This document is a Standard Details specification sheet for the Rehabilitation of Screened Final Effluent Pump Station, a capital project managed by the Great Lakes Water Authority (GLWA) with NORESCO serving as the contractor. The specifications represent Volume IV of IV and were prepared by W. Morton, with the document issued for permit in June 2025 and updated in August 2025. The Standard Details provide comprehensive technical drawings and construction specifications for the pump station rehabilitation project, including approximately 140 detailed construction standards covering concrete work, masonry, structural steel, electrical systems, plumbing, HVAC, and site work. The specifications include detailed drawings for form tie holes, wall construction joints, reinforcement patterns, pipe encasements, equipment pads, concrete saddles, beam reinforcements, concrete curbs, masonry wall details, stairs, railings, door frames, roof penetrations, mechanical equipment connections, electrical conduit installations, grounding systems, and site utilities. These Standard Details serve as the technical foundation for construction execution and ensure consistent quality and specification compliance across all structural and mechanical systems throughout the project.
The Standard Details specifications do not contain information regarding pricing terms, contract awards, response deadlines, funding sources, or commercial terms. Rather, the document functions as a technical reference guide establishing construction methodologies, material standards, reinforcement schedules, and installation procedures for all trades involved in the Screened Final Effluent Pump Station rehabilitation. The specifications reference coordination with equipment manufacturers, structural drawings, civil drawings, and architectural drawings, indicating integration with a comprehensive design package. These standards establish minimum requirements for concrete cover, lap lengths, reinforcement spacing, joint construction, anchor bolt installation, and finish specifications to ensure the completed facility meets design intent and performance requirements.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Rehabilitation of Screened Final Effluent Pump Station
Contract No. 2000970
NORESCO for the Great Lakes Water Authority
Volume IV of IV
Standard Details
Prepared By:
June 2025 wmorton Typewritten Text August 2025 wmorton Typewritten Text Issued for Permit
Rehabilitation of SFE Pump Station
Index of Standard Details
No. Standard Detail
0310-051 FORM SNAP-TIE HOLE
0310-052 ALTERNATIVE FORM TIE-THROUGH BOLT
0315-143 SLAB CONSTRUCTION JOINT AT WALL
0315-151 WALL VERTICAL CONSTRUCTION JOINT
0315-152 WALL CONSTRUCTION JOINT AT ELEVATED SLAB
0315-154 WALL BASE CONSTRUCTION JOINT
0330-001 OPENING REINFORCEMENT
0330-003 TYPICAL WALL CORNER & INTERSECTION REINFORCEMENT
0330-016 PIPE ENCASEMENT
0330-018 PIPE ENCASEMENT AT SLAB
0330-037 INTERIOR WALL LATERAL SUPPORT AT PRECAST SLAB/ROOF DETAIL
0330-038 ROOF EDGE PLATE DETAIL
0330-039 0330-044
PRECAST SLAB/ROOF AT NON-BEARING WALL DETAIL
IN-SLAB TRENCH DRAIN REINFORCEMENT
0330-056 (1 OF 5) CONCRETE EQUIPMENT PAD – TYPE ‘C’
0330-056 (2 OF 5) CONCRETE EQUIPMENT PAD – TYPE ‘E’
0330-056 (3 OF 5) CONCRETE EQUIPMENT PAD – TYPE ‘F’
0330-056 (4 OF 5) CONCRETE EQUIPMENT PAD – TYPE ‘H’
0330-056 (5 OF 5) CONCRETE EQUIPMENT PAD – NOTES
0330-059 TANK PAD – CONCRETE
0330-061 (1 OF 2) PIPE SUPPORT – CONCRETE SADDLE
0330-061 (2 OF 2) PIPE SUPPORT – CONCRETE SADDLE
0330-066 (1 OF 3) BEAM REINFORCEMENT
0330-066 (2 OF 3) BEAM REINFORCEMENT
0330-066 (3 OF 3) BEAM SCHEDULE
0330-080 CONCRETE CURB
0330-084 CONDUIT IN STRUCTURAL CONCRETE
0330-143 CONCRETE DEMOLITION
0421-002 TYPICAL BASE OF WALL DETAIL
0422-001 REINFORCED MASONRY WALL CORNERS (SINGLE & DOUBLE MAT)
0422-003 (1 OF 2) CMU OPENING REINFORCEMENT
0422-003 (2 OF 2) CMU OPENING REINFORCEMENT
0422-004 INTERMEDIATE REINFORCED MASONRY SHEAR WALL
0422-005 CMU WALL PIER
0422-006 CMU WALL COLUMN
0422-031 CMU CONTROL JOINT
0512-001 COLUMN BASE – STEEL
0512-020 TYPICAL BEAM CONNECTION – STEEL
0512-067 BEAM SEAT/EXTERIOR WALL – STEEL
0514-020 TYPICAL BEAM CONNECTION – ALUMINUM
0531-001 DECKING LEDGER SUPPORT ANGLE
0531-021 (1 OF 2) ROOF DECK OPENING
0531-021 (2 OF 2) ROOF DECK OPENING
0550-342 PIPE BOLLARD
0551-001 (1 OF 4) STAIR DETAILS – ALUMINUM
0551-001 (2 OF 4) STAIR DETAILS – ALUMINUM
0551-001 (3 OF 4) STAIR DETAILS – ALUMINUM
0551-001 (4 OF 4) STAIR DETAILS – ALUMINUM
0551-003 STAIR LANDING SUPPORT – ALUMINUM
0551-101 LADDER – ALUMINUM - PRE-ENGINEERED PIPE WITH EXTENSION TYPE ‘E’
0551-141 LADDER – STEEL – FLAT BAR UP AND OVER – TYPE ‘C’
0551-151 SHIPS LADDER
0552-001(1 OF 4) RAILING – 2 RAIL – ALUMINUM
0552-001(2 OF 4) RAILING – 2 RAIL – ALUMINUM (IBC)
0552-001(3 OF 4) RAILING POST ANCHORAGE TYPE ‘A’ – ALUMINUM
0552-001(4 OF 4) RAILING POST ANCHORAGE TYPE ‘C’ – ALUMINUM
0552-002 WALL HANDRAIL – ALUMINUM
0553-001 (1 OF 4) STANDARD GRATING
0553-001 (2 OF 4) STANDARD GRATING
0553-001 (3 OF 4) STANDARD GRATING
0553-001 (4 OF 4) STANDARD GRATING
0751-002 ROOF COPING DETAIL AT MASONRY PARAPET WALL
0753-004 BASE FLASHING
0753-005 ROOF/OVERFLOW DRAIN (CONCRETE DECK)
0753-007 PIPE PENETRATION
0753-100A SCUPPER
0753-100B SCUPPER
0770-009 PIPE THROUGH ROOF
0770-031 MECHANICAL EQUIPMENT CURB
0770-036 EXPANSION JOINT (MID ROOF)
0770-037 EXPANSION JOINT (AT WALL)
0770-038 ROOF HATCH
0770-804 PIPE PENETRATION (EXTERIOR WALL)
0811-003 DOOR HEAD DETAIL
0811-004 DOOR JAMB DETAIL
0811-017 DOOR HEAD
0833-003 OVERHEAD COILING DOOR – HEAD DETAIL
0833-004 OVERHEAD COLINING DOOR – JAMB DETAIL
0833-010 ROLLUP DOOR SILL (INSULATED)
0845-002 TRANSLUCENT WALL PANEL HEAD AND SILL
0871-001 DOOR SILL
1235-051 LAB CABINET SECTION
2113-552 PIPE PENETRATION – RATED WALL
2210-300 INTERIOR HOSE VALVE
2210-452 PIPE HANGER
2210-800 NATURAL GAS METER
2210-801 GAS FIRED EQUIPMENT CONNECTION
2213-140 FLOOR CLEANOUT
2213-170 SUMP PUMP
2213-171 LEVEL SWITCH SUPPORT BRACKET
2213-180 EXTERIOR CLEANOUT
2214-180 ROOF DRAIN
2245-410 EMERGENCY EYEWASH STATION
2305-804 DUCTWORK SUPPORT
2331-103 FLOOR EXHAUST
2331-112 RECTANGULAR DUCT TAKEOFF
2331-400 FIRE DAMPER INSTALLATION
2334-833 DUCTED ROOF MOUNTED FAN
2334-834 ROOF MOUNTED FAN
2337-809 DUCT MOUNTED AIR OUTLET OR INLET
2337-810 DUCT WALL PENETRATION
2380-427 UNIT HEATER MOUNTING
2605-002 DEVICE MOUNTING, WALL OR COLUMN
2605-003a DEVICE MOUNTING, NONFUSED DISCONNECT SWITCH 2605-003b DEVICE MOUNTING, NONFUSED DISCONNECT SWITCH 2605-005a DEVICE MOUNTING, CONTROL STATION PEDESTAL 2605-005b DEVICE MOUNTING, MOTOR CONTROL STATION 2605-008a DEVICE MOUNTING, PULLBOX PEDESTAL 2605-008b DEVICE MOUNTING SIDE MOUNTED PEDESTAL- ALUMINUM
2605-010 CONCRETE ANCHOR INSTALLATION
2605-011a DEVICE MOUNTING, PEDESTAL 2605-011b DEVICE MOUNTING, PEDESTAL
2605-012 DEVICE MOUNTING, PEDESTAL
2605-014 DEVICE MOUNTING, TUBE COLUMN BASE DETAIL
2605-015 MCC OR CONTROL PANEL CONDUIT ENTRANCE, BOTTOM ENTRY
2605-016 FLUSH MOUNTED CONDULET
2605-017 CONDUIT SUPPORT ON STRUCTURE
2605-018 FLEXIBLE CONDUIT SUPPORT
2605-100 TERMINATION OF SHIELDED INSTRUMENTATION CABLE
2605-100 UNACCEPTABLE METHOD OF GROUNDING INSTRUMENTATION CABLE
SHIELD
2605-102 TERMINAL JUNCTION BOX (TJB)
2605-201 GROUND TRIANGLE
2605-202 GROUND TEST WELL
2605-203 CONDUIT GROUNDING
2605-204 PAD MOUNTED TRANSFORMER AND PAD MOUNTED SWITCH GROUNDING
2605-205 GROUND ELECTRODE
2605-206 GROUND ELECTRODE
2605-207 GROUNDING, GENERAL STAIRWAY
2605-208 GROUND BUS
2605-235 GROUND ROD CONNECTION
2605-300 CONDUIT RACKING SYSTEM
2605-301 CONDUIT RACKING SYSTEM
2605-302 CONDUIT RACKING SYSTEM, VERTICAL
2605-303 CONDUIT TO EQUIPMENT FROM CEILING
2605-304 CONDUIT ENTRANCE
2605-305 CONDUIT TRANSITION AND SUPPORT
2605-306 INTERIOR WALL PENETRATION
2605-307 CONDUIT UNDERGROUND ENTRANCE
2605-308 (1 OF 2) WATERTIGHT WALL CONDUIT SEAL
2605-308 (2 OF 2) WATERTIGHT WALL CONDUIT SEAL
2605-309 FLUSH CONDUIT STUB
2605-310 INTERIOR FLOOR SLAB PENETRATION
2605-311 PEDESTAL MOUNTED DEVICE OVERHEAD FEED
2605-312 FLASHING
2605-313 CONDUIT IN CONTAINMENT AREA
2605-315 EXPANSION/DEFLECTION COUPLING
2605-316 EXPANSION FITTING FOR SOIL MOVEMENT
2605-317 CONDUIT EXPANSION JOINT
2605-318 VERTICAL CONDUIT SUPPORT
2605-400b (1 OF 2) DUCT BANK 2605-400c (2 OF 2) DUCT BANK
2605-403 CONCRETE ENCASED DUCT
2605-404 EXISTING DUCT BANK EXTENSION
2605-420 UNDERGROUND CONDUIT IN NON-PAVED AREAS
2605-443a (1 OF 2) MANHOLE-WITH GROUNDING 2605-443b (2 OF 2) MANHOLE-WITH GROUNDING
2605-444 HANDHOLE
2605-445 CONDUIT HANDHOLE/MANHOLE ENTRANCE
2605-446 CONDUIT HANHOLE/MANHOLE ENTRANCE
2605-447 CABLE SUPPORT BRACKET
2605-448 CABLE RACK
2605-600 DEVICE MOUNTING, BOX IN CONCRETE MASONRY WALL
2605-601 DEVICE MOUNTING, COMPUTER OUTLET BOX
2605-801 SAMPLE PUMP
2612-001 TRANSFORMER OR SWITCH PAD
2620-001 LARGE MOTOR CONNECTION
2622-002 TRANSFORMER MOUNTING
2605-003a PENDANT MOUNTED FIXTURE
2650-299 (1 OF 2) LIGHT POLE BASE
2650-299 (2 OF 2) LIGHT POLE BASE
2651-205 LUMINAIRE MOUNTING
2655-208 SAFETY SHOWER LIGHT FIXTURE
2656-207 PAVED AREA LIGHT POLE FOOTING
2656-216 SITE AREA LIGHT POLE FOOTING
3123-110 TYPICAL TRENCH
3123-120 TRENCH PIPE CROSSING
3123-915 WELDED STEEL PIPE TRENCH
3231-410 CHAIN LINK FENCE
3231-415 DOUBLE SWING GATE
3231-420 PEDESTRIAN GATE
3305-760 CASED UNDERCROSSING
3305-900 SURFACE MONITORING POINT
3305-901 UTILITY MONITORING POINT
3305-903 LAP JOINT WELD
3305-907 BUTT WELD – TUNNEL CASING PIPE JOINT
3305-936 2-1/2 INCH AND SMALLER OUTLETS
3312-650 AIR RELEASE VALVE MANHOLE
4005-500 PIPE SUPPORT SADDLE SUPPORT PEDESTAL TYPE – ADJUSTABLE
4005-501 PIPE SUPPORT SADDLE SUPPORT PEDESTAL TYPE – NON – ADJUSTABLE
4005-505 PIPE SUPPORT – WALL MOUNTED
4005-517 BASE BEND
4005-521 STACKED PIPE WALL SYSTEM
4005-554 PIPE HANGER
4005-555 STACKED TRAPEZE PIPE HANGER
4005-556 BEAM CLAMP
4005-558 TRAPEZE PIPE HANGER
4005-559 TYPICAL PIPE HANGER AND SUPPORT DETAIL
4005-573 (1 OF 2) PRECAST PLANK SINGLE PIPE SUPPORT
4005-573 (2 OF 2) PRECAST PLANK SINGLE PIPE SUPPORT
4027-191 LINE DRAIN VALVE INSTALLATION
4027-194 PRESSURE TEST POINT
4027-195 AIR RELEASE VALVE ASSEMBLY
4027-196 AIR RELEASE VALVE ASSEMBLY
4027-600 DUCTILE IRON WALL PIPE
4027-601 MECHANICAL JOINT WALL PIPE FOR DIP
4027-602 MECHANICAL JOINT WALL PIPE
4027-622 FLOOR PIPE
4027-957A CHEMICAL INJECTOR, RETRACTABLE, FLEXIBLE HOSE
4027-957C CHEMICAL INJECTOR, RETRACTABLE
4091-156 DISSOLVED OXYGEN PROBE INSTALLATION
4091-222G MAGNETIC FLOWMETER INSTALLATION
4091-248 TYPICAL FLOAT TYPE LEVEL SWITCH INSTALLATION
4091-252 FLANGE MOUNTED ULTRASONIC TRANSDUCER
4091-300 PRESSURE SWITCH OR INDICATOR INSTALLATION
4091-304A PRESSURE SWITCH & INDICATOR INSTALLATION
4091-304C PRESSURE SWITCH AND INDICATOR WITH ANNULAR SEAL INSTALLATION
4091-305A PRESSURE CONNECTION INSTALLATION
4091-305B PRESSURE CONNECTION INSTALLATION
4091-305C PRESSURE CONNECTION INSTALLATION
© JACOBS
REHABILITATION OF SCREENED FINAL EFFLUENT PUMP STATION
UNIFORM IN EACH DIRECTION.
APPROXIM ATELY EQUAL HORIZONTALLY AND VERTICALLY AND SHALL BE
THE SPACING OF FORM TIES ON EXPOSED PORTIONS OF W ALLS SHALL BE
iaw0310-051.dgn 5/19/2025
NTS
FORM SNAP-TIE HOLE
0310-051
EXPOSED FACE OF W ALL
W ATERSTOP
SIDE OF W ALL
INSIDE OR W ATER
INSERTS EACH FACE
USE CONICAL TYPE
SPECIFIED, TYP
DEPTH OF CONE AS
NOTE:
REPAIR M ATERIAL
FILL W ITH
1.
2.
3.
4.
DRIVE IN VINYL PLUG.
SANDBLAST OR MECHANICALLY ROUGHEN W ITH ELECTRIC EQUIPMENT.
NOTE:
CONSTRUCTION STEPS:
COAT HOLE ON DRY SIDE OF PLUG AND W HILE BONDING AGENT IS TACKY, DRYPACK.
5.
SURFACES
TAPER-TIE HOLE
SANDBLAST
ROUGHEN OR
MECHANICALLY
DRY SIDE
DRYPACK
BONDING AGENT
COAT HOLE W ITH
FACE OF W ALL
EXTERIOR (DRY SIDE)
SIDE) FACE OF W ALL
INTERIOR (W ATER
W ATER SIDE
DRYPACK
AT CENTER OF W ALL
REQD TO FIT TIGHT
SIZE OF PLUG AS
DRIVE IN VINYL PLUG,
HOLE DIAMETER AT INTERIOR FACE = 1 1/4"
MINIM UM HOLE DIAMETER AT EXTERIOR FACE = 1". TAPER HOLE SO THAT MINIM UM
USE CATEGORY II, NON-SHRINK GROUT AS SPECIFIED.
DRYPACK.
COAT HOLE ON W ATER SIDE OF PLUG AND W HILE BONDING AGENT IS TACKY,
iaw0310-052.dgn 5/19/2025
ALTERNATE FORM TIE-THROUGH BOLT
0310-052 iaw0315-143.dgn 5/19/2025
SLAB CONSTRUCTION JOINT AT W ALL
0315-143
0315-003
3/4"
3/4" x SLAB DEPTH + 1"
CONTINUOUS KEYW AY,
W ATERSIDE
DRY SIDE
FORMING
FACILITATE W ALL
CONNECTORS TO
THREADED
W / MECHANICAL
PROVIDE DOW ELS
OPTION TO
CONTRACTORS
HYDROPHILIC W ATERSTOP
SEAL
SLAB FOR COMPLETE
OF INTERMEDIATE
W ATERSIDE EDGES
GROOVE, TYP ALL
INTERMEDIATE SLAB
CONTINUOUS PAST
POUR W ALLS
& REINFORCEMENT
ELEVATION, THICKNESS
SEE PLANS FOR
INTERMEDIATE SLAB,
ROUGHEN AND CLEAN
PLAN
iaw0315-151.dgn 5/19/2025
W ALL VERTICAL CONSTRUCTION JOINT
0315-151
INDICATED ON PLANS
LAP REINF AS
FROM TOP OF W ALL
CONTINUOUS, STOP 1 1/2"
6" PLASTIC W ATERSTOP
T H
IC
K
N E
S S
W A
L L
T
T /2
1.
NOTES:
ALL REINFORCEMENT CONTINUOUS ACROSS JOINT.
W ALL
ELEVATED SLAB
/2
/2
W ATERSTOP
W ITH 6" PLASTIC
CONSTRUCTION JOINT
W ATERSTOP
W ITH 6" PLASTIC
CONSTRUCTION JOINT
iaw0315-152.dgn 5/19/2025
W ALL CONSTRUCTION JOINT AT ELEVATED SLAB
0315-152
C L
R
SECURE W ATERSTOP IN-PLACE AS SPECIFIED.
1.
2.
EQUAL
/2
W ATERSTOP
6" PLASTIC
JOINT
CONSTRUCTION
SEE PLANS
SLAB TOP REINF
LOCATION OF BASE
FACE, 1" CLEAR OF REINFORCEMENT.
FOR W ALLS W ITH SINGLE M AT OF REINFORCING LOCATE W ATERSTOP ON LIQUID
iaw0315-154.dgn 5/19/2025
W ALL BASE CONSTRUCTION JOINT
0315-154
L A P
2.
3.
4.
5.
6.
OPNG OPNG
1.
DO NOT W ELD REINFORCEMENT TO PIPE SLEEVES AND INSERTS.
FOR OPENINGS LARGER THAN 8'-0", REINFORCE SAME AS FOR 8'-0" OPENINGS.
PROVIDE MINIM UM LAP, SEE GENERAL STRUCTURAL NOTES.
NOTES:
iaw0330-001.dgn 5/19/2025
0330-001
7.
OPENING REINFORCEMENT
OTHERW ISE ON PLANS.
STRUCTURES AND ALL STRUCTURAL CONCRETE SLABS UNLESS INDICATED
TYPICAL FOR ALL OPENINGS IN CONCRETE W ALLS OF BELOW GRADE AND HYDRAULIC
FACE), INCLUDING DOW ELS AND CORNER BARS, TYPICAL.
PROVIDE A MINIM UM OF 2 "A" BARS AND 2 "B" BARS EACH SIDE OF OPENING (1 EACH
TOTAL AREA ON EACH SIDE OF OPENING.
SPACE AT 3 BAR DIAMETERS (OR 3" MINIM UM) ON CENTER. LOCATE HALF OF
EXTRA REINFORCEMENT W HICH W ILL FIT, AT THE BAR SPACING IN NOTE 6.
AT OPENINGS W ITHIN 12" OF AN INTERSECTING W ALL OR SLAB, PROVIDE ONLY THE
CUT, SEE NOTE 6 & 7
BAND "A" BARS
BARS EQUAL
TOTAL AREA OF
CUT, SEE NOTE 6 & 7
EQUAL BAND "B" BARS
TOTAL AREA OF BARS
SEE NOTE 1
CUT BAND "B"
STEEL REINF
CUT BAND "A"
STEEL REINF
LARGER THAN 8"
OF REINF FOR OPNGS
OPNG +8", IN EA LAYER
1 - #5 HOOP, DIA OF
EA LAYER OF REINF
AT EA CORNER FOR
ADD 1 - #5x4'-0" DIAG
SEE NOTE 1
iaw0330-003D.dgn 5/19/2025
0330-003
ON DRAW INGS
REINF AS SHOW N
TYP HORIZ W ALL
LAP
L A
P
"L"
NOTE
L
N O
T E
NOTE 2
"L"
N O
T E
LAP
L A
P
"L"
NOTE
"L"
N O
T E
L
N O
T E
NOTE 2
OTHERW ISE NOTED
HOOK UNLESS
STD ACI-318 90°
SEE NOTES 1 & 4
ON DRAW INGS,
REINF AS SHOW N
TYP HORIZ W ALL
NOTES:
TYPICAL W ALL CORNER & INTERSECTION REINFORCEMENT
SINGLE REINFORCEMENT M AT
DOUBLE REINFORCEMENT M AT
SM ALLER OF THE TW O REINFORCEMENT BARS BEING SPLICED.
W HERE LAPPED BARS ARE DIFFERENT SIZE, USE THE LAP LENGTH REQUIRED FOR THE5.
INDICATED IN THE GENERAL STRUCTURAL NOTES.
TYPICAL HORIZONTAL REINFORCEMENT SHALL BE LAPPED W HERE SHOW N OR AS4.
EXCEPT THAT IN NO CASE SHALL IT BE LESS THAN 2 FEET.
"NOTE 3" SHALL BE THE LESSER OF L/4, 10 FEET, OR 1.0 TIMES THE HEIGHT OF THE W ALL, EXCEPT W HERE OTHERW ISE SHOW N ON THE DRAW INGS, THE LENGTH INDICATED AS3.
SECTIONS.
CORNER BARS SHALL M ATCH SIZE OF TYPICAL HORIZONTAL REINFORCEMENT SHOW N IN2.
REINFORCEMENT SHOW N IN THIS DETAIL.
REINFORCEMENT SHALL BE ALTERNATED W ITH THE TYPICAL HORIZONTAL
W HERE SHOW N ON PLANS, ADDITIONAL HORIZONTAL W ALL CORNER AND INTERSECTION1.
3" CLR
REHABILITATION OF SCREENED FINAL EFFLUENT PUMP STATION
TYP
1.
SECTION
0330-018 iaw0330-016.dgn 5/19/2025
PIPE ENCASEMENT
0330-016
TOGETHER. SEE
W HEN PIPE ENCASEMENT IS CLOSER THAN 4" TO SLAB ABOVE, TIE SLAB & ENCASEMENT
#5 TIES @ 12"
NOTES
GENERAL STRUCTURAL
LAP LENGTH, SEE
AROUND
8" MIN ALL
CONTINUOUS
7 - #5
1.
TYP 1'-0" 1'-0"
M
IN
0330-016
SECTION
NOTES:
iaw0330-018.dgn 5/19/2025
PIPE ENCASEMENT AT SLAB
0330-018
2'-0"
ENCASEMENT AND BOTTOM OF SLAB IS LESS THAN 4".
TIE PIPE ENCASEMENT TO SLAB AS SHOW N W HEN DISTANCE BETW EEN PIPE
OF SLAB ABOVE
1'-0" INTO TOP
EXTEND VERTS & BEND
#5@ 12"
NOT SHOW N
TYPICAL SLAB REINF
#5@ 12"
SEE NOTE 2
JOINT
CONSTRUCTION
AT ENCASEMENT
THICKEN SLAB
SEE
PIPE ENCASEMENT REINF
iaw0330-037.dgn 5/19/2025
0330-037
INTERIOR W ALL LATERAL
SUPPORT AT PRECAST SLAB/ROOF DETAIL
PLAN FOR SIZE AND REINF
INTERIOR CM U W ALL. SEE
L5x3x3/8 x 0'-6"LG (LLV) @ 48" OC
6" MIN
TYP
TYP
3 SIDES,
TOW SEE PLAN
TOC SEE PLAN
TOPPING SLAB
FRAMING AND
PRECAST
1/4" CLR TYP
3/16
BOND BEAM, SEE PLAN
EACH ANGLE SUPPORT.
PRECAST SUPPLIER. TYP AT
M ASONRY SUPPORT ANGLES BY
CONTINUOUS EMBED FOR
84 00 AT FIRE-RATED W ALLS
FIRESTOPPING PER SECTION 07
OF NON-RATED W ALLS AND
BACKER AND SEALANT AT TOP
iaw0330-038.dgn 5/19/2025
0330-038
ROOF EDGE PLATE DETAIL
SEE PLAN
TOW EL,
8"4"2"
EMBED = 3", TYP
ADHESIVE ANCHOR,
POST-INSTALLED
OC FOR 1/2" DIA
W ITH STD HOLE @ 48"
CONT PL3/8x14" (GALV)
SEE PLANS FOR W ALL CONSTRUCTION
AIR SPACE
CONC FILL
SEE ARCH DW GS
VENEER,
DOW EL M AY BE FIELD BENT
LAP SPLICE
(2) #5 IN VERTICAL FACE
#5@ 16", UON
LAP SPLICE
1'-7"
4" UON, BEARING PAD BY PRECASTER
8" BOND BEAM REINF W / (2) #5, TYP UON
INFORM ATION
FOR ADDITIONAL
SEE ROOF PLAN
SUPPLIER,
PRECAST CONC
CONC PLANK BY
ON PRECAST
CONC TOPPING
3" MIN REINF
iaw0330-039.dgn 5/19/2025
0330-039
AT NON-BEARING W ALL DETAIL
PRECAST SLAB/ROOF
BREAK OUT CELL OF HOLLOW CORE
3" MIN CONC TOPPING
CORE PLANK
HOLLOW
#4 x CONTINUOUS
#4 @ 2'-0"
CM U
B O
N D
B E
A M
X C
O N
T
W
(2
0330-044
SIDES
TYP 4
REINF
TYP SLAB
REINF
TYP SLAB
0330-001
0330-001
THICKENED SLAB - TYPE 'B'
12" MIN1'-0"
#5@ 6" TYP
3'-0"
PER
REINF 4 SIDES
DIAG & ADDL
EMBEDMENT
OF BAR
LENGTH PLANS
SEE
P L
A N
S
S E
E
BAR SIZE AND SPG
M ATCH TOP M AT
TYPICAL SLAB - TYPE 'A'
SIDES PER
DIAG & ADDL REINF 3
BAR SIZE AND SPG
M ATCH TOP M AT
M
IN
S
E E
P L
A N
S
PLANS
SEEEMBEDMENT
TYP
OF BAR,
LENGTH
#5@ 6" TYP
3'-0"
IN-SLAB TRENCH DRAIN REINFORCEMENT
THICKNESS
SLAB
#4@ 12" EW
iaw0330-056C.dgn 5/19/2025
0330-056
THICKNESS NOT SHOW N SEE PLANS
SUSPENDED SLAB; FOR REINF AND
OF OPNG EW
2 MIN EA SIDE
GENERAL NOTE:
FOR GENERAL NOTES SEE DETAIL 5 OF 5.
M
IN1
M AX
1 1/2"
X
OF PAD
2 - #4 @ TOP
FOR PAD HT > 10"
ADDL #4@ 6"
4 1/2" MIN ALL AROUND
AROUND
3" MIN ALL
FORM TO RETAIN GROUT
PLANS & EQUIP MFR
OPNG SIZE, VERIFY W /
EQUIPMENT BASE
OR EPOXY GROUT
NON-SHRINK GROUT
1 1/2" FLUID
DETAILS
ANCHOR BOLT
SEE NOTES &
ANCHOR BOLT,
3/4" CHAMFER, TYP
LARGER)
FOR AB 3/4" OR
PER PAD (#5@ 12"
#4@ 12" MIN 4
OPENINGS > 6"
#4 OR FOR
OPNG IF "X" > 1'-6"
#4@ 12" BARS AT
CONSTRUCTION JOINT
NOTE 7
SEE
TYPE 'C'
CONCRETE EQUIPMENT PAD - TYPE 'C'
DETAIL 1 OF 5
1.
2.
NOTES:
iaw0330-056E.dgn 5/19/2025
GENERAL NOTE:
UNLESS NOTED OTHERW ISE.
EQUIPMENT SHALL BE 3 1/2" HIGH,
CONCRETE PADS FOR ELECTRICAL
ANCHORS SPECIFIED.
TO PAD IS REQUIRED, USE CONCRETE
W HEN ANCHORAGE OF EQUIPMENT
FOR GENERAL NOTES SEE DETAIL 5 OF 5.
CALCULATIONS
ANCHORAGE
OR AS REQUIRED BY
2" MIN ALL AROUND
10" M AX
REQD, 3 1/2" MIN,
PAD HEIGHT AS
FOR PAD HT > 4"
#4@ 12" EW , 1 1/2" CLR
FOR PAD HT < 4",
#3@ 12" EW , 1" CLR
EQUIPMENT
EQUIPMENT PAD
3/4" CHAMFER, TYP
FOR THICKNESS SEE PLANS
SLAB OR SLAB ON GRADE,
EXST OR NEW SUSPENDED
TO PLACING PAD
ROUGHEN & CLEAN PRIOR
CONSTRUCTION JOINT,
TYPE 'E'
CONCRETE EQUIPMENT PAD - TYPE 'E'
DETAIL 2 OF 5
@ 12" OC @ PERIMETER
#4 ADHESIVE DOW EL
DETAIL 3 OF 5
iaw0330-056F.dgn 5/19/2025
M AX
1 1/2"
M
IN1
4 1/2" MIN ALL AROUND
3" MIN ALL AROUND
#4@ 12" EW
FOR PAD HT > 10"
ADDL #4@ 6"SEE NOTE 7
2 - #4 @ TOP OF PAD
3/4" CHAMFER, TYP
& ANCHOR BOLT DETAILS
ANCHOR BOLT, SEE NOTES
EQUIPMENT BASE
OR EPOXY GROUT
NON-SHRINK GROUT
1 1/2" FLUID
ANCHOR BOLT SLEEVE
THICKNESS SEE PLANS
OR SLAB ON GRADE, FOR
EXST SUSPENDED SLAB
PRIOR TO PLACING PAD
ROUGHEN & CLEAN
CONSTRUCTION JOINT,
TYPE 'F'
CONCRETE EQUIPMENT PAD - TYPE 'F'
EMBED
@ 12" M AX, 4 MIN,
#5 ADHESIVE DOW EL
IN
© JACOBS
REHABILITATION OF SCREENED FINAL EFFLUENT PUMP STATION
iaw0330-056H.dgn 5/19/2025
1.5
NOTE:
ANCHORS SPECIFIED.
TO PAD IS REQUIRED, USE CONCRETE
W HEN ANCHORAGE OF EQUIPMENT
MIN
6"
M
IN
ON PLANS
NOTED OTHERW ISE
6" MIN, TYP UNLESS
#5@ 12" EW T&B
2 - #5 CONT
GRADE
FINISH
SEE NOTE
ANCHORS,
CONCRETE
EQUIPMENT
ALL AROUND
EDGE OF SLAB
THICKENED
TYP
CHAMFER,
3/4"
TYPE 'H'
CONCRETE EQUIPMENT PAD - TYPE 'H'
DETAIL 4 OF 5
iaw0330-056L.dgn 5/19/2025
CONCRETE EQUIPMENT PAD - NOTES
DETAIL 5 OF 5
AB DIA (IN.)
MIN PAD HT (IN.)
1 2
7 10 11 15 18 21 24
1/2 5/8 3/4 7/8 1 1/4 1 3/8 1 1/2 1 3/4
8 1/2 12 1/2 16 1/2
NOTES:
4" MINIM UM EDGE DISTANCE IN EACH DIRECTION.
AND APPROVED BY THE ENGINEER. ANCHORS SHALL BE INSTALLED W ITH
THAN 3/4" DIAMETER W HEN APPROVED BY THE EQUIPMENT M ANUFACTURER
OF CAST-IN-PLACE ANCHOR BOLTS FOR EQUIPMENT ANCHOR BOLTS LESS
AT CONTRACTOR'S OPTION, CONCRETE ANCHORS M AY BE USED IN LIEU6.
KEEP ANCHOR BOLT ABOVE SUPPORTING SLAB (SEE TABLE BELOW ).
HEIGHT OF PADS SHALL BE MINIM UM REQUIRED FOR ANCHOR BOLT CLEARANCE TO 5.
SET AND PACK VOID W ITH GROUT.
THE GROUT IS PLACED. W EDGES OR SHIMS SHALL BE REM OVED AFTER GROUT IS
W EDGES, SHIMS, OR LEVELING NUTS SHALL BE USED TO SUPPORT THE BASE W HILE4.
EQUIPMENT BASES SHALL BE INSTALLED LEVEL UNLESS INDICATED OTHERW ISE.3.
PAD IS BEING PLACED.
A TEMPLATE OR OTHER ACCEPTABLE MEANS, M ATCHING THE BASE PLATE, W HILE
APPROVED BY THE ENGINEER. ANCHOR BOLTS SHALL BE HELD IN POSITION W ITH
BOLTS SHALL BE DETERMINED BY THE EQUIPMENT M ANUFACTURER AND AS
THE SIZE, NUMBER, TYPE, LOCATION, AND THREAD PROJECTION OF THE ANCHOR 2.
INDICATED BY THE M ANUFACTURER AND APPROVED BY THE ENGINEER.
PAD SIZE SHALL BE MINIM UM INDICATED OR AS SHOW N ON THE PLANS OR AS 1.
iaw0330-059.dgn 5/19/2025
0330-059
PLAN
1. FOR CONCRETE EQUIPMENT PAD NOTES SEE
SEE PLAN
T.O. PAD EL
SECTION
TANK
SEE PLAN
T.O. CONC EL
#5@ 12" EW
#5@ 12"
SLAB, SEE PLANS
FOUNDATION
2"
T A N
K R
A D
IU
S
SIDES
8 EQUAL
LAP
TANK PAD - CONCRETE
TYPE 'A' SADDLE
iaw0330-061A.dgn 5/19/2025
PIPE SUPPORT - CONCRETE SADDLE
0330-061
DETAIL 1 OF 2
5" TYP
6" EMBEDMENT
DOW ELS,
ADHESIVE OR
D
D /4
2" CLR,
TYP
C L
R
/2
60° 60
SPACING
VERTICAL
#5@ 12" M AX
30°
#3
(2 x
D M
A X
V A
R
IE
S
GROUT, POURABLE
1" MIN NON-SHRINK
INDICATED ON PLANS
PIPE STRAP W HERE
TABLE
SADDLE, SEE
W IDTH 'B' OF
SEE PLAN
FOR ELEVATION,
NEW OR EXST
CONCRETE SLAB,
TO PIPE DURING POURING
FELT SECURE TIGHT
2 LAYERS OF ROOFING
AT TOP OF CONCRETE
'V', EXTEND TO 1 1/2" CLR
VERTICAL REINFORCEMENT
SEE TABLE
iaw0330-061D.dgn 5/19/2025
PIPE SUPPORT - CONCRETE SADDLE
0330-061
DETAIL 2 OF 2
NOTES:
18"
16"
12"
10"
9"
9"
B
W IDTH
SADDLE
3/8"x3"
3/8"x3"
1/4"x3"
1/4"x2"
3/16"x2 1/2"
3/16"x2"
S
STRAP SIZE
PIPE
PIPE SADDLE TABLE
60" < D = 72"
48" < D = 60"
36" < D = 48"
24" < D = 36"
12" < D = 24"
D = 12"
D
DIAMETER
PIPE
2 (EF)
2 (EF)
2 (EF)
2 (EF)
1 (CTRD)
1 (CTRD)
REINFORCEMENT
LAYERS OF
#6@ 12"
#6@ 12"
#5@ 12"
#5@ 12"
#5@ 12"
#5@ 12"
V
REINFORCEMENT
VERTICAL
8'-0"
6'-0"
4'-0"
3'-0"
2'-0"
1'-6"
W
W IDTH
FOOTING
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
2'-0"
C
DEPTH
FOOTING
60" < D = 72"
48" < D = 60"
36" < D = 48"
24" < D = 36"
12" < D = 24"
D = 12"
D
DIAMETER
PIPE
#5@ 6"
#5@ 6"
#5@ 12"
#5@ 12"
#5@ 12"
#5@ 12"
A
REINFORCEMENT
STRAPS
NO. OF
TYPE 'B' PIPE SADDLE FOOTING TABLE
AND PIPE.
PROVIDE 3/4" x (STRAP W IDTH PLUS 1" W IDE) NEOPRENE PAD BETW EEN STRAP6.
AT SUBMERGED CONDITIONS, STRAP SHALL BE STAINLESS STEEL.5.
INDICATED OTHERW ISE A STRAP IS NOT REQUIRED.
FOR LOCATIONS W HERE PIPE STRAP IS REQUIRED, REFER TO DRAW INGS. UNLESS4.
USE TYPE 'B' IN OTHER LOCATIONS.
USE TYPE 'A' SADDLE IN ALL LOCATIONS W HERE A SLAB (NEW OR EXISTING) OCCURS.3.
FORM 3/4" BEVEL ON ALL EXPOSED CORNERS OF SUPPORT.2.
BARS 90° TO HOOK AROUND VERTICALS , 1 1/2" COVER.
FOR 'B'=10" OR THICKER, USE 2 LAYERS OF REINFORCEMENT, TURN HORIZONTAL1.
DETAIL 1 OF 3
5/19/2025iaw0330-066A.dgn
0330-066
IS GREATER
WHICHEVER
NOTES:
CLR
2"
1/4 L1 1/3 L1 OR 1/3 L2
IS GREATER
WHICHEVER
1/3 L1 OR 1/3 L2
CLR
4"
TYP
3"
TYP
3"
FOR SIZE AND SPACING SEE SCHEDULE
SHEAR REINF
FOR SIZE AND SPACING SEE SCHEDULE
SHEAR REINF
L1 L2
(TC)(S)
(B)
(BC)
(T)
CL SUPPORT, BEAM IS CONTINUOUS
@ SUPPORT
SPLICE BC BARS
AT MIDSPAN
BARS AND "S" BARS
SPLICE TOP CONT
(TC)
SHEAR REINF(BC)
(B) STOP AT FACE OF SUPPORT
BARS
TOP
(T)
AS REQD, TYP
BEND, ROTATE
STANDARD 90°
IS DISCONTINUOUS
CL SUPPORT, BEAM
(TC)
NOTE 4
LONGITUDINAL BEAM SECTION
POCKET THE FULL WIDTH AND DEPTH OF BEAM.
CAST BEAM INTEGRAL WITH SUPPORT OR PROVIDE BEAM4.
CORNER OF STIRRUPS.
PROVIDE MINIMUM 1 - #5 CONTINUOUS AT EACH3.
BY ADJACENT SLAB.
DEGREE HOOK ONLY ALLOWED WHERE CROSS TIE CONFINED
SHOWN ( ), OR AS SHOWN ON "TYPICAL SECTION". 90
CLOSED STIRRUPS ( ), TWO PIECE WITH CROSS TIE AS
IN BEAM SCHEDULE. CLOSED STIRRUPS MAY BE SINGLE PIECE
PROVIDE CLOSED STIRRUPS UNLESS OTHERWISE INDICATED2.
MULTIPLE ROWS ONLY WHERE INDICATED IN SCHEDULE.
PLACE TOP (T & TC) AND BOTTOM (B & BC) BARS IN1.
BEAM REINFORCEMENT
BEAM SCHEDULE
REQUIRED, SEE
(S) WHERE
DETAIL 2 OF 3
5/19/2025iaw0330-066B.dgn
PERIMETER BEAM SECTION
B E
A M D
E P
T H
D
BEAM WIDTH
W
B E
A M D
E P
T
BEAM WIDTH
W
MIN
6"
BEND, TYP
STD 135° TYP SLAB REINF
IN LOWER LAYER UON
SHOULD BE PLACED
CORNERS, BC REINF
BC REINF @ STIRRUP
BC OR B REINF, PLACE
INTERSECTING BEAM
(S) BARS
SHEAR REINF
BEAM SCHEDULE
INDICATED IN
REQUIRED IF
INTERIOR STIRRUPS,
IN LOWER LAYER UON
SHOULD BE PLACED
CORNERS, BC REINF
BC REINF @ STIRRUP
BC OR B REINF, PLACE
INTERSECTING BEAM
ACCEPTABLE STIRRUP CONFIGURATIONS
AS SHEAR REINF, SEE NOTE 2 FOR OTHER
CROSS TIES, SAME SIZE AND SPACING
BE PLACED IN UPPERMOST LAYER UON
STIRRUP CORNERS, TC REINF SHOULD
TC OR T REINF, PLACE TC REINF AT
BEAM SCHEDULE
INDICATED IN
REQUIRED IF
INTERIOR STIRRUPS,
(S) BARS
SHEAR REINF
STD 135° BEND, TYP
UPPERMOST LAYER UON
SHOULD BE PLACED IN
CORNERS, TC REINF
TC REINF AT STIRRUP
TC OR T REINF, PLACE
CLR OF BEAM, TYP
AT BEAM, PLACE 3"
LONGITUDINAL REINF
DISCONTINUE SLAB
CLR OF BEAM, TYP
AT BEAM, PLACE 3"
LONGITUDINAL REINF
DISCONTINUE SLAB
TYP SLAB REINF
BY ADJACENT SLAB
ACCEPTABLE STIRRUP CONFIGURATIONS
AS SHEAR REINF, SEE NOTE 2 FOR OTHER
CROSS TIES, SAME SIZE AND SPACING
FOR NOTES, SEE DETAIL 1 OF 3.
NOTE:
TYPICAL BEAM SECTION
LAP LENGTH x (1.3)
BEAM REINFORCEMENT
1" CLR
1" CLR
1" CLR
1" CLR
SIZE
DETAIL 3 OF 3
SIZE
TBCBTCTDW
SHEAR REINF
REMARKS
TC
BOTTOM REINF
TYPE
(NOTE 5)
NO.
LEFT SUPPORT
* TOP REINF AT
NOTES:
PLANS)
(SEE
NO.
BEAM
RIGHT SUPPORT
* TOP REINF AT
BARS
S
LEFT SUPPORT
SPACING FROM
5/19/2025iaw0330-066C.dgn
BEAM SCHEDULE
BLOCKOUT.
BEARING. WALL REINFORCEMENT SHALL NOT BE INTERRUPTED THROUGHOUT
FULL HEIGHT AND WIDTH OF BEAM TO PROVIDE A MINIMUM 8" SEAT FOR BEAM
WHERE BEAMS FRAME INTO CONCRETE WALLS, WALLS SHALL BE BLOCKED OUT6.
"NO." INDICATES NUMBER OF STIRRUPS OR TIES PER SET.5.
PROVIDE CLOSED TIES IN LIEU OF STIRRUPS AND CLOSURE BARS.
DETAIL. WHERE SHEAR REINFORCEMENT "TYPE" IS INDICATED AS "CLOSED TIE",
SHEAR REINFORCEMENT AND CLOSURES AS SHOWN IN BEAM REINFORCEMENT
WHERE SHEAR REINFORCEMENT "TYPE" IS INDICATED AS "STIRRUP", PROVIDE4.
B1 26" 30" 7#9 7#9 7#9 1 #5 STIRRUP3#9 ES @6" MAX
B2 16" 20" 4#8 4#8 4#8 1 #4 STIRRUP1#9 ES @6" MAX
B3 16" 24" 4#9 4#9 4#9 1 #5 STIRRUP1#9 ES @6" MAX
DEPTH OF BEAM (D) SHOWN IS MINIMUM DEPTH.
CONSTANT WITH THE SLOPE, THOSE BEAMS THAT CROSS THE SLOPE,
WHERE BEAMS SLOPE WITH THE FLOOR, DEPTH OF BEAM SHALL BE 3.
IS DRAWN, UNLESS OTHERWISE NOTED ON PLAN.
THE LEFT SIDE OR BOTTOM OF SHEET ON WHICH FRAMING PLAN
LEFT SUPPORT IS DESIGNATED AS THE SUPPORT CLOSEST TO2.
SUPPORT" OF ADJACENT BEAM.)
THE RIGHT SUPPORT IS CALLED-OUT AS "TOP REINFORCEMENT AT LEFT
REINFORCEMENT AT RIGHT SUPPORT" OF BEAM THAT IS CONTINUOUS OVER
* TOP REINFORCEMENT MAY BE CALLED-OUT TWICE IN SCHEDULE. (I.E. "TOP1.
C L
R
/2
" THAN 9"
W IDTH IS LARGER
FACE W HEN CURB
#5@ 12" PLACE EA
W IDTH EXCEEDS 9"
LOCATE EF W HEN
HEIGHT LESS THAN 12"
MIN 2 BARS FOR CURB
HEIGHT EXCEEDS 12".
#5@ 12" W HEN CURB
2 - #5 @ TOP &
ON PLAN
OF CURB AS NOTED
W IDTH AND HEIGHT
iaw0330-080.dgn 5/19/2025
CONCRETE CURB
0330-080 iaw0330-084.dgn 5/19/2025
0330-084
CONDUIT IN STRUCTURAL CONCRETE
0330-001
AS DIRECTED BY ENGINEER.
FOR SHORT SECTIONS OF ELEMENTS, SUCH AS W ALL PIERS, PLACE CONDUITS
CONDUITS PER .
AT EXIT OR ENTRY TO SLAB, REINFORCE OPENINGS CREATED BY M ULTIPLE
2.
1.
NOTES:
SLAB ON GRADE
W ALL OR ELEVATED SLAB
T
/3
T
/3 T
/3
T
T
/3
T
/3 T
/3
T
OF SLAB THICKNESS
CONDUITS IN MIDDLE THIRD
REINF, TYP
REINF, TYP OF W ALL OR SLAB THICKNESS
CONDUITS IN MIDDLE THIRD
C L
R
M
IN
GRADE GREATER THAN 16"
CONDUITS IN SLAB ON
ALTERNATE LOCATION FOR
CONDUIT AT MIN 6" OC
2" INSIDE DIA OR LESS
DIA, MIN, TYP
3 x OUTSIDE
DIA, MIN, TYP
3 x OUTSIDE
1. REM OVE CONCRETE OUT TO SOUND CONCRETE.
2.
3.
4.
5.
NOTES:
DAM AGED SURFACES AS NOTED
CONCRETE FINISH, REPAIR ROUGH OR
CONCRETE TO M ATCH EXISTING ADJACENT
FINISH SLAB OR W ALL UNDER REM OVED
iaw0330-143.dgn 5/19/2025
CONCRETE DEM OLITION
0330-143
TO M ATCH APPEARANCE OF ADJACENT CONCRETE SURFACES.
FILL DEFECTIVE AREA W ITH AN APPROVED PREPACKAGED REPAIR M ATERIAL
TECHNIQUES.
BONDING AGENT M ANUFACTURER AND REPAIR M ATERIAL M ANUFACTURER ON
CURING PROCEDURES REQUIRED BY M ATERIAL M ANUFACTURERS. CONSULT W ITH
DEM ONSTRATE METHODS FOR REPAIR USING ACTUAL M ATERIALS, METHODS, AND
REPAIR M ATERIAL.
USE APPROVED BONDING AGENT ON SURFACES TO BE PATCHED PRIOR TO PLACING
EDGES.
REQUIRED, M AKE EDGES PERPENDICULAR TO THE SURFACE. DO NOT FEATHER
IF CHIPPING INTO THE SURFACE OF THE EXISTING SLAB OR W ALL TO REM AIN IS
CONCRETE SURFACES TO REM AIN
DAM AGE EXISTING ADJACENT
REM OVED, USE CARE NOT TO
EXISTING CONCRETE TO BE
SAW -CUT AND CHIP TO REM OVE
TO REM AIN
EXISTING CONCRETE
PATCH W ITH REPAIR M ATERIAL
TO REM AIN, CLEAN AND SOAK, AND
BELOW TOP OF EXISTING CONCRETE
EQUIPMENT ANCHORS TO 1 1/2" MIN
EXISTING REINFORCEMENT AND
1 1/2" DEEP, CHIP, AND REM OVE
CORE DRILL 2" DIAMETER HOLE,
iaw0421-002.dgn 5/19/2025
0421-002
1. EXTEND BASE FLASHING 6" HIGHER THAN M ORTAR BLOCK M ATERIAL.
2. SEE STRUCT DW GS FOR LOCATIONS OF CURBS.
@ 24" OC
W EEP VENTS
SEE CIVIL DW GS
FINISH GRADE,
1'-4" OR 1'-8"
SST EDGE DRIP
NOTES:
TYPICAL BASE OF W ALL DETAIL
04 21 13.13
SEE SECTION
M ORTAR BLOCK,
DW GS FOR REINFORCING
CM U W ALL, SEE STRUCT
BARRIER
AIR & W ATER
BAR AND SEALANT
TERMINATION
INSULATION
RIGID
AIR SPACE
SST EDGE DRIP
FLASHING W /
BASE OF W ALL
VENEER
BRICK
NOTE 2)
(SEE
CURB
CONC
OR 8"
COURSE
CM U
M ORTAR
OR
GROUT
SLOPED
INSUL
R-15 FACED
LAP
L
A P
NOTES:
INTERIOR CORNEREXTERIOR CORNER
FAR FACE
HOOK AT
STANDARD 90°
VERTS
2 TYP
iaw0422-001A.dgn 5/19/2025
0422-001
W ALL CORNERS (SINGLE & DOUBLE M AT)
SINGLE M AT PLAN FOR HORIZONTAL BARS
3 TYP VERTS
BAR SIZE & SPACING
M ATCH TYP HORIZ
CORNER BARS
0422-003
REINFORCED M ASONRY
DETAILS .
AT OPENINGS, CONTROL JOINTS, OR CORNERS LESS THAN 6'-0" IN LENGTH, SEE2.
UNLESS NOTED OTHERW ISE.
LAP=48 BAR DIAMETERS, BUT NOT LESS THAN 2'-0" FOR HORIZONTAL BARS1.
iaw0422-003A.dgn 5/19/2025
0422-003
CM U OPENING REINFORCEMENT
"W "
H
90°
HOOK
8" LINTEL SECTION
135°
HOOK
12" LINTEL SECTION
SCHEDULE
"A" BARS SEE
REINFORCEMENT
HORIZONTAL
LINTEL BOTTOM
8" CM U W ALL
SEE SCHEDULE
AS REQD
STIRRUPS
"A" BARS
LENGTH AS
STIRRUP, SAME
BAR AT TOP OF
HORIZONTAL
TYP W ALL
LINTEL BLOCK
SCHEDULE
DEPTH, SEE
LINTEL
NOTE 5
REINFORCEMENT,
ADDL HORIZONTAL
REINFORCEMENT
VERTICAL
TYP CM U W ALL
12" CM U W ALL
SEE SCHEDULE
AS REQD
STIRRUPS
LENGTH AS "A" BARS
STIRRUP, SAME
BAR AT TOP OF
HORIZONTAL
TYP W ALL
BARS SEE SCHEDULE
REINFORCEMENT "A"
HORIZONTAL
LINTEL BOTTOM
W IDTH W IDTH
JAMBJAMB
BOND BEAM
"B" BARS IN
IN 12" W ALLS)
(1 EF) PER CELL
W ALLS, TW O
PER CELL IN 8"
(ONE CENTERED
SIDE, SEE NOTE 2
"C" BARS EACH SEE NOTE 3
LINTEL BLOCK
"A" BARS IN
BOUNDARY AREA
W ITHIN SHADED
GROUT ALL CELLS
L
IN
T E
L
D E
P T iaw0422-003B.dgn 5/19/2025
0422-003
CM U OPENING REINFORCEMENT
5.
W
<2'-8" 8"
16"
24"
32"
48"
8"
8"
16"
24"
24"
8" W ALLS
#3@ 8"
#3@ 16"
#3@ 24"
>2'-8"<4'-0"
>4'-0"<6'-0"
>6'-0"<8'-0"
>8'-0"<10'-0"
W
<2'-8" 8"
16"
24"
32"
48"
8"
8"
16"
24"
24"
#3@ 8"
#3@ 16"
#3@ 24"
>2'-8"<4'-0"
>4'-0"<6'-0"
>6'-0"<8'-0"
>8'-0"<10'-0"
12" W ALLS
1.
2.
3.
4.
NOTES:
CM U OPENING REINFORCEMENT SCHEDULE
EXTEND REINFORCEMENT CONTINUOUS TO 2'-8" BEYOND FURTHEST OPENING.
SIDE OF THE OPENINGS. W HERE THERE IS LESS THAN 8'-0" BETW EEN ADJACENT OPENINGS, "A" AND "B" BARS SHALL EXTEND 48 BAR DIAMETERS, BUT NOT LESS THAN 2'-0" EACH
W ALL SECTIONS.
FOR BAR SIZES, M ATCH TYPICAL W ALL REINFORCEMENT AS SHOW N ON THE BUILDING
DEPTH
LINTEL
SIZE, SPG
STIRRUP
BARS
"A"
BARS
"B"
BARS
"C"
W IDTH
JAMB
DEPTH
LINTEL
SIZE, SPG
STIRRUP
BARS
"A"
BARS
"B"
BARS
"C"
W IDTH
JAMB
ON THE DRAW INGS.
USE BAR QUANTITIES AND SIZES GIVEN IN LINTEL SCHEDULE UNLESS OTHERW ISE NOTED
W ALL HORIZONTAL REINFORCEMENT.
HORIZONTAL REINFORCEMENT AT 12" FROM BOTTOM OF LINTEL. M ATCH SIZE OF TYPICAL
FOR LINTEL DEPTHS EQUAL TO OR GREATER THAN 48" PROVIDE ADDITIONAL LAYER OF
HEIGHT.
OF OPENING EXCEPT THAT W HEN "H" OR "W " EXCEEDS 2'-0", "C" BARS SHALL EXTEND FULL
EXTEND "C" BARS 48 BAR DIAMETERS, BUT NOT LESS THAN 2'-0" BEYOND TOP AND BOTTOM
DETAIL 2 OF 2
iaw0422-004B.dgn 5/19/2025
0422-004
INTERMEDIATE REINFORCED M ASONRY SHEAR W ALL
1.
2.
3.
5.
6.
7.
8.
NOTES: ELEVATION
0422-003
0422-003
0422-001
4.
REINF
VERT
TYP
NOTE 2
SEE
CONCRETE
TOP OF
SEE NOTE 4
DOW ELS,
REINF SEE
OPENING
CM U
SEE NOTE 2
LAP, TYP,
72 BAR DIA
COLUM N, SEE NOTE 7
W ALL PIER OR
HORIZONTAL JOINT REINFORCEMENT SPLICE = 1'-4".
DETAIL .
0422-006
0422-005
AND .
NOTE 8
SEE SEE NOTE 2
DIA LAP,
48 BAR
OC M AX
AT 16"
REINF
JOINT
HORIZ
TYP
LEVELS
FLOOR
ROOF AND
AT ALL
W ALL AND
AT TOP OF
HORIZ BARS
2 TYP
IN FIRST COURSE
HORIZ JOINT REINF
STRUCTURAL NOTES.
FACILITY. FOR MINIM UM REINFORCEMENT REQUIREMENTS, SEE GENERAL
FOR TYPICAL W ALL REINFORCEMENT, SEE W ALL SECTIONS AND DETAILS FOR EACH
LAP ALL OTHER VERTICAL BARS 72 BAR DIAMETERS.
LAP VERTICAL REINFORCEMENT W ITH W ALL DOW ELS 48 BAR DIAMETERS (2'-0" MIN),
PROVIDE DOW EL BARS IN FOUNDATION TO M ATCH ALL VERTICAL REINFORCEMENT.
FOR ADDED REINFORCEMENT AT W ALL INTERSECTIONS AND CORNERS, SEE .
GROUT EACH SIDE OF OPENING AS NOTED IN TYPICAL OPENING REINFORCEMENT
FOR HORIZONTAL REINFORCEMENT AT OPENINGS SEE PIER AND COLUM N DETAILS
DO NOT PLACE VERTICAL CONDUIT IN THE SAME CELL AS VERTICAL REINFORCEMENT.
iaw0422-005A.dgn 5/19/2025
0422-005
CM U W ALL PIER
1.
2.
3.
W HERE PIERS ARE CENTERED BELOW BEAM BEARING, REDUCE TIE SPACING TO 8".
NOTES:
0422-006
OPENING
OPENING OPENING2'-8" TO 4'-0"
(SEE NOTE 3)
2'-8" TO 4'-0"
(SEE NOTE 3)
CORNER PLAN
8" CM U W ALL
INTERIOR PLAN
0422-001
0422-003
0422-003
BOND BEAM
TIES IN
#3@ 16"
SEE SIM
REINFORCEMENT,
TYPICAL CORNER
TYP EA END OF PIER
"C" BARS PER HOOK
90°
HOOK
90°
SOLID GROUT PIERS FULL W ALL HEIGHT.
IN BOND BEAM
#3@ 16" TIES
TYP
PER
"C" BARS
FOR 8" CM U W ALL PIERS 2'-0" AND LESS, SEE W ALL COLUM N DETAIL
iaw0422-006A.dgn 5/19/2025
0422-006
CM U W ALL COLUM N
2'-0" OR LESSOPENING
180°
HOOK
8" CM U W ALL
CORNER PLAN
NOTE:
INTERIOR PLAN
0422-001
0422-003
TYP
PER
"C" BARS
BEAM BLOCK
IN BOND
#3@ 8"
OPENING OPENING
0422-003
HOOK
180°
2'-0" OR LESS
BEAM BLOCK
IN BOND
#3@ 8"1/2" CLR
TYP
GROUT W ALL COLUM NS FULL W ALL HEIGHT.
(4 BARS MIN IN COLUM N)
TYP EACH END OF PIER
"C" BARS PER SIM
SEE SIM
REINFORCEMENT,
TYP CORNER
iaw0422-031.dgn 5/19/2025
CM U CONTROL JOINT
0422-031
NOTE:
JOINT
PREFABRICATED
ENLARGED DETAIL
CM U BLOCK
BOND BREAKER TAPE
SEALANT
CM U BLOCK
/8
/8
3/8"
STRAIGHT W ALL
T-W ALL
IN TW O CELLS
REINFORCEMENT
VERTICAL
PROVIDE TYPICAL
SEE ENLARGED DETAIL
8" CM U W ALL
THROUGH JOINT
ROOF AND FLOOR LEVELS
HORIZONTAL BARS AT ALL
EXCEPT CONTINUE
REINFORCEMENT AT JOINT,
STOP TYPICAL HORIZONTAL
CENTERED ON JOINT
REINFORCEMENT IN CELL
PROVIDE TYPICAL VERTICAL
DETAIL, TYP
SEE ENLARGED
CONTROL JOINT
PREFABRICATED
BACK-UP ROD
SIDE OF JOINT
IN 2 CELLS EACH
REINFORCEMENT
VERTICAL
PROVIDE TYPICAL
8" CM U W ALL
FOR M ASONRY CONTROL JOINT LOCATIONS SEE PLANS.2.
12" CM U W ALL W ITH 2 LAYERS OF REINFORCEMENT IS SIMILAR.1.
/4
/4
T Y
P
MIN
M
IN
/2
M
IN
M
IN
TYP TYP
t"
S E
E t"
S E
E
/4
C O
L
M
IN
C O
L
/4
" COL + 5"
COL + 5" MIN
C O
L
COL + 1"
1 1/2" 1 1/2" iaw0512-001.dgn 5/19/2025
COLUM N BASE - STEEL
0512-001
THICKNESSES OVER 3/4". ALL W ELDS SHALL BE SINGLE-PASS W ELDS.
1/2", 1/4" FILLET FOR THICKNESSES OVER 1/2" TO 3/4", AND 5/16" FILLET FOR M ATERIAL
W ELD SIZE SHALL BE 3/16" FILLET FOR M ATERIAL THICKNESSES UP TO AND INCLUDING
W ELD SIZE SHALL BE DETERMINED BY THE THICKEST MEMBER JOINED; MINIM UM
ON COLUM N.
LEVELING NUTS AND 1'-0" MINIM UM EMBED AND BASEPLATES SHALL BE CENTERED
UNLESS OTHERW ISE NOTED, ANCHOR BOLTS SHALL BE 3/4" DIA x REQUIRED W ITH
2.
1.
(3 /4
U
N O
P L
A N
S
(3 /4
U
N O
P L
A N
S
NOTE 2
SEE
NOTE 2
SEE
T Y
P
M
IN
,IS
G
R E
A T
E R
W H
IC
H
E V
E R
A B
S P
G
C O
L
O
R
T Y
P
M
IN
6" MIN
COL + 1",
T Y
P
M
IN
PLAN PLAN
PLANPLAN
ELEVATION
TYPE A
ELEVATION
TYPE B
NOTES:
BOLTS
ANCHOR
W / 3/4" RADIUS TOOL
AS SPECD, ROUND CORNERS
1 1/2" NON-SHRINK GROUT
COLUM N
W OR HSS
BOLTS
ANCHOR
COLUM N
W OR HSS
W COLUM NW COLUM N
COLUM N
4" FOR W 14
W 12 COLUM N,
3 1/2" FOR
W 10 COLUM N,
2 1/2" FOR
COLUM N
HSS
COLUM N
HSS
16-18
12-15
8-10
4 1
NOTES:
L E
N G
T H
S E
E S
C H
E D
2 1/2"
COM MENTS
30 8
33 9
36 10
7/8"
7/8"
7/8"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
3/4"
1'-8 1/2"
1'-5 1/2"
1'-2 1/2"
0'-11 1/2"
0'-8 1/2"
0'-5 1/2"
0'-3"
0'-2 1/2"
2'-6"
2'-3"
2'-0"
ANGLE THK = 3/8"
ANGLE THK = 3/8"
ANGLE THK = 3/8"
STD
GAGE
ANGLE, TYP UON
5/16" x REQD DOUBLE
1 1/2" 1 1/2"
2 1/2" M AX
MINMIN
CL BOLTS
T&B
MIN,
1 1/4"
FOR 7/8" DIA BOLTS)
1" MIN (1 1/8" MIN
A325N BOLTS, TYP UON
DEPTH, INCHES
NOMINAL BEAM
BOLTS
ROW S OF
BOLTS)
FOR 7/8" DIA
FLANGE (1 5/16"
COPED BEAM
1 1/4" MIN AT
INSTALLATION
REQD FOR PROPER
COPE FLANGE AS
INCHES
BOLT DIA,
LENGTH, INCHES
DOUBLE ANGLE,
iaw0512-020.dgn 5/19/2025
TYPICAL BEAM CONNECTION - STEEL
0512-020
NOTE 3
SEE
OR COLUM N
STEEL BEAM
SUPPORTING
DIMENSION SHALL BE 3" UNLESS OTHERW ISE REQUIRED FOR PROPER FABRICATION.
CONNECTIONS W HEN REQUIRED OR USED.
PROVIDE ADDITIONAL 1 1/2" LENGTH TO DOUBLE ANGLE FOR STAGGERED BOLT
SPECIFICALLY NOTED OTHERW ISE OR APPROVED IN W RITING BY THE ENGINEER.
ALL BEAM FRAMING CONNECTIONS SHALL CONFORM TO THIS DETAIL UNLESS
3.
2.
1.
STEEL BEAM
SUPPORTED
6"x4"x5/16"
6"x4"x5/16"
W EB
SUPPORTED BEAM
OF 2 BOLTS AT
SHALL HAVE 1 ROW
6x4x5/16, 6" LEG
/4
1/4
2"
PLAN
ELEVATION
NOTE:
BEAM W / FIRESAFING
FILL VOID AROUND
CLOSURE PLATE
SEE FRAMING PLANS
STEEL BEAM,
BEAM ELEVATION)
TO M ATCH TOP OF
(TOP OF ANGLE
SUPPORT ANGLE
DECKING LEDGER
0531-001
0558-002
SEAT BLOCKOUT
OF M ASONRY ACROSS
CONTINUE FACE SHELLS
M A
X
OR SET BEAMS BEFORE COMPLETING W ALL ABOVE.
PROVIDE BLOCKOUT DEPTH AS REQUIRED FOR SETTING BEAMS, (BEAM DEPTH + 6") MIN,
SEE NOTE 1
BLOCKOUT DEPTH,
ON SINGLE BEAM SEAT)
(5'-4" MIN LENGTH CENTERED
AND BELOW BLOCKOUT
CONTINUOUS (#5 MIN) ABOVE
HORIZONTAL BARS
8" BOND BEAM W / 2 TYPNON-SHRINK GROUT
BEARING W ALL
M ASONRY EXTERIOR
iaw0512-067.dgn 5/19/2025
BEAM SEAT/EXTERIOR W ALL - STEEL
0512-067
W ASHERS
NUTS & 2 - HEAVY
BOLTS W / LEVELING
2 - 3/4"x0'-10" ANCHOR
PL 3/4x4
CL W ALL & BEARING
/2
T Y
P T
Y P
C L
R
HOLES
STANDARD OVERSIZED
SIDE OF BLOCKOUT
GROUT CELL EACH
1/4
1.
2.
5"
VARIES2 1/2"
2 3/4"
ALUMINUM
/2
/2
/2
2 1/2"
10 7 1/2"
7-8-9
5-6 1 3"
AL 4x4x5/16"
NOTES:
2 1/2" DIMENSION TYPICAL EXCEPT 2" FOR 4" BEAM.
NOTE:
BOLTS AS SPECD
3/4" DIA SST
F L
A N
G E
C O
P E
D B
E A
M
/4 M
IN
BEAM W EB
TO ENCLOSED
PROVIDE ADDL BOLT
1 ROW CONN ONLY,
AL 6x4x3/8", DEPTH, INCHES
NOMINAL BEAM
BOLTS
ROW S OF
OF ANGLE
LENGTH
W EB.
BOLTS TO ENCLOSED
EQUAL TO NUMBER OF
NUMBER OF ROW S IS
ON FRAMING PLANS.
DETAILED OTHERW ISE
SCHEDULE UNLESS
SHALL CONFORM TO
ALL FRAMING CONNECTIONS
iaw0514-020.dgn 5/19/2025
TYPICAL BEAM CONNECTION - ALUMINUM
0514-020 iaw0531-001.dgn 5/19/2025
DECKING LEDGER SUPPORT ANGLE
0531-001
STEEL DECKING
/4
/2
/2
1/2" CLR
1/2" CLR
DECKING AT ANGLE TO W ALL
DECKING NORM AL TO W ALL
STEEL DECKING
3"
NOTED
W ELD AS
AT 2'-0" ON CENTER
W ITH 5/8" ANCHOR BOLTS
L 3x3x1/4" x CONTINUOUS
M ASONRY W ALL
NOTED
W ELD AS
SEE PLANS
ROOF SLOPE,
PLANS
TST EL, SEE
W ORK POINT
SEE PLANS
TST EL,
THROUGH ALL CONTROL JOINTS
BAR, CONTINUOUS, INCLUDING
2 - TYPICAL HORIZONTAL
(BEND PLATE TO M ATCH SLOPE)
ANCHOR BOLTS @ 2'-0" OC
BENT PL 1/4 x CONT W / 5/8" iaw0531-021A.dgn 5/19/2025
0531-021
DETAIL 1 OF 2
ROOF DECK OPENING
O P
E N
IN
G
L E
N G
T H
CLOSURE
CLOSURE
6'-0" < W
L 4x3x1/4 (LLV)
S U
P P
O R
T
S U
P P
O R
T
'W '
'L
TYP
3/16
OPENING CLOSURE
L 3x3x1/4
NA
2'-0" < W < 4'-0"
4'-0" < W < 6'-0"
7'-6" < L
L 5x3x1/4 (LLV)
SUPPORT
NA
6'-0" < L < 7'-6"
DECK SPAN
L 4x3x1/4 (LLV)L < 6'-0"
M E
T A
L D
E C
K S
P A
N
0531-001
0531-002
W IDTH
OPENING
OR
DECK/W ALL CONN,
OPENINGS 2'-1" TO 6'-0"
PLAN
NOTES:
REFER TO SPECIFICATIONS FOR SM ALLER DECK OPENING REINFORCEMENT.2.
ATTACHMENTS.
NOT FALL AT SUPPORTS PARALLEL TO DECK SPAN, PROVIDE FILLER PIECES FOR EQUAL
SUPPORTS PARALLEL TO SPAN @ 6" ON CENTER. W HERE VALLEY OF DECKING DOES
SPECIFIED FASTENERS AT EACH VALLEY OF DECKING. ATTACH METAL DECKING TO
ATTACH METAL DECKING TO ALL SUPPORTS PERPENDICULAR TO DECKING SPAN W ITH1.
OR BEAM
JOIST
CL METAL
CONNECTION
BEAM SUPPORT
SEE JOIST OR
CONNECTION
SUPPORT
SEE W ALL
W ALL, TYP
iaw0531-021B.dgn 5/19/2025
0531-021
DETAIL 2 OF 2
ROOF DECK OPENING
D E
C K
S P
A N
TYP
3/16
3/16 3/16
'W ' 'W ' 'W '
OPENINGS 1'-0" TO 2'-0"
3/16
24" M AX
12" TO
0531-001
JOIST OR BEAM
OF METAL
TOP CHORD
/2
END
TYP EA
FRAMING CONNECTIONS
SECTION
PLAN
JOIST OR BEAM SUPPORT W ALL SUPPORT
AS REQD
COPE ANGLE
SEE SCHED
ANGLE,
SUPPORT
@ 5" GA, , SIM
DIA CONC ANCHORS
LONG W / 2 - 5/8"
L 5x3x1/4x0'-8"
TYP
L2x2x3/16", SEE NOTE 1
DECKING ATTACHMENT,
DECK
METAL ROOF
L2x2x3/16", TYP
PIPE BOLLARD
0550-342
8"
8"
4"DIA STL PIPE
1/4" PJF
x x x x x x
FILL W / CONC
4"
6 1/2" 6"
3/16 3/16
2 1/2"
SLOTTED HOLES
W / 11/16x2 1/2"
3/8" AL BOT PLATE
GROUT
NON-SHRINK
NOTE 7, TYP
SLOTTED HOLES
W / 11/16"x2 1/2"
3/8" AL BOT PLATE
4"
/2
PLAN
SECTION
BOTTOM CONNECTION
NOTES:
iaw0551-001A.dgn 5/19/2025
0551-001
STAIR DETAILS - ALUMINUM
DETAIL 1 OF 4
STAIR SLOPE
VARIES W /
6"
TYP
SEE DW GS,
RISERS,
UNIFORM
VARIES
PL 3/8x3x
END AL
DETAIL
RISER PLATE
SEE PARTIAL
RISER PLATE DETAIL.
3 3/4" M AXIM UM. FOR STAIRS W ITH PICKET RAILING EXTEND RISER PLATE PER FULL
CLEARANCE BETW EEN TOP OF RISER PLATE AND BOTTOM OF TREAD TO BE
FOR RISER PLATE SEE PARTIAL RISER PLATE DETAIL UNLESS NOTED OTHERW ISE.7.
FIELD VERIFY DIMENSIONS AND ELEVATIONS PRIOR TO FABRICATION.6.
ALL FASTENERS SHALL BE STAINLESS STEEL.5.
STAIR M ANUFACTURER TO COORDINATE BOLTED TREADS AND RAILING CONNECTIONS.4.
STAIR RAILING NOT SHOW N.3.
OTHERW ISE NOTED ON PLANS.
AMERICAN STANDARD C12x7.41 ALUMINUM STRINGERS TYPICAL EXCEPT W HERE2.
W ITH CONCRETE PER SPECIFICATIONS.
PROVIDE PROTECTION FOR DISSIMILAR METALS AND FOR ALUMINUM IN CONTACT1.
CONC ANCHORS
(2) 5/8" SST
iaw0551-001B.dgn 5/19/2025
3/16
G
11"
TYP
SEAL TYP
TREAD,
W / T.O. GRATING
TREAD FLUSH
INSTALL FIRST
TOP CONNECTION - ALUMINUM
GRATING
GS-2, SIM
PLATFORM
EDGE OF
11" LANDING
T Y P
EXCEPT AS NOTED
SIM
CONN
2 - ROW BOLTED
TYP
SEE DW GS,
RISERS,
UNIFORM
0514-020
STRINGER
STAIR
SEE PLANS
W IDTH
TYP
TREAD,
TYP
1" OVERLAP,
LANDING CONNECTION - ALUMINUM
IN STRINGER
SLOTTED HOLES
HORIZONTALLY
SHORT
NOTE 7, TYP
TYP
TREADS,
GRATING
NOSING, TYP
W / T.O. GRATING
TREAD FLUSH
INSTALL FIRST
GS-2, SIM
SEE PLANS
METAL BEAM,
NEAR FACE
SINGLE AL ANGLE
SEE LANDING CONNECTION.
FOR NOTES NOT SHOW N
NOTE:
DETAIL 2 OF 4
iaw0551-001D.dgn 5/19/2025
DETAIL 3 OF 4
2'-3" OR LESS
2'-9" OR LESS
3'-3" OR LESS
4'-7" OR LESS
1" x 3/16"
1 1/4" x 3/16"
1 1/2" x 3/16"
1 3/4" x 3/16"
TREAD BEARING BARS
NOTED ON PLANS
SEE NOTE 7
RISER PLATE,TREAD
GRATING OTHERW ISE
3'-0" UNLESS
W ALL UON
CLR FROM
SEE NOTE 7
M A
X
NOTED ON PLANS
OTHERW ISE
1'-0" MIN UNLESS
2" 1 1/2"
/4
STAIR SLOPE
VARIES W /
W IDTH
STAIRW AY
TREAD
ALUMINUM
1/2"
STAIR TREADS
BOTTOM CLOSURE PLATE
STRINGER
M OUNTING PL
AND STRINGER
CLEAR GROUT
BENT PL TO
COPE 3/16"
3/16" AL BENT PL
iaw0551-001E.dgn 5/19/2025
DETAIL 4 OF 4
6" OC
IN 1/4" DIA HOLE AT
TEK SCREW , 1" LONG
SST SELF-TAPPING
PARTIAL RISER PLATE
END M AX 12" OC
6" FROM EACH
CONC ANCHORS,
5/8" DIA SST
3/16" AL BENT PL
6" OC
IN 1/4" DIA HOLE AT
TEK SCREW , 1" LONG
SST SELF-TAPPING
M A
X
/4
M A
X
/4
M A
X
/8
FULL RISER PLATE
BENT PL
3/16" AL
8 GAGE AL PLATE
11 GAGE AL PLATE
END M AX 12" OC
FROM EACH
ANCHORS, 6"
5/8" SST CONC
TYP
HANDRAIL
AS REQD TO
1 1/2"
4 1/2"
4 1/2"
1 1/2" 3"
W ORK POINT
1/ 4"
3 1/2"1" T Y P
1/ 4"
3/16
3/16
3/16
3/16
2 - 3/4" DIA SST BOLTS
NOTE:
3/8" GUSSET PL
0514-056
STRINGERS
FULLY SEAT
AT ACCESS TO LANDING
GS-1 GRATING SUPPORT
M ASONRY W ALL
CONCRETE OR
OF LANDING
BEAM EACH SIDE
AL CLOSURE
@ 9" GA EW
MIN EMBEDMENT
ANCHORS W / 5 1/2"
DIA SST ADHESIVE
AL PL 5/8x12x12 W / 4 - 3/4" iaw0551-003.dgn 5/19/2025
STAIR LANDING SUPPORT - ALUMINUM
0551-003
OMIT HORIZ SLOTTED HOLES
AL 3 1/2x2 1/2x1/4 (LLV)
SST BOLTS
W / 2 - 3/4" DIA
SUPPORT BEAM
STRINGER TO
BOLT EACH
SUPPORT BEAM
CONT OVER
STAIR STRINGER
SST BOLTS
W / 2 - 3/4" DIA
CTRD ON BEAM
3/8" AL GUSSET PL
SST BOLT
W / 1 - 3/4" DIA
CTR OF BRACE
SPACER PL @
AL PL 3/8x3x3
W ALL SEE SIM,
FOR CONNECTION AT
AL I 8x6.35 SUPPORT BEAM, PER SPECIFICATIONS.
CONTACT W ITH CONCRETE
FOR ALUMINUM IN
PROVIDE PROTECTION
0551-101 iaw0551-101G.dgn 5/19/2025
NTS
M
IN
M
A X
ELEVATION SECTION
2'-0"
0552-001
7" MIN
10" M AX
SURFACE
W ALKING
3'-6" ABOVE
VERIFY
1'-2" MIN, FIELD
LADDER - ALUMINUM - PRE-ENGINEERED
PIPE W ITH EXTENSION TYPE 'E'
NOTES:
EACH RAIL
ANCHORS, TYP
4 SST CONCRETE
CONCRETE W ITH
CONN, SECURE TO
EXTRUDED AL BASE
CM U, TYP
TO CONCRETE OR
ANCHOR AT CONN
5/8" SST CONCRETE
SPECIFIED, TYP
BRACKET AS
EXTRUDED AL
SURFACE
W ALKING
TOP OF
NOTE 2, TYP
MIN, SEE
RUNG, 1" W IDE
EXTRUDED AL
AL PIPE, MIN, TYP
1 1/2" DIA SCHED 40
E
IG
H
T
H
MIN, TYP
M AX, 10"
@ 1'-0" OC
SPACED
EQUALLY
SURFACE
W ALKING
TOP OF
SEE NOTE 4 SEE NOTE 4
1'-6" UON
SEE NOTE 3
FOR H GREATER THAN 24'-0" PROVIDE SAFETY CLIMB DEVICE.4.
INCREASE W IDTH OF FLARE TO 2'-6" W HEN LADDER SAFETY CLIMB DEVICE IS USED.3.
PROVIDE CORRUGATED, KNURLED OR DIMPLED SURFACE ON TOP OF RUNG.2.
PROVIDE PROTECTION FOR ALUMINUM IN CONTACT W ITH CONCRETE PER SPECIFICATIONS.1.
INDICATED
GATE W HERE
SELF CLOSING
0551-141 iaw0551-141C.dgn 2025\05\21
NTS
3"
TYP
3/16
M A
X
T.O. ROOF
T.O. GRATING
M
IN
M A
X
M
IN
MAX, 10" MIN, TYP
SPACING @ 1'-0" OC
EQUAL TO RUNG
DETAIL, TYP
RUNGS, SEE RUNG
BAR 1" DIA STL
GRATING CONN DETAIL
1" STL GRATING, SEE
STL L5x3x1/4 LLV
7" MIN, 10" MAX
LADDER - STEEL - FLAT BAR UP AND OVER - TYPE 'C'
NOTES:
SEE NOTE 2
OR CMU
AT CONNECTION TO CONCRETE
W/ 4 1/2" MIN EMBEDMENT
5/8" SST CONCRETE ANCHORS
H E
IG
H T
H
SEE FLARE DETAIL
FLARE LADDER RAILS,
10" MIN, TYP
@ 1'-0" OC MAX,
EQUALLY SPACED
EACH RAIL, SEE NOTE 2
AT TOP CONNECTION, TYP
DIAGONAL BRACKETS
TYP
CJP,
3" CLR MIN
SEE NOTE 3
FOR H GREATER THAN 24'-0" PROVIDE SAFETY CLIMB DEVICE.3.
LADDER EXTENDS TO SLAB BELOW.
5/8" SST CONCRETE ANCHORS. DIAGONAL BRACKET NOT REQUIRED IF BASE OF
AT INTERIOR DRY AREAS, EXTEND RAILS AND BEND 3" AT FLOOR. SECURE WITH2.
HOT DIP GALVANIZE STEEL AFTER FABRICATION, UNLESS OTHERWISE NOTED.1.
EACH RAIL
@ 8'-0" OC MAX, TYP
BRACKETS T&B AND
3/8" x 2 1/2"
STL BAR
RECEIVE RUNGS
RAILS, PUNCH TO
STL FB 3/8" x 2 1/2" LADDER
SHARP EDGE AT TOP, TYP
PL 3/8" x 2 1/2", REMOVE
STL STIFFENER
0551-151.dgn 5/28/2025
SHIPS LADDER
0551-151
NOTES:
ROOF HATCH
TYP
G
3/16
'-0 " M
A X
2'-0" W IDE AL TREADS
SIM
STRINGER TOP
CONN
SIM
1" NOSING
TYP
3/16
3/16
2-6
2-6
* 6" M AX
SEE PLANS
LANDING EL
AL GRATING
SIM
0551-001
0553-001
0552-001
0551-001
0551-001
SIM
LANDING CONN
Q
U A
L R
IS
E
R S
M
A X
E Q
U A L S
P G
@ 2'-0" SPG
AL C10x10.4 STRINGERS
ANGLES EA SIDE
GRATING SUPPORT
AL L2x2x1/4
REQUIRED TO CLEAR.
* VERIFY MINIM UM AS
9"
HANDRAIL
STD 3 - RAIL
TO
TRANSITION
M AKE SM OOTH
CONC. PLANK
12" PRECAST
HANDRAIL
STAIR
2 - RAIL AL
PLATFORM
SUPPORT
GRATING
TOPPING
3" GROUT
AND CURB
ROOF HATCH
U S
E W
IT
H
C U
R B
2" 2"
TYP
NOTES:
1.
2.
4"
3/16
3/4"
3/8"
FASTEN RAIL TO W ALL FLANGE PER M ANUFACTURER'S RECOM MENDATIONS.
3.
R A
IL
IN
G
W ALL FLANGE TO BE M OUNTED TO W ALL W ITH (2) 3/8" DIA SST W EDGE ANCHORS.
T
Y P
M
IN
T
Y P
DETAIL 1 OF 4
M A
X
/4
T
Y P
POST, TYP
CL
@ 6'-0" M AX
EQUAL SPACES
SEE PLANS
FOR W IDTH
M AX
6'-0"
T Y
P
C L
P O
S T iaw0552-001A.dgn 5/19/2025
POST BEYOND
THE PLANS, SEE DETAILS
W HEN INDICATED ON
CONC RAILING CURB
6" HIGH x 10" W IDESEE DW GS
ANCHORAGE,
FOR TYPE OF
ELEVATION
HINGE
PLAN
ELEVATION
RAIL TERMINAL
PLAN
PL 3/8x2
R
A
IL
IN
G
RAILING - 2 RAIL - ALUMINUM
SEE DETAIL BELOW
RAIL TERMINAL, TYP,
BOARD
TOE
CONCRETE
EDGE OF
END OF RAIL
THREAD
W ITH 1/2"
1 1/4" STUD
3/8" DIA x
W ASHER
NYLON
1/8" THICK
PER SPECS
GATE SYSTEM
PER SPECS
W ALL FLANGE
TYP PER SPECS
TOE BOARD,
PER SPECS
RAILING SYSTEM
SPECIFICATIONS. ANODIZE FINISH AFTER ALL W ELDING PER SPECIFICATIONS.
AT CONTRACTOR'S OPTION FABRICATE HINGES OR PROVIDE OTHER HINGES PER
RAILING SECTION
CLR
RAILING DETAIL W ITHOUT LANDING
C L
R
BRACKET
NOTES:
DETAIL 2 OF 4
1.
2.
4"
1'-0"
EQUAL SPACING
11"
1 1/2"
/2
HANDRAIL
HANDRAIL
iaw0552-001D.dgn 5/19/2025
CONC STAIRS SIM
METAL STRINGER SHOW N,
MIN
SEE DETAIL BELOW
W HERE NO LANDING REQD
OF INTERMEDIATE LANDING,
LOCATE POST AT EACH END
5'-0" M AX
PROVIDE TOE BOARD AT LANDING W HERE REQUIRED.
ANCHORAGE DETAIL
SEE RAILING POST
SYSTEM
RAILING
GUARD
RETURN ENDS OF HANDRAIL TO GUARD AT BOTH ENDS.
HANDRAIL SEE NOTE 2
FOR RETURN AT
M
IN
M
IN
MIN
RAILING - 2 RAIL STAIR - ALUMINUM (IBC)
6"
PER SPECS
SYSTEM
RAILING
6 1/4"
/2
DETAIL 3 OF 4
MIN
8"
M
IN5
iaw0552-001XA.dgn 5/19/2025
NOT BE PERMITTED
OTHER REASON W ILL
POST ALIGNMENT OR ANY
GROUT, ETC FOR RAILING
THE USE OF SHIMS, W EDGES,
SIT SOLIDLY ON CONCRETE.
THE BASEPLATE SHALL
FIELD CUT TO FIT
ALUMINUM RAILING POST,
PLAN
ELEVATION
TYPE 'A'
NOTE:
BASE PER SPECIFICATIONS
TOP M OUNTED POST
SPECIFICATIONS
ANCHORS PER
4 - SST CONC
RAILING POST ANCHORAGE TYPE 'A' - ALUMINUM
CONCRETE PER SPECIFICATIONS.
PROVIDE PROTECTION FOR DISSIMILAR METALS AND FOR ALUMINUM IN CONTACT W ITH
STRINGER
STAIR
DETAIL 4 OF 4
iaw0552-001XC.dgn 5/19/2025
RAILING POST
ALUMINUM
BEAM
PLAN
ELEVATION
TYPE 'C'
NOTE:
RAILING POST ANCHORAGE TYPE 'C' - ALUMINUM
PER SPECS
SST BOLTS,
PER SPECS
POST BRACKET
TOP M OUNTED
PROVIDE PROTECTION FOR DISSIMILAR METALS PER SPECIFICATIONS.
1'-0"
11" iaw0552-002.dgn 5/19/2025
W ALL HANDRAIL - ALUMINUM
0552-002
1 1/2" MIN CLR
PLANW ALL BRACKET DETAIL
NOTE:
BOTH ENDS
TO W ALL AT
OF HANDRAIL
RETURN END
W ITH CONCRETE PER SPECIFICATIONS.
PROVIDE PROTECTION FOR DISSIMILAR METALS AND FOR ALUMINUM IN CONTACT2.
FOR ANCHORAGE TO W OOD OR METAL STUD FRAMING PROVIDE SOLID BLOCKING.1.
MIN
MIN
2 1/4" CLR
SEE NOTE 1
PER SPECIFICATIONS,
BRACKET TO W ALL
ATTACH W ALL
6'-0" M AXIM UM
EQUALLY SPACED
BY M ANUFACTURER
RAILS AS RECOM MENDED
SPECIFICATIONS, ATTACH TO
W ALL BRACKETS PER
TOP RISER
LOCATION OF
M
AX
6"
M
AX
6"
STAIRW AY, SEE PLANS
METAL OR CONCRETE
iaw0553-001A.dgn 5/19/2025
0553-001
STANDARD GRATING
DETAIL 1 OF 4
GS-2 - ONE SIDED
SEE NOTE 12
DIMENSION,
MIN BEARING
GS-1
GS-2 - TW O SIDED
DIMENSION, SEE NOTE 12
MIN BEARING
THICKNESS
GRATING
THICKNESS
GRATING
ENDED SUPPORTS, TYP
1/4" PL W ELDED AT OPEN
BEARING BAR
CONDITIONS, SEE PLAN
FOR SIZE AND END
SUPPORTING BEAM,
CONDITIONS, SEE PLAN
FOR SIZE AND END
SUPPORTING BEAM,
GRATING
BEARING BAR
BEAM FLANGE
TO FAR SIDE OF
EXTEND GRATING
GRATING
BEARING BAR
GRATING
AND CLAMP AS SPECIFIED
W ELDED THREADED STUD
EMBEDDED ANGLE W ITH
ATTACH GRATING TO
BANDING BAR
GRATING THICKNESS
AS REQD FOR
VERTICAL LEG
TRIM 1/4" THICK
@ 1'-6" CENTERS
3/8"x6" ANCHORS
CLAMP AS SPECIFIED
TO BEAM W ITH
ATTACH GRATING
CLAMP AS SPECIFIED
TO BEAM W ITH
ATTACH GRATING
THICKNESS
GRATING
1/4" iaw0553-001B.dgn 5/19/2025
DETAIL 2 OF 4
GS-3
THICKNESS
GRATING
DIMENSION, SEE NOTE 12
MIN BEARING
BEARING BAR
GRATING
EQUIPMENT OPENINGS
W ITH CLAMP AS SPECIFIED
ATTACH GRATING TO ANGLE
OPNG
EQPT
GRATING
W ELD TO GRATING
ALL AROUND OPENINGS,
1/4" BAR TOE STOP
L3"x3"x1/4"
/2
MIN EMBEDMENT
CENTERS M AX, 6"
SPACED @ 1'-6"
ANCHORS EQUALLY
5/8" ADHESIVE
PROCEDURES.
UTILIZE M ANUFACTURER'S LOW -TORQUE INSTALLATION
W HEN ANCHOR IS W ITHIN 4" OF A CONCRETE EDGE,3.
INSTALL ANCHORS M AXIM UM 4" FROM EACH END.2.
USE GS-3 ONLY FOR LIGHT DUTY GRATING, TYPE 'A'.1.
NOTES:
iaw0553-001C.dgn 5/19/2025
DETAIL 3 OF 4
GENERAL NOTES:
DIMENSION = 2" FOR GRATING DEPTH GREATER THAN 2 1/4"
DEPTH 2 1/4" OR LESS. MINIM UM BEARING HORIZONTAL
MINIM UM BEARING HORIZONTAL DIMENSION = 1" FOR GRATING12.
GREATER THAN 1/2" AND AS SPECIFIED.
GRATING SUPPORTS SHALL NOT BE LESS THAN 1/4" NOR
THE HORIZONTAL CLEARANCE BETW EEN THE GRATING AND11.
ALTHOUGH BOTH M AY NOT BE INCLUDED IN PROJECT.
AS SPECIFIED. THIS STANDARD DETAIL INCLUDES 2 TYPES,
TYPE OF M ATERIAL USED SHALL BE AS SHOW N ON PLANS OR10.
BAND ALL EDGES. M ATCH DEPTH OF BEARING BAR.9.
SEE SPECIFICATIONS FOR SPACING OF BEARING AND CROSS BARS.
BEARING BAR THICKNESS FOR GRATING TO BE 3/16" MINIM UM.8.
SHOW N IN TABLES BY 1/4".
FOR SERRATED BEARING BARS, INCREASE GRATING THICKNESSES7.
APPLICABLE GRATING TYPE.
SHALL BE AS TABULATED IN "GRATING THICKNESS TABLE" FOR
UNLESS NOTED OTHERW ISE ON PLANS, GRATING THICKNESS6.
STEEL.
TO BE EMBEDDED IN CONCRETE SHALL BE TYPE 316 STAINLESS
TO BE SAME AS GRATING, EXCEPT METAL SUPPORTS THAT ARE
M ATERIAL FOR SUPPORTS OF STEEL AND ALUMINUM GRATING5.
TO THE ENGINEER PRIOR TO FABRICATION.
SHOP DRAW INGS BASED ON FIELD DIMENSIONS SHALL BE SUBMITTED4.
W IDTH OF 2'-0" REGARDLESS OF W EIGHT.
FOR TYPES 'A' & 'B' GRATING. TYPE 'C' GRATING SHALL HAVE A MINIM UM
OR W EIGH M ORE THAN 150 POUNDS, UNLESS INDICATED OTHERW ISE,
INDIVIDUAL GRATING SECTIONS SHALL NOT EXCEED 3'-0" IN W IDTH3.
GRATING SPAN IS INDICATED BY , SEE PLAN.2.
NOTED ON DRAW INGS.
GRATING SHALL BE LIGHT DUTY GRATING UNLESS OTHERW ISE1.
iaw0553-001D.dgn 5/19/2025
DETAIL 4 OF 4
GRATING THICKNESS TABLE
3'-6"
4'-0"
4'-6"
5'-0"
5'-6"
6'-0"
6'-6"
2"
1"
1"
1"
M AXIM UM
SPAN
ALUMINUMSTEEL
1 1/4"
1 1/2"
1 3/4"
1 3/4"
2 1/4"
2 1/4"
1 1/4"
1 1/4"
1 1/2"
1 1/2"
7'-0" 2 1/2"1 3/4"
1'-0"
1'-8"
2'-0"
2'-6"
3'-3"
4'-0"
5'-0"
2'-6"
3'-0"
3'-6"
4'-0"
4'-6"
5'-0"
2"x3/16"
2 1/2"x1/4"
3 1/2"x3/8"
4"x3/8"
4 1/2"x3/8"
STEEL ALUMINUM
STEEL ALUMINUM
(100 PSF)
TYPE 'A'
(500 PSF)
TYPE 'B'
GRATING THICKNESS TABLE
GRATING THICKNESS TABLE
< 2'-0" 1"
1"
1 1/4"
1 1/4"
1 1/2"
1 3/4"
1 3/4"
5'-6"
6'-0" 2 1/4"
6'-6" 2 1/2"
2"
1"
1 1/4"
1 1/2"
1 3/4"
2 1/4"
2 1/2"
2"
(H 20 W HEEL LOAD)
TYPE 'C'
GRATING
ALUMINUM
DO NOT USE
GRATING
ALUMINUM
DO NOT USE
SPAN
M AXIM UM
3"x1/4"
2 1/2"x3/8" OR
4"x1/4"
3"x3/8" OR
SPAN
M AXIM UM
LIGHT DUTY GRATING
HEAVY DUTY GRATING
MEDIUM DUTY GRATING
iaw0751-002.dgn 5/19/2025
0751-002
SYSTEM
METAL COPING
PREFABRICATED
EMBED AT 16" OC
ANCHORS W /4"
5/8" DIA ADHESIVE
FLASHING, ADHERED
MEMBRANE ROOF
W ITHIN 12" OF ENDS
M AXIM UM AND
ANCHORS AT 24" OC
1/2" DIA M ASONRY
COUNTERSINK
4" 4" 8" OR 12"
SEE STRUCT DW GS
1'-4" OR 1'-8"
T Y
P F
A C
E D
IM
VERT FACES
AND EXTEND ONTO
OVER W OOD
MEMBRANE
W ATER SHIELD
APPLY ICE AND
OF PLYW OOD
BE USED IN LIEU
2X BLOCKING M AY
(ATTACH TOGETHER).
PLYW OOD NAILER
W IDTH PT
1 1/2" REQUIRED
ROOF COPING DETAIL AT M ASONRY PARAPET W ALL
VENEER
BRICK
BENT PLATE
4"x4"x3/16" GALV
RIGID INSULATION
ETC AS SHOW N
ANCHORS,
ANGLES,
LAP OVER
BARRIER, TYP.
AIR AND W ATER
VENTS
W EEP
CAVITY
TOP OF
CL
18" TO EDGE OF SUMP
OR 18" TO EDGE OF SUMP
24" CL TO CL OF DRAINS
OD LOCATIONS ONLY
ROOF LOW POINT AT
EXTENSION, 2" ABOVE
OVERFLOW DRAIN
ROOFING
EPDM MEMBRANE
TAPERED EDGE STRIP
ROOF INSULATION
1 1/2" MINIM UM RIGID
UNDERDECK CLAMP
SUMP RECEIVER
FIXED EXTENSION
CONCRETE SLAB
iaw0753-005.dgn 5/19/2025
ROOF/OVERFLOW DRAIN (CONCRETE DECK)
0753-005
REFER TO DETAIL 2214-180 FOR ADDITIONAL INFORM ATION2.
DRAIN PIPES AND LEADERS NOT SHOW N, SEE MECHANICAL.1.
PIPE SEAL
PR…