AHU 1 AIR APPARATUS
| AIR APPARATUS TEST REPORT | |||||||||||||
| BASE | W/O# | ||||||||||||
| SYSTEM | AHU 1 | BUILDING | DATE | NAME | |||||||||
| TYPE EQUIPMENT | AHU | SUPPLY FAN | EXHAUST | RETURN | |||||||||
| TYPE OF SYSTEM | CV | VAV | MULITZONE | DUAL DUCT | REHEAT | ||||||||
| FAN DATA | MOTOR DATA | ||||||||||||
| MANUFACTURER | Trane | MANUFACTURER | Baldor | ||||||||||
| MODEL NUMBER | MCCA025GAM0ABC | MODEL NUMBER | EM2513T-G | ||||||||||
| WHEEL TYPE | AIR FOIL | FORWARD CURVE | NAME PLATE HORSE POWER | 15 | NAME PLATE RPMS | 1765 | |||||||
| BACKWARDS INCLINE | OTHER | EFFICIENCY | 93 | POWER FACTOR | 86 | ||||||||
| BELT SIZE | B-77 2ea | SHAFT SIZE | 2 3/16 | SHAFT SIZE | 1 5/8 | AS FOUND | FINAL | ||||||
| PULLEY FAN OD | 11 1/2 | MOTOR OD | 6 3/8 | RPM | |||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | 26 | BHP | |||||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | |||||||||||||
| DESIGN | AS FOUND | FINAL | DESIGN | ACTUAL | FINAL | ||||||||
| FAN CFM | VOLTAGE A-B | 460 | |||||||||||
| FAN RPM | VOLTAGE B-C | ||||||||||||
| DISCHARGE S.P. | VOLTAGE C-A | ||||||||||||
| EXTERNAL S.P. | AMPERAGE A | 17.7 | |||||||||||
| REMARKS | AMPERAGE B | ||||||||||||
| Beltts loose and shives worn (needs replaced) | AMPERAGE C | ||||||||||||
| Total Static 3.77 | AIR VOLUMES | ||||||||||||
| Connected load 26,235 full cooling | DESIGN | AS FOUND | FINAL | ||||||||||
| Minimum air flow required 10,480 min cool and heat | MAX | MIN | MAX | MIN | MAX | MIN | |||||||
| Oa design 40% of 16,800 = 6,720 | O/A CFM | ||||||||||||
| R/A | S/A | AFTER CC/A | R/A CFM | ||||||||||
| O/A TEMP | R/A TEMP | M/A TEMP | |||||||||||
| STATIC PRESSURE DROPS | |||||||||||||
| COIL NAME AND DESIGN S.P. DROP | AS FOUND | FINAL | AS FOUND | FINAL | AS FOUND | FINAL | |||||||
| Cooling coil | |||||||||||||
| Heating coil |
Page &P of &N x x X
AHU 1 2nd floor Supply Air
| PITOT TUBE TRAVERSE LARGE ROUND DUCT | ||||||||||||||||||
| BASE: | JOB NO.: | DATE: | ||||||||||||||||
| LOCATION: | SYSTEM: | |||||||||||||||||
| LOCATION OF DUCT: | AREA SERVED: | DUCT TEMP.: | DUCT S.P.: | |||||||||||||||
| DUCT SIZE: | 18" | REQUIRED CFM: | REQUIRED FPM: | PERCENT OF DESIGN = ACTUAL CFM/REQUIRED CFM | ||||||||||||||
| DUCT AREA IN SQ.FT.: | ACTUAL CFM: | ACTUAL FPM: | ||||||||||||||||
| TRAVERSE POINTS | READINGS | |||||||||||||||||
| 2nd Floor VAVS in Max | 2nd Floor VAVS in Min | |||||||||||||||||
| FPM | FPM | FPM | FPM | |||||||||||||||
| 1 | 1956 | |||||||||||||||||
| 2 | 2024 | |||||||||||||||||
| 3 | 1771 | |||||||||||||||||
| 4 | 1789 | |||||||||||||||||
| 5 | 2092 | |||||||||||||||||
| 6 | 2751 | |||||||||||||||||
| 7 | 2839 | |||||||||||||||||
| 8 | 2981 | |||||||||||||||||
| 9 | 3008 | |||||||||||||||||
| 10 | 3020 | |||||||||||||||||
| 1 | 2918 | |||||||||||||||||
| 2 | 2856 | |||||||||||||||||
| DUCT DIA | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | ||||||||
| 3 | 2709 | |||||||||||||||||
| 12 | 3/8 | 1 | 1 3/4 | 2 3/4 | 4 1/8 | 7 7/8 | 9 1/4 | 10 1/4 | 11 | 11 5/8 | ||||||||
| 13 | 3/8 | 1 | 1 7/8 | 2 7/8 | 4 1/2 | 8 1/2 | 10 1/8 | 11 1/8 | 12 | 12 5/8 | 4 | 2557 | ||||||
| 14 | 3/8 | 1 1/8 | 2 | 3 1/8 | 4 3/4 | 9 1/4 | 10 7/8 | 12 | 12 7/8 | 13 5/8 | ||||||||
| 15 | 3/8 | 1 1/4 | 2 1/4 | 3 3/8 | 5 1/8 | 9 7/8 | 11 5/8 | 12 3/4 | 13 3/4 | 14 5/8 | 5 | 2329 | ||||||
| 16 | 3/8 | 1 1/4 | 2 3/8 | 3 5/8 | 5 1/2 | 10 1/2 | 12 3/8 | 13 5/8 | 14 3/4 | 15 5/8 | ||||||||
| 17 | 1/2 | 1 3/8 | 2 1/2 | 3 7/8 | 5 3/4 | 11 1/4 | 13 1/8 | 14 1/2 | 15 5/8 | 16 1/2 | 6 | 2223 | ||||||
| 18 | 1/2 | 1 1/2 | 2 5/8 | 4 1/8 | 6 1/8 | 11 7/8 | 14 1/2 | 15 3/8 | 16 1/2 | 17 1/2 | ||||||||
| 19 | 1/2 | 1 1/2 | 2 3/4 | 4 1/4 | 6 1/2 | 12 1/2 | 15 3/4 | 16 1/4 | 17 1/2 | 18 1/2 | 7 | 2186 | ||||||
| 20 | 1/2 | 1 5/8 | 2 7/8 | 4 1/2 | 6 7/8 | 13 1/8 | 17 1/8 | 17 1/8 | 18 1/2 | 19 1/2 | ||||||||
| 22 | 5/8 | 1 3/4 | 3 1/4 | 5 | 7 1/2 | 14 1/2 | 17 | 18 3/4 | 20 1/2 | 21 3/8 | 8 | 2124 | ||||||
| 24 | 5/8 | 2 | 3 1/2 | 5 1/2 | 8 1/8 | 15 3/4 | 18 1/2 | 20 1/2 | 22 | 23 3/8 | ||||||||
| 26 | 5/8 | 2 1/8 | 3 3/4 | 5 7/8 | 8 7/8 | 17 1/8 | 20 1/8 | 22 1/4 | 23 3/8 | 25 3/8 | 9 | 2070 | ||||||
| 28 | 3/4 | 2 1/4 | 4 1/8 | 6 3/8 | 9 5/8 | 18 3/8 | 21 5/8 | 23 7/8 | 25 3/4 | 27 1/4 | ||||||||
| 30 | 3/4 | 2 1/2 | 4 3/8 | 6 3/4 | 10 1/4 | 19 3/4 | 23 1/4 | 25 5/8 | 27 1/2 | 19 1/4 | 10 | 1683 | ||||||
| 32 | 7/8 | 2 5/8 | 4 5/8 | 7 1/4 | 11 | 21 | 24 3/4 | 27 3/8 | 29 3/8 | 31 1/4 | ||||||||
| 34 | 7/8 | 2 3/4 | 5 | 7 3/4 | 11 5/8 | 22 3/8 | 26 1/4 | 29 | 31 1/4 | 33 1/8 | TOTAL FPM | 47886 | 0 | 0 | 0 | |||
| 36 | 1 | 3 | 5 1/4 | 8 1/8 | 12 3/8 | 23 5/8 | 27 7/8 | 30 3/4 | 33 | 35 | ||||||||
| 38 | 1 | 3 1/8 | 5 1/2 | 8 5/8 | 13 | 25 | 29 3/8 | 32 1/2 | 34 7/8 | 37 | Divided by 20 | 2394.3 | 0 | 0 | 0 | |||
| 40 | 1 | 3 1/4 | 5 7/8 | 9 | 13 5/8 | 26 3/8 | 31 | 34 1/8 | 36 3/4 | 39 | ||||||||
| 42 | 1 1/8 | 3 3/8 | 6 1/8 | 9 1/2 | 14 3/8 | 27 5/8 | 32 1/2 | 35 7/8 | 38 5/8 | 40 1/8 | Times Duct Area | 1.76 | 1.76 | 1.76 | 1.76 | |||
| 44 | 1 1/8 | 3 5/8 | 6 3/8 | 10 | 15 | 29 | 34 | 37 5/8 | 40 3/8 | 42 7/8 | ||||||||
| 46 | 1 1/4 | 3 3/4 | 6 3/4 | 10 3/8 | 15 3/4 | 30 1/4 | 35 5/8 | 39 1/4 | 40 1/4 | 44 3/4 | = Total CFM | 4213.97 | 0 | 0.00 | 0 | |||
| 48 | 1 1/4 | 4 | 7 | 10 7/8 | 16 3/8 | 31 5/8 | 37 1/8 | 41 | 44 | 46 3/4 | ||||||||
| VAVs 1-11 1-12 1-27 | 1206 | |||||||||||||||||
| 5419.968 | 0 |
Page &P of &N
TRAVERSE POINT LAYOUT
6 7 8 9 10 1 2 3 4 5
RET FAN 1 AIR APPARATUS
| AIR APPARATUS TEST REPORT | |||||||||||||
| BASE | W/O# | ||||||||||||
| SYSTEM | Ret Fan 1 | BUILDING | DATE | NAME | |||||||||
| TYPE EQUIPMENT | AHU | SUPPLY FAN | EXHAUST | RETURN | |||||||||
| TYPE OF SYSTEM | CV | VAV | MULITZONE | DUAL DUCT | REHEAT | ||||||||
| FAN DATA | MOTOR DATA | ||||||||||||
| MANUFACTURER | Trane | MANUFACTURER | GE | ||||||||||
| MODEL NUMBER | FNA 309 | MODEL NUMBER | 5KS184LAB208 | ||||||||||
| WHEEL TYPE | AIR FOIL | FORWARD CURVE | NAME PLATE HORSE POWER | 5 | NAME PLATE RPMS | 1755 | |||||||
| BACKWARDS INCLINE | OTHER | EFFICIENCY | 89.5 | POWER FACTOR | 78.5 | ||||||||
| BELT SIZE | A-78 | SHAFT SIZE | 1 3/16 | SHAFT SIZE | 1 1/8 | AS FOUND | FINAL | ||||||
| PULLEY FAN OD | 8 1/4 | MOTOR OD | 6 3/4 | RPM | |||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | 28 1/4 | BHP | |||||||||||
| DESIGN | AS FOUND | FINAL | DESIGN | ACTUAL | FINAL | ||||||||
| FAN CFM | VOLTAGE A-B | 460 | |||||||||||
| FAN RPM | VOLTAGE B-C | 460 | |||||||||||
| DISCHARGE S.P. | VOLTAGE C-A | 460 | |||||||||||
| EXTERNAL S.P. | AMPERAGE A | 6.7 | |||||||||||
| REMARKS | AMPERAGE B | 6.7 | |||||||||||
| AMPERAGE C | 6.7 | ||||||||||||
| AIR VOLUMES | |||||||||||||
| DESIGN | AS FOUND | FINAL | |||||||||||
| MAX | MIN | MAX | MIN | MAX | MIN | ||||||||
| O/A CFM | |||||||||||||
| R/A | S/A | AFTER CC/A | R/A CFM | ||||||||||
| O/A TEMP | R/A TEMP | M/A TEMP | |||||||||||
| STATIC PRESSURE DROPS | |||||||||||||
| COIL NAME AND DESIGN S.P. DROP | AS FOUND | FINAL | AS FOUND | FINAL | AS FOUND | FINAL |
Page &P of &N X x
AHU 1 RET & OA TRAVERSE
| BASE: | SYSTEM: | LOCATION: | |||||||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | |
| A | 625 | 664 | 647 | 810 | 897 | 856 | 753 | ||||||||||
| B | 758 | 761 | 698 | 803 | 859 | 864 | 868 | ||||||||||
| C | 744 | 723 | 722 | 703 | 825 | 874 | 864 | ||||||||||
| D | 699 | 722 | 678 | 705 | 708 | 856 | 892 | ||||||||||
| E | |||||||||||||||||
| F | |||||||||||||||||
| G | |||||||||||||||||
| H | Return air 1st Floor | Outside Air | |||||||||||||||
| I | Total FPM = | 21578 | Total FPM = | 0 | |||||||||||||
| J | Ft per Minute Average = | 770.6428571429 | Ft per Minute Average = | 0 | |||||||||||||
| K | Area K (17" X 33") /144 = | 4.25 | Area K (34" X 60") /144 = | 14.166 | |||||||||||||
| L | Cubic Ft. per Minute = | 3,275 | Cubic Ft. per Minute = | 0 | |||||||||||||
| M | |||||||||||||||||
| N | |||||||||||||||||
| O | 389 | 490 | 409 | 422 | 453 | 488 | |||||||||||
| P | 542 | 440 | 558 | 519 | 508 | 460 | |||||||||||
| Q | 479 | 568 | 559 | 566 | 501 | 503 | |||||||||||
| R | 555 | 430 | 546 | 563 | 537 | 529 | |||||||||||
| S | |||||||||||||||||
| T | |||||||||||||||||
| U | |||||||||||||||||
| V | |||||||||||||||||
| W | Return air 2nd Floor | Outside Air | |||||||||||||||
| X | Total FPM = | 12014 | Total FPM = | 0 | |||||||||||||
| Y | Ft per Minute Average = | 500.5833333333 | Ft per Minute Average = | 0 | |||||||||||||
| Z | Area K (23" X 31") /144 = | 4.81 | Area K (34" X 60") /144 = | 14.166 | |||||||||||||
| Cubic Ft. per Minute = | 2407.8058333333 | Cubic Ft. per Minute = | 0 | ||||||||||||||
| Ribs Ret | 159 | ||||||||||||||||
| 2566.8058333333 | |||||||||||||||||
| 5841 |
AHU1 VAV
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 1 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | CO-2 LEVELS | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 1-1 | 650 | 260 | 507 | 78.0% | 202 | 77.7% | 745 | 115% | 258 | 99.2% | 667 | 103% | 258 | 99.2% | |||||||
| 1120 | 1 | 250 | 100 | 225 | 90.0% | 75 | 75.0% | 355 | 142.0% | 92 | 92.0% | 260 | 104.0% | 92 | 92.0% | ||||||
| 1117 | 2 | 140 | 56 | 102 | 72.9% | 46 | 82.1% | 128 | 91.4% | 65 | 116.1% | 147 | 105.0% | 65 | 116.1% | ||||||
| CC sec | 3 | 120 | 48 | 88 | 73.3% | 35 | 72.9% | 142 | 118.3% | 45 | 93.8% | 125 | 104.2% | 45 | 93.8% | ||||||
| 1115 | 4 | 140 | 56 | 92 | 65.7% | 46 | 82.1% | 120 | 85.7% | 56 | 100.0% | 135 | 96.4% | 56 | 100.0% | ||||||
| VAV 1-2 | 310 | 125 | 300 | 96.8% | 128 | 102% | 0.0% | 0.0% | 300 | 96.8% | 128 | 102% | |||||||||
| 1115 | 1 | 310 | 125 | 300 | 96.8% | 128 | 102.4% | 0.0% | 0.0% | 300 | 96.8% | 128 | 102.4% | ||||||||
| VAV 1-3 | 760 | 305 | 722 | 95.0% | 293 | 96.1% | 0.0% | 0.0% | 0.0% | 0.0% | |||||||||||
| 1114 | 1 | 190 | 76 | 134 | 70.5% | 50 | 65.8% | 0.0% | 0.0% | 0.0% | 0.0% | ||||||||||
| 1114 | 2 | 285 | 114 | 298 | 104.6% | 120 | 105.3% | 0.0% | 0.0% | 0.0% | 0.0% | ||||||||||
| 1114 | 3 | 285 | 114 | 290 | 101.8% | 123 | 107.9% | 0.0% | 0.0% | 0.0% | 0.0% | ||||||||||
| VAV 1-4 | 100 | 40 | 100 | 100% | 0.0% | 0.0% | 43 | 108% | 100 | 100% | 43 | 108% | |||||||||
| 1112 | 1 | 100 | 40 | 100 | 100.0% | 30 | 75.0% | 0.0% | 43 | 107.5% | 100 | 100.0% | 43 | 107.5% | |||||||
| RM NOT TESTED. LOCKED BUT ZEROED | |||||||||||||||||||||
| VAV 1-5 | 670 | 268 | 887 | 132% | 300 | 112% | 535 | 79.9% | 0.0% | 658 | 98.2% | 283 | 106% | ||||||||
| 1 | 1 | 90 | 36 | 130 | 144.4% | 45 | 50.0% | 75 | 83.3% | 0.0% | 100 | 111.1% | 35 | 97.2% | |||||||
| 2 | 2 | 145 | 58 | 152 | 104.8% | 50 | 86.2% | 95 | 65.5% | 0.0% | 115 | 79.3% | 50 | 86.2% | |||||||
| 3 | 3 | 145 | 58 | 200 | 137.9% | 70 | 120.7% | 125 | 86.2% | 0.0% | 145 | 100.0% | 65 | 112.1% | |||||||
| 4 | 4 | 145 | 58 | 205 | 141.4% | 70 | 120.7% | 120 | 82.8% | 0.0% | 150 | 103.4% | 68 | 117.2% | |||||||
| 5 | 5 | 145 | 58 | 200 | 137.9% | 65 | 112.1% | 120 | 82.8% | 0.0% | 148 | 102.1% | 65 | 112.1% |
Page &P of &N
AHU1 VAV (2)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 1 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | CO-2 LEVELS | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 1-6 | 220 | 90 | 152 | 69.1% | 60 | 66.7% | 257 | 117% | 87 | 96.7% | 242 | 110% | 87 | 96.7% | |||||||
| 1110 | 1 | 220 | 90 | 152 | 69.1% | 60 | 66.7% | 257 | 116.8% | 87 | 96.7% | 242 | 110.0% | 87 | 96.7% | ||||||
| VAV 1-7 | 545 | 220 | 541 | 99% | 0.0% | 364 | 66.8% | 0.0% | 470 | 86.2% | 179 | 81.4% | |||||||||
| valt | 1 | 80 | 32 | * | 0.0% | * | 0.0% | * | * | ||||||||||||
| 1108 | 2 | 155 | 62 | 184 | 118.7% | 42 | 67.7% | 123 | 79.4% | 0.0% | 151 | 97.4% | 61 | 98.4% | |||||||
| 1102 | 3 | 155 | 62 | 174 | 112.3% | 42 | 67.7% | 116 | 74.8% | 0.0% | 148 | 95.5% | 55 | 88.7% | |||||||
| 1102 | 4 | 155 | 62 | 183 | 118.1% | 47 | 75.8% | 125 | 80.6% | 0.0% | 171 | 110.3% | 63 | 101.6% | |||||||
| Unable to read. Secure vault | |||||||||||||||||||||
| VAV 1-8 | 1380 | 550 | 1246 | 90.3% | 0.0% | 0.0% | 0.0% | 1428 | 103% | 530 | 96.4% | ||||||||||
| 1 | 230 | 92 | 220 | 95.7% | 0.0% | 0.0% | 0.0% | 244 | 106.1% | 89 | 97.2% | ||||||||||
| 2 | 230 | 92 | 193 | 83.9% | 0.0% | 0.0% | 0.0% | 227 | 98.7% | 88 | 96.1% | ||||||||||
| 3 | 230 | 92 | 216 | 93.9% | 0.0% | 0.0% | 0.0% | 229 | 99.6% | 88 | 96.1% | ||||||||||
| 4 | 230 | 92 | 192 | 83.5% | 0.0% | 0.0% | 0.0% | 227 | 98.7% | 84 | 91.8% | ||||||||||
| 5 | 230 | 92 | 205 | 89.1% | 0.0% | 0.0% | 0.0% | 257 | 111.7% | 91 | 99.4% | ||||||||||
| 6 | 230 | 92 | 220 | 95.7% | 0.0% | 0.0% | 0.0% | 244 | 106.1% | 90 | 98.3% | ||||||||||
| VAV 1-9 | 1110 | 445 | 871 | 78.5% | 353 | 79.3% | 1140 | 103% | 437 | 98.2% | 1140 | 103% | 437 | 98.2% | |||||||
| 1 | 185 | 74 | 147 | 79.5% | 64 | 86.5% | 180 | 97.3% | 70 | 94.6% | 180 | 97.3% | 70 | 94.6% | |||||||
| 2 | 185 | 74 | 160 | 86.5% | 62 | 83.8% | 201 | 108.6% | 70 | 94.6% | 201 | 108.6% | 70 | 94.6% | |||||||
| 3 | 185 | 74 | 144 | 77.8% | 59 | 79.7% | 189 | 102.2% | 74 | 100.0% | 189 | 102.2% | 74 | 100.0% | |||||||
| 4 | 185 | 74 | 143 | 77.3% | 58 | 78.4% | 189 | 102.2% | 78 | 105.4% | 189 | 102.2% | 78 | 105.4% | |||||||
| 5 | 185 | 74 | 131 | 70.8% | 55 | 74.3% | 201 | 108.6% | 68 | 91.9% | 201 | 108.6% | 68 | 91.9% | |||||||
| 6 | 185 | 74 | 146 | 78.9% | 55 | 74.3% | 180 | 97.3% | 77 | 104.1% | 180 | 97.3% | 77 | 104.1% |
Page &P of &N
AHU1 VAV (3)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 1 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | CO-2 LEVELS | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 1-10 | 1180 | 472 | 1064 | 90.2% | 0.0% | 0.0% | 0.0% | 1162 | 98.5% | 461 | 97.7% | ||||||||||
| 1 | 340 | 136 | 302 | 88.8% | 0.0% | 0.0% | 122 | 89.7% | 322 | 94.7% | 134 | 98.5% | |||||||||
| 2 | 340 | 136 | 298 | 87.6% | 0.0% | 0.0% | 121 | 89.0% | 327 | 96.2% | 132 | 97.1% | |||||||||
| 3 | 340 | 136 | 312 | 91.8% | 0.0% | 0.0% | 118 | 86.8% | 344 | 101.2% | 130 | 95.6% | |||||||||
| 4 | 160 | 64 | 152 | 95.0% | 0.0% | 0.0% | 57 | 89.1% | 169 | 105.6% | 65 | 101.6% | |||||||||
| VAV 1-26 | 800 | 318 | 1564 | 196% | 0.0% | 0 | 0% | 0.0% | 818 | 102% | 312 | 98% | |||||||||
| 1 | 400 | 159 | 900 | 225.0% | 0.0% | 0.0% | 0.0% | 450 | 112.5% | 170 | 106.8% | ||||||||||
| 2 | 140 | 56 | 84 | 60.0% | 0.0% | 0.0% | 0.0% | 88 | 62.9% | 27 | 48.5% | ||||||||||
| 3 | 260 | 103 | 580 | 223.1% | 0.0% | 0.0% | 0.0% | 280 | 107.7% | 115 | 111.1% | ||||||||||
| This VAV serves a single room balance at diffusers is not critical |
Page &P of &N
AHU 1 VAV (4)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | TESTED BY | DATE | |||||||||||||||||||
| ROOM T-STAT | CO-2 LEVELS | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 1-11 | 275 | 110 | 352 | 128% | 96 | 87.3% | 267 | 97.1% | 0.0% | 267 | 97.1% | 104 | 94.5% | ||||||||
| 2022 | 1 | 275 | 110 | 352 | 128.0% | 96 | 87.3% | 267 | 97.1% | 0.0% | 267 | 97.1% | 104 | 94.5% | |||||||
| Found max setpoint at 398cfm | |||||||||||||||||||||
| VAV 1-12 | 275 | 110 | 344 | 125% | 101 | 91.8% | 272 | 98.9% | 0.0% | 272 | 98.9% | 101 | 91.8% | ||||||||
| 2022 | 1 | 275 | 110 | 344 | 125.1% | 101 | 91.8% | 272 | 98.9% | 0.0% | 272 | 98.9% | 101 | 91.8% | |||||||
| Found max setpoint at 398 cfm | |||||||||||||||||||||
| VAV 1-13 | 305 | 122 | 320 | 105% | 0.0% | 0.0% | 0.0% | 320 | 105% | 140 | 115% | ||||||||||
| 1 | 100 | 40 | 110 | 110.0% | 0.0% | 0.0% | 0.0% | 110 | 110.0% | 40 | 100.0% | ||||||||||
| 2 | 205 | 82 | 210 | 102.4% | 0.0% | 0.0% | 0.0% | 210 | 102.4% | 100 | 122.0% | ||||||||||
| VAV 1-14 | 735 | 295 | 635 | 86.4% | 231 | 78.4% | 774 | 105% | 290 | 98.4% | 774 | 105% | 290 | 98.4% | |||||||
| 2019 | 1 | 230 | 92 | 199 | 86.5% | 75 | 81.3% | 246 | 107.0% | 93 | 100.8% | 246 | 107.0% | 93 | 100.8% | ||||||
| 2019 | 2 | 230 | 92 | 199 | 86.5% | 67 | 72.6% | 240 | 104.3% | 89 | 96.5% | 240 | 104.3% | 89 | 96.5% | ||||||
| 2021 | 3 | 275 | 110 | 237 | 86.2% | 89 | 80.7% | 288 | 104.7% | 108 | 97.9% | 288 | 104.7% | 108 | 97.9% | ||||||
| VAV 1-15 | 580 | 230 | 611 | 105% | 164 | 71.3% | 568 | 97.9% | 217 | 94.3% | 580 | 100% | 217 | 94.3% | |||||||
| 1 | 290 | 117 | 299 | 103.1% | 83 | 71.0% | 284 | 97.9% | 109 | 93.3% | 289 | 99.7% | 109 | 93.3% | |||||||
| 2 | 290 | 117 | 312 | 107.6% | 81 | 69.3% | 284 | 97.9% | 108 | 92.4% | 291 | 100.3% | 108 | 92.4% | |||||||
| VAV not able to be calibrated. Stops reading airflow at 380 cfm,** shop repaired vav** box calibrated at calculated values | |||||||||||||||||||||
| VAV 1-27 | 800 | 320 | 855 | 107% | 350 | 109% | 0 | 0.0% | 0 | 0.0% | 805 | 101% | 350 | 109% | |||||||
| 2023 | 1 | 400 | 160 | 420 | 105.0% | 180 | 112.5% | 0.0% | 0.0% | 395 | 98.8% | 180 | 112.5% | ||||||||
| 2023 | 2 | 400 | 160 | 435 | 108.8% | 170 | 106.3% | 0.0% | 0.0% | 410 | 102.5% | 170 | 106.3% |
Page &P of &N
AHU 1 VAV (5)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | TESTED BY | DATE | |||||||||||||||||||
| ROOM T-STAT | CO-2 LEVELS | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 1-16 | 1200 | 480 | 1157 | 96% | 479 | 99.8% | 0.0% | 0.0% | 1157 | 96.4% | 479 | 99.8% | |||||||||
| 1 | 240 | 96 | 231 | 96.3% | 96 | 100.0% | 0.0% | 0.0% | 231 | 96.3% | 96 | 100.0% | |||||||||
| 2 | 240 | 96 | 230 | 95.8% | 95 | 99.0% | 0.0% | 0.0% | 230 | 95.8% | 95 | 99.0% | |||||||||
| 3 | 240 | 96 | 234 | 98% | 98 | 102.1% | 0.0% | 0.0% | 234 | 97.5% | 98 | 102.1% | |||||||||
| 4 | 240 | 96 | 236 | 98.3% | 98 | 102.1% | 0.0% | 0.0% | 236 | 98.3% | 98 | 102.1% | |||||||||
| 5 | 240 | 96 | 226 | 94.2% | 92 | 95.8% | 0.0% | 0.0% | 226 | 94.2% | 92 | 95.8% | |||||||||
| VAV 1-17 | 240 | 95 | 218 | 91% | 91 | 95.8% | 239 | 99.6% | 0.0% | 239 | 100% | 91 | 96% | ||||||||
| 2017 | 1 | 240 | 95 | 218 | 90.8% | 91 | 95.8% | 239 | 99.6% | 0.0% | 239 | 99.6% | 91 | 95.8% | |||||||
| VAV 1-18 | 300 | 120 | 274 | 91.3% | 120 | 100% | 311 | 104% | 0 | 0.0% | 311 | 104% | 120 | 100% | |||||||
| 2019 | 1 | 110 | 44 | 92 | 83.6% | 43 | 97.7% | 113 | 102.7% | 0.0% | 113 | 102.7% | 43 | 97.7% | |||||||
| 2019 | 2 | 190 | 76 | 182 | 95.8% | 77 | 101.3% | 198 | 104.2% | 0.0% | 198 | 104.2% | 77 | 101.3% | |||||||
| VAV 1-19 | 630 | 250 | 549 | 87.1% | 163 | 65.2% | 649 | 103% | 241 | 96.4% | 649 | 103% | 241 | 96.4% | |||||||
| 2208 | 1 | 125 | 50 | 115 | 92.0% | 32 | 64.0% | 132 | 105.6% | 48 | 96.0% | 132 | 105.6% | 48 | 96.0% | ||||||
| 2209 | 2 | 200 | 80 | 179 | 89.5% | 53 | 66.3% | 212 | 106.0% | 78 | 97.5% | 212 | 106.0% | 78 | 97.5% | ||||||
| 3 | 305 | 122 | 255 | 83.6% | 78 | 63.9% | 305 | 100.0% | 115 | 94.3% | 305 | 100.0% | 115 | 94.3% | |||||||
| min airflow setpoint was 160 cfm schedule calls for 250 min cfm. | |||||||||||||||||||||
| VAV 1-20 | 255 | 102 | 227 | 89% | 127 | 125% | 249 | 97.6% | 119 | 117% | 249 | 98% | 109 | 107% | |||||||
| 2011 | 1 | 255 | 102 | 227 | 89.0% | 127 | 124.5% | 249 | 97.6% | 119 | 116.7% | 249 | 97.6% | 109 | 106.9% | ||||||
| print calls for 255 cfm schedule calls for 235 cfm |
Page &P of &N
AHU 1 VAV (6)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | TESTED BY | DATE | |||||||||||||||||||
| ROOM T-STAT | CO-2 LEVELS | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 1-21 | 660 | 265 | 678 | 103% | 432 | 163% | 714 | 108% | 273 | 103% | 714 | 108% | 273 | 103% | |||||||
| 2005 | 1 | 190 | 76 | 209 | 110.0% | 132 | 173.7% | 207 | 108.9% | 77 | 101.3% | 207 | 108.9% | 77 | 101.3% | ||||||
| 2009 | 2 | 280 | 112 | 268 | 95.7% | 175 | 156.3% | 287 | 102.5% | 112 | 100.0% | 287 | 102.5% | 112 | 100.0% | ||||||
| 3 | 190 | 76 | 201 | 106% | 125 | 164.5% | 220 | 115.8% | 84 | 110.5% | 220 | 115.8% | 84 | 110.5% | |||||||
| VAV 1-22 | 1350 | 540 | 1133 | 84% | 496 | 91.9% | 1379 | 102% | 536 | 99.3% | 1379 | 102% | 536 | 99% | |||||||
| 1 | 220 | 88 | 195 | 88.6% | 84 | 95.5% | 236 | 107.3% | 91 | 103.4% | 236 | 107.3% | 91 | 103.4% | |||||||
| 2 | 220 | 88 | 193 | 87.7% | 83 | 94.3% | 233 | 105.9% | 88 | 100.0% | 233 | 105.9% | 88 | 100.0% | |||||||
| 3 | 220 | 88 | 171 | 77.7% | 75 | 85.2% | 204 | 92.7% | 81 | 92.0% | 204 | 92.7% | 81 | 92.0% | |||||||
| 4 | 220 | 88 | 177 | 80.5% | 78 | 88.6% | 213 | 96.8% | 85 | 96.6% | 213 | 96.8% | 85 | 96.6% | |||||||
| 5 | 220 | 88 | 190 | 86.4% | 83 | 94.3% | 229 | 104.1% | 91 | 103.4% | 229 | 104.1% | 91 | 103.4% | |||||||
| 2010 | 6 | 250 | 100 | 207 | 82.8% | 93 | 93.0% | 264 | 105.6% | 100 | 100.0% | 264 | 105.6% | 100 | 100.0% | ||||||
| VAV 1-23 | 530 | 210 | 465 | 87.7% | 189 | 90.0% | 532 | 100% | 208 | 99.0% | 532 | 100% | 208 | 99.0% | |||||||
| 1 | 230 | 92 | 213 | 92.6% | 86 | 93.5% | 245 | 106.5% | 94 | 102.2% | 245 | 106.5% | 94 | 102.2% | |||||||
| 2003 | 2 | 300 | 120 | 252 | 84.0% | 103 | 85.8% | 287 | 95.7% | 114 | 95.0% | 287 | 95.7% | 114 | 95.0% | ||||||
| Damper drive motor needs replace. Squeaking durring operation | |||||||||||||||||||||
| VAV 1-24 | 275 | 110 | 260 | 94.5% | 128 | 116% | 275 | 100% | 137 | 125% | 275 | 100% | 128 | 116% | |||||||
| 2006 | 1 | 275 | 110 | 260 | 94.5% | 128 | 116.4% | 275 | 100.0% | 137 | 124.5% | 275 | 100.0% | 128 | 116.4% | ||||||
| VAV 1-25 | 500 | 200 | 460 | 92% | 370 | 185% | 520 | 104% | 217 | 109% | 520 | 104% | 217 | 109% | |||||||
| 2004 | 1 | 190 | 76 | 160 | 84.2% | 85 | 111.8% | 165 | 86.8% | 67 | 88.2% | 165 | 86.8% | 67 | 88.2% | ||||||
| 2004 | 2 | 310 | 124 | 300 | 96.8% | 285 | 229.8% | 355 | 114.5% | 150 | 121.0% | 355 | 114.5% | 150 | 121.0% |
Page &P of &N
AHU 2 AIR APPARATUS
| AIR APPARATUS TEST REPORT | |||||||||||||
| BASE | W/O# | ||||||||||||
| SYSTEM | AHU 2 | BUILDING | DATE | NAME | |||||||||
| TYPE EQUIPMENT | AHU | SUPPLY FAN | EXHAUST | RETURN | |||||||||
| TYPE OF SYSTEM | CV | VAV | MULITZONE | DUAL DUCT | REHEAT | ||||||||
| FAN DATA | MOTOR DATA | ||||||||||||
| MANUFACTURER | Trane | MANUFACTURER | GE | ||||||||||
| MODEL NUMBER | MCCAA035GAM0ACA | MODEL NUMBER | 5KS254SAB205A | ||||||||||
| WHEEL TYPE | AIR FOIL | FORWARD CURVE | NAME PLATE HORSE POWER | 15 | NAME PLATE RPMS | 1770 | |||||||
| BACKWARDS INCLINE | OTHER | EFFICIENCY | 92.4 | POWER FACTOR | 84.5 | ||||||||
| BELT SIZE | B-47 2ea | SHAFT SIZE | 2 3/16 | SHAFT SIZE | 1 5/8 | AS FOUND | FINAL | ||||||
| PULLEY FAN OD | 7 3/8 | MOTOR OD | 6 3/4 | RPM | 1768 | ||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | 14 | BHP | |||||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | |||||||||||||
| DESIGN | AS FOUND | FINAL | DESIGN | ACTUAL | FINAL | ||||||||
| FAN CFM | 16,800 | 13,798 | VOLTAGE A-B | 460 | 479 | ||||||||
| FAN RPM | 1633 | VOLTAGE B-C | 479 | ||||||||||
| DISCHARGE S.P. | 2.11 | VOLTAGE C-A | 479 | ||||||||||
| EXTERNAL S.P. | AMPERAGE A | 18 | 15.5 | ||||||||||
| REMARKS | AMPERAGE B | 15.9 | |||||||||||
| Total Static 3.77 | AMPERAGE C | 16 | |||||||||||
| Connected load 26,235 full cooling | |||||||||||||
| Minimum air flow required 10,480 min cool and heat | |||||||||||||
| Oa design 40% of 16,800 = 6,720 | AIR VOLUMES | ||||||||||||
| DESIGN | AS FOUND | FINAL | |||||||||||
| MAX | MIN | MAX | MIN | MAX | MIN | ||||||||
| O/A CFM | 4,713 | ||||||||||||
| R/A | S/A | AFTER CC/A | R/A CFM | ||||||||||
| O/A TEMP | R/A TEMP | M/A TEMP | |||||||||||
| STATIC PRESSURE DROPS | |||||||||||||
| COIL NAME AND DESIGN S.P. DROP | AS FOUND | FINAL | AS FOUND | FINAL | AS FOUND | FINAL | |||||||
| Cooling coil | 0.334 | ||||||||||||
| Heating coil | 0.1 |
Page &P of &N x x x
AHU 2 Total Supply Air
| PITOT TUBE TRAVERSE LARGE ROUND DUCT | ||||||||||||||||||
| BASE: | JOB NO.: | DATE: | ||||||||||||||||
| LOCATION: | SYSTEM: | |||||||||||||||||
| LOCATION OF DUCT: | AREA SERVED: | DUCT TEMP.: | DUCT S.P.: | |||||||||||||||
| DUCT SIZE: | X | REQUIRED CFM: | REQUIRED FPM: | PERCENT OF DESIGN = ACTUAL CFM/REQUIRED CFM | ||||||||||||||
| DUCT AREA IN SQ.FT.: | ACTUAL CFM: | ACTUAL FPM: | ||||||||||||||||
| TRAVERSE POINTS | READINGS | |||||||||||||||||
| Total Supply VAVS in Max | Total Supply VAVS in Min | |||||||||||||||||
| FPM | FPM | FPM | FPM | |||||||||||||||
| 1 | 2077 | 1354 | ||||||||||||||||
| 2 | 1983 | 1595 | ||||||||||||||||
| 3 | 1992 | 1573 | ||||||||||||||||
| 4 | 1931 | 1580 | ||||||||||||||||
| 5 | 2010 | 1541 | ||||||||||||||||
| 6 | 2551 | 1534 | ||||||||||||||||
| 7 | 2486 | 1584 | ||||||||||||||||
| 8 | 2588 | 1539 | ||||||||||||||||
| 9 | 2617 | 1467 | ||||||||||||||||
| 10 | 2150 | 1294 | ||||||||||||||||
| 1 | 2114 | 1218 | ||||||||||||||||
| 2 | 2297 | 1248 | ||||||||||||||||
| DUCT DIA | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | ||||||||
| 3 | 2542 | 1241 | ||||||||||||||||
| 12 | 3/8 | 1 | 1 3/4 | 2 3/4 | 4 1/8 | 7 7/8 | 9 1/4 | 10 1/4 | 11 | 11 5/8 | ||||||||
| 13 | 3/8 | 1 | 1 7/8 | 2 7/8 | 4 1/2 | 8 1/2 | 10 1/8 | 11 1/8 | 12 | 12 5/8 | 4 | 2582 | 1243 | |||||
| 14 | 3/8 | 1 1/8 | 2 | 3 1/8 | 4 3/4 | 9 1/4 | 10 7/8 | 12 | 12 7/8 | 13 5/8 | ||||||||
| 15 | 3/8 | 1 1/4 | 2 1/4 | 3 3/8 | 5 1/8 | 9 7/8 | 11 5/8 | 12 3/4 | 13 3/4 | 14 5/8 | 5 | 2407 | 1325 | |||||
| 16 | 3/8 | 1 1/4 | 2 3/8 | 3 5/8 | 5 1/2 | 10 1/2 | 12 3/8 | 13 5/8 | 14 3/4 | 15 5/8 | ||||||||
| 17 | 1/2 | 1 3/8 | 2 1/2 | 3 7/8 | 5 3/4 | 11 1/4 | 13 1/8 | 14 1/2 | 15 5/8 | 16 1/2 | 6 | 2441 | 1625 | |||||
| 18 | 1/2 | 1 1/2 | 2 5/8 | 4 1/8 | 6 1/8 | 11 7/8 | 14 1/2 | 15 3/8 | 16 1/2 | 17 1/2 | ||||||||
| 19 | 1/2 | 1 1/2 | 2 3/4 | 4 1/4 | 6 1/2 | 12 1/2 | 15 3/4 | 16 1/4 | 17 1/2 | 18 1/2 | 7 | 2576 | 1582 | |||||
| 20 | 1/2 | 1 5/8 | 2 7/8 | 4 1/2 | 6 7/8 | 13 1/8 | 17 1/8 | 17 1/8 | 18 1/2 | 19 1/2 | ||||||||
| 22 | 5/8 | 1 3/4 | 3 1/4 | 5 | 7 1/2 | 14 1/2 | 17 | 18 3/4 | 20 1/2 | 21 3/8 | 8 | 2603 | 1664 | |||||
| 24 | 5/8 | 2 | 3 1/2 | 5 1/2 | 8 1/8 | 15 3/4 | 18 1/2 | 20 1/2 | 22 | 23 3/8 | ||||||||
| 26 | 5/8 | 2 1/8 | 3 3/4 | 5 7/8 | 8 7/8 | 17 1/8 | 20 1/8 | 22 1/4 | 23 3/8 | 25 3/8 | 9 | 2356 | 1668 | |||||
| 28 | 3/4 | 2 1/4 | 4 1/8 | 6 3/8 | 9 5/8 | 18 3/8 | 21 5/8 | 23 7/8 | 25 3/4 | 27 1/4 | ||||||||
| 30 | 3/4 | 2 1/2 | 4 3/8 | 6 3/4 | 10 1/4 | 19 3/4 | 23 1/4 | 25 5/8 | 27 1/2 | 19 1/4 | 10 | 2098 | 1422 | |||||
| 32 | 7/8 | 2 5/8 | 4 5/8 | 7 1/4 | 11 | 21 | 24 3/4 | 27 3/8 | 29 3/8 | 31 1/4 | ||||||||
| 34 | 7/8 | 2 3/4 | 5 | 7 3/4 | 11 5/8 | 22 3/8 | 26 1/4 | 29 | 31 1/4 | 33 1/8 | TOTAL FPM | 46401 | 0 | 29297 | 0 | |||
| 36 | 1 | 3 | 5 1/4 | 8 1/8 | 12 3/8 | 23 5/8 | 27 7/8 | 30 3/4 | 33 | 35 | ||||||||
| 38 | 1 | 3 1/8 | 5 1/2 | 8 5/8 | 13 | 25 | 29 3/8 | 32 1/2 | 34 7/8 | 37 | Divided by 20 | 2320.05 | 0 | 1464.85 | 0 | |||
| 40 | 1 | 3 1/4 | 5 7/8 | 9 | 13 5/8 | 26 3/8 | 31 | 34 1/8 | 36 3/4 | 39 | ||||||||
| 42 | 1 1/8 | 3 3/8 | 6 1/8 | 9 1/2 | 14 3/8 | 27 5/8 | 32 1/2 | 35 7/8 | 38 5/8 | 40 1/8 | Times Duct Area | 5.59 | 5.59 | 2.64 | ||||
| 44 | 1 1/8 | 3 5/8 | 6 3/8 | 10 | 15 | 29 | 34 | 37 5/8 | 40 3/8 | 42 7/8 | ||||||||
| 46 | 1 1/4 | 3 3/4 | 6 3/4 | 10 3/8 | 15 3/4 | 30 1/4 | 35 5/8 | 39 1/4 | 40 1/4 | 44 3/4 | = Total CFM | 12959.28 | 0 | 8182.33 | 0 | |||
| 48 | 1 1/4 | 4 | 7 | 10 7/8 | 16 3/8 | 31 5/8 | 37 1/8 | 41 | 44 | 46 3/4 | ||||||||
| Elevator rooms | 839 | 838 | ||||||||||||||||
| 13798.2837333333 | 9020 |
Page &P of &N
TRAVERSE POINT LAYOUT
6 7 8 9 10 1 2 3 4 5
RET FAN 2 AIR APPARATUS
| AIR APPARATUS TEST REPORT | |||||||||||||
| BASE | W/O# | ||||||||||||
| SYSTEM | BUILDING | DATE | NAME | ||||||||||
| TYPE EQUIPMENT | AHU | SUPPLY FAN | EXHAUST | RETURN | |||||||||
| TYPE OF SYSTEM | CV | VAV | MULITZONE | DUAL DUCT | REHEAT | ||||||||
| FAN DATA | MOTOR DATA | ||||||||||||
| MANUFACTURER | MANUFACTURER | GE | |||||||||||
| MODEL NUMBER | MODEL NUMBER | 5KS213SAB205 | |||||||||||
| WHEEL TYPE | AIR FOIL | FORWARD CURVE | NAME PLATE HORSE POWER | 7 1/2 | NAME PLATE RPMS | 1770 | |||||||
| BACKWARDS INCLINE | OTHER | EFFICIENCY | 91.7 | POWER FACTOR | 83.5 | ||||||||
| BELT SIZE | BX-82 | SHAFT SIZE | 1 7/16 | SHAFT SIZE | 1 3/8 | AS FOUND | FINAL | ||||||
| PULLEY FAN OD | 9 3/4 | MOTOR OD | 8 1/2 | RPM | 1399 | ||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | 28 1/4 | BHP | |||||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | |||||||||||||
| DESIGN | AS FOUND | FINAL | DESIGN | ACTUAL | FINAL | ||||||||
| FAN CFM | 11276 | VOLTAGE A-B | 460 | 477 | |||||||||
| FAN RPM | 1199 | VOLTAGE B-C | 460 | 477 | |||||||||
| DISCHARGE S.P. | VOLTAGE C-A | 460 | 477 | ||||||||||
| EXTERNAL S.P. | AMPERAGE A | 9.2 | 5.2 | ||||||||||
| REMARKS | AMPERAGE B | 9.2 | 5.2 | ||||||||||
| Fan operating at 47.1 hz | AMPERAGE C | 9.2 | 5.2 | ||||||||||
| Fan and motor pulleys are worn | |||||||||||||
| AIR VOLUMES | |||||||||||||
| DESIGN | AS FOUND | FINAL | |||||||||||
| MAX | MIN | MAX | MIN | MAX | MIN | ||||||||
| O/A CFM | |||||||||||||
| R/A | S/A | AFTER CC/A | R/A CFM | ||||||||||
| O/A TEMP | R/A TEMP | M/A TEMP | |||||||||||
| STATIC PRESSURE DROPS | |||||||||||||
| COIL NAME AND DESIGN S.P. DROP | AS FOUND | FINAL | AS FOUND | FINAL | AS FOUND | FINAL |
Page &P of &N
AHU 2 RET & OA TRAVERSE
| BASE: | SYSTEM: | LOCATION: | |||||||||||||||
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 | 15 | 16 | 17 | |
| A | 1332 | 1334 | 1351 | 1232 | 1372 | 1370 | 1179 | 175 | 156 | 0 | 124 | 357 | 270 | 143 | 58 | 80 | |
| B | 1347 | 1363 | 1301 | 1283 | 1364 | 1354 | 1282 | 153 | 254 | 147 | 309 | 344 | 336 | 207 | 107 | 215 | |
| C | 1269 | 1185 | 1183 | 1323 | 1271 | 1172 | 1279 | 234 | 312 | 232 | 372 | 423 | 427 | 305 | 259 | 308 | |
| D | 1097 | 844 | 1024 | 1026 | 1129 | 858 | 1103 | 342 | 323 | 352 | 407 | 439 | 428 | 343 | 412 | 414 | |
| E | 631 | 233 | 543 | 615 | 416 | 584 | 935 | 360 | 373 | 436 | 440 | 486 | 444 | 437 | 436 | 438 | |
| F | 416 | 0 | 0 | 244 | 249 | 375 | 395 | 315 | 420 | 480 | 494 | 490 | 529 | 541 | 543 | 537 | |
| G | |||||||||||||||||
| H | Return air | Outside Air | |||||||||||||||
| I | Total FPM = | 39863 | Total FPM = | 17966 | |||||||||||||
| J | Ft per Minute Average = | 949.119047619 | Ft per Minute Average = | 332.7037037037 | |||||||||||||
| K | Area K (32" X 62") /144 = | 11.88 | Area K (34" X 60") /144 = | 14.166 | |||||||||||||
| L | Cubic Ft. per Minute = | 11,276 | Cubic Ft. per Minute = | 4,713 | |||||||||||||
| M | |||||||||||||||||
| N | |||||||||||||||||
| O | |||||||||||||||||
| P | 335 | 369 | 435 | 500 | 475 | 393 | 269 | 333 | 215 | ||||||||
| Q | 275 | 417 | 532 | 520 | 594 | 472 | 410 | 424 | 265 | ||||||||
| R | 434 | 560 | 576 | 566 | 583 | 587 | 549 | 472 | 438 | ||||||||
| S | 465 | 578 | 585 | 591 | 572 | 624 | 603 | 571 | 456 | ||||||||
| T | 578 | 632 | 599 | 579 | 605 | 651 | 658 | 644 | 535 | ||||||||
| U | 453 | 650 | 573 | 521 | 643 | 652 | 678 | 676 | 625 | ||||||||
| V | |||||||||||||||||
| W | Return air | Outside Air | |||||||||||||||
| X | Total FPM = | 0 | Total FPM = | 27995 | |||||||||||||
| Y | Ft per Minute Average = | 0 | Ft per Minute Average = | 518.4259259259 | |||||||||||||
| Z | Area K (0" X 0") /144 = | 11.88 | Area K (34" X 60") /144 = | 14.166 | |||||||||||||
| Cubic Ft. per Minute = | 0 | Cubic Ft. per Minute = | 7,344 |
AHU 4 AIR APPARATUS
| AIR APPARATUS TEST REPORT | |||||||||||||
| BASE | W/O# | ||||||||||||
| SYSTEM | AHU 4 | BUILDING | DATE | NAME | |||||||||
| TYPE EQUIPMENT | AHU | SUPPLY FAN | EXHAUST | RETURN | |||||||||
| TYPE OF SYSTEM | CV | VAV | MULITZONE | DUAL DUCT | REHEAT | ||||||||
| FAN DATA | MOTOR DATA | ||||||||||||
| MANUFACTURER | Trane | MANUFACTURER | Baldor | ||||||||||
| MODEL NUMBER | MCCA050GAM0ACA | MODEL NUMBER | M4104T | ||||||||||
| WHEEL TYPE | AIR FOIL | FORWARD CURVE | NAME PLATE HORSE POWER | 30 | NAME PLATE RPMS | 1760 | |||||||
| BACKWARDS INCLINE | OTHER | EFFICIENCY | 93.6 | POWER FACTOR | 80 | ||||||||
| BELT SIZE | BX-53 4ea | SHAFT SIZE | 2 3/8 | SHAFT SIZE | 1 7/8 | AS FOUND | FINAL | ||||||
| PULLEY FAN OD | 9 7/8 | MOTOR OD | 7 3/4 | RPM | |||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | 16 | BHP | |||||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | |||||||||||||
| DESIGN | AS FOUND | FINAL | DESIGN | ACTUAL | FINAL | ||||||||
| FAN CFM | VOLTAGE A-B | 460 | |||||||||||
| FAN RPM | VOLTAGE B-C | ||||||||||||
| DISCHARGE S.P. | VOLTAGE C-A | ||||||||||||
| EXTERNAL S.P. | AMPERAGE A | 38 | |||||||||||
| REMARKS | AMPERAGE B | ||||||||||||
| AMPERAGE C | |||||||||||||
| AIR VOLUMES | |||||||||||||
| DESIGN | AS FOUND | FINAL | |||||||||||
| MAX | MIN | MAX | MIN | MAX | MIN | ||||||||
| O/A CFM | |||||||||||||
| R/A | S/A | AFTER CC/A | R/A CFM | ||||||||||
| O/A TEMP | R/A TEMP | M/A TEMP | |||||||||||
| STATIC PRESSURE DROPS | |||||||||||||
| COIL NAME AND DESIGN S.P. DROP | AS FOUND | FINAL | AS FOUND | FINAL | AS FOUND | FINAL |
Page &P of &N x x X
AHU4 AIR APPARATUS 2ND TRIP
| PITOT TUBE TRAVERSE LARGE ROUND DUCT | ||||||||||||||||||||
| BASE: | JOB NO.: | DATE: | ||||||||||||||||||
| LOCATION: Building | SYSTEM: | |||||||||||||||||||
| LOCATION OF DUCT: | AREA SERVED: | DUCT TEMP.: | DUCT S.P.: | |||||||||||||||||
| DUCT SIZE: | A= 24" | B=22" | REQUIRED CFM: | REQUIRED FPM: | PERCENT OF DESIGN = ACTUAL CFM/REQUIRED CFM | |||||||||||||||
| DUCT AREA IN SQ.FT.: | ACTUAL CFM: | ACTUAL FPM: | ||||||||||||||||||
| TRAVERSE POINTS | READINGS | |||||||||||||||||||
| DUCT A 1st flr | DUCT B 2nd flr | |||||||||||||||||||
| FPM | FPM | FPM | FPM | |||||||||||||||||
| 1 | 2471 | 2957 | 4338 | 2213 | ||||||||||||||||
| 2 | 2549 | 3171 | 4438 | 2235 | ||||||||||||||||
| 3 | 2600 | 3217 | 4404 | 2194 | ||||||||||||||||
| 4 | 2554 | 3150 | 4371 | 2209 | ||||||||||||||||
| 5 | 2620 | 3256 | 4494 | 2268 | ||||||||||||||||
| 6 | 3215 | 3293 | 4484 | 2905 | ||||||||||||||||
| 7 | 3475 | 3124 | 4302 | 2944 | ||||||||||||||||
| 8 | 3665 | 3180 | 4275 | 3153 | ||||||||||||||||
| 9 | 3770 | 2946 | 4230 | 3229 | ||||||||||||||||
| 10 | 3877 | 2733 | 3952 | 3267 | ||||||||||||||||
| 1 | 3525 | 3303 | 4700 | 2865 | ||||||||||||||||
| 2 | 3613 | 3359 | 4798 | 3043 | ||||||||||||||||
| DUCT DIA | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | ||||||||||
| 3 | 3503 | 3428 | 4789 | 2985 | ||||||||||||||||
| 12 | 3/8 | 1 | 1 3/4 | 2 3/4 | 4 1/8 | 7 7/8 | 9 1/4 | 10 1/4 | 11 | 11 5/8 | ||||||||||
| 13 | 3/8 | 1 | 1 7/8 | 2 7/8 | 4 1/2 | 8 1/2 | 10 1/8 | 11 1/8 | 12 | 12 5/8 | 4 | 3337 | 3398 | 4753 | 2968 | |||||
| 14 | 3/8 | 1 1/8 | 2 | 3 1/8 | 4 3/4 | 9 1/4 | 10 7/8 | 12 | 12 7/8 | 13 5/8 | ||||||||||
| 15 | 3/8 | 1 1/4 | 2 1/4 | 3 3/8 | 5 1/8 | 9 7/8 | 11 5/8 | 12 3/4 | 13 3/4 | 14 5/8 | 5 | 3188 | 3344 | 4688 | 2939 | |||||
| 16 | 3/8 | 1 1/4 | 2 3/8 | 3 5/8 | 5 1/2 | 10 1/2 | 12 3/8 | 13 5/8 | 14 3/4 | 15 5/8 | ||||||||||
| 17 | 1/2 | 1 3/8 | 2 1/2 | 3 7/8 | 5 3/4 | 11 1/4 | 13 1/8 | 14 1/2 | 15 5/8 | 16 1/2 | 6 | 3159 | 3230 | 4592 | 2775 | |||||
| 18 | 1/2 | 1 1/2 | 2 5/8 | 4 1/8 | 6 1/8 | 11 7/8 | 14 1/2 | 15 3/8 | 16 1/2 | 17 1/2 | ||||||||||
| 19 | 1/2 | 1 1/2 | 2 3/4 | 4 1/4 | 6 1/2 | 12 1/2 | 15 3/4 | 16 1/4 | 17 1/2 | 18 1/2 | 7 | 3262 | 3145 | 4530 | 2835 | |||||
| 20 | 1/2 | 1 5/8 | 2 7/8 | 4 1/2 | 6 7/8 | 13 1/8 | 17 1/8 | 17 1/8 | 18 1/2 | 19 1/2 | ||||||||||
| 22 | 5/8 | 1 3/4 | 3 1/4 | 5 | 7 1/2 | 14 1/2 | 17 | 18 3/4 | 20 1/2 | 21 3/8 | 8 | 3347 | 3087 | 4487 | 2958 | |||||
| 24 | 5/8 | 2 | 3 1/2 | 5 1/2 | 8 1/8 | 15 3/4 | 18 1/2 | 20 1/2 | 22 | 23 3/8 | ||||||||||
| 26 | 5/8 | 2 1/8 | 3 3/4 | 5 7/8 | 8 7/8 | 17 1/8 | 20 1/8 | 22 1/4 | 23 3/8 | 25 3/8 | 9 | 3255 | 3060 | 4469 | 2960 | |||||
| 28 | 3/4 | 2 1/4 | 4 1/8 | 6 3/8 | 9 5/8 | 18 3/8 | 21 5/8 | 23 7/8 | 25 3/4 | 27 1/4 | ||||||||||
| 30 | 3/4 | 2 1/2 | 4 3/8 | 6 3/4 | 10 1/4 | 19 3/4 | 23 1/4 | 25 5/8 | 27 1/2 | 19 1/4 | 10 | 3057 | 2683 | 4034 | 2879 | |||||
| 32 | 7/8 | 2 5/8 | 4 5/8 | 7 1/4 | 11 | 21 | 24 3/4 | 27 3/8 | 29 3/8 | 31 1/4 | ||||||||||
| 34 | 7/8 | 2 3/4 | 5 | 7 3/4 | 11 5/8 | 22 3/8 | 26 1/4 | 29 | 31 1/4 | 33 1/8 | TOTAL FPM | 64042 | 63064 | 89128 | 55824 | |||||
| 36 | 1 | 3 | 5 1/4 | 8 1/8 | 12 3/8 | 23 5/8 | 27 7/8 | 30 3/4 | 33 | 35 | ||||||||||
| 38 | 1 | 3 1/8 | 5 1/2 | 8 5/8 | 13 | 25 | 29 3/8 | 32 1/2 | 34 7/8 | 37 | Divided by 20 | 3202.1 | 3153.2 | 4456.4 | 2791.2 | |||||
| 40 | 1 | 3 1/4 | 5 7/8 | 9 | 13 5/8 | 26 3/8 | 31 | 34 1/8 | 36 3/4 | 39 | ||||||||||
| 42 | 1 1/8 | 3 3/8 | 6 1/8 | 9 1/2 | 14 3/8 | 27 5/8 | 32 1/2 | 35 7/8 | 38 5/8 | 40 1/8 | Times Duct Area | 2.64 | 2.64 | 3.14 | 3.14 | |||||
| 44 | 1 1/8 | 3 5/8 | 6 3/8 | 10 | 15 | 29 | 34 | 37 5/8 | 40 3/8 | 42 7/8 | ||||||||||
| 46 | 1 1/4 | 3 3/4 | 6 3/4 | 10 3/8 | 15 3/4 | 30 1/4 | 35 5/8 | 39 1/4 | 40 1/4 | 44 3/4 | = Total CFM | 8453.54 | 8324.448 | 13993.10 | 8769.95 | |||||
| 48 | 1 1/4 | 4 | 7 | 10 7/8 | 16 3/8 | 31 5/8 | 37 1/8 | 41 | 44 | 46 3/4 | ||||||||||
| 1163 | 0 | 466 | 313 | |||||||||||||||||
| static | 9616.544 | 8324.448 | 14459 | 9082.95 | ||||||||||||||||
| pitot tube | 0.93 | c/l 2.38 | Max VAV only | c/l 1.80" |
TRAVERSE POINT LAYOUT
6 7 8 9 10 1 2 3 4 5
AHU 4 Total Supply Air
| PITOT TUBE TRAVERSE LARGE ROUND DUCT | ||||||||||||||||||
| BASE: | JOB NO.: | DATE: | ||||||||||||||||
| LOCATION: | SYSTEM: | |||||||||||||||||
| LOCATION OF DUCT: | AREA SERVED: | DUCT TEMP.: | DUCT S.P.: | |||||||||||||||
| DUCT SIZE: | X | REQUIRED CFM: | REQUIRED FPM: | PERCENT OF DESIGN = ACTUAL CFM/REQUIRED CFM | ||||||||||||||
| DUCT AREA IN SQ.FT.: | ACTUAL CFM: | ACTUAL FPM: | ||||||||||||||||
| TRAVERSE POINTS | READINGS | |||||||||||||||||
| DUCT A 1st flr | DUCT B 2nd flr | |||||||||||||||||
| FPM | FPM | FPM | FPM | |||||||||||||||
| 1 | 2471 | 4338 | ||||||||||||||||
| 2 | 2549 | 4438 | ||||||||||||||||
| 3 | 2600 | 4404 | ||||||||||||||||
| 4 | 2554 | 4371 | ||||||||||||||||
| 5 | 2620 | 4494 | ||||||||||||||||
| 6 | 3215 | 4484 | ||||||||||||||||
| 7 | 3475 | 4302 | ||||||||||||||||
| 8 | 3665 | 4275 | ||||||||||||||||
| 9 | 3770 | 4230 | ||||||||||||||||
| 10 | 3877 | 3952 | ||||||||||||||||
| 1 | 3525 | 4700 | ||||||||||||||||
| 2 | 3613 | 4798 | ||||||||||||||||
| DUCT DIA | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | ||||||||
| 3 | 3503 | 4789 | ||||||||||||||||
| 12 | 3/8 | 1 | 1 3/4 | 2 3/4 | 4 1/8 | 7 7/8 | 9 1/4 | 10 1/4 | 11 | 11 5/8 | ||||||||
| 13 | 3/8 | 1 | 1 7/8 | 2 7/8 | 4 1/2 | 8 1/2 | 10 1/8 | 11 1/8 | 12 | 12 5/8 | 4 | 3337 | 4753 | |||||
| 14 | 3/8 | 1 1/8 | 2 | 3 1/8 | 4 3/4 | 9 1/4 | 10 7/8 | 12 | 12 7/8 | 13 5/8 | ||||||||
| 15 | 3/8 | 1 1/4 | 2 1/4 | 3 3/8 | 5 1/8 | 9 7/8 | 11 5/8 | 12 3/4 | 13 3/4 | 14 5/8 | 5 | 3188 | 4688 | |||||
| 16 | 3/8 | 1 1/4 | 2 3/8 | 3 5/8 | 5 1/2 | 10 1/2 | 12 3/8 | 13 5/8 | 14 3/4 | 15 5/8 | ||||||||
| 17 | 1/2 | 1 3/8 | 2 1/2 | 3 7/8 | 5 3/4 | 11 1/4 | 13 1/8 | 14 1/2 | 15 5/8 | 16 1/2 | 6 | 3159 | 4592 | |||||
| 18 | 1/2 | 1 1/2 | 2 5/8 | 4 1/8 | 6 1/8 | 11 7/8 | 14 1/2 | 15 3/8 | 16 1/2 | 17 1/2 | ||||||||
| 19 | 1/2 | 1 1/2 | 2 3/4 | 4 1/4 | 6 1/2 | 12 1/2 | 15 3/4 | 16 1/4 | 17 1/2 | 18 1/2 | 7 | 3262 | 4530 | |||||
| 20 | 1/2 | 1 5/8 | 2 7/8 | 4 1/2 | 6 7/8 | 13 1/8 | 17 1/8 | 17 1/8 | 18 1/2 | 19 1/2 | ||||||||
| 22 | 5/8 | 1 3/4 | 3 1/4 | 5 | 7 1/2 | 14 1/2 | 17 | 18 3/4 | 20 1/2 | 21 3/8 | 8 | 3347 | 4487 | |||||
| 24 | 5/8 | 2 | 3 1/2 | 5 1/2 | 8 1/8 | 15 3/4 | 18 1/2 | 20 1/2 | 22 | 23 3/8 | ||||||||
| 26 | 5/8 | 2 1/8 | 3 3/4 | 5 7/8 | 8 7/8 | 17 1/8 | 20 1/8 | 22 1/4 | 23 3/8 | 25 3/8 | 9 | 3255 | 4469 | |||||
| 28 | 3/4 | 2 1/4 | 4 1/8 | 6 3/8 | 9 5/8 | 18 3/8 | 21 5/8 | 23 7/8 | 25 3/4 | 27 1/4 | ||||||||
| 30 | 3/4 | 2 1/2 | 4 3/8 | 6 3/4 | 10 1/4 | 19 3/4 | 23 1/4 | 25 5/8 | 27 1/2 | 19 1/4 | 10 | 3057 | 4034 | |||||
| 32 | 7/8 | 2 5/8 | 4 5/8 | 7 1/4 | 11 | 21 | 24 3/4 | 27 3/8 | 29 3/8 | 31 1/4 | ||||||||
| 34 | 7/8 | 2 3/4 | 5 | 7 3/4 | 11 5/8 | 22 3/8 | 26 1/4 | 29 | 31 1/4 | 33 1/8 | TOTAL FPM | 64042 | 0 | 89128 | 0 | |||
| 36 | 1 | 3 | 5 1/4 | 8 1/8 | 12 3/8 | 23 5/8 | 27 7/8 | 30 3/4 | 33 | 35 | ||||||||
| 38 | 1 | 3 1/8 | 5 1/2 | 8 5/8 | 13 | 25 | 29 3/8 | 32 1/2 | 34 7/8 | 37 | Divided by 20 | 3202.1 | 0 | 4456.4 | 0 | |||
| 40 | 1 | 3 1/4 | 5 7/8 | 9 | 13 5/8 | 26 3/8 | 31 | 34 1/8 | 36 3/4 | 39 | ||||||||
| 42 | 1 1/8 | 3 3/8 | 6 1/8 | 9 1/2 | 14 3/8 | 27 5/8 | 32 1/2 | 35 7/8 | 38 5/8 | 40 1/8 | Times Duct Area | 3.142 | 3.142 | 2.64 | 2.64 | |||
| 44 | 1 1/8 | 3 5/8 | 6 3/8 | 10 | 15 | 29 | 34 | 37 5/8 | 40 3/8 | 42 7/8 | ||||||||
| 46 | 1 1/4 | 3 3/4 | 6 3/4 | 10 3/8 | 15 3/4 | 30 1/4 | 35 5/8 | 39 1/4 | 40 1/4 | 44 3/4 | = Total CFM | 10061.00 | 0 | 11765.58 | 0 | |||
| 48 | 1 1/4 | 4 | 7 | 10 7/8 | 16 3/8 | 31 5/8 | 37 1/8 | 41 | 44 | 46 3/4 | ||||||||
| 1163 | 466 | |||||||||||||||||
| 11223.9982 | 12232 | |||||||||||||||||
| Max VAV only |
Page &P of &N
TRAVERSE POINT LAYOUT
6 7 8 9 10 1 2 3 4 5
Ret Fan 4 AIR APPARATUS
| AIR APPARATUS TEST REPORT | |||||||||||||
| BASE | W/O# | ||||||||||||
| SYSTEM | Return Fan 4 | BUILDING | DATE | NAME | |||||||||
| TYPE EQUIPMENT | AHU | SUPPLY FAN | EXHAUST | RETURN | |||||||||
| TYPE OF SYSTEM | CV | VAV | MULITZONE | DUAL DUCT | REHEAT | ||||||||
| FAN DATA | MOTOR DATA | ||||||||||||
| MANUFACTURER | Trane | MANUFACTURER | Baldor | ||||||||||
| MODEL NUMBER | OFNA4491 | MODEL NUMBER | EM3311T-G | ||||||||||
| WHEEL TYPE | AIR FOIL | FORWARD CURVE | NAME PLATE HORSE POWER | 7 1/2 | NAME PLATE RPMS | 1770 | |||||||
| BACKWARDS INCLINE | OTHER | EFFICIENCY | 91 | POWER FACTOR | 79 | ||||||||
| BELT SIZE | B-98 | SHAFT SIZE | 1 11/16 | SHAFT SIZE | 1 3/8 | AS FOUND | FINAL | ||||||
| PULLEY FAN OD | 11 3/8 | MOTOR OD | 4 7/8 | RPM | |||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | 37 1/2 | BHP | |||||||||||
| FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT | |||||||||||||
| DESIGN | AS FOUND | FINAL | DESIGN | ACTUAL | FINAL | ||||||||
| FAN CFM | 24000 | VOLTAGE A-B | 460 | ||||||||||
| FAN RPM | 845 | VOLTAGE B-C | |||||||||||
| DISCHARGE S.P. | VOLTAGE C-A | ||||||||||||
| EXTERNAL S.P. | AMPERAGE A | 9.7 | |||||||||||
| REMARKS | AMPERAGE B | ||||||||||||
| Loose belt | AMPERAGE C | ||||||||||||
| AIR VOLUMES | |||||||||||||
| DESIGN | AS FOUND | FINAL | |||||||||||
| MAX | MIN | MAX | MIN | MAX | MIN | ||||||||
| O/A CFM | |||||||||||||
| R/A | S/A | AFTER CC/A | R/A CFM | ||||||||||
| O/A TEMP | R/A TEMP | M/A TEMP | |||||||||||
| STATIC PRESSURE DROPS | |||||||||||||
| COIL NAME AND DESIGN S.P. DROP | AS FOUND | FINAL | AS FOUND | FINAL | AS FOUND | FINAL |
Page &P of &N x
AHU 4 VAV (1)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-30 | 0.56 | 0.64 | 680 | 270 | 791 | 116% | 392 | 145% | 692 | 102% | 289 | 107% | 696 | 102% | 289 | 107% | |||||
| 1 | 340 | 136 | 380 | 111.8% | 198 | 145.6% | 345 | 101.5% | 147 | 108.1% | 349 | 102.6% | 147 | 108.1% | |||||||
| 2 | 340 | 136 | 411 | 120.9% | 194 | 142.6% | 347 | 102.1% | 142 | 104.4% | 347 | 102.1% | 142 | 104.4% | |||||||
| VAV 4-39 | 0.65 | 0.66 | 800 | 320 | 635 | 79% | 773 | 97% | 773 | 97% | 354 | 111% | |||||||||
| 2412 | 1 | 400 | 160 | 347 | 86.8% | 420 | 105.0% | 420 | 105.0% | 165 | 103.1% | ||||||||||
| 2412 | 2 | 400 | 160 | 288 | 72.0% | 353 | 88.3% | 353 | 88.3% | 189 | 118.1% | ||||||||||
| There is a third diffuser in the space that was not part of the original design. It was delivering 35 cfm. | |||||||||||||||||||||
| VAV 4-18 | 0.6 | 0.62 | 635 | 254 | 672 | 106% | 355 | 140% | 0 | 0% | 0 | 0.0% | 672 | 106% | 305 | 120% | |||||
| 2408 | 1 | 200 | 80 | 211 | 105.5% | 113 | 141.3% | 0.0% | 0.0% | 211 | 105.5% | 96 | 120.0% | ||||||||
| Hall | 2 | 175 | 70 | 181 | 103.4% | 95 | 135.7% | 0.0% | 0.0% | 181 | 103.4% | 82 | 117.1% | ||||||||
| 2412 | 3 | 260 | 104 | 280 | 107.7% | 147 | 141.3% | 0.0% | 0.0% | 280 | 107.7% | 127 | 122.1% | ||||||||
| VAV 4-22 | 0.64 | 0.93 | 1620 | 648 | 866 | 53.5% | 0 | 0% | 1736 | 107% | 0 | 0% | 1615 | 100% | 673 | 104% | |||||
| 2400b | 1 | 405 | 162 | 212 | 52.3% | 0.0% | 380 | 93.8% | 0.0% | 355 | 87.7% | 149 | 92.0% | ||||||||
| 2400b | 2 | 405 | 162 | 195 | 48.1% | 0.0% | 533 | 131.6% | 0.0% | 485 | 119.8% | 209 | 129.0% | ||||||||
| 2400b | 3 | 405 | 162 | 223 | 55.1% | 0.0% | 388 | 95.8% | 0.0% | 376 | 92.8% | 150 | 92.6% | ||||||||
| 2400b | 4 | 405 | 162 | 236 | 58.3% | 0.0% | 435 | 107.4% | 0.0% | 399 | 98.5% | 165 | 101.9% | ||||||||
| Reheat coil was blocked by duct insulation | |||||||||||||||||||||
| VAV 4-20 | 0.69 | 0.57 | 280 | 110 | 264 | 94% | 0 | 0% | 0 | 0% | 0 | 0% | 277 | 99% | 112 | 102% | |||||
| 2409 | 1 | 280 | 110 | 264 | 94.3% | 0.0% | 0.0% | 0.0% | 277 | 98.9% | 112 | 101.8% |
Page &P of &N
AHU 4 VAV (2)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-17 | 0.54 | 1.01 | 1801 | 502 | 2147 | 119% | 614 | 122% | 1959 | 109% | 495 | 99% | 1847 | 103% | 495 | 99% | |||||
| 2411 | 1 | 417 | 116 | 520 | 124.7% | 147 | 126.7% | 462 | 110.8% | 120 | 103.4% | 437 | 104.8% | 120 | 103.4% | ||||||
| 2411 | 2 | 417 | 116 | 370 | 88.7% | 107 | 92.2% | 347 | 83.2% | 86 | 74.1% | 329 | 78.9% | 86 | 74.1% | ||||||
| 2411 | 3 | 417 | 116 | 560 | 134.3% | 159 | 137.1% | 509 | 122.1% | 125 | 107.8% | 484 | 116.1% | 125 | 107.8% | ||||||
| 2411 | 4 | 275 | 77 | 345 | 125.5% | 103 | 133.8% | 328 | 119.3% | 82 | 106.5% | 304 | 110.5% | 82 | 106.5% | ||||||
| 2411 | 5 | 275 | 77 | 352 | 128.0% | 98 | 127.3% | 313 | 113.8% | 82 | 106.5% | 293 | 106.5% | 82 | 106.5% | ||||||
| Changed max from 2097 to 1800 cfm to allow proper balancing. Found minimum at 500 cfm. Left at this value. Room does not require 850 cfm at minimum. | |||||||||||||||||||||
| VAV 4-21 | 0.35 | 0.32 | 335 | 135 | 309 | 92% | 0% | 322 | 96% | 133 | 99% | ||||||||||
| 2412 | 1 | 335 | 135 | 309 | 92.2% | 0.0% | 322 | 96.1% | 133 | 98.5% | |||||||||||
| VAV 4-23 | 0.67 | 0.6 | 1050 | 420 | 956 | 91% | 373 | 89% | 0 | 0% | 0 | 0.0% | 1047 | 100% | 428 | 102% | |||||
| 2408 | 1 | 365 | 146 | 343 | 94.0% | 133 | 91.1% | 0.0% | 0.0% | 368 | 100.8% | 153 | 104.8% | ||||||||
| Hall | 2 | 365 | 146 | 332 | 91.0% | 127 | 87.0% | 0.0% | 0.0% | 379 | 103.8% | 153 | 104.8% | ||||||||
| 2412 | 3 | 320 | 128 | 281 | 87.8% | 113 | 88.3% | 0.0% | 0.0% | 300 | 93.8% | 122 | 95.3% | ||||||||
| VAV 4-24 | 455 | 182 | 387 | 85.1% | 184 | 101% | 481 | 106% | 0 | 0% | 481 | 106% | 188 | 103% | |||||||
| 2400b | 1 | 265 | 106 | 231 | 87.2% | 110 | 103.8% | 286 | 107.9% | 0.0% | 286 | 107.9% | 112 | 105.7% | |||||||
| 2400b | 2 | 190 | 76 | 156 | 82.1% | 74 | 97.4% | 195 | 102.6% | 0.0% | 195 | 102.6% | 76 | 100.0% |
Page &P of &N
AHU 4 VAV (3)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-19 | 0.77 | 0.7 | 1365 | 545 | 1266 | 93% | 538 | 99% | 1332 | 98% | 0 | 0% | 2299 | 168% | 538 | 99% | |||||
| 2400b | 1 | 250 | 100 | 239 | 95.6% | 98 | 98.0% | 251 | 100.4% | 0.0% | 472 | 188.8% | 98 | 98.0% | |||||||
| 2400b | 2 | 250 | 100 | 227 | 90.8% | 95 | 95.0% | 245 | 98.0% | 0.0% | 328 | 131.2% | 95 | 95.0% | |||||||
| 2400b | 3 | 250 | 100 | 215 | 86.0% | 97 | 97.0% | 252 | 100.8% | 0.0% | 515 | 206.0% | 97 | 97.0% | |||||||
| 2400b | 4 | 250 | 100 | 241 | 96.4% | 104 | 104.0% | 229 | 91.6% | 0.0% | 336 | 134.4% | 104 | 104.0% | |||||||
| 2400b | 5 | 250 | 100 | 233 | 93.2% | 99 | 99.0% | 241 | 96.4% | 0.0% | 324 | 129.6% | 99 | 99.0% | |||||||
| 2400b | 6 | 115 | 46 | 111 | 96.5% | 45 | 97.8% | 114 | 99.1% | 0.0% | 324 | 281.7% | 45 | 97.8% | |||||||
| VAV 4-25 | 0.72 | 0.8 | 475 | 150 | 490 | 103% | 136 | 91% | 0% | 322 | 68% | 133 | 89% | ||||||||
| 2402 | 1 | 225 | 75 | 214 | 95.1% | 58 | 77.3% | 0.0% | 322 | 143.1% | 133 | 177.3% | |||||||||
| 2402 | 2 | 250 | 75 | 276 | 110.4% | 78 | 104.0% | 0.0% | 322 | 128.8% | 133 | 177.3% | |||||||||
| Design max air flow was 375 cfm. Increased to 475 cfm (HVAC request) to help satisify the room during cooling mode. Box is at 100% damper | |||||||||||||||||||||
| VAV 4-26 | 0.54 | 0.25 | 440 | 215 | 389 | 88% | 0 | 0% | 0 | 0% | 0 | 0.0% | 449 | 102% | 203 | 94% | |||||
| 2401 | 1 | 250 | 122 | 213 | 85.2% | 0.0% | 0.0% | 0.0% | 242 | 96.8% | 113 | 92.6% | |||||||||
| 2401 | 2 | 190 | 93 | 176 | 92.6% | 0.0% | 0.0% | 0.0% | 207 | 108.9% | 90 | 96.8% | |||||||||
| VAV 4-27 | 0.64 | 0.57 | 595 | 203 | 625 | 105% | 201 | 99% | 590 | 99% | 0 | 0% | 625 | 105% | 201 | 99% | |||||
| 2403 | 1 | 320 | 109 | 333 | 104.1% | 106 | 97.2% | 313 | 97.8% | 0.0% | 333 | 104.1% | 106 | 97.2% | |||||||
| 2403 | 2 | 275 | 94 | 292 | 106.2% | 95 | 101.1% | 277 | 100.7% | 0.0% | 292 | 106.2% | 95 | 101.1% | |||||||
| VAV 4-28 | 0.64 | 0.53 | 930 | 372 | 896 | 96% | 0 | 0% | 0 | 0% | 0 | 0% | 923 | 99% | 354 | 95% | |||||
| 2400 | 1 | 370 | 148 | 355 | 95.9% | 0.0% | 0.0% | 0.0% | 373 | 100.8% | 140 | 94.6% | |||||||||
| 2400 | 2 | 370 | 148 | 362 | 97.8% | 0.0% | 0.0% | 0.0% | 370 | 100.0% | 145 | 98.0% | |||||||||
| 2400 | 3 | 190 | 76 | 179 | 94.2% | 0.0% | 0.0% | 0.0% | 180 | 94.7% | 69 | 90.8% |
Page &P of &N
AHU 4 VAV (4)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-29 | 0.54 | 0.48 | 1205 | 482 | 1080 | 90% | 0 | 0% | 1173 | 97% | 0 | 0% | 1173 | 97% | 501 | 104% | |||||
| 2400a | 1 | 280 | 112 | 275 | 98.2% | 0.0% | 320 | 114.3% | 0.0% | 320 | 114.3% | 130 | 116.1% | ||||||||
| 2400a | 2 | 325 | 130 | 295 | 90.8% | 0.0% | 302 | 92.9% | 0.0% | 302 | 92.9% | 135 | 103.8% | ||||||||
| 2400a | 3 | 300 | 120 | 259 | 86.3% | 0.0% | 271 | 90.3% | 0.0% | 271 | 90.3% | 119 | 99.2% | ||||||||
| 2400a | 4 | 300 | 120 | 251 | 83.7% | 0.0% | 280 | 93.3% | 0.0% | 280 | 93.3% | 117 | 97.5% | ||||||||
| VAV 4-31 | 0.55 | 0.53 | 1870 | 748 | 1887 | 101% | 746 | 100% | 0 | 0% | 0 | 0.0% | 1887 | 101% | 746 | 100% | |||||
| Corridor | 1 | 0 | 0 | 0 | 0.0% | 0 | 0.0% | 0.0% | 0.0% | 0 | 0.0% | 0 | 0.0% | ||||||||
| Corridor | 2 | 210 | 84 | 217 | 103.3% | 72 | 85.7% | 0.0% | 0.0% | 217 | 103.3% | 72 | 85.7% | ||||||||
| Corridor | 3 | 210 | 84 | 213 | 101.4% | 77 | 91.7% | 0.0% | 0.0% | 213 | 101.4% | 77 | 91.7% | ||||||||
| Corridor | 4 | 210 | 84 | 217 | 103.3% | 77 | 91.7% | 0.0% | 0.0% | 217 | 103.3% | 77 | 91.7% | ||||||||
| Corridor | 5 | 210 | 84 | 217 | 103.3% | 82 | 97.6% | 0.0% | 0.0% | 217 | 103.3% | 82 | 97.6% | ||||||||
| Corridor | 6 | 210 | 84 | 205 | 97.6% | 77 | 91.7% | 0.0% | 0.0% | 205 | 97.6% | 77 | 91.7% | ||||||||
| Corridor | 7 | 210 | 84 | 204 | 97.1% | 78 | 92.9% | 0.0% | 0.0% | 204 | 97.1% | 78 | 92.9% | ||||||||
| Corridor | 8 | 210 | 84 | 199 | 94.8% | 83 | 98.8% | 0.0% | 0.0% | 199 | 94.8% | 83 | 98.8% | ||||||||
| Ladies | 9 | 200 | 80 | 210 | 105.0% | 95 | 118.8% | 0.0% | 0.0% | 210 | 105.0% | 95 | 118.8% | ||||||||
| Mens | 10 | 200 | 80 | 205 | 102.5% | 105 | 131.3% | 0.0% | 0.0% | 205 | 102.5% | 105 | 131.3% | ||||||||
| Diffuser 1 was never connected due to a beam in the area. Air flow max was found at 1870 by original balancer (???) left at this value | |||||||||||||||||||||
| VAV 4-32 | 0.55 | 0.73 | 300 | 120 | 361 | 120% | 140 | 117% | 0 | 0% | 150 | 125% | 305 | 102% | 142 | 118% | |||||
| 2313 | 1 | 300 | 120 | 361 | 120.3% | 140 | 116.7% | 0.0% | 150 | 125.0% | 305 | 101.7% | 142 | 118.3% | |||||||
| Damper closed to 6% open and airflow at 142 cfm, box will not zero or calibrate correctly | |||||||||||||||||||||
| VAV 4-33 | 0.8 | 0.6 | 270 | 108 | 818 | 303% | 0 | 0% | 0 | 0% | 0 | 0% | 568 | 210% | 300 | 278% | |||||
| 2308 | 1 | 270 | 108 | 250 | 92.6% | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | |||||||||||
| VAV 4-34 | 0.85 | 0.73 | 300 | 120 | 284 | 95% | 0 | 0% | 0 | 0% | 0 | 0% | 284 | 95% | 150 | 125% | |||||
| 2306 | 1 | 300 | 120 | 284 | 94.7% | 0.0% | 0.0% | 0.0% | 284 | 94.7% | 150 | 125.0% | |||||||||
| Minimum air flow will not calibrate properly nd box will not zero. Possible controller issue. Found flow tubes off as well. |
Page &P of &N
AHU 4 VAV (5)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-37 | 0.56 | 0.45 | 725 | 290 | 593 | 82% | 0 | 0% | 666 | 92% | 0 | 0% | 684 | 94% | 277 | 96% | |||||
| 2311 | 1 | 160 | 64 | 118 | 73.8% | 0.0% | 138 | 86.3% | 0.0% | 141 | 88.1% | 48 | 75.0% | ||||||||
| 2311 | 2 | 160 | 64 | 76 | 47.5% | 0.0% | 84 | 52.5% | 0.0% | 128 | 80.0% | 56 | 87.5% | ||||||||
| 2309 | 3 | 135 | 54 | 129 | 95.6% | 0.0% | 144 | 106.7% | 0.0% | 135 | 100.0% | 57 | 105.6% | ||||||||
| 2305 | 4 | 135 | 54 | 135 | 100.0% | 0.0% | 150 | 111.1% | 0.0% | 140 | 103.7% | 58 | 107.4% | ||||||||
| 2303 | 5 | 135 | 54 | 135 | 100.0% | 0.0% | 150 | 111.1% | 0.0% | 140 | 103.7% | 58 | 107.4% | ||||||||
| Box is at 100% | |||||||||||||||||||||
| VAV 4-36 | 0.54 | 0.47 | 410 | 164 | 677 | 165% | 214 | 130% | 267 | 65% | 210 | 128% | 397 | 97% | 178 | 109% | |||||
| 2300 | 1 | 205 | 82 | 329 | 160.5% | 105 | 128.0% | 131 | 63.9% | 102 | 124.4% | 197 | 96.1% | 87 | 106.1% | ||||||
| 2300 | 2 | 205 | 82 | 348 | 169.8% | 109 | 132.9% | 136 | 66.3% | 108 | 131.7% | 200 | 97.6% | 91 | 111.0% | ||||||
| Corrected VAV size from 6" to 8" | |||||||||||||||||||||
| VAV 4-38 | 0.54 | 0.68 | 255 | 102 | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | |||||
| 2301 | 1 | 255 | 102 | 0 | 0.0% | 0 | 0.0% | 0 | 0.0% | 0 | 0.0% | 0 | 0.0% | 0 | 0.0% | ||||||
| Unable to calibrate possible controller issue | |||||||||||||||||||||
| VAV 4-35 | 0.55 | 0.56 | 1380 | 552 | 1445 | 105% | 499 | 90% | 0 | 0% | 0 | 0% | 1445 | 105% | 511 | 93% | |||||
| Corridor | 1 | 230 | 92 | 236 | 102.6% | 82 | 89.1% | 0.0% | 0.0% | 236 | 102.6% | 85 | 92.4% | ||||||||
| Corridor | 2 | 230 | 92 | 237 | 103.0% | 83 | 90.2% | 0.0% | 0.0% | 237 | 103.0% | 85 | 92.4% | ||||||||
| Corridor | 3 | 230 | 92 | 244 | 106.1% | 86 | 93.5% | 0.0% | 0.0% | 244 | 106.1% | 88 | 95.7% | ||||||||
| Corridor | 4 | 230 | 92 | 240 | 104.3% | 81 | 88.0% | 0.0% | 0.0% | 240 | 104.3% | 85 | 92.4% | ||||||||
| Corridor | 5 | 230 | 92 | 244 | 106.1% | 85 | 92.4% | 0.0% | 0.0% | 244 | 106.1% | 81 | 88.0% | ||||||||
| Corridor | 6 | 230 | 92 | 244 | 106.1% | 82 | 89.1% | 0.0% | 0.0% | 244 | 106.1% | 87 | 94.6% |
Page &P of &N
AHU 4 VAV (6)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-1 | 0.72 | 1160 | 464 | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | ||||||
| 1405 | 1 | 580 | 232 | 0 | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | |||||||||||
| 1405 | 2 | 580 | 232 | 0 | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | |||||||||||
| Damper motor not working | |||||||||||||||||||||
| VAV 4-2 | 0.64 | 0.6 | 1130 | 452 | 1063 | 94% | 453 | 100% | 0 | 0% | 0 | 0.0% | 1129 | 100% | 453 | 100% | |||||
| 1401 | 1 | 320 | 128 | 318 | 99.4% | 132 | 103.1% | 0.0% | 0.0% | 329 | 102.8% | 132 | 103.1% | ||||||||
| 1400a | 2 | 270 | 108 | 249 | 92.2% | 111 | 102.8% | 0.0% | 0.0% | 284 | 105.2% | 111 | 102.8% | ||||||||
| 1400a | 3 | 270 | 108 | 246 | 91.1% | 104 | 96.3% | 0.0% | 0.0% | 255 | 94.4% | 104 | 96.3% | ||||||||
| 1400a | 4 | 270 | 108 | 250 | 92.6% | 106 | 98.1% | 0.0% | 0.0% | 261 | 96.7% | 106 | 98.1% | ||||||||
| VAV 4-3 | 0.92 | 0.91 | 1615 | 646 | 1790 | 111% | 655 | 101% | 1645 | 102% | 0 | 0.0% | 1645 | 102% | 0 | 0% | |||||
| 1403 | 1 | 55 | 22 | 70 | 127.3% | 25 | 113.6% | 55 | 100.0% | 0.0% | 55 | 100.0% | 0.0% | ||||||||
| 1400a | 2 | 520 | 208 | 600 | 115.4% | 220 | 105.8% | 560 | 107.7% | 0.0% | 560 | 107.7% | 0.0% | ||||||||
| 1400a | 3 | 520 | 208 | 620 | 119.2% | 225 | 108.2% | 560 | 107.7% | 0.0% | 560 | 107.7% | 0.0% | ||||||||
| 1400a | 4 | 520 | 208 | 500 | 96.2% | 185 | 88.9% | 470 | 90.4% | 0.0% | 470 | 90.4% | 0.0% | ||||||||
| VAV 4-4 | 0.33 | 0.42 | 725 | 290 | 723 | 99.7% | 315 | 109% | 0 | 0% | 0 | 0% | 723 | 100% | 315 | 109% | |||||
| 1404 | 1 | 190 | 76 | 191 | 100.5% | 90 | 118.4% | 0.0% | 0.0% | 191 | 100.5% | 90 | 118.4% | ||||||||
| Corridor | 2 | 365 | 146 | 360 | 98.6% | 150 | 102.7% | 0.0% | 0.0% | 360 | 98.6% | 150 | 102.7% | ||||||||
| 1402 | 3 | 170 | 68 | 172 | 101.2% | 75 | 110.3% | 0.0% | 0.0% | 172 | 101.2% | 75 | 110.3% | ||||||||
| VAV 4-7 | 0.62 | 0.59 | 620 | 248 | 610 | 98% | 237 | 96% | 0 | 0% | 0 | 0% | 0 | 0% | 237 | 96% | |||||
| 2409 | 1 | 310 | 124 | 330 | 106.5% | 115 | 92.7% | 0.0% | 0.0% | 0.0% | 115 | 92.7% | |||||||||
| 2409 | 1 | 310 | 124 | 280 | 90.3% | 122 | 98.4% | 0.0% | 0.0% | 0.0% | 122 | 98.4% |
Page &P of &N
AHU 4 VAV (7)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-5 | 2160 | 864 | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | 0 | 0% | |||||||
| 1400a | 1 | 540 | 216 | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | ||||||||||||
| 1400a | 2 | 540 | 216 | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | ||||||||||||
| 1400a | 3 | 540 | 216 | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | ||||||||||||
| 1400a | 4 | 540 | 216 | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | 0.0% | ||||||||||||
| Unable to measure due to furniture and customers | |||||||||||||||||||||
| VAV 4-6 | 0.51 | 0.49 | 1400 | 560 | 1320 | 94% | 553 | 99% | 1378 | 98% | 0 | 0.0% | 1378 | 98% | 553 | 99% | |||||
| 1400 | 1 | 320 | 128 | 302 | 94.4% | 130 | 101.6% | 326 | 101.9% | 0.0% | 326 | 101.9% | 130 | 101.6% | |||||||
| 1400a | 2 | 270 | 108 | 276 | 102.2% | 113 | 104.6% | 281 | 104.1% | 0.0% | 281 | 104.1% | 113 | 104.6% | |||||||
| 1400a | 3 | 270 | 108 | 248 | 91.9% | 104 | 96.3% | 262 | 97.0% | 0.0% | 262 | 97.0% | 104 | 96.3% | |||||||
| 1400a | 4 | 270 | 108 | 245 | 90.7% | 102 | 94.4% | 250 | 92.6% | 0.0% | 250 | 92.6% | 102 | 94.4% | |||||||
| 1400a | 4 | 270 | 108 | 249 | 92.2% | 104 | 96.3% | 259 | 95.9% | 0.0% | 259 | 95.9% | 104 | 96.3% | |||||||
| VAV 4-8 | 0.67 | 2060 | 824 | 986 | 48% | 762 | 92% | 2070 | 100% | 0 | 0.0% | 2038 | 99% | 793 | 96% | ||||||
| 1303 | 1 | 300 | 120 | 31 | 10.3% | 114 | 95.0% | 264 | 88.0% | 0.0% | 301 | 100.3% | 116 | 96.7% | |||||||
| 1303 | 2 | 300 | 120 | 176 | 58.7% | 117 | 97.5% | 240 | 80.0% | 0.0% | 306 | 102.0% | 124 | 103.3% | |||||||
| 1303 | 3 | 215 | 86 | 23 | 10.7% | 82 | 95.3% | 262 | 121.9% | 0.0% | 210 | 97.7% | 81 | 94.2% | |||||||
| 1303 | 4 | 300 | 120 | 164 | 54.7% | 103 | 85.8% | 243 | 81.0% | 0.0% | 281 | 93.7% | 107 | 89.2% | |||||||
| 1303 | 5 | 215 | 86 | 19 | 8.8% | 76 | 88.4% | 297 | 138.1% | 0.0% | 215 | 100.0% | 80 | 93.0% | |||||||
| 1303 | 6 | 215 | 86 | 140 | 65.1% | 78 | 90.7% | 185 | 86.0% | 0.0% | 213 | 99.1% | 82 | 95.3% | |||||||
| 1303 | 7 | 300 | 120 | 190 | 63.3% | 103 | 85.8% | 266 | 88.7% | 0.0% | 282 | 94.0% | 108 | 90.0% | |||||||
| 1303 | 8 | 215 | 86 | 243 | 113.0% | 89 | 103.5% | 313 | 145.6% | 0.0% | 230 | 107.0% | 95 | 110.5% | |||||||
| Found box with 1197 max and 199 min should be 2060 and 824. Changed to correct values | |||||||||||||||||||||
| VAV 4-9 | 0.54 | 0.69 | 610 | 244 | 544 | 89% | 383 | 157% | 752 | 123% | 311 | 127% | 630 | 103% | 253 | 104% | |||||
| Wait | 1 | 305 | 122 | 268 | 87.9% | 186 | 152.5% | 395 | 129.5% | 151 | 123.8% | 327 | 107.2% | 132 | 108.2% | ||||||
| Wait | 1 | 305 | 122 | 276 | 90.5% | 197 | 161.5% | 357 | 117.0% | 160 | 131.1% | 303 | 99.3% | 121 | 99.2% | ||||||
| Reset VAV … corrected duct size from 10" to 8" heating valve actuator broken |
Page &P of &N
AHU 4 VAV (8)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-10 | 0.56 | 0.45 | 190 | 75 | 189 | 99% | 79 | 105% | 0 | 0% | 0 | 0% | 189 | 99% | 79 | 105% | |||||
| 1302 | 1 | 100 | 40 | 102 | 102.0% | 44 | 110.0% | 0.0% | 0.0% | 102 | 102.0% | 44 | 110.0% | ||||||||
| 1304 | 2 | 90 | 36 | 87 | 96.7% | 35 | 97.2% | 0.0% | 0.0% | 87 | 96.7% | 35 | 97.2% | ||||||||
| Not zeroed check mode | |||||||||||||||||||||
| VAV 4-11 | 0.55 | 0.66 | 375 | 150 | 442 | 118% | 0 | 0% | 392 | 105% | 0 | 0% | 392 | 105% | 0 | 0% | |||||
| 1300 | 1 | 375 | 150 | 442 | 117.9% | 392 | 104.5% | 392 | 104.5% | 0.0% | |||||||||||
| minimum air flow was measured at 242 cfm when the program shows the damper at zero. Box sees 144 cfm cannot calibrate until damper is allowed to close fully | |||||||||||||||||||||
| VAV 4-12 | 0.77 | 0.63 | 630 | 252 | 599 | 95% | 210 | 83% | 0 | 0% | 210 | 83.3% | 599 | 95% | 270 | 107% | |||||
| Corridor | 1 | 105 | 42 | 118 | 112.4% | 44 | 104.8% | 0.0% | 39 | 92.9% | 118 | 112.4% | 54 | 128.6% | |||||||
| Corridor | 2 | 105 | 42 | 107 | 101.9% | 42 | 100.0% | 0.0% | 43 | 102.4% | 107 | 101.9% | 43 | 102.4% | |||||||
| Corridor | 3 | 105 | 42 | 91 | 86.7% | 27 | 64.3% | 0.0% | 35 | 83.3% | 91 | 86.7% | 43 | 102.4% | |||||||
| Corridor | 4 | 105 | 42 | 90 | 85.7% | 31 | 73.8% | 0.0% | 27 | 64.3% | 90 | 85.7% | 42 | 100.0% | |||||||
| Corridor | 5 | 105 | 42 | 96 | 91.4% | 31 | 73.8% | 0.0% | 35 | 83.3% | 96 | 91.4% | 42 | 100.0% | |||||||
| Corridor | 6 | 105 | 42 | 97 | 92.4% | 35 | 83.3% | 0.0% | 31 | 73.8% | 97 | 92.4% | 46 | 109.5% | |||||||
| (Check mode) Minimum air flow was measured at 210 cfm when the program shows the damper at zero. | |||||||||||||||||||||
| VAV 4-13 | 0.71 | 0.64 | 1800 | 720 | 1606 | 89.2% | 635 | 88% | 0 | 0% | 0 | 0% | 1855 | 103% | 718 | 100% | |||||
| Break | 1 | 325 | 130 | 281 | 86.5% | 110 | 84.6% | 0.0% | 0.0% | 319 | 98.2% | 127 | 97.7% | ||||||||
| Break | 2 | 325 | 130 | 291 | 89.5% | 113 | 86.9% | 0.0% | 0.0% | 334 | 102.8% | 130 | 100.0% | ||||||||
| Break | 3 | 325 | 130 | 286 | 88.0% | 111 | 85.4% | 0.0% | 0.0% | 335 | 103.1% | 130 | 100.0% | ||||||||
| Break | 4 | 325 | 130 | 286 | 88.0% | 111 | 85.4% | 0.0% | 0.0% | 335 | 103.1% | 129 | 99.2% | ||||||||
| Bath Ent | 5 | 100 | 40 | 100 | 100.0% | 36 | 90.0% | 0.0% | 0.0% | 119 | 119.0% | 43 | 107.5% | ||||||||
| Ladies | 6 | 200 | 80 | 181 | 90.5% | 77 | 96.3% | 0.0% | 0.0% | 208 | 104.0% | 78 | 97.5% | ||||||||
| Mens | 7 | 200 | 80 | 181 | 90.5% | 77 | 96.3% | 0.0% | 0.0% | 205 | 102.5% | 81 | 101.3% | ||||||||
| Locked up after attempt to balance |
Page &P of &N
AHU 4 VAV (9)
| VAV Diffuser and Grill Test Data | |||||||||||||||||||||
| BASE | LOCATION | WORK ORDER | 0 | ||||||||||||||||||
| SYSTEM | AHU 4 | TESTED BY | DATE | ||||||||||||||||||
| ROOM T-STAT | K factor | AIR VOLUMES | |||||||||||||||||||
| Room | VAV Diff | TEMP S.P. | TEMP ACT | P/V. Out | AS FOUND | FINAL | DESIGN CFM | AS FOUND CFM | TEST #1 | FINAL AIR VOLUMES | ROOM TEMP | ||||||||||
| MAX | MIN | MAX | % | MIN | % | MAX | % | MIN | % | MAX | % | MIN | % | ||||||||
| VAV 4-14 | 0.54 | 0.85 | 1360 | 544 | 1740 | 128% | 598 | 110% | 0 | 0% | 0 | 0% | 1406 | 103% | 598 | 110% | |||||
| Corridor | 1 | 170 | 68 | 199 | 117.1% | 55 | 80.9% | 0.0% | 0.0% | 149 | 87.6% | 55 | 80.9% |
This is the start of the file's text. The full file is on GovTribe.