SPECIFICATION

REMOTE AIR/WATER CHILLER

Models: LC 340.01-A3.5

Spec:

Revision:

Issue date:

Page:

G22-47032

20.11.2017

CONFIDENTIAL: This document and any data disclosed therein is the property of IPG Photonics Corporation and its affiliates, and constitute and contain proprietary information. Neither receipt nor possession of this document confers or transfers any right to duplicate, use, or disclose any information contained herein except as expressly authorized in writing by IPG Photonics Corporation.

No representations and warranties are made hereby, except in a binding purchase order.

SPEC - G22-47032 R00 - LC 340.01-A.3.5- ENG.doc Original Copy

1. Laser Chiller LC 340.01-A.3.5 @ 400 V / 3P / 50 Hz

1.1 General data:

Cooling capacity 34 kW Refrigerant R407C Installation Roofed outdoor operation Number of compressors 2 Number of pumps 3

1.2 Design point:

Air inlet temperature 33°C Air flow 10000 m³/h

1.3 Operation limits:

Maximum air inlet temperature 40°C (@ lower cooling capacity) Minimum air inlet temperature 10°C Minimum air inlet temperature with 30% glycol -20°C Maximum storage temperature 64°C Minimum storage temperature without water filling -40°C

1.4 Electric power consumption:

Electric power consumption design point 19,5 kW (without tank heater) Maximum electric power consumption 22,6 kW Connection volatage 400 V / 3 Ph / PE Frequency 50 Hz Voltage tolerance +/- 10 %

1.5 Control

Micro controller type IG330 Manufacturer IPG

1.6 Dimensions (footprint)

Length 1061 mm Width 803 mm High 1951 mm

1.7 Cooling water circuit laser

Cooling capacity: 33 kW Cooling water outlet temperature 21°C Cooling water return temperature 28,6°C Accuracy of water outlet temperature +/- 1 K Water flow vs. water pressure 80 l/min @ 4,6 bar 120 l/min @ 4,1 bar 160 l/min @ 3,6 bar 200 l/min @ 3,0 bar

Models: LC 340.01-A3.5

Spec:

Revision:

Issue date:

Page:

G22-47032 receipt nor possession of this document confers or transfers any right to duplicate, use, or disclose any information contained herein except as expressly authorized in writing by IPG Photonics Corporation.

No representations and warranties are made hereby, except in a binding purchase order.

SPEC - G22-47032 R00 - LC 340.01-A.3.5- ENG.doc Original Copy

1.8 Cooling water circuit optic

Cooling capacity 1 kW Cooling water outlet temperature 30°C Cooling water inlet temperature 31°C Accuracy of water outlet temperature +/- 1 K Water flow vs. water pressure 20 l/min at 3 bar

1.9 Weight without water filling 480 kg

Models: LC 340.01-A3.5

Spec:

Revision:

Issue date:

Page:

G22-47032 receipt nor possession of this document confers or transfers any right to duplicate, use, or disclose any information contained herein except as expressly authorized in writing by IPG Photonics Corporation.

No representations and warranties are made hereby, except in a binding purchase order.

SPEC - G22-47032 R00 - LC 340.01-A.3.5- ENG.doc Original Copy

2. Diagram of the pump

Models: LC 340.01-A3.5

Spec:

Revision:

Issue date:

Page:

G22-47032 receipt nor possession of this document confers or transfers any right to duplicate, use, or disclose any information contained herein except as expressly authorized in writing by IPG Photonics Corporation.

No representations and warranties are made hereby, except in a binding purchase order.

SPEC - G22-47032 R00 - LC 340.01-A.3.5- ENG.doc Original Copy

3. Dimension