Appendix A - RCM and Vib Sev Chart.pdf
PDF 412 KB Posted
- Attached to
- Fuel Flow Transmitter Test Stand Federal contract opportunity
- Solicitation number
- FA812625Q0059
About this file
This document is a Statement of Work (SOW) Appendix A for Reliability Centered Maintenance (RCM), dated 25 April 2024, detailing comprehensive technical requirements for equipment maintenance and installation. The document outlines extensive specifications for rotating equipment, including vibration monitoring, data gathering points, bearing information, and alignment procedures. Key requirements include providing detailed technical documentation, performing various diagnostic tests (such as motor circuit analysis, insulation resistance testing, and surge testing), and adhering to strict installation and maintenance standards.
The SOW emphasizes design for reliability, with a focus on equipment longevity and precision installation. Contractors must level and align equipment according to original equipment manufacturer specifications, conduct thorough equipment health assessments, and ensure maintainability through design features like inspection ports and accessibility. The government will perform multiple verification surveys during installation, including thermography, airborne ultrasonics, and motor analysis, with the contractor responsible for correcting any identified discrepancies. The appendix includes detailed checklists and technical specifications for various equipment components, with a primary goal of minimizing maintenance and operational costs while ensuring equipment reliability over a ten-year lifecycle.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Solicitation Amendment FA812625Q00590003 SF 30.pdf | ||
| Solicitation Amendment FA812625Q00590002 SF 30.pdf | ||
| Combined Synopsis_Solicitation (CSS).pdf | ||
| Solicitation Amendment FA812625Q00590001 SF 30.pdf | ||
| Appendix C - Glossary and Definitions.pdf | ||
| Appendix F - Current Test Stand Technical Manuals.pdf | ||
| CDRL004 (CDR).pdf | ||
| Statement of Work (SOW).pdf | ||
| Appendix B - Safety Specifications.pdf | ||
| Appendix D - Environmental Language.pdf | ||
| Appendix E - Certification Test Plan.pdf | ||
| CDRL005 (Tech Data_ Drawings_ Manual).pdf | ||
| CDRL006 (Software).pdf | ||
| Solicitation - FA812625Q0059.pdf | ||
| Appendix H - UUT Test Specifications.pdf | ||
| CDRL002 (PDR).pdf | ||
| CDRL003 (IDR).pdf | ||
| Appendix G - Current Test Stand Drawings.pdf | ||
| Appendix I - 76 CMXG Design Guidelines.pdf | ||
| CDRL001 (Installation Plan).pdf | ||
| CDRL007 (Acceptance Tests).pdf |
Show all 21
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOW Appendix A: RCM 25 April 2024
Reliability Centered Maintenance (RCM) Reliability Centered Maintenance (RCM) is the process that is used to determine the most effective approach to equipment maintenance. RCM involves identifying actions that, when taken, will reduce the probability of equipment failure and which are the most cost effective. RCM includes the entire life cycle of the equipment starting with equipment design, manufacturing/construction and installation. RCM seeks the optimal mix of Condition-Based Actions, other Time or Cycle-Based actions, or a Run-to-Failure approach. The ultimate goal of RCM is to minimize maintenance and operational costs. This appendix is a condensed version of RCM related topics with a focus on predictive maintenance, acceptance testing utilizing predictive and/or proactive technologies, resulting in the creation of baseline data for each equipment asset and a more reliable piece of equipment.
1 RCM Baseline Data: Baseline data is condition monitoring information that is representative of equipment in proper operating condition and should be established as early as possible in the life of the equipment. The baseline readings and periodic monitoring data should be taken and recorded under the same conditions (or as close as can be achieved) and used for acceptance testing. The Equipment Engineering Flight organization, 76 MXSG/MXDEQ, will provide acceptance testing of equipment components using advanced technology listed in section 1. Final acceptance of the equipment will include a signature by the RCM Engineering Team Lead verifying equipment reliability.
1.1 Vibration Monitoring: The vibration specifications utilized for acceptance testing will be based on generic International Standards Organization (ISO) 3945, ISO I 0816, American National Standards Institute (ANSI), MIL-STD-167-1, MILSTD740-2 (Appendix C), and Lockheed Martin vibration specification LMMSS SPECIFICATION NO. V 1.0-1997. Equipment failing the vibration tests will be rejected by the Government.
1.1.1 Data Gathering Points: For all rotating equipment provided under the contract, the contractor shall provide, when possible, vibration monitoring points using the following guidelines: The contractor has the option of machining the equipment case in order to achieve a flat and smooth spot of 1" diameter with a surface finish of 32 micro-inches RMS or installing magnetic accelerometer pads either by welding or stud mount. The accelerometer pads must meet the size and finish requirements of the machined spot face.
1.1.1.2 The contractor shall ensure monitoring locations are positioned on structural members.
Installation of accelerometer pads on bolted cover plates or other non-rigid members is not acceptable.
1.1.1.3 Data gathering points are to be located in a horizontal, vertical, and axial orientation with respect to component bearing/shaft centerline.
1.1.1.4 Equipment containing Motors on blowers and/or fans shall have accelerometer pads installed in the radial (2 ea.) and axial (l ea.) directions. Fan bearings shall be monitored radially in the vertical direction.
1.1.2 Bearing Information
1.1.2.1 Drawings: The contractor shall provide to the procuring organization section drawings that show the component arrangement for all rotating equipment supplied under the contract. The section drawings shall accurately depict the bearing support structural arrangement, be drawn to scale, and show the dimensions to the centerline of all rotating shafts.
1.1.2.2 Manufacturer Data: The contractor shall provide to the procuring organization the bearing manufacturer and part number for all bearings used in all rotating equipment supplied under this contract. The information shall be included on the sectional drawings for each bearing location.
1.1.2.3 Operating Data: The contractor shall provide the procuring organization with the operating speed for constant speed units and the normal operating speed range for variable speed equipment. Additional information to be provided includes:
1.1.2.3.1 All vibration fault frequency information along with component locations.
1.1.2.3.2 All counts on number of blades, lobes, pistons, gears, impellers, stages.
1.1.2.3.3 Pulley sizes and belt information.
1.1.2.3.4 Coupling type and clearances.
1.1.2.3.5 Acceptable criteria for alignment results after laser alignment.
1.1.2.3.6 Thermal growth specification for alignment purposes.
1.1.2.4 Lubrication Data: The contractor/manufacture shall provide to the procuring organization the following information on all liquid lubricants contained within equipment/system or in bulk (5 gallons or more) supplied under this contractor/manufacturer:
1.1.2.4.1 Liquid Lubricants
1.1.2.4.1.1 Viscosity grade in ISO units
1.1.2.4.1.2 Viscosity Index
1.1.2.4.1.3 AGMA and/or SAE classification as applicable
1.1.2.4.1.4 Mil Spec and/or NATO Code as applicable
1.1.2.4.1.5 Cincinnati Milacron Specification Number as applicable
1.1.2.4.1.6 Viscosity in Centistokes (cst) @ 40° C and 100° C
1.1.2.4.1.7 Type Additive package. Example: ZDDP, Rust inhibitors, Foam inhibitors.
1.1.2.4.1.8 Neutralization, the TBN (alkalinity) and/or TAN (acidity).
1.1.2.4.1.9 Flash point
1.1.2.4.1.10 Pour point
1.1.2.4.2 Grease Lubricants
1.1.2.4.2.1 National Lubrication and Grease Institute (NLGI) Number
1.1.2.4.2.2 Type and percent of thickener
1.1.2.4.2.3 Dropping point
1.1.2.4.2.4 Maximum Service Temperature
1.1.2.4.2.5 Base oil viscosity range in Saybolt Universal Seconds or centipoise
1.1.3 Fans, Blowers: For all fans supplied under the contract, the contractor shall ensure sufficient access to the fan is present in order to allow for cleaning and in-place balancing of the fan.
The contractor shall provide to the procuring organization the following information on all fans/blowers supplied under the contract:
1.1.3.1 Type of fan or blower
1.1.3.2 Number of rotating fan blades/vanes
1.1.3.3 Number of stationary fan blades/vanes
1.1.3.4 Rotating speed(s)
1.1.3.5 Additional required information if the fans/air handlers are belt driven:
1.1.3.5.1 Number of belts
1.1.3.5.2 Belt lengths
1.1.3.5.3 Belt Part Number
1.1.3.5.4 Diameter of the drive sheave at the drive pitch line
1.1.3.5.5 Diameter of the driven sheave at the drive pitch line
1.2 Rotating Machinery Alignment
1.2.1 Laser Alignment: All directly shaft-driven flexibly coupled rotating machine alignment shall be performed using only laser shaft alignment systems.
1.2.2 Base: Machine bases shall be clean, level, planar, and rigid.
1.2.3 Distortion: 'Soft foot' (machine frame distortion) shall be eliminated prior to final alignment.
1.2.4 Target specifications: Target specifications for expected machine movement during operation shall be considered (if available) when performing final alignment of the machines.
If target specifications are not available, all due diligence shall be exerted to obtain this information via the methods detailed below. These methods shall prevail in the following order of priority of acceptance:
1.2.4.1 Data derived from a study of positional change.
1.2.4.2 Machine vendors' or manufacturers' recommendations.
1.2.4.3 Calculation performed via the TLC method (detailed in Table 1-1.)
Table 1-1: Thermal Growth Calculation
Formula ΔT x L x C = thermal growth, at any measured point along the shaft centerlines, in mils
Variables ΔT = change in temperature (°F).
L = distance of material involved (inches).
C = coefficient of linear expansion (mils/(in °F)).
Table 1-2: Common Coefficients (C)
Material Coefficient of Linear Expansion (mils/(in °F))
Aluminum 0.0126 Bronze 0.0100
Cast iron, Gray 0.0059 Stainless steel 0.0074
Mild steel, ductile iron 0.0063
1.2.4.4 A "hot alignment check".
1.2.4.5 Final shaft alignment shall be performed to the relevant alignment tolerances specified in the "Alignment Tolerances" charts in Table 1-3. Tolerances in the "excellent" column are design goals when new and tolerances in the "acceptable" column are indicative of equipment that has been in use for a specific time period usually one year or less.
1.2.4.6 All dimensions shall be measured and be accurate to the nearest 1/8th inch (0.125"). A complete alignment report shall be generated from the device and printed out on a connected printer or stored on a PC for archival and documentation purposes.
1.2.4.7 Spacer coupling tolerances are to be applied anytime the distance between flex planes in a coupling or a across a spacer shaft or spool piece is equal to or greater than 4 inches.
Figure 1-1: Spacer Coupling Angularity
1.2.4.8 Input the calculated thermal growth values at the machine support locations into the laser alignment system utilizing the Thermal Growth function.
1.2.4.9 A vibration analysis survey shall be performed during the start-up phase of the installation. All defects noted by the government shall be corrected by the contractor at no additional expense to the procuring organization. The government will re-survey repaired areas to assure proper corrective action has been taken.
Table 1-3: Shaft Alignment Tolerances
Short Coupling Spacer Coupling
Offset (mils) Angularity (mils/inch) Anguilarity (α and ß)
(mils/inch)
RPM Excellent Acceptable Excellent Acceptable Excellent Acceptable 600 5.0 9.0 1.0 1.5 1.8 3.0 900 3.0 6.0 0.7 1.0 1.2 2.0
1,200 2.5 4.0 0.5 0.8 0.9 1.5 1,800 2.0 3.0 0.3 0.5 0.6 1.0 3,600 1.0 1.5 0.2 0.3 0.3 0.5 7,200 0.5 1.0 0.1 0.2 0.15 0.25
1.3 Thermography
1.3.1 Electrical- The government will perform a thermographic survey on all electrical distribution equipment, motor control centers, and transformers during the start-up phase of the installation.
1.3.2 Motors and Bearings- Large machines shall be scanned closely. Abnormal hot spots on the body may indicate flaws in the stator windings. The surface temperature of a motor is normally lower than the winding temperature. Bearing temperatures are normally higher than the housing temperature.
1.3.2.1 Any defects noted by an observable difference in temperature of surveyed components or unexplained temperature rise above ambient shall be corrected by the contractor at no additional expense to the procuring organization. The government will re-survey repaired areas to assure proper corrective action has been taken.
1.3.2.2 There are two basic criteria for evaluating temperature conditions; differential temperature (ΔT) and absolute temperature. Each is described below.
1.3.2.2.1 Differential Temperature (ΔT): Temperature difference criteria are simple, easy to apply in the field, and provide an adequate qualitative screening system to identify thermal exceptions and problems. The ΔT criteria compares component temperature to the ambient temperature and may be used for electrical equipment. ΔT may also be used for mechanical components. 1.3.2.2.2 Absolute Temperature: Absolute temperature criteria are generally specific to an equipment model, type of equipment, class of insulation, service use, or any of many other salient characteristics. As a result, absolute temperatures are more suited to quantitative infrared thermography and critical temperature applications. The mechanical temperature specifications come primarily from manufacturer's manuals.
Electrical temperature specifications are set by three principal electrical standards organizations:
1.3.2.2.2.1 National Electrical Manufacturers Association, (NEMA).
1.3.2.2.2.2 International Electrical and Electronic Engineers, (IEEE).
1.3.2.2.2.3 American National Standards Institute, (ANSI).
1.4 Airborne Ultrasonics: The government shall perform an airborne ultrasonic survey during the start-up phase of the installation. The government shall survey electrical equipment for indications of arcing or electrical discharge, including corona. Piping systems shall be surveyed for indications of leakage. Baseline all electric motors for db levels using contact probe. All defects or exceptions noted by the use of airborne ultrasonics shall be corrected by the contractor at no additional expense to the procuring organization. The government will re-survey repaired areas to assure proper corrective action has been taken.
1.5 Motor Analysis: The government may perform a motor analysis survey during the start-up phase of the installation in order to verify the information to be provided by the contractor (or contractor's representative) as listed in 1.5.1 through 1.5.5 below. All defects or exceptions noted by the government shall be corrected by the contractor at no additional expense to the procuring organization. The government will re-survey repaired areas to assure proper corrective action has been taken.
1.5.1 Motor Circuit Analysis (Complex Phase Impedance): Upon motor installation, the contractor shall take and provide to the procuring organization the following acceptance/baseline readings and measurements, first for the motor alone, and then, for motor and circuit together:
1.5.1.1 Conductor path resistance
1.5.1.2 Inductive imbalance
1.5.1.3 Capacitance to ground
1.5.2 Motor Current Spectrum Analysis: With the motor installed and operational, the contractor shall conduct an acceptance/baseline spectral analysis on the loaded motor at 75% or greater load, when specified by the procuring organization.
1.5.3 Insulation Resistance: Upon installation, the contractor shall take and provide to the procuring organization the following acceptance/baseline readings and measurements;
initially, for the circuit or for the motor alone, and then, for the motor and circuit together:
1.5.3.1 Dielectric Absorption Ratio (for all motors)
1.5.3.2 Leakage current at test voltage
1.5.4 Surge Testing: The contractor shall perform surge testing and high potential (high-pot) resistance testing of the motor(s) prior to their installation and procuring organization's acceptance. The contractor shall provide to the procuring organization documentation of test results, including test voltage, waveforms, and high potential leakage current.
1.5.5 Start-up Tests: With the motor installed and operational, the contractor shall collect and provide to the procuring organization the following baseline data:
1.5.5.1 Coast-down time
1.5.5.2 Peak starting current
2 Maintainability and Ease of Monitoring: The contractor shall provide for equipment maintainability and ease of monitoring through design. For example, rotating equipment such as fans shall be equipped with an inspection/ clean out port. Accessibility to these ports shall facilitate inspection and cleaning of the fan blades.
3 Design for Reliability: Capital equipment purchased by the Air Force Material Command is depreciated on a ten year cycle; therefore, all equipment delivered shall be designed to last a minimum of ten years with a focus on designing for reliability. Example, all motors utilized on the equipment shall be equipped with aluminum cooling fans (design minimum), no plastic fans allowed.
4 Leveling of Equipment Upon Installation: The contractor shall level all installed rotating electrical and mechanical machinery in accordance with original equipment manufacturers (OEM) specifications and this SOW. The government will check the level of the machinery to verify accuracy. Any discrepancies detected by the government will be corrected by the contractor. The government will re-survey the installed equipment to assure proper corrective action has been taken.
5 Equipment Health Assessment Checklist: The Equipment Engineering Flight organization, 76 MXSS/MXDEA, will utilize the Equipment Health Assessment Checklist shown on page 8, along with the requirements detailed in sections 1 through 4, in order to verify the equipment health and precision installation of the installed equipment as part of the equipment acceptance criteria and to establish the equipment health baseline data of the equipment.
5.1 Discrepancies: Contractor shall fix/ repair any discrepancies found. The Government will then re-run that portion of the checklist until all discrepancies are corrected and the equipment is acceptable to the Government. The RCM Engineering Team Lead will then sign the filled out Equipment Health Assessment Checklist showing no remaining issues to verify the equipment is acceptable.
5.2 Warranty: Once the equipment has been accepted by the Government, and the warranty period begins. The Government will continue to utilize the Equipment Health Assessment Checklist, shown on page 8, on a periodic basis to detect equipment anomalies or issues that may require warranty attention. The Equipment Engineering Flight organization, 76 MXSS/MXDEA, will then contact the owning equipment's engineering office of responsibility who, in turn, will then contact the Contract Officer (CO) for warranty support when a problem is detected.
Figure 5-1: Vibration Severity Chart (ISO 10816-3)
Table 5-1: Equipment Health Assessment Checklist
Equipment Description: Date:
Equipment Location: Equipment Number (If Available):
Auditor Name(s)/Org:
Equipment Health Assessment Yes No N/A Pass Fail Infrared / Motor analysis:
Infrared scan electric panels, motors, and extreme temperature components?
Motor Analysis Baseline done & acceptable?
Motor(s) rotation marked and in correct direction?
Stroboscope:
Belts, couplings, and/or chains observed & acceptable?
Other rotating/moving components observed & acceptable?
Vibration:
Overall vibration levels checked & acceptable?
Accelerometer(s) pads installed?
Alignment:
Belts, shafts, pulleys, and couplings checked?
Machine level?
Ultrasound:
Piping scanned for leaks?
Equipment scanned for abnormal noise?
Oil/Grease/Fluids:
Are all lubricants checked and verified for correct type?
Are all grease and lube fittings labeled for correct type?
Are all fluid reservoirs labeled for fluid type and amount?
Safety:
Does equipment have safety guards over belts/chains/rotating equipment?
Are pinch points marked and/or guarded?
Does Equipment have functioning e-stop device?
Are stored energy sources isolated in the event of equipment failure?
Are isolation valves for steam, air, water, etc. included and labeled?
Is the load center panel easily accessible and marked with equipment information?
Installation:
Is equipment installed as per manufacturer’s recommendations?
Check for ease of maintainability (piping unions included, clearance for panel/cabinet doors opening, motor access, shut off valves for utilities, access platforms,…etc.)?
If equipment is designed for a fixed location, is it securely anchored?
Operational Check:
Operational check performed?
Does equipment function as required?
Is an operator or engineer present for operational check and POC information provided?
Operator: Engineer: 76 MXSS RCM Team Lead:
Results/Comments:
| 1 RCM Baseline Data: |
| 1.1 Vibration Monitoring: |
| 1.1.1 Data Gathering Points: |
| 1.1.1.1 The contractor has the option of machining the equipment case in order to achieve a flat and smooth spot of 1" diameter with a surface finish of 32 micro-inches RMS or installing magnetic accelerometer pads either by welding or stud mount. The... |
| 1.1.1.2 The contractor shall ensure monitoring locations are positioned on structural members. Installation of accelerometer pads on bolted cover plates or other non-rigid members is not acceptable. |
| 1.1.1.3 Data gathering points are to be located in a horizontal, vertical, and axial orientation with respect to component bearing/shaft centerline. |
| 1.1.1.4 Equipment containing Motors on blowers and/or fans shall have accelerometer pads installed in the radial (2 ea.) and axial (l ea.) directions. Fan bearings shall be monitored radially in the vertical direction. |
| 1.1.2 Bearing Information |
| 1.1.2.1 Drawings: |
| 1.1.2.2 Manufacturer Data: |
| 1.1.2.3 Operating Data: |
| 1.1.2.3.1 All vibration fault frequency information along with component locations. |
| 1.1.2.3.2 All counts on number of blades, lobes, pistons, gears, impellers, stages. |
| 1.1.2.3.3 Pulley sizes and belt information. |
| 1.1.2.3.4 Coupling type and clearances. |
| 1.1.2.3.5 Acceptable criteria for alignment results after laser alignment. |
| 1.1.2.3.6 Thermal growth specification for alignment purposes. |
| 1.1.2.4 Lubrication Data: |
| 1.1.2.4.1 Liquid Lubricants |
| 1.1.2.4.1.1 Viscosity grade in ISO units |
| 1.1.2.4.1.2 Viscosity Index |
| 1.1.2.4.1.3 AGMA and/or SAE classification as applicable |
| 1.1.2.4.1.4 Mil Spec and/or NATO Code as applicable |
| 1.1.2.4.1.5 Cincinnati Milacron Specification Number as applicable |
| 1.1.2.4.1.6 Viscosity in Centistokes (cst) @ 40 C and 100 C |
| 1.1.2.4.1.7 Type Additive package. Example: ZDDP, Rust inhibitors, Foam inhibitors. |
| 1.1.2.4.1.8 Neutralization, the TBN (alkalinity) and/or TAN (acidity). |
| 1.1.2.4.1.9 Flash point |
| 1.1.2.4.1.10 Pour point |
| 1.1.2.4.2 Grease Lubricants |
| 1.1.2.4.2.1 National Lubrication and Grease Institute (NLGI) Number |
| 1.1.2.4.2.2 Type and percent of thickener |
| 1.1.2.4.2.3 Dropping point |
| 1.1.2.4.2.4 Maximum Service Temperature |
| 1.1.2.4.2.5 Base oil viscosity range in Saybolt Universal Seconds or centipoise |
| 1.1.3 Fans, Blowers: |
| 1.1.3.1 Type of fan or blower |
| 1.1.3.2 Number of rotating fan blades/vanes |
| 1.1.3.3 Number of stationary fan blades/vanes |
| 1.1.3.4 Rotating speed(s) |
| 1.1.3.5 Additional required information if the fans/air handlers are belt driven: |
| 1.1.3.5.1 Number of belts |
| 1.1.3.5.2 Belt lengths |
| 1.1.3.5.3 Belt Part Number |
| 1.1.3.5.4 Diameter of the drive sheave at the drive pitch line |
| 1.1.3.5.5 Diameter of the driven sheave at the drive pitch line |
| 1.2 Rotating Machinery Alignment |
| 1.2.1 Laser Alignment: |
| 1.2.2 Base: |
| 1.2.3 Distortion: |
| 1.2.4 Target specifications: |
| 1.2.4.1 Data derived from a study of positional change. |
| 1.2.4.2 Machine vendors' or manufacturers' recommendations. |
| 1.2.4.3 Calculation performed via the TLC method (detailed in Table 1-1.) |
| 1.2.4.4 A "hot alignment check". |
| 1.2.4.5 Final shaft alignment shall be performed to the relevant alignment tolerances specified in the "Alignment Tolerances" charts in Table 1-3. Tolerances in the "excellent" column are design goals when new and tolerances in the "acceptable" column... |
| 1.2.4.6 All dimensions shall be measured and be accurate to the nearest 1/8th inch (0.125"). A complete alignment report shall be generated from the device and printed out on a connected printer or stored on a PC for archival and documentation purposes. |
| 1.2.4.7 Spacer coupling tolerances are to be applied anytime the distance between flex planes in a coupling or a across a spacer shaft or spool piece is equal to or greater than 4 inches. |
| 1.2.4.8 Input the calculated thermal growth values at the machine support locations into the laser alignment system utilizing the Thermal Growth function. |
| 1.2.4.9 A vibration analysis survey shall be performed during the start-up phase of the installation. All defects noted by the government shall be corrected by the contractor at no additional expense to the procuring organization. The government will ... |
| 1.3 Thermography |
| 1.3.1 Electrical- |
| 1.3.2 Motors and Bearings- |
| 1.3.2.1 Any defects noted by an observable difference in temperature of surveyed components or unexplained temperature rise above ambient shall be corrected by the contractor at no additional expense to the procuring organization. The government will ... |
| 1.3.2.2 There are two basic criteria for evaluating temperature conditions; differential temperature (ΔT) and absolute temperature. Each is described below. |
| 1.3.2.2.1 Differential Temperature (ΔT): Temperature difference criteria are simple, easy to apply in the field, and provide an adequate qualitative screening system to identify thermal exceptions and problems. The ΔT criteria compares component tempe... |
| 1.3.2.2.2 Absolute Temperature: Absolute temperature criteria are generally specific to an equipment model, type of equipment, class of insulation, service use, or any of many other salient characteristics. As a result, absolute temperatures are more ... |
| 1.3.2.2.2.1 National Electrical Manufacturers Association, (NEMA). |
| 1.3.2.2.2.2 International Electrical and Electronic Engineers, (IEEE). |
| 1.3.2.2.2.3 American National Standards Institute, (ANSI). |
| 1.4 Airborne Ultrasonics: |
| 1.5 Motor Analysis: |
| 1.5.1 Motor Circuit Analysis (Complex Phase Impedance): |
| 1.5.1.1 Conductor path resistance |
| 1.5.1.2 Inductive imbalance |
| 1.5.1.3 Capacitance to ground |
| 1.5.2 Motor Current Spectrum Analysis: |
| 1.5.3 Insulation Resistance: |
| 1.5.3.1 Dielectric Absorption Ratio (for all motors) |
| 1.5.3.2 Leakage current at test voltage |
| 1.5.4 Surge Testing: |
| 1.5.5 Start-up Tests: |
| 1.5.5.1 Coast-down time |
| 1.5.5.2 Peak starting current |
| 2 Maintainability and Ease of Monitoring: |
| 3 Design for Reliability: |
| 4 Leveling of Equipment Upon Installation: |
| 5 Equipment Health Assessment Checklist: |
| 5.1 Discrepancies: |
| 5.2 Warranty: |
File details come from the government source that posted it. Updated .