9-2-CR26075-26308480 Approved Plans.pdf
PDF 10 MB Posted
- Solicitation number
- CR26075
- Issued by
- Utah
About this file
Summary
This is an approved plans document and bid package for a Stage II construction project issued by the Utah Division of Facilities Construction and Management (DFCM) on behalf of the Utah National Guard for the American Fork Armory Latrine Remodel located at 251 South 200 East, American Fork, UT 84003. The project involves complete renovation and reconfiguration of the existing men's and women's restrooms, including full demolition of existing facilities, improved janitorial space, modified kitchen space, revised electrical distribution, plumbing upgrades, and removal and replacement of HVAC equipment serving the restrooms. The scope qualifies as a Level 2 Alteration under the 2021 International Existing Building Code, with all interior work occurring within the existing building footprint and minor patching and roof repairs for new and reused roof penetrations. The construction cost estimate is $813,054.00. Only contractors prequalified under Stage I and currently listed on the DFCM Prequalified Contractors list as of the solicitation date are eligible to bid. The permit set is dated 05.11.2026, and the project is designed to increase plumbing fixture and shower quantities to meet current code requirements and Utah National Guard drill weekend operational needs.
The approved plans package includes comprehensive architectural, mechanical, plumbing, and electrical drawings with detailed specifications for demolition, new construction, accessibility compliance, roof modifications, and finish schedules. General notes establish contractor responsibilities for coordinating all subcontractors and trades, field-verifying existing conditions, protecting existing fire-rated assemblies and wood flooring systems, and ensuring compliance with all applicable codes including the International Building Code, Plumbing Code, Mechanical Code, Fire Code, Energy Conservation Code, and Accessibility Code. The project requires temporary construction protection systems over existing wood gymnasium flooring, coordination with mechanical and electrical equipment relocations, and compliance with ADA accessibility requirements throughout the restroom renovations.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IND
USTRY
T H E
G R E A T
S E
A L
OF THE
S
T A T E
O F
U T A H
State of Utah-Department of Administrative Services
DIVISION OF FACILITIES CONSTRUCTION
AND MANAGEMENT
4315 South 2700 West, Floor 3/Taylorsville, Utah 84129-2128
BID PACKAGE GENERAL NOTES
A. THIS BID PACKAGE SHALL BE BID IN ITS ENTIRETY. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO REVIEW AND COORDINATE THE WORK OF ALL SUB-CONTRACTORS,
TRADES AND SUPPLIERS WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS
BEFORE COMMENCING CONSTRUCTION, AND TO ASSURE THAT ALL PARTIES ARE
AWARE OF ALL REQUIREMENTS, REGARDLESS OF WHERE THE REQUIREMENTS OCCUR
IN THE CONTRACT DOCUMENTS, WHICH MIGHT AFFECT THE WORK OF THAT PARTY.
B. AS PART OF THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE THE WORK OF ALL
SUB-CONTRACTORS, TRADES AND SUPPLIERS, THE CONTRACTOR SHALL ENDEAVOR
TO IDENTIFY AND NOTIFY THE ARCHITECT OF ANY DISCREPANCIES OR CONFLICTS
BETWEEN THE WORK OF DIFFERENT PARTIES AT THE EARLIEST POSSIBLE DATE SO AS
TO ALLOW REASONABLE AND ADEQUATE TIME FOR THE CONFLICT TO BE RESOLVED
WITHOUT DELAYING THE WORK. ALL DEVIATIONS FROM THAT WHICH IS REQUIRED BY
THE CONTRACT DOCUMENTS MUST BE APPROVED IN ADVANCE BY THE ARCHITECT.
C. IN CASE OF ANY DISCREPANCY WITHIN THE CONTRACT DOCUMENTS, THE MOST
STRINGENT REQUIREMENT OR MOST COSTLY OPTION SHALL APPLY, UNLESS
CLARIFICATION IS SOUGHT IN WRITING AND RECEIVED FROM THE ARCHITECT PRIOR
TO BIDDING. THE CONTRACTOR SHALL BRING ANY KNOWN DISCREPANCIES TO THE
ATTENTION OF THE ARCHITECT AS SOON AS POSSIBLE, AND IN ANY EVENT, PRIOR TO
COMMENCING AFFECTED WORK.
D. THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE OF ANY CONFLICTS
BETWEEN VENDOR DRAWINGS AND THE CONTRACT DOCUMENTS. THE LATEST
VENDOR DRAWINGS SHALL GOVERN AND BE VERIFIED WITH THE OWNER AND THE
ARCHITECT.
E. THE ARCHITECTURAL DRAWINGS TAKE PRECEDENCE IN ESTABLISHING AND
COORDINATING THE FINISHED APPEARANCE AND EXACT LOCATION OF ALL EXPOSED
ELEMENTS OF THE WORK OF ALL TRADES, INCLUDING THAT WORK WHICH IS
ILLUSTRATED PRIMARILY ON DRAWINGS OF OTHER DISCIPLINES. QUANTITIES ARE TO
BE PROVIDED AS SHOWN ON DRAWINGS OF OTHER DISCIPLINES, BUT LOCATIONS
SHOWN ON OTHER DRAWINGS ARE SUBJECT TO COORDINATION WITH THE
ARCHITECTURAL DRAWINGS WHERE SUCH ITEMS ARE SHOWN, UNLESS OTHERWISE
NOTED ON THE ARCHITECTURAL DRAWINGS.
F. EXCEPT WHERE DIRECTED TO PLACE ITEMS OF WORK AT THE APPROXIMATE
LOCATION SHOWN, DO NOT SCALE DRAWINGS FOR DIMENSIONAL INFORMATION. NOT
ALL ELEMENTS OF THE DRAWINGS MAY BE DRAWN TO EXACT SCALE. ALL REQUIRED
DIMENSIONS ARE SHOWN OR MAY BE DERIVED FROM THOSE SHOWN ON THE
DRAWINGS, SCHEDULES AND SPECIFICATIONS. IF DIMENSIONS ARE NOT PRESENT, THE
ARCHITECT IS TO BE NOTIFIED SO THAT A CLARIFICATION CAN BE ISSUED. DIMENSIONS
ARE TO BE COORDINATED WITH ALL DISCIPLINES, VENDORS AND OWNER-FURNISHED
EQUIPMENT, FURNITURE AND DEVICES TO ASSURE PROPER PLACEMENT AND
WARRANTY REQUIREMENTS.
G. ALL CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CODES, ORDINANCES AND
REGULATIONS. SEE THE GI-SERIES SHEETS FOR PARTIAL REGULATORY INFORMATION,
INCLUDING CODE COMPLIANCE TABLES, RATED ASSEMBLY TYPES AND TYPICAL
ACCESSIBILITY CLEARANCE AND COMPLIANCE REQUIREMENTS.
H. THE CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND THEIR
COMPATIBILITY WITH NEW CONSTRUCTION, AND COORDINATE ANY DISCREPANCIES
WITH THE ARCHITECT PRIOR TO PROCEEDING WITH AFFECTED WORK.
I. THE CONTRACTOR SHALL PROTECT ALL EXISTING FIRE-RESISTANCE-RATED
ASSEMBLIES AND SPRAY-APPLIED STRUCTURAL FIREPROOFING FROM DAMAGE.
PATCH AND FULLY REPAIR ANY DAMAGE TO SUCH ITEMS, WHETHER EXISTING OR
CAUSED BY NEW CONSTRUCTION OR DEMOLITION ACTIVITIES, TO LIKE-NEW
CONDITION IN ACCORDANCE WITH THE ORIGINAL LISTED SYSTEMS. SEAL ALL EXISTING
AND NEW ASSEMBLY PENETRATIONS WITH LISTED FIRE-RESISTANCE-RATED
ASSEMBLIES, WHERE OCCUR, TO MAINTAIN THE INTEGRITY OF THE ASSEMBLIES.
J. ALL UNUSED FLOOR SLAB PENETRATIONS 36 SQUARE INCHES OR LESS IN AREA ARE
TO BE INFILLED USING 4,000 PSI CONCRETE FOR THE FULL DEPTH OF THE EXISTING
SLAB. COORDINATE WITH ARCHITECT FOR INFILL OF LARGER OPENINGS.
CONTACT: E-MAIL:
PHONE: INTERNET:
AGENCY
Utah National Guard 12953 South Minuteman Drive
Draper, UT 84020
801.471.9696
Jonathan Butler jonathan.d.butler21.nfg@army.mil http://www.guard.utah.gov
CONTACT: E-MAIL:
PHONE: INTERNET:
ARCHITECT
Architectural NEXUS, Inc.
2505 East Parleys Way
Salt Lake City, UT 84109
801.924.5000
Stephen Springer sspringer@archnexus.com http://www.archnexus.com
CONTACT: E-MAIL:
PHONE: INTERNET:
STRUCTURAL ENGINEER
Structural Design Studio 2225 East Murray Holladay Rd., Suite 100
Salt Lake City, UT 84117
801.274.3950
Jake Merkley jake@structuralds.com http://www.structuralds.com
CONTACT: E-MAIL:
PHONE: INTERNET:
MECHANICAL ENGINEER
LYNK Engineers 505 East South Temple, Suite 100
Salt Lake City, UT 84102
801.505.5417
Mike Dallon Mike.Dallon@LynkEngineers.com http://www.lynkengineers.com
NEXUS PROJECT #: DFCM PROJECT #: 26308480
VICINITY MAP
PROJECT LOCATION
PROJECT DESCRIPTION:
DFCM APPROVAL
UTAH NATIONAL GUARD
AMERICAN FORK ARMORY
LATRINE REMODEL
251 South 200 East, American Fork, UT 84003
PERMIT SET
05.11.2026
25057
The American Fork Armory Latrine Remodel project renovates and reconfigures the existing men’s and women’s restrooms—originally built circa 1954 and previously upgraded in 2009 renovation (abatement), 2023 Electrical upgrades and
2024 Roofing System Replacement—to increase plumbing fixture and shower quantities to meet current code requirements and Utah National Guard drill weekend operational needs, including full demolition of existing restrooms, improved janitorial and modified existing kitchen space, revised electrical distribution, plumbing, removal and replacement of upgraded HVAC equipment serving the restrooms; all interior work occurs within the existing building footprint with minor patching and repairs of the existing roof system for new and/or reused roof penetrations, with no change to the building’s occupancy classification or occupant loads. This project qualifies as a Level 2 Alteration under the 2021 International Existing Building Code.
CONTACT: E-MAIL:
PHONE: INTERNET:
ELECTRICAL ENGINEER
LYNK Engineers 505 East South Temple, Suite 100
Salt Lake City, UT 84102
801.231.7025
Tyler Squire Tyler.Squires@LynkEngineers.com http://www.lynkengineers.com
CONTACT: E-MAIL:
PHONE: INTERNET:
OWNER
Utah DFCM 43145 South 2700 West, Fl. 3
Taylorsville, UT 84129
801.960.7647
Randy Mellor rmellor@utah.gov http://www.dfcm.utah.gov
INTERNATIONAL PLUMBING CODE
NATIONAL ELECTRICAL CODE
ZONING ORDINANCE:
INTERNATIONAL MECHANICAL CODE
INTERNATIONAL FIRE CODE
INTERNATIONAL ENERGY CONSERVATION CODE
INTERNATIONAL BUILDING CODE / EXISTING INTERNATIONAL BUILDING CODE
ACCESSIBILITY CODE
DESIGN CRITERIA
APPLICABLE CODES
OTHER CRITERIA
DEFERRED SUBMITTALS
PAM 415-12 ARMY NATIONAL GUARD FACILITIES ALLOWANCES
FIRE ALARM SYSTEM - 90 DAYS AFTER PERMIT
CURRENT
REMODEL LOCATION - EXISTING LEVEL 01
E A
S T
200 SOUTH
REFER TO SHEET GI101
No.
8182456
TYLER
SQUIRE
L
IC
E N
S E D
PROFESS IONAL
E N G
I N E
E R
STATE OF UTAH
04/20/2026
P R
O
FESS IONA L ENG
IN
E
E R
S
T A T E O F UT A
H
No. 318584-2202
Michael E. Dallon
04/20/2026 l:
04/30/2026
T
CR H IT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
05-11-26
STEPHEN M.
No. 7655609-0301
SPRINGER
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
06/08/2026
REVIEWED FOR CODE
COMPLIANCE
MATCH LINE
A1 / Axxx
MATCH LINE TAG
EXISTING WALL TO REMAIN
WALL TO BE DEMOLISHED
NEW WALL
BREAK LINE
CENTER LINE SYMBOL
0' x' y' z'
REVISION DESIGNATION
ELEVATION SYMBOL
REVISION NUMBER
ELEVATION ABOVE DATUM
ELEVATION DESCRIPTION
DRAWING SYMBOL LEGEND
CASEWORK TYPE DESIGNATION
CDS NUMBER (M DENOTES
MODIFICATION - SEE SHEET
A551 FOR MODIFIED MILLWORK
ELEVATIONS AND DETAILS)
AWS STANDARD CDS NUMBERING SYSTEM
WIDTH
HEIGHT DEPTH
NORTH ARROW
PLAN NORTH
GRAPHIC SCALES
ROUND BREAK LINE
REVISION CLOUD
SLOPE INDICATION
##" / 12"
DETAIL REFERENCE
A2 A401
A1
A3
INTERIOR ELEVATIONS
DETAIL NUMBER
SHEET NUMBER
A1 A501
DETAIL REFERENCE
DETAIL NUMBER
SHEET NUMBER
A1 A201
EXTERIOR ELEVATION REFERENCE
SHEET NUMBER
DETAIL NUMBER
A1 A302
WALL SECTION REFERENCE
SHEET NUMBER
DETAIL NUMBER
A1 A301
BUILDING SECTION REFERENCE
DETAIL NUMBER
SHEET NUMBER
ROOM DESIGNATION (FLOOR PLAN)
ROOM NUMBER
ROOM NAME
A1 A301
DETAIL NUMBER
SHEET NUMBER
ROOM DESIGNATION (REFLECTED
CEILING PLAN)
CEILING HEIGHT ABOVE FINISH FLOOR
ROOM NUMBER
GLASS TYPE DESIGNATION
KEYED NOTE DESIGNATION
ASSEMBLY TYPE DESIGNATION
EQUIPMENT DESIGNATION
WINDOW DESIGNATION
DOOR DESIGNATION
GLASS TYPE
EQUIPMENT NAME
KEY NOTE NUMBER
WINDOW TYPE
DOOR NUMBER
ASSEMBLY TYPE (FLOOR, WALL, CEILING, ROOF)
MATERIAL TYPE DESIGNATION
FINISH TYPE
SEE AI601 FINISH LEGEND
RISE
RUN
TRUE NORTH
CL
DETAIL / SHEET NUMBER
Room Name
### SF
EQUIPMENT MARK#####
DESCRIPTION
100'-0"
T.O. WALL
###M #W
#H
#D
MODIFICATION DESCRIPTION
xx" = 1'-0" GRAPHIC SCALE
A1 A301
12"
ROOM AREA
LIST OF ABBREVIATIONS
THE PRECEDING LIST OF ABBREVIATIONS
IS PRESENTED AS A GENERAL GUIDE AND
DOES NOT NECESSARILY SHOW ALL
ABBREVIATIONS USED. OTHER
GENERALLY ACCEPTED ABBREVIATIONS
MAY BE FOUND AMONG THE DRAWINGS -
SOME ABBREVIATIONS SHOWN ABOVE
MAY NOT BE USED WITHIN THIS DRAWING
SET.
A
A/C AIR CONDITIONING
ACT ACOUSTICAL CEILING TILE
APC ACOUSTICAL PANEL CEILING
AD AREA DRAIN
AFC ABOVE FINISHED CEILING
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ALUM ALUMINUM
ANOD ANODIZED
ARCH ARCHITECT
@ AT
B
BD BOARD
BLDG BUILDING
BO BOTTOM OF
C
C CELSIUS
CH COAT HOOK
CFCI CONTRACTOR FURNISHED,
CONTRACTOR INSTALLED
CG CORNER GUARD
CI CONTINUOUS INSULATION
CJ CONTROL JOINT
CL CENTERLINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONT CONTINUOUS
CORR CORRIDOR
CT CERAMIC TILE
CTJ CONSTRUCTION JOINT
D
D DEEP
DEG DEGREE
DEMO DEMOLITION
DF DRINKING FOUNTAIN
DIA DIAMETER
DIM DIMENSION
DN DOWN
DS DOWNSPOUT
DWGS DRAWINGS
E
(E) EXISTING
EA EACH
EJ EXPANSION JOINT
EIFS EXTERIOR INSULATION AND FINISH
SYSTEM
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
EOS EDGE OF SLAB
ERD EXISTING ROOF DRAIN
EQ EQUAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
F
F FAHRENHEIT
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
FDC FIRE DEPARTMENT CONNECTION
FD FLOOR DRAIN
FEC FIRE EXTINGUISHER CABINET
FE FIRE EXTINGUISHER
FE FINISHED EDGE
FG FINISH GRADE
FHC FIRE HOSE CABINET
FIN FINISH
FLR FLOOR
FND FOUNDATION
FO FINISHED OPENING
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FOS FACE OF STUD
FOW FACE OF WALL
FRG FIBER REINFORCED GYPSUM
FSP FIRE STANDPIPE
FT FEET
FV FIELD VERIFY
G
GA GAUGE
GALV GALVANIZED
GFRC GLASS-FIBER-REINFORCED
CONCRETE
GFRG GLASS-FIBER-REINFORCED GYPSUM
GL GLASS
GWB GYPSUM WALL BOARD
GYP GYPSUM
H
H HIGH
HB HOSE BIBB
HDR HEADER
HM HOLLOW METAL
HR HOUR
HT HEIGHT
I
ID INSIDE DIAMETER; INSIDE DIMENSION
IN INCH
INFO INFORMATION
INT INTERIOR
J
JAN JANITOR
K (NOT USED)
L
LAB LABORATORY
LAV LAVATORY
LBS POUNDS
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
M
MACH RM MACHINE ROOM
MAX MAXIMUM
MFR MANUFACTURER
MECH MECHANICAL
MEZZ MEZZANINE
MIN MINIMUM
MO MASONRY OPENING
N
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NOM NOMINAL
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER;
OUTSIDE DIMENSION
OFD OVERFLOW DRAIN
OH DR OVERHEAD DOOR
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OPH OPPOSITE HAND
OPP OPPOSITE
OFOI OWNER FURNISHED, OWNER INSTALLED
ORIG ORIGINAL
P
P LAM PLASTIC LAMINATE
PLAS PLASTER
PLUMB PLUMBING
PR PAIR
PSI POUNDS PER SQUARE INCH
PSF POUNDS PER SQUARE FOOT
Q
QT QUARRY TILE
R
R RISER
RAD RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIDGERATOR
REQD REQUIRED
REV REVISION
RH RELATIVE HUMIDITY
RM ROOM
RO ROUGH OPENING
RTU ROOF TOP UNIT
RWL RAIN WATER LEADER
S
S SMOKE DETECTOR
SAM SELF ADHESIVE MEMBRANE
SCHED SCHEDULE
SECT SECTION
SIM SIMILAR
SPEC SPECIFICATION
SS STAINLESS STEEL
STD STANDARD
STRUCT STRUCTURAL
T
T TREAD
TEL TELEPHONE
TEMP TEMPORARY
THK THICK
TOC TOP OF CONCRETE
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOS TOP OF SLAB; TOP OF STEEL
TOW TOP OF WALL
TYP TYPICAL
TO TOP OF
U
UL UNDERWRITER'S LABORATORIES
UNO UNLESS NOTED OTHERWISE
V
VCT VINYL COMPOSITE TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
W
W/ WITH
W/O WITHOUT
WD WOOD
WH WALL HYDRANT
WP WORKING POINT
WRB WEATHER RESISTIVE BARRIER
X,Y,Z (NOT USED)
CAST-IN-PLACE CONCRETE
CONCRETE MASONRY UNIT
PRECAST CONCRETE / GLASS FIBER
REINFORCED CONCRETE (GFRC)
BRICK VENEER
RIGID INSULATION
BATT INSULATION
CONTINUOUS MATERIAL
NON CONTINUOUS MATERIAL
(BLOCKING)
GYPSUM BOARD
PLYWOOD
UNDISTURBED EARTH
GRAVEL
HATCH LEGEND
NOTE: HATCHING ANGLES MAY VARY DUE TO ANGLE OF WALL DRAWN, WHILE HATCHING PATTERN REMAINS SIMILAR.
BACKFILL OR FILL
EXTERIOR SHEATHING
T
CR HIT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
05-11-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:2
:1
P M
A u to d e sk
D o c s:
U T
N G
A F
A rm o ry
L a tr in e R e m o d e l_ r2
/A R
C H
_2
-A m e ri c a n
F o rk A rm o ry L a tr in e
R e m o d e l_
.r v t
SHEET INDEX &
GENERAL
INFORMATION
MC
S o u th
E a s t, A m e ri c a n F o rk
U
T
U T
A H
N A
T
IO
N A
L G
U A
R D
25057
05.11.2026
PERMIT SET
GI001
AHW
A M
E R
IC
A
N F
O R
K A
R M
O R
Y
L A
T R
IN
E
R E
M O
D E
L
GENERAL:
GI000 COVER SHEET
GI001 SHEET INDEX & GENERAL INFORMATION
GI101 CODE ANALYSIS, EXITING AND OCCUPANCY PLAN
GI501 ASSEMBLY TYPES
GI701 ACCESSIBILITY COMPLIANCE
ARCHITECTURAL:
AD111 ENLARGED RESTROOM DEMOLITION PLANS &
DETAILS
AE111 RESTROOM FLOOR AND REFLECTED CEILING
PLANS
AE112 INTERIOR ELEVATIONS
AE120 ROOF PLAN AND DETAILS
AE501 ARCHITECTURAL DETAILS
AE601 DOOR SCHEDULE & TYPES
AE701 TYPICAL DETAILS
AI601 FINISH PLAN & SCHEDULES
AI701 TYPICAL FINISH DETAILS
MECHANICAL:
M-001 MECHANICAL LEGEND, SYMBOLS &
ABBREVIATIONS
MH101 LEVEL 1 MECHANICAL PLANS
MH102 LEVEL 2 MECHANICAL PLANS
MH501 MECHANICAL DETAILS
MH601 MECHANICAL SCHEDULES
PLUMBING:
P-001 PLUMBING LEGEND, SYMBOLS & ABBREVIATIONS
PL100 UNDERGROUND PLUMBING PLAN
PL101 LEVEL 1 PLUMBING PLAN
PL102 LEVEL 2 PLUMBING PLAN
PL501 PLUMBING DETAILS
ELECTRICAL:
E-001 ELECTRICAL LEGEND, SYMBOLS & ABBREVIATIONS
EP100 LEVEL 1 OVERALL POWER PLAN
EP101 LEVEL 1 POWER PLAN
EL101 LEVEL 1 LIGHTING PLAN
EY101 LEVEL 1 SYSTEMS PLAN
E-501 ELECTRICAL DETAILS
E-601 ELECTRICAL SCHEDULES
E-602 ELECTRICAL SCHEDULES
SHEET INDEX
# Date Revision
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
06/08/2026
North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a
3) Three Story: A (3)______
2) Two Story: A (2)______
1) One Story: ______
c) Total Allowable Area for:
1_< Allowable Area
Actual Area
b) Sum of the Ratio Calculations for Mixed Occupancies:
a)
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
e) Drinking Fountains: ______ Service Sinks: ______
d) Bath Tubs or Showers: ______
c) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) ______
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: __________ Exit Width Provided: ____________
Element Hours Assembly ListingListing
Element AssemblyHours
Smoke Partitions
Fire Partitions
Exterior Bearing Walls
Interior Bearing Walls
Exterior Non-Bearing Walls
Structural Frame
Partitions - Permanent
Fire Barriers
Floors - Ceiling Floors
Roofs - Ceiling Roofs
Exterior Doors and Windows
Shaft Enclosures
Fire Walls
BAHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: __________________________________
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:J:
Tabular Area:I:
per Floor (square feet): ____________________________________Actual AreaH:
Number of Stories: ______ Building Height: ______G:
Required: ______ Provided: ______
Sprinklers:F:
Mixed Occupancies: ______ Nonseparated Uses: ______E.
separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance RatingD.
C. Type of Construction (circle one):
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guildelines
ADA Accessibility
Building Conservation
Uniform Code for
National Electrical Code
Conservation Code
International Energy
International Fire Code
International Plumbing Code
International Mechanical Code
International Building Code
A. Occupancy and Group: ________ ________ ________ ________ ________
International Fuel Gas Code
Type of Sprinkler System (IBC 903.3.1)__________________
b) Urinals - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
(table 503): ____________________________________________
CODE ANALYSIS
APPLICABLE CODES
Year Year
1. SEE WALL TYPES ON FLOOR PLANS AND RATED
WALL ASSEMBLIES IN GI500s SHEET SERIES FOR
SPECIFIC WALL CONSTRUCTION TO ACHIEVE THE
RATINGS SHOWN ON THIS PLAN.
GENERAL NOTES - REGULATORY PLANS
361 SF
(E) KITCHEN
471 SF
MEN'S
RESTROOM
63 SF
JANITOR
348 SF
WOMEN'S
RESTROOM
(E)
ASSEMBLY
ROOM N.I.C.
(U.N.O.)
(E) STRONG
ROOM N.I.C.
(E)
VESTIBULE
N.I.C.
(E) SUPPLY
ROOM N.I.C.
7047 SF
(S-1)
OCCUPANCY LEGEND
Assembly w/o Fixed Seating:
Concentrated (Existing)
Business Areas (Existing)
Moderate-hazard Storage (Existing)
5332 SF
A-3
561 SF
S-1
508 SF
B
3349 SF
B
NOTE TO PLAN REVIEWER: NO FIRE SEPARATION REQUIRED PER 2009 RENOVATION CODE ANALYSIS; SEE CODE ANALYSIS TABLE.
COMMON PATH OF TRAVEL
COMMON PATH OF TRAVEL DISTANCE PER
TABLE 1006.2.1, WITHOUT SPRINKLERS:
OCCUPANCY
MAX. TRAVEL
DISTANCE
BUSINESS AREAS (OL<30) (B) 100'
ASSEMBLY (A-3) 75'
PATH OF TRAVEL
OCCUPANCY TAG
FIRE EXTINGUISHERS
COORDINATE TYPE AND LOCATION
WITH LOCAL FIRE MARSHALL
ROOM NUMBER
ROOM NAMERoom Name
### SF ROOM AREA
FEC
FIRE EXTINGUISHER CABINET; CLASS A-B-C
2021 2023
2010Guidelines
A-3
X X
NO
D 90
EXP. C
AMERICAN FORK ARMORY LATRINE REMODEL
0/1* 0 0 0
YES
NO* NO
N/A
2 23'
REDUCTION - ONE EXISTING OFFICE AREA AND PARTIAL KITCHEN
AREA CONVERTED INTO ENLARGED RESTROOM AREAS
2 1
N/A N/A
ICC A117.1
Type III-B Construction, per IBC 2021, Table 601
L1 = 18,002 (E), L2 = 5,875 (E)
AREA OF REMODEL = +/-1,023 (F.V.)
Aa = {At + [ NS x If ] } If = [ F/P - 0.25 ] W / 30
B
(No reduction in plumbing count)
15,789
31, 578
N/A
X
N/A
N/A
N/A N/A N/A
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
EXISTING
N/A - NO CHANGE N/A - NO CHANGE
4 (E) 1(E) 6 (N) 3 (N)
3 (E) N/A 6 (N) N/A
3 (E) 1 (E) 5 (N) 3 (N)
S-1
International Existing Building Code
*1 hr at existing S-1 Occupancy with fire separation distance of 13'
*The State Building Official determined that the 2009 alternation would not trigger a requirement for installing a new automatic sprinkler system throughout the existing building. Although the floor area and the fire area in the existing building exceeded the current allowable areas for the most restrictive non-separated occupancy (A-3), a new automatic sprinkler system would not be justified or required due to the limited impact of the alteration on the existing building.
(E) = EXISTING (To be removed)
(N) = NEW
0 REQUIRED, 4 (E), 9 (N)
9,500 + 6,289 = 15,789
9,500 (A-3 MOST RESTRICTIVE)
540/942 - 0.25 X 1 = 0.662
EXISTING
N/A (NON-SEPARATED OCCUPANCIES)
PROPOSED STAGING AREA
WITH SECURED DUMPSTERS
AND PORTABLE RESTROOM;
SURROUND WITH TEMPORARY
CONSTRUCTION FENCING
(MESH WITH OPAQUE SCREEN)
TEMPORARY
RESTROOM/SHOWER
FACILITIES DURING
CONSTRUCTION - PROVIDED
BY AND FOR OWNER ONLY
(E) SECURED AREA
(E) FENCING AND ACCESS
GATE - KEEP CLEAR
NONSTRUCTURAL COMPONENT CHECKLIST
ITEM DESCRIPTION
ON CONSTR.
DOCUMENTS
DEFERRED
SUBMITTAL COMMENTS
ARCHITECTURAL COMPONENTS:
INTERIOR NONSTRUCTURAL WALLS &
PARTITIONS
CEILINGS (I.E. SUSPENDED GRID OR HARD-LID)
MEP COMPONENTS:
MECHANICAL EQUIPMENT (I.E. HVAC, FANS,
AIR HANDLERS, BOILERS, FURNACES, TANKS,
CHILLERS, WATER HEATERS, HEAT
EXCHANGERS, EVAPORATORS, ENGINES,
TURBINES, PUMPS, COMPRESSORS, MFR
EQUIPMENT, ETC.)
LIGHTING FIXTURES
PIPING & CONDUIT SYSTEMS
DUCTWORK (INCLUDING IN-LINE COMPONENTS)
NOTES:
1. Deferred submittals for seismic restraint of nonstructural components must be submitted to the DFCM Building Official a minimum of two weeks prior to the planned installation in order to allow for plan review and forwarding to inspectors. In the event that the submittal is deficient additional time may become necessary.
2. When seismic restraint of non-structural components is installed prior to receiving DFCM approval it shall not be covered or concealed until receiving both plan review and inspection approval. Further, installers are proceeding at their own risk until plan review and inspection approval occurs.
3. The requirements for seismic restraint of nonstructural components cannot be satisfied by a general reference to Design Manuals. The design professional may utilize these manuals as a basis of their design, but must provide all supporting documentation to ensure that the design conforms to the requirements of ASCE 7-05, Chapter 13.
4. Submittals must include details of the proposed seismic restraint of nonstructural components. These details must show specific information relating to the materials, type, size, and locations of anchorages; materials used for bracing; attachment requirements of bracing to structure and component;
and locations of transverse and longitudinal sway bracing and rod stiffeners. Submittals may also require structural calculations, engineering reports, test data, and/or specifications to ensure code compliance.
T
CR HIT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
05-11-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:2
:2
P M
A u to d e sk
D o c s:
U T
N G
A F
A rm o ry
L a tr in e R e m o d e l_ r2
/A R
C H
_2
-A m e ri c a n
F o rk A rm o ry L a tr in e
R e m o d e l_
.r v t
CODE ANALYSIS,
EXITING AND
OCCUPANCY
PLAN
CG
S o u th
E a s t, A m e ri c a n F o rk
U
T
U T
A H
N A
T
IO
N A
L G
U A
R D
25057
05.11.2026
PERMIT SET
GI101
ST
A M
E R
IC
A
N F
O R
K A
R M
O R
Y
L A
T R
IN
E
R E
M O
D E
L
1/8" = 1'-0"GI101
A6 LEVEL 01 - OCCUPANCY & EXITING PLAN
EGRESS PATH LENGTHS
PATH #
COMMON PATH
OF TRAVEL
LONGEST PATH
OF TRAVEL
1 51' - 3" 104' - 2"
2 34' - 5" 67' - 7"
3 42' - 6" 95' - 6"
0' 8' 16' 24'
1/8" = 1'-0" GRAPHIC SCALE
T H
IS
S
H E
E T
T O
B E
P R
IN
T
E D
IN
C
O
LO
R
NOT TO SCALEGI101
A2 STAGING PLAN
# Date Revision
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
06/08/2026
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
T1 N/A N/A N/A N/A
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
F1 N/A N/A N/A N/A
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
S3 N/A N/A N/A N/A
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
S3A N/A N/A STC 45 *needs test info*
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
S3GA
N/A N/A
STC 30 N/A
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
S3G N/A N/A N/A N/A
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
3 5/8" METAL STUD FRAMING @ 16"
O.C. MAX
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
3 5/8" METAL STUD FRAMING @ 16"
O.C. MAX
ACOUSTIC SEALANT EACH
SIDE AT TOP AND BOTTOM
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
3 5/8" METAL STUD FRAMING @ 16"
O.C. MAX
3 5/8" METAL STUD FRAMING @ 16"
O.C. MAX
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
S6A45 N/A N/A STC 45 *needs test info*
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
S6 N/A N/A N/A N/A
ACOUSTIC SEALANT EACH
SIDE AT TOP AND BOTTOM
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
6" METAL STUD FRAMING @ 16"
O.C. MAX
3 1/2" SOUND ATTENUATION
BLANKET
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
6" METAL STUD FRAMING @ 16"
O.C. MAX
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
FIBERGLASS REINFORCED PANEL;
SEE FINISH LEGEND FRP1
CERAMIC TILE OVER THIN SET
MORTAR BED. SEE FINISH
SCHEDULE AND INTERIOR
ELEVATIONS FOR EXTENTS, SIZE
AND TYPE.
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
S2G N/A N/A N/A N/A
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
2 1/2" METAL STUD FRAMING @ 16"
O.C. MAX
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
S6A45G N/A N/A N/A N/A
ACOUSTIC SEALANT EACH
SIDE AT TOP AND BOTTOM
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
6" METAL STUD FRAMING @ 16"
O.C. MAX
3 1/2" SOUND ATTENUATION
BLANKET
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
(E)M12 N/A N/A N/A N/A
11 5/8"
FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
WALL TYPE:
(E)M8 N/A N/A N/A N/A
7 5/8"
SEE GENERAL WALL TYPE
ASSEMBLIES, NOTE B.
EXISTING CONCRETE
MASONRY UNIT
EXISTING CONCRETE
MASONRY UNIT
3 1/2" SOUND ATTENUATION
BLANKET 3 1/2" SOUND ATTENUATION
BLANKET
3 1/8"
4 1/4"4 1/4"4 7/8"4 7/8"
7 1/4" 7 1/4" 6 5/8"
CEILING TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:CS3.1
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
3 5/8" METAL STUD FRAMING @ 16"
O.C. MAX
ROOF TYPE:
FIRE RATING:
SOUND RATING: TEST:(E)ROOF
EXISTING 5" THICK
REINFORCED POST
TENSIONED CONCRETE ROOF
SLAB/DECK WITH #3 @12" O.C.
RUNNING EAST AND WEST
AND #3 @14" RUNNING NORTH
AND SOUTH W/ REINFORCED
CONCRETE BEAMS (PER 1954
AS-BUILTS); F.V.
EXISTING (2) LAYERS OF 2.5"
RIGID ISO BOARD INSULATION
W/ TAPERED INSULATION; F.V.
EXISTING SINGLE-PLY PVC
MEMBRANE, SIKA SARNAFIL
6110, 80 MIL, COLOR "REFLEX
GRAY", FULLY-ADHERED; F.V.
(2024 RE-ROOF, UNDER
WARRANTY, SEE SPECS)
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
CONTINUOUS 1-1/2" x 1-1/2" x 20 GA.
GALVANIZED STEEL CORNER ANGLE
CEILING TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:G1
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
EXISTING SUBSTRATE
SHIMS OR HAT CHANNEL AS
NECESSARY TO ATTACH GYP
BOARD
5" 5"
CEILING TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:CT0.1
CEILING TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:(E)CT0.3
(1) LAYER 5/8" TYPE 'X' MOISTURE
RESISTANT GYPSUM BOARD,
TAPED WITH 'DURABOND' OR
EQUIVALENT JOINT COMPOUND
7/8" HAT CHANNELS @24"
O.C. MAX.
HANGER WIRE
1 1/2" COLD ROLLED STEEL
CHANNEL @48" O.C.
(E) HANGER WIRE
(E) SALVAGED AND
REINSTALLED 24" x 48"
ACOUSTICAL CEILING PANEL
LAY-IN GRID SYSTEM,
MODIFY FOR NEW
CONSTRUCTION.
NOTE TO CONTRACTOR:
REPLACE DAMAGED TILES TO
MATCH EXISTING.N/A
N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A N/A
N/A
N/A N/A
3"
1/
2"
1/
4"
4 1/4"
NOTE: PROVIDE DIAGONAL
BRACING @32" O.C. MAX.
FLOOR TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
N/A
N/A
N/A N/AFG4
SCHEDULED FINISH, SEE FINISH
PLANS AND SCHEDULE FOR TYPE
AND LOCATION
FLOOR TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
N/A
N/A
N/A N/A(E)FLR-S
F.
V.
-4
F.
V.
- 4
'-0
F.
V.4"
(4 " M
IN
6"
GRANULAR SUB-BASE W/
LAYER OF 3/4" MINUS
CRUSHED STONE; 95% MIN.
COMPACTION DENSITY
CAST-IN-PLACE CONCRETE
SLAB W/ 6"x6"x#10x#10
W.W.MESH TO MATCH
EXISTING WHERE REMAINS
(EXISTING PIPING CRAWL SPACE)
EXISTING CAST-IN-PLACE
SUSPENDED CONCRETE
SLAB W/ 6"x6"x#10x#10
W.W.MESH (PER 1954 AS-
BUILTS); F.V.
EXISTING CAST-IN-PLACE
CONCRETE SLAB ON GRADE;
F.V.
FLOOR TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
N/A
N/A
N/A N/A(E)FLOOR
COMPACTED GRAVEL SUB-BASE
F.
V.
-4
F.
V.
-6
EXISTING CAST-IN-PLACE
CONCRETE SLAB W/ 6"x6"x# 10x#10 W.W.MESH (PER 1954
AS-BUILTS); F.V.
FLOOR TYPE: FIRE RATING:
FIRE TEST:
SOUND RATING: TEST:
N/A
N/A
N/A N/AFG4.1D
GRANULAR SUB-BASE W/
LAYER OF 3/4" MINUS
CRUSHED STONE; 95% MIN.
COMPACTION DENSITY
CAST-IN-PLACE CONCRETE
SLAB W/ 6"x6"x#10x#10
W.W.MESH (SIM. TO MATCH
EXISTING)
1 1/2"
4"
1/
2" D
EP
R
ES
SI
O N
4"
TILE IN THICK-SET MORTAR
BED @SHOWER STALLS;
SEE PLAN
EXISTING
4" 6"
(REMOVED EXISTING
FINISHES IN THEIR ENTIRETY,
PREP FOR NEW FINISH;
SCHEDULED FINISH, SEE
FINISH PLANS AND SCHEDULE
FOR TYPE AND LOCATION
SCHEDULED FINISH, SEE FINISH
PLANS AND SCHEDULE FOR TYPE
AND LOCATION
(REMOVED EXISTING
FINISHES IN THEIR ENTIRETY,
PREP FOR NEW FINISH;
SCHEDULED FINISH, SEE
FINISH PLANS AND SCHEDULE
FOR TYPE AND LOCATION
A. REFER TO STRUCTURAL DRAWINGS FOR
STRUCTURAL DECKING REQUIREMENTS AND
ATTACHMENTS.
B. PROVIDE SEISMIC BRACING AT WALL TYPES THAT
DO NOT EXTEND TO DECK. REFER TO DETAILS ON
A700s SHEET SERIES.
C. PENETRATIONS THROUGH FIRE RATED ASSEMBLIES
SHALL BE PROVIDED PER DETAILS ON G550s SHEET
SERIES.
D. INFORMATION SUPPLIED ON THIS SHEET IS
SUPPLIED AS A BASE CASE AND IS SUPERCEDED BY
LOCATION SPECIFIC DETAIL DRAWINGS.
E. REFER TO TYPICAL DETAILS ON A700s SHEET
SERIES FOR HORIZONTAL AND VERTICAL
CONNECTIONS.
F. ALL FIRE RATED ASSEMBLIES TO BE CONTINUOUS;
FIRE CAULK AND/OR FIRE SAFING TO BE PROVIDED
AT ALL ASSEMBLY TERMINATIONS.
G. ALL ACOUSTICALLY RATED ASSEMBLIES TO BE
CONTINUOUS; ACOUSTIC CAULK TO BE PROVIDED
AT ASSEMBLY TERMINATIONS OR PENETRATIONS.
H. LIGHT FIXTURES IN CEILINGS TO RECEIVE BATT
INSULATION ON TOP SHALL HAVE A BOX OUT TO
PROTECT THE INSULATION FROM THE HEAT OF THE
LIGHT SOURCE PER DETAIL.
I. ALL EXPOSED INTERIOR CONCRETE IS TO BE
SEALED UNLESS NOTED OTHERWISE.
J. INFORMATION IN THE LEGEND BELOW IS FOR
REFERENCE ONLY AND DOES NOT OVERRIDE THE
CONTENTS OF THE DETAILS ON THIS SHEET.
K. DO NOT SCALE DRAWINGS.
GENERAL NOTES -
HORIZONTAL ASSEMBLIES
A. WALL HEIGHT: ALL NEW INTERIOR WALL ASSEMBLIES
ARE CONTINUOUS TO BOTTOM OF DECK UNLESS
NOTED OTHERWISE. REFER TO THE LEGENDS ON
THIS SHEET AND COORDINATE WITH PLANS.
B. TILE BACKER / CEMENT BOARD: WALL TYPES
DESCRIBED ON THIS SHEET DO NOT SHOW OR
ACCOUNT FOR REQUIREMENTS WHERE A TILE FINISH
OCCURS. WHERE THE FINISH SCHEDULE OR
INTERIOR ELEVATIONS CALL FOR TILE, REPLACE
GYPSUM BOARD SHOWN IN THAT WALL'S ASSEMBLY
WITH TILE BACKER / CEMENT BOARD WHERE THE
TILE OCCURS. REPLACE OTHER GYPSUM BOARD
SHOWN IN THAT WALL'S ASSEMBLY WITH MOISTURE
RESISTANT GYPSUM BOARD WHERE NO TILE
OCCURS.
C. BACKING / SUPPORT: WALL TYPES DESCRIBED ON
THIS SHEET DO NOT ACCOUNT FOR REQUIRED
BACKING. CONTRACTOR TO PROVIDE BACKING /
SUPPORT FOR ALL MOUNTED FIXTURES, EQUIPMENT,
CASEWORK, AND/OR SYSTEMS FURNITURE.
COORDINATE WITH FLOOR PLANS, AND INTERIOR
ELEVATIONS PRIOR TO THE COVERING OF STUD
FRAMING. REFER TO MANUFACTURER'S
RECOMMENDATIONS WHERE APPLICABLE,
OTHERWISE REFER TO DETAILS ON A700s SHEET
SERIES.
D. STRUCTURAL SHEATHING: REFER TO STRUCTURAL
DRAWINGS FOR STRUCTURAL SHEATHING
REQUIREMENTS AND ATTACHMENTS.
E. SEISMIC BRACING: PROVIDE SEISMIC BRACING AT
ALL WALL TYPES THAT DO NOT EXTEND TO DECK,
REFER TO DETAILS ON A700s SHEET SERIES.
F. PENETRATIONS: PENETRATIONS THROUGH FIRE
RATED ASSEMBLIES SHALL BE PROVIDED PER G550s
SHEET SERIES.
G. LISTED ASSEMBLIES: RATED ASSEMBLIES PROVIDED
PER G550s SHEET SERIES.
H. ACOUSTIC WALLS: AT ALL WALLS WITH SOUND
ATTENUATION, SEAL ENTIRE TOP AND BOTTOM OF
WALL WITH SOUND SEALANT.
I. DEFLECTION TRACK: AT ALL WALLS THAT EXTEND
TO STRUCTURE PROVIDE DEFLECTION TRACK.
REFER TO DETAILS ON A700s SHEET SERIES.
J. RATED WALL PRIORITY: FOR PARTITION PRIORITY
FOR SEQUENCING OF RATED WALL CONSTRUCTION
REFER TO DETAILS ON A700s SHEET SERIES.
K. INFORMATION IN THE LEGENDS BELOW IS FOR
REFERENCE ONLY AND DOES NOT OVERRIDE THE
CONTENTS OF THE DETAILS ON THIS SHEET.
L. DO NOT SCALE DRAWINGS.
GENERAL NOTES -
WALL TYPE ASSEMBLIES
T
CR HIT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
05-11-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:3
:1
P M
A u to d e sk
D o c s:
U T
N G
A F
A rm o ry
L a tr in e R e m o d e l_ r2
/A R
C H
_2
-A m e ri c a n
F o rk A rm o ry L a tr in e
R e m o d e l_
.r v t
ASSEMBLY
TYPES
MC/JP/KM/SLT
S o u th
E a s t, A m e ri c a n F o rk
U
T
U T
A H
N A
T
IO
N A
L G
U A
R D
25057
05.11.2026
PERMIT SET
GI501
SLT
A M
E R
IC
A
N F
O R
K A
R M
O R
Y L
A T
R
IN
E R
E M
O D
E L
XCS#1.11
PREFIX: 'C' FOR CEILING
CONSTRUCTION TYPE (SEE BELOW)
STRUCTURE THICKNESS (TO NEAREST No.)
FIRE RATING (AS NEEDED, SEE BELOW)
CEILING TAG LEGEND
CONSTRUCTION TYPES
CONCRETE C
STEEL FRAMING S
SUSPENDED TRACK T
C-H (SHAFTWALL) STUD H
WOOD FRAMING W
FINISH F
FIRE RATING
1 HOUR
2 HOUR
3 HOUR
4 HOUR
NO RATING
TYPE (AS NEEDED)
PREFIX: 'X' FOR EXTERIOR
(AS NEEDED)
CS#1.11
INTERIOR FINISH TYPES
GYPSUM BOARD .1
ACT .3
WOOD .5
EXTERIOR FINISH TYPES
METAL PANEL .6
PROFILED METAL PANEL .7
EIFS .9
FINISH INDICATOR (SEE BELOW)
NOT SHOWN
S61M(C)
CONSTRUCTION TYPE (SEE BELOW)
STRUCTURE THICKNESS (TO NEAREST No.)
FIRE RATING (AS NEEDED, SEE BELOW)
MODIFIERS (AS NEEDED, SEE BELOW)
CONCRETE C
MASONRY M
STEEL STUDS S
C-H (SHAFTWALL) STUD H
WOOD STUDS W
DOUBLE STUD #D
ACOUSTIC RATING A
FURRING F
GYP. ONE SIDE G
LEAD SHIELDING L
RF SHIELDING R
MAGNETIC SHIELDING M
WALL TILE T
TOP OF WALL CONDITION MODIFIER (SEE BELOW)
SEE TABLE BELOW
0 HOUR (SMOKE) 0
1 HOUR 1
2 HOUR 2
3 HOUR 3
4 HOUR 4
NO RATING NOT SHOWN
INTERIOR WALL TAG LEGEND
CONSTRUCTION TYPES FIRE RATING
MODIFIER EXAMPLES TOP OF WALL CONDITIONS
TOP OF WALL MODIFIERS
(U) = UNDERSIDE / BOTTOM OF CEILING
WALL EXTENDS TO UNDERSIDE OF
CEILING. TERMINATE WITH "J" MOULD AT
GYP. BOARD WALLS.
EXAMPLE
LINE OF STRUCTURE ABV. TYP.
CEILING, TYP.
SUBSTRATE, TYP.
(C) = 6" ABOVE CEILING
WALLS WILL TERMINATE AT 6" ABOVE THE HIGHEST
ADJOINING CEILING (UNLESS OTHERWISE NOTED)
OR 1 FULL COURSE ABOVE FOR MASONRY WALLS.
(H) = PARTIAL HEIGHT
REFER TO DRAWINGS FOR TOP OF
WALL ELEVATION
(S) = ONE SUBSTRATE TO STRUCTURE
SUBSTRATE BOARD WILL TERMINATE TO BOTTOM
OF DECK ON ONE SIDE AND THE OTHER SIDE SHALL
TERMINATE AT 6" ABOVE ADJOINING CEILING
(UNLESS OTHERWISE NOTED). TERMINATE 1 FULL
COURSE ABOVE FOR MASONRY WALLS.
(N) = NO SUBSTRATES TO STRUCTURE
SUBSTRATE BOARDS WILL TERMINATE AT 6" ABOVE
ADJOINING CEILING (UNLESS OTHERWISE NOTED)
OR 1 FULL COURSE ABOVE FOR MASONRY WALLS.
BRACING, TYP.
DETAILS PROVIDED PER A700s SHEET SERIES.
STUDS, TYP.
6" A
BV
6"
A
BV
6" A
BV
FC#2.1
PREFIX: 'F' FOR FLOOR
CONSTRUCTION TYPE (SEE BELOW)
STRUCTURE THICKNESS (TO NEAREST No.)
FIRE RATING (AS NEEDED, SEE BELOW)
FLOOR TAG LEGEND
CONSTRUCTION TYPES
CONCRETE C
CONCRETE, S.O.G G
CONCRETE PAD P
STEEL JOIST / TRUSS S
WOOD JOIST / TRUSS W
METAL DECK W/ SUBSTRATE D
FIRE RATING
TYPE (AS NEEDED)
1 HOUR 1
2 HOUR 2
3 HOUR 3
4 HOUR 4
NO RATING NOT SHOWN
# Date Revision
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
06/08/2026
A. DETAILS AND DIAGRAMS ON THIS SHEET ARE
PROVIDED AS A MINIMUM DEMONSTRATION OF
ACCESSIBILITY REQUIREMENTS BASED ON THE 2017
ICC / ANSI A117.1 STANDARDS. SEE THE
AFOREMENTIONED STANDARD FOR A
COMPREHENSIVE COLLECTION OF DETAILS AND
BUILDING BLOCKS. SEE PROJECT SPECIFIC DETAILS
FOR ADDITIONAL INFORMATION. VERIFY WITH
ARCHITECT ANY DIFFERENCES OR DISCREPANCIES
BEFORE PROCEEDING WITH CONSTRUCTION.
B. PROVIDE BACKING / SUPPORT FOR ALL MOUNTED
FIXTURES, EQUIPMENT, CASEWORK, AND / OR
SYSTEMS FURNITURE. COORDINATE WITH FLOOR
PLANS, AND INTERIOR ELEVATIONS PRIOR TO THE
COVERING OF STUD FRAMING. REFER TO
MANUFACTURER'S RECOMMENDATIONS WHERE
APPLICABLE, OTHERWISE REFER TO DETAILS ON
AE700s SHEET SERIES.
C. DO NOT SCALE DRAWINGS.
GENERAL NOTES - ACCESSIBILITY
EXISTING BUILDING
CIRCULAR TURNING AREA
OVERLAP OF KNEE & TOE CLEARANCES
T-SHAPED TURNING SPACES SHALL BE PERMITTED TO INCLUDE KNEE AND TOE
CLEARANCE COMPLYING WITH SECTION 306 OF EITHER THE BASE OR ONE ARM
5' - 0"
2'
1"
EXISTING BUILDING
T-SHAPED TURNING AREA
5'
0"
5' - 0"
1' - 0" 3' - 0" 1' - 0"
EXISTING BUILDING
CLEAR FLOOR AREA
2' - 6"
4'
0"
VERTICAL CHANGES IN
LEVELS
1/4" MAX
BEVELED CHANGES IN
LEVELS
GREATER THAN 1/4" BUT NOT MORE
THAN 1/2" MAX SHALL BE BEVELED
WITH A SLOPE NOT STEEPER THAN
1:2
PREDOMINANT DIRECTION OF TRAVEL
LONG DIM. PERP. TO
DIRECTION OF TRAVEL
1/2" MAX
36"MIN
X
4"
60"MIN
X
5"
CLEAR FLOOR SPACE
FORWARD APPROACH
CLEAR FLOOR SPACE
PARALLEL APPROACH
MANEUVERING CLEARANCE
IN AN ALCOVE
FORWARD APPROACH
MANEUVERING CLEARANCE
IN AN ALCOVE
PARALLEL APPROACH
52" x 30" CLEAR FLOOR AREA FOR NEW BUILDINGS REPRESENTED
TO
C
O N
TR
O
LS
"M
AX
PAPER TOWEL
DISPENSER AND
TRASH
(UNOBSTRUCTED)
PAPER TOWEL
DISPENSER
(UNOBSTRUCTED)
SANITARY NAPKIN
VENDOR
(UNOBSTRUCTED)
TO
O
PE
N
IN
G
"M
AX
TOILET SEAT
COVERS
(UNOBSTRUCTED)
BABY CHANGING
STATION
(UNOBSTRUCTED)
HAND DRYER
(UNOBSTRUCTED)
TO
C
O N
TR
O
LS
"M
AX
18"MIN
TO
R
EF
LE
C
TI
VE
S
U R
FA
C
E
" M
IN
" M
AX
FULL LENGTH
MIRROR
(UNOBSTRUCTED)
TO
R E
FL
E
C
TI
V E
S
U R
FA
C
E
TO
D
IS
PE
N
SE
R
"M
AX
TO
D
IS
PE
N
SE
R
"M
AX
"M
AX
13 1/2" MIN
"M
IN
39" -41"
12"MAX 42"MIN.
54"MIN.
36"MIN 6"MAX
16" -18"
60"MIN.
NOTE: DIMENSIONS ARE TO TOP/BOTTOM OF GRAB BARS UNLESS NOTED OTHERWISE
7" -9"
"M
IN
CL
1/
2" M
IN
. C
LE
AR
"M
IN
. C
LE
AR
" M
AX
RECESSED
DISPENSERS ARE
ALLOWED WITHIN
SHADED AREA
TOILET PAPER DISPENSER LOCATION
" M
IN
W
AL
L
H U
N G
T O
IL
ET
42"MIN
FLUSH CONTROLS SHALL BE LOCATED
ON THE OPEN SIDE OF THE WATER
CLOSET IN ACCESSIBLE STALLS
17"MIN.
"M
AX
"M
IN
C
LE
AR
AN
C E
9" M
IN
. T
O E
11"MIN.
8"MIN.
LEG CLEARANCE
"M
AX
"M
IN
"M
AX
"M
AX
ADA STYLE LEVER FAUCETSSOAP DISPENSER
MIRROR
INSULATED PIPES
"M
IN
30"MIN.
TO
R
E
FL
E C
TI
V
E S
U R
FA
C
E
" M
IN
" M
AX
18"
BACK
1/2" MAX THRESHOLD
(BEVELED ROUNDED
OR VERTICAL)
SEAT WALL
CENTERLINE OF
CONTROL WALL
"M
IN
"M
AX
60" LONG HOSE, MIN. W/
VERTICAL BAR FOR
ADJUSTABLE HEIGHT OF
HAND SHOWER. MOUNT SO
AS TO NOT OBSTRUCT THE
USE OF GRAB BARS.
CONTROL AREA
CONTROL WALL
SEAT SEAT
" M
IN
3"
- 6
4"
MAX
15"
NOTE: DIMENSIONS ARE TO TOP/BOTTOM OF GRAB BARS.
CLEAR FLOOR SPACE
S E
A T
W A
LL
C O
N
TR
O L
W A
LL
BACK
18"
CLEAR INSIDE
36"
" M
IN
C
LE
AR
IN
SI
D
E
52"MIN
4" C L
18" VERTICAL
GRAB BAR
CLEAR FLOOR SPACE
S E
A T
W A
LL
C O
N
TR
O L
W A
LL
BACK
18"
CLEAR INSIDE
36"
" M
IN
C
LE
AR
IN
SI
D
E
52"MIN
4" C L
18" VERTICAL
GRAB BAR
NEW BUILDING OPT. 1
4"MAX
NEW BUILDING OPT. 2
22" -23"MAX.
2 1/2"MAX.
15" -16"MAX.
1/
2" M
AX
" M
IN
.1
5" M
AX
3" M
AX
SEAT DESIGN PER SECTION 610
WALL MOUNTED SIGNAGE TO BE
LOCATED ON LATCH SIDE OF DOOR &
CLEAR OF DOOR SWING. MOUNT AT 48"
MIN TO 60" MAX TO BOTTOM OF RAISED
LETTERING FROM FINISH FLOOR
WOMEN
WOMENHEIGHT OF LETTERING, 5/8"
TO 2" MAX, WITH UPPER
CASE CHARACTERS
CORRESPONDING GRADE 2 BRAILLE
LOCATION
SINGLE DOOR:
MOUNT ON LATCH SIDE OF DOOR
DBL DOOR - 1 ACTIVE LEAF:
MOUNT ON INACTIVE LEAF.
DBL DOOR - 2 ACTIVE LEAVES:
INSTALL ON RIGHT SIDE OF RIGHT
HAND DOOR
MEN WOMEN
UNISEX RESTROOM
MEN
HANDICAPPED
ACCESSIBLE
RESTROOM
TO
B
O
TT
O M
O F
R
AI
SE
L
ET
TE
R
IN
G
" M
IN
" M
AX
SEE CLEAR FLOOR AREA GRAPHIC
CL
18"MIN
" M
IN
CLEAR FLOOR AREA, CENTERED ON RAISED
CHARACTERS, OUTSIDE OF DOOR SWING
TO
B
AS
EL
IN
E
O F
BR
AI
LL
E
" M
IN
" M
AX
5"MAX.
15"MIN.
8"MIN.
9" M
IN
"M
IN
W H
EE
L
C H
AI
R
"M
AX
11"MIN.
"M
IN
52"MIN
CLEAR FLOOR SPACE
CONTROLS AT OR
NEAR FRONT EDGE
CANTILEVERED DRINKING FOUNTAIN & WATER COOLERS
W H
EE
L
C H
AI
R
" M
AX
ST
AN
D
IN
G P
ER
SO
N
3"
IF
IN
SI
D
E
AL
C O
VE
"M
IN
WHERE PROVIDED IN WET
LOCATIONS THE SURFACE OF THE
BENCH SHALL BE SLIP RESISTANT
AND WATER SHALL NOT
ACCUMULATE ON THE SURFACE
GROUND SLOPE NOT
STEEPER THAN 1:48
CLEAR
FLOOR
SPACE
42"MIN.
42"MIN.
SEE SECTION 903.4 FOR BACK SUPPORT CRITERIA
PLAN ELEVATION
RECEPTACLE
OUTLET
UNOBSTRUCTED
THERMOSTAT
UNOBSTRUCTED
SWITCH
RECEPTACLES AND SWITCH MOUNTING HEIGHTS
UNOBSTRUCTED FIRE
ALARM PULL BOX
"M
IN
.36
"M
IN
"M
AX
"M
AX
FIRE EXTINGUISHER
T
CR HIT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
05-11-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:2
:2
P M
A u to d e sk
D o c s:
U T
N G
A F
A rm o ry
L a tr in e R e m o d e l_ r2
/A R
C H
_2
-A m e ri c a n
F o rk A rm o ry L a tr in e
R e m o d e l_
.r v t
ACCESSIBILITY
COMPLIANCE
AN
S o u th
E a s t, A m e ri c a n F o rk
U
T
U T
A H
N A
T
IO
N A
L G
U A
R D
25057
05.11.2026
PERMIT SET
GI701
SLT
A M
E R
IC
A
N F
O R
K A
R M
O R
Y
L A
T R
IN
E
R E
M O
D E
L
3/8" = 1'-0"GI701
A4 ADA TURNING AREAS
6" = 1'-0"GI701
A2 CHANGES IN LEVEL
3/8" = 1'-0"GI701
B2 MANEUVERING CLEARANCES
3/8" = 1'-0"GI701
C2 MOUNTING HEIGHTS
3/8" = 1'-0"GI701
B6 URINALS & WATER CLOSETS
3/8" = 1'-0"GI701
C4 ACCESSIBLE SINKS
3/8" = 1'-0"GI701
C6 ACCESSIBLE 3x3 SHOWER STALL
3/8" = 1'-0"GI701
D5 TRANSFER SHOWER & SEAT
3/8" = 1'-0"GI701
D3 SIGNAGE
3/8" = 1'-0"GI701
B4 DRINKING FOUNTAIN DETAIL
3/8" = 1'-0"GI701
D6 ACCESSIBLE BENCH
3/8" = 1'-0"GI701
D1 MISC. MOUNTING HEIGHTS
# Date Revision
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
06/08/2026
A. PROTECT WALLS, CEILINGS, FLOORS,
DOORS, AND OTHER EXISTING FINISH WORK
THAT ARE TO REMAIN OR THAT ARE
EXPOSED DURING SELECTIVE DEMOLITION
OPERATIONS.
B. PATCH AND REPAIR DAMAGE TO WALLS,
CEILINGS, AND FLOORS RESULTING FROM
DEMOLITION OF EXISTING ITEMS OR
CONSTRUCTION OF NEW ITEMS AND/OR
REPLACE WITH NEW TO MATCH EXISTING.
CLEAN AND PREPARE TO RECEIVE NEW
FINISH.
C. PROTECT ADJACENT AREAS FROM DUST
AND DEBRIS DURING SELECTIVE
DEMOLITION OPERATIONS.
D. RECYCLE ALL DEBRIS. WHEN UNABLE TO
RECYCLE, TRANSPORT DEMOLISHED
MATERIALS OFF OWNER'S PROPERTY AND
LEGALLY DISPOSE OF DEBRIS.
E. FIELD VERIFY EXISTING CONDITIONS AND
THEIR COMPATIBILITY WITH NEW
CONSTRUCTION PRIOR TO THE
COMMENCEMENT OF WORK.
F. CLEAN ADJACENT AREAS OF DUST, DIRT,
AND DEBRIS CAUSED BY SELECTIVE
DEMOLITION OPERATIONS. RETURN
ADJACENT AREAS TO CONDITION EXISTING
BEFORE SELECTIVE DEMOLITION
OPERATIONS BEGAN.
G. SEE MECHANICAL, PLUMBING, & ELECTRICAL
DRAWINGS FOR ADDITIONAL INFORMATION
COORDINATE DISCREPANCIES WITH
ARCHITECT PRIOR TO PROCEEDING WITH
WORK.
H. ITEMS IDENTIFIED IN SALVAGE ACCESSORY
LEGEND TO BE RETURNED TO OWNER'S
STOCK. PROTECT FROM DAMAGE.
I. SOME INCIDENTAL ITEMS REQUIRING
REMOVAL MAY NOT BE SPECIFICALLY
CALLED OUT. REMOVAL OF ALL ITEMS
NECESSARY FOR THE COMPLETION OF
WORK IS THE RESPONSIBILITY OF THE
CONTRACTOR.
J. ASBUILT DRAWINGS ARE NOT AVAILABLE
FOR THIS BUILDING. CONTRACTOR TO
VERIFY EXISTING FIRE RATING TYPES AND
LOCATIONS AND ALERT ARCHITECT IF
DIFFERENT THAN SHOWN IN THE DRAWINGS.
K. DO NOT SCALE DRAWINGS.
GENERAL NOTES - DEMOLITION PLANS
(E) OFFICE
(E) UNISEX
(E) WOMEN'S
RESTROOM
(E) JANITOR
(E) MEN'S
RESTROOM
(E)
ASSEMBLY
ROOM
(E) STORAGE
(E) KITCHEN
02:RP1
02:RP5
02:RP2
02:RP21 02:DW1
02:RP5
02:DW1
02:RE1
02:DW1
02:RE1
02:RP2
02:DW1
02:RE1
02:RE1
02:RE1
02:RE1
02:RE1
02:RE1
02:RE1
02:RE1
02:RE2
02:RE102:RE1
02:RE1
02:RE1
02:RE202:RE2
02:RE1 02:RE1
02:DD2
02:DD202:DW1
02:DW1
02:EL2
02:TW1
02:TW1
5' - 0"
5'
0"
S3G
S3G
S3G
S3G
02:DW1
02:TF1
02:DF5
02:RD1
02:RP5
02:DF6
02:DW1
02:DF6
02:DF6
02:DF6
+/- 1' - 6"
- 3
+/- 3"
+/- 5' - 11 1/2" +/- 3' - 0" +/-8' - 4 1/8"
- 1
- 9
02:DF1
02:DF1
02:PL1
02:PL1
02:PL1
-6
- 3
+/- 3' - 6"
02:RE1
02:FH1
02:EL2
(E)
VESTIBULE
N.I.C.
- 1
- 3
/2
" F .V
.F.V.
+/- 2' - 10"
F.
V.
- 3
/2
+/- 2' - 10 1/4" F.V. +/- 12' - 7 3/4" F.V.F.
V.
- 3
1/
4"
F.
V.
- 3
/2
+/-3' - 0" F.V.
+/- 6"
F.V.
+/- 1' - 8"
F.V.
+/- 3' - 8 1/4"
F.V.
+/- 1' - 4"
- 3
/2
" F .V
- 8
" F
.V
45°
F.V.
+/- 4' - 7"
F.V
1'
- 8
F.
V.
- 3
F.
V.
- 1
- 8
" F
.V
F.V.
+/- 2' - 6 1/4"
F.V.
+/- 3' - 3 3/4"
135°
F.V.
+/- 3' - 1 1/4"
F.V
1'
- 4
+/-18' - 11 1/2"
-3
9'
1"
+/-26' - 10 3/4"
+/-59' - 5 1/2"
+/-10' - 7 1/2"
-1
0'
1/
2"
1/
4" +/-17' - 8 1/4"
COORD. W/ NEW CONSTR.
+/-6' - 6 1/4"
02:TF1
02:DD1
02:DD1
02:DD3
(E)FS
(E)FLOOR
(E)FLOOR
(E)FLR-S
(E)FLR-S
(E)FLOOR
NOTE TO CONTRACTOR: EXISTING 25/32" X 3" T&G MAPLE WOOD
GYM FLOORING SYSTEM OVER 3/4" WOOD SUB-FLOORING
PRESERVATIVE TREATED OVER 2X4 WOOD SLEEPERS @16" O.C.
PRESERVATIVE TREATED W/ DAMPPROOFING OVER DEPRESSED
CONCRETE SLAB (PER 1954 AS-BUILTS, FIELD VERIFY);
PERIMETER OF WOOD FLOORING SPACED 1" EXPANSION;
EXISTING PERIMETER 3"X2"X3/16" VENT COVE BASE ANCHORED
TO WALL; REMOVAL OF ANY EXISTING 2X4 WOOD SLEEPERS FOR
NEW CONSTRUCTION MUST BE REPLACED TO MATCH EXISTING
ALONG PERIMETER OF GYM FLOORING WHERE AFFECTED BY
NEW CONSTRUCTION; SCOPE OF WORK TO BE FIELD
DETERMINED; PROTECT ALL EXISTING WOOD FLOORING SYSTEM
TO REMAIN IN (E) ASSEMBLY ROOM.
(E) OFFICE
(E) UNISEX
(E) WOMEN'S
RESTROOM
(E) JANITOR
(E) MEN'S
RESTROOM
(E)
ASSEMBLY
ROOM N.I.C.
(U.N.O.)
(E) STORAGE
(E) KITCHEN
TYP.
02:DL1
02:DC1
02:DC1
02:DL1
02:DL1
EXISTING CONCRETE BALCONY, ABOVE
02:EL1
02:EL1
TYP.
02:DL1
(E)
VESTIBULE
N.I.C.
TYP.
02:RP12
TYP.
02:RP12
TYP.
02:RP12
TYP.
02:DL1
TYP.
02:DL1
TYP.
02:ED2
TYP.
02:ED2
TYP.
02:ED2
NEW CONSTRUCTION
AS REQUIRED FOR
PUBLIC SIDE RESTROOM
CONSTRUCTION SIDE
EXISTING FLOORING
3 5/8" X 25 GAUGE METAL STUDS @ 24" O.C.
SCREWED TO PLYWOOD BASE SHEETS
ONLY @ 32" O.C.
PROVIDE TEMPORARY CONSTRUCTION
FLOORING PROTECTION SYSTEM OVER
WOOD FLOORING SYSTEM: BASE LAYER W/
SYNTHETIC BREATHABLE FLOOR
PROTECTION (RAM BOARD), W/
INTERMEDIATE CUSHION LAYER (THIN
FOAM BOARD OR MASONITE HARDBOARD)
AND TOP LAYER (3/4" PLYWOOD W/ TAPPED
SEAMS, AVOID SCREWING TO THE GYM
FLOOR)
AD111
A6
AD111
B6
EXISTING CEILING SYSTEM TO REMAIN
1/2" PLYWOOD, CONT.
8 MIL "VIS-QUEEN" PLASTIC DUST
MEMBRANE.
EXISTING CEILING SYSTEM TO REMAIN
EXISTING FLOORING
PROVIDE TEMPORARY CONSTRUCTION
FLOORING PROTECTION SYSTEM OVER
WOOD FLOORING SYSTEM: BASE LAYER W/
SYNTHETIC BREATHABLE FLOOR
PROTECTION (RAM BOARD), W/
INTERMEDIATE CUSHION LAYER (THIN
FOAM BOARD OR MASONITE HARDBOARD)
AND TOP LAYER (3/4" PLYWOOD W/ TAPPED
SEAMS, AVOID SCREWING TO THE GYM
FLOOR)
8 MIL "VIS-QUEEN" PLASTIC DUST
MEMBRANE.
3 5/8" X 25 GAUGE METAL STUDS @ 24" O.C.
SCREWED TO PLYWOOD BASE SHEETS
ONLY @ 32" O.C.
T
CR HIT
E
A
IC
E
L
NS E D
C
O UT
HS
TE
TA
F
A
DATE:
DRAWN BY:
CHECKED BY:
NEXUS PROJ. #:
DFCM APPROVAL
123456
E
D
C
B
A
Architectural NEXUS, Inc.
2505 East Parleys Way Salt Lake City, Utah 84109 T 801.924.5000 http://www.archnexus.com
Original drawings remain the property of the Architect and as such the Architect retains total ownership and control. The design represented by these drawings is sold to the client for a one time use, unless otherwise agreed upon in writing by the Architect.
© ARCH NEXUS All Rights Reserved
D F
C M
P R
O J E
C T
N O
05-11-26
STEPHEN M.
No. 7655609-0301
SPRINGER
/1
/2
:2
:2
P M
A u to d e sk
D o c s:
U T
N G
A F
A rm o ry
L a tr in e R e m o d e l_ r2
/A R
C H
_2
-A m e ri c a n
F o rk A rm o ry L a tr in e
R e m o d e l_
.r v t
ENLARGED
RESTROOM
DEMOLITION
PLANS &
DETAILS
MC
S o u th
E a s t, A m e ri c a n F o rk
U
T
U T
A H
N A
T
IO
N A
L G
U A
R D
25057
05.11.2026
PERMIT SET
AD111
AW
A M
E R
IC
A
N F
O R
K A
R M
O R
Y
L A
T R
IN
E
R E
M O
D E
L
KEYNOTE SCHEDULE
TAG KEYNOTE TEXT
02:DC1 DEMOLISH PORTION OF CEILING (SHOWN DASHED)
02:DD1 REMOVE EXISTING DOORS. SALVAGE FOR REUSE IN
NEW CONSTRUCTION
02:DD2 REMOVE EXISTING METAL DOOR & FRAME
02:DD3 REMOVE EXISTING METAL DOOR & FRAME; PREP FOR
NEW INFILL WALL CONSTRUCTION
02:DF1 REMOVE EXISTING FLOOR FINISHES (SHADED AREAS)
IN THEIR ENTIRETY OVER CONCRETE SLAB OVER
GRADE (U.N.O.); OFFICES CARPET TILE AND
ADHESIVE; RESTROOMS FLOOR TILE AND THIN SET;
PATCH & REPAIR SUBSTRATES & PREP SURFACES
FOR NEW CONSTRUCTION
02:DF5 REMOVE DRINKING FOUNTAIN AND SALVAGE FOR
REUSE IN NEW CONSTRUCTION
02:DF6 SAW-CUT AND REMOVE SECTION(S) OF EXISTING
REINFORCED CONCRETE SLAB & FINISHES AS
REQUIRED FOR NEW UNDERGROUND PLUMBING AND
DEPRESSED SLABS FOR NEW SHOWER STALLS,
SHOWN IN DARK HATCHED CONCRETE AREAS;
COORDINATE WITH NEW CONSTRUCTION; EXTENT TO
BE FIELD DETERMINED
02:DL1 REMOVE AND SALVAGE EXISTING 2X4 LIGHT FIXTURE
FOR REUSE IN NEW CONSTRUCTION
02:DW1 DEMOLISH EXISTING WALL
02:EC2 EXISTING CEILING SYSTEM TO REMAIN
02:ED2 REMOVE EXISTING ACCESS DOOR, SALVAGE FOR
USE IN NEW CONSTRUCTION
02:EF5 EXISTING FLOORING
02:EL1 EXISTING LIGHT FIXTURE, TO REMAIN
02:EL2 REMOVE EXISTING METAL LOCKERS. SALVAGE FOR
REUSE IN NEW CONSTRUCTION
02:FH1 EXISTING FLOOR HATCH TO REMAIN, PROTECT IN
PLACE, PREPARE FOR NEW FINISHES
02:PL1 EXISTING PLUMBING PIPING CHASE BELOW
SUSPENDED CONCRETE SLAB (LIGHT SHADED GRAY
AREA), DASHED LINE REPRESENTS 6" THICK
REINFORCED FOUNDATION WALL BELOW
02:RD1 REMOVE EXISTING DOOR
02:RE1 TEMPORARILY REMOVE, SALVAGE & PROTECT
EXISTING EQUIPMENT; COORDINATE WITH BUILDING
USERS ON LOCATION
02:RE2 TEMPORARILY REMOVE, SALVAGE & PROTECT
EXISTING EQUIPMENT; REINSTALL PER NEW
CONSTRUCTION PLAN
02:RP1 REMOVE EXISTING RESTROOM PARTITIONS, DOORS,
ETC.
02:RP2 REMOVE EXISTING SINKS AND FAUCETS
02:RP5 REMOVE EXISTING PLUMBING FIXTURE
02:RP12 REMOVE EXISTING MECHANICAL SUPPLY & RETURN
AIR DIFFUSERS. COORDINATE W/ MECHANICAL
02:RP21 REMOVE EXISTING FLOOR SINK; PATCH/REPAIR CONC
SLAB FOR NEW CONSTRUCTION
02:TF1 PROVIDE TEMPORARY CONSTRUCTION FLOORING
PROTECTION SYSTEM OVER WOOD FLOORING
SYSTEM: BASE LAYER W/ SYNTHETIC BREATHABLE
FLOOR PROTECTION (RAM BOARD), W/ INTERMEDIATE
CUSHION LAYER (THIN FOAM BOARD OR MASONITE
HARDBOARD) AND TOP LAYER (3/4" PLYWOOD W/
TAPPED SEAMS, AVOID SCREWING TO THE GYM
FLOOR)
02:TW1 PROVIDE TEMPORARY DUST AND CONTROL WALL
CONSTRUCTION AND SECURED ACCESS DOOR
05:MS5 3 5/8" X 25 GAUGE METAL STUDS @ 24" O.C.
SCREWED TO PLYWOOD BASE SHEETS ONLY @ 32"
O.C.
06:PS4 1/2" PLYWOOD, CONT.
07:DM1 8 MIL "VIS-QUEEN" PLASTIC DUST MEMBRANE.
1/4" = 1'-0"AD111
A3 LEVEL 01 ENLARGED DEMOLITION PLAN
1/4" = 1'-0"AD111
D3 LEVEL 01 DEMOLITION REFLECTED CEILING PLAN
1 1/2" = 1'-0"AD111
A5 TEMPORARY CONSTRUCTION WALL SECTION
3" = 1'-0"AD111
A6 TYP. TEMPORARY WALL FLOOR CONNECTION
3" = 1'-0"AD111
B6 TEMPORARY WALL CEILING CONNECTION @ GYP. CEILING
KEYPLAN
0' 4' 8' 12'
1/4" = 1'-0" GRAPHIC SCALE
0' 4' 8' 12'
1/4" = 1'-0" GRAPHIC SCALE
# Date Revision
T H
IS
S
H E
E T
T O
B E
P R
IN
T
E D
IN
C
O
LO
R
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
06/08/2026
A. FIELD VERIFY ALL EXISTING CONDITIONS AND THEIR
COMPATIBILITY WITH NEW CONSTRUCTION PRIOR TO
THE COMMENCEMENT OF WORK. COORDINATE
DISCREPANCIES WITH ARCHITECT.
B. ALL NEW WALL ASSEMBLIES ARE CONTINUOUS TO
BOTTOM OF DECK UNLESS NOTED OTHERWISE.
C. PLAN WALL DIMENSIONS ARE TO GRID LINE OR FACE
OF WALL STRUCTURE, UNLESS NOTED OTHERWISE.
"CLEAR" DIMENSIONS ARE TO FACE OF WALL FINISH.
D. WHERE THE FINISH SCHEDULE OR INTERIOR
ELEVATIONS CALL FOR TILE, REPLACE GYPSUM
BOARD SHOWN IN THE WALL'S ASSEMBLY WITH TILE
BACKER BOARD WHERE TILE…
This is the start of the file's text. The full file is on GovTribe.