This document is a product specification sheet for FIREGUARD® double-wall fire-protected aboveground storage tanks manufactured by Steel Tank Institute (STI) members. The tanks feature an inner and outer steel construction with lightweight thermal insulation material that is 75% lighter than concrete, exceeding UL 2-hour fire test requirements. The insulation reduces shipping, installation, and relocation costs while minimizing product temperature variations and environmental emissions.

FIREGUARD® tanks are available in cylindrical and rectangular designs with capacities ranging up to 75,000 gallons and meet UL 2085 "Protected" tank standards, NFPA 30 & 30A, International Fire Code (IFC), California Air Resources Board (CARB) Standing Loss Control testing requirements, and STI Standard F941 for Protected Aboveground Storage Tanks. Key features include on-site tightness testing of primary and secondary tanks using standard procedures, interstitial space leak detection monitoring, steel outer wall weather protection, compatibility with biodiesel and ethanol fuels and chemicals, seismic support options, and emergency vents opening at minimum 2.5 psi pressure. The tanks are built to nationally-recognized standards with strict third-party quality control inspection through STI's Quality Assurance Program. Detailed specifications tables provide outer tank dimensions in inches and approximate weights for cylindrical designs (186 to 30,000 gallons) and rectangular designs (186 to 24,700 gallons). The document includes comparative advantages over concrete-encased alternatives, highlighting superior testability, durability, recyclability, and lower transportation costs.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIREGUARD® double‐wall fire‐protected aboveground storage tank features an inner and outer steel tank with a unique lightweight thermal insulation material that exceeds the UL 2‐hour fire test. Insulating material is 75% lighter than concrete, reducing shipping, installation and relocation costs.

• Insulates product in tank from ambient temperature variations, reducing emissions to the environment

• Primary and secondary tank can be tightness tested on site with standard testing procedures, unlike other designs

• Steel outer wall provides low cost maintenance and protection from weathering

• Primary storage tank and secondary containment compatible with a wide range of fuels and chemicals, including biodiesel and ethanol

• Support designs available for all seismic requirements

• Interstitial space can be monitored for leak detection

• Meets temperature requirements when the furnace test was extended to 4 hours

F I R E G UA R D ® f e a t u r e s :

Unique Thermal Insulating Material is 75% Lighter than Concrete

Compatible With a Wide Range of Fuels and Chemicals, Including Biodiesel and Ethanol

• Capacities range up to 75,000 gallons

• Steel construction allows for recycling

• Low cost compartments and customization

• Built to nationally‐recognized STI standards with strict third‐party quality control inspection program

A d d i t i o n a l f e a t u r e s :

• Horizontal • Vertical • Rectangular

A v a i l a b l e D e s i g n s :

• UL 2085 Listed “Protected” tank

• Ballistics and Impact protection per UL 2085

• Both the inner and outer steel tanks are built to UL standards

• National Fire Protection Association (NFPA) 30 & 30A

• International Fire Code (IFC)

• California Air Resources Board (CARB) Standing Loss Control testing requirements for air emissions

• Steel Tank Institute (STI) Standard F941 for Protected Aboveground Storage Tanks

F I R E G UA R D ® T h e o n l y t a n k t h a t m e e t s a l l o f t h e s e s t a n d a r d s :

FIREGUARD® is available from a large network of STI Licensed Manufacturers • www.steeltank.com

Outer Tank Dimensions (inches)* Outer Tank Dimensions (inches)*

Gallons Diameter Length Approx. Gallons Diameter Length Approx.

Weight(lbs.) Weight(lbs.)

186 48 54 1,750 4,000 90 174 12,300 250 48 68 2,100 5,000 102 168 13,750 300 50 72 2,350 6,000 102 198 15,500 500 60 76 3,100 8,000 102 258 20,000 560 60 84 3,350 10,000 102 330 24,500 1,000 70 78 3,800 12,000 102 390 28,000 1,500 70 114 5,500 15,000 126 312 34,500 2,000 70 150 6,500 20,000 126 414 39,500 2,500 70 186 7,900 25,000 126 516 49,000 3,000 70 222 9,000 30,000 126 618 74,000

Outer Tank Dimensions (inches)*

Gallons Length Width Height Approx. Weight (lbs.)

186 44 44 55 2,100 250 117 36 36 3,100 250 78 50 36 2,800 500 140 51 36 4,800 750 140 72 35 6,100 1,000 127 72 36 4,300 1,000 88 72 50 3,800 1,500 124 88 43 5,400 2,000 140 86 50 6,300 2,000 140 72 60 6,100 2,500 140 88 60 7,000 3,000 250 72 50 10,900 3,000 117 102 72 8,800 4,000 331 72 50 14,100 4,000 154 102 72 10,900 5,000 336 72 60 15,600 5,000 191 102 72 13,100 6,000 402 72 60 18,400 6,000 228 102 72 15,200 8,000 370 102 60 21,500 8,000 302 102 72 19,400 10,000 460 102 60 26,300 10,000 376 102 72 23,700 12,000 451 102 72 27,900 15,000 386 102 102 36,500 18,000 462 102 102 42,900 24,700 465 137 102 51,650

FIREGUARD® SPECIFICATIONS

CYLINDRICAL DESIGN

RECTANGULAR DESIGN

*Dimensions and weights are sample sizes. Individual manufacturers may have alternate dimensions.

• Secondary containment is testable on‐site using standard, economical testing procedures

• Impermeable, crack resistant steel outer tank which encloses the concrete encased primary tank

• Steel secondary containment provides added strength, security and is easily recycled

• The lightweight monolithic thermal insulation material Fireguard® uses is a specialized concrete that is part of a patented process resulting in a lighter material weight than concrete alone

• Both the primary and secondary tanks are fitted with emergency vents that will open in an emergency at a minimum pressure of 2.5 psi

• The secondary containment on certain designs may require elaborate and expensive procedures to be tested on‐site

• Exposed concrete outer wall is susceptible to cracking, spalling and weathering ‐ problems that are expensive to correct and are typically not covered by warranty

• Polyethylene sheeting depends on concrete for strength and takes years to decompose

• An average 12,000 gallon concrete‐encased tank weighs approximately 100,000 pounds ‐ increasing costs in transporting and setting the tank in a new location

• Primary tank is fitted with an emergency vent, but the secondary encasement is designed to fail in an emergency

IS YOUR ABOVEGROUND TANK EVERYTHING IT’S CRACKED UP TO BE?

F I R E G U A R D ® V S C o n c r e t e E n c a s e d

3/18-1M-Item #130-50-0001

Fireguard® is available from an extensive group of Steel Tank Institute fabricators who participate in the STI Quality Assurance Program.

Under the program, independent quality control inspectors make unannounced visits to STI members, ensuring fabrication to the highest possible standards.

A division of STI/SPFA 944 Donata Court Lake Zurich, IL 60047 Ph: (847)438-8265 Fx: (847)438-8766 Web: www.steeltank.com

File details come from the government source that posted it. Updated .