AG-0120-S-11-0032 Errata Sheet CWC 12 Person Bunkhouse Retrofit
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AG0120S110032_Amend002_SF30.pdf | ||
| AG0120S110032ConfCallAtndeList.pdf | ||
| AG0120S110032ConfCall_AgendaMtgNotes.pdf | ||
| WDOL_GnlDec_AK1_Mod33_19Aug2011.pdf | ||
| AG0120S110032_CWCBunkhouse_SF1442.pdf | ||
| AG0120S110032SiteAtndeList083111.pdf | ||
| AG0120S110032_Amend001.pdf | ||
| AG0120S110032_SiteVisitNotes.pdf | ||
| laundry room with floor hatch.JPG | JPG image | |
| tv room.JPG | JPG image | |
| west end bathroom.JPG | JPG image | |
| kitchen 2.JPG | JPG image | |
| entry interior.JPG | JPG image | |
| exterior1.JPG | JPG image | |
| west end from entryway.JPG | JPG image | |
| hallway with fire door.JPG | JPG image | |
| kitchen 1.JPG | JPG image | |
| west end bedroom one of two.JPG | JPG image | |
| west end foyer.JPG | JPG image | |
| west end shower room.JPG | JPG image | |
| entry.JPG | JPG image | |
| pantry.JPG | JPG image | |
| CRDBunkhouse_final_drawings_061710.pdf | ||
| CRDBunkhouse_final_specifications_081211.pdf | ||
| AG0120S110032_CWCBunkhouse_ReturnPkg.pdf | ||
| revised_M3.00_081211.pdf | ||
| revised_E3.00_081211.pdf | ||
| AG0120S110032_CWCBunkhouseRFP_FNL.pdf |
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ERRATA for CWC 12 PERSON BUNKHOUSE ACCESSIBILITY RETROFIT
PAGE # Section Description
DRAWINGS
General Drawings should be to scale if plotted on 11"x17" paper.
Delete "area of limited scope" in the Demolition Legend D1.01
D1.01 Storage area for the old ranges will be in one of the designated rooms on the east side of the building.
D1.01, D1.02
D1.02 Storage area for the old washers and dryers will be in the east entry porch.
A1.00 Dashed circles and dashed squares show wheelchair spaces.
A1.00 D= clothes dryer; W= clothes washer; DW= dishwasher; REF= refrigerator A1.01 Detail 1 Delete "Option A" from title.
A1.40 Chamfer exterior corners and edges of permanently exposed concrete.
A1.40
A2.00 Detail 1
A2.00 Detail 2 Grade is -3'-0".
A2.00 Detail 2
A3.00 Detail 1 Bottom of concrete footing is 5' below grade.
A3.00 Detail 2
A4.01 Detail 2 Concrete stoop is 5" thick.
A5.00 Note 1 Delete "both existing".
A5.00
A5.00 SCW= solid-core door with wood-veneer faces; HM= hollow metal.
A5.20 Change "Additive Bid Item" to "Option Item."
A5.20 Contractor shall submit rubber base color samples for selection by the FS.
A5.20 Wood cabinets: Style is "Frameless." Wood species is Alder. Color is "Natural."
A7.01 Detail 3 Change "2'-10" min. clear" to "2'-9 3/8" min. clear" A7.02 Detail 1 A nailer board is below the flashing and plywood joint.
A7.02 Detail 3
A7.02 Detail 5 Text arrow for "new siding to match existing" should point to the siding, not the sheathing.
A8.00 Detail 4 Delete "coord w/micro"
A8.02 Detail 3 Change "Relocate Closet Units" to "Existing Closet units will be removed before construction."
Storage area for items such as window frames will be in one of the designated rooms on the east side of the building.
Location of new steel bollard needs to be shifted to the west in order to maintain the clearance at the concrete stoop.
Replace the following statement "At Contractors Option- new vinyl siding and window trim to match existing may be provided- contractor shall replace damaged siding due to removal." with "New vinyl siding and window trim to match existing - Contractor shall replace damaged siding due to removal."
Note under Door and Frame Schedule: Delete "verify existing door height, new doors to match height of existing doors"
Contractor shall submit a proposal for a type of fastener that could be used for the new flashing.
The last line under the Demolition Legend notes that "existing GB ceiling to remain patch & repair @new construction. There is no hatch shown. "GB" should be "GWB."
Delete "reinstall existing siding and window trim" and "at contractors option".
Add "Color and style to match existing siding."
Change "sonotube expose 42 minimum" to "concrete pier foundation expose 42" minimum, 5' depth. See Sht S2.00, detail 1".
ERRATA for CWC 12 PERSON BUNKHOUSE ACCESSIBILITY RETROFIT
S1.00 Concrete cover should be 3" under slab and under the footings.
S1.01 Call outs for concrete details are on Sheet S2.00.
M3.00 Replace this mechanical systems plan with attached revised mechanical systems plan.
E3.00 Replace this new electrical plan with attached revised new electrical plan.