This is a mechanical equipment schedule and specification document for the Building 42 Tunnel Ventilation project at the National Institute of Standards and Technology (NIST) in Boulder, Colorado.
The document specifies three categories of mechanical equipment required for the tunnel ventilation system. The Automatic Air Damper Schedule requires six Greenheck VCD-20 dampers, each 24x18 inches with a maximum capacity of 2,000 CFM at 600 FPM velocity and 24V actuators. All dampers shall be normally closed with positive feedback actuators, and their mounting must be coordinated with the controls contractor. The Direct Fired Gas Make Up Air Unit Schedule specifies one Greenheck DGX unit (designation 42-MAU-001) capable of 12,000 CFM total at 5,280 feet elevation with a 5 HP direct-drive fan operating at 1,272 RPM. This unit includes direct gas heating with 1,200.0 MBH input and 1,104.0 MBH output, operating at 5 PSIG gas pressure, with a MERV-8 filter and 480/3 voltage configuration. The Unit Heater Schedule (Electric) requires three Indeeco UHIR electric unit heaters (designations 42-T-UH-001 through 42-T-UH-003), each rated at 10.0 KW, 480/3 voltage, 12.4 total amps, with horizontal discharge at 9-foot mounting height. All three unit heaters require cantilever arm mounting, power disconnect switches, integration with the building JCI control system, and 2-stage control capability. The design approval date is 3/10/2026.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Specifications.zip | ZIP file | |
| DRAFT SOW - Steam Tunnel Ventilation.docx | DOCX document | |
| 001000 General Contractor Requirements and Site Standards.zip | ZIP file | |
| Additional Tunnel Heating-M-1.pdf | ||
| Additional Tunnel Heating-M-2.pdf | ||
| Additional Tunnel Heating-M-3.pdf | ||
| 01A NIST Boulder General Contractor Requirements.pdf | ||
| Additional Tunnel Heating-M-0.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
AUTOMATIC AIR DAMPER SCHEDULE
DESIGNATION
AAD-1
AAD-2
AAD-3
AAD-4
AAD-5
AAD-6
MANUFACTURER
GREENHECK
GREENHECK
GREENHECK
GREENHECK
GREENHECK
GREENHECK
MODEL
VCD-20
VCD-20
VCD-20
VCD-20
VCD-20
VCD-20
SIZE
24X18
24X18
24X18
24X18
24X18
24X18
MAX. CFM
2,000
2,000
2,000
2,000
2,000
2,000
VELOCITY
600 FPM
600 FPM
600 FPM
600 FPM
600 FPM
600 FPM
ACTUATOR
24V
24V
24V
24V
24V
24V
NOTES:
DAMPERS SHALL BE NORMALLY CLOSED
COORDINATE ACTUATOR MOUNTING WITH CONTROLS CONTRACTOR
PROVIDE ACTUATORS WITH POSITIVE FEEDBACK
DIRECT FIRED GAS FIRED MAKE UP AIR UNIT SCHEDULE
SUPPLY FAN DATA
DESIGNATION
42-MAU-001
MANUF.
GREENHECK
MODEL
DGX
CFM TOTAL
@ 5280'
12,000 12,000 0.25
DRIVE TYPE
DIRECT
APPROX. RPM
1,272
MIN. FAN
HP
EAT
°F DB
0.7
LAT
% EFF.
°F DB
104.0 92 1,200.0
MBH INPUT
GAS DIRECT HEATING DATA
MBH OUTPUT
@ 5280'
1,104.0
GAS PRESSURE
5 PSIG
FILTER DATA
PLENUM
TYPE
MERV-8 24
OPER. WEIGHT
(LBS.)
1,450
VOLTAGE/
PHASE
480/3
CURB HEIGHT.
CFM OA
@ 5280'
ESP
UNIT HEATER SCHEDULE (ELECTRIC)
DESIGNATION
42-T-UH-001
42-T-UH-002
42-T-UH-003
MANUFACTURER
INDEECO
INDEECO
INDEECO
MODEL
UHIR
UHIR
UHIR
DISCHARGE
HORIZONTAL
HORIZONTAL
HORIZONTAL
MOUNTING
HEIGHT
9 FT
9 FT
9 FT
KW
10.0
10.0
10.0
VOLTAGE/
PHASE
480/3
480/3
480/3
TOTAL AMPS
12.4
12.4
12.4
NOTES
REFER TO BELOW
REFER TO BELOW
REFER TO BELOW
PROVIDE CANTILEVER ARM
NOTES
PROVIDE POWER DISCONNECT SWITH
UNIT CONTROLLED BY BUILDING JCI CONTROL SYSTEM
PROVIDE 2 STAGE CONTROL
SHEET NUMBER
PROJECT NAME of
325 BROADWAY BOULDER, COLORADO 80305-3328
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY
DATEDESIGN APPROVAL
BOULDER DESIGN AND CONSTRUCTION DIVISION
DATESUPV.BYDESCRIPTIONREVISION
3 DRAFTING
ADDITIONAL TUNNEL HEAT
COOK
BUILDING 42 TUNNEL VENTILATION
3/10/2026
M-4COOK
| Sheets and Views |
| M-4 |
File details come from the government source that posted it. Updated .