SYMBOL DESCRIPTION
THIS IS A COMPREHENSIVE SYMBOL SCHEDULE. NOT ALL SYMBOLS ARE APPLICABLE TO THESE DRAWINGS
MECHANICAL SYMBOLS & ABBREVIATIONS LEGEND
DESCRIPTION
CHEMICAL RESISTANT VENT
CHEMICAL RESISTANT WASTE
A
CRW
VAC
LPC
GHWR
G
IG
CRV
O2
LPSTM
GATE VALVE
BALL VALVE
2−WAY TEMPERATURE CONTROL VALVE
STRAINER
PIPE UP
TOP PIPE TAKE−OFF
PIPE DOWN
GHWS
CWR
CWS
HWS
HWR
HOT WATER
STORM DRAIN
VACUUM
COMPRESSED AIR
RECIRCULATING HOT WATER
HOT WATER SUPPLY
STORM
VENT PIPE
CAPPED PIPE
HPS
HPR
PC
CHECK VALVE, ARROW IN DIRECTION OF FLOW
FLOW SWITCH
PRESSURE GAUGE
THERMOMETER
UNION
FS
P
S
OXYGEN
COLD WATER
SANITARY WASTE
HOT WATER RETURN
CONDENSER WATER SUPPLY
CONDENSER WATER RETURN
GLYCOL HOT WATER SUPPLY
GLYCOL HOT WATER RETURN
NATURAL GAS
INTERRUPTIBLE NATURAL GAS
HEAT PUMP SUPPLY
HEAT PUMP RETURN
LOW PRESSURE STEAM
LOW PRESSURE CONDENSATE
PUMPED CONDENSATE
BOTTOM PIPE TAKE−OFF
PROPANEP
FUEL OIL RETURN
FUEL OIL SUPPLYFOS
FOR
CHILLED WATER RETURN
CHILLED WATER SUPPLY
CHWR
CHWS
WATER FLOW MEASURING DEVICE
GLOBE VALVE
BUTTERFLY VALVE
3−WAY TEMPERATURE CONTROL VALVE
RELIEF VALVE
BALANCING VALVE
BACKFLOW PREVENTER
PRESSURE REDUCING VALVE
SOLENOID VALVE
PIPE ANCHOR
HOSE BIBB OR WALL HYDRANT
FLEXIBLE PIPE CONNECTION
FOV FUEL OIL VENT
NITROGENN
N2O NITROUS OXIDE
REFRIGERANT LIQUIDRL
REFRIGERANT SUCTIONRS
REFRIGERANT DISCHARGERD
HOT GAS BYPASSHGB
CONDENSATE DRAIND
PIPE ALIGNMENT GUIDE
SAN
SYMBOL
PRESSURE/TEMPERATURE TEST PORT
AIR VENT
REDUCER, CONCENTRIC
REDUCER, ECCENTRIC
PRESSURE SWITCH
PS
DESCRIPTIONSYMBOL
DUCT UP TO ROOF VENTILATOR
( DASHED LINE INDICATES EQUIPMENT
FIRE DAMPER
MANUAL VOLUME DAMPER
SIDEWALL REGISTER OR GRILLE.
MOTOR OPERATED DAMPER
SMOKE DAMPER
RECTANGULAR DUCT WITH SIZE INDICATED20x12
ROUND DUCT WITH DIAMETER INDICATED20Ø
20x12 ACOUSTICALLY LINED DUCTWORK (OUTSIDE DIMENSION INDICATED)
POSITIVE PRESSURE DUCT −
(UP) (DN)
(DN)(UP)
NEGATIVE PRESSURE DUCT −
8Ø
DUCT UP THRU FLOOR OR DECK ABOVE
12x10
RETURN OR EXHAUST AIR INLET
SUPPLY AIR OUTLET
CEILING MOUNTED RETURN GRILLE, LAY−IN TYPE
(NEG. PRES.)(POS. PRES.)
(FIRST DIMENSION IS SIDE SHOWN)
FLEXIBLE DUCT CONNECTION
SUPPLY, RELIEF
RETURN, EXHAUST, OUTSIDE AIR
ON ROOF )
COMBINATION FIRE/SMOKE DAMPER
C
NEW REGISTER, DIFFUSER OR GRILLE REFERENCE SYMBOL
WITH TYPE AND AIRFLOW SHOWN (TYPE R−1; 200 CFM).
REFER TO SCHEDULE. (R=RETURN, S=SUPPLY, E=EXHAUST,
T=TRANSFER)
CEILING MOUNTED GRILLE OR REGISTER. RIGID DUCT FROM
MAIN WITH SIZE INDICATED (12x10). ( SUPPLY SHOWN −
RETURN & EXHAUST SIMILAR )
F
M
S
HUMIDISTATH
T THERMOSTAT
DEMOLITION NOTE
KEY NOTE1
CONNECT NEW TO EXISTING.
SQUARE NECK CEILING DIFFUSER WITH HIGH EFFICIENCY
TAKE OFF AND FLEXIBLE DUCT FROM MAIN WITH SIZE
INDICATED (8Ø)
CHANGE IN DUCT ELEVATION IN DIRECTION OF AIRFLOW
(RISE OR DROP)
FC
AD
ACCESS DOOR (MIN. SIZE NOT LESS THAN 2" SMALLER
(SQUARE) THAN DUCT DIMENSION.
DUCT MOUNTED HEATING COIL
(A) (B) (C)
DUCT ELBOWS. RADIUSED ELBOW (A), MITERED ELBOW (B),
MITERED ELBOW WITH TURNING VANES (C)
AIRFLOW MEASURING DEVICE/STATION
AFM
LFR
LFS LOOP FIELD SUPPLY
LOOP FIELD RETURN
STEAM TRAP
BALL VALVE INDICATOR
EMERGENCY GAS SHUT−OFF
TEMPERATURE TRANSMITTER
TT
T TEMPERATURE SENSOR
SENSOR WELL
PT
PRESSURE TRANSMITTER
BACKDRAFT DAMPER
B
V
AUTOMATIC FLOW CONTROL VALVE
MPC
MPSTM MEDIUM PRESSURE STEAM
MEDIUM PRESSURE CONDENSATE
HPC
HPSTM HIGH PRESSURE STEAM
HIGH PRESSURE CONDENSATE
GLYCOL CHILLED WATER RETURN
GLYCOL CHILLED WATER SUPPLY
GCWR
GCWS
ACID VENT
ACID WASTEAW
AV
TYPICAL SHUTOFF VALVE. VALVE MAY BE BALL, BUTTERFLY,
OR GATE. TYPE OF VALVE VARIES BY PIPE SIZE AND
SYSTEM. REFER TO SPECIFICATIONS FOR VALVE
REQUIREMENTS
CFM CUBIC FEET PER MINUTE
BUILDING AUTOMATION SYSTEM
AUTOMATIC TEMPERATURE CONTROLS CONTRACTOR
DRAIN
COLD WATER
BAS
ATC
D
CW
EXHAUST AIREA
OA
RHW
W
V
REG
VTR
RA
SA SUPPLY AIR
RETURN AIR
VENT THROUGH ROOF
REGISTER
VENT PIPE
WASTE PIPE
RECIRCULATING HOT WATER
OUTSIDE AIR
MOD
HW
GC
MC
F/SD
FD
GR
HC
COMBINATION FIRE/SMOKE DAMPER
HEATING COIL
GRILLE
FIRE DAMPER
MECHANICAL CONTRACTOR
GENERAL CONTRACTOR
HOT WATER
MOTOR OPERATED DAMPER
ELECTRICAL CONTRACTOR
EGG CRATE GRILLE
FRESH AIR
EC
FA
ECG
VARIABLE AIR VOLUME BOXVAV
VD VOLUME DAMPER
DRY BULB TEMPERATUREDb
DECIBELSdB
CABINET UNIT HEATER CUH−1
ETHYLENE GLYCOL MIXTURE (USED WITH % CONCENTRATION, I.E. 30% EG)EG
PG PROPYLENE GLYCOL MIXTURE (USED WITH % CONCENTRATION, I.E. 30% PG)
DEWPOINT TEMPERATUREDp
LBS/HR POUNDS PER HOUR
AIRFOILAF
AIR COOLED CONDENSING UNITACCU−1
SP STATIC PRESSURE
UH−1 UNIT HEATER
VARIABLE FREQUENCY DRIVEVFD
MER MECHANICAL EQUIPMENT ROOM
NOM. NOMINAL
HP HORSEPOWER
BOILER B−1
CHLR−1 CHILLER
EXHAUST FAN EF−1
RV−1 ROOF VENTILATOR
OBD OPPOSED BLADE DAMPER
WC−1 WATER CLOSET
P−1 PUMP
HP−1 HEAT PUMP
SOFT WATERSOFT
TEMPERED WATERTW
FLOOR DRAIN FD−1
WH−1 WATER HEATER
ELECTRIC WATER COOLEREWC−1
L−1 LAVATORY
S−1 SINK
AIR HANDLING UNIT AHU−1
MOD−1 MOTOR OPERATED DAMPER
RF−1 RETURN AIR FAN
SF−1 SUPPLY FAN
R−1
TRIPLE DUTY VALVE WITH MEASURING PORTS
REFRIGERANT THERMOSTATIC EXPANSION VALVE
DROP
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
MECHANICAL LEGEND AND INDEX
PHASING PLAN
PIPING DEMOLITION PLAN
VENTILATION DEMOLITION PLAN
MECHANICAL ROOF DEMOLITION PLAN
PIPING PLAN
VENTILATION PLAN
MECHANICAL ROOF PLAN
PIPING SCHEMATIC
DETAILS
DETAILS
DETAILS AND SCHEDULES
MECHANICAL SHEET INDEX
M000
M001
M101
M102
M103
M201
M202
M203
M301
M302
M303
M304
HEAD HOUSE
INTERIOR GLASS PARTITION
HEAD HOUSE
INTERIOR GLASS PARTITION
HEAD HOUSE GROWTH CHAMBER
LAB
PREP
ROOM
BOILER ROOM
CORRIDOR SERVER ROOM
GRAPHICS
OFFICE
LAB LAB
CORRIDOR
LAB
COLD
LAB
MICROSCOPE
ROOM
MENS
ROOM
WOMENS
ROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ENTRY
LAB LAB
KITCHEN
CHEMICAL
STORAGE
RECEPTIONIST
ADMINISTRATION
STAIR
CONFERENCE
LUNCH ROOM
CONFERENCE
ROOM
CORRIDOR
CORRIDOR
CORRIDOR
LAB 1LAB 2PREP ROOM
OPEN OFFICE
M.E.P.
MENS
ROOM
WOMENS
ROOM
CONTAINMENT LAB
AUTO-
CLAVE
ANALYSIS
ROOM
ANTEROOM DARK
ROOM
NORTH GREEN
HOUSE
SOUTH GREEN
HOUSE
RECEIVING
CORRIDOR
SEED SORTING
SEED STORAGE
PHASE #1
PHASING LEGEND
PHASE #2
PHASE #3
PHASE #4
SEE SPECIFICATION SECTION 01 10 00 FOR
DETAILED PHASING DESCRIPTION.
STAIR
MECHANICAL
ROOM
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
Main Floor Phasing Plan1
M001 3/32" = 1’−0"
Basement Phasing Plan2
M001 3/32" = 1’−0"
0’ 16’4’ 8’
HEAD HOUSE
INTERIOR GLASS PARTITION
HEAD HOUSE GROWTH CHAMBER
LAB
PREP
ROOM
BOILER ROOM
CORRIDOR SERVER ROOM
GRAPHICS
OFFICE
LAB LAB
CORRIDOR
LAB
COLD
LAB
MICROSCOPE
ROOM
MENS
ROOM
WOMENS
ROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ENTRY
LAB LAB
KITCHEN
CHEMICAL
STORAGE
RECEPTIONIST
ADMINISTRATION
STAIR
CONFERENCE
LUNCH ROOM
CONFERENCE
ROOM
CORRIDOR
CORRIDOR
CORRIDOR
LAB 1LAB 2PREP ROOM
OPEN OFFICE
M.E.P.
MENS
ROOM
WOMENS
ROOM
CONTAINMENT LAB
AUTO-
CLAVE
ANALYSIS
ROOM
ANTEROOM DARK
ROOM
NORTH GREEN
HOUSE
SOUTH GREEN
HOUSE
RECEIVING
CORRIDOR
SEED SORTING
SEED STORAGE
33 44
5 5
5 5
H W S
H W R
H W S
H W R
H W S
H W R
LPSLPS
COND
COND
COND
LPS
COND
L P S
C O N D
L P S
C O N D
L P S
C O N D
L P S
C O N D
H P S
H P S
HPS HPS
HPS
COND
8 8 8
13 13
EXIST. LAB
HOOD (TYP)
EXISTING AUTOCLAVE
EXISTING AUTOCLAVE
11 11 11
1111111111
11 11
10 10 10
11 11
10 10 10
11 11
15 16
17 18
H P S
EXISTING
HPS TO REMAIN.
HWS
H W R
STAIR
MECHANICAL
ROOM
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
REMOVE EXISTING FIN−TUBE RADIATION AND
ENCLOSURE. SEE 1/M201 FOR NEW FIN TUBE.
REMOVE EXISTING REHEAT COIL, BRANCH PIPING
AND ASSOCIATED CONTROLS.
REMOVE EXISTING CONDENSATE PUMP. FILL IN
PIT AND PATCH CONCRETE FLOOR.
REMOVE EXISTING FAN COIL UNIT, BRANCH
PIPING AND ASSOCIATED CONTROLS.
REMOVE EXISTING STEAM UNIT HEATER, BRANCH
PIPING AND ASSOCIATED CONTROLS.
REMOVE EXISTING CONDENSER WATER PUMPS.
SEE 1/M201 FOR NEW PUMPS.
REMOVE EXISTING BOILERS AND ASSOCIATED
STEAM PIPING, CONTROLS, CONCRETE PADS AND
FLUES. SEE 1/M201 FOR NEW BOILERS.
REMOVE EXISTING CONDENSATE RETURN PIPE
UNDER RADIATION.
REMOVE EXISTING CONDENSATE RECEIVER AND
PUMP. REROUTE DRIP LEG FROM STEAM
PRESSURE REDUCING STATION TO FLOOR DRAIN.
REMOVE EXISTING 2−WAY CONTROL VALVE AND
ASSOCIATED PNEUMATIC TUBING.
REMOVE EXISTING THERMOSTAT AND
ASSOCIATED PNEUMATIC TUBING.
REMOVE EXISTING CABINET UNIT HEATER ,
BRANCH PIPING AND ASSOCIATED CONTROLS.
REMOVE EXISTING STEAM AND CONDENSATE
PIPING ASSOCIATED WITH CURRENT HEATING
SYSTEM.
REMOVE EXISTING HWS AND HWR PIPING
ASSOCIATED WITH CURRENT HEATING SYSTEM.
REMOVE EXISTING CONDENSATE PUMP AND ALL
ASSOCIATED CONTROLS.
REMOVE EXISTING CONDENSATE RECEIVER TANK
REMOVE EXISTING STEAM TO WATER HEAT
EXCHANGER AND ALL ASSOCIATED PIPING.
REMOVE EXISTING HWS PUMPS.
REMOVE 2 OF 3 EXISTING AIR COOLED
CONDENSING UNITS. UNIT SERVING COLD LAB
WILL REMAIN, VERIFY.
REMOVE EXISTING CONDENSATE LINE AS
INDICATED BY HATCHING. CAP BELOW FLOOR AT
GRIDS XA & X1.
DEMOLITION NOTES:
Main Floor Piping Demolition1
M101 3/32" = 1’−0"
Basement Piping Demolition2
M101 3/32" = 1’−0"
HEAD HOUSE
INTERIOR GLASS PARTITION
HEAD HOUSE GROWTH CHAMBER
LAB
PREP
ROOM
BOILER ROOM
CORRIDOR SERVER ROOM
GRAPHICS
OFFICE
LAB LAB
CORRIDOR
LAB
COLD
LAB
MICROSCOPE
ROOM
MENS
ROOM
WOMENS
ROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ENTRY
LAB LAB
KITCHEN
CHEMICAL
STORAGE
RECEPTIONIST
ADMINISTRATION
STAIR
CONFERENCE
LUNCH ROOM
CONFERENCE
ROOM
CORRIDOR
CORRIDOR
CORRIDOR
LAB 1LAB 2PREP ROOM
OPEN OFFICE
M.E.P.
MENS
ROOM
WOMENS
ROOM
CONTAINMENT LAB
AUTO-
CLAVE
ANALYSIS
ROOM
ANTEROOM DARK
ROOM
NORTH GREEN
HOUSE
SOUTH GREEN
HOUSE
RECEIVING
CORRIDOR
SEED SORTING
SEED STORAGE
2 2
EXIST. LAB HOOD. TYP
14 14
STAIR
MECHANICAL
ROOM
EXISTING
AHU S−1
EXISTING ATC
AIR COMPRESSOR
EXISTING LAB
EQUIPMENT AIR
COMPRESSOR
EXISTING
AHU S−4 6
EXISTING 100x30
O.A. DUCT
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
REMOVE EXISTING TRANSFER DUCT AND GRILLE.
REMOVE EXISTING SUPPLY DIFFUSER. CAP DUCT
AT MAIN.
REMOVE EXISTING FAN COIL UNIT AND
DUCTWORK THROUGH ROOF. SEE A300 FOR
ROOF REPAIR. CAP STEAM AND CONDENSATE
PIPING AT MAINS.
REMOVE EXISTING SUPPLY DUCTWORK FROM
BASEMENT AIR HANDLER TO POINT SHOWN BY
HATCHING. PREPARE DUCTWORK FOR NEW
CONNECTION.
REMOVE EXISTING RETURN DUCTWORK FROM
BASEMENT AIR HANDLER.
DISCONNECT AND REMOVE EXISTING SUPPLY
DUCTWORK UP TO 1ST FLOOR. SEE 1/M102 FOR
CONTINUATION.
DISCONNECT AND REMOVE EXISTING RETURN
DUCTWORK UP TO 1ST FLOOR. SEE 1/M102 FOR
CONTINUATION.
DISCONNECT AND REMOVE EXISTING O.A. DUCT
AS SHOWN BY HATCHING.
DISCONNECT AND REMOVE EXISTING AHU AND
ALL ASSOCIATED PIPING, VALVES, CONTROLS,
CONCRETE PAD, ETC.
REMOVE AND CAP EXISTING COMBUSTION AIR
LOUVER.
REMOVE EVAPORATOR AND ASSOCIATED
REFRIGERANT PIPING TO CONDENSING UNIT IN
BASEMENT.
REMOVE EXISTING DUCTLESS MINI SPLIT
CONDENSER AND BOTH EVAPORATORS.
REMOVE EXISTING RELIEF DUCT AND GRILLES.
REMOVE EXISTING SUPPLY DUCT AND DIFFUSERS
AS SHOWN BY HATCHING.
PATCH EXISTING GRILLE OPENING IN OVERHANG
TO MATCH EXISTING.
DEMOLITION NOTES:
Main Floor Ventilation Demolition1
M102 3/32" = 1’−0"
Basement Ventilation Demolition2
M102 3/32" = 1’−0"
HEAD HOUSE
INTERIOR GLASS PARTITION
HEAD HOUSE GROWTH CHAMBER
LAB
PREP
ROOM
BOILER ROOM
CORRIDOR SERVER ROOM
GRAPHICS
OFFICE
LAB LAB
CORRIDOR
LAB
COLD
LAB
MICROSCOPE
ROOM
MENS
ROOM
WOMENS
ROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ENTRY
LAB LAB
KITCHEN
CHEMICAL
STORAGE
RECEPTIONIST
ADMINISTRATION
STAIR
CONFERENCE
LUNCH ROOM
CONFERENCE
ROOM
CORRIDOR
CORRIDOR
CORRIDOR
LAB 1LAB 2PREP ROOM
OPEN OFFICE
M.E.P.
MENS
ROOM
WOMENS
ROOM
CONTAINMENT LAB
AUTO-
CLAVE
ANALYSIS
ROOM
ANTEROOM DARK
ROOM
NORTH GREEN
HOUSE
SOUTH GREEN
HOUSE
RECEIVING
CORRIDOR
SEED SORTING
SEED STORAGE
L P S
C O N D
H P S
H P S
HPS HPS
HPS
H P S
HWS
H W R
HWR HWR
HWSHWS
H W R
H W S
H W R
H W S
HWR
HWS
HWR
HWS
H W R
H W S
B−1
HWP−1
HWP−2
UH−1
UH−3
UH−2
CUH−2
CUH−1
1 1/2"
2 1/2"
2"2"1 1/2"1 1/2"
RETURN PIPE UNDER
RADIATION (TYP.)
1 1/2"1 1/2"
2"2"1 1/2"1 1/2"
RETURN PIPE UNDER
RADIATION (TYP.)
EXIST. 2"
EXIST. 4"
1−1/2"1−1/2"
2−1/2"
1−1/2"
2 1/2"
2−1/2"
1" RETURN PIPE
UNDER RADIATION
(TYP.)
1" RETURN PIPE
UNDER RADIATION
(TYP.)
CONNECT TO
EXISTING 4"
CONNECT TO
EXISTING 4"
3" HWS & HWR
UP TO RTU
VAV−8VAV−9
NEW 2−WAY CONTROL
VALVE (TYP.)
NEW 2−WAY CONTROL
VALVE (TYP.)
EXIST. 2−1/2"
S T
ST
S T
S T
2" STEAM
DOWN TO SOIL
STERILIZER PROVIDE
VALVE 4’ A.F.F.
B−2
VAV−18
VAV−21
VAV−14
VAV−15
VAV−7
VAV−6
VAV−5
VAV−4
VAV−3
VAV−2
VAV−13VAV−12
VAV−10
VAV−11
VAV−1
VAV−22
CWP−1
CWP−2
2"
2"
6"
4"
4"
4"
3"
2−1/2" HWS & HWR
CAPPED FOR FUTURE
GREENHOUSE
3"
PROVIDE 4" CONCRETE
HOUSEKEEPING PAD UNDER
B−1 & B−2. PAD BY M.C.
VAV−19
VAV−20
2" STEAM DOWN
TO BASEMENT.
CONNECT TO LOW
PRESSURE SIDE OF
PRESSURE
REDUCING STATION.
RUN RETURN PIPE UNDER
ELEMENT IN ENCLOSURE.
SEE 1/M304
RUN RETURN PIPE UNDER
ELEMENT IN ENCLOSURE.
SEE 1/M304
EXISTING 2−1/2"
HPS DN.
EXIST.
1" HPS
VFD’S FOR
HWP−1 & 2
EXIST. 4" EXIST. 4" EXIST. 4"
EXIST. 2"EXIST. 2"EXIST. 2"
EXIST. 2"
EXIST. 4"EXIST. 4" EXIST. 4" EXIST. 4"
EXIST. 2"EXIST. 2"EXIST. 2"
EXIST. 2"
MOUNT TEMPERATURE
SENSOR 10’ A.F.F.
CENTERED IN
GREEHOUSE
(TYP. OF 10)
N G
EXISTING GAS METERROUTE NEW 1−1/2" 2psi NG
LINE TO GENERATOR.
GENERATOR.
EXIST.
3/4" HPS
EXISTING LPS & COND
IN CONTAINMENT LAB
TO BE ABANDONED.
NG
ET−1
GLYCOL MAKE−UP
TANK & PUMP
VAV−16VAV−17
DIFFERENTIAL
PRESSURE
SENSOR.
EXISTING 3" HWS
EXISTING 3" HWR
SLOPE STEAM LINE
TOWARDS BASEMENT.
PROVIDE VACUUM
BREAKERS ON ALL
HOSE BIBS IN
GROWTH CHAMBER.
CAP P−TRAP BEHIND
ICE MAKER IN LAB
REPLACE SPRINKLER
HEAD & REPLACE W/
286°F CONCEALED
HEAD.
SEE LINTEL
DETAIL 2/M304
SEE DETAIL 3/M201
STAIR
MECHANICAL
ROOM
VAV−22
2" STEAM UP. EXIST 3"
STEAM. VERIFY
2"
HW
R
HW
S
HWS
HWR
HWR
HWS
H W S
HW
R
HW
R
NEW 3" HWR
EXISTING 3" HWR
NEW 3" HWS
EXISTING 3" HWS
EXISTING HXER TO
BE REMOVED
EXISTING PUMPS TO
BE REMOVED
REMOVE EXISTING PIPING &
VALVES AS SHOWN BY
HATCHING. TYPICAL
EXISTING AIR SEPARATOR
TO REMAIN.
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
Main Floor Piping1
M201 3/32" = 1’−0"
Basement Piping2
M201 3/32" = 1’−0"
0’ 16’4’ 8’
0’ 16’4’ 8’
EXISTING 2006 ADDITION MECHANICAL ROOM PIPING ISOMETRIC3
M201 NO SCALE
HEAD HOUSE
INTERIOR GLASS PARTITION
HEAD HOUSE GROWTH CHAMBER
LAB
PREP
ROOM
BOILER ROOM
CORRIDOR SERVER ROOM
GRAPHICS
OFFICE
LAB LAB
CORRIDOR
LAB
COLD
LAB
MICROSCOPE
ROOM
MENS
ROOM
WOMENS
ROOM
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
ENTRY
LAB LAB
KITCHEN
CHEMICAL
STORAGE
RECEPTIONIST
ADMINISTRATION
STAIR
CONFERENCE
LUNCH ROOM
CONFERENCE
ROOM
CORRIDOR
CORRIDOR
CORRIDOR
LAB 1LAB 2PREP ROOM
OPEN OFFICE
M.E.P.
MENS
ROOM
WOMENS
ROOM
CONTAINMENT LAB
AUTO-
CLAVE
ANALYSIS
ROOM
ANTEROOM DARK
ROOM
NORTH GREEN
HOUSE
SOUTH GREEN
HOUSE
RECEIVING
CORRIDOR
SEED SORTING
SEED STORAGE
VAV−9
VAV−8
V A
V −1
V A
V −1
VAV−12
VAV−10
VAV−14
V A
V −1
VAV−18
VAV−21
VAV−7
VAV−6
VAV−5
VAV−4
VAV−3
VAV−2
V A
V −1
8x8
E X x6
E X x1
E
X x1
EX. 24x12 32x20
E X x1
E
X x2
EX. 12x12
E X x2
E X x2 x
8x8
8x8
8x8
10x8
8x8
6x6
8x8
12x8
EX. 12x8 x
12"Ø
6x6
VAV−20
VAV−19
VAV−16VAV−17
12x12 10x8
10x8
14x12
10x10
12x10
8x8
8x8
6x6
8x88x8
14x14
8x8 8x8
12x10
8x8
8x8
14x14 6x6
10x8
10x8
12x12
6x6
8x8
10x8 8x8
10x1018x18 x
E X x2
E X x2
8x8
8x8
12x10
8x8
8x8
16x12
12x10
8x8
8x8
8x8
10x8
34x14
8x8 x
42x24
16x10
18x1030x10 x x
12x10
10x8 x
20x1020x10
12x10 x
24x12
56x18
12"Ø
VAV−22
18x14 x
18x14
18x14
S.A. DN.
40x40 R.A.
UP TO RTU−1
34x50 S.A.
UP TO RTU−1
REBALANCE
EXISTING
REGISTERS TO
TAGGED CFM’S
(TYP 4)
REBALANCE
EXISTING
REGISTERS TO
TAGGED CFM’S
(TYP 4)
BUILDING STATIC
PRESSURE SENSOR
HOOD
HOOD
HOOD
HOOD
HOOD
CAP
28x18 x 056x20
24x12
HOOD
COORDINATE INSTALLATION
OF DUCT SMOKE DETECTOR
WITH ELECTRICAL CONTRACTOR
STAIR
MECHANICAL
ROOM AC−1
18x14
S.A. UP.
x
CONNECT PIPING
TO EXISTING LAB
AIR PIPING
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
Main Floor Ventilation1
M202 3/32" = 1’−0"
Basement Ventilation2
M202 3/32" = 1’−0"
EXISTING 2005 PENTHOUSE HVAC
EXISTING EXHAUST
FANS TO REMAIN.
(TYPICAL)
EXISTING EXHAUST
FANS TO REMAIN.
RTU−1
C−1
OUTDOOR
PRESSURE
SENSOR
BOILER FLUE
WATER HEATER
COMBUSTION AIR
GOOSENECK
RELOCATED
PLUMBING VENT
VERIFY EXISTING
PLUMBING VENTS
ARE MIN. 10’−0" AWAY
FROM RTU−1 O.A. INTAKE.
RELOCATE IF REQUIRED.
VERIFY EXISTING
EXHAUST HOOD IS A
MIN. 10’−0" AWAY FROM
RTU−1 O.A. INTAKE.
RELOCATE IF REQUIRED.
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
Mechanical Roof Plan1
M203 3/32" = 1’−0"
8’4’0’ 16’
HWS
HWR
HWS
HWRHWR
H W S
H W R
HWS
6"
MOUNT PUMP ON WALL
NEAR GLYCOL SUPPLY DRUM.
PROVIDE 8’−0" HOSE.55 GALLON GLYCOL DRUM W/
REMOVABLE COVER. FILL 3/4
FULL WITH 50% PROPYLENE
GLYCOL SYSTEM FLUID.
BASE MOUNTED PUMP
(TYP.) SEE DETAIL 2/M302
SUCTION DIFFUSER (TYP.)
3/4"
AUTOMATIC AIR
VENT (TYP.)
1"
AIR SEPARATOR AS−1
(TYP.) SEE DETAIL 6/M302
6"
6"
SYSTEM FILL
PRESSURE
SENSOR
SIDE STREAM
FILTER. SEE
CHEMICAL
FEEDER
BLADDER TYPE EXPANSION
TANK ET−1
1−1/4"
CONNECT TO
SIDE OF MAIN
AIR RECHARGING
CONNECTION. (TYP)
PRESSURE RELIEF
VALVE 35 PSI
PIPE DISCHARGE
NEAR FLOOR.
4"
HWP−1
HWP−2
SEE SPEC FOR PUMP INFORMATION.
6"
BOILERBOILER
4"
4"4"
DETAIL 1/M302
B−2 B−1
HWRHWRHWR
HWSHWSHWS
HWRHWR
HWSHWS
1 1/2"
12.6 GPM 4.8 GPM 8.4 GPM 7.8 GPM 4.8 GPM 7.8 GPM 13.2 GPM
1"
UH−2
1 1/2"
2" 1 1/2" 2" 2"2 1/2"
1 1/2" 1 1/2" 2"
EXISTING
2"
4"
EXISTING
4" EXISTING
2" 2 1/2"
1 1/2" 1 1/2" 2 1/2"
HWRHWR
HWSHWS
1 1/2"
12.6 GPM 4.8 GPM 8.4 GPM 7.8 GPM 4.8 GPM 7.8 GPM
RAD
13.2 GPM
1"
UH−3
1 1/2"
2" 1 1/2" 2" 2"2"
1 1/2" 1 1/2" 2"
EXISTING
2"
4"
EXISTING
4" EXISTING
2" 2 1/2"
1 1/2" 1 1/2" 2 1/2"
CAPPED FOR
FUTURE
GREENHOUSE
CONNECT TO EXISTING
106 MECHANICAL ROOM
2 1/2"
SOUTH
GREENHOUSE
NORTH
GREENHOUSE
UH−1
4"
VAV−20
RADRADRADRADRADRAD
RADRADRADRADRADRADRAD
VAV−19
3/4"
VAV−9
3/4"
VAV−8
RAD 0.8GPM
CUH−2
RAD 0.7GPMRAD 0.7GPMRAD 0.7GPMRAD 0.7GPM
CUH−1
3/4"
VAV−11VAV−10VAV−12VAV−13
RAD 0.7GPMRAD 0.8GPM
VAV−14 RTU−1
3/4"
VAV−21VAV−18VAV−15
3/4" 3"
SEE DETAIL 7/M302
FOR MORE INFORMATION
HWS
HWR
3/4" 3/4"
SEE DETAIL 9/M302
(TYP FOR ALL VAV’S)
HWS
HWR
HWS
HWR
3"
VAV−16 VAV−17
DIFFERENTIAL PRESSURE
SWITCH. SEE DETAIL
3/M302
4"
6"
6"
6"
3/4"
SEE DETAIL 10/M302
(TYP FOR ALL UH’S)
3/4" HOSE
CONNECTION.
3/4"3/4"
3"
3" 3"
40"x40" R.A.
18"x56" R.A.
12"x24" R.A. 24"x42" S.A. 20"x32" S.A.
34"x50" S.A.
RTU−1
RETURN AIR FAN.
SUPPLY AIR FAN
DX COOLING COIL
HOT WATER HEATING COILMIXING SECTION FILTER SECTION
CURB SHALL BE SUPPORTED
BY 6 POINTS AT CURB
CORNERS AND
MIDPOINT OF CURB.
42" CURB
SOUND ATTENUATOR SA−2
SOUND ATTENUATOR SA−1
ROOF
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
Piping Schematic1
M301 No Scale
RTU−1 SECTION2
M301 SCALE: 1/4" = 1’−0"
0’ 4’2’ 8’
NOTE:
SYSTEM CIRCULATING PUMPS
1/2" (15 MM)
1. ALLOW CLEARANCE FOR INSULATION OF PIPING AND VALVES.
SIDESTREAM FILTER DETAIL1
M302 NO SCALE
AUTOMATIC FLOW
CONTROL VALVE
SHUT OFF VALVE
(TYPICAL)
PRESSURE GAUGE
UNION (TYPICAL)
WATER
FILTER
3’−0"
FLOOR
2. SET CONTROL VALVE GPM AT 3% OF MAX GPM, OR MAXIMUM FLOW OF 10 GPM.
1/2" BALL VALVE (TYPICAL)
CONNECTOR
FLEXIBLE PIPE
END SUCTION PUMP
1/2" CAPPED DRAIN VALVE
BASE. REFER TO SPECIFICATIONS
FOR REQUIREMENTS.
MOTOR
THERMOMETER
W/ 3/4" NPT COPPER WELL
BUTTERFLY VALVE (TYPICAL)
SPRING AND NEOPRENE TYPE
VIBRATION ISOLATING PIPE
HANGER, FIRST THREE
HANGERS ON SYSTEM PIPING.
INSTALL FIRST HANGER AS
CLOSE TO PIPE ELBOW AS
POSSIBLE (TYPICAL)
SUCTION DIFFUSER WITH
STARTUP STRAINER, AND
OPERATING STRAINER. REFER
TO SPECIFICATIONS FOR
STRAINER REQUIREMENTS.
PROVIDE SUPPORT LEG
BASE MOUNTED PUMP DETAIL2
M302 NO SCALE
FILL VOIDS IN PUMP FRAME WITH
NON−SHRINKING GROUT.
PUMP
FRAME
BASE. REFER TO SPECIFICATIONS
FOR REQUIREMENTS.
ANCHOR BOLT. REFER TO
SPECIFICATIONS FOR
REQUIREMENTS.
ALLOW SPACE FOR SHIMS
PER MANUFACTURER’S
REQUIREMENTS.
PUMP FRAME SECTION
SEE
PUMP
FRAME
SECTION
CHECK VALVE
CONCENTRIC INCREASER
WHERE REQUIRED
CONCENTRIC REDUCER
WHERE REQUIRED
PRESSURE GAUGE (1/2" TAPS
INTO PUMP DISCHARGE,
PUMP INLET AND SUCTION
DIFFUSER INLET)
DIFFERENTIAL PRESSURE SENSOR DETAIL3
M302 NO SCALE
SUPPLY PIPE
RETURN PIPE
PRESSURE GAUGE
BALL VALVE
(TYPICAL)
DIFFERENTIAL
PRESSURE
TRANSDUCER
INSTALL BRANCH SHUT−OFF AS
CLOSE TO MAIN PIPE AS
POSSIBLE (TYPICAL)
INSTALL TAPS ON SIDE OF MAIN
PIPES ONLY. TOP OR BOTTOM
TAPS ARE NOT ACCEPTABLE.
"HIGH" PRESSURE
PORT
"LOW" PRESSURE
PORT
SEE NOTE 1
NOTES:
1. NO OTHER BRANCH TAPS BETWEEN PRESSURE
TAPS ON MAIN PIPES ARE PERMITTED.
INSULATE ALL
PIPE AND
FITTINGS.
REFER TO
SPECIFICATIONS UNION. MARK LOCATION
ON INSULATION JACKET
NOTE:
1. PROVIDE TEMPORARY BLOCKING BETWEEN BOTTOM OF PIPE AND HANGER TO
ALLOW SPACE FOR INSULATION. BLOCKING TO BE REMOVED UPON INSTALLATION OF
INSULATION. IN LIEU OF THIS, THE CONTRACTOR MAY INSTALL A SECTION OF
APPROPRIATE INSULATION AT THE HANGER PRIOR TO FINAL INSULATION OF THE
COMPLETE SYSTEM. THE HANGER MUST BE PROPERLY SEPARATED FROM THE PIPING
WHEN THE SYSTEM IS COMPLETE.
2. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION REGARDING INSULATION
AND PIPE SUPPORTS.
3. SEAL AND TAPE ALL JOINTS AS INDICATED IN SPECIFICATIONS
COVER VALVE BODIES WITH INSULATION.
PROVIDE HANDLE STAND−OFF IF REQUIRED.
PROVIDE A 6" MINIMUM LENGTH
OF INCOMPRESSIBLE
INSULATION AT HANGERS FOR
ALL PIPE 1−1/2" AND LARGER
ONE−PIECE PRE−MOLDED
PVC FITTING COVERS
(TYPICAL)
SHEET METAL SHIELD
AT EACH HANGER.
PIPE SUPPORT FROM
STRUCTURE ABOVE
AS REQUIRED
ON HEATING OR DOMESTIC HOT WATER
SYSTEMS, UNIONS TO BE UNINSULATED.
ON CHILLED WATER OR DOMESTIC COLD
WATER SYSTEMS OR SYSTEMS OF SIMILAR
OPERATING TEMPERATURE, INSULATE
UNION AND MARK LOCATION ON SURFACE
OF INSULATION
PIPING INSULATION DETAIL4
M302 NO SCALE
UNION (TYPICAL)
COIL
AIR VENT
REDUCER. IF REQUIRED
P/T PLUG (TYPICAL) BALANCING VALVE
FLOW MEASURING DEVICE
TYPICAL TERMINAL HEATING COIL PIPING DETAIL5
M302 NO SCALE
SHUT−OFF VALVE
NOTE:
1. SLOPE RETURN PIPING UP TOWARDS AIR VENT.
2. INSTALL FLOW MEASURING DEVICE WITH MINIMUM 5 PIPE DIAMETERS OF
STRAIGHT PIPE UPSTREAM, AND 2 PIPE DIAMETERS OF STRAIGHT PIPE
DOWNSTREAM TO ANY OTHER DEVICE OR FITTING.
1/2" HOSE END BALL
VALVE WITH CAP
LINE SIZE STRAINER
2−WAY CONTROL VALVE
TYPICAL CONNECTIONS TO RTU−1 WATER COIL (3−WAY CONTROL)7
M302 NO SCALE
SINGLE COIL
DOUBLE COIL
NOTES:
WATER COIL
DRAIN
PIPING INDEPENDENT OF COIL
PIPING INDEPENDENT OF COIL
PIPE HANGER SHALL SUPPORT
WATER COIL
WATER COIL
PIPE HANGER SHALL SUPPORT
THERMOMETER
(TYPICAL)
DRAIN
DRAIN
WATER FLOW
MEASURING DEVICE
(TYPICAL.)
TEST PLUG
(TYPICAL)
CONTROL VALVE. PROVIDE
REDUCERS WHERE REQUIRED
1. WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2
HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE.
2. PIPING SHALL BE INSTALLED IN SUCH MANNER THAT IT WILL NOT BLOCK THE SWING
OR USE OF ACCESS DOORS OR PANELS: NEITHER SHALL IT BLOCK THE SERVICING OF
FILTERS, VALVES, OR EQUIPMENT.
3. THE WATER FLOW MEASURING DEVICE MAY BE INSTALLED IN THE SUPPLY PIPING IF
THE REQUIRED MINIMUM UPSTREAM AND DOWNSTREAM DIMENSIONS CANNOT BE
OBTAINED IN THE RETURN PIPING
4. ON DOUBLE COIL ARRANGEMENTS, SET BALANCING VALVE ON EACH COIL BRANCH TO
MATCH RETURN WATER TEMPERATURE BETWEEN BOTH COILS.
WATER FLOW
MEASURING DEVICE
(TYPICAL.)
BALANCING VALVE
(TYPICAL)
DRAIN
SHUT−OFF VALVE
(TYPICAL.)
AIR VENT
(TYPICAL)
CONTROL VALVE. PROVIDE
REDUCERS WHERE REQUIRED
UNION (TYPICAL)
UNION (TYPICAL)
STRAINER
BALANCING VALVE
(TYPICAL)
SHUT−OFF VALVE
(TYPICAL.)
STRAINER
AIR VENT
(TYPICAL)
TEST PLUG (TYPICAL)
THERMOMETER
(TYPICAL)
PITCH DOWN TOWARD DRAIN
1" (25 MM)
CLEAN OUT
OPEN DRAIN
B
A
DRAIN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME
SIZE AS THE NIPPLE ON THE DRAIN PAN
AIR HANDLING UNIT DRAIN TRAP DETAIL8
M302 NO SCALE
WHERE X = STATIC PRESSURE IN PAN
DIMENSIONS
2" (50 MM)
A
X
B
PLUS X
BLOW THRU
DRAW THRU
1" (25 MM) 2X
MINIMUM
AIR CONTROL & PIPING FOR GLYCOL SYSTEMS6
M302 NO SCALE
NOTES:
1. DASHED PIPING SHOWS BOTH HORIZONTAL AND VERTICAL DIAPHRAGM TYPE EXPANSION TANKS. PROVIDE ONLY THE
TYPE OF TANK SELECTED AND THE ASSOCIATED PIPING.
2. CONNECT TO SIDE OF MAIN TO PREVENT AIR OR DEBRIS FROM ENTERING PIPE TO TANK, TOP OR BOTTOM CONNECTION
NOT PERMITTED.
3. PROVIDE 12" (300 MM) MINIMUM DROP ANTI−THERMOSYPHON LOOP TO PREVENT GRAVITY HEATING OF TANK.
4. SEE HOT WATER SPECIALTIES SCHEDULE FOR COMPONENT SIZES.
5. RELIEF VALVE FOR CHILLED WATER SYSTEM IS SHOWN. OMIT WHEN RELIEF VALVE IS SHOWN ON HEAT EXCHANGER DETAIL & SYSTEM IS USED ONLY FOR HOT WATER HEATING. COMBINATION HEATING & COOLING SYSTEMS WILL
REQUIRE THE RELIEF VALVE. PIPE VALVE TO FLOOR DRAIN.
6. PROVIDE STRAINER IN AIR SEPARATOR WHEN INDICATED IN HOT WATER SPECIALTIES SCHEDULE.
AIR SEPARATOR.
SEE NOTE 6
INSERT TEE HERE
WHERE MULTIPLE
PARALLEL TANKS ARE
USED
VERTICAL DIAPHRAGM
TYPE EXPANSION TANK
DRAIN
(TYPICAL)
PRESSURE GAUGE
(TYPICAL)
SEE
NOTE 2
TO PUMP SUCTION
AIR VENT
12" (300 MM) MIN.
SEE NOTE 3
T. & P. RELIEF
VALVE (SEE
NOTE 5)
GLYCOL DRUM WITH
REMOVABLE COVER. FILL 3/4
FULL WITH MIXTURE OF
REQUIRED CONCENTRATION
GLYCOL FILL
PUMP. SEE
PUMP
SCHEDULE
DOUBLE
CHECK
VALVE
UNION
(TYPICAL)
HIGH CAPACITY FLOAT
TYPE AIR VENT
AIR CHARGING VALVE
(PRESSURIZE DRY TANK
EQUAL TO FILL VALVE
PRESSURE)
GATE VALVE
(TYPICAL)
PROVIDE 8’
FILL HOSE
BALL VALVE
(TYPICAL)
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
Aaron J. Faiman
2/17/10 44922Date:
PLAN OR SIDE VIEW
20° MAX.
20° MAX.
PLAN OR SIDE VIEW
30° MAX.
TYPICAL DUCTWORK TRANSITION
E Q
U
IP
M E N
T
30° MAX.
20° MAX.
20° MAX.
AIR FLOWAIR FLOW
TYPICAL DUCT TRANSITIONS2
M303 NO SCALE
TYPICAL DUCTWORK TRANSITION WITH
EQUIPMENT MOUNTED IN DUCT
1/4W OR 4" (100 MM) MIN.
MAIN EXHAUST OR RETURN
PROVIDE VOLUME DAMPER
BRANCH DUCT
PLAN VIEW
W
45°
EXHAUST OR RETURN BRANCH DUCTWORK4
M303 NO SCALE
PLAN VIEW
AIR SPLIT DUCT TAKE−OFF
BRANCH DUCT TAKE−OFF
PLAN VIEW
MAIN SUPPLY DUCT
SUPPLY REGISTER OR BRANCH DUCT
MAIN SUPPLY
DUCT
TURNING VANES
1/4 W OR
SQUARE ELBOW SHOWN.
PROVIDE ROUND ELBOW
WHEN SHOWN ON FLOOR PLANS
PROVIDE VOLUME DAMPER
PROVIDE VOLUME DAMPER
W
SEE PLAN FOR SPLIT DIMENSION
4" (100 MM) MIN.
RECTANGULAR SUPPLY DUCTWORK BRANCH TAKE−OFFS3
M303 NO SCALE
HANDLE WITH
MULTI−BLADE DAMPERS & ROUND DAMPERS.
2.
1.
SIDE ELEVATION
NOTES:
DUCT
DAMPER BLADE
INSULATION
INSIDE END
QUADRANT
LOCKING
HANDLE WITH
STAND−OFF
INSULATION
1/2" (15 MM)
SECTION
DAMPER BLADE
1/8" (6 MM) CLEARANCE
ALL AROUND
OUTSIDE END BEARING
DUCT
INSULATION
DELETE INSULATION STAND−OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
ROUND ROD PIN
BEARING
LOCKING QUADRANT
VOLUME DAMPER DETAIL5
M303 NO SCALE
DIFFUSER INSTALLATION DETAIL6
M303 NO SCALE
HIGH−EFFICIENCY TAKE−OFF. SEAL
PERIMETER OF FLANGE AT ATTACHMENT
POINT TO MAIN DUCT WITH DUCT SEALANT.
REFER TO SPECIFICATIONS
DUCT INSULATION
(TYPICAL)
VOLUME DAMPER IN HIGH−EFFICIENCY TAKE−OFF,
OR PROVIDE IN RIGID DUCT RUNOUT TO DIFFUSER.
PROVIDE 2" INSULATION STANDOFF. INSTALL
DAMPER AS CLOSE TO MAIN DUCT AS POSSIBLE.
SUPPLY DUCT
RIGID
RUNOUT AS
REQUIRED
A
IR
F L O
W
GENERAL NOTES:
1. DUCT TAPES & NONMETALLIC BAND CLAMPS SHALL BE LISTED AND LABELED IN
ACCORDANCE WITH STANDARD UL 181B AND MARKED "181B−FX"
2. HIGH EFFICIENCY TAKE−OFF AND RUNOUT MAY BE ROUND OR RECTANGULAR
PROFILE, SEE PLANS FOR SIZE. PROVIDE SQUARE TO ROUND TRANSITION WHERE
RECTANGULAR RUNOUT DUCTS ARE INDICATED.
3. MAXIMUM LENGTH OF FLEXIBLE DUCT TO BE 5’−0". PROVIDE RIGID RUNOUT TO
POINT WHERE FLEXIBLE DUCT MAX LENGTH CAN BE MAINTAINED. SUPPORT
FLEXIBLE DUCT FROM STRUCTURE, REFER TO SPECIFICATIONS FOR
REQUIREMENTS
A
A
KEY NOTES:
PEEL BACK OUTER INSULATION OF FLEX DUCT AND SECURE
INNER CORE TO RIGID DUCT OR DUCT COLLAR WITH 2 FULL
WRAPS OF TAPE AND METAL SCREW BAND CLAMP OVER
TAPE. PULL INSULATION AND JACKET BACK INTO POSITION
AND SEAL ENDS WITH 2 FULL WRAPS OF TAPE AND METAL OR
NONMETALLIC BAND CLAMP.
INSULATED
FLEXIBLE
DUCT
SUPPLY DIFFUSER
ROUND NECK
INSULATE
BACK OF
DIFFUSER
A
INSTALL FLEX DUCT TO ENSURE
SECURE FASTENING TO
DIFFUSER AND MAXIMUM BEND
RADIUS. PROVIDE RIGID DUCT
AND ELBOW AT DIFFUSER IF
SECURE ATTACHMENT CANNOT
BE ACHIEVED.
SECURE INSULATED
SHEET METAL 90°
ELBOW TO DIFFUSER
HIGH−EFFICIENCY TAKE−OFF. SEAL
PERIMETER OF FLANGE AT ATTACHMENT
POINT TO MAIN DUCT WITH DUCT
SEALANT. REFER TO SPECIFICATIONS
DUCT
INSULATION
VOLUME DAMPER IN HIGH−EFFICIENCY
TAKE−OFF, OR PROVIDE IN RIGID DUCT
RUNOUT TO DIFFUSER. PROVIDE 2"
INSULATION STANDOFF. INSTALL DAMPER AS
CLOSE TO MAIN DUCT AS POSSIBLE.
RETURN OR
EXHAUST DUCT
RIGID
RUNOUT AS
REQUIRED
RETURN GRILLE
CEILING
INSULATED FLEXIBLE DUCT. MAXIMUM LENGTH OF FLEXIBLE
DUCT TO BE 8’−0". PROVIDE RIGID RUNOUT TO POINT WHERE
FLEXIBLE DUCT MAX LENGTH CAN BE MAINTAINED. SUPPORT
FLEXIBLE DUCT FROM STRUCTURE, REFER TO
SPECIFICATIONS FOR REQUIREMENTS
A
IR
F L O
W
ROUND DUCT
COLLAR
PLENUM. SIZE TO
MATCH GRILLE DUCT
CONNECTION SIZE
FASTEN DUCT
TO GRILLE
DUCTED RETURN OR EXHAUST GRILLE DETAIL7
M303 NO SCALE
INSULATE
PLENUM
GENERAL NOTES:
1. DUCT TAPES SHALL BE LISTED AND LABELED IN ACCORDANCE WITH STANDARD
UL 181B AND MARKED "181B−FX"
2. HIGH EFFICIENCY TAKE−OFF AND RUNOUT MAY BE ROUND OR RECTANGULAR
PROFILE, SEE PLANS FOR SIZE. PROVIDE SQUARE TO ROUND TRANSITION WHERE
RECTANGULAR RUNOUT DUCTS ARE INDICATED.
3. MAXIMUM LENGTH OF FLEXIBLE DUCT TO BE 8’−0". PROVIDE RIGID RUNOUT TO
POINT WHERE FLEXIBLE DUCT MAX LENGTH CAN BE MAINTAINED. SUPPORT
FLEXIBLE DUCT FROM STRUCTURE, REFER TO SPECIFICATIONS FOR
REQUIREMENTS.
4. REFER TO SPECIFICATIONS FOR DUCT SYSTEMS TO BE INSULATED. OMIT
INSULATION WHERE NOT REQUIRED.
A
KEY NOTES:
PEEL BACK OUTER INSULATION OF FLEX DUCT AND SECURE
INNER CORE TO RIGID DUCT OR DUCT COLLAR WITH 2 FULL
WRAPS OF TAPE AND METAL SCREW BAND CLAMP OVER
TAPE. PULL INSULATION AND JACKET BACK INTO POSITION
AND SEAL ENDS WITH 2 FULL WRAPS OF TAPE AND METAL OR
NONMETALLIC BAND CLAMP.
A
UNIT HEATER
HOT WATER SUPPLY
HOT WATER RETURN
TEST PLUG (TYPICAL)
FLOW MEASURING DEVICE
BALANCING VALVE
HORIZONTAL HOT WATER UNIT HEATER PIPING DETAIL1
M303 NO SCALE
2.
NOTES:
SEE NOTE 1 REHEAT COIL
HIGH−EFFICIENCY TAKE−OFF.
VAV TERMINAL
UNIT
SOUND ATTENUATOR
SEE NOTE 2
RIGID DUCT CONNECTION OF 3 DUCT DIAMETERS MINIMUM LENGTH SHALL BE PROVIDED
FOR AIR TERMINAL UNIT INLET DUCT CONNECTION.
USE SOUND ATTENUATOR ONLY IF REQUIRED TO MEET DESIGN ROOM NC LEVEL.
REFER TO SPECIFICATIONS FOR INSULATION REQUIREMENTS.
PROVIDE ACCESS DOOR IN BOX AND AT OUTLET FOR ACCESS TO BOTH SIDES OF
REHEAT COIL.
1.
SUPPLY DUCT
A
IR
F L O
W
TO SUPPLY
AIR OUTLETS
DUCT CONNECTION FOR VAV TERMINAL UNITS8
M303 NO SCALE
3.
ACCESS DOOR.
SEE NOTE 4
ACCESS DOOR.
SEE NOTE 4
4.
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
AIR COMPRESSOR SCHEDULE
TAG MANUFACTURER MODEL #
MAXIMUM CAPACITY RECEIVER ELECTRICAL
NOTES
PRESSURE (PSIG) (ACFM) (GAL.) HP VOLTS PHASE MCA
AC−1 INGERSOLL RAND SS3L3 135 10.3 60 3 230 1 1.
NOTES:
1. SEE SPECIFICATIONS FOR ACCESSORIES.
PUMP SCHEDULE
UNIT UNIT
FLUID TYPE
FLUID
TEMP.
HEAD MOTOR VFD PUMP MANUFACTURER
NO. LOCATION SERVICE TYPE GPM (FT.) HP VOLT PH USE RPM & MODEL NO. NOTES
HWP−1 BOILER RM BLR LOOP PG50 180 HES 414 66 15 208 3 Y 1750 BELL & GOSSETT 1510 3BC
HWP−2 BOILER RM BLR LOOP PG50 180 HES 414 66 15 208 3 Y 1750 BELL & GOSSETT 1510 3BC
CWP−1 HD HOUSE COND LOOP PG50 95 HES 75 40 2 208 3 N 1750 BELL & GOSSETT 1510 1−1/4AC
CWP−2 HD HOUSE COND LOOP PG50 95 HES 75 40 2 208 3 N 1750 BELL & GOSSETT 1510 1−1/4AC
NOTES: HES HORIZONTAL END SUCTION
1. PROVIDE SHAFT GROUNDING KITS FOR MOTORS USED HSC HORIZONTAL SPLIT CASE
WITH VARIABLE FREQUENCY DRIVES IL IN LINE
VT VERTICAL TURBINE
SUB SUBMERSIBLE
SP SUMP PUMP
W WATER
PG PROPYLENE GLYCOL (NUMBER
FOLLOWING INDICATES PERCENT SOLUTION)
EG ETHYLENE GLYCOL (NUMBER
FOLLOWING INDICATES PERCENT SOLUTION)
HOT WATER SPECIALTIES SCHEDULE
EXPANSION TANKS AIR SEPARATORS RELIEF
FLUID
TYPE
FLUID
TEMP.
UNIT NO.
TOTAL ACCEPT.
TYPE MODEL SIZE GAL GAL NO. MODEL SIZE GPM PSI NOTES
ET−1 H/E D−280V 30"x 76" 211 84 AS−1 RL−6F − 360 30 PG50 180
NOTES: E EXPANSION
1. MODEL NUMBERS TAKEN FROM BELL & GOSSETT CATALOG V VERTICAL
W WATER
PG PROPYLENE GLYCOL (NUMBER
FOLLOWING INDICATES PERCENT SOLUTION)
FIN RADIATION SCHEDULE
COVER COVER COVER TUBE FINS FIN BTU
UNIT FLUID COVER HEIGHT DEPTH LENGTH SIZE PER LENGTH PER TOTAL MANUFACTURER
NO. TYPE TYPE (IN) (IN) (FT) ROWS (IN) FT (FT) FT MBH & MODEL NO. NOTES
FTR−1 PG50 TO 26 5−3/8" PLAN 1 3/4 32 PLAN 990 VARIES RITTLING BG5 1., 2.
NOTES:
1. CAPACITIES BASED ON 170 °F AVG. WATER TO TOP OUTLET
TEMP AND 65 °F EAT BE BARE ELEMENT W/ EXPANDED METAL ENCLOSURE
2. CAPACITIES BASED ON INSTALL HEIGHT OF W−W WALL TO WALL
4" FROM FLOOR TO BOTTOM OF UNIT. W WATER
PG PROPYLENE GLYCOL
(NUMBER FOLLOWING INDICATES PERCENT SOLUTION)
UNIT HEATER SCHEDULE
UNIT UNIT OUTPUT MOTOR FLUID GPM MANUFACTURER
NO. LOCATION. TYPE CFM EAT LAT MBH HP VOLT PH EWT LWT TYPE RECESS & MODEL NO. NOTES
CUH−1 ENTRY R 185 60 135 15 1/15 120 1 180 160 PG50 1.5 R AIRTHERM RWI−1130−02
CUH−2 NE CORR SR 185 60 135 15 1/15 120 1 180 160 PG50 1.5 R AIRTHERM RWI−1130−02
UH−1 BLR CORR SUH 395 60 95 13 9W 120 1 180 160 PG50 1.3 − AIRTHERM HA−018B
UH−2 GH SUH 1100 60 104 47 1/20 120 1 180 160 PG50 5.3 − AIRTHERM HA−072B
UH−3 GH SUH 1100 60 104 47 1/20 120 1 180 160 PG50 5.3 − AIRTHERM HA−072B
NOTES: W WATER
1. SR SEMI RECESSED
SUH SUSPENDED UNIT HEATER
PG PROPYLENE GLYCOL
(NUMBER FOLLOWING INDICATES PERCENT SOLUTION)
CLOSED CIRCUIT COOLER SCHEDULE
UNIT EAT EWT LWT NOM. MOTOR MANUFACTURER &
NO. ( °F WB) ( °F) ( °F) GPM TONS CFM HP VOLT PH MODEL NO. NOTES
C−1 78 97 85 75 33.4 24,440 7.5 208 3 EVAPCO ATWB 4−4F12−Z 1
NOTES:
1. SEE DETAIL 2/M304 FOR STRUCTURAL MODIFICATIONS TO BUILDING.
HEATING COIL SCHEDULE
UNIT MAX EAT MAX FLUID TOTAL MANUFACTURER
UNIT NO. SERVED CFM APD DB WB LAT GPM WPD EWT LWT TYPE MBH & MODEL NO. NOTES
HC−1 RTU−1 14000 .09 15 80 110 8.5 180 160 PG50 987 INNOVENT
NOTES: W WATER
1. PG PROPYLENE GLYCOL
(NUMBER FOLLOWING INDICATES PERCENT SOLUTION)
EG ETHYLENE GLYCOL
(NUMBER FOLLOWING INDICATES PERCENT SOLUTION)
COOLING COIL SCHEDULE
COIL UNIT MAX EAT LAT MAX FLUID TOTAL SENS. MANUFACTURER
UNIT NO. TYPE SERVED CFM APD DB WB DB WB EER WPD EWT LWT TYPE MBH MBH & MODEL NO. NOTES
CC−1 DX RTU−1 14000 1.15 85.5 71.4 54.6 54.2 10.55 − − − DX 791 470 INNOVENT 1.
NOTES: DX DIRECT EXPANSION
1. PROVIDE 4 CIRCUITS OF COOLING WITH MODULATING W WATER
COMPRESSOR. PG PROPYLENE GLYCOL (NUMBER FOLLOWING INDICATES PERCENT SOLUTION)
EG ETHYLENE GLYCOL (NUMBER FOLLOWING INDICATES PERCENT SOLUTION)
AIR HANDLING UNIT SCHEDULE
FAN SECTION DATA MIN
UNIT UNIT FAN WHEEL BLADE TOTAL COOLING HEATING OA MANUFACTURER
NO. LOCATION. TYPE SECTION DIA TYPE VFD CFM ESP HP VOLTS PH COIL COIL CFM & MODEL NO. NOTES
RTU−1
ROOF
DT
SUPPLY 30 AF Y 14000 5.3 20 208 3
CC−1 HC−1 1100 INNOVENT CAHU−1C
RETURN 33 AF Y 14000 1.8 7.5 208 3
NOTES: H HORIZONTAL
1. FILTERS PROVIDED BY AHU MANUFACTURER, FOR MOUNTING IN AIR HANDLER CASING. SEE PLANS FOR AIR HANDLER V VERTICAL
ARRANGEMENT AND FILTER LOCATION. REFER TO SPECIFICATIONS FOR FILTER TYPES. AF AIRFOIL
PROVIDE 42 INCH TALL ENGINEERED CURB. PROVIDE MERV 8 PREFILTERS AND MERV 13 FINAL FILTERS. DT DRAW THRU
PROVIDE SOUND ATTENUATORS IN ROOF CURB. MZ MULTI ZONE
BT BLOW THRU
BOILER SCHEDULE
UNIT HEATING FIRING RATE NET ELECTRICAL MANUFACTURER
NO. MEDIUM TYPE FUEL MBH GPH MBH HP VOLTS PH & MODEL NO. NOTES
B−1 PG50 W NG 3000 2610 AERCO BMK3.0 1
B−2 PG50 W NG 3000 2610 AERCO BMK3.0 1
NOTES: W WATER
1. CONTROL BY BUILDING AUTOMATION SYSTEM. S STEAM
CI CAST IRON
FT FIRETUBE
WT WATERTUBE
NG NATURALGAS
O OIL
P PROPANE
E ELECTRIC
ELEMENT. PITCH UP IN
DIRECTION OF FLOW
ECCENTRIC REDUCER IF
REQUIRED
UNION (TYPICAL)
CONTROL VALVE
SHUT−OFF VALVE WITH
TEE HANDLE (TYPICAL)
SUPPLY RUNOUT, IF
DOWNFEED
CONCENTRIC REDUCER IF
REQUIRED
COVER
PROVIDE ACCESS DOORS
IN FRONT OF VALVES
SUPPLY
RETURN
NOTES:
1. REFER TO SCHEDULES AND SPECIFICATIONS FOR CABINET AND COVER TYPE AND INSTALLATION REQUIREMENTS.
2. ELEMENTS IN SERIES REQUIRE ACCESSORIES AT EACH END OF SERIES ONLY.
3. INTERCONNECTING PIPING BETWEEN ELEMENTS TO BE SAME SIZE AS ELEMENT TUBE.
TYPICAL HOT WATER FINNED−TUBE RADIATION DETAIL1
M304 NO SCALE
DIFFUSER, REGISTER AND GRILLE SCHEDULE
UNIT NECK MODULE THROW MANUFACTURER
NO. TYPE SIZE SIZE (1) NC MOUNTING OBD & MODEL NO. NOTES
S−1 REG SEE PLAN 24X24 <30 SEE PLAN N TITUS TMSA
S−2 REG − 12X12 21 <30 SUR N TITUS 301RL
R−1 GR − 24X24 −− <30 LIT N TITUS 50F
R−2 GR − 24X12 −− <30 LIT N TITUS 50F
R−3 GR − 48X10 −− <30 SUR N TITUS 350FL
NOTES: RCD ROUND CEILING DIFFUSER
1. THROW BASED ON TERMINAL VELOCITY SUR SURFACE MOUNT
OF 50 FPM REG REGISTER
GR GRILLE
OBD OPPOSED BLADE DAMPER
GYP GYPSUM WALL OR CEILING
LIT LAY−IN TILE
CB CONCRETE BLOCK
VARIABLE AIR VOLUME TERMINAL UNIT SCHEDULE
UNIT INLET OUTLET HEATING CFM COOLING CFM MAX TOTAL MAX FLUID MANUFACTURER
NO. SIZE SIZE MAX MIN MAX MIN APD EAT LAT MBH EWT LWT GPM WPD TYPE & MODEL NO. NOTES
VAV−1 5" 12"x8" 270 54 270 54 1.0 − − − − − − − − TITUS DESV 1
VAV−2 5" 12"x8" 270 54 270 54 − − − − − − − − − TITUS DESV 1
VAV−3 5" 12"x8" 270 54 270 54 − − − − − − − − − TITUS DESV 1
VAV−4 5" 12"x8" 270 54 270 54 − − − − − − − − − TITUS DESV 1
VAV−5 5" 12"x8" 370 74 370 74 − − − − − − − − − TITUS DESV 1
VAV−6 5" 12"x8" 270 54 270 54 − − − − − − − − − TITUS DESV 1
VAV−7 7" 12"x10" 550 110 550 110 − − − − − − − − − TITUS DESV 1
VAV−8 9" 14"x13" 1000 300 1000 300 0.6 55.0 114.0 16.6 180 148 1.3 0.6 PG50 TITUS DESV 2
VAV−9 10" 14"x13" 1080 324 1080 324 0.4 55.0 114.0 19.9 180 141 1.3 0.3 PG50 TITUS DESV 2
VAV−10 5" 12"x8" 300 90 300 90 0.1 55.0 100.0 4.2 180 142 0.3 0.1 PG50 TITUS DESV
VAV−11 5" 12"x8" 300 90 300 90 0.1 55.0 100.0 4.2 180 142 0.3 0.1 PG50 TITUS DESV
VAV−12 8" 12"x10" 680 204 680 204 0.2 55.0 84.0 6.2 180 125 0.3 0.2 PG50 TITUS DESV
VAV−13 12" 16"x15" 1720 430 1720 430 0.5 55.0 114.0 30.0 180 139 1.9 0.8 PG50 TITUS DESV 2
VAV−14 10" 14"x13" 960 240 960 240 0.2 55.0 95.0 11.8 180 155 1.2 0.3 PG50 TITUS DESV
VAV−15 8" 12"x10" 780 195 780 195 0.3 55.0 109.0 11.5 180 129 0.6 0.1 PG50 TITUS DESV 2
VAV−16 14" 20"x18" 2000 600 2000 600 0.7 55.0 100.0 46.9 180 138.8 2.9 1.8 PG50 TITUS DESV 2
VAV−17 14" 20"x18" 2000 600 2000 600 1.0 55.0 110.0 57.3 180 127.7 2.8 1.4 PG50 TITUS DESV 3
VAV−18 6" 12"x8" 400 120 400 120 0.1 55.0 100.0 5.6 180 156 0.6 0.2 PG50 TITUS DESV
VAV−19 4" 12"x8" 200 60 200 60 0.0 55.0 120.0 3.4 180 150 0.3 0.1 PG50 TITUS DESV
VAV−20 4" 12"x8" 200 60 200 60 0.0 55.0 120.0 3.4 180 150 0.3 0.1 PG50 TITUS DESV
VAV−21 5" 12"x8" 350 105 350 105 0.1 55.0 106.0 4.0 180 145 0.3 0.1 PG50 TITUS DESV
VAV−22 12" 16"x15" 1500 300 1500 300 − − − − − − − − − TITUS DESV 1
NOTES: W WATER
1 NO REHEAT COIL PG PROPYLENE GLYCOL
2 2 ROW COIL (NUMBER FOLLOWING INDICATES PERCENT SOLUTION)
3 3 ROW COIL
SOUND ATTENUATING UNIT SCHEDULE
DYNAMIC INSERTION LOSS DB
UNIT SIZE OCTAVE BAND & MID−FREQUENCY (CPS)
UNIT CFM MAX 63 125 250 500 1000 2000 4000 8000 MANUFACTURER
NO. SYSTEM DIA L W H [1] APD 1 2 3 4 5 6 7 8 & MODEL NOTES
SA−1 RTU−1 − 36 28.5 61 +14000 0.20 2 5 10 21 16 9 10 8 VIBRO ACOUSTICS RNM−MV−F8
SA−2 RTU−1 − 36 40 40 −14000 0.22 7 6 12 16 14 10 8 7 VIBRO ACOUSTICS RNM−MV−F6
NOTES:
1 A [+] SYMBOL INDICATES SOUND PATH SAME AS AIR
FLOW DIRECTION, A [−] INDICATES SOUND PATH AGAINST
AIRFLOW DIRECTION
KNOCK OUT FACE SHELL & GROUT FIRST (1)
AVAILABLE FULL CELL SOLID FULL HEIGHT
AT SIDE OF DOOR FARTHEST FROM BEAM EXISTING STEEL BEAM
KNOCK OUT FACE SHELL & GROUT FIRST (2)
AVAILABLE FULL CELLS SOLID FULL HEIGHT
AT SIDE OF DOOR CLOSEST TO BEAM
(2) 5 8"Ø x 6" TITEN HD SCREW IN
ANCHORS CENTERED ON EACH
GROUTED CORE AS SHOWN BELOW
NEW C8x11.5 STEEL CHANNEL
INSTALLED TIGHT TO
EXISTING STEEL BEAM
2" MIN.
LINTEL DETAIL FOR BOILER ROOM DOORWAY2
M304 3/4" = 1’−0"
D A
U S
Web: www.ulteig.com
3350 38th Avenue South
Phone: 701.280.8500
Fargo, North Dakota 58104
Ulteig Project: 09.01787
Fax: 701.280.8739
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the State of Minnesota.
Print Name:
Signed:
License Number:
| M000.pdf |
| 09.01787 M000.dwg |
| Layout1 |
| M001.pdf |
| 09.01787 M001.dwg |
| Layout1 |
| M101.pdf |
| 09.01787 M101.dwg |
| Layout1 |
| M102.pdf |
| 09.01787 M102.dwg |
| Layout1 |
| M201.pdf |
| 09.01787 M201.dwg |
| Layout1 |
| M202.pdf |
| 09.01787 M202.dwg |
| Layout1 |
| M203.pdf |
| 09.01787 M203.dwg |
| Layout1 |
| M301.pdf |
| 09.01787 M301.dwg |
| Layout1 |
| M302.pdf |
| 09.01787 M302.dwg |
| Layout1 |
| M303.pdf |
| 09.01787 M303.dwg |
| Layout1 |
| M304.pdf |
| 09.01787 M304.dwg |
| Layout1 |