Arch Dwg 1-5.pdf
PDF 4 MB Posted
- Attached to
- Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 Federal contract opportunity
- Solicitation number
- 36C24420R0075
About this file
This document package includes architectural drawings and specifications for the construction of a new parking garage, along with the corresponding federal contract solicitation. The scope of work involves providing all labor, materials, tools, equipment, permits, testing and reports to construct a new approximately 435-space parking structure for the Wilkes-Barre VA Medical Center in Pennsylvania, in accordance with the drawings, specifications and federal requirements. The magnitude of the project is estimated between $10-20 million. The solicitation is set aside for verified service-disabled veteran-owned small businesses and will use a tiered evaluation process including large businesses. Pricing must be in whole dollars. The contractor will be responsible for correct worker classification and wage compliance. The solicitation may be canceled before award if in the government's best interest.
View the file
Other files for this federal contract opportunity
Show all 50
Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
XXXX
XXXX
XXXXXXX
XXXXX X
X
X
X
X
X
X
X
X
XXXXXXXXXXXXXX
XXXXXXXXXX
RAMP UP
UP
RAMP DN
UP
XXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXX
XXXXXXXXXXXXXX
XXXXXXXXXX
X X
X X
X X
X
X X
X X
X
XXXXXXXXXXXXX XXXX XXXX
X
X
X X
RAMP DN RAMP UP
UP
DN
UP
UP
DN
XXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXX
XXXXXXXXXXXXXX
XXXXXXXXXX
X X
X X
X X
X
X X
X X
X X
X
XXXXXXXXXXXXX XXXXX
X
XX X
30'-10"
RAMP DN RAMP UP
UP
DN
DN
UP
DN
UP
XXXXXXXXXXXXXX
XXXXXXXXXX
X X
X X
X X
X
XX XXX X X
X
X X
X X
X
XXX
X
XXXXXXXXXXXXXX
XXXXXXXXXX
XX
VAN VAN VAN
30'-10"
RAMP DN RAMP UP
UP
DNDN
DN
UP
17' - 7"
170'
86'
19504 SF
PARTIAL GROUND TIER170'
FE
FE
FE
FE
FE
FE
FE
170'
145'
124'
192' 162'
34739 SF
GROUND TIER
3'
290' - 1"
FE FE
FE
FE
FE
FE
FE
FE
FE
FEFE
FE
FE
KEY PLAN
PARTIAL GROUND TIER
GROUND TIER
KEY PLAN
PARTIAL GROUND TIER
GROUND TIER
SECOND TIER
THIRD TIER
LIVING WALL LOCATIONS (CLOSED)
PEDESTRIAN PATH
124'
170'
145'
124'
192' 162'
34739 SF
SECOND TIER
290' - 1"
3'
FE FE
FE
FE
FE
FE
FE
FE
FE
FE
FE
FEFE
290' - 1"
124'
170'
145'
124'
192' 162'
34739 SF
THIRD TIER
FE FE
FE
FE
FE
FE
FE
FE
FE
FEFE
FE
FE
KEY PLAN
SECOND TIER
THIRD TIER
KEY PLAN
PROJECT NO.
DATE:
DRAWING NO.BUILDING NUMBER CHECKED DRAWN
LOCATION
DRAWING
DWG. OF
PROJECT TITLEDRAWING TITLE
FACILITY PROJECT NAME
REVISIONS DATE V
e te ra n s
A ff a ir s
CODE COMPLIANCE PARTIAL GROUND TIER
THROUGH THIRD TIER
7/10/2020
693-222
CC101
WILKES-BARRE V.A.
MEDICAL CENTER
PARKING GARAGE
WILKES-BARRE V.A. MEDICAL CENTER
GARAGE
1111 EAST END BLVD, WILKES-BARRE, PA
Checker Author
CODE COMPLIANCE LEGEND
CONSTRUCTION RESISTING PASSAGE OF SMOKE
1 HOUR RATED FIRE BARRIER
2 HOUR RATED FIRE BARRIER
2 HOUR RATED FIRE WALL
ACCESSIBLE ENTRANCE
ACCESSIBLE MEANS OF EGRESS
1/16" = 1'-0"CC101
1 CODE COMPLIANCE - PARTIAL GROUND TIER
1/16" = 1'-0"CC101
2 CODE COMPLIANCE - GROUND TIER
1/16" = 1'-0"CC101
6 CODE COMPLIANCE - SECOND TIER
1/16" = 1'-0"CC101
7 CODE COMPLIANCE - THIRD TIER
XXXXXXXX
X X X X
XXX
X X
X X
X X
X
XXXXXXXXXXXXXXXXX XXXX
XXXXXXXXXXXXXXXXXXXXX
X X
X X
XX
RAMP UP
OPEN BELOW
DN
DN
124'
192' 162'
23235 SF
FOURTH TIER
*FOURTH TIER: OPEN TO ABOVE
FE FE
FE
FE
FEFE
FE
FEFE
FE
FE
FOURTH TIER
KEY PLAN
847' - 4" Partial Ground Tier
858' - 8" Ground Tier
892' - 8" Fourth Tier
904' - 5" Top of Wall
870' - 0" Second Tier
881' - 4" Third Tier
847' - 4" Partial Ground Tier
858' - 8" Ground Tier
892' - 8" Fourth Tier
904' - 5" Top of Wall
870' - 0" Second Tier
881' - 4" Third Tier
915' - 11" Top of Roof
892' - 8" Fourth Tier
904' - 5" Top of Wall
870' - 0" Second Tier
881' - 4" Third Tier
915' - 11" Top of Roof
858' - 8" Ground Tier
892' - 8" Fourth Tier
904' - 5" Top of Wall
870' - 0" Second Tier
881' - 4" Third Tier
915' - 11" Top of Roof
PARTIAL GROUND
GROUND TIER
SECOND TIER
THIRD TIER
LIVING WALL LOCATIONS (CLOSED)
PEDESTRIAN PATH
PROJECT NO.
DATE:
DRAWING NO.BUILDING NUMBER CHECKED DRAWN
LOCATION
DRAWING
DWG. OF
PROJECT TITLEDRAWING TITLE
FACILITY PROJECT NAME
REVISIONS DATE V
e te ra n s
A ff a ir s
CODE COMPLIANCE FOURTH TIER AND
ELEVATIONS
7/10/2020
693-222
CC102
WILKES-BARRE V.A.
MEDICAL CENTER
PARKING GARAGE
WILKES-BARRE V.A. MEDICAL CENTER
GARAGE
1111 EAST END BLVD, WILKES-BARRE, PA
Checker Author
1/16" = 1'-0"CC102
1 CODE COMPLIANCE - FOURTH TIER - GC ALTERNATE
1/16" = 1'-0"CC102
2 OVERALL NORTH ELEVATION
1/16" = 1'-0"CC102
3 OVERALL EAST ELEVATION
1/16" = 1'-0"CC102
4 OVERALL SOUTH ELEVATION
1/16" = 1'-0"CC102
5 OVERALL WEST ELEVATION
CODE COMPLIANCE LEGEND
CONSTRUCTION RESISTING PASSAGE OF SMOKE
1 HOUR RATED FIRE BARRIER
2 HOUR RATED FIRE BARRIER
2 HOUR RATED FIRE WALL
ACCESSIBLE ENTRANCE
ACCESSIBLE MEANS OF EGRESS
jcalle Snapshot jcalle Snapshot
A
PROJECT NO.
DATE:
DRAWING NO.BUILDING NUMBER CHECKED DRAWN
LOCATION
DRAWING
DWG. OF
PROJECT TITLEDRAWING TITLE
FACILITY PROJECT NAME
REVISIONS DATE V
e te ra n s
A ff a ir s
SIGNAGE SCHEDULE
7/10/2020
693-222
A6.2
WILKES-BARRE V.A.
MEDICAL CENTER
PARKING GARAGE
WILKES-BARRE V.A. MEDICAL CENTER
GARAGE
1111 EAST END BLVD, WILKES-BARRE, PA
Checker Author
STAIRS
BRAILLE
RESTROOM MEN WOMEN
BRAILLE BRAILLE BRAILLE
AREA
OF
REFUGE
BRAILLE
A101
TYPE 1A-SIZE:
8"x8"
NOT TO SCALE
NAME
MAXIMUM
OCCUPANC
Y
BRAILLE
XXX
ROOMS XXX-XXX
ROOMS XXX-XXX
ROOMS XXX-XXX
MEDIA CENTER
CAFETERIA
GYMNASIUM
NATATORIUM
AUDITORIUM
A101
NAM
E
NAM
E
PAPER INSERT
NAME
A101
NAM
E
NAM
E
VACANT IN USE
BRAILLE
IN CASE OF
FIRE
USE STAIRS
EXIT
BRAILLE (NUMBER & NAME)
BRAILLE
BRAILLE (NUMBER & NAME) BRAILLE (NUMBER & NAME)
BRAILLE
EXIT
TYPE 1B-SIZE: 8"x8"
NOT TO SCALE
TYPE 1C-SIZE: 8"x8"
NOT TO SCALE
TYPE 2A-SIZE:
8"x8"
NOT TO SCALE
TYPE 2B-SIZE:
8"x8"
NOT TO SCALE
TYPE 2C-SIZE:
8"x8"
NOT TO SCALE
TYPE 3A-SIZE:
8"x8"
NOT TO SCALE
TYPE 3C-SIZE: 8"x8"
NOT TO SCALE
TYPE 3D-SIZE: 8"x8"
NOT TO SCALE
TYPE 4B-SIZE: 8"x8"
NOT TO SCALE
TYPE 4A-SIZE: 8"x8"
NOT TO SCALE
TYPE 4C-SIZE: 8"x8"
NOT TO SCALE
TYPE 4E-SIZE: 8"x8"
NOT TO SCALE
TYPE 4J-SIZE: 18"x24"
NOT TO SCALE
STAIR A
2ND FLOOR
EXIT 1 FLOOR
DOWN
BRAILLE
TYPE 3B-SIZE: 8"x12"
NOT TO SCALE
EXIT
BRAILLE
TYPE 4D-SIZE: 8"x8"
NOT TO SCALE
RESTROOM
BRAILLE
TYPE 4F-SIZE: 8"x8"
NOT TO SCALE
RESTROOM
BRAILLE
TYPE 4G-SIZE: 8"x8"
NOT TO SCALE
ASSISTIVE LISTENING
DEVICE AVAILABLE
AT TICKET OFFICE
BRAILLE BRAILLE
ELEVATOR IS NOT AN
ACCESSIBLE EMERGENCY
MEANS OF EGRESS.
USE STAIR 'X'
TYPE 4H-SIZE: 8"x8"
NOT TO SCALE
TYPE 4K-SIZE: 12"x8"
NOT TO SCALE
MAXIMUM OCCUPANCY
CONCENTRATED
BRAILLE
XXX
UNCONCENTRATED
XXX
SIGNAGE SCHEDULE
ORIGINAL SIGN TO READ SIGNAGE TYPE
ROOM# ARCHITECTURAL ROOM NAME ROOM# SIGN TO READ TYPE ADA FEMALE MALE QTY
Partial Ground Tier
001 PARTIAL GROUND TIER
002 ELECTRICAL ROOM
003 UTILITY ROOM
004 STORAGE
Ground Tier
000 ELEVATOR SHAFT
100 GROUND TIER
101 GROUND TIER VESTIBULE
102 ELEVATOR MACHINE ROOM
Second Tier
200 SECOND TIER
201 SECOND TIER VESTIBULE
Third Tier
300 THIRD TIER
301 THIRD TIER VESTIBULE
Fourth Tier
400 FOURTH TIER
401 FOURTH TIER VESTIBULE
904' - 5" Top of Wall
ELEVATOR SHAFT
STRUCTRUAL PRECAST
ROOF - SEE STRUCTRUAL
ROOF VENT - SEE
ELECTRICAL
DRAWINGS
915' - 11" Top of Roof
3'
6'
A-101
A-501
1'
1"
A-101
METAL COPING WITH
CONCEALED JOINT COVER
PLATE AND HOLD DOWN CLIP
CONTINUOUS PT WOOD
BLOCKING CAP
METAL WALL PANEL SYSTEM
6" METAL STUD FRAMING
@ 12" OC
STRUCTURAL PRE-CAST
ROOF DECK - SEE
STRUCTURAL DRAWINGS
CONT STEEL TUBE - WELD
TO STEEL COLUMNS
6" METAL STUD FRAMING
@ 12" OC - ANCHOR TO
STEEL BENT PLATE AND
TUBE
CONT 6"X6"X3/8" STEEL
BENT PLATE - WELD TO
TOP OF
STEEL COLUMNS
1/2" EXTERIOR GRADE
PLYWOOD SHEATHING
TAPERED INSULATION
W/ ROOFING MEMBRANE
12"
1/4"
STEEL MOUNTING PLATE
TYP EXPANSION BOLTS
- ANCHOR INTO PRECAST
DECK
A-101
3"
7"
PROVIDE SLOTTED HOLES IN
COPING WITH SELF-SEALING
OVER-SIZED WASHERS &
SCREWS @ 24" OC
MEMBRANE ROOFING &
FLASHING SYSTEM AS
SPECIFIED - TO EXTEND
OVER TOP OF WALL AS
INDICATED
2"
2'
METAL WALL PANEL SYSTEM
1/2" EXTERIOR GRADE
PLYWOOD SHEATHING
VAPOR RETARDER
VAPOR RETARDER
MEMBRANE ROOFING
SYSTEM - TO EXTEND
UP FRAMING AS INDICATED
MEMBRANE ROOFING
SYSTEM - TO EXTEND
UNDER TUBE AND UP
WALL FRAMING MIN 2"
6"x6" STEEL COLUMN
WELDED TO MOUNTING
PLATE - WRAP ROOFING
MEMBRANE AROUND
PERIMETER OF COLUMN
7"
METAL COPING WITH
CONCEALED JOINT COVER
PLATE AND HOLD DOWN CLIP
CONTINUOUS PT WOOD
BLOCKING CAP WITH TAPCON
FASTENERS (STAGGERED)
AT 12" OC
3'
1'
1"
HATCH DENOTES
BASE BID
A-101
A-101
SLOPE
ROOF DRAIN
TAPERED ROOF
INSULATION
SCREEN WALL -
GC ALTERNATE
R1 R2 R3
RA
RB
RC
E Q
E Q
THRU WALL
OVERFLOW SCUPPER
BELOW
PRECAST WALL
6X6 STEEL COLUMN
TYP OF (8)
SLOPE
H
IG
H P
O
IN
T
HIGH POINT
EQ EQ2' - 5" 2' - 5"
2'
2'
A-101
A-101
ROOF CONSTRUCTION - SEE
STRUCTURAL FOR SPECIFIC
MATERIALS AND
CONDITIONS
2"
18 GA. STAINLESS STEEL SCUPPER
SLEEVE - WATERTIGHT WELDED SEAMS
COORDINATE LOCATIONS WITH EXT.
ELEVATIONS & ADJACENT ROOF HEIGHTS
MEMBRANE FLASHING SYSTEM & SEALANT
NOTE: INSTALL SCUPPER SLEEVE
INTEGRAL WITH ROOF / FLASHING
CONSTRUCTION
SEALANT
SEALANT
1/2"- 45° FLARED
EDGE PERIMETER
PRECAST
CONCRETE WALL
SEE PLANS
7"
METAL COPING WITH
CONCEALED JOINT COVER
PLATE AND HOLD DOWN CLIP
CONTINUOUS PT WOOD
BLOCKING CAP WITH TAPCON
FASTENERS (STAGGERED)
AT 12" OC
4"
* SCUPPER 2" ABOVE TAPERED
INSULATION
6"x6" STEEL COLUMN
WELDED TO MOUNTING
PLATE
TYP EXPANSION BOLT
CONTINUOUS STEEL TUBE
AND METAL STUD WALL
ABOVE
PRECAST ROOF SLAB
CONTINUOUS STEEL TUBE
AND METAL STUD WALL
ABOVE
RIGID INSULATION AND
ROOFING MENBRANE
NOT SHOWN FOR CLARITY
3"6"3"
SLOPE
ROOF DRAIN
TAPERED ROOF
INSULATION
THRU WALL
OVERFLOW SCUPPER
PRECAST WALL
SLOPE
A-101
A-101
A-101
A-101
A-101
ROOF CONSTRUCTION - SEE
STRUCTURAL FOR SPECIFIC
MATERIALS AND
CONDITIONS
NOTE: INSTALL SCUPPER SLEEVE
INTEGRAL WITH ROOF / FLASHING
CONSTRUCTION
PRECAST
CONCRETE WALL
SEE PLANS
7"
METAL COPING WITH
CONCEALED JOINT COVER
PLATE AND HOLD DOWN CLIP
CONTINUOUS PT WOOD
BLOCKING CAP WITH TAPCON
FASTENERS (STAGGERED)
AT 12" OC
MEMBRANE ROOFING &
FLASHING SYSTEM AS
SPECIFIED - TO EXTEND
OVER TOP OF WALL, OVER
BLOCKING AS INDICATED
PROJECT NO.
DATE:
DRAWING NO.BUILDING NUMBER CHECKED DRAWN
LOCATION
DRAWING
DWG. OF
PROJECT TITLEDRAWING TITLE
FACILITY PROJECT NAME
REVISIONS DATE V
e te ra n s
A ff a ir s
VESTIBULE ROOF PLAN AND DETAILS
7/10/2020
693-222
A-101
WILKES-BARRE V.A.
MEDICAL CENTER
PARKING GARAGE
WILKES-BARRE V.A. MEDICAL CENTER
GARAGE
1111 EAST END BLVD, WILKES-BARRE, PA
Checker Author
1/4" = 1'-0"A-101
5 STAIR / ELEVATOR SCREEN WALL SECTION - GC ALTERNATE
1 1/2" = 1'-0"A-101
6 SCREEN WALL DETAIL - GC ALTERNATE
1/8" = 1'-0"A-101
4 STAIR TOWER ROOF
1 1/2" = 1'-0"A-101
3 THRU WALL SCUPPER DETAIL
1 1/2" = 1'-0"A-101
7 SCREEN WALL MOUNTING PLATE DETAIL - GC ALTERNATE
GC ALTERNATE
1/8" = 1'-0"A-101
1 STAIR / ELEVATOR ROOF PLAN - BASE BID
1 1/2" = 1'-0"A-101
2 PARAPET CAP DETAIL
847' - 4" Partial Ground Tier
847' - 4" Partial Ground Tier
858' - 8" Ground Tier
858' - 8" Ground Tier
892' - 8" Fourth Tier
892' - 8" Fourth Tier
904' - 5" Top of Wall
904' - 5" Top of Wall
870' - 0" Second Tier
870' - 0" Second Tier
881' - 4" Third Tier
881' - 4" Third Tier
4 2 1 4
A-501
W1 W1
W1W1
W1 W1
W1W1
W1
A-502
A-502
1 2 1 2 1 6 18
W1 W1
W1W1
W1 W1
W1
4 4 4 4 4 4 44 4 4
A-502
6'
9/
5'
3'
1/A-201
KEY PLAN
2/A-201
847' - 4" Partial Ground Tier
858' - 8" Ground Tier
892' - 8" Fourth Tier
904' - 5" Top of Wall
870' - 0" Second Tier
881' - 4" Third Tier
14 2 1
738 1
1011 9 6
W2 W2
W1 W1
W1W1
W1 W1
W1W1
W1 W1
H4
915' - 11" Top of Roof
A-502
A-502
4 44
20209 9 920 2021
21 10 109 9 9 9 9 9 9 20 16
2'
15 124
A
PROJECT NO.
DATE:
DRAWING NO.BUILDING NUMBER CHECKED DRAWN
LOCATION
DRAWING
DWG. OF
PROJECT TITLEDRAWING TITLE
FACILITY PROJECT NAME
REVISIONS DATE V
e te ra n s
A ff a ir s
OVERALL ELEVATIONS
7/10/2020
693-222
A-201
WILKES-BARRE V.A.
MEDICAL CENTER
PARKING GARAGE
WILKES-BARRE V.A. MEDICAL CENTER
GARAGE
1111 EAST END BLVD, WILKES-BARRE, PA
Checker Author
1/8" = 1'-0"A-201
1 LARGE SCALE ELEVATION - NORTH
ELEVATION LEGEND
TAG ELEVATION NOTE
1 STAMPED PRECAST CONCRETE - GC ALTERNATE
2 PRECAST SPANDREL CONCRETE
3 HOLLOW METAL FRAME
4 GUARDRAIL
5 SIGNAGE
6 ALUMINUM STORE FRONT
7 METAL PANEL
8 METAL FASCIA
9 CANOPY COLUMN - GC ALTERNATE
10 TRANSLUCENT METAL PANEL CANOPY - GC ALTERNATE
11 CANOPY SUPPORT
12 LIVING WALL SYSTEM
13 PRECAST CONCRETE TRAFFIC BOLLARD (SEE STRUCTURAL)
14 METAL HANDRAIL
15 PREFABRICATED FIBERGLASS PLANTER
16 CANOPY GUTTER - GC ALTERNATE
17 OVERFLOW SCUPPER
18 PRECAST BUTT JOINT
19 METAL COPING
20 METAL DOWNSPOUT - GC ALTERNATE
21 SNOW GUARD - GC ALTERNATE
1/8" = 1'-0"A-201
2 LARGE SCALE ELEVATION - EAST
| Sheets |
| G-001 - COVER SHEET |
| G-002 - GENERAL INFORMATION |
| CC101 - CODE COMPLIANCE PARTIAL GROUND TIER THROUGH THIRD TIER |
| CC102 - CODE COMPLIANCE FOURTH TIER AND ELEVATIONS |
| A6.2 - SIGNAGE SCHEDULE |
| A-101 - VESTIBULE ROOF PLAN AND DETAILS |
| A-201 - OVERALL ELEVATIONS |
| A-202 - OVERALL ELEVATIONS |
| A-401 - LARGE SCALE FLOOR PLANS |
| A-402 - REFLECTED CEILING PLANS |
| A-403 - LARGE SCALE STAIR PLANS |
| A-404 - LARGE SCALE CANOPY A & B PLANS - GC ALTERNATE |
| A-405 - CANOPY A & B SECTIONS - GC ALTERNATE |
| A-406 - LARGE SCALE CANOPY C, D & E PLANS & SECTIONS - GC ALTERNATE |
| A-407 - Unnamed |
| A-501 - DETAILS |
| A-502 - DETAILS - GUARDRAIL |
| A-504 - DETAILS - LIVING WALL SYSTEM - GC ALTERNATE |
| A-601 - ALUMINIUM STOREFRONT, HOLLOW METAL FRAME ELEVATIONS & DETAILS, DOOR SCHEDULE AND ROOM FINISH SCHEDULE |