9-7-MP27006-26032100 Approved Structural Calculations.pdf
PDF 5 MB Posted
- Solicitation number
- MP27006-Stage 1
- Issued by
- Utah
About this file
This document is a comprehensive set of structural design calculations prepared by Horrocks Engineers, Inc. for the Utah Department of Corrections (UDOC) Division of Facilities Construction and Management (DFCM) for a fire storage tank and booster station facility at the Utah State Correctional Facility in Salt Lake City, Utah. The project, numbered UT-11178-25, involves the design and construction of a 0.5 million-gallon circular concrete fire storage tank with an inside diameter of 65.75 feet and wall height of 20 feet, along with an associated booster station building measuring 21'-4" by 16'-0" with a 10-foot wall height. The calculations were prepared in accordance with 2021 IBC and ACI 350-20 standards for environmental engineering concrete structures, with design work completed on October 12, 2026, and reviewed for code compliance by DFCM on November 3, 2026. The project includes detailed engineering for the tank's concrete structure, reinforcement placement, drop panels, ring footings, column footings, and interior support columns, along with hazard analysis reports and booster station design incorporating wind, snow, and seismic loads per ASCE 7-22 standards.
The design incorporates extensive site-specific hazard data for the Salt Lake City location at 4,220 feet elevation, including a 3,000-year mean recurrence interval wind speed of 113 miles per hour, ground snow load of 46 pounds per square foot, and seismic design category D parameters based on a soil class DE site. The tank design uses 5,000 psi concrete with reinforcing steel at 60 ksi yield strength, with Environmental Durability Factor applied per ACI 9.2.6 for normal environmental exposure. The booster station is an enclosed, rigid structure designed for risk category I with ordinary reinforced masonry shear walls. All design calculations include multiple load combinations for leakage test conditions, backfilled empty tank conditions, full tank conditions, and seismic loading scenarios, with detailed moment tables, reinforcement requirements, and capacity verification charts provided for the tank walls, slabs, footings, and supporting columns. The document reflects compliance with current structural codes and establishes the engineering foundation for the separation of culinary and fire water systems on the USCF campus.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Utah State Correctional Facility
1480 N 8000 W, Salt Lake City, UT 84116
DFCM USCF Fire Storage Tank and Booster Station Horrocks Project No. UT-11178-25
Design Calculations
KIRK
WINEGAR
No. 9206167-2202 10/26/2026
DELTA 1 (P.C. REVISIONS): Pages 1-12, 17, 30-42, 45-50, 85-86
DELTA 2 (P.C. REVISIONS): Pages 17A, 17B
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
11/03/2026
2162 West Grove Parkway Project: DFCM USCF
Suite 400 Job No.: UT-11178-25
Pleasant Grove, UT 84062
(801) 763-5100 Engineer: GL www.horrocks.com Checker: KGW
TABLE OF CONTENTS
Tank Hazards Report .................................................................................................. 1-5
Tank Design Criteria
Concrete Tank Design ............................................................................................... 7-44
Booster Station Design Criteria
Building Hazards Report ......................................................................................... 46-50
Design Loads ......................................................................................................... 51-61
Load Diagrams ....................................................................................................... 62-64
Booster Station Design Calcs .................................................................................. 65-84
ASCE Hazards Report Address:
No Address at This Location
Standard: ASCE/SEI 7-22 Latitude: 40.803
Risk Category: IV Longitude: -112.086
Soil Class: DE Elevation: 4220.034917068672 ft
(NAVD 88)
Wind
Results:
Wind Speed 113 Vmph
10-year MRI 73 Vmph
25-year MRI 79 Vmph
50-year MRI 84 Vmph
100-year MRI 89 Vmph
300-year MRI 97 Vmph
700-year MRI 103 Vmph
1,700-year MRI 109 Vmph
3,000-year MRI 113 Vmph
10,000-year MRI 122 Vmph
100,000-year MRI 139 Vmph
1,000,000-year MRI 156 Vmph
Data Source: ASCE/SEI 7-22, Fig. 26.5-1D and Figs. CC.2-1–CC.2-4, and Section 26.5.2
Date Accessed: Fri Oct 09 2026
Page 1 ofhttps://ascehazardtool.org/ Fri Oct 09 202684 https://ascehazardtool.org/
Value provided is 3-second gust wind speeds at 33 ft above ground for Exposure C Category, based on linear interpolation between contours. Wind speeds are interpolated in accordance with the 7-22 Standard. Wind speeds correspond to approximately a 1.6% probability of exceedance in 50 years (annual exceedance probability = 0.00033, MRI = 3,000 years). Values for 10-year MRI, 25-year MRI, 50-year MRI and 100-year MRI are Service Level wind speeds, all other wind speeds are Ultimate wind speeds.
Site is not in a hurricane-prone region as defined in ASCE/SEI 7-22 Section 26.2.
Page 2 of https://ascehazardtool.org/ Fri Oct 09 202684
PGA M : 0.52
SMS : 1.37
SM1 : 1.24
SDS : 0.91
SD1 : 0.83
TL : 8
SS : 1.37
S1 : 0.47
VS30 : 185
Seismic Design Category: D
Multi-Period Design Spectrum
S (g) vs T(s)a
Multi-Period MCE SpectrumR
S (g) vs T(s)a
Two-Period Design Spectrum
S (g) vs T(s)a
Two-Period MCE SpectrumR
S (g) vs T(s)a
Design Vertical Response Spectrum
Vertical ground motion data has not yet been made available by USGS.
MCE Vertical Response SpectrumR
Vertical ground motion data has not yet been made available by USGS.
Seismic
DESite Soil Class:
Results:
Page 3 of https://ascehazardtool.org/ Fri Oct 09 202684
Data Accessed: Fri Oct 09 2026
Date Source:
USGS Seismic Design Maps based on ASCE/SEI 7-22 and ASCE/SEI 7-22 Table 1.5-2. Additional data for site-specific ground motion procedures in accordance with ASCE/SEI 7-22 Ch. 21 are available from USGS.
Page 4 of https://ascehazardtool.org/ Fri Oct 09 202684
Snow
Results:
Ground Snow Load, p : 46 lb/ftg
20-year MRI Value: 9.98 lb/ft^2
Winter Wind Parameter: 0.25
Mapped Elevation: 4219.8 ft
Data Source: ASCE/SEI 7-22, Figures 7.6-1 and 7.6-2 A-D
Date Accessed: Fri Oct 09 2026
Values provided are ground snow loads. In areas designated "case study required," extreme local variations in ground snow loads preclude mapping at this scale. Site-specific case studies are required to establish ground snow loads at elevations not covered.
Snow load values are mapped to a 0.5 mile resolution.
This resolution can create a mismatch between the mapped elevation and the site-specific elevation in topographically complex areas. Engineers should consult the local authority having jurisdiction in locations where the reported ‘elevation’ and ‘mapped elevation’ differ significantly from each other.
Ground Snow Loads for IRC only, p :g(asd) 32.2 lb/ft
The ASCE Hazard Tool is provided for your convenience, for informational purposes only, and is provided “as is” and without warranties of any kind. The location data included herein has been obtained from information developed, produced, and maintained by third party providers; or has been extrapolated from maps incorporated in the ASCE standard. While ASCE has made every effort to use data obtained from reliable sources or methodologies, ASCE does not make any representations or warranties as to the accuracy, completeness, reliability, currency, or quality of any data provided herein. Any third-party links provided by this Tool should not be construed as an endorsement, affiliation, relationship, or sponsorship of such third-party content by or from ASCE.
ASCE does not intend, nor should anyone interpret, the results provided by this Tool to replace the sound judgment of a competent professional, having knowledge and experience in the appropriate field(s) of practice, nor to substitute for the standard of care required of such professionals in interpreting and applying the contents of this Tool or the ASCE standard.
In using this Tool, you expressly assume all risks associated with your use. Under no circumstances shall ASCE or its officers, directors, employees, members, affiliates, or agents be liable to you or any other person for any direct, indirect, special, incidental, or consequential damages arising from or related to your use of, or reliance on, the Tool or any information obtained therein. To the fullest extent permitted by law, you agree to release and hold harmless ASCE from any and all liability of any nature arising out of or resulting from any use of data provided by the ASCE Hazard Tool.
Page 5 of https://ascehazardtool.org/ Fri Oct 09 202684
CLIENT:
PROJECT:
BY: CHECKED BY:
MATERIAL PROPERTIES: Unit Weight of Concrete: pcf WATER TABLE DATA:
Unit Weight of Tank Liquid: pcf Height of Water Table Above top of Slab: ft
Unit Weight of Soil: pcf
Soil Equivalent Fluid Pressure: Above Water Table: pcf
Below Water Table: pcf
DESIGN CRITERIA: ACI 350-20; Code Requirements for Environmental Engineering Concrete Structures and Commentary
Design Method - Load Factor w/ Service Load Checks f'c : psi fc (allowable) : psi Environmental Durability Factor: (ACI 9.2.6) fy : psi fs (allowable) : psi n : Z (allowable) : kips/in
Es: psi Shrinkage Coef. "c":
TANK DATA: SLAB DATA: Ring Footing:
Top Slab:
Bottom Slab:
COLUMN DATA:
RESERVOIR PLAN VIEW: No. of Columns:
DROP PANELS: Grid Spacing: ft
No. of Panels: Diameter: in
Thickness: in Column Strip = ft
Length / Width: ft Middle Strip = ft
Total Panel Wgt: kips Clear Span, ln = ft
LOADS: COLUMN FOOTINGS:
Uniform Live Load: psf Thickness: in
Live Load Surcharge: psf Length / Width: ft
Seismic Load: %
Uniform Snow Load: psf (pf = 0.7*Ce*Ct*pg)
Soil Cover: psf
'd' STRENGTH COMBINATIONS: (ACI 9.2)
SERVICE COMBINATIONS: (ASCE 7-16, 2.4.1)1. 1.4(D + F)
1. D + F 2. 1.2(D + F) + 1.6(L + H) + 0.5(Lr or S or R)
Input max column end-span distance, 'd': ft 2. D + H + F + L 3. 1.2(D + F) + 1.6(Lr or S or R) + (1.0L or 0.5W) ft 3. D + H + F + S 4. 1.2(D + F)+ 1.0(W + L) + 0.5(Lr or S or R)
4. D + H + F + 0.75L + 0.75S 5. 1.2(D + F) + 1.0(E + L) + 1.6H + 0.2S
Input min column end-span distance, 'd': ft 5. D + H + F + 0.7E 6. 0.9D + 1.2F + 1.0W + 1.6H ft 6. D + H + F + 0.525E + 0.75L + 0.75S 7. 0.9D + 1.2F + 1.0E + 1.6H
8. 1.4(D + F) + 0.6H
Inside Diameter, Din:
Wall Thickness, tw:
Distance to Reinf., d:
Tank Wall Weight =
9.625
Footing Thickness:65.75 8.00
21.00
Wall Height, Hwall:
1.00 in Slab Weight = ft kips
Slab Thickness, ts:
629.10
12.00
40.00
0.00
11.78 in
35.00
8.00
120.00
2.90E+07 0.0003 in in
Backfill Height, Hbf:
Liquid Height, Hliq: Slab Thickness, ts:
69.75
Flexural Stress:
ft
60,000.00
5,000.00
8.00
Distance to Reinf., d:
ft ft
.7
14.00'
Distance to Reinf., d:
in
4.00
19.00
20.00 Outside Diam., Dout:
ft
Outside Diam., Dout: 67.75
45.0
Direct and Hoop Tensile Stress:
150.0
Environmental Exposure: NORMAL
Varies
Varies
Allow. Brg Pressure:
500.00
24,000.00
125.00
Footing Width: 5.00 ftinft 10.00
UT-11178-25
150.00
62.50
PAGE NO.JOB NUMBER:
DATE:
KGW
Tank Design
10/12/2026
APPROVED BY:
SUBJECT:
KGW
0.00
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
Ledge Width =
36.00
32.625 ft
450.63 kips in
Clear Span, ln =
Clear Span, ln =
8.00
14.00
18.00
0.00
7.00
7.00
19.75
5.00
12.665
19.08
12.25
76.8
86.00
3.00 psf
Y
X
Circular Water Tank Analysis_2021 IBC & ACI 350-20_25-0718_24FT Wall
BY: CHECKED BY:
UT-11178-25
PAGE NO.JOB NUMBER:
DATE:
KGW
Tank Design
10/12/2026
APPROVED BY:
SUBJECT:
KGW
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
Two-Way Top Slab Design: (In accordance with ACI 14.6 - Direct Design Method)
14.6.2.2: Mo = (wu * l2 * ln ) * (1/8) (Eqn. 14-4)
Determine factored load per unit area, wu: Load Combinations: 1. ksf ksf
2. ksf k-ft Interior Span
3. ksf k-ft End Span
5. ksf
14.6.3.2: In an interior span, total factored static moment Mo shall be distributed as follows:
Negative factored moment = 0.65 * Mo = k-ft
Positive factored moment = 0.35 * Mo = k-ft
14.6.3.3: In an end span, total factored static moment Mo shall be distributed as follows:
14.6.4 - 14.6.6: Factored Moments in Design Strips End Span Condition:
No Errors
163.36
1.68
99.07
No Errors
137.22
139.02
#N/A
#N/A
MuSd (k-ft)
Sd
Mu (k-ft)
Errors
Column Strip fs (ksi)
#VALUE!
NA
Slab Moments
(k-ft) Ext. Negative
End Spans
Positive Int. Negative
Z crack (k/in) #N/A 99.47
Total Moment
NA
109.02
81.77
No. of
Bars
No. of
Bars
Bar
Size
1.68
#N/A 24.66
No. of
BarsReinforcement
20.010.00
37.16
0.70 0.65
Positive factored moment
Exterior negative factored moment
0.75
0.63
0.00
129.79 k-ft k-ft0.00
Interior negative factored moment k-ft
112.49
0.2571
0.2048wu =
Bar
Size
Slab with beams between all supports
(1) w/o edge beam
(2) (3)
Exterior edge unrestrained w/ edge beam
0.2716
0.2226 wu = wu =
76.23 k-ft 60.57
173.05
0.16 0.26 0.30 0.65 k-ft89.99 86.53
0.57
49.55
26.68
0.70
121.14 k-ft
0.52
121.14 k-ft
0.70 k-ft k-ft wu = Mo =
Mo =
0.2716Design wu =
(5)
112.49 k-ft51.92
Bar
Size
No. of
Bars
93.94101.83
17.50
(4) k-ft27.69 k-ft
Exterior edge fully restrained
Slab without beams between interior supports
0.50
121.14 k-ft
Positive Negative
129.79
97.34
44.99 k-ft
6 6
189.52
33.58
0.35
109.02 k-ft 98.64
(1)
1.68
62.37
47.75 95.47
Bar
Size
Interior Spans
49.5526.68
#VALUE!
0.00
21.46
No. of
Bars
Bar
Size
No Errors No Errors
1.68
16.15
BY: CHECKED BY:
UT-11178-25
PAGE NO.JOB NUMBER:
DATE:
KGW
Tank Design
10/12/2026
APPROVED BY:
SUBJECT:
KGW
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
Column Strip Reinforcement:
3 # 6 bars
9 # 6 bars 3 # 6 bars
NA # NA bars 3 # 6 bars
Middle Strip Reinforecement:
2 # 6 bars 6" 2 # 6 bars
2 # 6 bars 4 # 6 bars
NA # NA bars
Reinforcement Clear Cover in Top Slab:
8.00''
Ext. Negative Positive
113.35Z crack (k/in) #N/A 95.22
Reinforcement
Sd
4.33'
Middle Strip
Int. Negative
Slab Moments
(k-ft)
Bar
Size
32.450.00
No. of
Bars
Bar
Size
No. of
Bars
Bar
Size
Bar
Size
27.26
No. of
Bars
No. of
Bars
End Spans
12.39
Interior Spans
6.67
MuSd (k-ft) #VALUE! 45.74 54.45
18.01 21.45
8.67
64 6NA NA
fs (ksi) #N/A
4 6
16.11
57.76 107.28
1.68#VALUE! 1.68
63.36 63.36
5.83'
No Errors
Mu (k-ft) #N/A
Errors #N/A No Errors No Errors
31.99
No. of
Bars
Bar
Size
Positive Negative
6.67'
10.00'
7.17'
Clear Cover (in)
Bottom Sides
Between Layers &
Top
1.50
10.00''
2.00 2.00
1.68 1.68
20.79
8.00'
10.00''
11.19
1.00'
31.99
No Errors
Max.
BY: CHECKED BY:
UT-11178-25
PAGE NO.JOB NUMBER:
DATE:
KGW
Tank Design
10/12/2026
APPROVED BY:
SUBJECT:
KGW
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
Design of Drop Panels:
Inputs:
S ft Center-Center Spacing of Supports
Ln ft Clear Span in Long Direction tslab in Thickness of Slab γc pcf Unit Weight of Concrete
Cc1 in Clear Cover @ Drop Panel
Cc2 in Clear Cover @ Slab w/o Drop Panel
Bar Bar Size in Drop Panel & Slab db in Dia of Rebar in Drop Panel & Slab dcol in Diameter of Column wu ksf Total Factored Design Load f'c psi Concrete Compressive Strength
Solution:
hmin in Min thickness of drop panel below slab (ACI 318 8.2.4)
Lmin ft Min extended distance of drop panel from CL (ACI 318 8.2.4) h in Thickness of drop panel below slab
L ft Extended distance of drop panel from CL of support hs in Total thickness of slab + drop panel
Check 1-way Shear
Evaluate average effective depth dl in dt in davg in
Check adequacy of slab thickness (1-way shear) from edge of interior column
Atrib ft
Trib area for critical section, located at distance d from edge of column, and 12" wide strip
Vu kips
ΦVc kips Concrete Shear Strength (ACI 318 22.5.5.1)
DCR OK
Check critical section at the edge of drop panel (slab without drop panel)
Evaluate average effective depth dl in dt in davg in
Check adequacy of slab thickness (1-way shear) from edge of interior drop panel
Atrib ft
Trib area for critical section, located at the face of support, and 12" wide strip
Vu kips
ΦVc kips Concrete Shear Strength (ACI 318 22.5.5.1)
DCR OK
4.98
1.35
5,000
14.00
12.665
10.00
150.00
2.00
1.50
14.88
15.63
0.75
18.00
0.2716
15.25
9.86
0.08
19.41
0.07
7.375
8.125
7.75
3.00
2.5
2.33
8.00
0.81
BY: CHECKED BY:
UT-11178-25
PAGE NO.JOB NUMBER:
DATE:
KGW
Tank Design
10/12/2026
APPROVED BY:
SUBJECT:
KGW
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
Check 2-way Shear
Critical section at distance d/2 from the edge of the column (slab section with drop panel)
Atrib ft
Trib area for critical section from edge of column
Vu kips
ΦVc kips
DCR OK
Critical section at the edge of the drop panel (slab section w/o drop panel)
Atrib ft
Trib area for critical section from edge of drop panel
Vu kips
ΦVc kips Concrete 2-way Shear Strength (ACI 318 22.6.5.2)
DCR OK
A slab thickness of 10" and a drop panel increase of 8" is acceptable for 1-way and 2-way shear
Check Reinforcement in drop panel
Check minimum steel req for 12" wide strip
As_min in
Min flextural reinf (ACI 318 8.6.1.1)
As_act in
Area of steel provided
Use #6 bars @ 12"O.C.
188.32
51.14
430.26
0.12
Critical Sections for one-way shear
Critical Sections for two-way shear
0.05
0.39
0.44
OK
682.27
121.25
32.93
BY: CHECKED BY:
UT-11178-25
PAGE NO.JOB NUMBER:
DATE:
KGW
Tank Design
10/12/2026
APPROVED BY:
SUBJECT:
KGW
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
Shear Design of Two-Way Slab System (ACI 11.11.7)
Factored Shear Stress, vu = Vu / Ac + (γv * Mu) / Jc γf = 1 / [1 + (2/3) * sqrt(b1/b2)] b1 = b2 = in γf = γv =
Ac = 2d * (c1 + c2 + 2d) = sq in
Jc = [d*(c1 + d) ]/6 + [(c1 + d)*d
]/6 + [d*(c2 + d)(c1 + d)
]/2
Jc = in
14.6.3.6 - The gravity load moment to be transferred between slab and edge column in accordance with 14.5.3.1 shall be 0.3*Mo
Mu = 0.3*Mo = k-ft
Vu = kips vu = psi φVc = psi
14.6.9: Factored Moments in Columns and Walls
Mu = 0.07 * [( wdu + 0.5 * wlu ) * l2 * ln
- wDu' * l2' * (ln' )
] = k-ft (ACI Eqn. 14-7)
RING FOOTING DESIGN: Footing Pressure = P + M
A S
Dead Load Computation, DL (k/ft) Section: (Factored Pressure for Design) Footing Width = ft
DL Top Slab = k/ft Dout = ft
DL Launder Slab = k/ft Pressure at Face = ksf
DL Wall = k/ft Vu @ Face = k/ft
Mu @ Face = k-ft/ft
Soil Load Computation, H (k/ft) Vws @ Face = k/ft
Soil Load = k/ft Mws @ Face = k-ft/ft
Live Load Computation, LL (k/ft)
Live Load = k/ft ksf
# 6 @ 12
Snow Load Computation, S (k/ft) ksf
Snow Load = k/ft
Service Combinations: Strength Combinations: Net Bearing Pressure Check:
1. k/ft 1. k/ft Footing Heal: psf
2. k/ft 2. k/ft Footing Toe: psf
3. k/ft 3. k/ft
4. k/ft 5. k/ft k/ft k/ftwu = wu = 4.63 wu = 4.79
51.92
3.000
46.22
0.40
2049.28
372040.09
23.22
282.84
0.60
OK!
1.234
32.02
0.901
69.75
Bar
Spa
(in)
Errors No Errors fs (ksi) 6.57
Z crack (k/in)
Mu (k-ft)
Sd
MuSd (k-ft)
64.31
Reinforcement
1.79
Bar
Size
OK!
OK!
36.00''
1667.01
2.73
3.00'
7.48
17.07
5.45
9.55
7.59
42.64
4.33
6.03 wu = 5.55
4.79 wu =4.58
248.93
6.03 wu = 5.89 wu = 5.93
-0.32
0.346 wu = 4.23
0.000
1.00'
1.00' wu =
0.395 wu =
0.000
BY: CHECKED BY:
UT-11178-25
PAGE NO.JOB NUMBER:
DATE:
KGW
Tank Design
10/12/2026
APPROVED BY:
SUBJECT:
KGW
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
COLUMN FOOTING DESIGN: Footing Pressure = P + M
A S
Tributary Area = sf
Factored Moment, Mu = k-ft
Service Moment, Mws = k-ft
Dead Load Computation, DL Section: (Factored Pressure for Design) Footing Width = ft
DL Top Slab = kips Pressure at Face = ksf
DL Drop Panel = kips Vu @ Face = k/ft
DL Column = kips Mu @ Face = k-ft/ft
Vws @ Face = k/ft
Soil Load Computation, H Mws @ Face = k-ft/ft
Soil Load = kips
Live Load Computation, LL
Live Load = kips ksf # 5 @ 12
Snow Load Computation, S ksf
Snow Load = kips
Service Combinations: Strength Combinations: Net Bearing Pressure Check:
1. kips 1. kips Footing Heal: psf
2. kips 2. kips Footing Toe: psf
3. kips 3. kips
4. kips 5. kips kips kips
Punching Shear Check:
At Column Edge: φVc = 4*sqrt (f 'c) * bo * d = kips > Pu, At Footing Edge: φVc = 4*sqrt (f 'c) * bo * d = kips > Pu, Pu =
1534.42 OK!
Pu = 50.43
644.36 OK!
52.44
2125.14
1638.84
59.20
62.05
62.05
Pu = 47.05 Pu =
42.88 Pu =
Pu =
Pu =
Pu =
0.000
7.840
6.860
2.12
47.05 Pu =
43.86 Pu =
36.02
OK!
3.60
2.86
36.09
4.75
5.63
4.22
OK!
3.00''
21.00''
Errors No Errors
Bar
Spa
(in)
Bar
Size
MuSd (k-ft)
2.84 fs (ksi)
Reinforcement
Mu (k-ft)
Sd
Z crack (k/in)
2.590
28.30
1.52
6.43
1.750'
5.00'
196.00
24.500
6.400
5.125
7.48
5.07
BY: CHECKED BY:
Seismic Design of Liquid Containing Structures and Commentary (ACI 350.3-20)
(Seismic Criteria in Accordance with ASCE 7-16: Minimum Design Loads for Buildings and Other Structures)
TANK PROPERTIES:
ft ft pcf pcf psi psi lbs lbs (Note: Includes weight of soil cover and column drop panels) lbs
Site Location:
Site Class: (ASCE Table 20.3.1)
Importance Factor: (ACI Table 4.1.1(a))
Response Modification Factor: (ACI Table 4.1.1(b))
Seismic Spectral Response Parameters:
Liquid Weight:
Stored Liquid Weight, WL = lbs
(ACI Eq. 9.3.1a) (ACI Eq. 9.3.1b)
4,031,949
Circular Tank: Shell
Impulsive Component, W i (lbs): 1,338,715
Convective Component, Wc (lbs): 2,525,476
SDS SD1
1.370 0.470 0.996 2.650 1.365 1.246 0.910 0.830
SMS SM1
1.50
Impulsive Component, Ri: 2.25
Compulsive Component, Rc: 1.0
Ss S1 Fa Fv
Latitude: 40 48 12
112.09
D
Sec Dec Deg
40.80
Longitude: 112 5 10.3
(Defalut)
Ec: 4,286,826
Structure Weight: 1,079,732
Deg Min
Effective Mass Coeff., ε 0.54
Superimposed DL: 76,800
Total Weight: 1,156,532
Height to C.G. (ft) 10.00 20.42 Concrete, f'c: 5,000
Weight (lbs) 629,104 450,628 Concrete Weight, γc:
19.00
Thickness (in) 12.00 10.00 Liquid Weight, γL: 62.50
Inside Diameter (ft): 65.75 65.75 Liquid Height, HL:
DFCM - Utah Department of Corrections
JOB NUMBER:
UT-11178-25
KGW
APPROVED BY:
KGW
Circular Tank: Shell
Fire Storage Tank
SUBJECT:
Tank Design
Roof Wall Height, HW:
ANT
PAGE NO.
8/9/2026
DATE:
20.00 tanh 0.866
0.866
Li
L
L
D
HW
W D
H
0.230 tanh 3.68 c L
L L
W HD
W H D
BY: CHECKED BY:
DFCM - Utah Department of Corrections
JOB NUMBER:
UT-11178-25
KGW
APPROVED BY:
KGW
Fire Storage Tank
SUBJECT:
Tank Design
ANT
PAGE NO.
8/9/2026
DATE:
Height Factors:
(Excluding Base Pressure, EBP)
For tanks w D/HL<1.333, hi / HL = 0.5-0.09375(D/HL) (ACI Eq. 9.3.2a)
For tanks w D/HL>=1.333, Hi / HL = 0.375 (ACI Eq. 9.3.2b)
(ACI Eq. 9.3.2c)
(Including Base Pressure, IBP)
For tanks w D/HL<0.75, hi' / HL = 0.45 (ACI Eq. 9.3.3a)
For tanks w D/HL>=0.75, (ACI Eq. 9.3.3b)
(ACI Eq. 9.3.3c)
Dynamic Properties: (ACI 9.3.4)
(ACI Eq. 9.3.4a) (ACI Eq. 9.3.4b) (ACI Eq. 9.3.4c) (ACI Eq. 9.3.4f)
(ACI Eq. 9.3.4g) (ACI Eq. 9.3.4h) (ACI R9.4.3)
Fundamental Period of Tank Oscillation, Ti (sec): 0.042
Coefficient, λ 9.657
Circular Frequency of Convective Vibration Mode, ωc (rad/s): 1.19
Natural Period of Convective Mode of Sloshing, Tc (sec): 5.276
Natural Period of Vibration of Vertical Liquid Motion, Tv (sec): 0.038
Circular Frequency of Impulsive Vibration Mode, ωi (rad/s): 149.87
Height above base to C.G. of Impulsive Lateral Force, hi' (ft): 26.24
Height above base to C.G. of Convective Lateral Force, hc' (ft): 24.45
Circular Tank: Shell
Coefficient, Cw: 0.142
Coefficient, Cl: 0.247
Circular Tank: Shell
Circular Tank: Shell
Height above base to C.G. of Impulsive Lateral Force, hi (ft): 7.13
Height above base to C.G. of Convective Lateral Force, hc (ft): 10.30 cosh 3.68 1
3.68 sinh 3.68
L c
L L L
H
Dh
H H H
D D cosh 3.68 2.01
3.68 sinh 3.68
L c
L L L
H
Dh
H H H
D D
0.866
0.125
2* tanh 0.866
Li
L
L
D
Hh
H D
H i l c
L c g C E H ω γ i iT ω π2= c D λω =
3.68 tanh 3.68 LHg D λ = c cT ω π2= w l w t C C r
L L v w c
DH
T gt E γπ=
BY: CHECKED BY:
DFCM - Utah Department of Corrections
JOB NUMBER:
UT-11178-25
KGW
APPROVED BY:
KGW
Fire Storage Tank
SUBJECT:
Tank Design
ANT
PAGE NO.
8/9/2026
DATE:
Seismic Response Coefficients: (ACI 9.4)
Calculation of Ci:
For Ti <= Ts, Ci = SDS (ACI Eq. 9.4.1a)
For Ti > Ts, Ci = (SD1 / Ti) <= SDS (ACI Eq. 9.4.1b)
Ts = sec (ACI Eq. 9.4.1c)
Calculation of Cc:
For Tc <= TL, Cc = (1.5SD1 / Tc) <= 1.5SDS (ACI Eq. 9.4.2a)
For Tc > TL, Cc = (1.5SD1*TL / Tc ) (ACI Eq. 9.4.2b)
TL = (ASCE 7-16, Fig. 22-14)
Calculation of Ct: Wave Oscillation: (ACI 7.1)
Ct = SDS (ACI Eq. 9.4.3a) dmax = (D/2) Cc I (ACI Eq. 7.1c)
Shell Wall: dmax = ft ft
Dynamic Lateral Forces: (ACI 4.1.1)
(ACI Eq. 4.1.1a) Pw' = lb/ft of wall
(ACI Eq. 4.1.1c) Pr = lb/ft of wall
(ACI Eq. 4.1.1d) Pi = lb/ft of wall
(ACI Eq. 4.1.1e) Pc = lb/ft of wall
Total Base Shear: (ACI 4.1.2)
(ACI Eq. 4.1.2)
Tangential Shear Stress, q = psi lb/ft of wall Allow. Shear Stress, qallow = psi
Vertical Acceleration: (ACI 4.1.4) pvy = uv*qhy (ACI Eq. 4.1.4.2a) uv = Ct I (b/Ri) >= 0.2SDS (ACI Eq. 4.1.4.2b) uv = qhy = γL (HL - y) = psf pvy = psf (at wall base)
< ho = 1.00 FAIL
480.11
1187.50
OK!
0.404
1,000
1,323
3,930
4,329
Shell 140.85
V = 7,606 141.42
Shell
COEFFICIENT Shell
Ci 0.910
Cc 0.236
Ct 0.910
0.913
11.64 w W i i
W P C I
R ε i r ir
R
W
ICP
c c cc
R
W
ICP
i i ii
R
W
ICP
( ) 222 egcrwi PPPPPV ++++=
Circular Water Tank Analysis_2021 IBC & ACI 350-20_25-0718_24FT Wall
SEE ADDITIONAL
CALCULATIONS ON
PAGE 17.
BY: CHECKED BY:
DFCM - Utah Department of Corrections
JOB NUMBER:
UT-11178-25
KGW
APPROVED BY:
KGW
Fire Storage Tank
SUBJECT:
Tank Design
ANT
PAGE NO.
8/9/2026
DATE:
181.01
173.25
165.49
157.73
149.98
142.22
134.46
126.70
118.95
111.19
103.43
95.67
87.92
80.16
72.40
64.65
56.89
49.13
41.37
33.62
25.86
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
20.00
0 50 100 150 200
F lu id H e ig h t
(f t)
Force (lb/ft)
Dynamic Force Distribution (Shell Wall)
Impulsive Force
84.99
87.89
90.78
93.67
96.57
99.46
102.36
105.25
108.15
111.04
113.93
116.83
119.72
122.62
125.51
128.40
131.30
134.19
137.09
139.98
142.88
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
20.00
0 50 100 150 200
F lu id H e ig h t
(f t)
Force (lb/ft)
Dynamic Force Distribution (Shell Wall)
Convective Force
CLF = 1.4 (min) or 3.2 (max)
CLF = 2.2 (average) <= Used for Design, Per ACI 350.3-20, R7.1
Upward Fluid Pressure on Underside of Flat Roof
FR/AV = CLFγL (dmax/I-h0)
FR = Total Upward Force on Roof Structure (lbs)
AV = Project Area of Roof Impacted by the Wave (ft γL = 62.4 Unit Weight of Tank Liquid (lbs/ft dmax = 11.64 Maximum Wave Oscillation (ft)
I = 1.5 Seismic Importance Factor h0 = 1.0 Distance from Undisturbed Water Surface to Underside of Roof (ft)
Li = Distance of Flat Roof Structure from Wall Subject to Upward Pressure, F R/AV
Li = D/2 - D/πsin -1
(h0/dmax) (For Circular Tanks)
D = 65.75 Tank Inside Diameter (ft)
Li = 28.628 (ft)
FR/AV = 3195.9 (lbs/ft
(FR/AV) * Li = 91493 (lbs/ft)
See "Roof Slab w/ Wave Uplift" Calculation on Page
Tensile Capacity of #7 Rebar
Diameter = 7 /8 = 0.88 (in)
Area = 0.60 (in
Yield Strength = 60,000 (lbs/in
Yield Capacity = 36079 (lbs)
Ultimite Tensile = 90000 (lbs/in
Ultimate Breaking = 54119 (lbs)
(2) #7 hooked dowels into roof slab from top of wal to resist uplift, (2) * 26507 = 72158.46 (lbs)
(FR/AV) * Li * spacing of (2) #7 dowels = 68619.68 (lbs)
OK
Wall Forces in Circular Tanks with Inadequate Freeboard q0 = cos -1
(h0/dmax) kc = [2q0 + sin(2q0)]/2π h0 = 1 Distance from Undisturbed Water Surface to Underside of Roof (ft) dmax = 11.64 Maximum Wave Oscillation (ft)
I = 1.5 Seismic Importance Factor q0 = 1.484779642 (rad) kc = 0.499865146
Excluding Bottom Pressure
Pi-w = [(1-kc)W i + kc(Hw/HL)WL]Ci(I/Ri)
Pc-w = (1-kc)Cc(I/Rc)Wc
Mi-w = [(1-kc)W ihi + kc(Hw/HL)WL(Hw/2)]Ci(I/Ri)
Mc-w = Pc-whc
W i = 1,338,715 Impulsive Component (lbs)
Wc = 2,525,476 Convective Component (lbs)
WL = 4,031,949 Stored Liquid Weight (lbs)
Hw = 20 Height of Wall (ft)
HL = 19 Height of Liquid (ft)
Ri = 2.25 Response Modification Factor, Impulsive Component
Ci = 0.910 Period-Dependent Seismic Response Coefficient
Rc = 1.0 Response Modification Factor, Convective Component
Cc = 0.236 Period-Dependent Seismic Response Coefficient hi = 7.13 Height above base to C.G. of Impulsive Lateral Force (ft) hc = 10.3 Height above base to C.G. of Convective Lateral Force (ft)
Pi-w = 8197.31
Pc-w = 2164.65
Mi-w = 76329.40
Mc-w = 22295.91
Resultant Wall Force = => 8478.3
Height of Resultant = / => 9.38
(Total base shear is not less than the corresponding value computed assuming that the adequate freeboard is provided, therefore moments are also within acceptable ranges, by inspection)
2 + �
2+�
2 �
2 + �
17A
Including Bottom Pressure
Mi-w' = [(1-kc)W ihi' + kc(Hw/HL)WL(Hw/2)]Ci(I/Ri)
Mc-w' = Pc-whc' hi' = 26.24 Height above base to C.G. of Impulsive Lateral Force (ft) hc' = 24.45 Height above base to C.G. of Convective Lateral Force (ft)
Pc = 4329 Dynamic Lateral Force (lbs/ft of wall)
Mi-w' = 113907.99
Mc-w' = 52936.30
17B
BY: CHECKED BY:
Design Condition No. 1 - Leakage Test Prior to Backfilling
Design for Shear at Wall Base:
Wall Shear Capacity, k/ft
Shear, φ = therefore, k/ft
Triangular Load: Note: Consider Base as
(from Table A-12, coef. = )
Design for Ring Tension: H /Dt = H = ft Applied Shear, Vu = coef. X wuH
= k/ft wu = Sd * 1.4 * pcf = pcf D = ft wuHR = lbs/ft t = in Vu (max) = k/ft < k/ft O.K.
Environmental Durability Factor, Sd = =
20 * 1.4
Ring Tension Table - Hinged Base w/ Free Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
263.51
95,426
95,426
47,713
95,426
186.15
95,426
264.90
12.00
Outside Face
Size Spa (in)
12.00
Ring Steel
Provided
(in /ft)
Concrete
Stress, fc
(psi)
78.82
0.884
53.926
Provided
Tension
(lbs/ft)
6 12.00
47,713
47,713
244.28
111.37
6 6.00
6.00
6 6.00
6.00
1.767
6 12.00
6.00
95,426
240.17
6.00
6.00
6.006
12.00
95,426
0.566
0.640 71,017
0.645
61,048
71,609 1.33
636,5640.329
140.51
47,71350.880.884
1.767
47,713
12.00 6 12.00
0.95
6 6.00
Point
1.767
1.767
1.13
1.16
1.32
0.342 37,977
0.222
0.103
Coefficeint from Table
A-5
-0.011 -1,239
11,398
6 12.00
12.00
62,804
0.000
51,290
0.550
0.462
1.767
217.32
0.70
6.00
0.68
0.00
UT-11178-25
JOB NUMBER:
0.884
0.884
1.767
DFCM - Utah Department of Corrections
ANT
PAGE NO.
KGW
APPROVED BY:
KGW
SUBJECT:
Fire Storage Tank
6.86 12.25
0.196
6.86
0.75
168.79
6.08
Tank Design
DATE:
Fixed
20.00
65.75
12.00
16.33
12.25
62.50
110,978
8/9/2026
0.9 * 60
1.929
24,678
0.21
0.46
Ring Steel
Required
(in /ft)
Inside Face
Size Spa (in)
Ring
Tension
(lbs/ft)
0.02
0.884
6.00
6.00 6
12.00
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-20,000 0 20,000 40,000 60,000 80,000 100,000 120,000
T a n k H e ig h t
Ring Tension (lbs/ft)
Hinged Ring Steel
2 'c wV f c b d= = cVφ =
BY: CHECKED BY:
UT-11178-25
JOB NUMBER:
DFCM - Utah Department of Corrections
ANT
PAGE NO.
KGW
APPROVED BY:
KGW
SUBJECT:
Fire Storage Tank Tank Design
DATE:
8/9/2026
Design for Wall Flexure: H /Dt = H = ft t = in wuH = lb-ft/ft D = ft wu = pcf * 1.4 = pcf
Wall Moment Table - Hinged Base w/ Free Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
Wall Moment Table - Fixed Base w/ Free Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
0.0009.00
65.75
20.00
2.2530.006
24.595
0.000 0.000
10.07
0.064 4.87
0.000
0.00
Point
Coefficeint from Table
A-7
Mult
(kip-ft)
Z
(kips/in) Sd
As ult
(in /ft)
1.607
1.607
1.607
0.409
0.000.409
0.409
0.409
0.0270.0008 0.862 5
Bar
Size
0.020
0.000
0.0000
0.000
0.0002
0.0000
700,000
9.00
9.00
0.206
0.000
0.000
0.005 9.00
0.000
0.000
As Min
(in /ft)
1.607
As
Provided
(in /ft) fs
(ksi) φMn
(kip-ft)
17.275
62.50
0.409 0.00 0.000
0.00354
Bar
Spacing
(in)
0.0000
0.00354
0.00354
0.00354 ρactual
0.00354
0.00354
0.409
0.589
0.589
1.607
1.607
0.00354
9.00
17.275
2.02 9.422
Point
Coefficeint from Table
A-2
Mult
(kip-ft)
7.5840.0067
0.0000 0.000
0.48
0.000
0.0018 2.081 0.048
9.00
0.409
17.275 0.00
1.607
1.6070.0038 4.298
0.0077 8.676
0.100 5 9.00
74.976
0.133 φMn
(kip-ft) ρactual
0.409 17.275
17.275
22.738
46.961
66.701
As ult
(in /ft)
Bar
Diam.
(in)
Bar
Spacing
(in)
As
Provided
(in /ft)
9.00 24.595
0.177
0.000 0.00510 0.0001.607
6 9.00
17.275
58.3050.236
0.270
As Min
(in /ft)
9.00
9.00 fs
(ksi)
0.213 16.07
9.00 0.409
0.000 0.00
0.0001 0.108 0.002 5 9.00 0.409 1.178
17.275 0.770.0003 0.328
0.25
0.0019 2.086 0.048 5 0.00354 4.88 22.789
0.027
9.00 0.409
9.00 0.409 0.00354 17.2750.0008 0.872 0.020 5 2.04 9.525
0.0045 5.090 0.118 5
9.00 0.409 0.00354
0.0050 5.676 0.132 5
9.00 0.409 17.275 0.1580.00354
17.275 0.109 8.26
11.92
38.5110.0031 3.525 0.082 5
1.607
1.607
-0.0185 -20.845 0.496 6
9.00 0.589
-0.0040 -4.523 0.105 6
24.595 25.0810.0029 3.263 0.076 6 5.38
-24.595
1.607
55.6171.607
3.585
0.000
17.275
Z
(kips/in)
0.0000.0000 0.000 0.000 5 9.00 0.409
0.160
0.203
1.607 0.00510
12.00
87.50
17.275
0.00510
24.595
1.607 17.275
0.00354
12.50
14.30
0.00354
17.275
17.275 0.003
0.0061 6.862
17.275 0.064
0.010
1.607
1.607
1.607
0.00354
1.607
1.607
1.607
0.00354
Sd
6.08
0.008 5
0.589
9.00 0.589
9.00 0.589
1.607
0.00510
0.00354
0.00510
0.00510
0.176 13.29 62.020
160.24934.350.408
0.140
0.101
7.45 34.773
-24.595
9.00 0.409
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Fixed Base Moments Reinforcement
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-5.00 0.00 5.00 10.00 15.00 20.00 25.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Hinged Base Moments Reinforcement
BY: CHECKED BY:
Design Condition No. 2 - Backfilled Empty Tank
Design for Shear at Wall Base:
Wall Shear Capacity, k/ft
Shear, φ = therefore, k/ft
Triangular Load: Note: Consider Base as
(from Table A-12, coef. = )
Design for Ring Tension: H /Dt = H = ft Applied Shear, Vu = coef. X wuH
= k/ft
D = ft t = in Vu (max) = k/ft < k/ft O.K.
Environmental Durability Factor, Sd = =
20 * 1.6
Earth Pressure Calculations: wuHR = psf * 1.6 * (Sd = ) * R = lbs/ft puR = psf * 1.6 * (Sd = ) * R = lbs/ft
Condition No. 1 - Normal Earth Pressure Condition No. 2 - Seismic Earth Pressure
Soil Pressure @ H = ft = psf Soil Pressure @ H = ft = psf
Soil Pressure @ H = ft = psf Soil Pressure @ H = ft = psf
Water Pressure @ H = ft = psf Water Pressure @ H = ft = psf
Design, wH = psf Design, wH = psf
Design, pH = psf Design, pH = psf
Ring Compression Table - Hinged Base w/ Free Top Ring Compression Table - Hinged Base w/ Fixed Top
Note: VR/H =
0.0 H 0.0 H
0.1 H 0.1 H
0.2 H 0.2 H
0.3 H 0.3 H
0.4 H 0.4 H
0.5 H 0.5 H
0.6 H 0.6 H
0.7 H 0.7 H
0.8 H 0.8 H
0.9 H 0.9 H
1.0 H 1.0 H
16.33
Fixed
10.50
0.75
0.196
-7071.32
Total Ring
Comp.
(lbs/ft)
-18,442
-9.079 64,197
-5.178 36,615
1,485
0.352
468,000 0.593
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
0.462
0.566
4.00
4.00
150.00
4.00 334.80
Equiv. Pressure (pcf): 45.00
1.022
Point Point
0.550 485
-10,133
-3,612
-45,778
-36,4941.042
0.750
1.062
1.066
1.040
-0.011
0.429
DATE:
KGW
Tank Design
8/9/2026
UT-11178-25
4.00 334.80
Above Water
Table
10.50
PAGE NO.JOB NUMBER:
KGW
APPROVED BY:
SUBJECT:
180.00
Seismic earth pressure without environmental durability factor applied controls.
-64,197
-27,207
0.329
0.000 00.000 468,000
0.010 -71
00.000
1,555
12.25
0.989
Backfill Height (ft): 4.00
Above Water
Table
Below Water
Table
Coefficeint from Table
A-8
Ring
Comp.
(lbs/ft)
4.00
468,000
Ring
Comp.
(lbs/ft)
Coefficeint from Table
A-6
4.00 0.00
0.945
Backfill Height (ft):
Coefficeint from Table
A-5
0.103 -55,057
0.640
0.645
-18,312
0.222
0.342
1.003
0.345 -2,442 -6,054
-1339.20
Allowable
Comp.
(lbs/ft)
468,000
468,000
468,000
1.688
6.08 20.00
65.75
12.2512.00
0.9 * 60
83.70
-693-1,1780.167
1674.00
468,000
-2,490
0.00
-720.00
180.00
0.00
900.00
4.00
88,052
279.00
1674.00 1.000
-1339.20 1.000
Below Water
Table
0.00
-63,928
Equiv. Pressure (pcf):
-2.252
468,000
-0.480 3,394 -33,100
Allowable
Comp.
(lbs/ft)
468,000
468,000
468,000
468,000
15,928 -29,850
-29,697
468,000
-13,861
-4,190 -22,501
-3,7270.527
468,000
468,000
468,000
468,000
468,000
468,000
468,000
468,000
468,000
2 'c wV f c b d= = cVφ =
BY: CHECKED BY:
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
DATE:
KGW
Tank Design
8/9/2026
UT-11178-25
PAGE NO.JOB NUMBER:
KGW
APPROVED BY:
SUBJECT:
Design for Wall Flexure: H /Dt =
Wall Moment Table - Hinged Base w/ Free Top: wuH + puH
= lb-ft/ft
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
Wall Moment Table - Fixed Base w/ Free Top: wuH = lb-ft/ft puH
= lb-ft/ft
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
0.0067
0.0061 -5.237
0.0077 -6.622
0.0000
460,800
Coefficeint from Table
A-4
0.0000
0.0001 φMn
(kip-ft)
0.076
0.589
0.589
0.409
0.0000
17.275
-5.788
1.406
1.406
0.4099.00
1.406
9.00
0.122
0.000
1.406
0.000
0.180
10.73
9.55
Point
Coefficeint from Table
A-7
0.000 5
As
Provided
(in /ft)
Bar
Diam.
(in)
0.0000 0.000
0.0000
0.0000 0.000
-17.275
0.00
6.72
0.000
8.35 38.9360.00510
1.406
1.406
0.00510
50.069
15.184
6.292
17.275
0.00 fs
(ksi)
0.000
0.000 0.00
As Min
(in /ft)
0.000
0.409
0.00354
17.275
-17.275
0.000
Mult
(kip-ft)
As ult
(in /ft)
9.000.000
0.0000.000
0.00
Z
(kips/in)
0.409
9.00
0.409
9.00
-17.275
6.08
0.0038 -3.280
0.0002 -0.157
0.0018 -1.588
0.0008 -0.658 5
9.00 0.409
0.037
0.154 6
50.004
0.015 9.00 0.409
0.00354
-610,560
Bar
Spacing
(in)
Sd ρactual
1.406
1.406
Point
Coefficeint from Table
A-2
Mult
(kip-ft)
As ult
(in /ft)
0.000.000 0.000
0.409
1.406 0.00354
0.409
1.406
0.00354
1.4060.409
9.00
0.005 0.32
-17.275
-24.595
0.162
0.020
Bar
Spacing
(in)
Sd
Bar
Diam.
(in)
0.589
-1,071,360
9.00
9.00
9.00
9.00
9.00
0.049
0.00354
-24.595
As
Provided
(in /ft) fs
(ksi)
Z
(kips/in)
As Min
(in /ft)
0.000
0.0004
0.4099.000.0001 -0.082 0.002
1.4069.00 -17.275 0.006 0.390.409
5 0.17 0.787
0.0019 -1.406 0.033 5
0.98 4.554
0.0021
0.0008 -0.476 0.011 50.0011 -17.275 0.015
0.0003 -0.188 0.004 5
9.00
0.409
0.409
1.4069.00 -17.275 0.043 2.88
0.0045 -3.691 0.086 5
-17.275 0.075 4.99 23.2920.0031 -2.436 0.056 50.0035
9.00 0.409
9.26
0.0048 -17.275 0.114 7.56
1.406
0.0050 -4.518 0.105 50.0048 9.00 0.409 1.406 0.140 43.198
24.595-0.0040 1.416 0.033 6-0.0072
0.0029 -3.249 0.075 60.0017 21.8534.68
2.041.406
-0.0185 12.391 0.291 6-0.0240 9.00 0.589 1.406 83.35017.87
9.00 0.589 9.528
35.283
13.438
1.800
0.000
1.504
0.000
31.361
44.543
0.000
3.25
1.35
0.101
-17.275
0.135
0.000
0.100
-17.275
1.406 -17.275 0.003
1.406
1.406
0.589
0.206
0.00354
1.406 φMn
(kip-ft)
17.275
0.00354
0.00354
24.595
0.00510
24.595 0.388
1.406
-24.595
0.044
9.00
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Fixed Base Moments Reinforcement
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Hinged Base Moments Reinforcement
BY: CHECKED BY:
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
DATE:
KGW
Tank Design
8/9/2026
UT-11178-25
PAGE NO.JOB NUMBER:
KGW
APPROVED BY:
SUBJECT:
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
Wall Moment Table - Fixed Base w/ Fixed Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H 0.4095 9.00 1.406-0.0058 -0.415 11.976 0.281 17.275 0.375 24.54 114.490
1.406-0.0049 -0.349 1.067 0.025 5 9.00 0.409 17.275 0.033 2.19 10.201
-0.0030 -0.215 -3.464 0.080 5 9.00 1.406 0.107 7.10 33.113
1.406
-17.275
1.406 0.149
0.409 -17.275
9.00 0.409
0.0057 0.412 -3.278 0.076 5 9.00
-0.0001 -0.006 -4.524 0.105
1.406 0.101 6.720.409
5 -17.275 0.140 9.27 43.255
31.343
0.0175 1.257 -1.179 0.027 5 9.00 0.409 -17.275 0.036 2.42 11.2721.406
0.035 2.320.0354 2.535 1.130 0.026 5 9.00 1.4060.409 17.275 10.802
0.409
0.0695 4.981 4.793 0.111 6
1.4060.0554 3.969 3.493 0.081 5 9.00 17.275 0.108 7.16 33.391
32.243
0.135 6.27 29.2400.0618 4.429 4.347 0.101 9.00 1.4060.589 24.595
9.00 24.595 6.910.589
0.0000 0.000 0.000 0.000 1.406 0.000 0.000.589 24.595
6 9.00 0.000
As ult
(in /ft)
Bar
Diam.
(in)
As
Provided
(in /ft)
Sd fs
(ksi)
Z
(kips/in) Point
Coefficeint from Table
A-9
Mult
(kip-ft)
Total Mult
(kip-ft)
Bar
Spacing
(in) φMn
(kip-ft)
As Min
(in /ft)
Point
Coefficeint from Table
A-9
Mult
(kip-ft)
Total Mult
(kip-ft)
As ult
(in /ft)
Bar
Size
Bar
Spacing
(in)
As
Provided
(in /ft)
Sd φMn
(kip-ft)
Z
(kips/in)
As Min
(in /ft) fs
(ksi)
9.00 0.0000.589 0.00
6 9.00 0.589 0.137 6.39 29.7931.406 24.5950.0618 4.429 4.429 0.103
24.595 0.0001.40660.0000 0.000 0.000 0.000
0.0554 3.969 3.812 0.088 5
6 9.00 0.589 24.5951.406 0.154 7.18 33.5090.0695 4.981 4.981 0.116
5 9.00
36.440
0.058
7.81
0.0354 2.535 1.877 0.043 0.409
0.11817.2751.4069.00 0.409
17.9471.406 3.85
1.406 0.010 0.68 3.165
17.275
0.0175 1.257 0.409 -17.275
0.089 5.881.4060.409 -17.275
5 9.00
0.0057 0.412 -2.868 0.066 5 9.00
-0.331 0.008
-0.0001 -0.006 -5.243 0.122 5 9.00 0.409
27.421
-0.0030 -0.215 -6.837 0.159 5
9.00 0.409 1.406
0.409
0.191
1.406 0.163-17.275 50.12610.74
58.677
0.2139.00 14.011.406 -17.275
-0.0049 -0.349 -6.138 0.143 5
65.361
-0.0058 -0.415 -0.415 0.010 5 -17.2751.406 0.85 3.9680.013
-17.275 12.58
0.4099.00
50970.88Wall Moment Table - Hinged Base w/ Fixed Top
-9.079
*Note: VH =
1.688
64,197
32.875
* 20
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Fixed Base Moments Reinforcement
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Hinged Base Moments Reinforcement
BY: CHECKED BY:
DFCM - Utah Department of Corrections
Fire Storage Tank
ANT
DATE:
KGW
Tank Design
8/9/2026
UT-11178-25
PAGE NO.JOB NUMBER:
KGW
APPROVED BY:
SUBJECT:
Revise Moments for Top Slab Moment: Slab Moment = k-ft (From 2-Way Slab Calculations)
Wall Moment Table - Hinged Base w/ Fixed Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
Wall Moment Table - Fixed Base w/ Fixed Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
12.00
0.000
Radius of
Gyration, 'R'
(in)
2.89
3.46
Moment of
Inertia, 'I'
( in
As ult
(in /ft)
Bar
Size
Bar
Spacing
(in)
Point
Coefficeint from Table
A-11
Mult
(kip-ft)
Total Mult
(kip-ft)
10.00
SLAB
WALL 20.00
Relative
Stiffness
Calc's
Length, 'L'
(ft)
Base, 'b'
(in)
Height, 'h'
(in)
12.00
As ult
(in /ft)
Bar
Size
0.4099.00
9.00
Bar
Spacing
(in)
As
Provided
(in /ft)
Point
Coefficeint from Table
A-11
4.347 0.101
0.2489 0.000 4.793 0.111
17.275 0.000
8.91 41.5565 9.00
Sd
5 9.00 0.409 1.406 -17.275 0.089
6 9.00 0.589 1.406 -24.595 0.213
5 9.00 0.409 1.406
0.154 10.21
-0.0380 0.000 1.130 0.026
7.16 33.3915 9.00 0.409 1.406 17.275 0.108
1.0000 0.000 0.000 0.000 fs
(ksi)
Z
(kips/in)
0.00 0.000 φMn
(kip-ft)
As Min
(in /ft)
5 9.00 0.409 1.406 17.275 0.149 9.82 45.824
0.5696 0.000
-0.0651 0.000 -1.179 0.027
-0.0574 0.000 -3.278 0.076
2.42 11.2725 9.00 0.409 1.406 -17.275 0.036
0.409 1.406 17.275 0.135
5 9.00 0.409 1.406 17.275 0.035 2.32 10.802
0.0547 0.000 3.493 0.081
-0.0392 0.000 -4.524 0.105
-0.0176 0.000 -3.464 0.080
9.27 43.2555 9.00 0.409 1.406 -17.275 0.140
5 9.00 0.409 1.406 -17.275 0.101 6.72 31.343
-0.0048 0.000 1.067 0.025
0.0000 0.000 11.976 0.281
1.54 7.1776 9.00 0.589 1.406 24.595 0.033
6 9.00 0.589 1.406 -24.595 0.107 4.99 23.299
6 9.00 0.589 1.406 24.595 0.375 17.27 80.558
1.406
17.275
17.275 0.000 0.001.0000 0.000 0.000 0.000 0.000
Ratio L/R
Relative
Stiffness
Distrib.
Moment
(k-ft)
As
Provided
(in /ft)
Sd φMn
(kip-ft)
As Min
(in /ft) fs
(ksi)
Z
(kips/in)
54.23%
6.84
5.7712.00
19.75 0.000
0.000
1000.00
1728.00
45.77%
Mult
(kip-ft)
Total Mult
(kip-ft)
47.624
0.2489 0.000 4.981 0.116 9.00 0.409 1.406 17.275
42.3430.5696 0.000 4.429 0.103 0.409 1.406 0.137 9.08
3.85 17.9475 9.00 0.409 1.406
0.409 1.406
17.275 0.058-0.0380 0.000 1.877 0.043
0.0547 0.000 3.812 0.088 7.81 36.44017.275 0.1189.00
5.88 27.421
-0.0651 0.000 -0.331 0.008
-0.0574 0.000 -2.868 0.066
0.68 3.1655 9.00 0.409 1.406 -17.275 0.010
9.86 45.989
-0.0392 0.000 -5.243 0.122
-0.0176 0.000 -6.837 0.159
10.74 50.1265 9.00 0.409 1.406 -17.275 0.163
6 9.00 0.589 1.406 -24.595 0.013 0.60 2.792
-0.0048 0.000 -6.138 0.143
0.0000 0.000 -0.415 0.010
8.85 41.2876 9.00 0.589 1.406 -24.595 0.191
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Fixed Base Moments Reinforcement
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00
T a n k H e ig h t
Bending Moment (k-ft)
Hinged Base Moments Reinforcement
BY: CHECKED BY:
Design Condition No. 3 - Full Tank (Soil Pressure Ignored)
Ring Tension Table - Hinged Base w/ Fixed Top
Note: VR/H =
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
PAGE NO.
DATE:
UT-11178-25
JOB NUMBER:
SUBJECT:
Tank Design
8/9/2026
38,043
70,945
51,242
0.010
0.000
-1
Point
-72
-47
-2.252
-0.480
Coefficeint from Table
A-8
-9.079
Ring
Tension
(lbs/ft)
-5.178 707
0.00
0.22
01,239
KGW
0.46 6
Ring Steel
Required
(in /ft)
12.00
12.0012,105
24,986
-136.51
APPROVED BY:
6.00
6.006
6.00
KGW
DFCM - Utah Department of Corrections
ANT
Fire Storage Tank
0.593
0.527
0.345 71,562
1.16
612.00
6.00
Total Ring
Tension
(lbs/ft) Spa (in)
12.00
6.00 6
1.767
95,426
12.00
6.00
6.00
240.12
6.00
6.00 6.006
12.00
47,7130.884 50.8812.00
Spa (in)
47,713
186.30
217.21
95,426
Size
Concrete
Stress, fc
(psi)
50.88
80.56
6 95,426
0.884
Outside Face
Size
12.00
112.13
47,713
Provided
Tension
(lbs/ft)
Inside Face
47,7130.884
1.767
0.884
95,426
95,426244.09
0.68
1.13
1.767 95,426263.34
1.767
47,7136
612.00
1.767
0.00 6
0.167
0.352 6
-48
-81
-23
6.0062,723
61,026
1.33
1.31
1.767 264.79
140.50
6.00
36,562
12.00 0.884
Ring Steel
Provided
(in /ft)
0.70
0.95
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0 20,000 40,000 60,000 80,000 100,000 120,000
T a n k H e ig h t
Ring Tension (lbs/ft)
Hinged Ring Steel
BY: CHECKED BY:
PAGE NO.
DATE:
UT-11178-25
JOB NUMBER:
SUBJECT:
Tank Design
8/9/2026KGW
APPROVED BY:
KGW
DFCM - Utah Department of Corrections
ANT
Fire Storage Tank
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
Wall Moment Table - Fixed Base w/ Fixed Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H 1.406
1.406
1.406
1.406 -17.275
17.275
1.406
17.275
0.02
1.406
1.406
1.406
24.595 0.000
-20.838 0.496 50.007 fs
(ksi)
Z
(kips/in)
0.00 0.000
0.025 8.792
0.408-17.275
-0.0049 -4.517 0.105 50.006 10.58
7.65
9.00
9.00 0.409
0.409 17.275 0.176
0.140
-0.0058
-0.0001 5.676 0.132 50.000
9.00 0.409 35.686
13.29
-0.0030 3.266 0.076 50.004
49.355
0.118 5-0.007
62.0211.406
0.4099.00
17.275 0.108 8.21 38.279
17.275 0.158 11.91
17.275 0.063 4.782.043 0.047 5 9.00 0.409
0.409
0.0695 0.244 0.006 6 24.595 0.008 0.40
0.0554 0.805 0.019 5 9.00
0.0618 0.033 0.001 6
0.0354
7.590
-0.0030 8.680
0.0057 4.291
-0.0001
0.820
0.0175 2.060
Point
Coefficeint from Table
A-9
Total Mult
(kip-ft)
As ult
(in /ft)
Mult
(kip-ft) Sd
1.406
6.862
0.409
0.0554
0.0000
0.0618
-0.0840.0695
17.275
17.2750.139
0.000
0.002
0.000
0.5890.002
-0.075
0.5896
-0.084
9.00
Wall Moment Table - Hinged Base w/ Fixed Top
1.406
Z
(kips/in)
74.977
1.406
0.00024.595
1.929
Sd
-861.05
0.019 5
1.406 φMn
(kip-ft)
0.12
As Min
(in /ft)
0.00
-9.079
Note: VH = 1,239
As ult
(in /ft)
Bar
Size
Bar
Spacing
(in)
As
Provided
(in /ft)
32.875
0.589 fs
(ksi)
Mult
(kip-ft)
1.92
0.33
0.160
Point
Coefficeint from Table
A-9
Total Mult
(kip-ft)
0.000
-0.075
-24.595
6 0.003
1.406
1.406
9.00
9.00 0.6470.14
0.002 0.575
9.00
9.00
0.100
0.048
0.003
20.33
46.885
8.954
5 9.00
9.00 0.409
0.4099.00 22.506
1.406
0.0251.406 17.275
0.409 16.0717.275
0.133
4.82
10.05
0.064
5 9.00
9.00 48.80
1.406
As Min
(in /ft)
1.520
0.409
0.077
0.271
17.780.236
1.406 17.275
1.406
1.406 1.875
22.321
55.541
1.88
0.589 24.595
1.4060.409
0.101
227.6730.409
-0.021
0.0040.409
0.000
-24.595
0.203
17.275
17.275
0.589
0.000
-0.043
0.000
0.004
-0.067
-0.075
-0.084
-0.067
-0.007
-0.043
0.213
0.409
0.409
9.00
0.177
0.000
0.006
0.007 5
0.000 0.000
0.0354
9.00 0.589
9.00
17.275
9.00
Bar
Diam.
(in)
9.000.007
-0.0049
94.836
82.929
-0.0058
0.0000 6
0.0175 3.503 0.081-0.021
0.0057 5.083
0.001
Bar
Spacing
(in)
As
Provided
(in /ft)
9.00
0.000 φMn
(kip-ft)
0.05 0.254
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Fixed Base Moments Reinforcement
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Hinged Base Moments Reinforcement
BY: CHECKED BY:
PAGE NO.
DATE:
UT-11178-25
JOB NUMBER:
SUBJECT:
Tank Design
8/9/2026KGW
APPROVED BY:
KGW
DFCM - Utah Department of Corrections
ANT
Fire Storage Tank
Revise Moments for Top Slab Moment: Slab Moment = k-ft (From 2-Way Slab Calculations)
Note: This condition assumes that the tank is full of water and experiences vertical soil pressure, but not lateral soil pressure.
Wall Moment Table - Hinged Base w/ Fixed Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
Wall Moment Table - Fixed Base w/ Fixed Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
φMn
(kip-ft)
As Min
(in /ft) fs
(ksi) SdPoint
Coefficeint from Table
A-11
Mult
(kip-ft)
Total Mult
(kip-ft)
As ult
(in /ft)
Bar
Size
Bar
Spacing
(in)
As
Provided
(in /ft)
0.002 6 9.00 0.589
6 9.00 24.595 0.0000.589 1.4060.000 0.000 0.000
Z
(kips/in)
0.00 0.000
0.5751.406 -24.595 0.002 0.120.000 -0.075
0.6470.2489 0.000 -0.084 0.002 6 9.00 0.589
1.0000
0.0547 0.000 0.139 0.003
1.406 -24.595 0.003
0.5696
0.14
9.00 0.409 1.406 17.275 0.025 1.92
5 9.00 0.409 1.406 17.275 0.004 0.33 1.520
8.954
-0.0651 0.000 2.060 0.048 5 9.00 0.409 1.406
-0.0380 0.000 0.820 0.019 5
-0.0574 0.000 4.291 0.100 5 9.00 0.409
17.275 0.064 4.82 22.506
-0.0392 0.000 6.862 0.160
1.406 17.275 0.133 10.05 46.885
5 9.00 0.409 1.406 17.275 0.213 16.07 74.977
-0.0176 0.000 8.680 0.203 5
-0.0048 0.000 7.590 0.177 5 9.00 0.409 1.406
0.271 20.339.00 0.409 1.406 17.275 94.836
0.0770.0000 0.000 0.007 0.000 5 9.00 0.409
17.275 0.236 17.78 82.929
Point
Coefficeint from Table
A-11
Mult
(kip-ft)
Total Mult
(kip-ft)
1.406 17.275 0.000 0.02
As ult
(in /ft)
Bar
Diam.
(in)
Bar
Spacing
(in)
As
Provided
(in /ft)
Sd φMn
(kip-ft)
As Min
(in /ft) fs
(ksi)
1.0000 0.000 0.000 0.000 6 9.00 0.589 1.406
Z
(kips/in)
0.5696 0.000 0.033 0.001 6 9.00 0.589
24.595 0.000 0.00 0.000
1.406 24.595 0.001 0.05 0.254
6 9.00 0.589 1.406 24.595 0.008 0.40 1.8750.2489 0.000 0.244 0.006
-0.0380 0.000 2.043 0.047 5 9.00 0.409 1.406
8.7921.406 17.275 0.025 1.880.0547 0.000 0.805 0.019 5 9.00 0.409
-0.0651 0.000 3.503 0.081 5 9.00 0.409
17.275 0.063 4.78 22.321
1.406 17.275 0.108 8.21 38.279
5 9.00 0.409 1.406 17.275 0.158 11.91 55.541-0.0574 0.000 5.083 0.118
-0.0176 0.000 3.266 0.076 5 9.00 0.409 1.406
62.0211.406 17.275 0.176 13.29-0.0392 0.000 5.676 0.132 5 9.00 0.409
-0.0048 0.000 -4.517 0.105 5 9.00 0.409
17.275 0.101 7.65 35.686
5 9.00 0.409 1.406 -17.275 0.408 48.80 227.6730.0000 0.000 -20.838 0.496
1.406 -17.275 0.140 10.58 49.355
0.000
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Fixed Base Moments Reinforcement
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Hinged Base Moments Reinforcement
BY: CHECKED BY:
Design Condition No. 4: Seismic Loading - Full Tank
Note: This condition assumes that the tank is full of water and experiences vertical soil pressure, but not lateral soil pressure.
Load Case No. 5: 1.2F + 1.0E
Seismic Pressure, p = psf (Total base shear, 'V' divided by the wall height)
Ring Tension Table - Hinged Base w/ Fixed Top pR = lb/ft
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H 50.88
95,426
0.884
380.31
12502.62
12.00
6 6.00
6.00
0.63
81.19
0.42 6
1.37
0.884
6.00
1.767
12.0012.00
1.767
95,426
95,426254.31
95,426
6.00
107.050.884
47,713
204.09
231.16
140.86 47,713
270.06
268.52
60.00
241.66
1.767
6.00
1.767
12.00
95,426
6.00
12.00
12.00
1.767
0.884
Ring Steel
Provided
(in /ft)
134.71
0.884
6.00
47,713
12,363
36,709
1.062
5,369
0.85
1.06
1.14
Ring Steel
Required
(in /ft)
Outside Face
Size
Inside Face
Size Spa (in) Spa (in)
12.0060.23 12.00
12.00
0.429
13,280
13,327
57,201
1.066
0.000
6.00
67,090
61,686
73,157
0.68
1.35
73,812
1.24 6
9,378
6.00
6.00
12,536
Point
13,002
11,818
12,782
13,030
1.022
1.042
Ring
Tension
(lbs/ft)
1.003
Coefficeint from Table
A-6
KGW
45,638
22,912
34,199
1.767
Concrete
Stress, fc
(psi)
12.00
Provided
Tension
(lbs/ft)
Total Ring
Tension
(lbs/ft)
DFCM - Utah Department of Corrections
ANT
SUBJECT:
Tank Design
PAGE NO.
8/9/2026KGW
JOB NUMBER:
Fire Storage Tank
0.989 12,363
1.040
0.945
0.750
DATE:
UT-11178-25
95,426
6.00
47,713
47,713
APPROVED BY:
6.00
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
0 20,000 40,000 60,000 80,000 100,000 120,000
T a n k H e ig h t
Ring Tension (lbs/ft)
Hinged Ring Steel
BY: CHECKED BY:
KGW
DFCM - Utah Department of Corrections
ANT
SUBJECT:
Tank Design
PAGE NO.
8/9/2026KGW
JOB NUMBER:
Fire Storage Tank
DATE:
UT-11178-25
APPROVED BY:
Design for Wall Flexure: H /Dt = pH = lb-ft/ft
Wall Moment Table - Hinged Base w/ Fixed Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
Wall Moment Table - Fixed Base w/ Fixed Top
0.0 H
0.1 H
0.2 H
0.3 H
0.4 H
0.5 H
0.6 H
0.7 H
0.8 H
0.9 H
1.0 H
0.180
0.724
0.263
17.735
0.409
9.006.606 1.000 17.275
6.08
1.028
-0.013
0.000
Mult
(kip-ft)
0.282
1.000
1.000
9.00
0.000
0.024 5
9.000.103
0.409
0.002
0.009
11.73 φMn
(kip-ft) fs
(ksi)
-24.595
As
Provided
(in /ft)
0.00
9.00
0.04
17.2755
0.000
1.000 -24.595 0.203
3.257
9.00 0.589
As ult
(in /ft)
Bar
Size
24.595 0.008 0.50
-17.275 0.113 38.947
2.319
24.595 0.000
0.363
0.70
24.595 0.0001.000
9.00 0.409 1.000
0.071
0.137
28.247
54.744
0.205
0.465
0.000
0.10
0.053 9.00
0.409
0.154
71.263
0.240
6.05
0.409
0.409
17.275
1.000
0.032 2.67
20.93
1.000
17.275
17.275
97.653
12.442
Z
(kips/in)
As Min
(in /ft)
Sd
152,123
Coefficeint from Table
A-4
Total Mult
(kip-ft)
0.001-0.050
1.0000.409
1.000
0.007
0.162
0.059
0.589
0.5890.015
0.000
Bar
Spacing
(in)
9.00
9.00 φMn
(kip-ft)
9.00 0.589
Point
Coefficeint from Table
A-4
0.0048
0.0001
-0.0240
-0.0072
0.0000
4.412
0.0017 7.703
0.0035 2.302
0.326
0.536
0.734
0.0021
0.0048
0.0011
0.0004
Point
-1.090
-3.644
Total Mult
(kip-ft)
0.00 0.000
15.280.168
Mult
(kip-ft)
5.416 0.126
0.084
Bar
Diam.
(in)
Bar
Spacing
(in)
-3.638
As ult
(in /ft)
As Min
(in /ft)
9.00
As
Provided
(in /ft)
1.000
Sd
8.350.4099.00 fs
(ksi)
Z
(kips/in)
17.275
1.000 0.001 0.0824.5956
0.0000 0.000 0.000
9.00 0.589
6 1.0000.000
0.0150.0001 0.043 0.001
0.0011 0.852 0.020 5
9.00 0.5890.0004 0.268 0.006 6
1.000 17.275 0.026 2.26 10.530
0.059
0.162
17.275 0.064 5.53 25.8090.0021 2.077 0.048 50.326
0.0035 3.539 0.082 5 9.00 0.409 1.0000.536
9.00 0.409
17.275 0.109 9.44 44.021
0.0048 5.589 0.130 50.724
0.0048 5.091 0.118 50.734 9.00
0.0017 3.063 0.071 50.263 9.00
14.96
0.095 8.251.000 17.2750.409
9.00 1.000 0.173 69.772
0.408
13.08 61.021
9.00 0.409
1.000
1.000
-0.0072 -4.961 0.115 5-1.090
38.503
0.409
-0.0240 -21.505 0.513 5-3.644
9.00 0.409
9.00
57.17 266.696-17.275
-17.275 0.154
1.000 13.590.409 63.40017.275 0.158
0.409 17.275
1.000
1.000
82.727
17.275
0.000
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Fixed Base Moments Reinforcement
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
-30.00 -20.00 -10.00 0.00 10.00 20.00 30.00
T a n k H e ig h t
Bending Moment (k-ft)
Hinged Base Moments Reinforcement
BY: CHECKED BY:
Concrete Column Spiral Reinforcement Design
Inputs:
f'c psi Concrete Compressive Strength fyt psi Yield Strength of Transverse Reinforcement
Ties Spiral Bar Size
Dc in Diameter of Column
Ds in Diameter of Spiral Reinforcement
Dagg in Nominal Max Size of Coarse Aggregate
Solution:
Ag in
Cross sectional area of Column
Ach in
Cross sectional area of transverse reinforcement
Asp in
Area of trasnverse reinforcement
Required Transverse Reinforcement (ACI 318-19 25.7.3.3) s_req in Required transverse reinforcement pitch s_max in Max allowable transverse reinforcement pitch
S_min in Min allowable transverse reinforcement pitch s in Provided pitch of spiral
Use #4 spiral with 3" pitch
0.20
1.3333
1.00
254.47
176.71
KGW
APPROVED BY:
5,000
60,000
#4
18.00
15.00
KGW
DATE:
8/9/2026
DFCM - Utah Department of Corrections
JOB NUMBER:
UT-11178-25
PAGE NO.
Fire Storage Tank
SUBJECT:
Tank Design
ANT
Concrete Column LIC# : KW-06014224,…
This is the start of the file's text. The full file is on GovTribe.