Add-Alter B210 - Type B-3 - Specs Div 26-33.pdf
PDF 6 MB Posted
- Attached to
- ADAL Communications Bldg 210 Construction Federal contract opportunity
- Solicitation number
- W50S8Z25BA010
About this file
This file contains specifications for electrical systems and components related to project KJAQ199077 for the Add/Alter Communications Building 210 at Kingsley Field Air National Guard Base in Oregon. The specifications detail requirements for a comprehensive interior electrical distribution system including conduit, wiring, cable trays, transformers, circuit breakers, switches, receptacles, motor controllers, and other electrical equipment. The document provides detailed technical requirements for materials and installation, with specific focus on seismic protection requirements, power system studies, and testing procedures. Key requirements include high-efficiency motors, surge protection, grounding systems, and coordination with telecommunications infrastructure.
The specifications fall under Department of the Army Oregon Army National Guard contract W50S8Z25BA010 and reference UFC and industry standards including NFPA 70, UL listings, and NEMA requirements. Materials must meet rigorous quality standards with products manufactured no more than 24 months prior to delivery. Specific attention is given to proper labeling, testing, and documentation requirements, including arc flash hazard studies and coordination studies. The contractor must provide complete operation and maintenance data for all electrical systems installed.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract of Offers B210_Final.pdf | ||
| Pre Bid RFIs_Answer Sheet V5 -6 Feb 2025.docx | DOCX document | |
| OR_gnsrv_NoRfnd.pdf | ||
| Add-Alter B210 - Type B-3 - Amendment 1.pdf | ||
| Solicitation - W50S8Z25BA010 Amendment 4.pdf | ||
| D101-210-0324.pdf | ||
| Pre Bid RFIs_Answer Sheet V4 -24 Jan 25.docx | DOCX document | |
| Pre-bid Conference Sign in Sheet.pdf | ||
| Solicitation - W50S8Z25BA010 Amendment 2.pdf | ||
| Pre Bid RFIs_Answer Sheet V3.docx | DOCX document | |
| Solicitation - W50S8Z25BA010 - Amendment 1.pdf | ||
| Add-Alter B210 - Type B-3 - Drawings.pdf | ||
| JA Brand Name - Automatic Logic KO Signed.pdf | ||
| WD OR20240093.pdf | ||
| Add-Alter B210 - Type B-3 - Specs Div 01-07.pdf | ||
| JA Brand Name - Monaco Fire panels 18 Nov KO Signed.pdf | ||
| Add-Alter B210 - Type B-3 - Specs Div 08-25.pdf | ||
| Solicitation - W50S8Z25BA010.pdf | ||
| JA Brand Name - Advantor Final 18 Nov KO Signed.pdf |
Show all 19
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T Y P E B - 3 F I N A L
Add/Alter Communications B210 Project No. KJAQ199077
Specifications (Divisions 26-33)
Prepared for
173rd Civil Engineering Squadron Oregon Air National Guard
Kingsley Field ANG Base, OR
September 2024
Jacobs Government Services Company
1100 NE Circle Blvd, Suite 300 Corvallis, OR 97330
ADD/ALTER B210 COMMUNICATIONS OR AIR NATIONAL GUARD
KINGSLEY FIELD ANGB, OR PROJECT NO. KJAQ199077
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REQUIREMENTS AND REPORTING
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 45 00 QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 00 CLOSEOUT SUBMITTALS
01 91 00.15 BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
02 42 51 CARPET REMOVAL AND RECLAMATION
02 81 00 TRANSPORTATION AND DISPOSAL OF HAZARDOUS MATERIALS
02 82 00 ASBESTOS REMEDIATION
02 83 00 LEAD REMEDIATION
02 84 16 HANDLING OF LIGHTING BALLASTS AND LAMPS CONTAINING PCBs
AND MERCURY
02 84 33 REMOVAL AND DISPOSAL OF POLYCHLORINATED BIPHENYLS (PCBs)
DIVISION 03 - CONCRETE
03 01 00 REHABILITATION OF CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 05 20 POST-INSTALLED CONCRETE AND MASONRY ANCHORS
05 05 23.13 10 ULTRASONIC INSPECTION OF WELDMENTS
05 05 23.16 STRUCTURAL WELDING
05 12 00 STRUCTURAL STEEL
05 30 00 STEEL DECKS
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 72 00 DECORATIVE METAL SPECIALTIES
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
01 78 23 OPERATION AND MAINTENANCE DATA
01 50 00 TEMPORARY CONTRUCTION FACILITIES AND CONTROLS
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 27 10 BUILDING AIR BARRIER SYSTEM
07 27 19.01 SELF-ADHERING AIR BARRIERS
07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS
07 41 13 METAL ROOF PANELS
07 41 63 FABRICATED ROOF PANEL ASSEMBLIES
07 42 13 METAL WALL PANELS
07 42 63 FABRICATED WALL PANEL ASSEMBLIES
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 31 00 ACCESS DOORS AND PANELS
08 33 13 COILING COUNTER DOORS
08 33 23 OVERHEAD COILING DOORS
08 34 73 SOUND CONTROL DOOR ASSEMBLIES
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL AND DOOR LOUVERS
DIVISION 09 - FINISHES
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 62 38 STATIC-CONTROL FLOORING
09 65 00 RESILIENT FLOORING
09 68 00 CARPETING
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 22 39 FOLDING PANEL PARTITIONS
10 26 00 WALL AND DOOR PROTECTION
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
DIVISION 12 - FURNISHINGS
12 21 00 WINDOW BLINDS
DIVISION 21 - FIRE SUPPRESSION
21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
21 22 00.00 40 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 05 48.19 SEISMIC BRACING FOR HVAC
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 08 00 COMMISSIONING OF MECHANICAL AND PLUMBING SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 20 FACILITY GAS PIPING
23 23 00 REFRIGERANT PIPING
23 30 00 HVAC AIR DISTRIBUTION
23 52 00 HEATING BOILERS
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
23 81 23 COMPUTER ROOM AIR CONDITIONING UNITS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
DIVISION 26 - ELECTRICAL
26 05 48 SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
26 05 73 POWER SYSTEM STUDIES
26 08 00 APPARATUS INSPECTION AND TESTING
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 27 13.10 30 ELECTRIC METERS
26 29 23 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS UNDER 600 VOLTS
26 32 15.00 ENGINE-GENERATOR SET STATIONARY 15-2500 KW, WITH
AUXILIARIES
26 33 53 STATIC UNINTERRUPTIBLE POWER SUPPLY (UPS)
26 36 23 AUTOMATIC TRANSFER SWITCHES AND BY-PASS/ISOLATION SWITCH
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 13.43 TELEVISION DISTRIBUTION SYSTEM
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 51 16 PUBLIC ADDRESS SYSTEMS
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 10 05 ELECTRONIC SECURITY SYSTEMS (ESS)
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM,
ADDRESSABLE
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 11 00 CLEARING AND GRUBBING
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 11 20 BASE COURSE FOR RIGID PAVING
32 11 23 AGGREGATE BASE COURSE FOR FLEXIBLE PAVING
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 ROAD-MIX ASPHALT PAVING
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 31 13 CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
DIVISION 33 - UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORMWATER UTILITIES
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
-- End of Project Table of Contents --
CODES AND STANDARDS REFERENCED HEREIN
THIS PROJECT IS DESIGNED IN ACCORDANCE WITH THE 2021 INTERNATIONAL BUILDING
CODE (IBC) AND THE 2021 INTERNATIONAL EXISTING BUILDING CODE (IEBC) AS
MODIFIED BY UFC 1-200-01, 12 JUNE 2023.
THE UNITED FACILITIES GUIDE SPECIFICATIONS (UFGS) ARE UPDATED REGULARLY.
THE VERSION OR EDITION OF CODES AND STANDARDS REFERENCED HEREIN MAY
DIFFER FROM THOSE SPECIFIED IN CHAPTER 35 OF THE 2021 IBC AND CHAPTER 16 OF
THE 2021 IEBC. IN THE EVENT OF DISCREPENCIES REGARDING VERSION OR EDITION OF
CODES AND STANDARDS, THE 2021 IBC AND 2021 IEBC WILL TAKE PRECEDENCE.
Section 26 05 48 Page 1
SECTION 26 05 48
SEISMIC PROTECTION FOR ELECTRICAL EQUIPMENT
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
ASCE 7-16 (2017; Errata 2018; Supp 1 2018) Minimum
Design Loads and Associated Criteria for Buildings and Other Structures
AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME)
ASME B18.21.1 (2009; R 2016) Washers: Helical Spring-Lock, Tooth Lock, and Plain Washers (Inch Series)
ASME B18.22M (1981; R 2017) Metric Plain Washers
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2020; Errata 1 2021) Structural Welding Code
- Steel
ASTM INTERNATIONAL (ASTM)
ASTM A36/A36M (2019) Standard Specification for Carbon
Structural Steel
ASTM A53/A53M (2022) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A153/A153M (2023) Standard Specification for Zinc
Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A307 (2021) Standard Specification for Carbon
Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength
ASTM A500/A500M (2021a) Standard Specification for Cold-
Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM A563 (2021; E 2022a) Standard Specification for
Carbon and Alloy Steel Nuts
Section 26 05 48 Page 2
ASTM A572/A572M (2021; E 2021) Standard Specification for High-Strength Low-Alloy Columbium-Vanadium Structural Steel
ASTM A603 (2019) Standard Specification for Zinc-Coated
Steel Structural Wire Rope
ASTM A992/A992M (2022) Standard Specification for Structural
Steel Shapes
ASTM B695 (2021) Standard Specification for Coatings of
Zinc Mechanically Deposited on Iron and Steel
ASTM E580/E580M (2022) Standard Practice for Installation of
Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Subject to Earthquake Ground Motions
ASTM F436 (2011) Hardened Steel Washers
ASTM F959/F959M (2017a) Standard Specification for
Compressible-Washer-Type Direct Tension Indicators for Use with Structural Fasteners, Inch and Metric Series
ASTM F1554 (2020) Standard Specification for Anchor
Bolts, Steel, 36, 55, and 105-ksi Yield Strength
ASTM F3125/F3125M (2019) Standard Specification for High
Strength Structural Bolts and Assemblies, Steel and Alloy Steel, Heat Treated, Inch Dimensions 120 ksi and 150 ksi Minimum Tensile Strength, and Metric Dimensions 830 MPa and 1040 MPa Minimum Tensile Strength
ICC EVALUATION SERVICE, INC. (ICC-ES)
ICC ES AC156 (2012) Acceptable Criteria for Seismic
Certification by Shake-Table Testing of Nonstructural Components
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2021) International Building Code
METAL FRAMING MANUFACTURERS ASSOCIATION (MFMA)
MFMA-4 (2004) Metal Framing Standards Publication
U.S. DEPARTMENT OF DEFENSE (DOD)
MIL-STD-810 (2022; Rev H; Change 1) Environmental
Engineering Considerations and Laboratory Tests
UFC 3-301-01 (2023) Structural Engineering
Section 26 05 48 Page 3
UFC 3-301-02 (2020) Design of Risk Category V Structures, National Strategic Military Assets
UNDERWRITERS LABORATORIES (UL)
UL 1598 (2021; Reprint Jun 2021) Luminaires
VIBRATION ISOLATION AND SEISMIC CONTROL MANUFACTURERS ASSOCIATION
(VISCMA)
VISCMA 413 (2014) Installing Seismic Restraints for
Electrical Equipment
1.2 SYSTEM DESCRIPTION
1.2.1 General Requirements
Design and provide seismic supports and attachments in accordance with UFC 3-301-01 and ASCE 7-16.
Provide seismic supports and attachments as indicated and in accordance with UFC 3-301-01 and ASCE 7-16.
Components, supports, and attachments must comply with following structural design criteria:
Risk Category: II.
Seismic Design Category: D.
Seismic Design Spectral Response Acceleration Parameter at Short Period (SDS): See Structural Drawings.
Apply the seismic requirements described in this section and on the drawings to the electrical components listed in paragraph ELECTRICAL COMPONENTS.
Electrical components and their supports must be attached or anchored to structure.
1.2.2 Electrical Components
Provide seismic supports and attachments for the following electrical components in accordance with the requirements of this specification:
Components with Importance Factor (Ip) = 1.0:
Battery Systems Control Panels Generators Light Fixtures Motors Transformers Uninterruptible Power Supply Systems Distribution Systems Conduit, Cable Tray, and Raceway Utility and Service Lines
Components with Importance Factor (Ip) = 1.5 Designated Seismic Systems
Emergency and standby power systems Fire detection and suppression systems
Section 26 05 48 Page 4
Emergency exit lighting
1.2.3 Contractor Designed Supports and Attachments
Provide seismic supports and attachments, and isolation and energy dissipation systems for electrical components.
Contractor must retain services of a Registered Professional Engineer to design supports and attachments, and isolation and energy dissipation systems for electrical components. Supports and attachments, and isolation and energy dissipation systems that induce torsion in structural members are not permitted.
Submit copies of the Design Calculations and Design Drawings. Calculations and Drawings must be stamped and signed by Contractor's Registered Professional Engineer.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Equipment Requirements; G
Lighting Fixtures; G
SD-03 Product Data
Supports and Attachments; G
Equipment Requirements; G
Lighting Fixtures; G
Flexible Fittings; G
Anchors; G
Isolation And Energy Dissipation Systems; G
SD-05 Design Data
Design Calculations; G
Design Drawings; G
SD-06 Test Reports
Anchors; G
Section 26 05 48 Page 5
SD-07 Certificates
ICC ES AC156 Shake Table Test; G
PART 2 PRODUCTS
2.1 EQUIPMENT REQUIREMENTS
Equipment must be rugged enough to survive design seismic event.
Submit detail drawings of supports and attachments, and isolation and energy dissipation systems along with calculations, catalog cuts, templates, and erection and installation details, as appropriate, for the items listed in paragraph ELECTRICAL COMPONENTS. Indicate thickness, type, grade, class of metal, and dimensions; and show construction details, reinforcement, anchorage, and installation with relation to the building construction.
Submit calculations and drawings that are stamped and signed by Contractor's registered professional engineer. Design must be based on actual equipment and system layout. Design must include calculated loads and capacity of materials utilized for the connection of the equipment or system to the structure. Analysis must detail anchoring methods. Include drawing for Designated Seismic System Equipment indicating the equipment location in the facility to be used for the installation. Equipment must be rigidly or flexibly mounted as indicated. Roof mounted equipment both vibration isolated and nonisolated, must have support members designed and anchored to building structure.
2.1.1 Rigidly (Base and Suspended) Mounted Equipment
The following specific items of equipment must be constructed and assembled to withstand the seismic forces specified in UFC 3-301-01. Entirely locate each item of rigid electrical equipment and rigidly attach on one side only of a building expansion joint. Provide items such as electrical conduit, which cross the building expansion joint with flexible joints that are capable of accommodating displacements equal to the full width of the joint in each orthogonal direction.
Engine-Generators Transformers Free Standing Electric Motors
Equipment furnished under this Contract must be rigidly mounted using cast-in-place anchor bolts or post-installed anchors that are qualified for use in cracked concrete. Cast-in-place anchor bolts must conform to ASTM F1554.
For any rigid equipment which is rigidly anchored, provide flexible joints for electrical conduit, cabletray, busway, and raceway, that are capable of accommodating displacements equal to the full width of the joint in both orthogonal directions. Designated Seismic Systems (DSS) for RC IV buildings assigned to Seismic Design Category (SDC) C, D, E, or F and Risk Category IV components needed for continued operation after an earthquake must have two nuts provided on each bolt.
Section 26 05 48 Page 6
2.2 LIGHTING FIXTURES
Provide lighting fixtures and supports and attachments conforming to UL 1598.
2.3 SUPPORTS AND ATTACHMENTS
Material used for members listed in this section and on the drawings, must conform with the following:
a. Plates, rods, and rolled shapes, ASTM A36/A36M, ASTM A572/A572M Grade
50, or ASTM A992/A992M.
b. Wire rope, ASTM A603 pre-stretched, with Class B weight zinc-coated wires throughout rope. Connect rope at ends using ferrule or saddle-type wire rope clamp systems. Ferrule clamps must be qualified by testing for use in seismic applications per VISCMA 413. Saddle-type clamps must be used with minimum of two clamps at each end of wire rope.
c. Tubes, ASTM A500/A500M, Grade B.
d. Pipes, ASTM A53/A53M, Grade B.
e. Angles, ASTM A36/A36M.
f. Channels (Struts) with in-turned lips and associated hardware for fastening to channels at discrete points conforming to MFMA-4.
g. Fasteners:
(1) High-strength bolts, ASTM F3125/F3125M, Grade A325, heavy hex.
(2) Nuts, ASTM A563. Use heavy hex nuts for high strength bolts and anchor bolts.
(3) Washers, ASME B18.22M and ASME B18.21.1, except use ASTM F436 washers for high strength bolts.
(4) Galvanized coating, ASTM A153/A153M.
(5) Direct Tension Indicator Washers, ASTM F959/F959M. Provide ASTM B695, Class 55, Type 1 galvanizing. Submit product data for direct tension indicator washers.
(6) Standard bolts, ASTM A307.
h. Anchor bolts:
(1) Cast in anchors: Refer to Section 05 12 00 STRUCTURAL STEEL and 05
50 13 MISCELLANEOUS METAL FABRICATIONS for requirements.
(2) Post-installed anchors: Refer to Section 05 05 20 POST-INSTALLED CONCRETE AND MASONRY ANCHORS for requirements.
i. Welding: Refer to Section 05 12 00 STRUCTURAL STEEL for requirements.
Section 26 05 48 Page 7
2.4 FLEXIBLE FITTINGS
Provide flexible fittings to allow conduit, cabletray, busway, and raceway systems to accommodate seismic movement between equipment and conduit, cabletray, busway, and raceway systems and supporting structure. Use specification grade steel fittings conforming to Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM. Provide suitable watertight expansion fittings that maintain electrical continuity by bonding jumper or other means.
PART 3 EXECUTION
3.1 SUPPORTS AND ATTACHMENTS
Provide supports and attachments with continuous load path to distribute electrical component seismic loads to structure.
Provide supports and attachments for electrical components that conform to UFC 3-301-01 requirements. Install vertical diagonal braces at a 45-degree slope. Where interference is present, the slope may be minimum of 30 degrees or a maximum of 60 degrees per VISCMA 413.
Provide bolted and welded connections for supports and attachments in accordance with UFC 3-301-01.
Provide welding in accordance with AWS D1.1/D1.1M.
3.2 BUILDING DRIFT
Do not attach electrical components to two dissimilar structural elements of a building that may respond differentially during an earthquake unless a flexible joint is provided. Electrical components, supports, and attachments must be capable of accommodating building story drifts, deflections, and relative displacements.
3.3 CONDUIT, CABLETRAY, BUSWAY, AND RACEWAY
Provide supports and attachments for conduit, cabletray, busway, and raceway conforming to the requirements of UFC 3-301-01.
3.4 LIGHTING FIXTURES
Provide lighting fixtures and supports conforming to the following:
3.4.1 Pendant Fixtures
Provide pendant fixtures conforming to the requirements of UFC 3-301-01.
3.4.2 Ceiling Attached Fixtures
3.4.2.1 Recessed Fixtures
Support recessed individual or continuous-row mounted fixtures by a seismic-resistant suspended ceiling support system built in accordance with ASTM E580/E580M. Provide supports and attachments for the fixtures conforming to the requirements of UFC 3-301-01. Recessed lighting fixtures not over 56 pounds in weight and not required to be supported separately from the structure, may be supported by and attached directly to the ceiling system
Section 26 05 48 Page 8 runners using screws or bolts, number and size as required by the seismic design. Provide lock or screw attachments for fixture accessories, including diffusers and lenses.
3.4.2.2 Surface-Mounted Fixtures
Attach surface-mounted individual or continuous-row fixtures to a seismic-resistant ceiling support system built in accordance with Section 09 51 00 ACOUSTICAL CEILINGS. Provide supports and attachments for the fixtures conforming to the requirements of UFC 3-301-01.
3.4.3 Assembly Mounted on Outlet Box
Design a supporting assembly, that is intended to be mounted on an outlet box, to accommodate mounting features on 4 inch boxes, plaster rings, and fixture studs.
3.4.4 Wall-Mounted Emergency Light Unit
Design and secure attachments for wall-mounted emergency light units for the worst expected seismic disturbance at the site.
3.5 ANCHORS
3.5.1 General
Submit copies of test results to verify the adequacy of the specific anchor and application, as specified. Ensure housekeeping pads have adequate space to mount equipment and seismic restraint devices allowing adequate edge distance and embedment depth for restraint anchor bolts. Identify position of reinforcing steel and other embedded items prior to drilling holes for post-installed anchors. Do not drill holes in concrete or masonry until concrete, mortar, or grout has achieved full design strength. Fill annular gap with nonshrink grout at equipment anchor bolts where clearance between anchor and equipment support hole exceeds 0.125 inches.
3.5.2 Cast-In-Place Anchors
Use templates to locate cast-in-place bolts accurately and securely in formwork. Provide anchor bolts with an embedded straight length with heavy hex nut and plate washer as to provide required strength and ductility.
Anchor bolts that exceed the normal depth of equipment foundation piers or pads must either extend into concrete floor or the foundation or increase depth of the piers or pads to accommodate bolt lengths.
3.5.3 Post-Installed Anchors
Refer to Section 05 05 20 POST-INSTALLED CONCRETE AND MASONRY ANCHORS for requirements.
3.6 EQUIPMENT SUPPORT REQUIREMENTS
3.6.1 Suspended Equipment
Provide supports and attachments for components supported from structural systems. Provide supports and attachments that consist of angles, rods, wire rope, bars, channels (struts) or pipes arranged as shown in bracing
Section 26 05 48 Page 9 submittals and secured at both ends with not less than 1/2 inch bolts.
Provide sufficient supports and attachments to resist seismic forces as specified in UFC 3-301-01 without exceeding capacity of structural components.
Submit details of supports and attachments for acceptance. In lieu of bracing with vertical supports, these items may be supported with hangers inclined at 45 degrees directed up and radially away from equipment and oriented symmetrically in 90-degree intervals on the horizontal plane, bisecting the angles of each corner of the equipment, provided that supporting members are properly sized to support operating weight when hangers are inclined. Where interference is present, the inclined hanger slope may be minimum of 30 degrees or a maximum of 60 degrees per VISCMA 413.
3.6.2 Floor or Pad Mounted Equipment
3.6.2.1 Shear Resistance
Bolt components to floor or pads. Provide bolts to resist seismic forces in accordance with paragraph ANCHORS.
3.6.2.2 Overturning Resistance
Use the ratio of the overturning moment from seismic forces to the resisting moment due to gravity loads to determine if overturning forces need to be considered in the sizing of anchor bolts. Provide calculations to verify the adequacy of the anchor bolts for combined shear and tension. Provide bolts to resist seismic forces in accordance with paragraph ANCHORS.
3.7 SPECIAL TESTING FOR SEISMIC-RESISTING COMPONENTS
Electrical components designated as Designated Seismic Systems required to remain operational after an earthquake must be seismic qualified by shake table testing conforming to ICC ES AC156 Shake Table Test procedures. The manufacturer is to provide a certification by a fully qualified testing agency for the specific components. Prequalified certifications are acceptable unless noted otherwise.
Components that are required to be certified must bear permanent marking or nameplates constructed of a durable heat and water resistant material.
Provide component identification nameplates in accordance with UFC 3-301-01.
Mechanically attach nameplates to electrical components.
3.8 SPECIAL INSPECTION FOR COMPONENTS, SUPPORTS, AND ATTACHMENTS
Perform special inspections for seismic-resisting systems, designated seismic systems, components, supports and attachments, and equipment per Section 01 45 35 SPECIAL INSPECTION attachment Schedule of Special Inspections and ICC IBC 1705.13.4; electrical components per ICC IBC 1705.13.6.
Special Inspector must inspect and test items required in Schedule of Special Inspections and Statement of Special Inspection.
Section 26 05 48 Page 10
Special Inspector must examine Designated Seismic Systems requiring seismic qualification in accordance with ASCE 7-16 and verify the label, anchorage and mounting conform to the certificate of compliance.
Provide a Statement of Special Inspections and Final Special Inspection Report in accordance with UFC 3-301-01.
-- End of Section --
Section 26 05 73 Page 1
SECTION 26 05 73
POWER SYSTEM STUDIES
The publications listed below form a part of this specification to the
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 1584 (2018; E 2019) Guide for Performing Arc-Flash
Hazard Calculations
IEEE 1584.1 (2022) Guide for the Specification of Scope and Deliverable Requirements for an Arc-Flash Hazard Calculation Study
IEEE 3002.2 (2018) Recommended Practice for Conducting
Load-Flow Studies and Analysis of Industrial and Commercial Power Systems
IEEE 3002.3 (2018) Recommended Practice for Conducting
Short-Circuit Studies and Analysis of Industrial and Commercial Power Systems
IEEE C2 (2023) National Electrical Safety Code
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70E (2024) Standard for Electrical Safety in the
Workplace
1.2 SYSTEM DESCRIPTION
The power system covered by this specification consists of: The electrical distribution system beginning at the secondary of the pad-mounted transformer and downstream including all distribution within Building 210.
classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section C:\USERS\RICHARJ1\ONEDRIVE - JACOBS\DP- SPECIFICATIONS\Jobs\FA877009\prntdata\Word\01 33 00.docx SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals
Field Examination Plan; G
Section 26 05 73 Page 2
Arc Flash Label Formats; G
Field Examination
System Analyzer; G
SD-11 Closeout Submittals
Model Files; G
Load Flow Study; G
Fault Current Study; G
System Coordination Study; G
Arc Flash Hazard Study; G
1.4 QUALITY ASSURANCE
1.4.1 System Analyzer
The System Analyzer must perform the power system studies. The System Analyzer must be a registered professional electrical engineer with a minimum of 3 years of experience with power system studies. Include a list of three comparable jobs performed by the System Analyzer with specific names and telephone numbers for reference. Include the license number and state of the registered Professional Engineer.
1.4.2 System Verifier
The System Verifier may inspect and record settings, markings, and otherwise document the existing equipment. The System Verifier may also place appropriate hazard labels on equipment. The System Verifier must not make any calibrations or adjustments or place equipment into service. When working with energized equipment, the system verifier must be a Qualified Person per NFPA 70E or working under the direct supervision of a Qualified Person. The System Verifier may communicate with the system owner to determine if the equipment within the studied system has received maintenance and testing in accordance with NETA MTS or NFPA 70B.
Not used.
3.1 FIELD EXAMINATION
For each pre- and post-study inspection, submit a field examination plan identifying which facilities must be examined to complete the required work.
Include a complete information verification procedure, where Qualified Personnel will be required, PPE requirements for "live" equipment
Section 26 05 73 Page 3 examinations, and equipment to be used within the limited approach boundary of the equipment.
3.1.1 General
Perform field inspections of the site and equipment before the first study and after the last study to determine the state and settings of the equipment and to verify the final settings agree with the studies. Perform the post-study inspection(s) after changing settings, after performing acceptance tests, and before placing equipment in service.
Schedule the field examination by the System Verifier with the Contracting Officer at least 10 business days before conducting examination. Furnish all materials, labor, and equipment necessary to conduct the examination.
Maintain a written record of the all equipment examined, equipment location, equipment ratings, settings, personnel involved, and the date the examination was performed. Submit the written record of each field examination.
3.1.2 Safety
Where examination of the equipment requires energized equipment to be opened, provide a Qualified Person to directly supervising any non-Qualified Person within the hazard area. Use PPE, protective barriers, danger signs and other safety devices to protect and warn personnel in the vicinity of "live" equipment being examined.
3.1.3 Application of Arc Flash Labels
Install arc flash warning labels using Qualified Personnel as necessary after the setting and inspection is complete. For new or modified equipment, install labels before the equipment is energized for the first time after installation/modification or setting changes. Schedule the label placement with the Contracting Officer at least 5 business days before label placement. Furnish all materials, labor, and equipment necessary to place the labels. Maintain a written record of the all equipment that received labels, personnel involved, and the date labels were placed.
3.2 POWER SYSTEM STUDIES
Perform power system studies to demonstrate that the equipment selected and system constructed meet the contract requirements for fault current and interrupt ratings, coordination, protection, and Arc Flash Hazard. Submit reports of the studies along with protective device equipment submittals.
Apply Arc Flash Hazard labels to equipment after the studies are approved.
Update and resubmit the studies after any changes to the equipment or systems which may affect the study results, and re-apply Arc Flash Hazard labels to equipment after the resubmitted studies are approved. The Government is not responsible for any changes to equipment, device ratings, settings, or additional labor for installation of equipment or devices or labels ordered and/or procured before approval of the study.
3.2.1 Scope of Studies
Section 26 05 73 Page 4
The scope of the studies must begin at the utility service entrance of a building and extend down to load buses/panels where the fault current is 2,000 amperes or less (symmetrical) for distribution buses nominally operating at 208 volt AC and above.
The "source bus" is the source of energy for system being analyzed. This may be the energy feed from a utility, the first bus upstream of the work, generators within the work or upstream of the work, or any other source capable of contributing significant energy into the system being analyzed.
In the systems model for the studies, incorporate all existing and new equipment within the scope of the studies. Incorporate any additional sources or load equipment necessary to accurately model the system's performance.
Where multiple sources of power may be in service in various combinations or where electrical loops are in the system, incorporate into the studies all the modes of operation to evaluate the impact of the modes of operation on the system. The primary modes of operation are listed below.
1. ATS in normal position where utility is powering the distribution system in Building 210.
2. ATS is in emergency position where the generator is power the distribution system in Building 210.
3.2.2 Determination of Facts
Determine and document the time-current characteristics, features, ratings, ampacities, and nameplate data for each existing protective device, electrical equipment, and feeder cables. Obtain the available fault current from the owner of the source bus. For multiple modes of operation, use the mode with available fault current that produces the greatest incident energies in the arc flash hazard study.
Utilize field-verified data in the power system studies. Document the field-verified data in the report.
3.2.3 Single Line Diagram
Provide a single line diagram showing the electrical system buses, devices, transformation points, and all sources of load current and fault current, including generator and motor contributions. Provide a diagram from the system model. Each bus, device or transformation point must have a unique identifier. Show the location of switches, breakers, and circuit interrupting devices on the diagram together with available fault data, and the device interrupting rating.
The naming of existing components within the system model and single line diagram must match existing installed equipment names. The naming of new components within the system model and single line diagram must use unique identifiers and be coordinated with the Government.
3.2.4 Load Flow Study
Section 26 05 73 Page 5
Perform the load flow study in accordance with IEEE 3002.2 to identify initital steady-state conditions for the fault current study. For each operating scenario, provide load flow results on the diagram or in the report. Show or describe the loading factors and assumptions used in each operating mode.
3.2.5 Fault Current Study
Use the results of the load flow study to perform the fault current study in accordance with IEEE 3002.3. Provide balanced three-phase fault, bolted line-to-line fault, and single line-to-ground fault current values at each voltage transformation point and at each power distribution bus. For each location, show in tabular form on the diagram or in the report the maximum and minimum available fault currents of all modes of operation for that location.
Where the available fault current at the source bus is not available, describe how the fault contribution from the source bus was determined and why this method is reasonable for the study.
3.2.6 System Coordination Study
Use the results of the load flow study and fault current study. For normal modes of operation, demonstrate that selectivity has been obtained between the devices within the scope of the project. Demonstrate the equipment, machines, and conductors are protected from damage from overloads and fault conditions. Include a description of the coordination of the protective devices in this project. Provide a written narrative describing which devices may operate in the event of a fault at each bus; the logic used to arrive at device ratings and settings; situations where system coordination is not achievable due to device limitations; coordination between upstream and downstream devices; and relay settings. Provide recommendations to improve or enhance system reliability, and detail where such changes would involve additions or modifications to the contract and cost damages (addition or reduction). Provide composite coordination plots on a log-log scale. Where recommendations are provided to improve or enhance system reliability, provide separate coordination plots on log-log scale showing the system coordination before and after the implementation of the recommendations. Where coordination has been adjusted to lower arc flash values, include a discussion of the change and the impact on the system within the report.
3.2.7 Arc Flash Hazard Study
Perform the arc flash hazard study in accordance with IEEE 1584.1. Utilize the data from the fault current study to determine the worst case incident energy per IEEE 1584 and OSHA 29 CFR 1910.269 Appendix E. Use identified modes of operation to determine the worst case arc flash energy. If not included in another study, include a description of the devices and device settings for the operating modes that provided the highest arc flash energy.
The use of a "maintenance switch" to temporarily reduce the Arc Flash incident energy for maintenance work is acceptable. Where the adjusting the coordination of devices to obtain lower arc flash values, include a discussion of the change and the impact on the system within the report.
Where the arc flash energies exceed 4 cal/cm2 provide recommendations to reduce the arc flash energy to 4 cal/cm2.
Section 26 05 73 Page 6
Where the AC system voltage is 208 volts or less with an available short-circuit current less than 2000 A, an arc flash hazard study is not required.
3.2.8 Study report(s)
a. Include a narrative describing the studies performed; the bases and methods used; and the desired method of coordinated protection of the power system.
b. Include descriptive and technical data for existing devices and new protective devices proposed. Include manufacturers published data, nameplate data, and definition of the fixed or adjustable features of the existing or new protective devices. For existing devices, included statements on the condition of the equipment based upon field inspections and owner's statements and reports.
c. Document utility company data including system voltages, fault MVA, system X/R ratio, time-current characteristic curves, current transformer ratios, and relay device numbers and settings; generator resistance and reactance values, and time constants; and existing power system data including time-current characteristic curves and protective device ratings and settings. Identify all assumptions about the protection devices, equipment, and system where data was not available.
d. For each bus in the system, provide fully coordinated composite time-current characteristics (TCC) curves as required to ensure coordinated power system protection between protective devices and equipment. In a tabular format, provide existing and recommended ratings and settings of all protective devices.
e. Provide an arc flash study report in accordance with IEEE 1584.1.
f. Provide the calculations performed for the studies, including computer programs utilized. Provide the name of the software package, developer, and version number.
f. The System Analyzer must stamp the study reports.
3.2.9 Arc Flash Labels
Provide arc flash warning labels on electrical equipment likely to require examination, servicing, or maintenance while energized. Typical types of equipment include pad-mounted transformers, switchgear, switchboards, panelboards, disconnect switches, industrial control panels, meter socket enclosures, and motor control centers that are in other than dwelling occupancies. The arc flash label naming must match the naming used in the system modeling and the single line diagram.
Comply with the label requirements specified in . Obtain approval of arc flash label formats before printing.
a. Provide a 3.5 inch x 5 inch to 4 inch x 6 inch thermal transfer type label of high adhesion polyester for each location device analyzed.
The label must remain in place and be legible for at least 5 years in the installed environment.
Section 26 05 73 Page 7
b. Labels must be machine printed with no field markings. Provide arc flash labels in the following manner. All labels must be based on implemented overcurrent devices and settings.
1. Provide at least one arc flash label for each 480 volt and 208 volt panelboards.
2. Provide at least one arc flash label for each low voltage (less than 1000 V) switchboard.
3. Where the equipment construction has different hazards levels in different areas, provide a single label representing the worst case hazard for all branch circuits and a separate unique label for the compartment containing the main protective device. On the worst case label, indicate which branch circuit compartments have the worst case hazard.
c. Use the worst case hazard of all operating scenarios unless mitigation procedures are used. If mitigation procedures are used, explain the procedures on the label.
3.3 MODELING
Develop a software model of the electrical system identified in the scope of the studies. Use the latest version of SKM PowerTools(TM). Develop the model with accurate, verified information. Model existing electrical equipment, machines, devices, and conductors directly connected to, altered by, or otherwise affected by the work. This includes, but is not limited to generators, transformers, switchgear, switchboards, panelboards, motor control centers, motors, voltage regulators, tap changers, protective relays, circuit breakers, switches, fuses, conductors, capacitors, reactors, grounding system, and control equipment.
Provide the final model files in their native editable formats for future use by the Government. Include device information for devices not in the software vendor's standard distribution.
Section 26 08 00 Page 1
SECTION 26 08 00
APPARATUS INSPECTION AND TESTING
The publications listed below form a part of this specification to the
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2021) Standard for Acceptance Testing
Specifications for Electrical Power Equipment and Systems
1.2 RELATED REQUIREMENTS
Section C:\Users\RicharJ1\Desktop\New folder\26 20 00.docx INTERIOR DISTRIBUTION SYSTEM applies to this section with additions and modifications specified herein.
classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section C:\USERS\RICHARJ1\ONEDRIVE - JACOBS\DP- SPECIFICATIONS\Jobs\FA877009\prntdata\Word\01 33 00.docx SUBMITTAL
PROCEDURES:
Acceptance Tests and Inspections; G
Qualifications of Organization, and Lead Engineering Technician; G
Acceptance Test and Inspections Procedure; G
1.4 QUALITY ASSURANCE
1.4.1 Qualifications
Engage the services of a qualified testing organization to provide inspection, testing, calibration, and adjustment of the electrical distribution system and generation equipment listed in paragraph ACCEPTANCE TESTS AND INSPECTIONS herein. Organization must be independent of the supplier, manufacturer, and installer of the equipment. The organization must be a first tier subcontractor. No work required by this section of the specification may be performed by a second tier subcontractor.
Section 26 08 00 Page 2
a. Submit name and qualifications of organization. Organization must have been regularly engaged in the testing of electrical materials, devices, installations, and systems for a minimum of 5 years. The organization must have a calibration program, and test instruments used must be calibrated in accordance with NETA ATS.
b. Submit name and qualifications of the lead engineering technician performing the required testing services. Include a list of three comparable jobs performed by the technician with specific names and telephone numbers for reference. Testing, inspection, calibration, and adjustments must be performed by an engineering technician, certified by NETA (Level III) or the National Institute for Certification in Engineering Technologies (NICET) with a minimum of 5 years' experience inspecting, testing, and calibrating electrical distribution and generation equipment, systems, and devices.
1.4.2 Acceptance Tests and Inspections Reports
Submit certified copies of inspection reports and test reports. Include certification of compliance with specified requirements, identify deficiencies, and recommend corrective action when appropriate. Type and neatly bind test reports to form a part of the final record. Submit test reports documenting the results of each test not more than 10 days after test is completed.
1.4.3 Acceptance Test and Inspections Procedure
Submit test procedure reports for each item of equipment to be field tested at least 45 days prior to planned testing date. Do not perform testing until after test procedure has been approved.
Not used.
3.1 ACCEPTANCE TESTS AND INSPECTIONS
Testing organization will perform acceptance tests and inspections. Test methods, procedures, and test values must be performed and evaluated in accordance with NETA ATS, the manufacturer's recommendations, and paragraph FIELD QUALITY CONTROL of each applicable specification section. Tests identified as optional in NETA ATS are not required unless otherwise specified. Place equipment in service only after completion of required tests and evaluation of the test results have been completed. Supply to the testing organization complete sets of shop drawings, settings of adjustable devices, and other information necessary for an accurate test and inspection of the system prior to the performance of any final testing. Notify Contracting Officer at least 14 days in advance of when tests will be conducted by the testing organization. Perform acceptance tests and inspections on applicable equipment and systems specified in the following sections:
a. Section C:\Users\RicharJ1\Desktop\New folder\26 32 15.00.docx ENGINE-
GENERATOR SET STATIONARY 15-2500 KW, WITH AUXILIARIES. Functional engine shutdown tests, vibration base-line test, and load bank test
Section 26 08 00 Page 3 will not be performed by the testing organization, but by the start-up engineer.
e. Section C:\USERS\RICHARJ1\ONEDRIVE - JACOBS\DP- SPECIFICATIONS\Jobs\FA877009\prntdata\Word\33 71 02.docx UNDERGROUND ELECTRICAL DISTRIBUTION. Medium voltage cables and grounding systems only.
i. Section C:\Users\RicharJ1\Desktop\New folder\26 36 23.docx AUTOMATIC
TRANSFER SWITCHES AND BY-PASS/ISOLATION SWITCH
3.2 SYSTEM ACCEPTANCE
Final acceptance of the system is contingent upon satisfactory completion of acceptance tests and inspections.
3.3 PLACING EQUIPMENT IN SERVICE
A representative of the approved testing organization must be present when equipment tested by the organization is initially energized and placed in service.
Section 26 20 00 Page 1
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
0BPART 1 GENERAL
3B1.1 REFERENCES
The publications listed below form a part of this specification to the
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI C12.1 (2014; Errata 2016) Electric Meters - Code for Electricity Metering
ASTM INTERNATIONAL (ASTM)
ASTM B1 (2013) Standard Specification for Hard-Drawn
Copper Wire
ASTM B8 (2011; R 2017) Standard Specification for
Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM D709 (2017) Standard Specification for Laminated
Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2023) National Electrical Safety Code
IEEE Stds Dictionary (2009) IEEE Standards Dictionary: Glossary of
Terms & Definitions
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2021) Standard for Acceptance Testing
Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION (NECA)
NECA NEIS 1 (2015) Standard for Good Workmanship in
Electrical Construction
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C12.7 (2022) Requirements for Watthour Meter
Sockets
Section 26 20 00 Page 2
ANSI C80.1 (2020) American National Standard for
Electrical Rigid Steel Conduit (ERSC)
ANSI C80.3 (2020) American National Standard for
Electrical Metallic Tubing (EMT)
ANSI C80.5 (2020) American National Standard for
Electrical Rigid Aluminum Conduit
NEMA 250 (2020) Enclosures for Electrical Equipment
(1000 Volts Maximum)
NEMA BU 1.1 (2010) General Instructions for Proper
Handling, Installation, Operation and Maintenance of Busway Rated 600 V or Less
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2022) Standard for Industrial Control and
Systems: General Requirements
NEMA ICS 2 (2000; R 2020) Industrial Control and Systems
Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 3 (2005; R 2010) Medium-Voltage Controllers
Rated 2001 to 7200 V AC
NEMA ICS 4 (2015) Application Guideline for Terminal
Blocks
NEMA ICS 6 (1993; R 2016) Industrial Control and
Systems: Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous
Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2021) Motors and Generators
NEMA MG 10 (2017) Energy Management Guide for Selection and Use of Fixed Frequency Medium AC Squirrel-Cage Polyphase Induction Motors
NEMA MG 11 (1977; R 2012) Energy Management Guide for
Selection and Use of Single Phase Motors
NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC)
Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (2014) Dry-Type Transformers for General
Applications
NEMA TC 2 (2020) Standard for Electrical Polyvinyl
Chloride (PVC) Conduit
Section 26 20 00 Page 3
NEMA TC 3 (2021) Polyvinyl Chloride (PVC) Fittings for
Use With Rigid PVC Conduit and Tubing
NEMA TC 14 (2002) Standard for Reinforced Thermosetting
Resin Conduit (RTRC) and Fittings
NEMA VE 2 (2018; ERTA 1-2 2018) Cable Tray Installation
Guidelines
NEMA WD 1 (1999; R 2020) Standard for General Color
Requirements for Wiring Devices
NEMA WD 6 (2021) Wiring Devices Dimensions
Specifications
NEMA Z535.4 (2011; R 2017) Product Safety Signs and
Labels
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2023; ERTA 4 2023) National Electrical Code
NFPA 70E (2024) Standard for Electrical Safety in the
Workplace
NFPA 780 (2023) Standard for the Installation of
Lightning Protection Systems
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568.1 (2020e) Commercial Building
Telecommunications Infrastructure Standard
TIA-569 (2019e; Add 1 2022) Telecommunications
Pathways and Spaces
TIA-607 (2019d) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
10 CFR 431 Energy Efficiency Program for Certain
Commercial and Industrial Equipment
29 CFR 1910.147 The Control of Hazardous Energy (Lock Out/Tag
Out)
29 CFR 1910.303 Electrical, General
UNDERWRITERS LABORATORIES (UL)
UL 1 (2005; Reprint Jan 2022) UL Standard for
Safety Flexible Metal Conduit
Section 26 20 00 Page 4
UL 4 (2004; Reprint Mar 2021) UL Standard for Safety Armored Cable
UL 5 (2016; Reprint Jul 2022) UL Standard for
Safety Surface Metal Raceways and Fittings
UL 5A (2015; Reprint Aug 2020) Nonmetallic Surface
Raceways and Fittings
UL 6 (2022) UL Standard for Safety Electrical
Rigid Metal Conduit-Steel
UL 6A (2008; Reprint Mar 2021) UL Standard for
Safety Electrical Rigid Metal Conduit - Aluminum, Red Brass, and Stainless Steel
UL 20 (2018; Reprint May 2023) UL Standard for
Safety General-Use Snap Switches
UL 44 (2018; Reprint May 2021) UL Standard for
Safety Thermoset-Insulated Wires and Cables
UL 50 (2015) UL Standard for Safety Enclosures for
Electrical Equipment, Non-Environmental Considerations
UL 67 (2018; Reprint Aug 2023) UL Standard for
Safety Panelboards
UL 83 (2017; Reprint Mar 2020) UL Standard for
Safety Thermoplastic-Insulated Wires and Cables
UL 248-4 (2010; Reprint Apr 2019) Low-Voltage Fuses -
Part 4: Class CC Fuses
UL 248-8 (2011; Reprint Aug 2020) Low-Voltage Fuses -
Part 8: Class J Fuses
UL 248-10 (2011; Reprint Aug 2020) Low-Voltage Fuses -
Part 10: Class L Fuses
UL 248-12 (2011; Reprint Aug…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .