errata_cwc12personbunkhouseaccessretrofit_081211.pdf

PDF 70 KB Posted

Attached to
Cordova Work Center (CWC) 12 Person Bunkhouse Accessibility Retrofit
Solicitation number
AG-0120-S-11-0032
Issued by

About this file

AG-0120-S-11-0032 Errata Sheet CWC 12 Person Bunkhouse Retrofit

View the file

Other files

File Type Posted
AG0120S110032_Amend002_SF30.pdf PDF
AG0120S110032ConfCallAtndeList.pdf PDF
AG0120S110032ConfCall_AgendaMtgNotes.pdf PDF
WDOL_GnlDec_AK1_Mod33_19Aug2011.pdf PDF
AG0120S110032_CWCBunkhouse_SF1442.pdf PDF
AG0120S110032SiteAtndeList083111.pdf PDF
AG0120S110032_Amend001.pdf PDF
AG0120S110032_SiteVisitNotes.pdf PDF
laundry room with floor hatch.JPG JPG image
tv room.JPG JPG image
west end bathroom.JPG JPG image
kitchen 2.JPG JPG image
entry interior.JPG JPG image
exterior1.JPG JPG image
west end from entryway.JPG JPG image
hallway with fire door.JPG JPG image
kitchen 1.JPG JPG image
west end bedroom one of two.JPG JPG image
west end foyer.JPG JPG image
west end shower room.JPG JPG image
entry.JPG JPG image
pantry.JPG JPG image
CRDBunkhouse_final_drawings_061710.pdf PDF
CRDBunkhouse_final_specifications_081211.pdf PDF
AG0120S110032_CWCBunkhouse_ReturnPkg.pdf PDF
revised_M3.00_081211.pdf PDF
revised_E3.00_081211.pdf PDF
AG0120S110032_CWCBunkhouseRFP_FNL.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ERRATA for CWC 12 PERSON BUNKHOUSE ACCESSIBILITY RETROFIT

PAGE # Section Description

DRAWINGS

General Drawings should be to scale if plotted on 11"x17" paper.

Delete "area of limited scope" in the Demolition Legend D1.01

D1.01 Storage area for the old ranges will be in one of the designated rooms on the east side of the building.

D1.01, D1.02

D1.02 Storage area for the old washers and dryers will be in the east entry porch.

A1.00 Dashed circles and dashed squares show wheelchair spaces.

A1.00 D= clothes dryer; W= clothes washer; DW= dishwasher; REF= refrigerator A1.01 Detail 1 Delete "Option A" from title.

A1.40 Chamfer exterior corners and edges of permanently exposed concrete.

A1.40

A2.00 Detail 1

A2.00 Detail 2 Grade is -3'-0".

A2.00 Detail 2

A3.00 Detail 1 Bottom of concrete footing is 5' below grade.

A3.00 Detail 2

A4.01 Detail 2 Concrete stoop is 5" thick.

A5.00 Note 1 Delete "both existing".

A5.00

A5.00 SCW= solid-core door with wood-veneer faces; HM= hollow metal.

A5.20 Change "Additive Bid Item" to "Option Item."

A5.20 Contractor shall submit rubber base color samples for selection by the FS.

A5.20 Wood cabinets: Style is "Frameless." Wood species is Alder. Color is "Natural."

A7.01 Detail 3 Change "2'-10" min. clear" to "2'-9 3/8" min. clear" A7.02 Detail 1 A nailer board is below the flashing and plywood joint.

A7.02 Detail 3

A7.02 Detail 5 Text arrow for "new siding to match existing" should point to the siding, not the sheathing.

A8.00 Detail 4 Delete "coord w/micro"

A8.02 Detail 3 Change "Relocate Closet Units" to "Existing Closet units will be removed before construction."

Storage area for items such as window frames will be in one of the designated rooms on the east side of the building.

Location of new steel bollard needs to be shifted to the west in order to maintain the clearance at the concrete stoop.

Replace the following statement "At Contractors Option- new vinyl siding and window trim to match existing may be provided- contractor shall replace damaged siding due to removal." with "New vinyl siding and window trim to match existing - Contractor shall replace damaged siding due to removal."

Note under Door and Frame Schedule: Delete "verify existing door height, new doors to match height of existing doors"

Contractor shall submit a proposal for a type of fastener that could be used for the new flashing.

The last line under the Demolition Legend notes that "existing GB ceiling to remain patch & repair @new construction. There is no hatch shown. "GB" should be "GWB."

Delete "reinstall existing siding and window trim" and "at contractors option".

Add "Color and style to match existing siding."

Change "sonotube expose 42 minimum" to "concrete pier foundation expose 42" minimum, 5' depth. See Sht S2.00, detail 1".

ERRATA for CWC 12 PERSON BUNKHOUSE ACCESSIBILITY RETROFIT

S1.00 Concrete cover should be 3" under slab and under the footings.

S1.01 Call outs for concrete details are on Sheet S2.00.

M3.00 Replace this mechanical systems plan with attached revised mechanical systems plan.

E3.00 Replace this new electrical plan with attached revised new electrical plan.

Sheet1