This document is an appendix that outlines the device accuracy and calibration requirements for the CSD Governor Test Stand. It provides the minimum required accuracy for various devices such as pressure gauges, pressure transducers, temperature measurement devices, and RPM sensors, along with the instruments used by PMEL to calibrate the existing test stand configuration. The document is in support of a federal contract opportunity for the CSD Governor Test Stands Upgrade, which is a 100% Small Business Set-aside solicitation issued by the Department of the Air Force Materiel Command Air Force Sustainment Center. The purpose of this draft solicitation is to allow potential contractors to submit questions, and a Rough Order of Magnitude (ROM) quote is not required at this time.
View the file
Other files for this federal contract opportunity
Show all 18
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CSD Governor Test Stand Device Accuracy and Calibration Requirements
The minimum required accuracy is shown for each device along with the instrument that PMEL uses to calibrate the existing test stand configuration.
Device Range Minimum Required Accuracy
Existing PMEL Calibration Instrument
Underdrive Analog Pressure Gauge
0-400 PSI ± 2% full scale XP2i Crystal Gauge
Overdrive Analog Pressure Gauge
0-400 PSI ± 2% full scale XP2i Crystal Gauge
Underdrive Pressure Transducer
0-400 PSI ± 2% full scale XP2i Crystal Gauge
Overdrive Pressure Transducer
0-400 PSI ± 2% full scale XP2i Crystal Gauge
Charge Pressure Transducer
0-600 PSI ± 2% full scale XP2i Crystal Gauge
Lube Pressure Transducer
0-30 PSI ± 2% full scale XP2i Crystal Gauge
Oil Temperature Measurement Devices
50-300F ± 2% full scale Fluke 5520A
AC Voltage transducers
0-120VAC ± 2% full scale Fluke 5520A
DC current transducers
0-100mA ± 0.5% full scale Fluke 5520A
RPM 0-8000RPM ± 7 RPM Non-contact tachometer