TECHNICAL SUMMARY

for Bilfinger Tebodin Hungary Kft.

Pressurized Instant Foam Fire Protection System

forstoragetanksandtechnologicalareas
Rev.2

Client: Bilfinger Tebodin Hungary Kft.

Bikszadi u. 6/a, 1119 Budapest

Project:ERI(EUROPEANREASSURANCEINITIATIVE)
AFMILCON,POLIncreaseCapacity

Kecskemet Air Base, Hungary

TABLE OF CONTENTS

1.Introduction .................................................................................................................................... 3
2.Preliminaries ................................................................................................................................... 3
3.Scope of work ................................................................................................................................. 4
4.Storage-tank and annular space fire protection ............................................................................. 4
5.Protection of other technological areas (optional) ........................................................................ 6
6.Operational description of the Pressurized Instant Foam Fire Fighting system ............................. 6
7.Technical summary ......................................................................................................................... 7
7.1.Mechanical system ................................................................................................................ 7
7.2.Fire detection and extinguishment control system ............................................................... 8
8.Construction of the Pressurized Instant Foam Fire Protection System .......................................... 9
9.Inspection and maintenance to be done by Client ......................................................................... 9
10.Inspection and maintenance to be done by an SFPRD specialist ............................................... 9
11.Certifications .............................................................................................................................. 9
12.Cost estimates .......................................................................................................................... 10

1. INTRODUCTION

ThePressurizedInstantFoamFireFightingsystem(orPiFoamSysteminshort)wasdeveloped
bySwissFireProtectionResearch&DevelopmentAG(SFPRD)tofightfiresinvolvingpolaror
non-polarflammableliquids,soitisverysuitableforprotectingstoragetankswithfixedor
floatingroofsaswellastherelatedtechnologicalareasandequipment.Otherapplicationsofthe
systemarecapableofextinguishingflammableliquidsfromtherangeofhandhelddevicestofire
trucks,butthoseapplicationsarenotinthescopeofthisdocument.
Theconceptofthissystemis:thefirefightingfoamisstoredunderpressureinavesselwith
solublegasmixture,thereforewhenreleased,itisintroducingself-expandingfoambytheforce
ofthepressurewithoutanymachineryorfoamgeneratorstotheburningliquidsurface.The
PressurizedInstantFoamFireFightingsystemappliesaveryhighqualityoffoamatsignificantly
higherquantityperminutethanothersystems.Thisreducesenvironmentalimpactsandlimits
foamdecompositionontheburningsurface.Anystoragetankfireiscoveredbyfoamwithina
maximumofthreeminutes.
Theextinguishingsystemdoesnotdependonawaternetwork,electricitysupply,soitis
suitableforfireprotectionofisolatedstorageterminalsandtheirprocessareaalso.
Thesystemrequireslessmaintenancecomparedtotheother,traditionalfirefightingsystemson
themarket.

2. PRELIMINARIES

BilfingerTebodinHungaryKft.(hereinafter:Client)participatestoengineeringand
constructionworkofKecskemétAirBaseinHungary.TheprojectwillincreasePOLstorage
capacitythroughconstructionofanoperationaljetfuelstoragefacilitythatwillaccommodate
NATOequivalentTacticalFighterAircraft(TFA)andStrategicTransportAircraft(STA).
TheClient,recognizingtheneedforafireprotectionsystematthenewtank-storagefacility,asked
SwissFireProtectionResearch&DevelopmentAGtoofferapriceestimateforinstallingthe
PressurizedInstantFoamfireprotectionsystematthenewJET-Astoragetanks(ST5,ST6).
Tankstoragefacilityconstitutesoftwosimilarstoragetankfarms,SITEAandSITEBcompriseof
anexistingprocessareaandtwosmallerST1,ST2,andST3,ST4storagetankwithavolumeof
1250m3each.Firewatersystemandfireextinguishsystemisnotpresent,sotheexistingtanks
lacksanyfirefightingequipment.
AccordingtotheagreementwiththeClient,thepriceestimationcontainsthecostoffirefighting
installationsforthenewtanksonly,butwenotethat,theexistingtanksmaybecoveredwith
fireprotectionwithaminimaladditionalcost.

Possible risk areas:

● Annularspaceofstoragetanks:anyleakageoftankflangesmayresultinavaporizing
combustibleliquidsurface,whereanignitionsourcemaycauseanexplosionandafire.
● Prolongedfire(>5-10min)intheannularspaceheatsupthetankwallandrisksan
additionalexplosioninsidethestoragetank.So,insuchcase,theannularspaceandthe
interiorofthetankshouldalsobecoveredwithfoam.

3. SCOPE OF WORK

Theoffercoversallfire-protectionandfire-suppressiontasksaccordingtothenewST5andST6
storagetanks.
Optionally,weofferthecostofautomaticfireprotectionofJET-Afilterandpumproomsalso,as
basedonthesitevisit,wefoundoutthatthereisnoprotectioninitandasmallfiretherecan
rendertheoperationofthetanksimpossibleforalongerperiod.Thereforewestrongly
recommendtoextendthefireprotectiontothefilterandpumproom.

The system can be operated independently from water mains and electricity.

ThecalculationisvalidwithSFPRD’sfirefightingfoamonly.ThefoamorthePressurizedInstant
FoamSystemarenotseparableinthiscase,becausetheexceptionalfireextinguishing
performancecanbeguaranteedwiththecombinationofthem.
Thesystemcanbeusedwithotherfoamsonthemarket,butthatwouldrequirebiggerpressure
vesselsduetothelessefficientextinguishmentcapabilityofthem,soifthatisrequired,thecost
estimationshallberecalculated.
4. STORAGE-TANKANDANNULARSPACEFIREPROTECTION
Thesystemdesigncoversthefireprotectionofthefollowingsurfaces:

Fire surfaces:

● AnnularspaceofST5andST6(each):95.11m2
● Firesurfaceofonetank(ST5orST6):380m2(D=22m)
● Option:JET-Afilterandpumprooms:100m2

Protection techniques:

- Topreventtheriskofescalation,leakagedetectionisrecommendedfortheannularspaces
(notincludedinthescopeofthisoffer).Leakagecontrolpitshallbecheckedregularly,and
theannularspaceshallbeequippedwithvaporconcentrationmonitorcertifiedtofuel

vapors.

- Incaseasevereleakageisdetected,andanot-expectedignitionsourceispresent,the
annularspacemaybefloodedwithfoamtopreventexplosion(ifnecessary).
- Incaseofafireintheannularspaceorinsidethetank,thefiremaybedetectedinavery
reliablemethod:theannularspace(andtheinnerrimofthetanks)shallbefittedwith
melttubes,allaroundtheperimeter.Incaseofafire,themelttubelosesitsstructural
integrity,burstsandthepressuredropcanbedetectedinthecontrolbox,whichlaunches
theextinguishmentprocess.SeemoreinformationinChapter6.
- Incaseofafireintheannularspace,theextinguishmentstartsautomatically,andtheinner
spaceofthetankcanbecoveredmanuallyorautomaticallywithfoaminthesametime
(subjecttotherequirementsoftheClient,butwerecommendthatthefoamejectiontothe
innerspacemaystartincaseofabiggerfireintheannularspace).
- Foamflowtotheannularspaceisdesignedtoproduceacoolingblanketontheoutside
wallofthetanktopreventtheignitionofvaporsinsideofthetank.

- In case of a fire detected inside the tank, only the interior of the tank shall be covered with foam.

- Incaseofafiredetectedinthefilterandpumproom,theflooroftheroomcanbeflooded
withfoamautomaticallyormanually.

Design information:

- Specificfoamintensity:14.97L/m2min
- Foamflowtoannularspace:1423L/min
- Foamflowtotank:5688L/min
- foamflowtofilterandpumproom:1497L/min(optional)
- Durationoffoamintroduction:2minutes(ifbothsurfacescoveredsimultaneously–

otherwise it is shorter)

Flow velocity calculation of foam header:

- Totalfoamflow:7111L/min=0.1185m3/sec
- Selectedpipesize:DN200,219.1x6
- Innerdiameter:207mm
- Crosssection:0.03365m2
- Foamvelocityintheheader:v=Q/A=0.1185m3/sec/0.03365m2=3.52m/sec

Flow velocity calculation of tank extinguish pipe:

- Foamflow:5688L/min=0.0948m3/sec
- Selectedpipesize:DN150,168.3x5
- Innerdiameter:158.3mm
- Crosssection:0.01968m2
- Foamvelocityinthetankextinguishpipe:v=Q/A=0.0948m3/sec/0.01968m2=4.81

m/sec

Flow velocity calculation of annular space extinguish pipe:

- Foamflow:1423L/min=0.023716m3/sec
- Selectedpipesize:DN100,114.3x4.5.
- Innerdiameter:105.3mm
- Crosssection:0.0087m2
- Foamvelocityintheannularextinguishpipe:v=Q/A=0.023716m3/sec/0.0087m2=2.72

m/sec

Flow velocity calculation of optional filter and pump room extinguishment (optional):

- Foamflow:1497L/min=0.02495m3/sec
- Selectedpipesize:DN100,114.3x4.5.
- Innerdiameter:105.3mm
- Crosssection:0.0087m2
- Foamvelocityintheannularextinguishpipe:v=Q/A=0.02495m3/sec/0.0087m2=2.87

m/sec

Maximum allowed foam velocity is 5 m/sec.

5. PROTECTION OF OTHER TECHNOLOGICAL AREAS (OPTIONAL)

Otherareasofthefacilitycanbeprotectedinthesameway.Thesetechnologicalareasmayalso
beequippedwithautomaticextinguishingsystemthroughdryheaderpipes,accordingtothe
layoutofthestation.
Werecommendkeepingtheoptionofmanualinterventionduetopossiblehiddenareasthatare
difficulttoextinguishwithafixedmonitor(aswewerenotonasitevisityet,thesearejust

assumptions).

Duetothepreferredlocationofthefoamtanksareveryclosetotheprocessarea,thisautomatic
systemandthemanualinterventiondevicescanbeequippedwithaminimaladditionalmaterial
cost,thereforewerecommendthemforaddedsecurity.

6. OPERATIONAL DESCRIPTION OF THE PRESSURIZED INSTANT FOAM FIRE FIGHTING

SYSTEM

ThepatentedPressurizedInstantFoamsystemconsistsofapressurizedfoam-storagepipefilled
withaspeciallydevelopedfoamsolutionandapropellantgas.Thegaspartlydissolvesinthefoam
solution,soitwillbereadytoreleaseatanytimewithoutadditionalenergyinput.
Thetwo-valvesystemreducestheriskofaccidentalfoamdispensationwithatwo-stageenabling
system.Fireisdetectedbyaflamedetector,CCTV,oranytypeofheat/smokedetector(according
totherequirementsoftheClient).Theoperatorgetsasignalonthescreenofthefire-alarmcenter.
Itisthenpossibletostartextinguishingautomatically(instantlyortime-delayed)ormanually,
accordingtotheClient’srequirements.
Thevalvesinthefoamnetworksarepreferablythespring-returntype,whichreturnstoanopen
positionincasethepressure-airsystemisdamaged.

Pneumatic, heat burst pipe type fire detection system (our recommendation)

Themaintaskofthepneumaticfiredetectionsystemistodetectfireinsidethetankandtoopen
thebutterflyvalveoffoampipes.Itisalsoresponsibleforthetransmissionofthestatussignals
tothecontrolsystem.
Withthepneumaticdetectionandcontrolsystem,theextinguishingofthetankfiresbecomes
completelyautomatic.Thesafeoperationisabsolutelyguaranteedsincenoexternalenergyis
neededtoopenthefloodingandshut-offvalves.
Asignificantdecreaseofgaspressureinthedetectorsisprocessedbyapneumaticlogicunit.
Thebutterflyvalveisactuatedbytheworkingcylinderswhichislocatedinsidethepneumatic
logicunit.
Thepneumaticsystemisfilledwithcompressedairwhichoperationalpressureis10bar.In
standbymode,thepneumaticsystemconsumeszeroenergy.Eachpneumaticdetectorisan
annularringmadeofapneumatictube.Incaseoffire,thedetectortubemeltsandthepressure
ofthecompressedairinsidedrops.Thispressuredroplaunchesthefireextinguishingprocess
insidethetank.
Atleast2pneumaticdetectorsshallbeplacedinsidethetank(topreventaccidentalrelease,our
recommendationisa2outof3activationsystem).

Reliability

Wedeclarethatinthisconfiguration,thePiFoamfirefightingsystemdoesnotrequireany
externalenergyinputorhumaninterventionforactivation,thereforetheriskoffailingisvery

low.

When extreme reliability is required, flood and shut-off valves and detection system can be duplicated.

Foryourinformation,wedevelopedanextinguishlaunchingsystemwhichdoesnotincludeany
movingparts(noopeningvalvesrequiredforactivation)andstilloperateswithoutexternal
energyinput,thereforeitsreliabilityisextremelyhigh–wehavenotdesignedthistypeof
systemtothisprojectyet,butnaturallywecanifthereisthedemandforthat.Thissystem
launchesthefoamflowbyburstingdiscs,whicharecontrolledbythementionedheatburst
detectorinapatentedway.Thelackofanymovingpartsmakesitsuitabletoanyindustrialand
militarypurposes,whereextremereliabilityandmaintenance-freeoperationisrequired.

7. TECHNICAL SUMMARY

7.1. MECHANICALSYSTEM
Theextinguishmentsystemisabletoextinguishthelargestrequiredfirearea(eg.thebiggest
storagetankanditsannularspace),oralltanksurfacesthemsimultaneously(accordingtothe

requirements).

Pressurized Instant Foam Pressure Vessel

Thefoamshouldbestoredinapressurevessel,accordingtothevolumecalculatedforeach
scenario.Thepressurevesselandthepipesshouldbeburiedtominimizetemperature
fluctuationsandvulnerabilitybyaccidentorsabotage.Basedonthesitevisit,werealizedthatthe
groundwaterlevelissohigh,thattheundergroundlocationofthepressurevesselswouldbe
unadvisable,sowecameupwithahalf-buried,half-builtsolution,whichchangesthepricesto
onlyaminimalextent.

Volume: 2x10m3

Diameter: 2 m

Layout: Horizontal

Material:Carbonsteelwithinternalepoxylayer.Theinternallayercontinuestothesealingfaces
oftheflanges,strikeovercheckedat1000V.

Material charge: Foam solution

External coating: External PE coating

Design,manufacturing,certification:AccordingtoEN13445,2014/68/EUdirective(PED-
2014),orASME,APIstandards

Periodic inspection: Visual inspection every five years, thorough inspection every 10 years

Valves: Valves in contact with the foam solution:

Largervalves(DN50andabove)shouldbebutterflyvalvesbecausethey
aremadewithinternalPFTEcoatingandastainless-steelclosingelement.
Theyarealsocosteffective.
Operationofthebutterflyvalvesshouldbedoneusingapneumatic
actuatorwithautomaticspringreturn.
Smallvalvesincontactwithfoamshouldbestainlesssteelballvalves.The
othervalves(notincontactwiththefoamsolution)aremadeofcarbon
steel,butbrassballvalvesmayalsobeusedinthepressure-airsystem.

Pipes

Pipes are internally coated with epoxy paint. The pressure-air pipes are made of galvanized steel.

7.2. FIRE DETECTION AND EXTINGUISHMENT CONTROL SYSTEM

The dike area of the storage tanks will be protected by a heat-burst or electric fire-detection system.

The electric fire-detection system consists the following main parts:

● maincontrolpanel
● subcontrolpanel

● detectors

● firealarmcablenetwork
● uninterruptiblepowersupply(UPS)system
● graphicdisplay
ThemaincontrolpanelwillbelocatedinsidetheControlRoom.Itsprimaryroleistoreceive
signalsfromsubcontrolpanels,releasetheextinguishmentcommandandtransmitsignalstothe
plant’sfirealarmcenter(ifexist).
Thesubcontrolpanelsareconnectedtotheelectricfiredetectorsandthepneumaticlogicalunits.
Thesepanelswillbeplacedinanon-hazardousarea.
Flamedetectorsareoptionalfordetectingfireinsidethedikearea,andinthiscase,two-step
releasecanbebuilttodecreasetheriskofaccidentalfoamspillage.
Industrystandardsdonotobligeplantstoprotecttheothertechnologicalareas(pumpstations,
loadingstations,meteringskid,etc.)fromfire.
Duetothelowdistancebetweenthepreferredlocationoffoamtanksandtheprocessarea,we
recommendatleastmanualinterventiondevices(handlines)intheprocessarea(seeChapter5).
Thereisanotheroptiontoreleasethefoammanuallywithacontrolbuttonlocatedinsidethe
plant’sControlRoom.
Thecablesofthefire-alarmnetworkwillbesinglefire-alarmcables,exceptwhentheyhave
controlfunctions.Inthiscasefireproofcableswillbeinstalled.

The extinguishing control panels powered by independent “UPS” power system.

8. CONSTRUCTION OF THE PRESSURIZED INSTANT FOAM FIRE PROTECTION SYSTEM

Constructionmustbehandledbyacertifiedlocalconstructioncompanywithweldersandproject
leaderswhoarequalifiedforworkinthepetrochemicalindustry.Theymustalsohaveexperience
workinginexplosiveareas.

Pipes and pipe support would be of the welded type, painted with two-component epoxy-based paint.

9. INSPECTION AND MAINTENANCE TO BE DONE BY CLIENT

Theinspectionofthesystembythefinalclientisquiteeasy.ThePressurizedInstantfoam-storage
tankwillbeequippedwithpressureandtemperatureswitcheswhosesignalswilldisplayonthe
mainpanelofthecontrolroom.
Allvalvescanbetestedforfunctionalityonsite,eithermanuallyorviaremotecontrolfromthe
firealarmpanel.

10. INSPECTION AND MAINTENANCE TO BE DONE BY AN SFPRD SPECIALIST

Foamquality,drainagetimeandexpansionratiosshouldbecheckedeveryyearbyanSFPRD
expert.ThePressurizedInstantfoam-storagepipewillbeinspectedeveryfiveyears(visual
check),withathoroughinspectionandpressuretestevery10years.

11. CERTIFICATIONS

TÜVSÜDofGermanysuccessfullycarriedoutatestonthestorage-tankmodelforthepurposeof
verifyingthesuitabilityofanewfire-extinguishingtechnologyforstoragetanks.
TheexperimentaltankwasequippedwithPressurizedInstantFoamFireProtectionSystem.The
diameterofthemodelwas25.2meters,sothefiresurfacewas500m2.
OnSeptember22,2010,TÜVSüdissuedanExpertReport(IS-EG2-MUC/Rh)onthetest
conclusions(seeattachment).
ThePressurizedinstantFoamSystemhasthenecessaryapprovalandmarketingauthorizationof
HungarianNationalDirectorateGeneralforDisasterManagement,MinistryoftheInterior(BM

OKF).

12. COST ESTIMATES

The cost estimate is based on the drawings received from the Client. It uses EU material and labor prices.

SITE A USD

Construction and piping material cost 198 000

Budget reserve for unforeseen construction cost, 30 % 60 000

Fire control panel 20 000

Engineering 20 000

Foam and filling cost 20 000

Licence fee (12% of total construction cost, but at least 50k USD per tank) 50 000

Construction supervision and QA (Quality Assurance) cost 20 000

Total (Site A): 388 000

SITE B USD

Construction and piping material cost 191 000

Budget reserve for unforeseen construction cost, 30 % 58 000

Fire control panel 20 000

Engineering 20 000

Foam and filling cost 20 000

Licence fee (12% of total construction cost, but at least 50k USD per tank) 50 000

Construction supervision and QA (Quality Assurance) cost 20 000

Total (Site B): 379 000

TOTAL (Site A + Site B) 767 000

OPTIONAL: Pump Room protection (Site A + B) 44 000

SFPRDmaintenancefeewillbearoundUSD10,000peryear,whichconsisttheyearlysampling
andcheckingofthefoaminourlaboratoryinHungary.

Validity

Thisdocumentationhasbeenmadeaccordingtotheinformationprovidedelectronicallybythe
Clientbasedontheinformationacquiredduringasitevisiton22/11/2018.
Anyinformationwhichcanonlybediscoveredatthesite,maycauseslightchangesinthe
documentationandrevisionscanbenecessaryondrawings,textorcostestimate.Thecost
estimationisbasedonSFPRDcorporatefinancialcostestimationsoftware,Europeanraw
materialandlaborprices,andcostofrecentprojects.Theaccuracyofthecostestimation–dueto
thedetailslevelofthedesigninformationavailable–isabout+/-30%.