About this file

This is an Addendum 04 document issued by the Missouri Department of Transportation (MoDOT) addressing supplier questions regarding radio tower grounding system specifications for a state contract opportunity. The addendum responds to a supplier's request for clarification on grounding system design requirements, specifically addressing concerns that the R56 specification alone provides insufficient information for proper grounding system design and installation.

MoDOT's response clarifies that Motorola R56 grounding specifications establish industry standards for telecommunications sites and require the creation of a single, low-resistance common grounding system with a target resistance of under 5 ohms. The response specifies minimum requirements including bare copper conductors of at least #6 AWG, ground rods of 8 feet or longer with a minimum diameter of 5/8 inches, ground plates with a minimum area of 2 square feet, and ground rod spacing of 10 to 15 feet. All elements including power, communications, and lightning protection systems must be bonded together with appropriate bonding jumpers and clear pathways for surge dissipation. These specifications exceed basic electrical code requirements to ensure critical system safety at telecommunications sites.

View the file

Other files

File Type Posted
MODOT 0000000123SL_6_SUPPLIER.pdf PDF
Addendum 03 - Radio Towers.docx DOCX document
Addendum 01 - Radio Towers.docx DOCX document
Bid Bond & Anti-Collusion Document.pdf PDF
32_WO026 Prevailing Wage Cole County.pdf PDF
32_WO080 Prevailing Wage Pettis County.pdf PDF
Addendum 02 - Radio Towers.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Addendum 04 Supplier Question and MoDOT Response:

Question 1: I am being told that R56 specification is not enough information to design grounding system. Will following be clarified? Size and length of ground rods, ground rod spacing, grounding wire size.

Response: Motorola R56 grounding specs set industry standards for telecom sites, focusing on creating a single, low-resistance (ideally under 5 ohms) common grounding system by bonding all elements (power, comms, lightning) with bare copper conductors (min #6 AWG), using proper ground rods (8ft+, 5/8" min) or plates (2 sq ft min), and ensuring clear pathways for surge dissipation. Key elements include minimum conductor sizes, ground rod spacing (10-15 ft), and bonding jumpers, exceeding basic electrical codes for critical system safety.