AJT_-_400A_to_200A.pdf
PDF 79 KB Posted
- Attached to
- Theater Lighting Renovations
- Solicitation number
- 26-CD-020
- Issued by
- Pinellas County, Florida
About this file
This file contains a product specification document for EP.MERSEN AJT Reducer Fuses related to the Pinellas County School District's Theater Lighting Renovations project in Florida. The document outlines technical specifications for Class J time-delay power fuses designed to reduce current ratings without requiring temporary fuse reducer accessories. The fuses are available in amperage ratings from 125 to 400 amperes, with voltage ratings up to 600VAC and 500VDC, and are intended for applications including motor circuits, feeders, branch circuits, lighting, heating, transformers, control panels, and bus ducts. The specification document includes detailed dimensional information, catalog numbers for both single-pole and three-pole configurations, and recommended fuse block options. The Pinellas County School District is soliciting sealed electronic bids for the Theater Lighting Renovations project with a submission deadline of 4:00 p.m. on Friday, May 15, 2026, via the District's e-Procurement Portal.
The fuses specified are UL and CSA listed to standard 248-8 and IEC 269-2-1, featuring arc flash mitigation capabilities, high current-limiting properties, and optional mechanical indicators. Key product benefits include dimensional stability through fiberglass construction, fast arc quenching via high-grade silica filler, and metal-embossed identification for traceability. Catalog numbers are provided for amperage ratings ranging from 125/400A through 400/600A, with specific pole configurations available. Interested bidders are strongly encouraged to register and download bid documents through the OpenGov Procurement Portal at https://procurement.opengov.com/portal/pcsb to receive automatic notifications of any addenda or updates.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EP.MERSEN.COMPF 3
P F
R AT I N G S :
Volts: 600VAC, 500VDC
Amps: 125 to 200A (in 400A body), 250 to 400A (in 600A body)
IR: 200kA I.R. AC, 100kA I.R. DC (Self-certified for 600VAC, 300kA I.R., UL witnessed).
A P P L I C AT I O N S :
• Motor circuits
• Mains
• Feeders
• Branch circuits
• Lighting, heating & general loads
• Transformers
• Control panels
• Circuit breaker back-up
• Bus duct
• Load centers
Note: See motor fuse applications tables for additional information
A P P R OVA L S :
AJT (1-600):
• UL Listed to standard
248-8 File E2137
• IEC 269-2-1
AJT Reducer Fuses are a safe permanent solution for decreasing your current rating without using a Fuse Reducer accessory, which is designed for temporary use only. These special purpose UL Listed reduced rating Class J fuses provide the same trusted protection levels as a traditional AJT fuses, but in a larger body.
F E AT U R E S / B E N E F I T S :
• Replaces traditional temporary-use only Fuse Reducer accessories
• Recommended for Arc Flash energy reduction
• Extremely current-limiting for low peak let-thru current
• Most current-limiting UL class fuse
• Time-delay for motor starting and transformer inrush
• High-visibility orange label gives instant brand recognition
• Metal-embossed date and catalog number for traceability and lasting identification
• Fiberglass body provides dimensional stability in harsh industrial settings
• High-grade silica filler ensures fast arc quenching
• �Optional EI indicator/switch
H I G H L I G H T S :
• Class J Reduced Rating
• Arc Flash mitigating
• Highly current-limiting
• Time-delay
• DC ratings
• Optional mechanical indicator
AJT Reducer Fuses Time Delay/Class J
UL/CSA L ISTED POWER FUSES
DECREASE YOUR CURRENT RATING WITHOUT
USING A FUSE REDUCER
PF 18
EP.MERSEN.COM PF 4
UL/CSA L ISTED
POWER FUSES
P F
C ATA LO G N U M B E R S ( A M P S ) R E C O M M E N D E D F U S E B LO C K S
W I T H B OX C O N N E C TO R S F O R
A M P -T R A P ® C L A S S J F U S E S
A variety of pole configurations and termination provisions are available.
Refer to Section FB for details.
70-600A
D I M E N S I O N S
Ampere Rating A B C D E F G H in mm in mm in mm in mm in mm in mm in mm in mm
125-200 7-1/8 181 2-1/8 54 1/4 6.3 1-5/8 41 1-7/8 48 5-1/4 133 17/32 14 13/32 10
250-400 8 203 2-1/2 64 3/8 9.5 2 51 2-1/8 54 6 152 11/16 18 17/32 13
Amp Rating/ Body Size
Catalog Number
600V or Less
1 Pole 3 Pole
125/400-200/400 64031J 64033J 250/600- 400/600 6631J 6633J
Catalog Numbers Amp Rating Body Size
AJT125/400 125A
400A
AJT150/400 150A
AJT175/400 175A
AJT200/400 200A
AJT250/600 250A
600A
AJT300/600 300A
AJT350/600 350A
AJT400/600 400A
CLASS J
Reducer Fuses
PF 19
File details come from the government source that posted it. Updated .