Addendum 1 Drawings
937 KB Posted
- Attached to
- Pettigrew Boiler Replacement
- Solicitation number
- FVSU-2022-FM1-PHB2021
- Issued by
- Paulding County, Georgia
About this file
This is Addendum 1 Drawings for the Pettigrew Boiler Replacement project at Fort Valley State University (FVSU) in Georgia, prepared by NBP Engineers, Inc. The addendum contains 100% construction documents including electrical and mechanical system specifications for the boiler and chiller mechanical room. The project scope includes demolition of existing equipment (boiler, fluorescent light fixtures, and associated electrical connections) and installation of new equipment including a new boiler (BLR-1), variable frequency drives (VFDs), air compressor pump (ACP), and heating water pump (HP-1 and HP-2). The electrical work encompasses new conduit installation (EMT), copper THWN-2 conductors, panel board connections, emergency lighting with integral battery packs, and associated disconnect switches and circuit breakers. Sealed bids for the construction work were due by 2:00 PM Eastern Time on Tuesday, September 28, 2021, with bids to be opened publicly at FVSU's Pettigrew Ballroom in Fort Valley, Georgia. Bidding documents were available from NBP Engineers, Inc. through email request to moore@nbpengineers.com.
The construction documents require compliance with the 2017 National Electrical Code (NEC) and include specifications for heavy-duty fused disconnects, a 30-ampere/3-phase fused disconnect for the VFD, a 20-ampere/1-phase circuit for boiler control, and a 30-ampere/2-pole non-fused disconnect. The design professional's Certificate of Authorization (COA#PEF000774) expires June 30, 2022. No pricing information, funding sources, or contract award amounts are disclosed in this addendum document.
Text of this file
P:\20066\20066e00.dgn
DATE PLOTTED
DGN FILE
23-SEP-2021
SEAL
SCALE:
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\20066\20066e00.dgn
AS SHOWN
08.18.2021
TWT
JCW
TWT
20066
F O
R T
V A
L L
E Y G
E O
R G
IA
S T
A
E
U N
IV
E R
S
IT
Y
D
COA Expiration: 6.30.2022
NBP Engineers, Inc. COA#PEF000774
P E
T T
IG
R
W
B O
IL
P L
A C
E M
E N
T F
O
L L
S
A
IV
E R
S
IT
Y
C
N S T
R U
C T
IO
C U
M E
N T S
F V
P
O J E o P
H B
E0.0
ELECTRICAL
NOTES, & DETAILS -
LEGEND, SCHEDULE,
EXISTING POWER RISER DIAGRAM
NOT TO SCALE
XFMR
PADMOUNT
750 KVA
EXISTING
T T
LDP
PANEL
XFMR
DRY
300 KVA
EXISTING XDP
MDP
PANEL
MCC
EXISTING
15KV, URD
3#4/0 ALUM,
4"-2W, SETS
MANHOLE #20
TO EXIST. PRIMARY 4#500MCM, 4"C
2 SETS:
MCM, 3•"C
3 SETS: 4#400
MDP-3
HA
PANEL
LDP-1
LA
PANEL
HA-9
MDP-1
(INVERTER)
A.C. PACKAGE
EMER.
"E"
LDP-2
LB
PANEL
MDP-5
HC
PANEL
LDP-5
LE
PANEL
PANEL
DIMMER
LIGHTING
STAGE
LDP-6
LF
PANEL
MDP-4
HB
PANEL
LDP-3
LC
PANEL
LDP-4
LD
PANEL
CT
TRACK LIGHTS: QUANTITY OF HEADS AS SHOWN EMERGENCY BATTERY PACK-CEILING
EMERGENCY BATTERY PACK-WALL
PANELBOARD-250 VAC OR LESS
SURFACE MOUNTED
PANELBOARD-250 VAC OR LESS
RECESSED
PANELBOARD-OVER 250 VAC
SURFACE MOUNTED
PANELBOARD-OVER 250 VAC
RECESSED
CABLE TRAY
BACKBOARD
CONNECTION TO EQUIPMENT
CAP
CONDUIT DOWN
CONDUIT UP
J
F
BT
C
C
BR
SLAB OR BELOW GRADE
GROUNDING CONDUCTOR- UNDER
U
SP
DP
PE
M
ICM
S
V
S
IC
MM
MC
GG
G
LIGHTING FIXTURES (SYMBOLS VARY BASED ON FIXTURES TYPE)
LIGHTING CONTROL
RECEPTACLES
CIRCUITS
GENERAL EQUIPMENT
FIRE PROTECTION EQUIPMENT
COMMUNICATIONS
LIGHTNING PROTECTION AND GROUNDING
T
JJ
I
UI
I
ELECTRICAL LEGEND
TV
C
G
B
K
LED ON "NORMAL" POWER
CEILING MOUNTED FIXTURE
WALL MOUNTED FIXTURE
EXIT LIGHT (ARROWS AS SHOWN)
LIFE SAFETY EGRESS FIXTURE
CEILING MOUNTED ULTRASONIC OCCUPANCY
SENSOR AND RELAY
CEILING/WALL MOUNTED INFRARED OCCUPANCY
SENSOR AND RELAY
CEILING MOUNTED COMBINATION INFRARED/
ULTRASONIC OCCUPANCY SENSOR AND RELAY -
SWITCHING PHOTOCELL (INTERIOR TYPE) F.C. NOTED
DIMMING PHOTOCELL (INTERIOR TYPE)
EXTERIOR TYPE PHOTO SWITCH
LOW VOLTAGE OVERRIDE SWITCH
INFRARED OCCUPANCY SENSOR
WALL MOUNTED SWITCH
"P" INDICATES PILOT LIGHT
KEYED SWITCH
DIMMER SWITCH
FOUR WAY SWITCH
THREE WAY SWITCH
SINGLE POLE SWITCH
DUPLEX RECEPTACLE - NORMAL
QUAD - NORMAL
GFCI DUPLEX RECEPTACLE - NORMAL
GFCI QUAD - NORMAL
FLOOR DUPLEX RECEPTACLE - NORMAL
FLOOR QUAD - NORMAL
CEILING DUPLEX RECEPTACLE - NORMAL CLOCK OUTLET
WALL/CEILING RACEWAY
CEILING SPECIAL - TYPE NOTED OR SHOWN
SPECIAL - TYPE NOTED OR SHOWN
HORIZONTALLY MOUNTED DUPLEX RECEPTACLE
WEATHER PROOF RECEPTACLE (GFCI)
ELECTRIC WATER COOLER RECEPTACLE(GFCI)
CONDUIT CONCEALED IN CEILING OR WALL
CONDUIT IN GROUND, SLAB, OR UNDER FLOOR
FLEXIBLE RACEWAY
RACEWAY EXPOSED
TRANSFORMER
FRAME AMPS/POLES/NEMA TYPE
FUSE PER MANUFACTURERS RECOMMENDATIONS
ENCLOSED BREAKER-RECESSED IN WALL
ENCLOSED CIRCUIT BREAKER
EMERGENCY PUSHBUTTON
COMBINATION STARTER AND DISCONNECT
EXHAUST FAN
MANUAL STARTER AND MOTOR RATED SWITCH
MOTOR
JUNCTION BOX - WALL/CEILING/FLOOR
SURGE SUPPRESSOR
VOICE OUTLET, QUANTITY OF JACKS AS NOTED
DATA OUTLET, QUANTITY OF JACKS AS NOTED
COMBINATION VOICE/DATA OUTLET, QUANTITY OF
VOICE/DATA JACKS AS NOTED
FLOOR VOICE OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR DATA OUTLET, QUANTITY OF JACKS
AS NOTED
FLOOR COMBINATION VOICE/DATA OUTLET,
QUANTITY OF JACKS AS NOTED
MASTER CLOCK
INTERCOM MASTER STATION
INTERCOM CALL-IN STATION
WALL MOUNTED VOLUME CONTROL
BOX, STUB-UP, AND MODULAR PLATE W/ BLANKS
TELEVISION OUTLET
SPEAKER: CEILING/WALL
MICROPHONE: FLOOR/WALL
FIBER OUTLET
GROUND ROD - C IF CHEMICAL
GROUND CONNECTION (SCHEMATIC)
CONCEALED IN ROOF OR WALLS
GROUNDING CONDUCTOR-
GROUNDING CONDUCTOR- EXPOSED
AIR TERMINAL
GROUNDING PLATE
FACP
FAA
WF
VS
DH
SMOKE DETECTOR/SENSOR - BEAM RECEIVER
SMOKE DETECTOR/SENSOR - BEAM TRANSMITTER
SPEAKER/VISUAL ALARM: CEILING/WALL
VISUAL ALARM: CEILING/WALL
AUDIO/VISUAL ALARM: CEILING/WALL
MANUAL PULL STATION
FIRE ALARM ANNUNCIATOR
FIRE ALARM PANEL
DUCT MOUNTED SMOKE DETECTOR
SMOKE DETECTOR: CEILING / WALL
HEAT DETECTOR: CEILING / WALL
WATER FLOW SWITCH
WATER TAMPER SWITCH
DOOR HOLDER
FIREMAN'S PHONE OUTLET
EWC
WP
H
D
P
I
L
TWO ZONE LOW VOLTAGE SWITCHL2
VACANCY AUTO SHUT OFF
FOUR ZONE LOW VOLTAGE SWITCHL4
DUPLEX RECEPTACLE WITH INTEGRAL USBUSB
TV DUPLEX RECEPTACLETV
AC
ABOVE COUNTER DUPLEX RECEPTACLE (COORDINATE
HEIGHT WITH ARCHITECT)
J-HOOK
SECURITY
C CARD READER
P DOOR POSITION SENSOR
SECURITY CAMERA: CEILING/WALL MOUNTED
ES ELECTRIC STRIKE
C
CABLE TRAY
DUPLEX RECEPTACLE MOUNTED IN RACEWAYR
R DATA OUTLET MOUNTED IN RACEWAY
DUPLEX RECEPTACLE - TAMPER PROOFT
DUPLEX RECEPTACLE - GENERATOR CIRCUIT, RED IN COLOR
QUAD - GENERATOR CIRCUIT, RED IN COLOR
SINGLE ZONE LOW VOLTAGE SWITCHL1
HOMERUN - ONE ARROW PER CIRCUIT
DISCONNECT SWITCH: "F" IF FUSED
F
1 ADDDENDUM No. 1 09.23.21
SCALE:
= 1'-0
4 0 2 4 8
SCALE:
= 1'-0
4 0 2 4 8
E2.0
BOILER/CHILLER MECHANICAL ROOM - DEMOLITION - SYSTEMS/HVAC POWER
LARGE SCALE -
BOILER/CHILLER MECHANICAL ROOM - NEW WORK - SYSTEMS/HVAC POWER
LARGE SCALE -
SYSTEMS/HVAC POWER
DEMOLITION & NEW WORK -
MECHANICAL ROOM -
BOILER/CHILLER
LARGE SCALE -
MDP
XDP
LDP
LB-18
MDP-7
MCC-9
LDP-14
LDP-18
MCC-8
MCC-1
MCC-2
MCC-9
MCC-3
T
45KVA
M
F
WP
J
EF-9
EX.
EF-8
EX.
F A
C P
M C
C
EXISTING HP
REMOVE
EXISTING BOILER
REMOVE
EXISTING TO REMAIN
DEMOLITION
NEW WORK
POINT OF CONNECTION
LINE LEGEND
TO REMAIN
EXISTING AFTERCOOLER
CHEMICAL FEED TO REMAIN
EXISTING CHW BYPASS
EXISTING PUMP GAUGES TO REMAIN
TO REMAIN
EXISTING AIR COMPRESSOR
TO REMAIN
EXISTING CP
EXISTING WATER HEATER TO REMAIN
EXISTING ACP TO REMAIN
EXPANSION TANK TO REMAIN
EXISTING CHW
TO REMAIN
EX. UH
GENERAL NOTES:(THIS SHEET ONLY)
ALL NEW CONDUIT SHALL BE EMT.A
B ALL NEW CONDUCTORS SHALL BE COPPER, THWN-2.
C
NOTES:(THIS SHEET ONLY)
UNSWITCHED HOT TO THESE BATTERY PACKS FOR SENSING POWER LOSS.
TWO OF THE FIXTURES SHALL HAVE INTEGRAL EMERGENCY BATTERY PACKS. PROVIDE
REPLACE WITH FOUR ACUITY MODEL CLX-L96-6000LM-SEF-FDL-MVOLT-GZ10-40K-80CRI.
REMOVE FOUR EXISTING 8 FOOT FLUORESCENT LIGHT FIXTURES FROM THIS SPACE AND 1
1 1
F
F
3AND PROVIDE A NEW LABEL TO INDICATE "SPARE".
BOILER AND THE HEATING WATER PUMP CAN REMAIN IN PLACE. REMOVE EXISTING LABELS
CENTER. THE EXISTING MOTOR CONTROL CENTER BUCKETS THAT CURRENTLY SERVE THE
STARTERS, CONDUCTORS, AND CONDUIT BACK TO SERVING PANELBOARD OR MOTOR CONTROL
FOR ALL EXISTING EQUIPMENT SHOWN TO BE DEMOLISHED, REMOVE ALL DISCONNECTS,
PROVIDE LOCKABLE 30A/2P NON-FUSED DISCONNECT TO FEED THE BOILER.4
BREAKER MATCHING EXISTING PANEL AIC RATING. MAKE ALL FINAL CONNECTIONS.
#12 AWG, ƒ"C TO 1000A POWER STYLE PANELBOARD LDP. PROVIDE A NEW 20A/1P CIRCUIT
PROVIDE DEDICATED 20A, 120 VOLT CONTROL CIRCUIT TO THE NEW BOILER. ROUTE 5
COMPLY WITH THE 2017 NATIONAL ELECTRICAL CODE (NEC).D
NEW FUSED DISCONNECTS SHALL BE HEAVY DUTY (HD) TYPE.E
NEW WIREWAY TO BE MOUNTED ON WALL ABOVE EQUIPMENT. FOLLOW NEC TAP RULES.
PROVIDE 30A/3P FUSED DISCONNECT ON LINE SIDE OF NEW VFD. TAP CONDUCTORS FROM
ADJACENT TO MAIN SERVICE PANEL MDP. REFER TO NOTE 6 BELOW.
ROUTE 3#8 AWG, 1#10G, 1"C FROM NEW WIREWAY BACK TO NEW ENCLOSED CIRCUIT BREAKER
ABOVE HP-1 AND HP-2 VFDS.
1#10G. FOLLOW ALL NEC TAP RULES. LABEL CIRCUIT BREAKER AS "SERVES WIREWAY
CASE CIRCUIT BREAKER ADJACENT TO MDP. TAP CONDUCTORS SHALL BE 4#8 AWG,
TAP THE MAIN BUS IN MAIN SERVICE PANEL MDP AND SET A NEW 30A/3P ENCLOSED 6
1 ADDDENDUM No. 1 09.23.21
P:\20066\20066e20.dgn
DATE PLOTTED
DGN FILE
23-SEP-2021
SEAL
SCALE:
FILE PATH:
SHEET NUMBER:
316 CORPORATE PARKWAY
NBP Engineers, Inc.
MACON, GEORGIA 31210
NBP
ENGINEERS
478-745-1691 www.nbpengineers.com
No. REVISIONS/SUBMISSIONS DATE
DRAWN:
CHECKED:
DESIGNED:
DATE:
PROJECT NUMBER:
P R
O J E
C T
T
IT
L E
SHEET TITLE:
CONSULTANTS
THIS DRAWING IS THE PROPERTY OF THE
ENGINEER AND MAY NOT BE REPRODUCED
OR USED IN WHOLE OR IN PART
WITHOUT HIS WRITTEN PERMISSION. IT IS
TO BE USED FOR THE PROJECT
SPECIFICALLY IDENTIFIED HEREIN AND TO
BE RETURNED UPON REQUEST.
P:\20066\20066e20.dgn
AS SHOWN
08.18.2021
TWT
JCW
TWT
20066
F O
L L
E Y G
E O
R G
IA
S T
A
IV
E R
S
IT
COA Expiration: 6.30.2022
NBP Engineers, Inc. COA#PEF000774
P E
T T
IG
R
W
B
IL
P L
A C
E M
E N
T F
O
L L
A
IV
E R
S
IT
Y
N S T
R U
C T
IO
C U
M E
N T S
F V
P
O J E o P
H B
MDP
XDP
LDP
LB-18
MDP-7
MCC-9
LDP-14
LDP-18
MCC-8
MCC-1
MCC-2
MCC-9
MCC-3
T
45KVA
M
F
WP
J
EF-9
EX.
EF-8
EX.
F A
C P
M C
C
TO REMAIN
EXISTING AFTERCOOLER
CHEMICAL FEED TO REMAIN
EXISTING CHW BYPASS
EXISTING PUMP GAUGES TO REMAIN
TO REMAIN
EXISTING AIR COMPRESSOR
TO REMAIN
EXISTING CP
EXISTING WATER HEATER TO REMAIN
EXISTING ACP TO REMAIN
EXPANSION TANK TO REMAIN
EXISTING CHW
TO REMAIN
EX. UH
BLR-1
NEW
NEW VFD
NEW ACP
HP-1
NEW
HP-2
NEW
| 20066e00 |
| References |
| tb, 20066tb.dgn |
| 20066e20 |
| References |
| tb, 20066tb.dgn |
| afp1, 20066aX1.dgn |
| afp2, 20066aX1.dgn |
| existing, 20066e20.dgn |
| new Hvac equip, 20066m20.dgn |
Other files
| File | Type | Posted |
|---|---|---|
| Cancelation Notice | — | |
| Pre-Bid Sign In Sheet | — | |
| Project Drawings | — | |
| Project Manual | — | |
| Addendum 1 | — | |
| Invitation to Bid | — |