Addendum 1 ITB S-DASOBO-00015523.pdf

PDF 7 MB Posted

Attached to
Oregon Employment Department - Roseburg Capital Improvements Project
Solicitation number
S-DASOBO-00015523
Issued by
Douglas County, Oregon

About this file

Addendum 1 to Oregon Employment Department - Roseburg Capital Improvements Project ITB

This Addendum 1 modifies Invitation to Bid #S-DASOBO-00015523 issued by the Oregon Department of Administrative Services, State Procurement Services, on behalf of the Oregon Employment Department. The addendum replaces ten electrical drawing sheets (E0.01, E0.02, E0.03, E2.11, E2.12, E2.21, E2.22, E3.11, E3.21, and E4.00) with revised versions addressing electrical legend, schedules, notes, one-line diagrams, panel schedules, power demolition plans, power plans, lighting demolition plans, lighting plans, and electrical details for the Roseburg facility capital improvements project. The addendum increases the number of alternates from nine to ten, adding Alternate 10 for a 14' x 60' mobile office building with restroom to be parked facing the street without blocking ADA parking. The revised pricing form (Form A-2) reflects this additional alternate item. Requests for clarification, change requests, and protests of Addendum 1 must be submitted by 2:00 PM on Wednesday, April 15, 2026 (Pacific time). All bidders must sign and return the addendum and acknowledge receipt via the "Acknowledgement of Addenda" section of Form A-1 prior to the original bid closing date of April 23, 2026, at 2:00 PM, or their bids will be rejected as non-responsive.

The addendum provides detailed electrical specifications for the project, including symbols and notation conventions for power devices, lighting devices, equipment connections, control systems, and conduit routing. General notes clarify contractor responsibilities for site familiarization, removal of existing electrical systems scheduled for demolition, protection of systems to remain, maintenance of temporary electrical systems during construction, and proper handling of abandoned wiring and conduit. Keyed notes address specific requirements such as coordinating with architectural and mechanical drawings, providing separate neutral conductors for each phase, maintaining existing systems designated for reuse, and ensuring existing items remain unless otherwise noted. The addition of Alternate 10 provides bidders with the option to include pricing for temporary office space accommodating up to ten people with an insulated structure, heating and air conditioning system, commercial carpet, vinyl flooring, handicapped accessible restroom, and a steel Hoeman outrigger chassis.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STATE OF OREGON

INVITATION TO BID (ITB)

OREGON EMPLOYMENT DEPARTMENT – ROSEBURG CAPITAL IMPROVEMENTS PROJECT

BID# S-DASOBO-00015523

ADDENDUM# 1

ITB# S-DASOBO-00015523 ADDENDUM #1

OREGON EMPLOYMENT DEPARTMENT – ROSEBURG CAPITAL IMPROVEMENTS PROJECT Page 1 of 17

This Solicitation Addendum modifies the above captioned ITB only to the extent indicated herein.

All other areas not specifically changed or otherwise modified by this Solicitation Addendum shall remain in full force and effect.

This Solicitation Addendum# 1 modifies the ITB as follows:

I. Replace Electrical Sheets E0.01, E0.02, E0.03, E2.11, E2.12, E2.21, E2.22, E3.11, E3.21, E4.00 in Attachment C Plans and Drawings with “Addendum 1 Attachment C Plans and Drawings ELECTRICAL (Addendum 1 Attachment 1)”

II. Revise subsection 8. Alternates 1-9 to read as “8. Alternates 1-10” and add “Alternate 10: 14’ x 60’ Mobile Office Building with Restroom” in A.1 Project Description of the ITB as follows:

8. Alternates 1-[9] 10:

• ALTERNATE 10: Provide 14’ x 60’ Mobile Office Building with Restroom for working during the day as specified in “Attachment E-3 Alternate 10 for 14’ x 60’ Mobile Office Building with Restroom (Addendum 1 Attachment 2)”. Park the trailer facing the street and do not block the ADA parking.

III. Add “Attachment E-3 Alternate 10 for 14’ x 60’ Mobile Office Building with Restroom

(Addendum 1 Attachment 2)” to ITB and update Table of Contents by adding Attachment E-3 to read as follows:

ATTACHMENT E-3: ALTERNATE 10 FOR 14’ X 60’ MOBILE OFFICE BUILDING

WITH RESTROOM

Attachment E-3 is found under Addendum# 1 to this ITB as “Addendum 1 Attachment 2”

IV. Add “Exhibit 12: Alternate 10 for 14’ x 60’ Mobile Office Building with Restroom” under Section 5. Exhibits in Attachment D-1 Sample Public Improvement Contract Form to read as follows:

EXHIBIT 12: ALTERNATE 10 FOR 14’ X 60’ MOBILE OFFICE BUILDING WITH

RESTROOM [in resulting contract, insert ITB Attachment E-3]

V. Replace Attachment A, Form A-2 Pricing Form with “Addendum 1 Attachment A, Form A-2 Pricing Form (Addendum 1 Attachment 3)” to add Alternate Item 10.

ITB# S-DASOBO-00015503 ADDENDUM #1

OREGON EMPLOYMENT DEPARTMENT – ROSEBURG CAPITAL IMPROVEMENT PROJECT Page 2 of 17

Requests for clarification, requests for change, and protests of this Solicitation Addendum #1 must be received by DAS by 2:00 PM on Wednesday, April 15, 2026 (Pacific time) or they will not be considered.

THIS SOLICITATION ADDENDUM MUST BE SIGNED AND RETURNED PRIOR TO THE BID

CLOSING DATE AND TIME. THIS ADDENDUM RECEIPT MUST ALSO BE ACKNOWLEDGED BY

COMPLETING “ACKNOWLEDGEMENT OF ADDENDA” SECTION OF THE ATTACHMENT A, FORM

A-1 - BIDDER INFORMATION AND CERTIFICATIONS FORM. FAILURE TO DO SO MAY RESULT IN

REJECTION OF THE BID AS NON-RESPONSIVE.

Signature: ___________________________________________________ Date: ____________________

Bidder Name: __________________________________________________________________________ (Please Print)

ATTACHMENTS TO THIS ADDENDUM# 1:

• Addendum 1 Attachment 1 Addendum 1 Attachment C Plans and Drawings ELECTRICAL (attached herein on pages 3-13)

• Addendum 1 Attachment 2 Attachment E-3 Alternate 10 for 14’ x 60’ Mobile Office Building with Restroom (attached herein on page 14)

• Addendum 1 Attachment 3 Addendum 1 Attachment A, Form A-2 Pricing Form (attached herein on pages 15-17)

OREGON EMPLOYMENT DEPARTMENT – ROSEBURG CAPITAL IMPROVEMENT PROJECT Page 3 of 17

ADDENDUM 1 ATTACHMENT 1

Addendum 1 Attachment C Plans and Drawings ELECTRICAL

[Below sheets in Addendum 1 Attachment C Plans and Drawings ELECTRICAL are attached in following order:

SHEET E0.01 ELECTRICAL LEGEND, SCHEDULES AND NOTES

SHEET E0.02 ONE-LINE DIAGRAM

SHEET E0.03 PANEL SCHEDULES

SHEET E2.11 FIRST & SECOND FLOOR POWER DEMOLITION PLAN

SHEET E2.12 ROOF POWER DEMOLITION PLAN

SHEET E2.21 FIRST & SECOND FLOOR POWER PLAN

SHEET E2.22 ROOF POWER PLAN

SHEET E3.11 FIRST & SECOND FLOOR LIGHTING DEMOLITION PLAN

SHEET E3.21 FIRST & SECOND FLOOR LIGHTING PLAN

SHEET E4.00 ELECTRICAL DETAILS]

SINGLE-POINT ELECTRICAL CONNECTION

ELECTRICAL MOTOR CONNECTION

FUSED SAFETY SWITCH

SAFETY SWITCH

POWER/DATA POLE

ELECTRICAL EQUIPMENT CONNECTION

SPECIAL PURPOSE POWER RECEPTACLE [+ 18'']

DOUBLE DUPLEX RECEPTACLE [ABOVE COUNTER]

DUPLEX RECEPTACLE [ABOVE COUNTER]

DOUBLE DUPLEX RECEPTACLE [+ 18'']

LIGHTING RELAY

FOUR-WAY SWITCH [+ 45'']

LOW VOLTAGE SWITCH [+ 45'']

DUPLEX RECEPTACLE [+ 18'']

R

SD

SLV

DIMMER SWITCH [+ 45'']

FLUSH CONTROL PANEL [MAX 6'-6'' TO TOP]

SURFACE CONTROL PANEL [MAX 6'-6'' TO TOP]

METER BASE & SOCKET

J

SURFACE ELECTRICAL PANEL [MAX 6'-6'' TO TOP]

FLUSH ELECTRICAL PANEL [MAX 6'-6'' TO TOP]

OS

P

THREE-WAY SWITCH [+ 45'']

SURFACE MOUNTED EMERGENCY

PENDANT MOUNTED LIGHT FIXTURE

POLE ARM MOUNT LIGHT FIXTURE

CEILING MOUNTED EXIT SIGN

WALL MOUNTED EXIT SIGN [+ 18'' ABOVE DOOR]

S

PENDANT LIGHT FIXTURE

RECESSED LIGHT FIXTURE

RECESSED LIGHT FIXTURE

PENDANT EMERGENCY LIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE

WALL MOUNTED EMERGENCY LIGHT FIXTURE

CONDUIT WITH

MECHANICAL. EQUIPMENT NOTE MARK

NEUTRAL CONDUCTOR

FEEDER MARK

PLAN NOTE MARK

PHASE CONDUCTOR

GROUND CONDUCTOR

X

X X

BALLAST LOAD TRANSFER

LINEAR WALL MOUNTED EMERGENCY FIXTURE

RECESSED EMERGENCY LIGHT FIXTURE

RECESSED EMERGENCY LIGHT FIXTURE

JUNCTION BOX

SURFACE MOUNTED LIGHT FIXTURE

LINEAR WALL MOUNTED LIGHT FIXTURE

COMBO EXIT SIGN/

EMERGENCY LIGHT [+ 18'' ABOVE DOOR]

CP

SO OCCUPANCY SENSOR SWITCH [+ 45'']

SURFACE MOUNTED EMERGENCY LIGHT FIXTURE

STRIP LIGHT FIXTURE

EMERGENCY STRIP LIGHT FIXTURE

RECESSED DOWNLIGHT

SINGLE-POLE SWITCH [+ 45'']

OCCUPANCY SENSOR ONE WAY CEILING MOUNT

OCCUPANCY SENSOR POWER PACK

PHOTOCELL

(SIGN FACE)

EMERGENCY RELAY

STANDARD MOUNTING HEIGHT UNLESS

OTHERWISE NOTED ON DRAWINGS

[+ XX'']

XXXXX

LIGHT FIXTURE

DISTRIBUTION & EQUIPMENT

POWER DEVICES ABBREVIATIONSLIGHTING DEVICES

REFERENCE SYMBOLS & WIRING

(E) EXISTING TO REMAIN

(F) FUTURE

(R) EXISTING TO BE RELOCATED

(D) EXISTING TO BE DEMOLISHED

AB ABOVE COUNTER BACKSPLASH

AC ALTERNATING CURRENT

A, AMP AMPERES

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFI ARC-FAULT CIRCUIT INTERRUPTER

AHJ AUTHORITY HAVING JURISDICTION

AIC EQUIPMENT SHORT CIRCUIT INTERRUPT RATING.

AL ALUMINUM

ALC AUTOMATIC LIGHTING CONTROL

ATS AUTOMATIC TRANSFER SWITCH

AUX AUXILIARY

AWG AMERICAN WIRE GAUGE

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CLG CEILING

CT CURRENT TRANSFORMER

CU COPPER

DC DIRECT CURRENT

DISC DISCONNECT

DIA DIAMETER

DIV DIVISION

DP DISTRIBUTION PANEL

DWG DRAWING

EF EXHAUST FAN

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

FA FIRE ALARM

FAA FIRE ALARM ANNUNCIATOR

FBO FURNISHED BY OTHERS

FC FOOT CANDLES

FLA FULL LOAD AMPERES

FSD FIRE/SMOKE DAMPER

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

HP HORSEPOWER

HTR HEATER

IG ISOLATED GROUND

KCMIL THOUSAND CIRCULAR MILS

KW KILOWATTS

KVA KILOVOLT-AMPERES

LTG LIGHTING

LCP LIGHTING CONTROL PANEL

MAX MAXIMUM

MB MAIN BREAKER

MCA MINIMUM CIRCUIT AMPERES

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MSP MAIN SERVICE PANEL

MTD MOUNTED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MFGR'S ASSOCIATION.

NL NIGHT LIGHT

NTS NOT TO SCALE

OFCI OWNER FURNISHED, CONTRACTOR INSTALLED

OFOI OWNER FURNISHED, OWNER INSTALLED

OS OCCUPANCY SENSOR

PH, Ø PHASE

PNL PANEL

PROVIDE TO FURNISH AND INSTALL

SDP SUB DISTRIBUTION PANEL

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TB TERMINAL BOARD

TEL TELEPHONE

TK INSTALL TOE KICK

TYP TYPICAL OF ALL OCCURANCES

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTS

VA VOLT-AMPERES

VFD VARIABLE FREQUENCY DRIVE

VR VANDAL RESISTANT

W WATT

W/ WITH

W/O WITHOUT

WG WIRE GUARD

WP WEATHERPROOF

XFMR TRANSFORMER

S4

S3

FLUSH AUTOMATIC DOOR ACTUATOR [+45'']

M

C

X X

SINGLE RECEPTACLE [+ 18'']

SHEET REFERENCE MARK

HOMERUN ARROW

LIGHTING CONTACTOR

SURFACE MOUNTED LIGHT FIXTURE

PENDANT MOUNTED EMERGENCY LIGHT FIXTURE

UNDER GROUND

ABOVE GROUND, IN WALL, CEILING, ETC.

LINETYPE LEGEND

NEW EQUIPMENT (TYPICAL)

EXISTING EQUIPMENT (TYPICAL)

DEMOLISHED EQUIPMENT (TYPICAL)

RECESSED EMERGENCY DOWNLIGHT

OS OCCUPANCY SENSOR TWO WAY CEILING MOUNT

OS OCCUPANCY SENSOR 360° CEILING MOUNT

OS OCCUPANCY SENSOR WALL MOUNT

DA

EM

DWG DESCRIPTION

E0.01 ELECTRICAL LEGEND, SCHEDULES AND NOTES

E0.02 ONE-LINE DIAGRAM

E0.03 PANEL SCHEDULES

E2.11 FIRST & SECOND FLOOR POWER DEMOLITION PLAN

E2.12 ROOF POWER DEMOLITION PLAN

E2.21 FIRST & SECOND FLOOR POWER PLAN

E2.22 ROOF POWER PLAN

E3.11 FIRST & SECOND FLOOR LIGHTING DEMOLITION PLAN

E3.21 FIRST & SECOND FLOOR LIGHTING PLAN

E4.00 ELECTRICAL DETAILS

DRAWING INDEXLIGHTING FIXTURE SCHEDULE1

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

E0.01

1 ADDENDUM #1 04/02/2026

ATTACHMENT 1 - ADDENDUM 1 ATTACHMENT C PLANS AND DRAWINGS ELECTRICAL

E0.02

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

E0.03

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

PANEL C.3

MDP

SDP

PANEL D

M

UP

UP

A

A

1 1

E

E

7 7

5 5

4 4

B

B

3 3

2 2

6 6

C

C

D

D

PANEL B

TELEPHONE

BACKBOARD

PANEL AUTILITY METER

PANEL C.2

PANEL C

MECH.

MEETING

MEETING

MEETING

MEN

WOMEN

JANITOR

OFFICE

OFFICE

MEETING

STORAGE

WOMEN

MEN

STORAGE

STAIR

STOR.

STAIR

OPEN OFFICE

HALL

ALTERNATE 1

(D) CEILING

EXHAUST FAN

(D) CEILING

EXHAUST

FAN

A. CONTRACTOR SHALL VISIT THE SITE AND BECOME

THOROUGHLY FAMILIAR WITH THE EXISTING

CONDITIONS PRIOR TO BIDDING. ELECTRICAL

OUTLETS, DEVICES, AND EQUIPMENT SHOWN

DASHED REPRESENT EXISTING TO BE DEMOLISHED.

EXISTING ELECTRICAL OUTLETS, DEVICES, AND

EQUIPMENT TO REMAIN ARE SHOWN WITH '(E)'

DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.

B. LABOR AND MATERIALS REQUIRED TO CHANGE THE

EXISTING ELECTRICAL INSTALLATION AS INDICATED

SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC

AND DO NOT SHOW EXISTING INTERCONNECTING

COMPONENTS.

C. UNLESS OTHERWISE NOTED, REMOVE EXISTING

ELECTRICAL OUTLETS, DEVICES, EQUIPMENT AND

ASSOCIATED CONDUITS, CONDUCTORS, AND

HARDWARE IN AREAS SCHEDULED FOR DEMOLITION

AND AS SHOWN ON DRAWINGS. COORDINATE WITH

ARCHITECTURAL DRAWINGS. EXTEND AND

RECONNECT INTERRUPTED CIRCUITS TO OTHER

EXISTING ELECTRICAL OUTLETS, DEVICES, AND

EQUIPMENT WHICH ARE TO REMAIN. THE

CONTRACTOR SHALL INCLUDE COSTS FOR LABOR

AND MATERIALS REQUIRED TO MAINTAIN EXISTING

SYSTEMS INDICATED FOR REUSE.

D. EXCEPT AS MAY BE SPECIFICALLY INDICATED,

OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF

ELECTRICAL MATERIALS AND EQUIPMENT INTENDED

FOR DEMOLITION. OTHERWISE ELECTRICAL

MATERIALS AND EQUIPMENT REMOVED FROM THE

EXISTING INSTALLATION IN THE COURSE OF

PERFORMING THE INDICATED WORK SHALL BECOME

THE PROPERTY OF THE CONTRACTOR AND SHALL BE

REMOVED FROM THE SITE.

E. CONTRACTOR SHALL PROVIDE NECESSARY LABOR

AND MATERIALS TO MAINTAIN TEMPORARY

ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY

ARCHITECT OR OWNER IN OPERATION DURING THE

CONSTRUCTION PERIOD.

F. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND

WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL

BE PROTECTED FROM DAMAGE DURING THE

DEMOLITION.

G. ABANDONED WIRING SHALL BE REMOVED

COMPLETELY BACK TO SOURCE; EXISTING CONDUIT

MAY BE REUSED IF PRACTICAL, CAPPING OFF

CONDUIT STUBS THAT MAY REMAIN. CONDUIT

PENETRATING WALLS AND FLOORS WHICH ARE TO

REMAIN SHALL BE CUT OFF FLUSH. SEAL

ABANDONED CONDUIT.

H. INFORMATION GIVEN ON THE DRAWINGS IN

REFERENCE TO EXISTING FEATURES HAS BEEN

OBTAINED FROM RECORD DRAWINGS AND RECENT

SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED

TO BE COMPLETELY ACCURATE. VERIFY

INFORMATION BEFORE PROCEEDING WITH ANY

WORK.

GENERAL NOTES:

1. WALL AND DOOR IS TO BE DEMOLISHED AND

RE-BUILT. COORDINATE DEMO AND INSTALL OF NEW

WALL AND DOOR WITH EXISTING EQUIPMENT /

DEVICES. REMOVE AND REPLACE CIRCUITS AS

NECESSARY TO FACILITATE THE REMOVAL AND

CONSTRUCTION OF THE NEW WALL AND DOOR.

2. DEMOLISH ELECTRICAL DEVICES NOT INTENDED FOR

RELOCATION. INTERCEPT AND EXTEND RACEWAY

AND CONDUCTORS TO MAINTAIN CONTINUITY OF

EXISTING TO REMAIN DOWNSTREAM DEVICES.

KEYED NOTES:

PANEL E

DN

DN

E

E

C

C

D

D

WOMEN

MEN

HALL

CLOSET

OPEN OFFICE

STAFF

OFFICE

OFFICE

HALL

(D) CEILING

EXHAUST

FAN

(D) CEILING

EXHAUST

FAN

E2.11

1 FIRST FLOOR - POWER DEMOLITION PLAN

1/8" = 1'-0" 0' 4' 8' 16'

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

N

2 SECOND FLOOR - POWER DEMOLITION PLAN

1/8" = 1'-0" 0' 4' 8' 16'

N

RTU

CU

WP

GFI

WP

GFI

CU

CU

(E) ROOF

HATCH

(E)

(E)

A

1 1

E

7 7

5 5

4 4

B

3 3

2 2

6 6

C D

1. DEMOLISH ELECTRICAL CONNECTIONS, J-BOXES,

DISCONNECTS AND ASSOCIATED CIRCUITING

COMPLETE.

2. DEMOLISH ELECTRICAL CONNECTIONS, J-BOXES,

AND DISCONNECTS. MAINTAIN EXISTING CONDUIT

AND CONDUCTORS FOR NEW MECHANICAL UNITS.

3. DEMOLISH ROOF TOP RECEPTACLE MAINTAIN

EXISTING CONDUIT AND CONDUCTORS FOR NEW

RECEPTACLE LOCATION.

A. CONTRACTOR SHALL VISIT THE SITE AND BECOME

THOROUGHLY FAMILIAR WITH THE EXISTING

CONDITIONS PRIOR TO BIDDING. ELECTRICAL

OUTLETS, DEVICES, AND EQUIPMENT SHOWN

DASHED REPRESENT EXISTING TO BE DEMOLISHED.

EXISTING ELECTRICAL OUTLETS, DEVICES, AND

EQUIPMENT TO REMAIN ARE SHOWN WITH '(E)'

DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.

B. LABOR AND MATERIALS REQUIRED TO CHANGE THE

EXISTING ELECTRICAL INSTALLATION AS INDICATED

SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC

AND DO NOT SHOW EXISTING INTERCONNECTING

COMPONENTS.

C. UNLESS OTHERWISE NOTED, REMOVE EXISTING

ELECTRICAL OUTLETS, DEVICES, EQUIPMENT AND

ASSOCIATED CONDUITS, CONDUCTORS, AND

HARDWARE IN AREAS SCHEDULED FOR DEMOLITION

AND AS SHOWN ON DRAWINGS. COORDINATE WITH

ARCHITECTURAL DRAWINGS. EXTEND AND

RECONNECT INTERRUPTED CIRCUITS TO OTHER

EXISTING ELECTRICAL OUTLETS, DEVICES, AND

EQUIPMENT WHICH ARE TO REMAIN. THE

CONTRACTOR SHALL INCLUDE COSTS FOR LABOR

AND MATERIALS REQUIRED TO MAINTAIN EXISTING

SYSTEMS INDICATED FOR REUSE.

D. EXCEPT AS MAY BE SPECIFICALLY INDICATED,

OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF

ELECTRICAL MATERIALS AND EQUIPMENT INTENDED

FOR DEMOLITION. OTHERWISE ELECTRICAL

MATERIALS AND EQUIPMENT REMOVED FROM THE

EXISTING INSTALLATION IN THE COURSE OF

PERFORMING THE INDICATED WORK SHALL BECOME

THE PROPERTY OF THE CONTRACTOR AND SHALL BE

REMOVED FROM THE SITE.

E. CONTRACTOR SHALL PROVIDE NECESSARY LABOR

AND MATERIALS TO MAINTAIN TEMPORARY

ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY

ARCHITECT OR OWNER IN OPERATION DURING THE

CONSTRUCTION PERIOD.

F. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND

WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL

BE PROTECTED FROM DAMAGE DURING THE

DEMOLITION.

G. ABANDONED WIRING SHALL BE REMOVED

COMPLETELY BACK TO SOURCE; EXISTING CONDUIT

MAY BE REUSED IF PRACTICAL, CAPPING OFF

CONDUIT STUBS THAT MAY REMAIN. CONDUIT

PENETRATING WALLS AND FLOORS WHICH ARE TO

REMAIN SHALL BE CUT OFF FLUSH. SEAL

ABANDONED CONDUIT.

H. INFORMATION GIVEN ON THE DRAWINGS IN

REFERENCE TO EXISTING FEATURES HAS BEEN

OBTAINED FROM RECORD DRAWINGS AND RECENT

SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED

TO BE COMPLETELY ACCURATE. VERIFY

INFORMATION BEFORE PROCEEDING WITH ANY

WORK.

GENERAL NOTES:

KEYED NOTES:

E2.12

1 ROOF - POWER DEMOLITION PLAN

1/8" = 1'-0" 0' 4' 8' 16'

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

UP

UP

A

A

1 1

E

E

7 7

5 5

4 4

B

B

3 3

2 2

6 6

C

C

D

D

PANEL C.3

MDP

SDP

PANEL D

M

PANEL B

TELEPHONE

BACKBOARD

PANEL AUTILITY METER

PANEL C.2

PANEL C

MECH.

MEETING

MEETING

MEETING

OFFICE

OFFICE

MEETING

STORAGE

STORAGE

STAIR

STOR.

STAIR

OPEN OFFICE

HALL

WOMEN

JANITOR

MEN

UNISEX

UNISEX

BREAK ROOM

VESTIBULE

GFI

J J

GFI

GFIGFI

J

GFI

J

GFI

J

GFI

GFI3

GFI

GFI

DA

DA

DA

DA

DA

DA

DA

DA

J

UNDERCOUNTER

FRIDGE PLUG

H-8

H-10

H-14

H-14

H-14H-14

H-12

H-16

H-18

H-20

H-22 H-24

H-13

H-15

ALTERNATE 1

CP

GAS FIRED

WATER HEATER

IGNITER

H-13

T

PANEL H

XFMR-H

1. PROVIDE POWER CONNECTION TO LOW VOLTAGE

TRANSFORMER FOR AUTOMATIC SENSOR FLUSH

VALVE AND SENSOR-ACTIVATED LAVATORY.

2. PROVIDE 120V ELECTRICAL CONNECTION TO

MOTORIZED DOOR OPERATOR. PROVIDE 1/2" C. FROM

OPERATOR TO DOOR ACTUATOR FOR LOW-VOLTAGE

CONTROL WIRING. COORDINATE WITH EQUIPMENT

SUPPLIER.

3. MOUNT OUTLET UNDER SINK FOR SOAP DISPENSER.

4. PROVIDE 24V LOW VOLTAGE TRANSFORMER

(GEORGIA PACIFIC: CAT#59478) FOR PAPER TOWEL

DISPENSER. COORDINATE LOCATION OF J-BOX WITH

EQUIPMENT SUPPLIER.

5. PROVIDE 500W 120V 1PH CEILING MOUNTED

ELECTRIC HEATER. (KING: WHFC1210-W, WHSC-C-W

OR EQUAL). MOUNT THERMOSTAT TO OCTAGONAL

COLUMN WITHIN VESTIBULE VERIFY EXACT LOCATION

WITH ARCHITECT PRIOR TO INSTALL.

6. PROVIDE 7.8AMPS 120V POWER FOR HAND DRYER.

COORDINATE LOCATION OF J-BOX WITH ARCHITECT

PRIOR TO INSTALL.

7. MOUNT AUTOMATIC DOOR ACTUATOR ON EXTERIOR

BOLLARD. SEE ARCHITECTURAL 1/A1.21.

8. INSTALL NEW OUTLET IN NEW WALL CONNECT TO

EXISTING CIRCUIT.

KEYED NOTES:

A. COORDINATE EXACT LOCATION OF ALL OUTLETS AND

EQUIPMENT WITH ARCHITECTURAL AND MECHANICAL

DRAWINGS PRIOR TO ROUGH-IN.

B. CONDUCTOR DESIGNATION "TIC MARKS" MAY NOT

APPEAR ON THIS DRAWING. CONDUCTORS SHALL BE

PROVIDED AS NECESSARY TO ACCOMPLISH THE

INTENT OF THE CIRCUITING.

C. PROVIDE SEPARATE NEUTRAL CONDUCTOR FOR

EACH PHASE. DO NOT SHARE NEUTRALS.

D. ALL EXISTING ITEMS ARE TO REMAIN, UNLESS NOTED

OTHERWISE.

GENERAL NOTES:

DN

DN

E

E

C

C

D

D

PANEL E

WOMEN

MEN

HALL

CLOSET

OPEN OFFICE

STAFF

OFFICE

OFFICE

HALL

EF

E2.21

1 FIRST FLOOR - POWER PLAN

1/8" = 1'-0" 0' 4' 8' 16'

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

N

2 SECOND FLOOR - POWER PLAN

CU

WP

GFI

CU

(E) ROOF

HATCH

EF

EF

RTU

EF

RTU

WP

GFI

A

A

1 1

E

E

7 7

5 5

4 4

B

B

3 3

2 2

6 6

C

C

D

D

RTU

CU

H-17

WP

GFI

H-17

H-17

1. INTERCEPT EXISTING CONDUIT AND EXTENT TO NEW

LOCATION.

KEYED NOTES:

A. COORDINATE EXACT LOCATION OF ALL OUTLETS AND

EQUIPMENT WITH ARCHITECTURAL AND MECHANICAL

DRAWINGS PRIOR TO ROUGH-IN.

B. CONDUCTOR DESIGNATION "TIC MARKS" MAY NOT

APPEAR ON THIS DRAWING. CONDUCTORS SHALL BE

PROVIDED AS NECESSARY TO ACCOMPLISH THE

INTENT OF THE CIRCUITING.

C. PROVIDE SEPARATE NEUTRAL CONDUCTOR FOR

EACH PHASE. DO NOT SHARE NEUTRALS.

GENERAL NOTES:

E2.22

1 ROOF - POWER PLAN

1/8" = 1'-0" 0' 4' 8' 16'

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

PANEL C.3

MDP

SDP

PANEL D

M

A

A

1 1

E

E

7 7

5 5

4 4

B

B

3 3

2 2

6 6

C

C

D

D

A

A

1 1

E

E

7 7

5 5

4 4

B

B

3 3

2 2

6 6

C

C

D

D

PANEL B

TELEPHONE

BACKBOARD

PANEL AUTILITY METER

PANEL C.2

PANEL C

1 (TYP)

MECH.

MEETING

MEETING

MEETING

MEN

WOMEN

JANITOR

OFFICE

OFFICE

MEETING

STORAGE

WOMEN

MEN

STORAGE

STAIR

STOR.

STAIR

OPEN OFFICE

HALL

A. CONTRACTOR SHALL VISIT THE SITE AND BECOME

THOROUGHLY FAMILIAR WITH THE EXISTING

CONDITIONS PRIOR TO BIDDING. ELECTRICAL

OUTLETS, DEVICES, AND EQUIPMENT SHOWN

DASHED REPRESENT EXISTING TO BE DEMOLISHED.

EXISTING ELECTRICAL OUTLETS, DEVICES, AND

EQUIPMENT TO REMAIN ARE SHOWN WITH '(E)'

DESIGNATION OR OTHERWISE SPECIFICALLY NOTED.

B. LABOR AND MATERIALS REQUIRED TO CHANGE THE

EXISTING ELECTRICAL INSTALLATION AS INDICATED

SHALL BE PROVIDED. DRAWINGS ARE DIAGRAMMATIC

AND DO NOT SHOW EXISTING INTERCONNECTING

COMPONENTS.

C. UNLESS OTHERWISE NOTED, REMOVE EXISTING

ELECTRICAL OUTLETS, DEVICES, EQUIPMENT AND

ASSOCIATED CONDUITS, CONDUCTORS, AND

HARDWARE IN AREAS SCHEDULED FOR DEMOLITION

AND AS SHOWN ON DRAWINGS. COORDINATE WITH

ARCHITECTURAL DRAWINGS. EXTEND AND

RECONNECT INTERRUPTED CIRCUITS TO OTHER

EXISTING ELECTRICAL OUTLETS, DEVICES, AND

EQUIPMENT WHICH ARE TO REMAIN. THE

CONTRACTOR SHALL INCLUDE COSTS FOR LABOR

AND MATERIALS REQUIRED TO MAINTAIN EXISTING

SYSTEMS INDICATED FOR REUSE.

D. EXCEPT AS MAY BE SPECIFICALLY INDICATED,

OWNER SHALL HAVE FIRST RIGHT OF SALVAGE OF

ELECTRICAL MATERIALS AND EQUIPMENT INTENDED

FOR DEMOLITION. OTHERWISE ELECTRICAL

MATERIALS AND EQUIPMENT REMOVED FROM THE

EXISTING INSTALLATION IN THE COURSE OF

PERFORMING THE INDICATED WORK SHALL BECOME

THE PROPERTY OF THE CONTRACTOR AND SHALL BE

REMOVED FROM THE SITE.

E. CONTRACTOR SHALL PROVIDE NECESSARY LABOR

AND MATERIALS TO MAINTAIN TEMPORARY

ELECTRICAL SYSTEMS AS MAY BE REQUIRED BY

ARCHITECT OR OWNER IN OPERATION DURING THE

CONSTRUCTION PERIOD.

F. EXISTING ELECTRICAL SYSTEMS, CONDUIT AND

WIRING WHICH ARE NOT TO BE DEMOLISHED SHALL

BE PROTECTED FROM DAMAGE DURING THE

DEMOLITION.

G. ABANDONED WIRING SHALL BE REMOVED

COMPLETELY BACK TO SOURCE; EXISTING CONDUIT

MAY BE REUSED IF PRACTICAL, CAPPING OFF

CONDUIT STUBS THAT MAY REMAIN. CONDUIT

PENETRATING WALLS AND FLOORS WHICH ARE TO

REMAIN SHALL BE CUT OFF FLUSH. SEAL

ABANDONED CONDUIT.

H. INFORMATION GIVEN ON THE DRAWINGS IN

REFERENCE TO EXISTING FEATURES HAS BEEN

OBTAINED FROM RECORD DRAWINGS AND RECENT

SITE OBSERVATIONS, BUT CANNOT BE GUARANTEED

TO BE COMPLETELY ACCURATE. VERIFY

INFORMATION BEFORE PROCEEDING WITH ANY

WORK.

GENERAL NOTES:

1. DEMOLISH EXISTING LIGHT FIXTURE AND RACEWAYS

AS MUCH AS NECESSARY TO ACCOMMODATE

REMOVAL. MAINTAIN CIRCUITING FOR CONNECTION

TO NEW LIGHT FIXTURE LOCATION.

KEYED NOTES:

PANEL E

DN

DN

E

E

C

C

D

D

E

E

C

C

D

D

WOMEN

MEN

HALL

CLOSET

OPEN OFFICE

STAFF

OFFICE

OFFICE

HALL

E3.11

1 FIRST FLOOR - LIGHTING DEMOLITION PLAN

1/8" = 1'-0" 0' 4' 8' 16'

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

N

2 SECOND FLOOR - LIGHTING DEMOLITION PLAN

A

1 1

E

7 7

5 5

4 4

B

3 3

2 2

6 6

C D

AA

A A

A A

A A

A A

A A

A A

A A

A A

A A

A A

A A A A

A A

A A A A

A A

A A A A

A A

A A A A

A A AAE

A A A A

A

A

A

A

AA

A A A A

A A A

A A A A

A A A

A A A A

A A A

AA

B

BE

A

1 1

E

7 7

5 5

4 4

B

3 3

2 2

6 6

C D

PANEL C.3

MDP

SDP

PANEL D

M

PANEL B

TELEPHONE

BACKBOARD

PANEL AUTILITY METER

PANEL C.2

PANEL C

C C C C

C

C

X1

X1 AE

X1

X1

DEDE

AEAE AE

AEAE AE

AEAE

AEAE

AE

AE

D DDD D

DD D D

D

D

D

D

F F

X1

X1

LV

LV

LV

1 (TYP)

LVLV

LV

LV

LV

LVLV

LV

LV

LV

LV

LV

LV

LV

LV

LV LV

LV

4 (TYP)

5 (TYP)

6 (TYP)

7 (TYP)

S1 S1

S2

S3 S4

B

B

B

B

S3

S5

E4.00 4 8

BE

T

PANEL H

XFMR-H

1. INTERCEPT AND MODIFY EXISTING LIGHTING CIRCUIT

AS NECESSARY TO CONNECT TO NEW LIGHT

FIXTURES.

2. SURFACE MOUNT WIRELESS AREA CONTROLLER ON

CEILING. PROVIDE CAT 6 CONNECTION TO LIGHTING

CONTROL PATCH PANEL. SEE DETAIL 1 ON E4-00.

3. INSTALL LIGHTING CONTROL PATCH PANEL AND

SURFACE MOUNT BACNET INTEGRATION DEVICE. SEE

DETAIL 1 ON SHEET E4.00.

4. PROVIDE WIRELESS WALL STATION CONTROL

DEVICE. INSTALL IN EXISTING SWITCH J-BOX, VERIFY

EXACT LOCATION. WALL STATION REQUIRES 120V

ELECTRICAL CONNECTION. EXTEND EXISTING

NEUTRAL CONDUCTOR AS NECESSARY. SEE DETAIL 3

ON SHEET E4.00 FOR BUTTON CONFIGURATION.

5. SEE DETAIL 2 ON E4.00 FOR TYPICAL EMERGENCY

DRIVER WIRING.

6. CONNECT TO UN-SWITCHED LEG OF LIGHTING

CIRCUIT.

7. ROUTE EXTERIOR LIGHTING CIRCUIT THRU NEW TIME

CLOCK.

8. INSTALL POLE LIGHT IN PARKING LOT. SEE SHEET

A1.01 FOR LOCATION. CONNECT TO EXISTING

EXTERIOR LIGHTING CIRCUIT.

KEYED NOTES:

A. ALL EXISTING ITEMS ARE TO REMAIN, UNLESS NOTED

OTHERWISE.

B. CONTRACTOR SHALL PROVIDE A TEMPORARY

NETWORK SOLUTION FOR LIGHTING CONTROLS

DURING CONSTRUCTION. ALL FIXTURES SHALL BE

MAPPED AND INDIVIDUALLY LABELED WITHIN THE

SYSTEM PRIOR TO HANDOFF TO THE OWNER.

GENERAL NOTES:

E

E

C

C

D

D

E

E

C

C

D

D

A A A

A

A A

AA

A

AA

A

AE

A A A

A A A A

A A A

A A A A

A

A

AE

D

X1

X1

D

D

D

PANEL E

AE

AE AE

AEAE

AE

A

A

D

LV

LV

LV

LV

LV

LV

LV

LV

LV

LV LV

WOMEN

MEN

HALL

CLOSET

OPEN OFFICE

STAFF

OFFICE

OFFICE

HALL

F F

B

DE

DE

DE

E3.21

1 FIRST FLOOR - LIGHTING PLAN

1/8" = 1'-0" 0' 4' 8' 16'

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

N

2 SECOND FLOOR - LIGHTING PLAN

1/8" = 1'-0" 0' 4' 8' 16'

1 ADDENDUM #1 04/02/2026

E4.00

PROJECT #

DATE:

REVISIONS

Copyright © 2020-21 STUDIO 3 ARCHITECTURE, INC.

SHEET:

05/06/2024

SO-6366

O

RE

G O

N E

M

PL

O

YM

EN

T

DE

PA

RT

M

EN

T

RO

SE

BU

RG

B

UI

LD

IN

G

UP

GR

AD

ES

S E P

IN

E S

T

R O

S E B U

R G

O

R

Note: Dimensions, and door & window locations shown are nominal. Actual dimensions, layout, and roof slope may vary depending on model or model year selected.

Call Your Local Sales Professional

800.944.3442

14’ x 60’ Mobile Office Building with Restroom

Office, 14x60 WMS (NonStd)(Item2133)

• �840 square feet of open office space with two private offices and a spacious front office with accommodations for up to ten people.

• �Our buildings are completely insulated and come with a heating and air conditioning system to provide a comfortable work environment.

• �Commercial carpet for a quiet and productive office.

• �Vinyl floors offer a near maintenance free office building.

• �Constructed with a steel Hoeman outrigger chassis.

• �Handicapped accessible restroom.

60'

HVAC

www.mobilemodular.com

ADDENDUM 1 ATTACHMENT 2

ATTACHMENT E-3: Alternate 10 for 14’ x 60’ Mobile Office Building with Restroom

OREGON EMPLOYMENT DEPARTMENT – ROSEBURG CAPITAL IMPROVEMENT PROJECT Page 15 of 17

ADDENDUM 1 ATTACHMENT 3

ADDENDUM 1 ATTACHMENT A

FORM A-2 — PRICING FORM

ITB# S-DASOBO-00015523

Oregon Employment Department – Roseburg Capital Improvements Project

PRICING SUBMITTAL INSTRUCTIONS:

Bidder shall enter pricing and other required information for all Bid Items listed in this Pricing Form. If this Pricing Form is replaced by Addendum, Bidders shall use the Addendum form to provide pricing and other required information. If the Pricing Form is only modified by Addendum, Bidders shall follow the instructions in the Addendum for making modifications to the Pricing Form. Failure to supply the required information in the Pricing Form, as modified by subsequent Addenda, may result in Bid rejection as non-responsive.

BASE BID (LUMP SUM for 1-7) and ALTERNATES (A1-A[9] A10): To include all Work described in the ITB, Plans and Drawings (Attachment C), Technical Specifications (Attachment B) and any issued Addenda.

BASE BID:

(1) LED Lighting Upgrades: Redesign of building lighting; Replace/upgrade interior and exterior lighting to LED fixtures for interior and exterior lighting; addition of parking lot lighting pole, installation of new transformer in mechanical room; Replace lighting controls system;

Replace ceiling system (energy efficiency);

(2) Roofing Replacement Level 1 & 2; Roof: Asbestos Abatement, including demolition; Roof Replacement SBS 2-ply modified roof system and insulation; Install new steel roof door and access ladder at Level 2; (energy efficiency);

(3) Building/Structural Upgrades: Install two (2) structural columns required for roof support (structural upgrade and code compliance);

(4) Mechanical Plumbing Upgrades: Replace HVAC equipment; Replace HVAC controls system; Modification to HVAC duct routing; New exhaust fans, New diffusers; Remove range in Level 2 kitchen, replace flooring, counter and cabinet base (energy efficiency);

(5) Exterior/Structural Upgrades: Reconstruct ADA parking spot with concrete pad to grade/code and restriping of ADA spaces (ADA compliance);

(6) Exterior/Structural Upgrades: Replace exterior window and door system including ADA operators; and install new vestibule at public entrance (energy efficiency and ADA compliance); and

(7) Asbestos Abatement: Required for any areas touched by proposed work as noted in 2024 ABM & LBP Report

BASE BID LUMP SUM: $

ALTERNATE BID ITEMS:

OREGON EMPLOYMENT DEPARTMENT – ROSEBURG CAPITAL IMPROVEMENT PROJECT Page 16 of 17

ALTERNATE BID ITEMS

# ALTERNATE BID ITEM NAME UNIT

TYPE

QUANTI

TY

UNIT

COST

TOTAL

COST

A1 Demolish existing flooring and base in staff Room 208; prepare and install new flooring and base as indicated

LS 1 $ $

A2 Building/Structural Upgrades: Construct new ADA compliant break room on the 1st floor Room 208

LS 1 $ $

A3 Restroom Upgrades & ADA Upgrades: Replace wall-mounted drinking fountain with bottle filling station

LS 1 $ $

A4 Restroom Upgrades & ADA Upgrades: Convert (front) Level 1 restrooms to single use; Demo & replace floor-mounted water closets, toilets, urinals; install auto flush valves; replace wall-hung lavatories, sinks, faucets with motion sensors;

install plumbing soft trap insulation (sinks), vertical and horizontal grab bars; and flooring (all items noted in plans and specs). Base Bid to assume mechanical and lighting revisions. (Plumbing Upgrade, ADA Upgrade, energy efficiency) (Executive order, energy efficiency and ADA code compliance)

LS 1 $ $

A5 Restroom Upgrades & ADA Upgrades: upgrade (rear) Level 1 restrooms. Demo & replace floor-mounted water closets, toilets, urinals; install auto flush valves; replace wall-hung lavatories, sinks, faucets with motion sensors; install plumbing soft trap insulation (sinks), vertical and horizontal grab bars and flooring (all items noted in plans and specs). Base Bid to assume mechanical and lighting revisions. (Plumbing Upgrade, ADA Upgrade, energy efficiency)

LS 1 $ $

A6 Mechanical, Plumbing, Structural Assess:

Plumbing and piping of sanitary system

LS 1 $ $

A7 Kitchen Upgrades Level 2:

(a) Replace casework, floor-mounted base cabinets, countertops, wall mounted cabinets;

(b) Flooring replacement; and

(c) Replace wall tile

LS

A8 Asbestos and Lead Based Paint Abatement for any areas touched by proposed work as noted on 2024 ABM & LBP Report and throughout plans and specifications

LS 1 $ $

A9 Additional ceiling tiles replaced at Owner’s request (excludes ceiling tiles replaced within project scope). See Attachment C Plans and Drawings, Sheet# A1.13 requirements for General Notes/Additional Note #1.

Tile* 1 (1) $____ (tile replacem ent)

(2) $____

Above enter:

(1)+(2)

OREGON EMPLOYMENT DEPARTMENT – ROSEBURG CAPITAL IMPROVEMENT PROJECT Page 17 of 17

*for Unit Cost, enter price for replacing 1 tile, which includes: (1) ceiling tile replacement per tile cost and (2) installation per tile for labor)

*for Unit Cost, enter price for replacing 1 tile, which includes: (1) ceiling tile replacement per tile cost and (2) installation per tile for labor)

(installati on per tile)

A

Provide 14’ x 60’ Mobile Office Building with Restroom for working during the day as specified in “Attachment E-3 Alternate 10 for 14’ x 60’ Mobile Office Building with Restroom (Addendum 1 Attachment 2)”. Park the trailer facing the street and do not block the ADA parking

LS 1 $ $

SUBTOTAL ALTERNATE BID LUMP SUM $

BASE BID: TOTAL BASE BID: $

(Base Bid Lump Sum)

ADD ALTERNATE A1 – A9 A10:

ADD ALTERNATE LUMP SUM: $________________________________________________

(Base Bid Lump Sum + Alternate Lump Sum) NOTE: Bid price is total contract price including contractor’s profit and overhead. Items not explicitly listed in the bid schedule above are considered incidental.

The undersigned understands that the State reserves the right to increase or decrease the above quantities at the same unit prices as shown or to remove items as necessary to meet budgetary constraints. The undersigned has carefully examined the Contract Documents and the site of the work, and agrees to furnish all necessary plant, labor, equipment, accessories, materials, permits, and perform all operations shown and specified in accordance with the Contract Documents for the price(s) set herein.

Bid submitted by:

(Legal Business Name)

(Authorized Representative Name) (Title)

(Authorized Representative Signature) (Date)

*******THE END OF ADDENDUM# 1********

ADD ALTERNATE A1 – A9 A10:
Addendum 1 Attachment 3 Addendum 1 Attachment C Plans and Drawings ELECTRICAL.pdf
Sheets and Views
6366E001-Layout1
6366E002-Layout
6366E003-Layout
6366E211-Layout1
6366E212-Layout1
6366E221-Layout1
6366E222-Layout1
6366E311-Layout1
6366E321-Layout1
6366E400-Layout

File details come from the government source that posted it. Updated .