94197779 - Proposed VA Hospital Garland - Limited Mold Assessment Report - DRAFT.pdf
PDF 3 MB Posted
- Attached to
- Y1NB--336C25726R0025 C549-23-600 Construct Garland Energy Center Design-Build Construction Sources Sought 2
- Solicitation number
- 36C25726R0025_4
About this file
This is a Limited Mold Assessment Report for three buildings at the proposed VA Hospital Garland in Garland, Texas, conducted by Terracon Consultants, Inc. in June 2019. The assessment evaluated three facilities: the Main Hospital (2300 Marie Curie Boulevard), the Plaza Building (700 Walter Reed Boulevard), and the Storage Building (900 North Shiloh Road). The evaluation was limited to readily observable and accessible surfaces, with visual inspections and moisture content measurements conducted across multiple floors and areas of each building. The assessment identified extensive moisture damage from historical rain water intrusion and mechanical/plumbing leaks, along with suspect visible fungal growth in numerous locations.
The assessment documented significant fungal contamination exceeding the 25 square foot regulatory threshold established in Texas's Mold Assessors and Remediators Administrative Rules (MARAR) in specific areas, including Main Hospital Rooms 309, 312B, 1136, 1131, and the Northeast Large Mechanical Room; Plaza Building's Day Surgery area, AHU P-05, and basement storage; and various other locations. Surface samples were collected and analyzed, identifying fungal species including Stachybotrys, Chaetomium, Cladosporium, Memnoniella, and Ulocadium. The report recommends identifying and repairing moisture intrusion sources, replacing moisture-damaged materials, and conducting fungal remediation by licensed Texas Department of Licensing and Regulation (TDLR) contractors for areas exceeding the 25 square foot threshold. Additional recommendations include destructive investigation of air handler ductwork by a licensed Mold Assessment Consultant and asbestos surveying prior to remediation activities.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Limited Mold Assessment Report
Proposed VA Hospital Garland – Three (3) Buildings
2300 Marie Curie Boulevard
Garland, Texas
June 21, 2019
Terracon Project No. 94197779
Prepared for:
Enapay, LLC
Mesquite, Texas
Prepared by:
Terracon Consultants, Inc.
Dallas, Texas DRAFT
Terracon Consultants, Inc. 8901 Carpenter Freeway, Suite 100 Dallas, Texas 75247
P [214] 630 1010 F [214] 630 7070 terracon.com/dal las
June 21, 2019
Mr. Marshall Hamilton
Enapay, LLC
207 West Main Street
Mesquite, Texas 75149
Telephone: (214) 607-0247
E-mail: mjh@enapayllc.com
Re: Limited Mold Assessment Report
2300 Marie Curie Boulevard
Dear Mr. Hamilton:
The purpose of this report is to present the results of the limited mold assessment performed on June 10 - 19, 2019, at the site of the proposed VA Hospital Garland located at 2300 Marie Curie Boulevard, 700 Walter Reed Boulevard, and 900 North Shiloh Road in
Garland, Texas. We understand that this inspection was requested for informational purposes prior to building renovation.
Terracon appreciates the opportunity to provide this service to Enapay, LLC. If you have any questions regarding this report, please contact the undersigned at (817) 268-8600.
Sincerely, Michael Crandall Matthew R. Mooney
Senior Industrial Hygienist Senior Project Manager
DRAFT
mailto:mjh@enapayllc.com
TABLE OF CONTENTS
1.0 PROJECT DESCRIPTION
1.1 Scope of Work
1.2 Standard of Care
1.3 Reliance
2.0 EVALUATION CRITERIA
2.1 Visual Evaluation
2.2 Moisture Intrusion
3.0 METHODS
3.1 Visual Evaluation
3.2 Moisture Detection
4.0 RESULTS
4.1 Visual Evalutation - Main Hospital
4.2 Visual Evaluation - Plaza Building
4.3 Visual Evaluation - Storage Building…………………………………………………….….34
5.0 SUMMARY
6.0 RECOMMENDATIONS
APPENDIX A: Analytical Results
APPENDIX B: Photographs
APPENDIX C: Licenses
Responsive ■ Resourceful ■ Reliable 1
LIMITED MOLD ASSESSMENT REPORT
Proposed VA Hospital Garland – Three (3) Buildings
2300 Marie Curie Boulevard
1.0 PROJECT DESCRIPTION
Terracon Consultants, Inc. (Terracon) conducted a limited mold assessment at the proposed VA
Hospital Garland located at 2300 Marie Curie Boulevard, 700 Walter Reed Boulevard, and 900
North Shiloh Road in Garland, Texas. The limited mold assessment conducted on June 10 – 19, 2019 was performed by the following Terracon personnel:
◼ Mr. Andrew Cassidy, a Texas Department of Licensing and Regulation (TDLR) Mold
Assessment Consultant (License MAC1496), ◼ Mr. Matthew R. Mooney, a TDLR Mold Assessment Consultant (License MAC1362), and
◼ Mr. George Slay, a TDLR Mold Assessment Consultant (License No. MAC1107).
The mold assessment was limited to readily observable and accessible surfaces. Based on information provided by the client, the buildings are proposed for renovation.
1.1 Scope of Work
The assessment consisted of a visual evaluation of accessible areas within the subject buildings.
Additionally, a visual evaluation of accessible areas within a representative number of air handling units was conducted. Measurements of moisture content of suspect building materials were also conducted.
Terracon made reasonable efforts to assess suspect materials on the interior of each building;
however, the following limitations were encountered at the time of the survey:
◼ Locked rooms throughout the interior of each building/one set of keys with property management, CBRE, on-site. Additionally, CBRE did not have access to several key-pad doors, ◼ Expedited schedule/access limited to the schedule of building security, ◼ Vacant areas of each building used for storage of remnant furnishings, ◼ Operational mental health clinic on the fourth and fifth floors of the main building, and
◼ Multiple occupied medical clinics in the plaza building.
Limited Mold Assessment
2300 Marie Curie Boulevard ■ Garland, Texas
June 21, 2019 ■ Terracon Project No. 94197779
Responsive ■ Resourceful ■ Reliable 2
Due to the referenced limitations encountered at the time of the survey, access to various areas throughout each building was limited and the potential exists for additional suspect fungal growth or water damaged materials to be present in those inaccessible areas.
Terracon assessed multiple areas above the drywall and lay-in ceiling systems in each building, where possible, but did not observe additional suspect fungal growth except where noted in this report; however; due to occupancy, building condition, and building usage at the time of the survey, access to areas above the ceiling was limited and the potential exists for additional suspect fungal growth or water damaged materials to be present in these inaccessible areas.
Terracon assessed multiple areas of the crawlspace, where possible, but did not observe additional suspect materials except where noted in this report; however, due to the condition of the crawlspace, access was limited to the standing areas and the potential exists for additional suspect fungal growth or water damaged materials to be present in these inaccessible areas.
1.2 Standard of Care
The evaluation was conducted at the subject buildings on June 10 - 19, 2019, based on information provided to Terracon regarding building conditions. This investigation was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale.
The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our June 10 - 19, 2019, assessments. Many factors such as weather conditions, building occupancy, ventilation patterns, and seasonal variations in fungal concentrations can affect the conditions observed. The information contained in this report should not be relied upon to represent conditions that existed previously or at a later date. Terracon does not warrant the services of regulatory agencies, laboratories, or other third parties supplying information that may have been used in the preparation of this report.
1.3 Reliance
The report has been prepared on behalf of and exclusively for use by Enapay, LLC for specific application to their project as discussed. No other individual or entity may rely on this report without written permission of Terracon and Enapay, LLC. Reliance on this report by Enapay, LLC and all authorized parties will be subject to the key understandings and limitations stated in the proposal, this report, and Terracon’s Agreement for Services. The limitation of liability defined in Terracon’s
Agreement for Services is the aggregate limit of Terracon’s liability to Enapay, LLC and all relying parties.
Responsive ■ Resourceful ■ Reliable 3
2.0 EVALUATION CRITERIA
2.1 Visual Evaluation
Indoor air quality can be degraded due to multiple contaminant sources from within a building or from the outdoor environment. If contaminant sources are not controlled, indoor air quality issues that affect occupants can arise, even with well-maintained heating, ventilating, and air conditioning (HVAC) systems. Based on the multiple sources of potential indoor/outdoor contaminants that can affect indoor air quality, the visual evaluation is conducted to assess general indoor hygiene, building maintenance practices, HVAC system design and hygiene, moisture intrusion and uncontrolled condensate formation. Indoor air frequently contains a mixture of pollutants at low concentrations that are well below regulatory occupational exposure limits. The visual assessment focuses on collecting primarily observational data (i.e., information obtained by visual inspection of the building and interviews with the building management, owners, and occupants).
Since many building materials can provide a source of nutrients for fungal growth, moisture is the limiting factor in minimizing the potential for fungal growth. Therefore, visible fungal growth, excessive dirt and water-damaged building materials should not be observed. When these conditions are observed, it indicates a need to conduct additional assessment, cleaning, and/or remediation activities.
2.2 Moisture Intrusion
Elevated fungal bioaerosol concentrations in indoor environments can occur when excessive moisture and a nutrient source are present, especially in closed or concealed areas that trap moisture and have minimal air disturbance. The cellulose in the paper surfacing of drywall or gypsum wallboard provides an adequate food source for the growth of many fungal species. On-site moisture measurements are obtained using a direct-reading instrument or infrared thermography. Results from similar materials in non-suspect locations, such as non-impacted drywall walls or ceiling surfaces, are compared and used to assess the likelihood of fungal growth conditions in suspect or historically water-damaged materials.
There are no current regulatory standards that limit moisture levels in walls or building materials, but the data can be valuable when results from different locations are compared.
METHODS
3.1 Visual Evaluation
The visual evaluation was conducted in general accordance with regulations published by the TDLR
(Mold Assessors and Remediators Administrative Rules, 2017), and consensus guidelines from the
American Conference of Governmental Industrial Hygienist (ACGIH, Bioaerosols; Assessment and
Control, 1999) and American Society of Testing and Materials (ASTM, Standard Guide for Assessment of Fungal Growth in Buildings, Method D7338-14). The indoor environment and internal
Responsive ■ Resourceful ■ Reliable 4 components/surfaces in representative air handler units (AHUs) were evaluated for visual evidence of moisture intrusion, visible fungal growth or other hygiene concerns that could impact indoor air quality.
Destructive sampling or disassembly of mechanical enclosures was not within the scope of work for the project.
Terracon collected surface samples for microscopic analysis using Environmental Monitoring Systems
(EMS) Mold Tape Slide™ samplers. The samplers were touched to the surface of interest and then placed in a plastic shipping container. Seventeen (17) samples were collected from various surfaces exhibiting suspect fungal growth. Criteria to establish fungal growth on the substrate sampled were microscopic confirmation of fungal somatic and reproductive structures. Surface samples were submitted under chain of custody protocol to Terracon-Fort Worth, a TDLR-licensed Mold Analysis
Laboratory (LAB1010).
3.2 Moisture Detection
A FLIR, Model C-2, thermal imager was used to evaluate temperature differences in building materials that would be consistent with moisture intrusion.
Moisture content of building materials was evaluated with a digital moisture meter; Protimeter Mini
BLD2000, from Amphenol Thermometrics, Inc. The moisture meter was calibrated prior to use in the field. Normal moisture content of building materials was standardized by evaluating similar building materials that were not subjected to atypical moisture conditions.
4.0 RESULTS
4.1 Visual Evaluation – Main Hospital
Facility Description:
Main Hospital – 2300 Marie Curie Boulevard
Building
Five-story hospital building with a basement constructed circa 1970 with additions, including the plaza building, constructed circa 1975, 1999, and 2003
Total Area 167,236 square feet (sq. ft.)
Roof Multi-level rubber membrane, rolled-on composition roofing material and tar and gravel roofing material
Exterior Walls Texture on concrete, texture on concrete masonry unit (CMU) and brick
Responsive ■ Resourceful ■ Reliable 5
Interior Description
Occupied inpatient mental health clinic, offices, exam rooms, x-ray rooms, procedure rooms, operating rooms, pharmaceutical rooms, break rooms, conference rooms, corridors, restrooms, electrical rooms, mechanical rooms, elevator lobbies, and stairwells
Interior Walls
Textured drywall, textured concrete, textured CMU blocks, wainscoting on drywall, wall covering on drywall, and ceramic tile on drywall
Interior Ceilings
Textured drywall and 2’x4’ and 2’x2’ lay-in ceiling tile suspended from a concrete deck; spray-on fireproofing was observed in various areas throughout the main hospital on the concrete deck and on the metal decks of the stairwells
Interior Floors Unfinished concrete, terrazzo, floor coating, resilient floor covering, vinyl floor tile, carpet, and ceramic tile on a concrete substrate
Survey Limitations/
Inaccessible Areas
The fourth and fifth floors were occupied by an inpatient mental health clinic; although the remaining areas of the building were vacant, a large portion of the rooms were locked or used as storage space. Various areas of the vacant spaces had limited lighting and some areas had no lighting. Debris and remnant furnishings were observed in various vacant areas throughout the interior of the building. Hard ceilings were installed in various areas throughout the interior of the building.
General Observations: Conditioned air is provided to the building by multiple AHUs and rooftop air handler units (RTUs) that are located in various mechanical rooms throughout the building and on the roof. A central chiller tower is also located on the exterior of the building.
Air Handler Units:
Air Handler Unit (AHU) G19 was assessed in the main hospital basement. Based on information provided by CBRE personnel, this AHU is representative of a typical AHU for the main hospital.
The main ducts were wrapped with exterior insulation. Standing water was observed in the drain pan below the coils. Approximately 4 square feet of suspect fungal growth was observed on the metal walls of the AHU. No suspect fungal growth was visible in the supply plenum or visible duct run.
Rooms and Corridors:
Moisture damaged building materials were observed in various areas throughout the building. The moisture damage appeared to be related to historic rain water intrusion through the building envelope and/or historic leaks or condensate drip from plumbing fixtures and mechanical components.
Responsive ■ Resourceful ■ Reliable 6
Suspect visible fungal (mold) growth was observed in various areas throughout the building. The suspect fungal growth was observed on walls, ceilings, ceiling tiles and HVAC supply registers.
Surface samples were collected from a drywall wall in the fifth-floor elevator lobby, drywall wall in
Room 384 located on the third floor, drywall wall in the east nurse’s station on the second floor and metal HVAC supply register in the basement storage area. Microscopic analysis identified
Stachybotrys, Chaetomium, Cladosporium, and Memnoniella from the referenced sample locations
(Appendix A). The quantity of visible fungal growth observed in these areas was less than the regulatory threshold of 25 square feet as defined in the MARAR. Destructive sampling or disassembly of mechanical components was not within the scope of work for the project. Terracon did not access areas underneath floor tiles, wall paneling, or inside wall cavities. Fungal growth may be present in these areas, if moisture intrusion has occurred.
The Visual Evaluation results are summarized in Table 1.0
TABLE 1.0, LIMITED MOLD ASSESSMENT RESULTS TABLE
Pharmacy Ceiling tiles with historic moisture stain (3 ft2) None Observed
Room Adjoining to
Pharmacy
Ceiling tile with historic moisture stain (1 ft2) None Observed
Plant Operations
Office
Ceiling tile with historic moisture stain (1 ft2) None Observed
Hallway at Plant
Operations Office
Ceiling tile with historic moisture stain (2 ft2) None Observed
Hallway at Main Lobby Ceiling tile with historic moisture stain (2 ft2) None Observed
Room A1 – Intake Ceiling tile with historic moisture stain (10 ft2) None Observed
Employee Elevator
Lobby
Gypsum board concealed behind vinyl cove base
(6 ft2)
Suspect fungal growth (6 ft2) behind cove base on perimeter wall
Main Building – 5th Floor
Location Moisture Damaged
Building Material
Suspect Visible
Fungal Growth
Responsive ■ Resourceful ■ Reliable 7
Hallway at Electrical
Room
Ceiling tile with historic moisture stain (2 ft2) None Observed
Westside Nurses
Station
Gypsum board ceiling with historic moisture stain (4 ft2) None Observed
Westside Hallway /
Elevator Lobby
Gypsum board ceiling with historic moisture stain (6 ft2)
Gypsum board wall with historic moisture stain
(10 ft2)
None Observed
Room 402 - Restroom Gypsum board ceiling with historic moisture stain (4 ft2) None Observed
Room 410 - Restroom Gypsum board ceiling with historic moisture stain (2 ft2) None Observed
Room 412 – Restroom Gypsum board ceiling with historic moisture stain (1 ft2) None Observed
Room 414 – Restroom Gypsum board ceiling with historic moisture stain (4 ft2) None Observed
Room 449 Gypsum board wall with historic moisture stain (5 ft2) None Observed
Room B3 Gypsum board ceiling with historic moisture stain (2 ft2) None Observed
Room 423 – Restroom Gypsum board ceiling with historic moisture stain (6 ft2) None Observed
Room 475 Gypsum board wall with historic moisture stain (1 ft2) None Observed
Main Building – 4th Floor
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 8
Room 483 Gypsum board wall with historic moisture stain (2 ft2) None Observed
Southwest Stairwell Ceiling tile with historic moisture stain (6 ft2)
Main Building – 4th Floor (Cont.)
Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 9
Room 384
Gypsum board ceiling with historic moisture stain (3 ft2)
Gypsum board wall around perimeter window with evidence of historic moisture intrusion
Suspect fungal growth (10 ft2) around window casing
Room 385
Gypsum board wall with historic moisture stain (1 ft2) around perimeter window
None Observed
Room 386 - Restroom Gypsum board ceiling with historic moisture stain (3 ft2) None Observed
Room 387 - Restroom Gypsum board ceiling with historic moisture stain (5 ft2) None Observed
Room 388 - Restroom Gypsum board ceiling with historic moisture stain (2 ft2) None Observed
Room 390
Gypsum board wall around perimeter window with evidence of historic moisture intrusion
Suspect fungal growth (5 ft2) around window at header
Room 392 Gypsum board ceiling with historic moisture stain (4 ft2) None Observed
Room 393 – Restroom Gypsum board ceiling with historic moisture stain (2 ft2) None Observed
Room 394 - Restroom Gypsum board ceiling with historic moisture stain (5 ft2) None Observed
Hallway outside Room
Ceiling tile with historic moisture stain (1 ft2) None Observed
Room 305 Gypsum board ceiling with historic moisture stain (2 ft2) None Observed
Main Building – 3rd Floor
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 10
Room 307 Gypsum board ceiling with historic moisture stain (4 ft2) None Observed
Room C10 Ceiling tile with historic moisture stain (1 ft2) None Observed
Room 309
Gypsum board wall and ceiling with damage from active water leak
Suspect fungal growth (30 ft2) on gypsum board ceiling and wall above sink
Room 311 - Restroom Gypsum board ceiling with historic moisture stain (3 ft2) None Observed
Room 3098
Wet carpeting (64 ft2) and wet gypsum board wall
(10 ft2) from active water leak
None Observed
Room 343 Ceiling tile with historic moisture stain (4 ft2) None Observed
Room 345 Ceiling tile with historic moisture stain (4 ft2) None Observed
Room 346 Ceiling tile with historic moisture stain (2 ft2) None Observed
Room 347 Ceiling tile with historic moisture stain (10 ft2) None Observed
Room 353 Ceiling tile with historic moisture stain (1 ft2)
Suspect fungal growth (4 ft2) on ceiling tile
Room 354
Gypsum board ceiling in restroom with historic moisture stain (2 ft2)
Ceiling tile with historic moisture stain (4 ft2)
None Observed
Main Building – 3rd Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 11
Hallway outside Room
Ceiling tile with historic moisture stain (2 ft2) None Observed
Room 357 Ceiling tile with historic moisture stain (1 ft2)
Suspect fungal growth (4 ft2) on ceiling tile
Room 358 Ceiling tile with historic moisture stain (1 ft2)
Suspect fungal growth (4 ft2) on ceiling tile
Room 359 Ceiling tile with historic moisture stain (1 ft2)
Suspect fungal growth (4 ft2) on ceiling tile
Room 361
Ceiling tile with historic moisture stain (2 ft2)
Gypsum board ceiling in entry way above ceiling grid with historic moisture stain (2 ft2)
None Observed
Room 362 Ceiling tile with historic moisture stain (2 ft2) None Observed
Room 312B
Gypsum board wall and ceiling with damage from historic water leak
Suspect fungal growth (115 ft2) on gypsum board ceiling and
(15 ft2) on wall
Room 316 Gypsum board ceiling with historic moisture stain (2 ft2) None Observed
Room 371 – Restroom
Damaged gypsum board ceiling from historic moisture intrusion
(4 ft2)
Suspect fungal growth (2 ft2) on gypsum board ceiling
Room 372
Gypsum board ceiling at perimeter window with historic moisture stain (3 ft2)
None Observed
Main Building – 3rd Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 12
Room 373
Damaged gypsum board ceiling at perimeter window from previous moisture intrusion (10 ft2)
Suspect fungal growth (4 ft2) on window fur down
Room 374
Damaged gypsum board ceiling at perimeter window from previous moisture intrusion (4 ft2)
None Observed
Room 375 – Restroom Gypsum board ceiling with historic moisture stain (1 ft2) None Observed
Room 377 – Restroom Gypsum board ceiling with historic moisture stain (3 ft2) None Observed
Room 379 – Restroom Gypsum board ceiling with historic moisture stain (3 ft2) None Observed
Room 380
Damaged gypsum board ceiling at perimeter window from previous moisture intrusion (6 ft2)
None Observed
Room 381 - Restroom Gypsum board ceiling with historic moisture stain (4 ft2) None Observed
Room 382
Gypsum board ceiling in restroom with historic moisture stain (4 ft2)
Damaged gypsum board ceiling at perimeter window from previous moisture intrusion (5 ft2)
None Observed
Room 383 Gypsum board ceiling with historic moisture stain (4 ft2)
Main Building – 3rd Floor (Cont.)
Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 13
Throughout Water stained/damaged TSI above ceiling throughout None Observed
Staff Lounge – Room
Gypsum board wall around perimeter window with evidence of historic moisture intrusion
Suspect fungal growth (60 ft2) around window casing and below perimeter windows
Restroom Gypsum board ceiling with historic moisture stain (3 ft2) None Observed
Room 2020
Gypsum board wall around perimeter window with evidence of historic moisture intrusion
Ceiling tile with historic moisture stain (3 ft2)
Suspect fungal growth (12 ft2) around window casing
Hallway at Ultrasound Ceiling tile with historic moisture stain (3 ft2) None Observed
Medical Director
Office
Water damaged ceiling tile (4 ft2) from active water leak None Observed
Hallway at Locked
Storage Room
Ceiling tile with historic moisture stain
Suspect fungal growth (4 ft2) on ceiling tile
On-Call Nurses Office
Gypsum board around perimeter window with evidence of historic moisture intrusion (1 ft2)
None Observed
Hallway at Dialysis Water damaged gypsum board wall (20 ft2) behind double doors None Observed
ICU Room 11 Ceiling tile with historic moisture stain (1 ft2) None Observed
Office Adjoining ICU
Room 11
Ceiling tile with historic moisture stain (3 ft2) None Observed
Main Building – 2nd Floor
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 14
Room 24 - Restroom Gypsum board ceiling with historic moisture stain (4 ft2) None Observed
Room 23 – Restroom Gypsum board ceiling with historic moisture stain (1 ft2) None Observed
Eastside Nurses
Station
Water damaged gypsum board wall behind wallpaper
Suspect fungal growth (5 ft2) on gypsum board wall behind vinyl wallpaper at med station
Room 14 Water damaged gypsum board wall behind wallpaper
Suspect fungal growth (72 ft2) on gypsum board wall behind vinyl wallpaper on dividing wall to room 13
Room 13 Water damaged gypsum board wall behind wallpaper
Suspect fungal growth (45 ft2) on gypsum board wall behind vinyl wallpaper on dividing wall to room 14
Room 12 Water damaged gypsum board wall behind wallpaper
Suspect fungal growth (45 ft2) on gypsum board wall behind vinyl wallpaper on dividing wall to room 13
Room 11 Water damaged gypsum board wall behind wallpaper
Suspect fungal growth (15 ft2) on gypsum board wall behind vinyl cove base on dividing wall to room 12
Room 6 - Restroom Gypsum board ceiling with historic moisture stain (3 ft2) None Observed
Corridor at Chapel Ceiling tile with historic moisture stain (20 ft2) None Observed
Main Building – 2rd Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 15
Main Waiting Area Ceiling tile with historic moisture stain (1 ft2) None Observed
Physical Storage –
Restroom
Gypsum board ceiling with historic moisture stain (5 ft2) None Observed
Hallway at Patient
Holding None Observed
Suspect fungal growth (1 ft2) on ceiling tile
Responsive ■ Resourceful ■ Reliable 16
Throughout Water stained/damaged TSI above ceiling throughout None Observed
NW 108
Moisture damaged ceiling tile debris on floor (2 ft2) None Observed
NW 122
Historic moisture stain on drywall adjacent to the supply air vent (1 ft2)
None Observed
NW 131
Elevated moisture detected on damaged drywall, ceiling tiles and crown molding (6 ft2), adjacent to exterior wall.
None Observed
NW 133
Historic moisture damage on drywall, ceiling tiles and crown molding adjacent to exterior wall
(20 ft2)
None Observed
NW 134
Historic moisture damage on drywall and vinyl floor adjacent to exterior wall (30 ft2)
None Observed
Hallway by Ortho
Storage Room
Historic moisture damage on drywall (12 ft2)
None Observed
NW Hallway, Desk
Area by Administration
Offices
Historic moisture damage on drywall adjacent to sink (3 ft2)
Suspect fungal growth on drywall adjacent to sink (1 ft2)
Hallway by 1 NW
Therapy Gym
Historic moisture damage on drywall (8 ft2) None Observed
1 NW Therapy Gym Historic moisture damage on drywall (4 ft2) None Observed
Nurse Supervisor
Office
Historic moisture damage on drywall (8 ft2) None Observed
Main Building – 1st Floor
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 17
COU 01
Historic moisture damage on vinyl floor (40 ft2) overhead drywall (10 ft2)
Suspect fungal growth on overhead drywall (4 ft2)
COU 03
Historic moisture damage on vinyl floor (8 ft2) None Observed
COU North Hallway Historic moisture stain on desktop (4 ft2) None Observed
COU Staff Only Room Elevated moisture and damage on overhead TSU (3 ft2)
Suspect fungal growth on vinyl floor (8 ft2)
Cath lab 3 Three ceiling tiles with historic moisture stains (<1 ft2 each) None Observed
Cath lab Common
Area
One ceiling tile with historic moisture stain (1 ft2) None Observed
Cath lab Utility Closet Six ceiling tiles with historic moisture stains (1 ft2 each) None Observed
Quality Management
Director Room None Observed
Suspect fungal growth on drywall (4 ft2)
Hallway by Quality
Management Director
Room
Two ceiling tiles with historic moisture stains (1 ft2 each)
Historic water damage on overhead TSI (3 ft2)
None Observed
Administration Suite
Men’s Bathroom
Historic moisture damage on ceramic tile floor (40 ft2) None Observed
Main Building – 1st Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 18
Administration Suite
Server Room
Condensation visible on ceiling tiles and plastic overhead light coverings (180 ft2)
Suspect fungal growth on moisture-impacted ceiling tiles (20 ft2, non-contiguous)
Hallway SW of
Administration Suite
Historic moisture damage on vinyl floor tile adjacent to exterior doors (150 ft2)
None Observed
Conference Room
South of Social
Services Room
Historic moisture damage on carpet (60 ft2) None observed
West Storage Area, Decon. Storage Room
Historic moisture damage on ceiling tiles and insulation (30 ft2) drywall (10 ft2) plaster ceiling in closet (16 ft2)
Suspect fungal growth on moisture-damaged drywall (5 ft2)
West Storage Area, Diet. Office
Historic moisture damage on ceiling tiles and insulation (30 ft2)
None Observed
MRI Zone 2, Common
Area
Elevated moisture detected on moisture damaged drywall (18 ft2)
Suspect fungal growth on moisture damaged drywall behind cove base (3 ft2)
MRI 2
Historic moisture damage on vinyl floor (20 ft2)
Main Building – 1st Floor (Cont.)
Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 19
MRI 1
vinyl floor (8 ft2)
Three ceiling tiles with historic
None observed
MRI Equipment 2 floor (15 ft2) wall-mounted TSI (2 ft2)
None Observed
Medical Imaging
Lobby
Historic moisture damage on fireproofing on the concrete deck
(30 ft2)
Moisture damaged ceiling tile debris on the floor (8 ft2)
None Observed
Radiology Suite, Diagnostic Radiology
Room
One ceiling tiles with historic moisture stain (1 ft2 each) None Observed
Hallway South of
Radiology Suite, Women’s Bathroom
Historic moisture damage on drywall (4 ft2) None Observed
Main Entrance, Lobby One ceiling tiles with historic moisture stain (1 ft2 each) None Observed
Main Entrance, Cancer Resource
Center
Historic moisture damage on metal pipes above missing ceiling tiles (4 ft2)
None Observed
Main Building – 1st Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 20
Surgery Waiting Area Historic moisture damage on carpet (20 ft2) None Observed
Exit Door at Room
Historic moisture damage on perimeter plaster wall behind vinyl wallpaper
(80 ft2)
Suspect fungal growth (80 ft2) on perimeter plaster wall concealed behind vinyl wallpaper
Room 153 None Observed
Suspect fungal growth (32 ft2) behind vinyl wallpaper on dividing wall to room 153
Room 151 - Restroom Ceiling tile with historic moisture stain (1 ft2) None Observed
Room 156 – Restroom None Observed Suspect fungal growth (2 ft2) on
HVAC supply vent
Room 158 Ceiling tile with historic moisture stain (1 ft2) None Observed
Hallway outside Room
None Observed
Suspect fungal growth (4 ft2) on
HVAC supply vent
Room 148 – Restroom None Observed Suspect fungal growth (10 ft2) on wooden door and metal door frame
Room 147 – Restroom None Observed Suspect fungal growth (10 ft2) on wooden door
Clean Assembly
Room None Observed
Suspect fungal growth (15 ft2) on
HVAC supply vents
Equipment
Decontamination
Room
Water stained TSI above decontamination equipment (20 linear foot)
None Observed
Bio Med Storage Ceiling tile with historic moisture stain (1 ft2) None Observed
Main Building – 1st Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 21
Equipment Storage Ceiling tile with historic moisture stain (1 ft2) None Observed
OR 11
Water staining on vinyl floor from historic water leak
(15 ft2)
None Observed
Unsterile Supply
Storage
Water damaged gypsum wall board (30 ft2) behind vinyl wallpaper from active water leak
Suspect fungal growth (5 ft2) on gypsum board wall above ceiling tile
Hallway Outside OR 7 Ceiling tile with historic moisture stain (4 ft2) None Observed
OR 7
Water staining on vinyl floor from historic water leak
(15 ft2)
None Observed
Equipment Storage at
OR 7
Ceiling tile with historic moisture stain (2 ft2) None Observed
Emergency
Department Storage None Observed
Suspect fungal growth (4 ft2) on gypsum board wall at cove base
Hallway at Room 1147 Ceiling tile with historic moisture stain (2 ft2) None Observed
Hallway at Room 1163 Ceiling tile with historic moisture stain (1 ft2) None Observed
Room 1120 Ceiling tile with historic moisture stain (2 ft2) None Observed
Room 1130 None Observed Suspect fungal growth (4 ft2) on ceiling tile
Main Building – 1st Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 22
Room 1136
Water damaged gypsum board walls adjoining to exterior mechanical room
Suspect fungal growth (48 ft2) on gypsum board walls concealed behind vinyl wall paper
Nurses Station
Outside Room 1136
Water damaged gypsum board walls adjoining to exterior mechanical room
Suspect fungal growth (100 ft2) on gypsum board walls concealed behind vinyl wall paper
Room 1131
Water damaged gypsum board walls adjoining to exterior mechanical room
Suspect fungal growth (56 ft2) on gypsum board walls concealed behind wall panels
Northeast Large
Mechanical Room
Water damaged TSI throughout
Water damaged gypsum board walls adjoining patient room 1131 and 1136
Suspect fungal growth (50 ft2) on gypsum wall board walls adjoining patient room
Suspect fungal growth (160 ft2) on gypsum board walls in northwest corner
Northeast Small
Mechanical Room
Water damaged gypsum board walls adjoining large mechanical room
Suspect fungal growth (20 ft2) on gypsum board walls adjoining large mechanical room
Men’s Restroom at ER
Waiting Room
Water damaged gypsum wall board ceiling (5 ft2) above restroom stalls
Suspect fungal growth (10 ft2) on gypsum board ceiling
Gross Cutting Area
Water staining on vinyl floor from historic water leak
(5 ft2)
None Observed
Chemistry Department Ceiling tile with historic moisture stain (1 ft2) None Observed
Phlebotomy
Department
Ceiling tile with historic moisture stain (1 ft2)
Responsive ■ Resourceful ■ Reliable 23
Bed Repair / Bed
Storage Area None Observed
Suspect fungal growth (150 ft2) of sheetrock debris at building footer in crawlspace remaining after mold remediation activities
Hallway at Soiled
Linen None Observed
Suspect fungal growth (4 linear foot) on TSI
Suspect fungal growth (1 ft2) on
Bulk Storage None Observed Suspect fungal growth (2 ft2) on
HVAC supply vents
Receiving Office Ceiling tile with historic moisture stain (2 ft2) None Observed
Purchasing Work Area Ceiling tile with historic moisture stain (2 ft2) None Observed
Laundry Room Water damaged gypsum board wall (5 ft2) behind washer unit None Observed
X-Ray Files Storage
Room
Water damaged/stained gypsum board wall (15 ft2) at bottom of wall
None Observed
Conference / Break
Room
Ceiling tile with historic moisture stain (2 ft2) None Observed
Hallway at Telecom
Office
Ceiling tile with historic moisture stain (2 ft2) None Observed
Center Mech Room Water damaged gypsum board wall (15 ft2) behind AHU
Suspect fungal growth (2 ft2) on gypsum board wall at HVAC duct penetration
Main Building – Basement
Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 24
Charts/Processing
Department
15 ft2 of water stained carpeting from previous pipe leak
Suspect fungal growth (60 ft2) concealed behind wooden cabinets
Suspect fungal growth (2 ft2) on concrete decking at entry
Waiting Area Outside
Code Supervisor
Office
None Observed Suspect fungal growth (5 ft2) on gypsum board wall
Hallway at Base of
Ramp None Observed
Suspect fungal growth (2 ft2) on gypsum board wall
Central Plant Water stained / damaged TSI throughout
Suspect fungal growth (15 ft2) on various TSI throughout
VP Medical Staff
Office
Ceiling tile with historic moisture stain (6 ft2) None Observed
Entrance / Holding
Area in Pharmacy
Ceiling tile with historic moisture stain (2 ft2) None Observed
Southeast Mechanical
Room
Water stained / damaged TSI throughout
Suspect fungal growth (10 ft2) on various TSI and ducting throughout
Hallway Outside
Engineering Shop None Observed
Suspect fungal growth (5 ft2) concealed behind vinyl cove base on gypsum board wall
AHU G19
Visible water pooling in the drain pan beneath the coils
Return Air Plenum:
None Observed
Supply Air Plenum:
Suspect fungal growth on metal interior walls (8 ft2)
Main Building – Basement (Cont.)
Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 25
The representative building materials evaluated in the targeted area exhibited normal moisture content during the site reconnaissance, with the exception of Treatment Room 1136, Treatment Room 1131 and adjoining hallway, hallway outside first floor unsterile supply storage room, 2nd floor staff lounge, Room 309, Room 3098, Medical Director’s Office, COU Staff Only Room, MRI Zone 2 Common Area, Central Plant, 1st floor northeast large and small mechanical rooms, and Basement Mechanical
Rooms. Standing water was observed in the basement mechanical rooms.
4.2 Visual Evaluation – Plaza Building
Plaza Building – 700 Walter Reed Boulevard
Building Four-story, multi-tenant medical building attached to the main hospital building
Total Area (Included with the main building)
Roof Rubber membrane, rolled-on composition roofing material
Exterior Walls Texture on concrete and texture on plaster
Interior Description
Offices, exam rooms, x-ray rooms, procedure rooms, operating rooms, break rooms, conference rooms, corridors, restrooms, electrical rooms, mechanical rooms, elevator lobbies, and stairwells
Interior Walls
Textured drywall, textured concrete, textured CMU blocks, textured plaster, unfinished drywall, fiberglass reinforced panel on drywall, wall covering on drywall, and ceramic tile on drywall
Interior Ceilings
Textured drywall and 2’x4’ and 2’x2’ lay-in ceiling tile suspended from a concrete deck; spray-on fireproofing was observed on the concrete deck
Interior Floors Unfinished concrete, floor coating, resilient floor covering, vinyl floor tile, raised flooring, carpet, and ceramic tile on a concrete substrate
Survey Limitations/
Inaccessible Areas
Multiple medical suites located in various area of the building were occupied and operational at the time of the survey. The tenants of the occupied suites did not allow unlimited access and access was not granted to the final suite until June 14, 2019. Although the remaining areas of the building were vacant, a large portion of the rooms were locked or used as storage space. Various areas of the vacant spaces had limited lighting and some areas had no lighting.
Debris and remnant furnishings were observed in various vacant areas throughout the interior of the building. Hard ceilings were installed in various areas throughout the interior of the building.
Responsive ■ Resourceful ■ Reliable 26 on the roof.
AHU P-05 was assessed on the third floor of the Plaza Building. Based on information provided by
CBRE personnel, this AHU is representative of a typical AHU for the Plaza Building. No access was available to the fan box, coils or supply air plenum, due to being bolted on. Suspect fungal growth was observed on the interior insulation of the AHU. The quantity of suspect visible fungal growth on interior insulation within the return air plenum was estimated at > 25 square feet, which exceeds the regulatory threshold of 25 square feet established in the Mold Assessors and
Remediators Administrative Rules (MRAR).
moisture damage appeared to be related to historic rain water intrusion through the building envelope suspect fungal growth was observed on walls, ceilings, ceiling tiles and doors/door frames. Surface samples were collected from a drywall wall in Suite 311, ceiling tile in a second-floor corridor closet, and drywall wall in Suite 203. Microscopic analysis identified Stachybotrys, Cladosporium, and
Ulocadium from the referenced sample locations (Appendix A). The quantity of visible fungal growth observed in these areas was less than the regulatory threshold of 25 square feet as defined in the
MARAR. Destructive sampling or disassembly of mechanical components was not within the scope of work for the project. Terracon did not access areas underneath floor tiles, wall paneling, or inside wall cavities. Fungal growth may be present in these areas, if moisture intrusion has occurred.
A surface sample was collected from the ceramic wall tile in the Day Surgery area located on the first floor. Microscopic analysis identified Cladosporium from the referenced sample location
(Appendix A). The quantity of visible fungal growth observed in the day surgery area and basement storage room were above the regulatory threshold of 25 square feet as defined in the MARAR.
The Visual Evaluation results are summarized in Table 2.0
Responsive ■ Resourceful ■ Reliable 27
TABLE 2.0, LIMITED MOLD ASSESSMENT RESULTS TABLE
302 - 1 One ceiling tiles with historic moisture stain (1 ft2) None Observed
302 - 2 One ceiling tiles with historic moisture stain (1 ft2) None Observed
302 - 7
Historic moisture stains on bathroom sink cabinet base and drywall (2 ft2)
None Observed
306 - 6 vinyl floor tile (10 ft2)
None Observed
306 - 7
Historic moisture stains on sink cabinet base (2 ft2)
None Observed
306 - 10 Six ceiling tiles with moisture stains (1 ft2 each)
Two ceiling tiles on the floor with suspect fungal growth (1 ft2 each)
308 - 3 Two ceiling tiles with historic moisture stains (1 ft2 each)
One ceiling tile with suspect fungal growth (1 ft2)
308 - 4
Two ceiling tiles with historic moisture stains (1 ft2 each)
Historic moisture damage on carpet
(8 ft2)
None Observed
Plaza Building – 3rd Floor
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 28
308 - 5
Historic moisture damage on carpet
(4 ft2)
None Observed
311 - 18
Historic moisture stains on sink cabinet base and adjacent drywall (2 ft2)
Suspect fungal growth on drywall behind sink cabinet (1 ft2)
311 - 13 One ceiling tile with historic moisture stain (1 ft2) None Observed
311 - 3 None Observed
Suspect fungal growth on sink cabinet base (3 ft2) and adjacent drywall (2 ft2)
311 - 2 and
311 - 19
Nine ceiling tiles with historic moisture stains (1-2 ft2 each)
Moisture damage on carpet, with elevated moisture detected in some areas (200 ft2) drywall and desks (40 ft2)
One ceiling tile on the floor with suspect fungal growth (1 ft2)
Suspect fungal growth on drywall behind cove base (4 ft2)
305 - 1 Four ceiling tiles with historic moisture stains (1 ft2 each) None Observed
305 - 2
Three ceiling tiles with historic moisture stains in bathroom
(1 ft2 each)
None Observed
305 - 3 Two ceiling tiles with historic moisture stains (1 ft2 each) None Observed
Plaza Building – 3rd Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 29
305 - 4 moisture stains in attached bathroom (1 ft2 each)
One ceiling tile on the floor with suspect fungal growth (2 ft2)
305 - 6 moisture stains (1 ft2 each) None Observed
3rd Floor Mechanical
Room
Moisture damaged TSI throughout None Observed
3rd Floor North-South
Hallway
Two ceiling tiles with historic moisture stains (1 ft2 each) None Observed
3rd Floor East-West
Hallway
Four ceiling tiles with historic moisture stains (1 ft2 each) None Observed
Air Handling Unit
(AHU) P05
None Observed
Return Air Plenum: Suspect visible fungal growth on interior insulation
(>25 ft2)
Supply Air Plenum:
No Access
Plaza Building – 3rd Floor (Cont.)
Moisture Damaged
Building Material
Suspect Visible
Responsive ■ Resourceful ■ Reliable 30
Plaza Building – 2nd Floor
Location Moisture Damaged
Building Material
Suspect Visible
Fungal Growth
Suite 201
Ceiling tiles with historic moisture stains (2 ft2) throughout
None Observed
Suite 203
Ceiling tiles with historic moisture stains (4 ft2) throughout
Suspect fungal growth on drywall behind cove base (2 ft2)
Suite 204
Ceiling tiles with historic moisture stains (14 ft2) throughout
None Observed
Suite 205
Ceiling tiles with historic moisture stains (32 ft2) throughout
None Observed
Suite 208
Ceiling tiles with historic moisture stains (10 ft2) throughout
None Observed
Suite 209
Ceiling tiles with historic moisture stains (8 ft2) throughout
None Observed
Hallway Mechanical
Room None Observed
Return Air Plenum: Environmental debris on interior insulation throughout
Supply Air Plenum:
No Access
Responsive ■ Resourceful ■ Reliable 31
Plaza Building – 1st Floor
Location Moisture Damaged
Building Material
Suspect Visible
Fungal Growth
Nurses Station at Bone
Density
Ceiling tiles with historic moisture stains (4 ft2) None Observed
Area outside Nurses
Station
Ceiling tiles with historic moisture stains (12 ft2)
Historic moisture stains on sheet vinyl flooring (12 ft2)
None Observed
Main Entry Vestibule
Evidence of historical moisture intrusion around perimeter metal window frames (20 linear foot)
None Observed
Hallway at Rooms K1-
K4
Ceiling tiles with historic moisture stains (10 ft2)
Ceiling tile with suspect fungal growth
(1 ft2)
Room M8 Ceiling tiles with historic moisture stains (3 ft2)
Suspect fungal growth on wall column
(2 ft2)
Hallway outside room
M8
Ceiling tiles with historic moisture stains (2 ft2) None Observed
Room M28 stains (35 ft2)
Historic water stains on gypsum board wall (75 ft2)
Ceiling tile with suspect fungal growth
(8 ft2)
Room M10 Ceiling tiles with historic moisture stains (96 ft2)
Ceiling tile with suspect fungal growth
(6 ft2)
Responsive ■ Resourceful ■ Reliable 32
Plaza Building – 1st Floor (Cont.)
Location Moisture Damaged
Building Material
Suspect Visible
Fungal Growth
Hallway outside room
M6
Ceiling tiles with historic moisture stains (2 ft2) None Observed
Day Surgery (Rooms
M15-M27 and ORs 1-4)
TSI piping with historic water stains
Suspect fungal growth
(1,800 ft2) observed on multiple surfaces (i.e. ceramic walls, metal door frames, etc.) throughout
Room M16 None Observed
Suspect fungal growth
(580 ft2) observed on multiple surfaces (i.e. ceramic walls, metal door frames, etc.) throughout
Room M15 None Observed
Suspect fungal growth
(144 ft2) observed on multiple surfaces (i.e. ceramic walls, metal door frames, etc.) throughout
Responsive ■ Resourceful ■ Reliable 33
Plaza Building – Basement
Location Moisture Damaged
Building Material
Suspect Visible
Fungal Growth
Janitor Closet Gypsum board ceiling with historic moisture stains (2 ft2) None Observed
Storage Area Ceiling tiles with historic moisture stains (10 ft2)
Suspect fungal growth observed on gypsum wallboard behind existing cabinets (45 ft2) and within the small storage closet (16 ft2)
Mechanical Room TSI piping with historic water stains None Observed
Stairwell Historic water staining on perimeter concrete wall (100 ft2)
The representative building materials evaluated in the targeted area exhibited normal moisture content during the site reconnaissance.
Responsive ■ Resourceful ■ Reliable 34
4.3 Visual Evaluation – Storage Building
Storage Building – 900 North Shiloh Road
Building Single-story medical building constructed circa 1968
Total Area 19,881 sq. ft.
Roof Tar and gravel roofing system
Exterior Walls Texture on concrete and CMU blocks
Interior Description
Reception, exam rooms, offices, meeting rooms, conference rooms, corridors, restrooms, boiler room, electrical room, warehouse, and shipping/receiving
Interior Walls Textured concrete, textured drywall, wall covering on drywall, ceramic tile on drywall, and fiberglass reinforced panel on drywall
Interior Ceilings 2’ x 4’ lay-in ceiling tile system suspended from a concrete deck;
spray-on fireproofing was not overserved on the concrete deck
Interior Floors Epoxy floor coating, vinyl floor tile, carpet, and ceramic tile on a concrete substrate and unfinished concrete
Survey Limitations/
Inaccessible Areas
The vacant building is currently being used for storage; debris and remnant furnishings were observed throughout the interior of the building. The janitorial closet, Exam Room 101 and the dark room were locked and inaccessible during the assessment.
on the roof.
AHU 1A was assessed in the mechanical room of the Storage Building. AHU 1A was non-functional at the time of the assessment. The fan unit shaft was observed to be broken and no access was available to the fan box, coils or return air plenum, due to being bolted on. AHU 2A was observed to have no suspect visible fungal growth in the supply plenum. No access was available to the fan box, coils or return air plenum, due to being bolted on.
moisture damage appeared to be related to historic rain water intrusion through the building envelope
Responsive ■ Resourceful ■ Reliable 35 suspect fungal growth was observed on walls and ceiling tiles. Surface samples were collected from a ceiling tile in Work Room 9M, concrete tilt panel in the loading dock area and a ceiling tile in the north large work room. Microscopic analysis identified Stachybotrys and Cladosporium from the referenced sample locations (Appendix A). The quantity of visible fungal growth observed in these areas was less than the regulatory threshold of 25 square feet as defined in the MARAR. Destructive sampling or disassembly of mechanical components was not within the scope of work for the project. Terracon did not access areas underneath floor tiles, wall paneling, or inside wall cavities.
Fungal growth may be present in these areas, if moisture intrusion has occurred.
The Visual Evaluation results are summarized in Table 3.0
TABLE 3.0, LIMITED MOLD ASSESSMENT RESULTS TABLE
Storage Building – 900 North Shiloh Road
Moisture Damaged
Building Material
Suspect Visible
Fungal Growth
Office 3M Ceiling tiles with historic moisture stain (1 ft2) None Observed
Office 4M Perimeter concrete wall with historic moisture stain (3 ft2) None Observed
Office 6M Perimeter concrete wall with historic moisture stain (3 ft2) None Observed
Office 1M Ceiling tiles with historic moisture stain (1 ft2) None Observed
Work Room Hallway Ceiling tiles with historic moisture stain (2 ft2) None Observed
Work Room 9M Ceiling tiles with historic moisture stain (12 ft2) 3 ft2 on ceiling tiles
Office 205 Perimeter concrete wall with historic moisture stain (3 ft2) None Observed
Office 206 Perimeter concrete wall with historic moisture stain (8 ft2) None Observed DRAFT
Responsive ■ Resourceful ■ Reliable 36
Storage Building – 900 North Shiloh Road (Cont.)
Moisture Damaged
Building Material
Suspect Visible
Fungal Growth
Office 208 Perimeter concrete wall with historic moisture stain (5 ft2) None Observed
Reception Area
Perimeter concrete wall with historic moisture stain (5 ft2) – Wooden baseboard observed to be 20-90% wet
None Observed
Exam Room 100 Perimeter concrete wall with historic moisture stain (4 ft2) None Observed
Exam Room 101 Ceiling tiles with historic moisture stain (2 ft2) None Observed
Exam Room 104 Perimeter concrete wall with historic moisture stain (4 ft2) None Observed
Exam Room 106 Perimeter concrete wall with historic moisture stain (4 ft2) 4 ft2 around base of window
Nurses Station Ceiling tiles with historic moisture stain (2 ft2) None Observed
Dexa Room 114 Ceiling tiles with historic moisture stain (4 ft2) None Observed
Work Room at Room
Ceiling tiles with historic moisture stain (2 ft2) None Observed
Large Open Work
Room
Ceiling tiles with historic moisture stain (12 ft2)
Suspect fungal growth on HVAC supply registers (5 ft2)
Suspect fungal growth on return…