Addendum Four .pdf

PDF 673 KB Posted

Attached to
RFB-266-25 Maintenance Facility Renovation Madisonville KY
Solicitation number
RFB 785 2500000732 7
Issued by
Hardin County, Kentucky

About this file

This is Addendum Four to Invitation to Bid No. RFB-266-25 issued by the Commonwealth of Kentucky Department for Facilities and Support Services, Division of Engineering and Contract Administration, for Maintenance Facility Renovations at the Kentucky Transportation Cabinet facility in Madisonville, Kentucky. The addendum, dated June 24, 2025, contains four substantive revisions to the project specifications and drawings that become binding upon the contract to be issued. The primary changes include: updating the water utility contact to Keith Browning at the Madisonville Water Department with a specified phone number, modifying HVAC diffuser specifications to require surface mount frames for drywall ceiling installation, and completely replacing two technical drawings—H101 (HVAC Floor Plan, Revision 1) and E101 (Electrical Lighting Floor Plan, Revision 1)—both dated June 23, 2025, with new versions prepared by Marcum Engineering.

The revised drawings detail mechanical and electrical work including HVAC ductwork routing, outdoor packaged unit installation on concrete maintenance pads, protective bollard installation, condensate termination, exhaust air wall cap termination, and electrical lighting modifications. The electrical work encompasses removal and reinstallation of existing light fixtures, connection of exhaust fans, installation of LED emergency drivers, and necessary conduit and wiring to interconnect exit signage with existing lighting circuitry. The contractor is responsible for all water meter and tap installation fees. The document references specifications contained in the formal bid documents and related addenda distributed by Lynn Imaging.

View the file

Other files

Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMMONWEALTH OF KENTUCKY

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

INVITATION TO BID NO: RFB-266-25

FOR: Maintenance Facility Renovations Kentucky Transportation Cabinet Madisonville, Kentucky

DATE: June 24, 2025

RFB-785-2500000732

ADDENDUM NO. Four (4)

BIDDER SHALL CONFORM TO THE FOLLOWING CHANGES AS SAME SHALL BECOME BINDING

UPON THE CONTRACT TO BE ISSUED IN RESPONSE TO THIS INVITATION TO BID.

Item 1: Refer to addendum to be distributed by Lynn Imaging for all additions, deletions, and/or changes to specifications and/or drawings.

END OF ADDENDUM

Invitation to Bid No. RFB-266-25 For: Maintenance Facility Renovations Kentucky Transportation Cabinet Madisonville, Kentucky

Susan Ward, Statewide Procurement Analyst II Division of Engineering and Contract Administration

KYTC MAINTENANCE FACLITY

MADISONVILLE, KENTUCKY

CLOTFELTERSAMOKAR NO. 2418

MARCUM NO. 24626

MECHANICAL AND ELECTRICAL ADDENDUM 4.00

JUNE 23, 2025

The following Addendum Items shall be made part of the Contract Documents for the referenced project.

4.01 Refer to Drawing U101. Revise the Water Utility Contact to be Keith Browing, Madisonville Water Department (270) 824-2140. The Utility Company will install meter and tap. Contractor shall be responsible for paying all fees.

4.02 Refer to Drawing H001 – Grille and Diffuser Schedule. Furnish diffusers tagged

S-1 with surface mount frame for installation in drywall ceiling.

4.03 Refer to Drawing H101. Omit this drawing in its entirety and replace with the attached Drawing H101, Revision 1 dated 06/23/2025.

4.04 Refer to Drawing E101. Omit this drawing in its entirety and replace with the attached Drawing E101, Revision 1 dated 06/23/2025.

Attachments:

1. Drawing H101, Revision 1

2. Drawing E101, Revision 1

END OF ADDENDUM 4.00

CREW ROOM

TOILET

MECH. RM.

OFFICE

OFFICE

OFFICE

SHOWER

ADA TOILET

FEMALE

TOILET

MAINT. BAY

AC

TAC-1

1 1

CH

CH-1

T x1

S

A

14x12 SA 14x12 SA

S-3

S-3

S-3

S-2 150 S-2

S-1

S-1

S-2

S-2

S-2

S-2

S-2

S-4

12x10 SA 10x10 SA

EF

12x12 SA

R-1

R-1

R-1

R-1

R-1 x1

R

A

22x12 RA

12x12 RA

14x12 RA

10x10 EA

14x14 RA

2 4

EF

6Ø EA

(TYP.)

'-0

M

IN

IM

U M

F.F. ELEVATION

CEILING (REFER TO

ARCH. DWGS)

EXHAUST AIR

DUCTWORK

NORTH

PROJECT

SCALE: 1/8" = 1'-0"

FLOOR PLAN

WWW.CLOTFELTER-SAMOKAR.COM

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

228 E. REYNOLDS RD., SUITE ONE, LEXINGTON, KY 40517 / PH. 859.273.3700 / FAX 859.271.6605

AS-BUILT DATE

DECA LOG #

DESCRIPTION OF REVISIONS DATE

DESCRIPTION OF REVISIONS DATE

DRAWING INFORMATION

A & E FILE NO.

DRAWING DATE

DRAWN BY

CHECKED BY

PHASE

RTA DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

ACCOUNT NO.

609-C940-Z001-85A

24626

04/15/25

RTA

KYTC MAINTENANCE FACILITY

MADISONVILLE, KENTUCKY

Paducah, KY Office 2301 McCracken Blvd, Paducah, KY 42001 270-444-9274 / MarcumEngineering.net

03/28/25

H101

HVAC FLOOR PLAN

BA

TRN

MECHANICAL

CONSTRUCTION TAG NOTES

REMOVE EXISTING SUPPLY AIR DUCTWORK INSULATION ON EXTERIOR OF

BUILDING. INSTALL NEW INSULATION ON SUPPLY AND RETURN AIR DUCT FROM

UNIT CONNECTION UP BUILDING WALL AND TO INTERIOR OF BUILDING WALL. REFER

TO SPECIFICATIONS FOR REQUIREMENTS.

2 OUTDOOR PACKAGED UNIT. INSTALL ON 6" CONCRETE MAINTENANCE PAD. REFER

TO GENERAL HVAC NOTES ON DRAWING H001.

3 ROUTE DUCT AS HIGH AS POSSIBLE IN SPACE.

MAINTAIN AT MINIMUM 10'-0" RADIUS FROM OUTSIDE AIR INTAKE AND EXHAUST AIR

STREAMS, GAS VENTS, DRIVE WAYS, ETC.

5 TERMINATE 1" CONDENSATE ON GRADE.

INSTALL PROTECTIVE PIPE BOLLARDS TO PREVENT VEHICULAR DAMAGE TO UNIT.

BOLLARDS SHALL BE 6" DIAMETER, MINIMUM OF 5'-0" TALL ABOVE GRADE, MINIMUM

2'-0" BELOW GRADE, INSTALLED IN 18" DIAMETER CONCRETE BASE. PAINT IN COLOR

TO BE SELECTED BY ARCHITECT.

7 INSTALL RETURN AIR DUCTWORK WITH VOLUME DAMPER IN THE VERTICAL.

8 TERMINATE EXHAUST AT WALL CAP TERMINATION IN COLOR TO BE SELECTED BY

ARCHITECT.

9 EXISTING DUCTWORK IN THIS SPACE TO REMAIN.

DUCT RUN-OUT

SCHEDULE

CFM RANGE SIZE

0 - 100 6"Ø / 6x6

101 - 200 8"Ø / 8x8 201 - 325 10"Ø / 10x10

SECTION

SCALE: NONE

ADDENDUM 06/23/2025

06/23/2025

CREW ROOM

TOILET

MECH. RM.

OFFICE

OFFICE

108 OFFICE

SHOWER

104ADA TOILET

FEMALE

TOILET

MAINT. BAY

A1

A1 A1

A1

EG1

EX1

SS

SS

C1

C1

RR

OSOS

A1E

A1 OSOS RR

A1E

A1

OSOS

RR

A1E

A1A1 A1

A1E

A1E

A1E

A1E

EX1

EX1 EX1

1 1

EG1

RR RR

DSDS DSDS

EG1

RR

DSDS

A1

A1 A1

A1 A1

A1

(TYP.)

LP3

LP3-7

S PS P

LP1

LP2

T F

T F

EG1

EX1

EG1

EX1 EG1

EX1

EG1

EX1

EX1

LP3-8

EX1

NORTH

PROJECT

SCALE: 1/8" = 1'-0"

FLOOR PLAN

WWW.CLOTFELTER-SAMOKAR.COM

REVISION HISTORY OF THIS DRAWING

DRAWING NO.

228 E. REYNOLDS RD., SUITE ONE, LEXINGTON, KY 40517 / PH. 859.273.3700 / FAX 859.271.6605

AS-BUILT DATE

DECA LOG #

DESCRIPTION OF REVISIONS DATE

DESCRIPTION OF REVISIONS DATE

DRAWING INFORMATION

A & E FILE NO.

DRAWING DATE

DRAWN BY

CHECKED BY

PHASE

RTA DATE

COMMONWEALTH OF KENTUCKY

FINANCE AND ADMINISTRATION CABINET

DEPARTMENT FOR FACILITIES AND SUPPORT SERVICES

DIVISION OF ENGINEERING AND CONTRACT ADMINISTRATION

FRANKFORT, KENTUCKY

ACCOUNT NO.

609-C940-Z001-85A

24626

04/15/25

RTA

KYTC MAINTENANCE FACILITY

MADISONVILLE, KENTUCKY

Paducah, KY Office 2301 McCracken Blvd, Paducah, KY 42001 270-444-9274 / MarcumEngineering.net

03/28/25

E101

ELECTRICAL LIGHTING FLOOR PLAN

MRM

MRM

ELECTRICAL

CONSTRUCTION TAG NOTES

(APPLIES TO THIS DRAWING ONLY)

1 EXISTING LIGHTING LOCATED WITHIN SPACE SHALL REMAIN AND BE LEFT ACTIVE.

2 CONNECTION TO EXHAUST FAN LOCATED WITHIN SPACE. REFER TO POWER

DRAWING FOR CONTINUATION.

CONTRACTOR SHALL REMOVE EXISTING LIGHT FIXTURES AND TURN OVER TO THE

OWNER. THE CONTRACTOR SHALL RECEIVE NEW FIXTURES FROM OWNER AND

INSTALL IN SAME LOCATION. TYPICAL OF 20 FIXTURES THROUGHOUT THE

BUILDING.

4 CONTRACTOR SHALL USE EXISTING SPARE CIRCUIT BREAKER IN PANEL TO SERVE

CIRCUITRY AS INDICATED. UPDATE PANEL INDEX TO REFLECT CIRCUITS ADDED.

FURNISH AND INSTALL ALL NECESSARY CONDUIT, WIRE, BOXES, ETC. AS REQUIRED

TO INTERCONNECT EXIT SIGNAGE WITH EXISTING LIGHTING CIRCUITRY WITHIN

CEILING SPACE.

FURNISH AND INSTALL LED EMERGENCY DRIVER EQUAL TO BILLDA RUGBY LED

DRIVER FOR INSTALLATION BETWEEN JUNCTION BOX AND LIGHT FIXTURE TO BE

FURNISHED BY THE OWNER. COORDINATE ALL FINAL CONNECTIONS WITH

MANUFACTURER REQUIREMENTS.

ADDENDUM 06/23/20254

06/23/2025

Addendum Four