This document is a bid plan for a state and local contract opportunity to restore various roofs at the Marquette Branch Prison Administration and Brooks Center buildings in Marquette, Michigan. The work involves removing and disposing of existing walkway pads and roof materials down to the existing insulation, inspecting and repairing the roof deck as needed, and installing a new multi-ply fully-adhered 60 mil. reinforced rupture resistant EPDM roofing system with new walkway pads. The project also requires relocating and reinstalling an existing air conditioning unit and security fence, as well as replacing existing turbine vents, roof drain domes/caps, and surface-mounted conduit. The bid opening date is November 11, 2019. Interested parties are encouraged to attend a pre-bid meeting and to verify the meeting has not been postponed due to travel conditions. The contract is for the Marquette Branch Prison, which is located in Delta County and Menominee City, Michigan.
The bid requires pricing for the proposed roofing system and associated work. The contract will be awarded by the Michigan Department of Corrections. No other details about pricing terms, set asides, incumbents, funding sources, or contract amounts are provided in the documents.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Admin 472-19456.JBB (Advertisment).pdf | ||
| LEIN Request REV 09-2019.pdf | ||
| 472-19456.JBB Admin Spec.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R
ID
G E
ADMINISTRATION BUILDING BROOKS CENTER BUILDING
SLOPE SLOPE6
7 3
1 8
9 10 10
22 2 2
129 9
16 16 6
2 2
2 2
6 6
TYP. OF (4)
17171717
15 REMOVE AND DISPOSE OF EXISTING WALKWAY PADS.
1. GENERAL CONTRACTOR TO COORDINATE ALL WORK WITH OWNER.
2. WORK LABELED (NIC), OR OTHERWISE NOT NOTED IS NOT IN CONTRACT FOR ANY ARCHITECTURAL IMPROVEMENTS.
3. THE GENERAL CONTRACTOR & THEIR SUB-CONTRACTORS SHALL VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS WITH CONDITIONS
SHOWN IN THE CONTRACT DOCUMENTS AND SHALL REPORT ANY DEVIATIONS, DISCREPANCIES AND/OR CONFLICTS TO THE ARCHITECT.
4. EXISTING ROOF DRAIN SYSTEMS ARE TO REMAIN FULLY OPERATIONAL / FUNCTIONAL DURING THE RE-ROOFING AND CONTRACTOR IS
RESPONSIBLE FOR PROVIDING TEMPORARY PROTECTION DURING DEMOLITION AND RENOVATION ACTIVITIES.
5. EXISTING ROOF DRAINS ARE TO BE CLEANED AND MAINTAINED FREE OF DEBRIS DURING RE-ROOFING. ALL DRAIN DOMES / CAPS TO BE
REPLACED.
6. EXISTING ROOFING SYSTEM IS TO BE REMOVED DOWN TO THE INSULATION. SEE PLAN FOR LOCATIONS WHERE INSULATION IS TO BE
REPLACED DOWN TO TOP OF EXISTING DECK AND DISCARDED. REPAIR EXISTING DECK AS REQUIRED TO PROCEED. APPROPRIATE
SURFACE TO RECEIVE NEW ROOFING SYSTEM.
7. EXISTING ROOF PENETRATIONS: VENT PIPING, STRUCTURAL SUPPORTS AND MECHANICAL EQUIPMENT THAT WILL NOT BE REUSED ARE
TO BE REMOVED AND DISCARDED. REPAIR ROOF DECKING AND INSTALL NEW ROOFING SYSTEM.
8. PERFORM REMEDIAL REPAIRS AS NECESSARY TO EXISTING ROOF PENETRATIONS, PENETRATION POCKETS, VENT PIPING, CONDUITS
AND ROOF CURBS THAT ARE TO REMAIN TO RECEIVE NEW ROOFING SYSTEM.
9. EXISTING EQUIPMENT SHALL BE REMOVED AS REQUIRED AND APPROPRIATELY STORED ON-SITE FOR REINSTALLATION. CONTRACTOR TO COORDINATE w/ INTERNET PROVIDER TO MINIMIZE DOWNTIME (MAXIMUM OF ONE WEEK OFF-LINE PERMITTED).
10. EXISTING ROOF EXHAUST FANS & CURBS TO REMAIN.
11. CONTRACTOR TO COORDINATE WITH OWNER FOR PLACEMENT OF DUMPSTER AND LOCATION OF STAGING AREA.
12. EXISTING MISCELLANEOUS DEBRIS, ETC. ON THE ROOF IS TO BE REMOVED AND DISCARDED ON A DAILY BASIS.
13. REMOVE ANY CONDENSATE PIPES (WHERE OCCURS) AND MAKE TEMPORARY ACCOMMODATIONS TO PIPES DURING RE-ROOFING.
14. REMOVE ANY FIBER OPTIC CONDUIT (BY CERTIFIED ELECTRICIAN) AND MAKE TEMPORARY ACCOMMODATIONS FOR CONDUIT DURING
RE-ROOFING.
15. ALL DIMENSIONS, EQUIPMENT, PIPES, ETC. ARE TO BE FIELD VERIFIED.
16. CONTRACTOR SHALL ENSURE PROPER STORAGE OF ANY MATERIALS / EQUIPMENT INTENDED TO BE REUSED / REINSTALLED. ANY
MISSING OR DAMAGED ITEMS DUE TO IMPROPER STORAGE, OR BY CONTRACTORS ACTIVITIES, SHALL BE REPLACED BY THE
CONTRACTOR AT NO COST TO THE OWNER.
17. CONTRACTOR SHALL PROVIDE TEMPORARY WEATHER PROOFING AT ALL TIMES SO THAT THE BUILDING SHALL REMAIN OCCUPIED AND
OPERATIONAL AND IN WEATHER TIGHT CONDITION DURING DEMOLITION AND RE-ROOFING.
GENERAL DEMOLITION NOTES
REMOVE EXISTING WALKWAY PADS AND ROOFING MATERIAL DOWN TO EXISTING
INSULATION. INSPECT INSULATION PRIOR TO INTALLING NEW ROOF AND REPORT ANY
DISCREPANCIES AND/OR CONFLICTS TO THE ARCHITECT.
DEMOLITION KEYNOTES
2 EXISTING PLUMBING VENT TO REMAIN.
3 EXISTING 12"Ø TURBINE VENTS TO BE REPLACED.
4 EXISTING 8"Ø VENTS TO REMAIN.
5 EXISTING 14"Ø VENT TO REMAIN.
6 EXISTING CONDUIT TO REMAIN.
MECHANICAL CONTRACTOR TO TEMPORARILY REMOVE EXISTING AIR CONDITIONING
UNIT. REMOVE EXISTING METAL ENCLOSURE AND WOOD BASE / CURB AS REQ'D FOR
ROOF REPLACEMENT.
8 EXISTING SECURITY FENCE AND GATE TO REMAIN. RE-FLASH ALL EXISTING FENCE
POST PIPE SLEEVES.
9 ALL ROOF DRAIN DOMES / CAPS SHALL BE REPLACED. EXISTING ROOF DRAINS ARE TO
BE CLEANED AND MAINTAINED FREE OF DEBRIS DURING RE-ROOFING.
REMOVE EXISTING BALLASTED ROOF SYSTEM DOWN TO EXISTING DECK. INSPECT
DECK PRIOR TO INSTALLING NEW ROOF AND REPORT ANY DISCREPANCIES AND/OR
CONFLICTS TO THE ARCHITECT.
11 REMOVE EXISTING SECURITY FENCE AND (4) ROLLS OF RAZOR WIRE. RE-INSTALL THE
SAME DAY (AFTER NEW ROOFING SYSTEM & FLASHING HAS BEEN INSTALLED).
12 EXISTING EXHAUST FAN TO REMAIN.
EXISTING SURFACE MOUNTED CONDUIT (FOR FIBER OPTIC CABLE) AND CONDUIT
SUPPORTS SHALL BE REMOVED BY CERTIFIED ELECTRICIAN. PROVIDE TEMPORARY
ACCOMMODATIONS AS REQ'D DURING ROOF REPLACEMENT.
PROPOSED STAGING AREA FOR CRANE AND BITUMINOUS ROOF REMOVAL LOCATED
AT EXISTING ACCESS ROAD. SALVAGE ALL REMOVED GRAVEL AND COORDINATE WITH
OWNER FOR ON-SITE STORAGE. NOTE: STAGING AREA SHALL BE CONSIDERED AS A
PART OF THE SECURE AREA.
15 REMOVE AND DISPOSE OF EXISTING WALKWAY PADS.
17 CAUTION! CONTRACTOR SHALL AVOID WALL MOUNTED CONDUIT FOR FIBER OPTIC
CABLE WHEN WORKING ON ROOF FLASHING ALONG BASE OF WALL.
16 CONTINUE ROOFING MEMBRANE UP WALL TO FACE OF WINDOW. PROVIDE FLASHING
ALONG ENTIRE BASE OF WINDOW.
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
© U.P. Engineers & Architects, Inc.
PR
OJ
EC
T
NO
DR
AW
N
BY
CH
EC
KE
D:
AP
PR
OV
ED
DE
SI
GN
ED
B Y:
w w w .u pe a.
co m
IS
SU
ED
F
O R
D
AT
E:
FI
LE
N O
. M D
O C
/1
.J
BB
AD
M
IN
IS
TR
AT
IO
N
B
R O
O K
S C
EN
TE
R
P:
\M
-1
D
TM
B- Ad m in a nd
O D or m
R oo f R ep la ce m en ts \D w gs
\R ev it\ M
-1
R oo f R ep la ce m en t A dm in -B ro ok s_ R
.rv t
1/
/2
:5 5:
A
M
A101
ADMINISTRATION /
BROOKS CENTER
DEMOLITION PLAN
R
ES
TO
R
IN
G
V
AR
IO
U
S R
O O
FS
M.
D.
O.
C.
M
AR
QU
ET
TE
B
RA
NC
H
PR
IS
ON
U S-
M
AR
QU
ET
TE
, M I
M
-1
R M
A K
R C
K A
D
R M
A
R
ES
TO
R
IN
G
V
AR
IO
U
S R
O O
FS
M .D
.O .C
. M
AR
Q U
ET
TE
B R
AN
C
H P
R
IS
O N
3/32" = 1'-0"A1 ADMIN. BUILDING & BROOKS CENTER ROOF DEMOLITION PLAN
NORTH
R
EV
IE
W
/1
1/
R
EV
IE
W
/1 /2
BI
D
D
IN
G
/1 1/
SLOPE
SLOPE
SLO
PE
SLO
PE
SLOPESLOPE
D4 A103
D3 A103
1 1 1
10 10
D2 A103
A1
A103
A1
A103
A1
A103
A1
A103
A1
A103
B4
A103
SIM.
SLOPESLO
PE
SLO
PESLOPE
SLOPE
SLO
PESLOPE
SLO
PE
ADMINISTRATION BUILDING BROOKS CENTER BUILDING
14 14 14 14 14
11 11 11 11 11 11
11 11 11
11 1212
14 12
D3 A103
D3 A103
B3
A103
TYP.
A4
A103
TYP.
A3
A103
SIM.
16 1616
D1
A103
C1
A103
57' - 5"
18 18
SPACING
10' - 0" MAX.
" V
ER
IF
Y
TYP.
1 PROPOSED MULTI-PLY FULLY-ADHERED 60 MIL. REINFORCED RUPTURE RESISTANT EPDM MEMBRANE.
ADMINISTRATION / BROOKS CENTER KEYNOTES
2 NEW WALKWAY PADS ADHERED TO MULTI-PLY FULLY-ADHERED 60 MIL. REINFORCED RUPTURE
RESISTANT EPDM MEMBRANE ON NEW 2" LAYER RIGID INSULATION ON EXISTING ROOF DECK.
3 PROVIDE NEW 12"Ø INTERNALLY BRACED GALV. ALUMINUM TURBINE VENT.
4 EXISTING 8"Ø VENT TO REMAIN.
5 EXISTING 14"Ø VENT TO REMAIN.
6 EXISTING CONDUIT PENETRATION THROUGH ROOF. REFER TO ROOF CONDUIT PENETRATION DETAIL.
RELOCATE EXISTING AIR CONDITIONING UNIT AS REQUIRED TO AVOID SECURITY FENCE INSTALLATION.
MECHANICAL CONTRACTOR SHALL REINSTALL EXISTING AIR CONDITIONING UNIT & METAL FRAMEWORK.
PROVIDE NEW CURB ON EPDM ROOFING SYSTEM. EXTEND REFRIGERANT AND ELEC. LINES AS NEEDED
FOR RELOCATION.
9 EXISTING SECURITY FENCE AND GATE TO REMAIN. RE-FLASH ALL EXISTING FENCE POST PIPE SLEEVES.
10 NEW RETROFIT ROOF DRAIN INSERT WITH DOME AND CLAMPING RING, TYPICAL.
11 EXTEND EXISTING ROOF VENT (AS REQ'D) TO 12" MIN ABOVE ROOF. PROVIDE NEW FLASHING AND WATER
TIGHT CLAMP, TYPICAL.
12 EXISTING EXHAUST FAN ON EXISTING ROOF CURB. CONTINUE NEW ROOFING MEMBRANE UP SIDES OF
ROOF CURB, TYP.
13 EXISTING SURFACE MOUNTED CONDUIT (FOR FIBER OPTIC CABLE) AND CONDUIT SUPPORTS SHALL BE
RE-INSTALLED BY CERTIFIED ELECTRICIAN.
14 PROPOSED 1-1/2" CRICKETING TO PROVIDE ADDITIONAL SLOPE FOR ROOF DRAINAGE.
8 PROVIDE CONTINUOUS STEP FLASHING AND TERMINATION BAR ON STONE WALL IN PREVIOUS STEP
FLASHING LOCATIONS, TYPICAL. PROVIDE 8" MINIMUM COVER, VERT.
15 PROPOSED STAGING AREA FOR CRANE LOCATED AT EXISTING ACCESS DRIVE.
NOTE: STAGING AREA SHALL BE CONSIDERED AS A PART OF THE SECURE AREA.
16 CAUTION! AVOID INTERFERENCE w/ WALL MOUNTED CONDUIT FOR FIBER OPTIC CABLE.
PROVIDE NEW 3"Ø x 14' - 0" LONG GALV. SS40 PIPE FOR PROPOSED SECURITY FENCE POSTS. 10' - 0" MAX.
POST SPACING. REFER TO DETAILS C2 AND C3 ON SHEET A103. ALL FENCE POSTS SHALL BE INSTALLED
BY SECURITY FENCE INSTALLER.
PROVIDE NEW 4"Ø x 14' - 0" LONG GALV. SS40 PIPE FOR PROPOSED SECURITY FENCE. FIXED FENCE POST LOCATIONS SHALL BE INSTALLED AT THE PEAK AND WHERE THE SLOPED ROOF MEETS THE FLAT ROOF.
POSTS SHALL ALIGN WITH GATE POST AT FLAT ROOF. SECURITY FENCE INSTALLATION BY OTHERS.
1. ALL DIMENSIONS SHOWN ARE APPROXIMATE. CONTRACTOR SHALL VIELD VERIFY ALL DIMENSIONS PRIOR TO ORDERING ANY MATERIALS.
2. CONTRACTOR TO COORDINATE WITH OWNER FOR PLACEMENT OF DUMPSTER AND LOCATION OF STAGING AREA.
3. CONTRACTOR IS REQUIPRED TO REMOVE ALL DEBRIS AND TO RESTORE ALL SITE FEATURES, INCLUDING WALKS, DRIVES AND GRASS
AREAS, DISTURBED BY THEIR WORK.
4. CONTRACTOR TO VERIFY NUMBER AND LOCATION OF ALL VENT STACKS, ROOF STRUCTURES, ROOF DRAINS, CONDUIT AND ANY OTHER
OBJECTS OR OBSTRUCTIONS ON THE ROOF THAT WILL AFFECT THE WORK.
5. ALL EXISTING WALKWAY PADS ARE TO BE REMOVED BY THE CONTRACTOR AND TO BECOME PROPERTY OF THE CONTRACTOR.
6. REFER TO ROOF PLAN (AND KEYNOTE #2) FOR LOCATION OF NEW WALKWAY PADS.
7. DRAWINGS ARE DIAGRAMMATICAL. CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONDITIONS AND OBSTRUCTIONS THAT MAY AFFECT
THE WORK.
GENERAL NOTES
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
© U.P. Engineers & Architects, Inc.
PR
OJ
EC
T
NO
DR
AW
N
BY
CH
EC
KE
D:
AP
PR
OV
ED
DE
SI
GN
ED
B Y:
w w w .u pe a.
co m
IS
SU
ED
F
O R
D
AT
E:
FI
LE
N O
. M D
O C
/1
.J
BB
AD
M
IN
IS
TR
AT
IO
N
B
R O
O K
S C
EN
TE
R
P:
\M
-1
D
TM
B- Ad m in a nd
O D or m
R oo f R ep la ce m en ts \D w gs
\R ev it\ M
-1
R oo f R ep la ce m en t A dm in -B ro ok s_ R
.rv t
1/
/2
2:
:0
PM
A102
ADMINISTRATION /
BROOKS CENTER
ROOF PLAN
R
ES
TO
R
IN
G
V
AR
IO
U
S R
O O
FS
M.
D.
O.
C.
M
AR
QU
ET
TE
B
RA
NC
H
PR
IS
ON
U S-
M
AR
QU
ET
TE
, M I
M
-1
R M
A K
R C
K A
D
R M
A
R
ES
TO
R
IN
G
V
AR
IO
U
S R
O O
FS
M .D
.O .C
. M
AR
Q U
ET
TE
B R
AN
C
H P
R
IS
O N
3/32" = 1'-0"A1 ADMIN. BUILDING & BROOKS CENTER ROOF PLAN
NORTH
R
EV
IE
W
/1
1/
R
EV
IE
W
/1 /2
BI
D
D
IN
G
/1 1/
XXXXXXXXXXXXXX
Center Line of Drain
NEW RETROFIT ROOF
DRAIN & DOME
PROPOSED 2" RIGID INSULATION,
TAPERED @ ROOF DRAIN
FULLY-ADHERED EPDM
ROOFING SYSTEM
EXISTING CONC.
ROOF DECK
EXISTING TAPERED
INSULATION
EXISTING DRAIN PIPE
NEW CLAMPING RING
NEW
RETROFIT ROOF
DRAIN INSERT
WATER
CUT-OFF
MASTIC
EDGE OF DEPRESSED AREA
2' - 6"
EXISTING (2) LAYERS 1" INSUL.
ON TAPERED INSUL.
M
IN
1'
- 4
M
IN
8"
LAP
SEALANT
Center Line of Pipe
EXISTING CONC. ROOF DECK
EXISTING VENT PIPE
24GA. GALVANIZED STEEL COUNTER-
FLASHING BY ROOFING CONTRACTOR
FULLY-ADHERED EPDM ROOFING SYSTEM ON
PROPOSED 2" RIGID INSULATION ON EXISTING
(2) LAYERS 1" INSUL. ON TAPERED INSUL.
GALVANIZED STEEL COUNTERFLASHING BY ROOFING CONTRACTOR
WATER CUT-OFF MASTIC w/ WATER TIGHT NOSE CLAMP Center Line of Conduit
EXISTING 1-1/2"Ø UP TO 6"Ø VENT PIPE
WATER TIGHT NOSE CLAMP
FULLY-ADHERED EPDM ROOFING
SYSTEM ON PROPOSED 2" RIGID
INSULATION ON EXISTING (2) LAYERS
1" INSUL. ON TAPERED INSUL.
25GA. GALVANIZED STEEL FLASHING
BY ROOFING CONTRACTOR
EXISTING CONC. ROOF DECK
EXISTING VENT PIPE
WATER
CUT-OFF MASTIC
4" M
IN
1'
- 0
ADJACENT STONE BUILDING,
NOT IN SCOPE OF WORK
PROVIDE CONTINUOUS HEAVY
APPLICATION OF SEALANT @ TOP
TERMINATION BAR
BONDING ADHESIVE
1 1/2" RIGID INSULATION
(HEIGHT VARIES)
PROPOSED 2" RIGID INSULATION
EXISTING (2) LAYERS 1" RIGID INSULATION ON
EXISTING TAPERED INSUL. ON CONCRETE ROOF DECK
FULLY-ADHERED 60 MIL. REINFORCED
RUPTURE RESISTANT EPDM MEMBRANE,
WRAP ALL EXPOSED AREAS
FASTENERS @ 12" O.C. AS REQ'D
CAUTION! AVOID INTERFERENCE
w/ WALL MOUNTED CONDUIT FOR
FIBER OPTIC CABLE
NOTE: NO WALL MOUNTED
CONDUIT AT SIMILAR CONDITION
REGLET FLASHING
IN
W
AL
L
FO
R
NE
W
F
LA
SH
IN
G
HE
IG
HT
V
AR
IE
S, U
SE
E
XI
ST
IN
G
RE
CE
SS
ADHERE RIGID INSUL. TO STONE WALL
w/ CONSTRUCTION ADHESIVE
EXISTING CONC.
ROOF DECK
MULTI-PLY FULLY-ADHERED 60 MIL.
REINFORCED RUPTURE RESISTANT
EPDM MEMBRANE ON PROPOSED
2" RIGID INSULATION
ROOF FLASHING
CANT STRIP /
DIVERTER
SEALANT
EXISTING ROOF TOP UNIT TO REMAIN
(SEE ROOF PLAN)
CONTINUE ROOFING MEMBRANE UP CURB, TYP.
TERMINATE PER MANUF'R RECOMMENDATIONS
EXISTING (2) LAYERS 1" RIGID
INSUL. ON TAPERED INSUL.
EXISTING SECURITY
FENCE MOUNTING
BRACKET
EXISTING SECURITY FENCE
AND FRAMEWORK
X X
X X
X
MULTI-PLY FULLY-ADHERED 60 MIL.
REINFORCED RUPTURE RESISTANT
EPDM MEMBRANE ON PROPOSED
2" RIGID INSULATION
EXISTING (2) LAYERS 1" RIGID INSUL.
ON EXISTING TAPERED INSUL.
EXISTING CONCRETE ROOF DECK
PROPOSED EXTRUDED
ALUM. BASE SHOE
ALUM. FASCIA,
FASTEN PER MANUF'R
RECOMMENDATIONS
PROPOSED 2x4 TREATED WOOD
BLOCKING ON PROPOSED 1/2"
TREATED PLYWOOD ON
EXISTING WOOD BLOCKING
PROPOSED 2x4
TREATED WOOD
BLOCKING
6"
EXISTING WALL
NEW EPDM ROOFING STRIP w/ FASTENING PLATE
& ADHESIVE, PER MANUF'R REQUIREMENTS
REMOVE EXISTING RAZOR WIRE TO ALLOW
FOR NEW ROOFING MEMBRANE. RE-INSTALL
THE SAME DAY PER MANUF'R REQUIREMENTS
1-1/2" GALV. WIRE STAPLES,
(2) PER COIL. MATCH
EXISTING GAUGE
PROPOSED 2x6 TREATED
WOOD BLOCKING
CONTRACTOR FORMED ALUM. FASCIA
TO MATCH ADJACENT FASCIA
CONTRACTOR FORMED ALUM.
(PROFILE TO MATCH EXISTING)
EXISTING WALL
MULTI-PLY FULLY-ADHERED 60 MIL. REINFORCED
RUPTURE RESISTANT EPDM MEMBRANE ON
PROPOSED 2" RIGID INSULATION
EXISTING (2) LAYERS 1" RIGID INSUL.
ON EXISTING TAPERED INSUL.
EXISTING WD BLOCKING w/
GALVANIZED SCREW FASTENERS
LAP SEALANT
NEW 2x TREATED WOOD BLOCKING, AS REQ'D
EXISTING WALL
EXISTING FASCIA BOARD
PROVIDE NEW FASCIA BOARD
w/ WEEP HOLES @ 6"O.C.
PROPOSED 2" RIGID INSULATION
MULTI-PLY FULLY-ADHERED 60
MIL. REINFORCED RUPTURE
RESISTANT EPDM MEMBRANE
PROPOSED RUBBER WALKWAY PADS
ADHERED TO NEW ROOFING MEMBRANE
EXISTING 2x4 TREATED WOOD
BLOCKING, REPAIR AS REQ'D
SEALANT
OVERLAP
6" MIN.
MULTI-PLY FULLY-ADHERED
60 MIL. REINFORCED RUPTURE
RESISTANT EPDM MEMBRANE
MULTI-PLY FULLY-ADHERED
60 MIL. REINFORCED RUPTURE
RESISTANT EPDM MEMBRANE
PRIMER / ADHESIVE
EPDM SEAM TAPE
PRIMER / ADHESIVE NOTE: SPLICE AREA MUST BE
CLEAN PRIOR TO ATTACHMENT
Center Line of Conduit
COUNTERFLASHING
FULLY-ADHERED EPDM ROOFING
SYSTEM ON PROPOSED 2" RIGID
INSULATION ON EXISTING (2) LAYERS
1" INSUL. ON TAPERED INSUL.
2x6 TREATED
WOOD BLOCKING
M
IN
8"
LAP
SEALANT
EXISTING CONDUIT
EXISTING CONC. ROOF DECK
EXISTING ROOF
STRUCTURE
MULTI-PLY FULLY-ADHERED
60 MIL. REINFORCED
RUPTURE RESISTANT
EPDM MEMBRANE
ROOF FLASHING
CANT STRIP / DIVERTER
SEALANT
EXISTING AIR CONDITIONING
UNIT TO BE REINSTALLED
WRAP ROOFING MEMBRANE
UP AND OVER PROPOSED
CURB, TYP.
EXISTING RIGID INSUL.
PROPOSED ROOF PAVERS
PROPOSED 2" RIGID
INSULATION
X X
2" 2"
EXISTING SECURITY FENCE & POST(S) CLEARANCE REDUCED TO 2" FROM
ADDED RIGID INSUL., MAINTAIN
APPROPRIATE CLEARANCE @ GATE
RUBBER WALKWAY PADS
ADHERED TO NEW MULTI-PLY
FULLY-ADHERED 60 MIL.
REINFORCED RUPTURE
RESISTANT EPDM MEMBRANE
ON PROPOSED 2" RIGID INSUL.
EXISTING ROOF STRUCTURE
EXISTING RIGID INSUL.
EXISTING ROOF
STRUCTURE
EXISTING TAPERED
RIGID INSUL.
EXISTING (2) LAYERS 1" RIGID INSUL.
ON EXISTING TAPERED INSUL.
MULTI-PLY FULLY-ADHERED 60 MIL.
REINFORCED RUPTURE RESISTANT
EPDM MEMBRANE ON PROPOSED
2" RIGID INSULATION
PROVIDE NEW BOOT & CLAMP @ EXISTING
PIPE SLEEVE FOR SECURITY FENCING
PROVIDE WATERTIGHT SEAL & CLAMP
PROVIDE WATERTIGHT SEAL
EXISTING CONC.
ROOF STRUCTURE
EXISTING RIGID INSUL.
PROPOSED 2" RIGID INSULATION
MULTI-PLY FULLY-ADHERED 60
MIL. REINFORCED RUPTURE
RESISTANT EPDM MEMBRANE
PROPOSED ROOF PAVERS
CUT TO FIT AROUND
FENCE POST & BOOT
PROVIDE NEW BOOT & CLAMP
PROVIDE WATERTIGHT SEAL
3"Ø GALV. SS40 LINE POST OR
4"Ø GALV. SS40 TERMINAL
POST, SEE PLANS
CUT-OUT 12" x 12" PORTION OF EXISTING
INSULATION TO EXPOSE ROOF DECK FOR
SECURITY FENCE INSTALLATION. FILL
VOID w/ NEW RIGID INSULATION AS REQ'D
METAL CAP WELDED TO
TOP OF POST, TYP.
NOTE: ALL FENCE POSTS
SHALL BE INSTALLED BY
SECURITY FENCE INSTALLER.
RE
QU
IR
ED
OPENING TO CONC. DECK
1' - 0" x 1' - 0"
1/2"Ø x 3" LONG EXP. ANCHOR BOLTS w/ EPOXY, TYP. OF (4)
3"Ø OR 4"Ø FENCE POST
WELDED TO BASE PLATE
1/2"Ø x 3" LONG EXP. ANCHOR BOLTS w/ EPOXY, TYP. OF (4)
1 1/2" 5" 1 1/2"
8"
1/
2" 5"
1/
2"
8"
8" x 8" x 1/4" STEEL BASE PLATE
PROVIDE SEALANT UNDER BASE
PLATE PRIOR TO INSTALLATION
1 2 3 4 5
1 2 3 4 5
D
C
B
A
D
C
B
A
© U.P. Engineers & Architects, Inc.
PR
OJ
EC
T
NO
DR
AW
N
BY
CH
EC
KE
D:
AP
PR
OV
ED
DE
SI
GN
ED
B Y:
w w w .u pe a.
co m
IS
SU
ED
F
O R
D
AT
E:
FI
LE
N O
. M D
O C
/1
.J
BB
AD
M
IN
IS
TR
AT
IO
N
B
R O
O K
S C
EN
TE
R
P:
\M
-1
D
TM
B- Ad m in a nd
O D or m
R oo f R ep la ce m en ts \D w gs
\R ev it\ M
-1
R oo f R ep la ce m en t A dm in -B ro ok s_ R
.rv t
1/
/2
2:
:4
PM
A103
ROOF DETAILS
R
ES
TO
R
IN
G
V
AR
IO
U
S R
O O
FS
M.
D.
O.
C.
M
AR
QU
ET
TE
B
RA
NC
H
PR
IS
ON
U S-
M
AR
QU
ET
TE
, M I
M
-1
R M
A K
R C
K A
D
R M
A
R
ES
TO
R
IN
G
V
AR
IO
U
S R
O O
FS
M .D
.O .C
. M
AR
Q U
ET
TE
B R
AN
C
H P
R
IS
O N
1 1/2" = 1'-0"B3 ROOF DRAIN DETAIL
1 1/2" = 1'-0"A3 ROOF DETAIL @ SMALL VENT PIPE
1 1/2" = 1'-0"A4 ROOF DETAIL @ LARGE VENT PIPE
3" = 1'-0"A1 TERMINATION DETAIL 1
1 1/2" = 1'-0"B4 ROOF CURB DETAIL
1 1/2" = 1'-0"D4 ROOF EDGE @ BROOKS BLDG.
3" = 1'-0"D3 ROOF EDGE @ BROOKS BLDG.
1 1/2" = 1'-0"D2 ROOF EDGE @ ADMIN BLDG.
NOT TO SCALEB2 EPDM SEAM DETAIL
1 1/2" = 1'-0"A2 ROOF CONDUIT PENETRATION DETAIL
1 1/2" = 1'-0"D1 DETAIL @ ROOF CURB
1 1/2" = 1'-0"C1 TRANSITION DETAIL
1 1/2" = 1'-0"C2 SECURITY FENCE POST DETAIL
3" = 1'-0"C3 BASE PLATE DETAIL
R
EV
IE
W
/1
1/
R
EV
IE
W
/1 /2
BI
D
D
IN
G
/1 1/
| M12-19570 Admin Brooks__G001 (signed) |
| M12-19570 Admin Brooks_A101 |
| Sheets |
| A101 - ADMINISTRATION / BROOKS CENTER DEMOLITION PLAN |
| M12-19570 Admin Brooks_A102 |
| Sheets |
| A102 - ADMINISTRATION / BROOKS CENTER ROOF PLAN |
| M12-19570 Admin Brooks_A103 |
| Sheets |
| A103 - ROOF DETAILS |