Appendix 20_Repairing and Disenfecting waterlines 508c.pdf

PDF 107 KB Posted

Attached to
Prospectus for Campground and Related Granger-Thye Concessions Monongahela National Forest
Solicitation number
071825
Issued by

About this file

This document is an appendix detailing procedures for repairing and disinfecting water lines in campground facilities, specifically for the United States Department of Agriculture (USDA) Granger-Thye Concessions program. The document provides comprehensive, step-by-step instructions for managing water line breaks, including two primary processes: repairing leaks and disinfecting water lines. Key repair procedures include isolating the break, ensuring proper excavation safety (adhering to OSHA guidelines), selecting appropriate repair components, carefully refilling the line, and backfilling with sand or gravel. Disinfection procedures involve flushing the line, adding chlorine at specific concentrations (50-200 mg/L), maintaining appropriate contact times, and collecting BAC-T samples to confirm water safety before returning the line to service.

View the file

Other files

File Type Posted
Site Visit Questions and Answers.pdf PDF
UPDATED VERSION 2 - SZFinalMONONGAHELA_ProspectusV2.pdf PDF
Appendix 18_FS-6500-25 Request for Verification 508c.pdf PDF
Appendix 2- Map of Developed Sites_SZ.pdf PDF
Appendix 14 FS-2700-4h App H GT Fee Offset Certification.pdf PDF
Appendix 3_Inventory of Gov Furnished Property_SZ_Draft.pdf PDF
SZFinalMONONGAHELA_Prospectus.pdf PDF
Appendix 7 Sample Performance Eval 508c.pdf PDF
Appendix 19_National Quality Standards 508c.pdf PDF
Appendix 4- Applicable Forest Orders.pdf PDF
Appendix 8_Law Enforcement 508c.pdf PDF
Appendix 15 SampleCollectionAgreementGTFeeOffsetWork.pdf PDF
Appendix 10 FS-2700-4h and App G .pdf PDF
Appendix 11_FS-2700-4h App B_GT offset agreement_092020.pdf PDF
Appendix 13_Indirect_cost_reimburse_letter_508c.pdf PDF
Appendix 1 - Vicinity Map_SZ.pdf PDF
Appendix 16_ Sample Business Plan 508c.pdf PDF
Appendix 17_FS_6500_24 Financial Statement 508c.pdf PDF
Appendix 9 SampleMinimumContentofProposedAnnualOperatingPlan.pdf PDF
Appendix 5_Sample Use Report 508c.pdf PDF
Appendix 21_Graffiti Removal Protocols 508c.pdf PDF
Appendix 12_Potential Gov MRRI Projects 508c.pdf PDF
Appendix 6_ Sample Comment Card 508c (1).pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

United States Department of Agriculture Appendix 20: Repairing and Disinfecting Waterlines

Prospectus for Campground and Related Granger-Thye Concessions

Repairing and Disinfecting Water Lines

In the event a water line breaks, the following procedures must be followed for repairing and disinfecting the line:

Proper procedure for repairing leaks:

1. Isolate the break by shutting all valves necessary to stop the flow of water

2. If the excavation is going to be over 5 feet deep, make sure that the proper shoring equipment is available or that the trench is adequately sloped according to OSHA guidelines. The area around the leak should be large enough to work comfortably, usually one foot on either side of the pipe. A sump hole is dug at one end of the trench to allow the water to flow away from the leak and be pumped or dipped out.

3. The type of repair clamp or coupling is selected once the line has been uncovered. The replacement part should be of equal or superior quality.

4. Refill the line by carefully cracking the shut off valve and opening any nearby hydrant to vent out air as it fills. Do not fill the line quickly or water hammer could occur when the water finally fills the pipe.

5. Backfilling the excavation should be done by hand at first preferably with sand or gravel.

This should be tamped carefully to avoid damaging the clamps and couplings. Prior to putting the line back in service, it should be disinfected and have BAC-T samples taken.

Proper procedure for disinfecting a water line after fixing a water leak:

1. Flush the line.

2. Disinfect the line. Enough chlorine should be added to create a dosage of 50mg/L with a residual of 5mg/L after 24 hours. In some instances a higher chlorine dosage can be used and the contact time can then be reduced. If the dosage is 200 mg/L the contact time is only 2 hours.

3. After the appropriate contact time has been achieved, flush the line again.

4. After the line is flushed and the free chlorine residual is below 2.0mg/l, collect a BAC-T sample from the line. If negative results come back, the line is ready to be put into service.

Repairing and Disinfecting Water Lines
Proper procedure for repairing leaks:
Proper procedure for disinfecting a water line after fixing a water leak: