This is an AHERA (Asbestos Hazard Emergency Response Act) Three-Year Re-Inspection Data Summary document prepared by Baltimore City Public Schools (BCPS) with environmental compliance managed by Sheila R. Howard. The report documents asbestos-containing building material (ACBM) inspections conducted during Winter 2025 at five school facilities: Benjamin Franklin High School at Masonville Cove (PS239), Digital Harbor High School (PS416), Paul Laurence Dunbar High School (PS414), National Academy Foundation High School (PS421) at Dunbar Middle School Building #133, and National Academy Foundation Middle School (PS421M) at Building #102. Inspections were performed by EPA-accredited inspectors including Sharon Thompson, Michael Jackson, and Dylan Gomez-Starnes between February 25 and March 14, 2025. The inspections identified assumed and tested positive ACBM materials including pipe insulation, thermal systems insulation, fire doors, floor tiles, ceiling tiles, cove base, mastics, grout, and terrazzo throughout the facilities. Multiple homogeneous materials were categorized and assessed for friability status and damage conditions.

The report identifies 12 materials requiring Abatement Required (AR) response actions across the five schools, including cove base adhesive with exposed areas in Benjamin Franklin High School stairwells and hallways, damaged ceiling tiles in the gymnasium, black mastic in stairwells, white and beige floor tiles with damaged sections in hallways and various rooms, and terrazzo tile damage at Paul Laurence Dunbar High School. The majority of identified ACBM materials are classified as Assessment Category 5 (ACBM with potential for damage) requiring continued Operations and Maintenance (O&M) surveillance. All facilities have confirmed 3-year re-inspections and 6-month surveillance protocols in place. New suspect ACBM materials were identified at Benjamin Franklin High School (ceiling tile spline) and Paul Laurence Dunbar High School (brown glue dots), while no new suspect materials were identified at the other three facilities. Management plans were originally developed by VERSAR, Inc. in 1989, with subsequent reinspection reports from KAYCO Environmental, KCI Environmental, and BATTA Environmental conducted between 2004 and 2021.

View the file

Other files

File Type Posted
7CVERS~1.PDF PDF
Addendum #1.pdf PDF
Project Drawings.pdf PDF
7AVERS~1.PDF PDF
7EVERS~2.PDF PDF
5a. Package 4 Specs.pdf PDF
Solicitation Document.pdf PDF
7DVERS~1.PDF PDF
7BVERS~1.PDF PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AHERA Three (3) Year (Winter 2025) Re-Inspection Data Summary

Facility Name and Number: Benjamin Franklin High School at Masonville Cove PS239

Baltimore City Public Schools

LEA Point of Contact: Sheila R. Howard, Environmental Compliance Facility Name and Number: Benjamin Franklin High School at Masonville Cove PS239

2 Facility Address:

1201 Cambria Street

Baltimore, MD 21225

3 Date of Inspection: Monday, March 10, 2025

EPA Accredited Inspector(s): Name: Sharon Thompson Number: VAIMPR-01302025-04

Management Planner(s): Name: Sharon Thompson Number: VAIMPR-01302025-04

5A Information provided by BCPS to BATTA for Review:

• Management Plan by VERSAR, Inc., 1989 (Missing)

• Reinspection Report by KAYCO Environmental, 2004

• Reinspection Report by KAYCO Environmental, 2007

• Reinspection Report by KAYCO Environmental, 2010

• Reinspection Report by KAYCO Environmental, 2013

• Reinspection Report by KCI Environmental, 2016

• Reinspection Report by BATTA Environmental, 2019

• Reinspection Report by BATTA Environmental, 2021

• The presence of the 3-year re-inspection is confirmed

5B Comments and Issues:

• Cove base, cove base adhesive, ceramic tile grout, ceramic tile, terrazzo tile grout, terrazzo throughout the school are assumed ACBM.

• A portion of the school was recently renovated in approximately 2019

• The presence of the 6-month surveillance is confirmed

6 New suspect ACBM identified during Winter 2025 Re-Inspection

Homogeneous Material Description Location(s)

Sampling Information ACM? Samples Collected for HA

HA ID: M030 Type: Misc.

Throughout building A Detail:

Spline Ceiling tiles

HA ID: M031 Type: Misc.

Throughout building: A Detail:

Spline Ceiling tiles glue dots

7 Assessment of Friable and Non-friable Assumed Positive or Tested Positive Materials

Homogeneous Material Description Location(s) ACM Friable?

Assessment and Response Action- Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response

Action

Change in

Conditio n (Y/N)

If “Y”, Describe Change in Condition Prior Current Action Notes/Comments

HA ID: T005 Type: TSI

1950 addition Y F 5 5 O&M N Detail:

Supply Duct Insulation HA ID: M008 Type: Misc.

1950 attic Y NF 5 5 O&M N Detail:

Ductwork Flexible Connector HA ID: M009 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Fire Doors HA ID: M012 Type: Misc.

Throughout Y NF 5 5 O&M N Detail:

Original Floor Tile HA ID: M013 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Mastic associated with M012 Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Assessment and Response Action- Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response

Action

Change in

Conditio n (Y/N)

If “Y”, Describe Change in Condition Prior Current Action Notes/Comments

HA ID: T006 Type: TSI

Throughout Y NF 5 5 O&M N Detail:

Pipe Insulation HA ID: T007 Type: TSI

Throughout Y NF 5 5 O&M N Detail:

Pipe Fittings HA ID: M014 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Cove Base HA ID: M015 Type: Misc.

Throughout A NF 5 3 AR

Stairwell by

109 (50LF

exposed)

Hallway by

016 (35LF

exposed)

N Detail:

Cove Base Adhesive

HA ID: M016 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Ceramic Tile Grout Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response

Action Change in Condition

(Y/N)

If “Y”, Describe

Change in Condition Prior Current Action Notes/Comments

HA ID: M017 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Ceramic Tile HA ID: M018 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Terrazzo Tile Grout HA ID: M019 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Terrazzo Tile HA ID: M020 Type: Misc. Newer Portion –

Hallway, Guidance Office, Rooms 102, 104, 105, 107, 117

A NF 5 5 O&M Y Damage in 1st floor hall

Detail:

12”x12” Green Floor Tile

HA ID: M021 Type: Misc. Newer Portion – Hallway, Guidance Office, Rooms 102, 104, 105, 107

A NF 5 5 O&M Y Damage in 1st floor hall

Detail:

12”x12” Yellow Floor Tile

Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response

Action Change in Condition

(Y/N)

If “Y”, Describe

Change in Condition Prior Current Action Notes/Comments

HA ID: M022 Type: Misc. Newer Portion – Rooms 102, 104, 105, 109 A NF 5 5 O&M N Detail:

12”x12” Off-White Floor Tile/Mastic HA ID: M023 Type: Misc.

Newer Portion – Hallway, Rooms

104, 105, 109

12”x12” Dark Green Floor Tile/Mastic HA ID: M024 Type: Misc.

Main Office 100, Room 108 A NF 5 5 O&M N Detail:

Carpet Mastic HA ID: M025 Type: Misc.

Throughout

A NF 5 3 AR

Hallways (200sf damaged) N Detail:

12”x12” White Floor Tile/Mastic HA ID: M026 Type: Misc.

Hallway by 113, Room 117 A NF 5 3 AR

Hallway by 113 (20sf damaged)

N Detail:

12”x12” Beige Floor Tile Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response

Action Change in Condition

(Y/N)

If “Y”, Describe

Change in Condition Prior Current Action Notes/Comments

HA ID: M027 Type: Misc.

Stairwells

Stair Tread Mastic HA ID: M028 Type: Misc.

Gym A NF 5 3 AR ~50% falling or missing from the ceiling

N Detail:

2’x2’ Ceiling Tile HA ID: M029 Type: Misc.

Stairwell by 109, 016, Stairwell by

A NF 5 3 AR

Stairwell by 109 (100sf exposed), 016 (130sf exposed) Stairwell by

016 (60sf exposed)

N

Detail:

Black Mastic

Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Facility Name and Number: Digital Harbor High School PS416

LEA Point of Contact: Sheila R. Howard, Environmental Compliance

Facility Name and Number: Digital Harbor High School PS416

2 Facility Address:

1100 Covington Street

Baltimore, MD 21230

3 Date of Inspection: Friday, March 14, 2025

EPA Accredited Inspector(s): Name: Michael Jackson Number: EHSBIR-250131-00002

Management Planner(s): Name: Sharon Thompson Number: VAIMPR01302025-04

5A

Information provided by BCPS to BATTA for Review:

• Management Plan by VERSAR, Inc., 1989

• Reinspection Report by KAYCO Environmental, 2004

• Reinspection Report by KAYCO Environmental, 2007

• Reinspection Report by KAYCO Environmental, 2010

• Reinspection Report by KAYCO Environmental, 2013

• Reinspection Report by KCI Environmental, 2016

• Reinspection Report by BATTA Environmental, 2019

• Reinspection Report by BATTA Environmental, 2021

• The presence of the 3-year re-inspection is confirmed

5B Comments and Issues:

• 2016 Reinspection Report states the School Administrator indicated that all previously identified asbestos-containing floor tiles have been replaced with non-

ACM floor tiles. Fire doors are the only known ACM in the school.

• The presence of the 6-month surveillance is confirmed

• Cove base, cove base adhesive, ceramic tile, ceramic tile grout, terrazzo tile, & terrazzo tile grout throughout the school are assumed ACBM.

6 New suspect ACBM identified during Winter 2025 Re-Inspection – N/A no new suspect ACBM identified

Homogeneous Material Description Location(s) Sampling Information

ACM? Samples Collected for HA

Assessment and Response Action-

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re-

Inspection

AHERA

Assessment Category

Management Planner’s recommended Response Action

Change in

Condition (Y/N)

If “Y”, Describe

Change in

Condition Prior Current Action Notes/

Comments

HA ID: M008 Type: Misc.

Throughout Y NF 5 5 O&M N Detail:

Fire Doors

HA ID: M009 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Cove Base

HA ID: M010 Type: Misc.

Cove Base Adhesive

HA ID: M011 Type: Misc.

Ceramic Tile Grout

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material

ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re-

Inspection

AHERA

Assessment Category

Management Planner’s recommended Response

Action

Change in

Condition

(Y/N)

If “Y”, Describe

Change in

Condition Prior Current Action Notes/Comments

HA ID: M012 Type: Misc.

Ceramic Tile

HA ID: M013 Type: Misc.

Terrazzo Tile

HA ID: M014 Type: Misc.

Terrazzo Tile grout

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material

ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment

Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Facility Name and Number: Paul Laurence Dunbar High School PS414

LEA Point of Contact: Sheila R. Howard, Environmental Compliance

Facility Name and Number: Paul Laurence Dunbar High School PS414

2 Facility Address:

1400 Orleans Street

Baltimore, MD 21231

3 Date of Inspection: Thursday, March 13, 2025

EPA Accredited Inspector(s): Name: Michael Jackson Number: EHSBIR-250131-00002

Management Planner(s): Name: Sharon Thompson Number: VAIMPR01302025-04 for Review:

• Management Plan by VERSAR, Inc., 1989

• Reinspection Report by KAYCO Environmental, 2004

• Reinspection Report by KAYCO Environmental, 2007

• Reinspection Report by KAYCO Environmental, 2010

• Reinspection Report by KAYCO Environmental, 2013

• Reinspection Report by KCI Environmental, 2016

• Reinspection Report by BATTA Environmental, 2019

• Reinspection Report by BATTA Environmental, 2021

• The presence of the 3-year re-inspection is confirmed

5B Comments and Issues:

• 2016 Reinspection Report states the school has been completely abated (all new materials assumed).

• The presence of the 6-months surveillance is confirmed

• Cove base, cove base adhesive, ceramic tile grout, ceramic tile, terrazzo tile grout, terrazzo tile grout, 12”x12” floor tile, floor tile mastic, and 2’x2’ ceiling tile throughout the school are assumed ACBM.

6 New suspect ACBM identified during Winter 2025 Re-Inspection

Sampling Information

ACM? Samples Collected for HA

HA ID: M008 Type: Misc.

Teachers Lounge 2nd

Floor A

Brown Glue Dots on wall

Assessment and Response Action-

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re-

Inspection

AHERA

Assessment Category

Management Planner’s recommended Response Action Change in

Condition

(Y/N)

If “Y”, Describe

Change in

Condition Prior Current Action Notes/Comments

HA ID: M001 Type: Misc.

Cove Base

HA ID: M002 Type: Misc.

Cove Base Adhesive

HA ID: M003 Type: Misc.

Ceramic Tile Grout

HA ID: M004 Type: Misc.

Ceramic Tile

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material

ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible

Assessment and Response Action- Winter

2024 Periodic Surveillance

Winter 2025 3-year Re-

Inspection

AHERA

Assessment

Category

Management Planner’s recommended

Response Action Change in

Condition

(Y/N)

If “Y”, Describe

Change in

Condition Prior Current Action Notes/Comments

HA ID: M005 Type: Misc.

Throughout A NF 5 3 AR

Recommend

Sampling to determine if asbestos-containing.

Exit 10 by Door (5sf damaged)

N

Terrazzo Tile

HA ID: M006 Type: Misc.

Terrazzo Tile Grout

HA ID: M007 Type: Misc.

Throughout A NF 5 5 O&M

Minor Chipping and

Cracking in Rooms

345 and 230

Maintain Wax

Sealant

N

12”x12” White and Gray Floor Tile and Mastic

HA ID: M008 Type: Misc.

Throughout A F 5 5 O&M N Detail:

2’x4’ Ceiling Tile

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material

ACM: A= Assumed, Y= Determined to be asbestos through sampling

Friable F= Friable, NF= Non-friable

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible

Facility Name and Number: National Academy Foundation High School PS421 at Dunbar Middle School Building #133

LEA Point of Contact: Sheila R. Howard, Environmental Compliance Facility Name and Number: National Academy Foundation High School PS421 at Dunbar Middle School Building #133

2 Facility Address:

540 North Caroline Street

Baltimore, MD 21205

3 Date of Inspection: Tuesday, February 25, 2025

EPA Accredited Inspector(s): Name: Dylan Gomez-Starnes Number: EHSBIR-250131-00002

Management Planner(s): Name: Sharon Thompson Number: VAIMPR01302025-04 for Review:

• Management Plan by VERSAR, Inc., 1989 (Missing)

• Reinspection Report by KAYCO Environmental, 2004

• Reinspection Report by KAYCO Environmental, 2007

• Reinspection Report by KAYCO Environmental, 2010

• Reinspection Report by KAYCO Environmental, 2013

• Reinspection Report by KCI Environmental, 2016

• Reinspection Report by BATTA Environmental, 2019

• Reinspection Report by BATTA Environmental, 2021

• The presence of the 3-year re-inspection is confirmed

5B Comments and Issues:

• Old reinspection notes states: “School has been totally abated. All 12x12 floor tile”

• The presence of the 6-months surveillance is confirmed.

• Transite panel in auditorium, cove base, cove base adhesive, ceramic tile, ceramic tile grout, terrazzo tile, & terrazzo tile grout throughout are assumed ACBM.

Facility Name and Number: National Academy Foundation High School PS421 at Dunbar Middle School Building #133

Facility Name and Number: National Academy Foundation High School PS421 at Dunbar Middle School Building #133

Assessment and Response Action- Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment

Category

Management Planner’s recommended Response Action

Change in Condition

(Y/N)

If “Y”, Describe Change in Condition Prior Current Action Notes/Comments

HA ID: T004 Type: TSI

Boiler Room Y NF 5 5 O&M N Detail:

Boiler Flue Insulation

HA ID: T005 Type: TSI

Boiler Room Y NF 5 5 O&M N Detail:

Hot Water Generator Tank Insulation

HA ID: T006 Type: TSI Storage

Mechanical Room #227

Y NF 5 5 O&M N Detail:

Insulation on Fresh Air Intake Ductwork

HA ID: M002 Type: Misc.

Throughout Y NF 5 1 AR

Electric Room 203 (1sf exposed), Stairwell A 2nd Floor (2sf exposed)

Basement Hallway (2sf exposed)

N Detail:

Fire Doors

HA ID: M001 Type: Misc.

Throughout Y NF 5 3 AR

Cafeteria by Room 09 (8sf damaged), Classroom 302 (2sf damaged)

N Detail:

12”x12” Floor Tile (various colors) Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Facility Name and Number: National Academy Foundation High School PS421 at Dunbar Middle School Building #133

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response Action Change in

Condition (Y/N)

If “Y”, Describe

Change in Condition

Prior Current Action Notes/Comments

HA ID: T001 Type: TSI Crawlspace and Boiler

Room Y NF 5 5 O&M N Detail:

Pipe Insulation

HA ID: T002 Type: TSI

Throughout Y NF 5 5 O&M N Detail:

Pipe Fitting Insulation

HA ID: T003 Type: TSI

Boiler Room Y NF 1 5 O&M N Detail:

Boiler Insulation

HA ID: M003 Type: Misc.

Auditorium Y NF 5 5 O&M N Detail:

Transite Wall Boards HA ID: M004 Type: Misc.

Boiler Room, Storage room - - - - - Removed N Detail:

Furnace Cement Rope

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Facility Name and Number: National Academy Foundation High School PS421 at Dunbar Middle School Building #133

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response

Action Change in Condition

(Y/N)

If “Y”, Describe Change in Condition Prior Current Action Notes/Comments

HA ID: M005 Type: Misc.

Boiler Room, Storage Room - - - - - Removed N Detail:

Gasket

HA ID: M006 Type: Misc.

Boiler Room, Storage Room - - - - - Removed N Detail:

Valve Packing

HA ID: M007 Type: Misc.

Boiler Room, Storage Room - - - - - Removed N Detail:

Rope

HA ID: M008 Type: Misc.

Auditorium A NF 5 5 O&M N Detail:

Floor Tile Mastic

HA ID: M009 Type: Misc. Ductwork Throughout Y NF 5 5 O&M N Detail:

Flexible Connectors HA ID: T008 Type: Misc.

Throughout Y F 5 5 O&M 400sf N Detail:

Duct Insulation Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Facility Name and Number: National Academy Foundation High School PS421 at Dunbar Middle School Building #133

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response Action

Change in Condition

(Y/N)

If “Y”, Describe Change in Condition Prior Current Action Notes/Comments

HA ID: M012 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Cove Base

HA ID: M013 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Cove Base Adhesive

HA ID: M014 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Ceramic Tile Grout

HA ID: M015 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Ceramic Tile HA ID: M016 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Terrazzo Tile HA ID: M017 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Terrazzo Tile Grout HA ID: M018 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Transite Panel Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Facility Name and Number: National Academy Foundation High School PS421 at Dunbar Middle School Building #133

Facility Name and Number: National Academy Foundation Middle School PS421M at Building #102

LEA Point of Contact: Sheila R. Howard, Environmental Compliance Facility Name and Number: National Academy Foundation Middle School PS421M at Building #102

2 Facility Address:

601 Central Avenue

Baltimore, MD 21205

3 Date of Inspection: Tuesday, February 25, 2025

EPA Accredited Inspector(s): Name: Dylan Gomez-Starnes Number: EHSBIR-250131-00002

Management Planner(s): Name: Sharon Thompson Number: VAIMPR01302025-04 for Review:

• Management Plan by VERSAR, Inc., 1989

• Reinspection Report by KAYCO Environmental, 2004

• Reinspection Report by KAYCO Environmental, 2007

• Reinspection Report by KAYCO Environmental, 2010

• Reinspection Report by KAYCO Environmental, 2017

• Reinspection Report by BATTA Environmental, 2019

• Reinspection Report by BATTA Environmental, 2021

• The presence of the 3-year re-inspection is confirmed

5B

Comments and Issues:

• Formerly Thomas G. Hayes Elementary School PS102

• School reportedly abated in approximately 2007.

• The presence of the 6-months surveillance is confirmed

• Cove base, cove base adhesive, ceramic tile, ceramic tile grout, terrazzo tile, & terrazzo tile grout throughout are assumed ACBM.

Assessment and Response Action- Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment

Category

Management Planner’s recommended Response Action

Change in Condition

(Y/N)

If “Y”, Describe Change in Condition Prior Current Action Notes/Comments

HA ID: T004 Type: TSI

Boiler Room - - - - - Removed N Detail:

Boiler Flue Insulation

HA ID: T005 Type: TSI

Boiler Room - - - - - Removed N Detail:

Hot Water Generator Tank Insulation

HA ID: T006 Type: TSI Storage

Mechanical Room #227

- - - - - Removed N Detail:

Insulation on Fresh Air Intake Ductwork

HA ID: M002 Type: Misc.

Throughout Y NF 5 5 O&M N Detail:

Fire Door Insulation HA ID: M001 Type: Misc.

Throughout A NF 5 3 AR Recommend

Sampling to determine if asbestos-containing

Classroom 206 N

Damage in rooms 314,315,316,117,114, 113,213 Detail:

12”x12” Floor Tile Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response Action Change in

Condition (Y/N)

If “Y”, Describe

Change in Condition

Prior Current Action Notes/Comments

HA ID: T001 Type: TSI Crawlspace and Boiler

Room

- - - - - Removed N Detail:

Pipe Insulation

HA ID: T002 Type: TSI

Throughout - - - - - Removed N Detail:

Pipe Fitting Insulation

HA ID: T003 Type: TSI

Boiler Room - - - - - Removed N Detail:

Boiler Insulation

HA ID: M003 Type: Misc.

Auditorium Y NF 5 5 O&M N Detail:

Transite Wall Boards HA ID: M004 Type: Misc.

Boiler Room Storage Room - - - - - Removed N Detail:

Furnace Cement Rope

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response

Action Change in Condition

(Y/N)

If “Y”, Describe Change in Condition Prior Current Action Notes/Comments

HA ID: M005 Type: Misc.

Boiler room

Storage room - - - - - Removed N Detail:

Gasket

HA ID: M006 Type: Misc. Boiler room Storage room - - - - - Removed N Detail:

Valve Packing

HA ID: T008 Type: Misc.

Throughout Y NF 5 5 O&M

Observed Duct Insulation was

Fiberglass N Detail:

Duct Insulation

HA ID: M008 Type: Misc.

Auditorium A NF 5 5 O&M

Not Observed

– May be under Carpet N Detail:

Floor Tile Mastic HA ID: M009 Type: Misc. Ductwork

Throughout Y NF 5 5 O&M N Detail:

Flexible Connectors HA ID: M012 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Cove Base Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

Winter 2024 Periodic Surveillance

Winter 2025 3-year Re- Inspection

AHERA

Assessment Category

Management Planner’s recommended Response Action

Change in Condition

(Y/N)

If “Y”, Describe Change in Condition Prior Current Action Notes/Comments

HA ID: M013 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Cove Base Adhesive

HA ID: M014 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Ceramic Tile Grout

HA ID: M015 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Ceramic Tile

HA ID: M016 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Terrazzo Tile HA ID: M017 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Terrazzo Tile Grout HA ID: M018 Type: Misc.

Throughout A NF 5 5 O&M N Detail:

Carpet Mastic Key to Abbreviations:

Type: TSI= Thermal Systems Insulation, Surf. = Surfacing Material, Misc.= Miscellaneous Material ACM: A= Assumed, Y= Determined to be asbestos through sampling.

Friable F= Friable, NF= Non-friable.

AHERA

Assessment Category:

1)= Damaged or significantly damaged TSI ACBM, 2) = Damaged friable surfacing ACBM, 3) = Significantly damaged friable surfacing ACBM

4) = Damaged or significantly damaged friable miscellaneous ACBM, 5) = ACBM with potential for damage, 6) = ACBM with potential for significant damage

7) = Any remaining friable ACBM or friable suspected ACBM. (8) = Not applicable (non-friable surfacing or miscellaneous material).

Response Action: O&M= Continue surveillance and Operations and Maintenance, AR= Abatement Required as soon as possible.

8a. AHERA-Benjamin Franklin HS at Masonville Cove PS239.pdf
8b. AHERA-Digital Harbor HS.pdf
8c. AHERA- Paul Laurence Dunbar HS.pdf
8d. Natl. Academy Foundation High School PS421 at Dunbar MS Bldg. #133.pdf
8e. AHERA- Natl. Academy Foundation Middle School PS421M at Bldg. #102.pdf

File details come from the government source that posted it. Updated .