About this file
This document is Appendix C - Scope of Work for a roof replacement project for the Pueblo West Library, located at 298 S Joe Martinez Blvd. in Pueblo West, Colorado, under the jurisdiction of the Pueblo Regional Building Department. The project involves a comprehensive roof replacement for a single-story, 26,614 square foot public library building constructed in 1999, with two primary scope options: 1) a complete tear-off and replacement with a new PVC membrane roof system, and 2) a recover option using an EPDM membrane. The scope of work includes removing the existing single-ply TPO membrane roof installed in 2018, installing new vapor retarder, inspecting and replacing insulation, adding tapered crickets, installing cover board, and applying new membrane with detailed flashing at parapet walls, curbs, and penetrations. Additional work includes resetting mechanical equipment, replacing wall coping, and implementing comprehensive safety measures.
The project requires extensive site preparation, including setting up a construction yard, placing a dumpster, installing safety guard rails, and managing pedestrian traffic. The roof structure is a metal building with a steel frame and roof deck, featuring a low-slope design with a 1/4 inch per foot slope. The total roof area is approximately 157.1 square feet, with additional areas for parapet and wall flashing. While specific pricing is not detailed in the document, the scope suggests a comprehensive replacement approach that prioritizes warranty requirements, structural integrity, and adherence to manufacturers' installation instructions and OSHA safety standards. The project appears to be funded through local government resources, with a focus on maintaining the library's infrastructure and ensuring long-term roof performance.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Professional Construction Services
11877 W. 80th Ave. Arvada, CO 80005 Phone: 720-340-7530
Fax: 866-459-3334
Appendix C
Scope of Work and
Roof Details
Building Information
Location: 298 S Joe Martinez Blvd. Pueblo West, Colorado 81007
Jurisdiction Pueblo Regional Building Department is the authority having jurisdiction (AHJ)
Elevation: 5,131 feet Built: 1999 Building Use: Public Library Classification: Group A-3 Assembly occupancies Construction: Metal building with steel frame and roof deck No. Stories 1 GFA 26,614 SF approximate gross floor area
ROOF STRUCTURE
Type: Steel structure Roof Deck: Metal M-Deck (gauge T.B.D.)
Purlins: Gauge and thickness T.B.D.
Columns: T.B.D.
ROOF
Roof Style: Low Slope
Roof Covering: Single Ply TPO Membrane Roof Installed: 2018 Roof Age: 3-yrs
Roof Slope: 1/4 in per foot
Roof Height: Approximately 16 to 18 feet from the ground to the top of the parapet walls.
EXTERIOR
Walls Concrete block
DRAINAGE
Drains Internal roof drains and overflow drains
ACCESS
Roof Access: Front. Left and right parking areas
BUILDING INFORMATION
03/21/25
Pueblo West Library
Scope of Work
Item Qty Unit Action
PROPOSED SCOPE OF WORK
Notes
Pueblo West Library 03/21/25
Tear-off 157.1 SQ Remove Remove and haul away the existing roof system including the membrane all roof components
Vapor Retarder 157.1 SQ Install Install new class 2 vapor retarder with a perm rating from 0.1 to 1.0
Insulation 157.1 SQ Install Inspect and replace damaged insulation board as necessary
Taper / Crickets 33.8 SQ Replace Install new 1/4” slope crickets at the upslope of all curbs
Cover Board 157.1 SQ Install Install new 1/2-inch Fiberglass reinforced gypsum cover board
Protective Matt 157.14 SQ Install Install specified protective matt in the field
Membrane 212.9 SQ Total Install new single ply 60 or 80 mil PVC membrane
Field 157.1 SQ Install Install new 60 mil reinforced single ply PVC membrane in the field
Parapet Walls 23.4 SQ Install Install new single ply PVC membrane at the parapet walls to extend up and over by 2" min.
Walls 27.6 SQ Install Install new single ply PVC membrane at the walls to extend under siding a minimum of 2"
Curbs 4.8 SQ Install Install new single ply PVC membrane to the top of all curbs and up and over where possible.
Curb Flashings
Termination 173.7 LF Install Terminate membrane up and over the curb or at top of curbs with 1" term bar and counter flashing
Wall Coping 733 LF Replace Remove and replace wall coping with new 24-gauge coated steel coping with taper
Electrical Lines T.B.D. LF D&R Detach and reset electrical lines as necessary. Must use licensed electrician.
Gas Lines 56 LF D&R Detach and reset gas lines as necessary. Must use licensed mechanical contractor.
Deicing T.B.D. LF D&R Carefully detach, save, and reinstall any existing heat trace cable.
Drains 10 EA Reflash Reflash existing 4-in roof drains with new membrane flashings (do not reduce drain size)
Overflow Drains 10 EA Reflash Reflash existing 4-in roof scuppers and extend membrane through the roof and over a min of 2"
Dome Strainers 20 EA Replace Replace existing do9me strainers with new coated cast iron dome strainers
Pipe Flashings 6 EA Replace Install new field fabricated membrane flashing at all roof penetrations
Vent Flashings 4 EA Replace Install new field fabricated membrane flashing at all roof penetrations
Pitch Pockets 4 EA Replace Replace pitch pockets with new PVC coated pitch pockets up to 6-in x 8-in
Storm Collars 4 EA Reuse Seal storm collars. Replace damaged storm collars as necessary.
Gas Caps 4 EA Replace Replace damaged 8-in type B gas vents
Pipe Stands 10 EA Reuse Install new pipe stands as needed
Walk Pads 200 LF Reuse Install new 30-in square PVC or rubber walk pads around RTU's (minimum 0.125-in thick)
Satellite Dish 1 EA D&R Detach and reset ballasted satellite dish
AC Condenser Units 1 EA D&R Detach and reset A/C condensers. Use licensed mechanical contractor to recharge if disconnected
Ballast Pavers 4 EA D&R Detach and reset 24 to 36-in concrete pavers under A/C condenser units
2. Recover (PVC membrane) Prepare 157.1 SQ Remove Clean and prepare the existing TPO roof membrane
Cover Board 157.1 SQ Install Install new 1/2-inch Fiberglass reinforced gypsum cover board
Insulation 157.1 SQ Install Inspect and replace damaged insulation board as necessary
Taper / Crickets 33.8 SQ Replace Install new 1/4” slope crickets at the upslope of all curbs as needed.
Membrane 212.9 SQ Total Install new single ply 60 or 90 mil EPDM membrane
Field 157.1 SQ Reuse Install single ply FIT EPDM membrane with pre-taped seams in the field
Parapet Walls 23.4 SQ Install adhered EPDM membrane at the parapet walls to extend up and over by 2" min.
Walls 27.6 SQ Install adhered EPDM membrane at the parapet walls to extend up and over by 2" min.
Curbs 4.8 SQ Install adhered EPDM membrane to the top of all curbs and up and over where possible.
Curb Flashings
Termination 173.7 LF Install Terminate membrane up and over the curb or at top of curbs with 1" term bar and counter flashing
Wall Coping 733 LF Replace Remove and replace wall coping with new 24-gauge coated steel coping with taper
Electrical Lines T.B.D. LF D&R Detach and reset electrical lines as necessary. Must use licensed electrician.
Gas Lines 56 LF D&R Detach and reset gas lines as necessary. Must use licensed mechanical contractor.
Deicing T.B.D. LF D&R Carefully detach, save, and reinstall any existing heat trace cable.
Drains 10 EA Reflash Reflash existing 4-in roof drains with new membrane flashings (do not reduce drain size)
Overflow Drains 10 EA Reflash Reflash existing 4-in roof scuppers and extend membrane through the roof and over a min of 2"
Dome Strainers 20 EA Replace Replace existing do9me strainers with new coated cast iron dome strainers
Pipe Flashings 6 EA Replace Install new field fabricated membrane flashing at all roof penetrations
Vent Flashings 4 EA Replace Install new field fabricated membrane flashing at all roof penetrations
Pitch Pockets 4 EA Replace Replace pitch pockets with new PVC coated pitch pockets up to 6-in x 8-in
Storm Collars 4 EA Reuse Seal storm collars. Replace damaged storm collars as necessary.
Gas Caps 4 EA Replace Replace damaged 8-in type B gas vents
Pipe Stands 10 EA Reuse Install new pipe stands as needed
Walk Pads 200 LF Reuse Install new 30-in square PVC or rubber walk pads around RTU's (minimum 0.125-in thick)
Satellite Dish 1 EA D&R Detach and reset ballasted satellite dish
AC Condenser Units 1 EA D&R Detach and reset A/C condensers. Use licensed mechanical contractor to recharge if disconnected
Ballast Pavers 4 EA D&R Detach and reset 24 to 36-in concrete pavers under A/C condenser units
Item Qty Unit Action
PROPOSED SCOPE OF WORK
Notes
Pueblo West Library 03/21/25
Job Considerations Construction Yard 1 Lot Install Setup a construction yard to procure materials
Dumpster 1 EA Install Place dumpster onsite for excess debris collection and removal
Safety
Guard Rails 1 Lot Install Set-up safety guard rails at parapet walls in areas being worked on as required by OSHA standards
Cones 1 Lot Install Setup cones and/or bollards as necessary to block and/or direct pedestrian traffic
Caution Tape 1 Lot Install Install caution tape as necessary to block of areas being worked on
Debris Chute 1 Lot Install Setup debris chute to collect and transfer roofing materials an debris
Crane / Telehandler 8 HRS Install Crane or telehandler forklift to load and offload materials and equipment onto roof
Toilet 1 EA Install Place portable toilet during roof installation
ADDITIONAL NOTES
1. Follow the job specifications or manufacturers installation instructions requirements for all installation details. Use whichever is the most stringent.
2. An approved safety plan meeting OSHA standards is required to be in place prior to construction and adhered to during installation.
3. Roof access for installation must be from the exterior with proper safety measures in place
4. Construction loads must stay within the allowable loads as determined by the structural certification.
5. Warranty requirements: ensure all roof materials and appurtenances are installed to meet the required warranty.
Roof Details
Description Width Height Length Wall Over Total Notes
# In In Ft Area (sf) Area (sf) Area (sf)
1 Parapet Walls 13.5 20.75 721.7 1247.9 932.2 2180.1 Varies from 14.5" to 27" high
2 34 54.6 154.7 9.1 163.8
3 -54.6 0.0
4 0.0 0.0 0.0
5 0.0 0.0 0.0
6 0.0 0.0 0.0
7 0.0 0.0 0.0
8 0.0 0.0 0.0
9 0.0 0.0 0.0
10 0.0 0.0 0.0
Avg. Avg. Total Parapet Add'l Total
Width Height Length Area Area Area
13.5 54.8 721.7 1402.6 941.3 2343.9
Area Over includes a 2-inch lap over the walls
Heights highlighted in yellow need to be verified.
Description Width Height Length Wall Over Total Notes
# In In Ft Area (sf) Area (sf) Area (sf)
1 Walls 0 0.5 661.9 27.6 27.6 Atrium walls
2 0.0 0.0
3 0.0 0.0
4 0.0 0.0
5 0.0 0.0
6 0.0 0.0
7 0.0 0.0
8 0.0 0.0
9 0.0 0.0
10 0.0 0.0
Avg. Avg. Total Wall Add'l Total
Width Height Length Area Area Area
0.0 0.5 661.9 27.6 0.0 27.6
WALL FLASHING
PARAPET WALL DETAILS
Curb Description Counter Taper Perim.. Raise
# Flash Crickets Length Width Height Length Area Curb
CURBS SF IN IN IN LF SF IN
1 RTU 74.7 239 358.0 90.0 12.0 74.67 74.67
2 RTU 74.7 239 358.0 90.0 12.0 74.67 74.67
3 Ventilator 20.0 20.0 12.0 6.67 6.67
4 Roof Hatch 30.0 36.0 12.0 11.00 11.00
5 Ventilator 20.0 20.0 12.0 6.67 6.67
6 A/C Condensorr on 2 ea 2' x 2' pavers 0.00 0.00
7 Ballasted Sattelite Dish 0.00 0.00
8 A/C Condensor on 2 ea 3' x 3' pavers 0.00 0.00
0.00 0.00
TOTALS 149.3 477.3 65.50 21.33 5.00 173.67 173.67
(LF) (SF) (LF) (LF) (LF) (LF) (SF)
Dimensions
CURB DETAILS