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 06 Description SYR VOP Tee-Pee on the Top - Roof Flashing Top Layer , Black
032304554-0006 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black Inconclusive: None Detected05/14/2023 <1.00% Glass 100.00% Other
TEM NYS 198.4 NOB Black None Detected05/16/2023 100.00% Other
Sample ID 07 Description SYR VOP Tee-Pee on the Top - Roof Flashing Top Layer Joints Tar, Black
032304554-0007 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Black05/14/2023 None 98.80% Other 1.20% Chrysotile
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/14/2023
Sample ID 08 Description SYR VOP Tee-Pee on the Top - Roof Flashing Top Layer Joints Tar, Black
032304554-0008 Homogeneity
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Positive Stop (Not Analyzed)05/14/2023
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/14/2023
Sample ID 09 Description SYR VOP Tee-Pee on the Top - Roof Flashing Top Layer Joints Tar, Black
032304554-0009 Homogeneity
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Positive Stop (Not Analyzed)05/14/2023
TEM NYS 198.4 NOB Positive Stop (Not Analyzed)05/14/2023
Sample ID 10 Description SYR VOP Tee-Pee on the Top - Joints Caulking , White
032304554-0010 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB White/ Black Inconclusive: None Detected05/14/2023 100.00% Other
TEM NYS 198.4 NOB White/ Black05/16/2023 None 100.00% Other <1% Chrysotile
Sample ID 11 Description SYR VOP Tee-Pee on the Top - Joints Caulking , White
032304554-0011 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB White/ Black Inconclusive: None Detected05/14/2023 100.00% Other
TEM NYS 198.4 NOB White/ Black05/16/2023 None 100.00% Other <1% Chrysotile
Page 2 of 5ASB_198x_0009_0001 Printed 5/16/2023 11:32:59PM
Tel/Fax: (212) 290-0051 / (212) 290-0058 http://www.EMSL.com / manhattanlab@emsl.com
032304554EMSL Order:
Customer ID: TRCE51
Customer PO: 545895
Project ID:
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 12 Description SYR VOP Tee-Pee on the Top - Joints Caulking , White
032304554-0012 Homogeneity Heterogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB White/ Black Inconclusive: None Detected05/14/2023 100.00% Other
TEM NYS 198.4 NOB White/ Black None Detected05/16/2023 100.00% Other
Sample ID 13 Description SYR VOP Tee-Pee on the Top - Access Door Insulation Gasket , Brown
032304554-0013 Homogeneity Homogeneous
PLM NYS 198.1 Friable Brown None Detected05/14/2023 100.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 14 Description SYR VOP Tee-Pee on the Top - Access Door Insulation Gasket , Brown
032304554-0014 Homogeneity Homogeneous
PLM NYS 198.1 Friable Brown None Detected05/14/2023 100.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 15 Description SYR VOP Tee-Pee on the Top - Access Door Insulation Gasket , Brown
032304554-0015 Homogeneity Homogeneous
PLM NYS 198.1 Friable Brown None Detected05/14/2023 25.00%
3.00%
10.00%
55.00%
7.00%
Ca Carbonate
Mica
Non-fibrous (other)
Perlite
Quartz
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 16 Description SYR VOP Tee-Pee on the Top - Fiberglass Tee-Pee, White, Yellow
032304554-0016 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray/ White None Detected05/14/2023 85.00% Glass 10.00%
5.00%
Non-fibrous (other)
Quartz
Result includes a small amount of inseparable attached material
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 17 Description SYR VOP Tee-Pee on the Top - Fiberglass Tee-Pee, White, Yellow
032304554-0017 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray/ White None Detected05/14/2023 80.00% Glass 15.00%
5.00%
Non-fibrous (other)
Quartz
Result includes a small amount of inseparable attached material
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Page 3 of 5ASB_198x_0009_0001 Printed 5/16/2023 11:32:59PM
Tel/Fax: (212) 290-0051 / (212) 290-0058 http://www.EMSL.com / manhattanlab@emsl.com
032304554EMSL Order:
Customer ID: TRCE51
Customer PO: 545895
Project ID:
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 18 Description SYR VOP Tee-Pee on the Top - Fiberglass Tee-Pee, White, Yellow
032304554-0018 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray/ White None Detected05/14/2023 80.00% Glass 7.00%
10.00%
3.00%
Ca Carbonate
Non-fibrous (other)
Quartz
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Page 4 of 5ASB_198x_0009_0001 Printed 5/16/2023 11:32:59PM
Tel/Fax: (212) 290-0051 / (212) 290-0058 http://www.EMSL.com / manhattanlab@emsl.com
032304554EMSL Order:
Customer ID: TRCE51
Customer PO: 545895
Project ID:
Test Report:Asbestos Analysis of Bulk Material
The samples in this report were submitted to EMSL for analysis by Asbestos Analysis of Bulk Materials via NYS ELAP Approved Methods. The reference number for these samples is the EMSL Order ID above. Please use this reference number when calling about these samples.
Report Comments:
Sample Receipt Date:
Analysis Completed Date: Analysis Completed Time:
Sample Receipt Time:4/28/2023 8:32 PM
5/16/2023 4:10 PM
Analyst(s):
Angelica Serrano PLM NYS 198.1 Friable (4) Kerrie Gibson PLM NYS 198.1 Friable (2)
Kerrie Gibson PLM NYS 198.6 NOB (9) Steven Dutter TEM NYS 198.4 NOB (6)
Samples reviewed and approved by:
Charles Johnson, Asbestos Laboratory Manager or Other Approved Signatory
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received. Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. Estimation of uncertainty available upon request.
This report is a summary of multiple methods of analysis, fully compliant reports are available upon request. All samples examined for the presence of vermiculite when analyzed via NYS 198.1. A combination of PLM and TEM analysis may be necessary to ensure consistently reliable detection of asbestos. Polarized-light microscopy is not consistently reliable in detecting asbestos in floor coverings and similar non-friable organically bound materials. This report must not be used to claim product endorsement by
NVLAP of any agency or the U.S. Government . Quantitative transmission electron microscopy is currently the only method that can be used to determine if this material can be considered or treated as non-asbestos containing. NOB= Non friable organically bound; N/A= Not applicable VCM= Vermiculite containing material.
Samples analyzed by EMSL Analytical, Inc. Long Island City, NY NYS ELAP 11506, NVLAP Lab Code 101048-9
Page 5 of 5ASB_198x_0009_0001 Printed 5/16/2023 11:32:59PM
O r d e r I D
P a g e f d e r I D
P a g e
Client Sample Description ConcentrationLab ID Analyzed Lead
Collected
EMSL Analytical, Inc.
528 Mineola Avenue, Carle Place, NY 11514 Phone/Fax: (516) 997-7251 / (516) 997-7528 http://www.EMSL.com carleplacelab@emsl.com
Attn: Dimitriy Khimich TRC Environmental Corporation 1430 Broadway 10th Floor New York, NY 10018
Received: 5/1/2023 07:14 PM
Federal Avaiation Administration (FAA); FAA - SYR VOR Facility Room-Mounted Tee-pee Replacemet FAA - Syracuse Hancock
Fax: (212) 221-7840 Phone: (212) 221-7822
Project:
4/28/2023Collected:
Test Report: Lead in Paint Chips by Flame AAS (SW 846 3051A/7000B)*
062307610 CustomerID: TRCE51 CustomerPO: 545895000000000 ProjectID:
EMSL Order:
Site: SYR VOP Engine Generator Room Ceiling Desc: White Paint Wood
062307610-0001LCP - 01 0.49 % wt5/7/20234/28/2023
Site: SYR VOR Tee-Pee Base Access Hatch Desc: White Paint Wood
062307610-0002LCP - 02 0.36 % wt5/7/20234/28/2023
Site: SYR VOP Ceiling Area of the EG Room Desc: White Paint Wood
062307610-0003LCP - 03 0.73 % wt5/7/20234/28/2023
Site: SYR VOP Tee-Pee Inside Base Desc: Dark Grey Paint Wood
062307610-0004LCP - 04 4.1 % wt5/7/20234/28/2023
Site: SYR VOP Tee-Pee Inside Base Desc: Light Grey Paint Wood
062307610-0005LCP - 05 2.8 % wt5/7/20234/28/2023
Site: SYR VOP Tee-Pee on the Top Desc: White Paint Fiberglass Plastic
062307610-0006LCP - 06 0.024 % wt5/7/20234/28/2023
James Han, Chemistry Laboratory Manager or other approved signatory
Test Report ChmSnglePrm/nQC-7.32.3 Printed: 5/8/2023 8:12:18 AM
EMSL maintains liability limited to cost of analysis. Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. The report reflects the samples as received.
Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted.
Analysis following Lead in Paint by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is 0.008% wt. based on the minimum sample weight per our SOP. "<" (less than) result signifies the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. Definitions of modifications are available upon request.
Samples analyzed by EMSL Analytical, Inc. Carle Place, NY AIHA LAP, LLC-ELLAP Accredited #102344, CT PH-0249, NYS ELAP 11469, CA 2339
Initial report from 05/08/2023 08:12:18 http://www.EMSL.com mailto:carleplacelab@emsl.com d e r I D
P a g e d e r I D
P a g e
Appendix D – Certification(s)
Dmitriy Khimich has fulfilled the requirements of the Toxic Substances Control Act (TSCA) Section 402, and has received certification to conduct lead-based paint activities pursuant to 40 CFR Part 745.226 as:
All EPA Administered Lead-based Paint Activities Program States, Tribes and Territories
This certification is valid from the date of issuance and expires July 20, 2025
Certification #
LBP-R-15508-3
Issued On
February 18, 2022
Ben Conetta, Chief
Chemicals and Multimedia Programs Branch
Risk Assessor
File details come from the government source that posted it. Updated .