Appendix_C_-_Transient_Set_Drawings_-_260708.pdf

PDF 3 MB Posted

Attached to
MWWTP Effluent FM Surge & Transient Design Build Services (UN 1282)
Solicitation number
27-002
Issued by
Charles County, Maryland

About this file

Appendix C - Transient Set Drawings Summary

This file consists of technical drawings prepared for the Board of Commissioners for Charles County, Maryland's design-build project for surge and transient management infrastructure at the Mattawoman Wastewater Treatment Plant. The appendix contains schematic and detailed drawings illustrating the configuration of the new 40-foot diameter standpipe system, including the three concrete valve vaults (influent, effluent, and bypass), interconnecting ductile iron piping, and associated hydraulic management components. The drawings depict the spatial relationships between existing and new infrastructure at the treatment plant facility located at 5310 Hawthorne Road, La Plata, Maryland 20646. Design-build teams must incorporate these transient set specifications into their 60%, 90%, and 100% design packages, with the complete design phase not to exceed 270 days from Notice to Proceed and the overall contract term spanning 690 consecutive calendar days (construction not to exceed 420 days). A non-mandatory pre-proposal meeting is scheduled for July 30, 2026, with a site visit available August 13, 2026, and questions due August 20, 2026, with proposals due October 1, 2026 at 11:00 a.m.

The project requires comprehensive design-build services with performance and payment bonds equal to 100% of the contract price. The lead design firm must demonstrate a minimum 15 years' experience with three completed municipal wastewater treatment plant projects exceeding $2 million each at facilities rated 5 million gallons per day or greater, while the lead construction firm requires 10 years' experience with three similar projects. A Minority and Women-Owned Business Enterprise subcontractor participation goal of 33.96% applies to this County-financed project exceeding $500,000, with prevailing wage rates mandated. Evaluation criteria weight price at 50 points, technical approach at 20 points, key personnel experience at 10 points, and design-build team qualifications, construction experience, construction schedule, and safety risk management at 5 points each.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

2 LOCATION MAP

SCALE: NOT TO SCALE

GHD Inc.

16701 Melford Boulevard, Suite 330 Bowie MD 20715 USA T 1 240 206 6810 F 1 240 206 6811 W www.ghd.com

1 BRIDGING DOCUMENTS TM HJS 10/17/25

CHARLES COUNTY GOVERNMENT

DEPARTMENT OF PLANNING AND GROWTH MANAGEMENT

DEVELOPMENT SERVICES DIVISION

APPROVED FOR: REMARKS OR CONDITIONS

AS - BUILTSCONSTRUCTIONGRADING

ROADS

STORM DRAINAGE

STORMWATER

MANAGEMENT

WATER

SEWER

OTHER

DATESIGNED

THIS PERMIT EXPIRES ON

DATE:

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

Project

Client

Plot Date: 16 October 2025 - 9:56 AM \\ghdnet\ghd\US\Bowie\Projects\565\12571916\Digital_Design\ACAD\Sheets\12571916-GHD-XX-XX-DRG-G-0001.dwgPlotted By: Kristopher Larson

Bar is one inch on original size sheet

Approved Date Author Drafting Check

Designer Project Director

Project No. Date

Filename:

Drawing NumberThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Title

1"

IssueNo. Checked

Design Check

Project Manager Conditions of Use

Scale Sheet

ANSI D

Size of

CHARLES COUNTY, MARYLAND

MWWTP EFFLUENT PS FORCE MAIN SURGE

MANAGEMENT SYSTEM CONSTRUCTION

T. JUNKER

J. STURDEVANT 12571916 10/2025 8

MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LA PLATA, MARYLAND 20646

COVER SHEET

G001 1AS NOTED

L. BERRY

T. JUNKER

B. BLANCHARD

T. BIAGIOLI

DEPARTMENT OF PUBLIC WORKS

CHARLES COUNTY, MARYLAND

MATTAWOMAN WASTEWATER TREATMENT PLANT -

EFFLUENT PS FORCE MAIN SURGE MANAGEMENT

SYSTEM CONSTRUCTION

OCTOBER 2025

BRIDGING DOCUMENTS

N

GENERAL NOTES:

1. LOT ADDRESS: MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LAPLATA, MARYLAND 20646

2. OWNER: CHARLES COUNTY

SANITARY DISTRICT, INC

3. TAX MAP/ GRID/ TAX MAP 0021, GRID 0008, PARCEL 0012, BLOCK N/A

PARCEL/ BLOCK:

4. ZONING IH - HEAVY INDUSTRIAL

5. LOT SIZE: 121.022 ACRES

6. DEED REFERENCES: /00126/ 00719

7. TAX ACCOUNT ID: 07-040059

8. ADC MAP: MAP 07, GRID E10 (26th EDITION)

9. ELECTION DISTRICT: 7th

10. VERTICAL DATUM: NAVD88 PLUS 1.12 FEET

11. HORIZONTAL DATUM: NAD 1983 (1991 MARYLAND STATE PLANE COORDINATE SYSTEM)

SITE LOCATION

SITE LOCATION

PERMIT APPLICATIONS*

PERMIT APPROVING AGENCY PERMIT NO. STATUS APPROVAL DATE EXPIRATION DATE

CONCEPT

STORMWATER

MANAGEMENT PLAN

CHARLES COUNTY PLANNING AND GROWTH

MANAGEMENT

SITE STORMWATER

MANAGEMENT PLAN

CHARLES COUNTY PLANNING AND GROWTH

MANAGEMENT

DEVELOPMENT SERVICE

PERMIT

CHARLES COUNTY PLANNING AND GROWTH

MANAGEMENT

BUILDING PERMIT CHARLES COUNTY PLANNING AND GROWTH

MANAGEMENT

STORMWATER

CONSTRUCTION PERMIT

MARYLAND DEPARTMENT OF THE

ENVIRONMENT (MDE)

SOIL CONSERVATION

DISTRICT PERMIT

CHARLES COUNTY SOIL CONSERVATION

DISTRIC

OBSTRUCTION

EVALUATION FEDERAL AVIATION ADMINISTRATION

1 VICINITY MAP

SCALE: NOT TO SCALE

*NOT A FINAL LIST OF PERMITS. CONTRACTOR TO DETERMINE NECESSARY PERMITS.

N http://www.ghd.com/ http://www.ghd.com

GHD Inc.

16701 Melford Boulevard, Suite 330 Bowie MD 20715 USA T 1 240 206 6810 F 1 240 206 6811 W www.ghd.com

1 BRIDGING DOCUMENTS TM HJS 10/17/25

CHARLES COUNTY GOVERNMENT

DEPARTMENT OF PLANNING AND GROWTH MANAGEMENT

DEVELOPMENT SERVICES DIVISION

APPROVED FOR: REMARKS OR CONDITIONS

AS - BUILTSCONSTRUCTIONGRADING

ROADS

STORM DRAINAGE

STORMWATER

MANAGEMENT

WATER

SEWER

OTHER

DATESIGNED

THIS PERMIT EXPIRES ON

DATE:

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

Project

Client

Plot Date: 16 October 2025 - 9:56 AM G:\565\12571916\Digital_Design\ACAD\Sheets\12571916-GHD-XX-XX-DRG-G-0002.dwgPlotted By: Kristopher Larson

Bar is one inch on original size sheet

Approved Date Author Drafting Check

Designer Project Director

Project No. Date

Filename:

Drawing NumberThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Title

1"

IssueNo. Checked

Design Check

Project Manager Conditions of Use

Scale Sheet

ANSI D

Size of

CHARLES COUNTY, MARYLAND

MWWTP EFFLUENT PS FORCE MAIN SURGE

MANAGEMENT SYSTEM CONSTRUCTION

T. JUNKER

J. STURDEVANT 12571916 10/2025 8

MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LA PLATA, MARYLAND 20646

LIST OF DRAWINGS, GENERAL

NOTES, ABBREVIATIONS,

LEGENDS, AND SYMBOLS

G002 2AS NOTED

L. BERRY

T. JUNKER

B. BLANCHARD

T. BIAGIOLI

LIST OF ABBREVIATIONS

ABD ABANDONED

CL CENTERLINE

CONC CONCRETE

CP CONSTRUCTION POINT

CV CHECK VALVE

DA DRAINAGE AREA

DIP DUCTILE IRON PIPE

EL / ELEV ELEVATION

EX EXISTING

FCH FUTURE CHEMICAL

FF FINISHED FLOOR

INV INVERT

MH MANHOLE

MIN MINIMUM

PVC POLYVINYL CHLORIDE

QTY QUANTITY

RP ROAD CONSTRUCTION POINT

SB SOIL BORING

STD STANDARD

T TELEPHONE

12" DIP, PEF

12" DIP, PEF

12" DIP, PEF

N

NEW GRAPHICS; EQUIPMENT, STRUCTURES, ETC., ARE

SHOWN AS BOLD LINEWORK AND IN THIS TEXT FORMAT.

SECTION LETTER

DRAWING NUMBER

(REPRESENTS DRAWING

WHERE SECTION IS DRAWN)

SECTION LETTER

DRAWING NUMBER

(REPRESENTS DRAWING WHERE

SECTION MARKS ARE SHOWN)

DETAIL NUMBER

DRAWING NUMBER

(REPRESENTS DRAWING

WHERE DETAIL IS DRAWN)

DETAIL NUMBER

DRAWING NUMBER

(REPRESENTS DRAWING

WHERE DETAIL IS DRAWN)

PIPING DESIGNATION

(VARIES, SEE 'LIST OF PIPING

DESIGNATIONS')

PIPE SIZE AND MATERIAL

GENERAL LEGEND

EXISTING PIPE CALLOUT (FOR PLANS)

TYPICAL SECTION MARKS (FOR PLANS)

TYPICAL SECTION SUB-TITLE (FOR SECTIONS)

TYPICAL DETAIL MARKS

TYPICAL DETAILING

PIPE SIZE AND PIPING DESIGNATION

(VARIES, SEE 'LIST OF PIPING

DESIGNATIONS')

NEW PIPE CALLOUT (FOR PLANS)

PIPING DESIGNATION

(VARIES, SEE 'LIST OF PIPING

DESIGNATIONS')PIPE SIZE AND MATERIAL

NEW/EXIST PIPE CALLOUT (FOR SECTIONS)

INVERT or CENTER LINE

ELEVATION

INVERT or CENTER LINE

NOT REQUIRED

PIPE SIZE AND PIPING

DESIGNATION

(VARIES, SEE 'LIST OF

PIPING DESIGNATIONS')

NORTH ARROW

A X-301

DETAIL NAME

A X-301

X-501

G00X

DETAIL

SCALE:

A G00X

SECTION

SCALE:

DRAINAGE AREA

DIVIDE

SILT FENCESF SF

FENCEX X

CONTOUR LINE (MAJOR)

CONTOUR LINE (MINOR)

100 YEAR FLOODPLAIN (FEMA)

EASEMENT LINE

LIGHT POST

RADIUSR##'

RP-X

XxX

ELEV

POINT #

CLEANOUTCO

YARD HYDRANT

TELEPHONET T

L L

E E

ROAD SIGN

VALVE

WATER LINEW W

SURVEY CONTROL POINT/

MONUMENT (BENCHMARK)

UTILITY POLE

LIGHT POLE

PROCESS MANHOLE

CONCRETE

EXISTING STRUCTURE

PROPERTY LINE

WOODS

TEMPORARY FENCE

SOIL DIVIDE LINE

SOIL TYPE

RIPRAP

MH

X X X X

ELECTRICAL DUCTBANK

SANITARY MANHOLESMH

FIRE HYDRANT

ROADWAY CONSTRUCTION

STAKEOUT POINT

CHEMICAL MANHOLE

DRAINAGE MANHOLE

ELECTRICAL MANHOLE

ELECTRICAL HANDHOLE

15-25% SLOPES

>25% SLOPES

NEW STRUCTURE

CP-X

CMH

DMH

FH

LIMIT OF DISTURBANCE

SCE

LOD LOD

CIVIL LEGEND

CULVERT

M

S

SOLENOID VALVE

PRESSURE RELIEF VALVE

PRESSURE GAUGE

MOTOR OPERATOR

HOSE BARB

QUICK CONNECT (FEMALE)

T

FM

I

TEMPERATURE GAUGE

FLOW METER

HEAT TRACED AND INSULATED

PIPING (FOR INSULATION LIMITS

AND REQUIREMENTS REFER TO

INDIVIDUAL DRAWINGS)

PIPE FITTINGS AND VALVE SYMBOLS

PLUG VALVE

PINCH VALVE

GATE VALVE

CHECK VALVE

BALL VALVE

GLOBE VALVE

BUTTERFLY VALVE

PRSSURE REDUCING VALVE

3-WAY PLUG VALVE

DIAPHRAGM VALVE

FLUSHING CONNECTION

W/ CAP OR PLUG

AIR RELEASE VALVE

ELBOW UP

ELBOW DOWN

TEE IN PLANE

TEE DOWN

TEE UP

45° ELBOW

90° ELBOW

LATERAL WYE

CONCENTRIC REDUCER

ECCENTRIC REDUCER

BLIND FLANGE

PIPE CAP

MECHANICAL JOINT

FLANGED JOINT

WELDED JOINT

EXPANSION JOINT

DISMANTLING JOINT/

FLANGED COUPLING ADAPTER

EXPANSION COUPLING

MECHANICAL COUPLING

FLOWMETER

RESTRAINED JOINT/ PUSH ON JOINT

FM

RESTRAINED DISMANTLING JOINT/

RESTRAINED FLANGE COUPLING

ADAPTER

INSULATED PIPING

HOSE BIBB

HOSE RACK

DOUBLE LINE SINGLE LINE

90° BEND

45° BEND

TEE

LATERAL WYE

REDUCER

PLUG VALVE

GATE VALVE

YARD PIPING LEGEND

ELBOW UP

ELBOW DOWN

90° ELBOW IN PLANE

TEE UP

TEE DOWN

ECCENTRIC REDUCER

45° ELBOW IN PLANE

SINGLE LINE

PIPING SYMBOLS

Y STRAINER

DRAIN

GRAVEL PAVEMENT

ELECTRIC POLE

INV EL XX.XX

℄ EL XX.XX

SB-X SOIL BORING

DRAINAGE SWALE> >

WETLAND

25' WETLAND BUFFER

LIST OF DRAWINGS

SHEET

COUNT

DRAWING

# SHEET TITLE

GENERAL

1 G001 COVER SHEET

2 G002 LIST OF DRAWINGS, GENERAL NOTES, ABBREVIATIONS, LEGENDS, AND SYMBOLS

CIVIL

3 C001 EXISTING SITE PLAN AND DEMOLITION PLAN

4 C002 PROPOSED SITE, PIPING, AND GRADING PLAN

MECHANICAL

5 M001 PARTIAL PROCESS FLOW DIAGRAM AND DESIGN CRITERIA

6 M002 STANDPIPE STRUCTURES PLANS

7 M003 STANDPIPE STRUCTURES SECTIONS

ELECTRICAL

8 E001 ELECTRICAL SITE PLAN

LIST PIPING DESIGNATIONS

PIPE DESIGNATION PIPE NAME

ABD ABANDONED

DRN DRAIN

EFF PLANT EFFLUENT

FTR FUTURE USE

INF STANDPIPE INFLUENT

NPW NON POTABLE WATER

PA PROCESS AIR

PD PANT DRAIN

PW POTABLE WATER

RAW RAW INLUENT

SAMP SAMPLE LINE

SD STORM DRAIN

SEF SCREEN EFFLUENT

SPD SUMP PUMP DISCHARGE

UW UTILITY WATER

VT VENT

1. EXISTING FACILITIES AND PIPING SHOWN LIGHT. NEW FACILITIES

AND PIPING SHOWN DARK.

2. EXISTING CONDITIONS SHOWN ON THE DRAWINGS ARE BASED

ON TOPOGRAPHIC SURVEY PERFORMED BY D.H. STEFFENS

COMPANY IN JUNE 2024, AND OBTAINED FROM AVAILABLE

CONTRACT AND RECORD DRAWINGS. LOCATIONS MUST BE

CONSIDERED APPROXIMATE ONLY.

3. THE DESIGN IN THIS DRAWING SET IS PRELIMINARY AND BASED

ON THE INFORMATION AVAILABLE AT THE TIME OF DESIGN. FINAL

DESIGN FOR ALL ASPECTS SHALL BE BY THE DESIGN BUILDER.

GENERAL NOTES

11.0 FT FLOOD ELEVATION

(SEE NOTE 2)

EXISTING

PUMPING STATION

100 YEAR FLOODPLAIN

(SEE NOTE 1)

(SEE NOTE 3)

DEMOLISH PIPING AND FITTINGS AS

NECESSARY FOR STANDPIPE INFLUENT

AND EFFLUENT PIPE CONNECTIONS (TYP)

DEMOLISH PIPING

SCALE: 1"=10'-0"

EXISTING SITE PLAN AND DEMOLITION PLAN

0 20'

SCALE 1" = 10' AT ORIGINAL SIZE

15105

NOTES:

1. 100 - YEAR FLOODPLAIN IS FROM FEMA FIRM PANEL 155 OF 575, MAP 24017C0155D, EFF DATE 5/4/2015.

2. BASE FLOOD ELEVATION (11 FEET) PER FEMA FIRM PANEL 24017C0155C EFF. DATE 9/4/2013.

3. EXTENT OF PAVEMENT DEMOLITION NOT SHOWN. DESIGN BUILDER SHALL DEMOLISH PAVEMENT WITHIN THE AREA OF PROPOSED WORK TO THE EXTENT DIRECTED BY THE COUNTY AND AS NECESSARY TO INSTALL THE PROPOSED WORK.

4. DESIGN BUILDER SHALL NOT INITIATE DEMOLITION WITHOUT PRIOR COORDINATION WITH THE OWNER.

5. PROTECT EXISTING FENCE AND GATE DURING CONSTRUCTION. ANY DAMAGE OR REMOVED FENCING DURING CONSTRUCTION ACTIVITIES SHALL BE REPLACED IN KIND AT DESIGN BUILDER'S ESPENSE. NO ADDITIONAL EXPENSE TO THE OWNER.

GHD Inc.

16701 Melford Boulevard, Suite 330 Bowie MD 20715 USA T 1 240 206 6810 F 1 240 206 6811 W www.ghd.com

1 BRIDGING DOCUMENTS TM HJS 10/17/25

CHARLES COUNTY GOVERNMENT

DEPARTMENT OF PLANNING AND GROWTH MANAGEMENT

DEVELOPMENT SERVICES DIVISION

APPROVED FOR: REMARKS OR CONDITIONS

AS - BUILTSCONSTRUCTIONGRADING

ROADS

STORM DRAINAGE

STORMWATER

MANAGEMENT

WATER

SEWER

OTHER

DATESIGNED

THIS PERMIT EXPIRES ON

DATE:

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

Project

Client

Plot Date: 16 October 2025 - 9:56 AM G:\565\12571916\Digital_Design\ACAD\Sheets\12571916-GHD-XX-XX-DRG-C-0001.dwgPlotted By: Kristopher Larson

Bar is one inch on original size sheet

Approved Date Author Drafting Check

Designer Project Director

Project No. Date

Filename:

Drawing NumberThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Title

1"

IssueNo. Checked

Design Check

Project Manager Conditions of Use

Scale Sheet

ANSI D

Size of

CHARLES COUNTY, MARYLAND

MWWTP EFFLUENT PS FORCE MAIN SURGE

MANAGEMENT SYSTEM CONSTRUCTION

T. JUNKER

J. STURDEVANT 12571916 10/2025 8

MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LA PLATA, MARYLAND 20646

EXISTING SITE PLAN AND

DEMOLITION PLAN

C001 3AS NOTED

L. BERRY

T. JUNKER

B. BLANCHARD

T. BIAGIOLI

N

LEGEND

DEMOLITION

EXISTING

PUMPING STATION

EFFLUENT

VALVE VAULT

INFLUENT

VALVE VAULT

54"x42"

WYE

THRUST BLOCK

(SEE NOTE 3)

THRUST BLOCK

(SEE NOTE 3)

42"x36" REDUCER

RESTRAINED

MECHANICAL

TEMPORARY ISOLATION

VALVE AND BLIND FLANGE

TEMPORARY BYPASS PIPE

FM

TEMPORARY FLOWMETER

TEMPORARY BYPASS PIPE

(SEE NOTE 4)

40ft DIAMETER

DUAL OVERFLOW

36"x24" REDUCER

36"x24"

WYE

6" DIP, DRN

OVERFLOW ROUTED

TO WET WELL

DRAIN TIES IN WITH

OVERFLOW TO WET WELL

11.0 FT FLOOD ELEVATION

(SEE NOTE 2)

100 YEAR FLOODPLAIN

(SEE NOTE 1)

36" GATE VALVE

WITH ELECTRIC

ACTUATOR

CONNECT SUMP PUMP

DISCHARGE TO PLANT

SEWER (TYP)

STANDPIPE

(T/S EL. 18.00)

BYPASS VALVE VAULT RESTRAINED

DISMANTLING

JOINT (TYP)

45° BEND

SCALE: 1"=10'-0"

PROPOSED SITE, PIPING AND GRADING PLAN

0 20'

SCALE 1" = 10' AT ORIGINAL SIZE

15105

GHD Inc.

16701 Melford Boulevard, Suite 330 Bowie MD 20715 USA T 1 240 206 6810 F 1 240 206 6811 W www.ghd.com

1 BRIDGING DOCUMENTS TM HJS 10/17/25

CHARLES COUNTY GOVERNMENT

DEPARTMENT OF PLANNING AND GROWTH MANAGEMENT

DEVELOPMENT SERVICES DIVISION

APPROVED FOR: REMARKS OR CONDITIONS

AS - BUILTSCONSTRUCTIONGRADING

ROADS

STORM DRAINAGE

STORMWATER

MANAGEMENT

WATER

SEWER

OTHER

DATESIGNED

THIS PERMIT EXPIRES ON

DATE:

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

Project

Client

Plot Date: 16 October 2025 - 9:56 AM G:\565\12571916\Digital_Design\ACAD\Sheets\12571916-GHD-XX-XX-DRG-C-0002.dwgPlotted By: Kristopher Larson

Bar is one inch on original size sheet

Approved Date Author Drafting Check

Designer Project Director

Project No. Date

Filename:

Drawing NumberThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Title

1"

IssueNo. Checked

Design Check

Project Manager Conditions of Use

Scale Sheet

ANSI D

Size of

CHARLES COUNTY, MARYLAND

MWWTP EFFLUENT PS FORCE MAIN SURGE

MANAGEMENT SYSTEM CONSTRUCTION

T. JUNKER

J. STURDEVANT 12571916 10/2025 8

MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LA PLATA, MARYLAND 20646

PROPOSED SITE, PIPING, AND

GRADING PLAN

C002 4AS NOTED

L. BERRY

T. JUNKER

B. BLANCHARD

T. BIAGIOLI

20' -0"

MINIMUM

N

NOTES:

1. 100 - YEAR FLOODPLAIN IS FROM FEMA FIRM PANEL 155 OF 575, MAP 24017C0155D, EFF DATE 5/4/2015.

2. BASE FLOOD ELEVATION (11 FEET) PER FEMA FIRM PANEL 24017C0155C EFF. DATE 9/4/2013.

3. THRUST BLOCKS ARE NOT DRAWN TO SCALE. DESIGN BUILDER TO SIZE THRUST BLOCKS.

4. DESIGN BUILDER SHALL BE RESPONSIBLE FOR THE DESIGN OF THE TEMPORARY BYPASS PIPE AND ALL ASSOCIATED FITTINGS, CONNECTION DETAILS, THRUST RESTRAINT, TEMPORARY SUPPORTS AND ALL OTHER FACILITIES REQUIRED FOR THE FULL DURATION OF THE ANTICIPATED TEMPORARY OPERATING SCENARIOS.

DESIGN BUILDER TO DETERMINE THE FEASIBILITY OF REUSING THE EXISTING TAPS FOR LINE STOPS.

5. DESIGN BUILDER SHALL DESIGN THE NUMBER AND DISTRIBUTION OF BOLLARDS TO PROTECT EXPOSED

PIPING, STAIRCASE, AND STANDPIPE.

6. EXTENT OF PAVEMENT AND YARD RESTORATION NOT SHOWN. DESIGN-BUILDER SHALL RESTORE PAVEMENT

AND YARD WITHIN THE AREA OF PROPOSED WORK TO THE EXTENT DIRECTED BY THE COUNTY.

7. DESIGN BUILDER SHALL DESIGN A SWALE CAPABLE OF CONVEYING 60 MGD FROM THE CONCRETE SPLASH

PAD TO THE OUTSIDE OF THE EXISTING FENCE.

8. DESIGN BUILDER SHALL REPLACE ANY DAMAGED OR REMOVED FENCE IN KIND DURING CONSTRUCTION.

CONCRETE SPLASH PAD

FOR BLOW OFF PANELS

(REFER TO DWG M003)

36"x36" TEE

SEE NOTE 8

SEE NOTE 7

SEE NOTE 6

RELOCATE EXISTING

DRAINS AS NECESSARY

BOLLARD (TYP)

(SEE NOTE 5)

COUPLING (TYP)

GHD Inc.

16701 Melford Boulevard, Suite 330 Bowie MD 20715 USA T 1 240 206 6810 F 1 240 206 6811 W www.ghd.com

1 BRIDGING DOCUMENTS TM HJS 10/17/25

CHARLES COUNTY GOVERNMENT

DEPARTMENT OF PLANNING AND GROWTH MANAGEMENT

DEVELOPMENT SERVICES DIVISION

APPROVED FOR: REMARKS OR CONDITIONS

AS - BUILTSCONSTRUCTIONGRADING

ROADS

STORM DRAINAGE

STORMWATER

MANAGEMENT

WATER

SEWER

OTHER

DATESIGNED

THIS PERMIT EXPIRES ON

DATE:

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

Project

Client

Plot Date: 16 October 2025 - 9:57 AM G:\565\12571916\Digital_Design\ACAD\Sheets\12571916-GHD-XX-XX-DRG-M-0001.dwgPlotted By: Kristopher Larson

Bar is one inch on original size sheet

Approved Date Author Drafting Check

Designer Project Director

Project No. Date

Filename:

Drawing NumberThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Title

1"

IssueNo. Checked

Design Check

Project Manager Conditions of Use

Scale Sheet

ANSI D

Size of

CHARLES COUNTY, MARYLAND

MWWTP EFFLUENT PS FORCE MAIN SURGE

MANAGEMENT SYSTEM CONSTRUCTION

T. JUNKER

J. STURDEVANT 12571916 10/2025 8

MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LA PLATA, MARYLAND 20646

PARTIAL PROCESS FLOW

DIAGRAM AND DESIGN CRITERIA

M001 5NOT TO SCALE

L. BERRY

T. JUNKER

B. BLANCHARD

T. BIAGIOLI

FM

STANDPIPE

DESIGN CRITERIA

FLOWS

DESIGN FLOW 60 MGD

STANDPIPE

NUMBER OF STANDPIPES 1

MINIMUM TOP OF WALL ELEVATION 138 FT

MINIMUM FREEBOARD 15 FT

MINIMUM DIAMETER 40 FT

OVERFLOW LOCATION EXTERIOR

MINIMUM COMBINED OVERFLOW

CROSS SECTIONAL AREA 900 SQ IN

FLOW METERFM

GATE VALVE

INFLUENT

VALVE VAULT

OVERFLOW

EFFLUENT

VALVE VAULT

UTILITY WATER

CONNECTION

SUMP DRAIN

M

MMDRAIN

VENT

NEW/ MODIFY

LEGEND

MAIN PROCESS FLOW

DRAIN

VENT

GATE VALVE

CHECK VALVE

PUMP

BYPASS VALVE VAULT

SUMP PUMP

DISCHARGE (TYP)

MINIMUM COMBINED OVERFLOW

CROSS SECTIONAL AREA

900 SQ IN

40' DIAMETER

T/W EL. 138.00

T/S EL. 18.00

42" DIP, EFF

PLATFORM

(12'-0"x5'-0" MIN)

A M003

C M003

42" DIP, INF

CL OF INFLUENT PIPE

LADDER

(SEE NOTE 1)

CL OF EFFLUENT PIPE

COVER

FROM EFFLUENT

PUMP STATION

TO EFFLUENT

FORCE MAIN

24" OVERFLOW

24" OVERFLOW

36"x24" WYE

36"x24" REDUCER

36" OVERFLOW ROUTED

TO WET WELL

MANWAY AT GRADE

24"x10" WYE

10" GATE VALVE

10" SUMP DRAIN

B M003

3'-0" MIN

(SEE NOTE 5)

1'-0"

4'- 0"

MI

N

42" GATE VALVE

42" DIP, EFF

SUMP PUMP

DISCHARGE

CONCRETE

VALVE VAULT

(SEE NOTE 3)

3'- 0"

MI

N

SUMP PUMP

LADDER

SEE NOTE 2

RESTRAINED

DISMANTLING

JOINT

1'-0"

MIN

B

M003

CONCRETE

VALVE VAULT

PERSONNEL

ACCESS

REMOVABLE TO SLAB TO

ACCESS VALVE (SEE NOTE 4)

0 4'-0"

SCALE 3/16"=1'-0" AT ORIGINAL SIZE

8'-0" 12'-0"

1 STANDPIPE PLAN

SCALE: 3/16"=1'-0"

N

GHD Inc.

16701 Melford Boulevard, Suite 330 Bowie MD 20715 USA T 1 240 206 6810 F 1 240 206 6811 W www.ghd.com

1 BRIDGING DOCUMENTS TM HJS 10/17/25

CHARLES COUNTY GOVERNMENT

DEPARTMENT OF PLANNING AND GROWTH MANAGEMENT

DEVELOPMENT SERVICES DIVISION

APPROVED FOR: REMARKS OR CONDITIONS

AS - BUILTSCONSTRUCTIONGRADING

ROADS

STORM DRAINAGE

STORMWATER

MANAGEMENT

WATER

SEWER

OTHER

DATESIGNED

THIS PERMIT EXPIRES ON

DATE:

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

Project

Client

Plot Date: 16 October 2025 - 9:57 AM G:\565\12571916\Digital_Design\ACAD\Sheets\12571916-GHD-XX-XX-DRG-M-0002.dwgPlotted By: Kristopher Larson

Bar is one inch on original size sheet

Approved Date Author Drafting Check

Designer Project Director

Project No. Date

Filename:

Drawing NumberThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Title

1"

IssueNo. Checked

Design Check

Project Manager Conditions of Use

Scale Sheet

ANSI D

Size of

CHARLES COUNTY, MARYLAND

MWWTP EFFLUENT PS FORCE MAIN SURGE

MANAGEMENT SYSTEM CONSTRUCTION

T. JUNKER

J. STURDEVANT 12571916 10/2025 8

MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LA PLATA, MARYLAND 20646

3 INFLUENT/EFFLUENT VALVE VAULT TOP PLAN

SCALE: 1/2"=1'-0"

2 INFLUENT/EFFLUENT VALVE VAULT BOTTOM PLAN

SCALE: 1/2"=1'-0"

STANDPIPE STRUCTURES PLANS

M002 6AS NOTED

L. BERRY

T. JUNKER

B. BLANCHARD

T. BIAGIOLI

SCALE 1/2"=1'-0" AT ORIGINAL SIZE

1'-0" 4'-0"2'-0" 3'-0"

SCALE 1/2"=1'-0" AT ORIGINAL SIZE

1'-0" 4'-0"2'-0" 3'-0"

NOTES:

1. STANDPIPE INTERIOR LADDER SHALL HAVE INTERMEDIATE LANDINGS AS DIRECTED

BY THE OWNER OR OSHA REGULATIONS.

2. 12" FUTURE UTILITY WATER CONNECTION WITH ISOLATION VALVE AND BLIND

FLANGE ON EFFLUENT VALVE VAULT. 6" DRAIN CONNECTION WITH ISOLATION VALVE

ROUTED TO OVERFLOW PIPE ON INFLUENT VALVE VAULT. SEE CIVIL DRAWINGS.

3. DESIGN BUILDER SHALL BE RESPONSIBLE FOR DESIGN OF ALL CONCRETE VAULTS

PER THE CRITERIA OUTLINED IN THE SPECIFICATIONS.

4. VALVE VAULT TOP SLABS TO HAVE EMBEDDED LIFTING HOOKS.

5. BYPASS VALVE VAULT NOT SHOWN. DESIGN BUILDER SHALL DESIGN BYPASS VALVE

VAULT TO THE SAME SPECIFICATIONS AND MINIMUM DIMENSIONS AS SHOWN FOR

THE INFLUENT AND EFFLUENT VALVE VAULTS.

MIN

WALL PENETRATION PER

SPECIFICATIONS (TYP)

T/W EL 138.00 ±

T/S EL 18.00 ±

GRADE EL 17.50 ±

TOP PLATFORMCOVER

VENTS (TYP)

(SEE NOTE 6)

0 4'-0" 16'-0"

SCALE 1/8"=1'-0" AT ORIGINAL SIZE

8'-0" 12'-0" A

M002

SECTION

SCALE: 1/8"=1'-0"

NOTES:

1. DESIGN BUILDER SHALL BE RESPONSIBLE FOR STRUCTURAL DESIGN AND CONNECTION DETAILS

ASSOCIATED WITH THE SPIRAL STAIRCASE. LOCATION OF SPIRAL STAIRCASE SHALL BE

COORDINATED WITH INFLUENT/EFFLUENT PIPE, OVERFLOW PIPES, AND PLATFORMS. LANDINGS

SHALL BE PROVIDED AT SPACING REQUIRED BY OSHA OR REQUESTED BY THE COUNTY.

2. SIZE, STYLE, AND DISTRIBUTION OF BLOWOFF PANELS BY THE DESIGN BUILDER. BLOWOFF

PANELS MUST HAVE CONCRETE SPLASH PAD BENEATH AT GRADE WITH SWALE TO CARRY

OFFSITE. SEE CIVIL SHEETS.

3. DESIGN BUILDER SHALL BE RESPONSIBLE FOR DESIGN OF ALL CONCRETE VAULTS PER THE

CRITERIA OUTLINED IN THE SPECIFICATIONS.

4. THE DESIGN BUILDER SHALL BE RESPONSIBLE FOR THE BASE SLAB AND FOUNDATION

STRUCTURAL DESIGN, UTILIZING THE GEOTECHNICAL INFORMATION PROVIDED IN THE

SPECIFICATIONS. FOUNDATION DESIGN TO INCLUDE ANY NECESSARY GROUND IMPROVEMENT

AND/ OR OVER-EXCAVATION AND PLACEMENT OF CLEAN FILL, AS DETERMINED BY THE DESIGN

BUILDER.

5. THE DESIGN BUILDER SHALL BE RESPONSIBLE FOR DETERMINING THE REQUIRED SPACING OF ALL

INTERIOR AND EXTERIOR PIPE SUPPORTS, FOR ALL PIPING SYSTEMS.

6. DESIGN BUILDER SHALL BE RESPONSIBLE FOR SIZING AND DISTRIBUTING VENTS TO PREVENT PRESSURIZATION OF THE STANDPIPE. VENTS SHALL HAVE STAINLESS STEEL 316 BIRD SCREENS

AND SHALL BE DESIGNED TO PREVENT SUNLIGHT FROM ENTERING THE STANDPIPE.

7. RESTRAINED EXPANSION JOINTS SHALL BE SIZED BY THE DESIGN BUILDER TO ACCOMMODATE

STANDPIPE SETTLEMENT.

GHD Inc.

16701 Melford Boulevard, Suite 330 Bowie MD 20715 USA T 1 240 206 6810 F 1 240 206 6811 W www.ghd.com

1 BRIDGING DOCUMENTS TM HJS 10/17/25

CHARLES COUNTY GOVERNMENT

DEPARTMENT OF PLANNING AND GROWTH MANAGEMENT

DEVELOPMENT SERVICES DIVISION

APPROVED FOR: REMARKS OR CONDITIONS

AS - BUILTSCONSTRUCTIONGRADING

ROADS

STORM DRAINAGE

STORMWATER

MANAGEMENT

WATER

SEWER

OTHER

DATESIGNED

THIS PERMIT EXPIRES ON

DATE:

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

Project

Client

Plot Date: 17 October 2025 - 10:45 AM \\ghdnet\ghd\US\Bowie\Projects\565\12571916\Digital_Design\ACAD\Sheets\12571916-GHD-XX-XX-DRG-M-0003.dwgPlotted By: Kristopher Larson

Bar is one inch on original size sheet

Approved Date Author Drafting Check

Designer Project Director

Project No. Date

Filename:

Drawing NumberThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Title

1"

IssueNo. Checked

Design Check

Project Manager Conditions of Use

Scale Sheet

ANSI D

Size of

CHARLES COUNTY, MARYLAND

MWWTP EFFLUENT PS FORCE MAIN SURGE

MANAGEMENT SYSTEM CONSTRUCTION

T. JUNKER

J. STURDEVANT 12571916 10/2025 8

MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LA PLATA, MARYLAND 20646

STANDPIPE STRUCTURES

SECTIONS

M003 7AS NOTED

L. BERRY

T. JUNKER

B. BLANCHARD

T. BIAGIOLI

B M002

SECTION

SCALE: 1/2"=1'-0"

C M002

SECTION

SCALE: 1/4"=1'-0" 0 2'-0" 8'-0"

SCALE 1/4"=1'-0" AT ORIGINAL SIZE

4'-0" 6'-0"

SCALE 1/2"=1'-0" AT ORIGINAL SIZE

1'-0" 4'-0"2'-0" 3'-0"

TO/ FROM EFFLUENT

FORCE MAIN

STANDPIPE

T/S EL 18.00±

STAINLESS STEEL

316 SAFETY CAGE

'-0

" M

IN

42" DIP EFF

(SEE NOTE 5)

SUMP PUMP

SLOPE TO SUMP

1'- 0"

MI

N

3'-0"

MIN

1'-0"

MIN

RESTRAINED

DISMANTLING JOINT

PIPE STAND (AS NEEDED)

CONCRETE VALVE VAULT

(SEE NOTE 3)

FLUSH WITH GRADE

T/S EL 17.50±

℄ EL 8.25±

PERSONNEL ACCESS

DUAL 24" OVERFLOW

(SEE NOTE 5)

OVERFLOW SCUPPER

BOX INV EL 123.00±

JOG STAIRCASE AROUND

OVERFLOW (TYP)

SPIRAL STAIRCASE

(SEE NOTE 1)

BLOWOFF PANELS

(TYP) (SEE NOTE 2)

BOTTOM SLAB

SHALL SLOPE

TO SUMP

(SEE NOTE 4)

10" SUMP DRAIN

MANWAY(S) ACCESSIBLE FROM

GRADE. LOCATION AND SIZE TBD

TO WET WELL

℄ EL BY THE

DESIGN-BUILDER 42" DIP, EFF

℄ EL 8.25±

WALL PENETRATION PER

SPECIFICATIONS (TYP)

WALL PENETRATION PER

SPECIFICATIONS (TYP)

SLAB PENETRATION PER

SPECIFICATIONS (TYP)

MAX WSE 123.00

RESTRAINED EXPANSION JOINT

(SEE NOTE 7)

VALVE SUPPORT

EXISTING

PUMPING STATION

54"x42"

WYE

THRUST BLOCK THRUST BLOCK

36" GATE VALVE

42"x36" REDUCER

MECHANICAL

COUPLING

11.0 FT FLOOD ELEVATION

100 YEAR FLOODPLAIN

EFFLUENT

VALVE VAULT

INFLUENT

VALVE VAULT

STANDPIPE

(T/S EL 18.00)

SCALE: 1"=10'-0"

EXISTING SITE PLAN

0 20'

SCALE 1" = 10' AT ORIGINAL SIZE

15105

GHD Inc.

16701 Melford Boulevard, Suite 330 Bowie MD 20715 USA T 1 240 206 6810 F 1 240 206 6811 W www.ghd.com

1 BRIDGING DOCUMENTS TM HJS 10/17/25

CHARLES COUNTY GOVERNMENT

DEPARTMENT OF PLANNING AND GROWTH MANAGEMENT

DEVELOPMENT SERVICES DIVISION

APPROVED FOR: REMARKS OR CONDITIONS

AS - BUILTSCONSTRUCTIONGRADING

ROADS

STORM DRAINAGE

STORMWATER

MANAGEMENT

WATER

SEWER

OTHER

DATESIGNED

THIS PERMIT EXPIRES ON

DATE:

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

CONSTRUCTION

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

AS - BUILTS

Project

Client

Plot Date: 16 October 2025 - 9:58 AM G:\565\12571916\Digital_Design\ACAD\Sheets\12571916-GHD-XX-XX-DRG-E-0001.dwgPlotted By: Kristopher Larson

Bar is one inch on original size sheet

Approved Date Author Drafting Check

Designer Project Director

Project No. Date

Filename:

Drawing NumberThis document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

www.ghd.com

Title

1"

IssueNo. Checked

Design Check

Project Manager Conditions of Use

Scale Sheet

ANSI D

Size of

CHARLES COUNTY, MARYLAND

MWWTP EFFLUENT PS FORCE MAIN SURGE

MANAGEMENT SYSTEM CONSTRUCTION

T. JUNKER

J. STURDEVANT 12571916 10/2025 8

MATTAWOMAN WASTEWATER TREATMENT PLANT

5310 HAWTHORNE RD

LA PLATA, MARYLAND 20646

ELECTRICAL SITE PLAN

E001 8AS NOTED

L. BERRY

T. JUNKER

B. BLANCHARD

T. BIAGIOLI

N

NOTES:

1. DRAWING DOES NOT INCLUDE ALL INSTRUMENTS AND SENSORS THAT ARE REQUIRED.

2. DUCTBANKS, JUNCTION BOXES AND PULL BOXES ARE NOT SHOWN.

3. ALL STRUCTURES SHALL BE GROUNDED.

4. LIGHTING SHALL BE PROVIDED AROUND THE STANDPIPE, VAULTS, AND WITHIN THE VAULTS.

5. LIGHTING SHALL BE PROVIDED ON STANDPIPE AS REQUIRED BY FAA.

6. PROVIDE CONTROL PANELS NEAR THE BASE OF THE STANDPIPE. THE CONTROL PANELS

SHALL BE MOUNTED TO A FREESTANDING EQUIPMENT MOUNTING RACK WITH POSTS

ANCHORED INTO A RAISED CONCRETE PAD. A VALVE CONTROL PANEL SHALL BE PROVIDED

TO OPEN AND CLOSE THE THREE MOTORIZED GATE VALVES. ADDITIONALLY, PLACE EACH

SUMP PUMP CONTROL PANEL IN THIS LOCATION.

7. NEW ELECTRICAL EQUIPMENT AND INSTRUMENTATION TO BE FED FROM LIGHTING

PANELBOARDS LP-1 AND LP-2 LOCATED IN THE EFFLUENT PUMP STATION ELECTRICAL

ROOM. DESIGN BUILDER TO COORDINATE WITH THE COUNTY AND DETERMINE THE EXACT

LOCATION OF ELECTRICAL FEED AND AVAILABLE CAPACITY.

8. I/O FOR NEW INSTRUMENTATION TO BE WIRED TO EXISTING CONTROL PANELS IN THE

EFFLUENT PUMP STATION, INCLUDING PS-RIO AND PS-CP. DESIGN BUILDER TO

COORDINATE WITH THE COUNTY AND DETERMINE THE EXACT LOCATION TO WIRE I/O.

LS

M M

M

LS

LS

LSLSLS

LE

ZS

MOTORIZED GATE

VALVE (TYP OF 3)

SUMP PUMP

(TYP OF 3)

FLOAT LSHH, LSH,

LSL (TYP OF 3) M M

M

BLOWOFF PANEL POSITION

SWITCHES (TYP FOR EACH)

RADAR

FLOAT LSHH

FLOAT LSH

FLOAT LSL ELECTRICAL PANELS

(SEE NOTE 6)

http://www.ghd.com/ http://www.ghd.com

Sheets and Views
12571916-GHD-XX-XX-DRG-G-0001-Layout1

File details come from the government source that posted it. Updated .