6-7-CR26075-26308480 Mechanical Compliance Certificate.pdf

PDF 428 KB Posted

Attached to
DFCM Construction - Prequalified General Stage II - Utah National Guard- American Fork Armory Latrine Remodel - Project #26308480
Solicitation number
CR26075
Issued by
Utah

About this file

This is a Mechanical Compliance Certificate for the Utah National Guard (UTNG) American Fork Armory Latrine Remodel project (DFCM #26308480, AN #25057), reviewed and approved by the Division of Facilities Construction and Management (DFCM). The project involves the renovation and reconfiguration of existing men's and women's restrooms, demolition of existing facilities, improvements to janitorial and kitchen spaces, revised electrical distribution, plumbing modifications, and removal and replacement of upgraded HVAC equipment. The certificate confirms compliance with the 2018 IECC energy code requirements through a COMcheck analysis (version 4.1.5.3) and documents the project's progression through multiple review stages, including a 90% Review Set dated February 11, 2026, and a final Permit Set dated May 11, 2026. The project is located in American Fork, Utah 84003.

The mechanical compliance review covers multiple inspection phases including plan review, footing/foundation inspection, plumbing rough-in inspection, mechanical rough-in inspection, and final inspection. All assessed requirements across these inspection phases are marked as compliant, addressing high-impact (Tier 1), medium-impact (Tier 2), and low-impact (Tier 3) items. Key compliance areas include HVAC duct insulation and construction, heated water supply piping requirements, exhaust air energy recovery, automatic controls for heating and cooling systems, commissioning plan requirements, equipment testing, control system calibration, and system balancing reports. The document was reviewed by Jason Van Ausdal on June 8, 2026, and designed by Darrin Revels. The construction cost estimate for the project is $813,054.00, with eligibility limited to prequalified Stage I contractors currently listed on the DFCM Prequalified Contractors list as of the solicitation date.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

)*+,-./012/3-4

5657089::

)*+,-./01;<-4 =3/-*>/2+?

@+.>/2+?4 =A-*2.>?0B+*CD0E/>F

:32A>/-0G+?-4 HI

:+?J/*K./2+?0L2/-4

5H70L+K/F056609>J/

=A-*2.>0B+*CD0E10MN66O

PQ?-*R=S-?/4

L/-T-01>??-*

=*.FU-VKJ

5H6509>J/0)>*3-;J0W>;

L>3/0@>C-0:2/;D0E10MN76X

Y-J2S?-*R:+?/*>./+*4

Y>**2?0Z-T-3J :+3T2?09?S2?--*2?S H6H090L+K/F01-A<3-

L>3/0@>C-0:2/;D0E10MN675

[�\����]�
�̂
���

9?-*S;0:+_-4

=A-*2.>?0B+*C0=*A+*;0@>**2?-0Z-A+_-3

̀��a���̂ ��b��� cd ����a�a���̂ �eaf��g�h�����f�� �

L2?S3-0)>.C>S-0i->/0)KA< i->/2?S0j+_-40:><>.2/;0k0550Cl/KRFD 0000)*+<+J-_09mm2.2-?.;0k0Xn660iL)B5D0Z-oK2*-_09mm2.2-?.;0k0pnq60iL)B5 :++32?S0j+_-40:><>.2/;0k07M0Cl/KRFD 0000)*+<+J-_09mm2.2-?.;0k07Mn660L99Z5D0Z-oK2*-_09mm2.2-?.;0k07OnN60L99Z5 0000)*+<+J-_0)>*/0@+>_09mm2.2-?.;0k06n660D0Z-oK2*-_0)>*/0@+>_09mm2.2-?.;0k06n66 B>?0L;J/-A400E?J<-.2m2-_

7 PYEr70sL2?S3-0G+?-t4

L2?S3-0)>.C>S-0i->/0)KA< i->/2?S0j+_-40:><>.2/;0k0770Cl/KRFD 0000)*+<+J-_09mm2.2-?.;0k0Xn660iL)B5D0Z-oK2*-_09mm2.2-?.;0k0pnq60iL)B5 :++32?S0j+_-40:><>.2/;0k0X0Cl/KRFD 0000)*+<+J-_09mm2.2-?.;0k07pn660L99Z5D0Z-oK2*-_09mm2.2-?.;0k07OnN60L99Z5 0000)*+<+J-_0)>*/0@+>_09mm2.2-?.;0k06n660D0Z-oK2*-_0)>*/0@+>_09mm2.2-?.;0k06n66 B>?0L;J/-A400E?J<-.2m2-_

7 PYEr50sL2?S3-0G+?-t4 i->/2?S4070->.F0r0E?2/0i->/-*D093-./*2.D0:><>.2/;0k0760Cl/KRF 0000U+0A2?2AKA0-mm2.2-?.;0*-oK2*-A-?/0><<32-J B>?0L;J/-A400E?J<-.2m2-_

7 9Eir70sL2?S3-0G+?-t4 u>J08?J/>?/>?-+KJ0W>/-*0i->/-*D0:><>.2/;4050S>33+?JD08?<K/0Z>/2?S40H660Cl/KRF0QR0:2*.K3>/2+?0)KA< 0000U+0A2?2AKA0-mm2.2-?.;0*-oK2*-A-?/0><<32-J

5 W>/-*0i->/-*074

̀�� ̂ f̀� vwxyz{|}~����|��x�}��001F-0<*+<+J-_0A-.F>?2.>30>3/-*>/2+?0<*+,-./0*-<*-J-?/-_02?0/F2J0_+.KA-?/02J0.+?J2J/-?/0Q2/F0/F-0IK23_2?S <3>?JD0J<-.2m2.>/2+?JD0>?_0+/F-*0.>3.K3>/2+?J0JKIA2//-_0Q2/F0/F2J0<-*A2/0><<32.>/2+?n01F-0<*+<+J-_0A-.F>?2.>30J;J/-AJ0F>T-0I--?

_-J2S?-_0/+0A--/0/F-05657089::0*-oK2*-A-?/J02?0:Pj~��~�0�-*J2+?0:Pj.F-.CW-I0>?_0/+0.+A<3;0Q2/F0>?;0><<32.>I3- A>?_>/+*;0*-oK2*-A-?/J032J/-_02?0/F-08?J<-./2+?0:F-.C32J/n

U>A-0r012/3- L2S?>/K*- Y>/-

)*+,-./012/3-4

Y>/>0m23-?>A-4

=A-*2.>?0B+*C0=*A+*;0@>**2?-0Z-A+_-3 6NRO6R5pZ-<+*/0_>/-4

X70+m)>S-

04/30/2026Darrin Revels-Designer

Utah National Guard UTNG American Fork Armory Latrine Remodel 11 May 2026 American Fork, UT 84003 DFCM #26308480 | AN #25057 PERMIT SET

APPENDIX B

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

Jason Van Ausdal

06/08/2026

REVIEWED FOR CODE

COMPLIANCE

Inspection Checklist Requirements: 0.0% were addressed directly in the COMcheck software

COMcheck Software Version 4.1.5.3

Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.

Energy Code: 2018 IECC

Section

& Req.ID Plan Review Complies? Comments/Assumptions

C103.2

[PR2]1

Plans, specifications, and/or calculations provide all information with which compliance can be determined for the mechanical systems and equipment and document where exceptions to the standard are claimed. Load calculations per acceptable engineering standards and handbooks.

Complies Does Not Not Observable Not Applicable

C103.2

[PR3]1

Plans, specifications, and/or calculations provide all information with which compliance can be determined for the service water heating systems and equipment and document where exceptions to the standard are claimed. Hot water system sized per manufacturer's sizing guide.

Complies Does Not Not Observable Not Applicable

Additional Comments/Assumptions:

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

112 ofPage

Utah National Guard UTNG American Fork Armory Latrine Remodel 11 February 2026 American Fork, UT 84003 DFCM # 26308480 | NGB # | AN #25057 90% Review Set

Utah National Guard UTNG American Fork Armory Latrine Remodel 06 March 2026

American Fork, UT 84003 DFCM # 26308480 | NGB # | AN #25057 PERMIT SET

Section

& Req.ID Footing / Foundation Inspection Complies? Comments/Assumptions

C403.12.2 C403.12.3

[FO9]3

Snow/ice melting system and freeze protection systems have sensors and controls configured to limit service for pavement temperature and outdoor temperature. future connection to controls.

Complies Does Not Not Observable Not Applicable

Additional Comments/Assumptions:

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

113 ofPage

& Req.ID Plumbing Rough-In Inspection Complies? Comments/Assumptions

C404.5, C404.5.1, C404.5.2

[PL6]3

Heated water supply piping conforms to pipe length and volume requirements. Refer to section details.

Complies Does Not Not Observable Not Applicable

C404.5, C404.5.1, C404.5.2

[PL6]3

Heated water supply piping conforms to pipe length and volume requirements. Refer to section details.

Complies Does Not Not Observable Not Applicable

C404.5, C404.5.1, C404.5.2

[PL6]3

Heated water supply piping conforms to pipe length and volume requirements. Refer to section details.

Complies Does Not Not Observable Not Applicable

C404.5, C404.5.1, C404.5.2

[PL6]3

Heated water supply piping conforms to pipe length and volume requirements. Refer to section details.

Complies Does Not Not Observable Not Applicable

C404.6.1, C404.6.2

[PL3]1

Automatic time switches installed to automatically switch off the recirculating hot-water system or heat trace.

Complies Does Not Not Observable Not Applicable

C404.6.3

[PL7]3

Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after end of heating cycle.

Complies Does Not Not Observable Not Applicable

C404.6.3

[PL7]3

Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after end of heating cycle.

Complies Does Not Not Observable Not Applicable

C404.6.3

[PL7]3

Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after end of heating cycle.

Complies Does Not Not Observable Not Applicable

C404.6.3

[PL7]3

Pumps that circulate water between a heater and storage tank have controls that limit operation from startup to <= 5 minutes after end of heating cycle.

Complies Does Not Not Observable Not Applicable

C404.7

[PL8]3

Demand recirculation water systems have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F.

Complies Does Not Not Observable Not Applicable

C404.7

[PL8]3

Demand recirculation water systems have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F.

Complies Does Not Not Observable Not Applicable

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

114 ofPage

& Req.ID Plumbing Rough-In Inspection Complies? Comments/Assumptions

C404.7

[PL8]3

Demand recirculation water systems have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F.

Complies Does Not Not Observable Not Applicable

C404.7

[PL8]3

Demand recirculation water systems have controls that start the pump upon receiving a signal from the action of a user of a fixture or appliance and limits the temperature of the water entering the cold-water piping to 104°F.

Complies Does Not Not Observable Not Applicable

Additional Comments/Assumptions:

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

115 ofPage

& Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions

C402.2.6

[ME41]3

Thermally ineffective panel surfaces of sensible heating panels have insulation >= R-3.5.

Complies Does Not Not Observable Not Applicable

C403.11.3

[ME61]2

HVAC piping insulation insulated in accordance with Table C403.11.3.

Insulation exposed to weather is protected from damage and is provided with shielding from solar radiation.

Complies Does Not Not Observable Not Applicable

C403.8.1

[ME65]3

HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp.

Complies Does Not Not Observable Not Applicable

See the Mechanical Systems list for values.

C403.8.1

[ME65]3

HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp.

Complies Does Not Not Observable Not Applicable

See the Mechanical Systems list for values.

C403.8.1

[ME65]3

HVAC fan systems at design conditions do not exceed allowable fan system motor nameplate hp or fan system bhp.

Complies Does Not Not Observable Not Applicable

See the Mechanical Systems list for values.

C403.8.3

[ME117]2

Fans have efficiency grade (FEG) >=

67. The total efficiency of the fan at the design point of operation <= 15% of maximum total efficiency of the fan.

Complies Does Not Not Observable Not Applicable

C403.8.3

[ME117]2

Fans have efficiency grade (FEG) >=

67. The total efficiency of the fan at the design point of operation <= 15% of maximum total efficiency of the fan.

Complies Does Not Not Observable Not Applicable

C403.8.3

[ME117]2

Fans have efficiency grade (FEG) >=

67. The total efficiency of the fan at the design point of operation <= 15% of maximum total efficiency of the fan.

Complies Does Not Not Observable Not Applicable

C403.12.1

[ME71]2

Systems that heat outside the building envelope are radiant heat systems controlled by an occupancy sensing device or timer switch.

Complies Does Not Not Observable Not Applicable

C403.2.3

[ME55]2

HVAC equipment efficiency verified. Complies Does Not Not Observable Not Applicable

See the Mechanical Systems list for values.

C403.2.2

[ME59]1

Natural or mechanical ventilation is provided in accordance with International Mechanical Code Chapter 4. Mechanical ventilation has capability to reduce outdoor air supply to minimum per IMC Chapter 4.

Complies Does Not Not Observable Not Applicable

C403.7.1

[ME59]1

Demand control ventilation provided for spaces >500 ft2 and >25 people/1000 ft2 occupant density and served by systems with air side economizer, auto modulating outside air damper control, or design airflow >3,000 cfm.

Complies Does Not Not Observable Not Applicable

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

116 ofPage

& Req.ID Mechanical Rough-In Inspection Complies? Comments/Assumptions

C403.7.2

[ME115]3

Enclosed parking garage ventilation has automatic contaminant detection and capacity to stage or modulate fans to 50% or less of design capacity.

Complies Does Not Not Observable Not Applicable

C403.7.6

[ME141]3

HVAC systems serving guestrooms in Group R-1 buildings with > 50 guestrooms: Each guestroom is provided with controls that automatically manage temperature setpoint and ventilation (see sections C403.7.6.1 and C403.7.6.2).

Complies Does Not Not Observable Not Applicable

C403.7.4

[ME57]1

Exhaust air energy recovery on systems meeting Table C403.7.4(1) and C403.7.4(2).

Complies Does Not Not Observable Not Applicable

C403.7.5

[ME116]3

Kitchen exhaust systems comply with replacement air and conditioned supply air limitations, and satisfy hood rating requirements and maximum exhaust rate criteria.

Complies Does Not Not Observable Not Applicable

C403.11.1 C403.11.2

[ME60]2

HVAC ducts and plenums insulated in accordance with C403.11.1 and constructed in accordance with C403.11.2, verification may need to occur during Foundation Inspection.

Complies Does Not Not Observable Not Applicable

C403.4.1.

[ME63]2

Heating for vestibules and air curtains with integral heating include automatic controls that shut off the heating system when outdoor air temperatures > 45F. Vestibule heating and cooling systems controlled by a thermostat in the vestibule with heating setpoint <= 60F and cooling setpoint >= 80F.

Complies Does Not Not Observable Not Applicable

C403.3.3

[ME35]1

Hot gas bypass limited to: <=240 kBtu/h – 50% >240 kBtu/h – 25%

Complies Does Not Not Observable Not Applicable

C403.3.3

[ME35]1

Hot gas bypass limited to: <=240 kBtu/h – 50% >240 kBtu/h – 25%

Complies Does Not Not Observable Not Applicable

C403.3.3

[ME35]1

Hot gas bypass limited to: <=240 kBtu/h – 50% >240 kBtu/h – 25%

Complies Does Not Not Observable Not Applicable

C408.2.2.

[ME53]3

Air outlets and zone terminal devices have means for air balancing.

Complies Does Not Not Observable Not Applicable

C403.5, C403.5.1, C403.5.2

[ME123]3

Refrigerated display cases, walk-in coolers or walk-in freezers served by remote compressors and remote condensers not located in a condensing unit, have fan-powered condensers that comply with Sections C403.5.1 and refrigeration compressor systems that comply with C403.5.2..

Complies Does Not Not Observable Not Applicable

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

117 ofPage

Additional Comments/Assumptions:

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

118 ofPage

& Req.ID Final Inspection Complies? Comments/Assumptions

C303.3, C408.2.5.

[FI8]3

Furnished O&M manuals for HVAC systems within 90 days of system acceptance.

Complies Does Not Not Observable Not Applicable

C403.2.2

[FI27]3

HVAC systems and equipment capacity does not exceed calculated loads.

Complies Does Not Not Observable Not Applicable

C403.2.4.

[FI47]3

Heating and cooling to each zone is controlled by a thermostat control.

Minimum one humidity control device per installed humidification/dehumidification system.

Complies Does Not Not Observable Not Applicable

C403.2.4.

[FI47]3

Heating and cooling to each zone is controlled by a thermostat control.

Minimum one humidity control device per installed humidification/dehumidification system.

Complies Does Not Not Observable Not Applicable

C403.2.4.

[FI47]3

Heating and cooling to each zone is controlled by a thermostat control.

Minimum one humidity control device per installed humidification/dehumidification system.

Complies Does Not Not Observable Not Applicable

C403.4.1.

[FI38]3

Thermostatic controls have a 5 °F deadband.

Complies Does Not Not Observable Not Applicable

C403.2.4.

1.3

[FI20]3

Temperature controls have setpoint overlap restrictions.

Complies Does Not Not Observable Not Applicable

C403.2.4.

[FI39]3

Each zone equipped with setback controls using automatic time clock or programmable control system.

Complies Does Not Not Observable Not Applicable

C403.2.4.

2.1, C403.2.4.

2.2

[FI40]3

Automatic Controls: Setback to 55°F (heat) and 85°F (cool); 7-day clock, 2-hour occupant override, 10-hour backup

Complies Does Not Not Observable Not Applicable

C404.3

[FI11]3

Heat traps installed on supply and discharge piping of non-circulating systems.

Complies Does Not Not Observable Not Applicable

C404.4

[FI25]2

All piping insulated in accordance with section details and Table C403.11.3.

Complies Does Not Not Observable Not Applicable

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

119 ofPage

& Req.ID Final Inspection Complies? Comments/Assumptions

C404.6.1

[FI12]3

Controls are installed that limit the operation of a recirculation pump installed to maintain temperature of a storage tank. System return pipe is a dedicated return pipe or a cold water supply pipe.

Complies Does Not Not Observable Not Applicable

C408.2.1

[FI28]1

Commissioning plan developed by registered design professional or approved agency.

Complies Does Not Not Observable Not Applicable

C408.2.3.

[FI31]1

HVAC equipment has been tested to ensure proper operation.

Complies Does Not Not Observable Not Applicable

C408.2.3.

[FI10]1

HVAC control systems have been tested to ensure proper operation, calibration and adjustment of controls.

Complies Does Not Not Observable Not Applicable

C408.2.4

[FI29]1

Preliminary commissioning report completed and certified by registered design professional or approved agency.

Complies Does Not Not Observable Not Applicable

C408.2.5.

[FI7]3

Furnished HVAC as-built drawings submitted within 90 days of system acceptance.

Complies Does Not Not Observable Not Applicable

C408.2.5.

[FI43]1

An air and/or hydronic system balancing report is provided for HVAC systems.

Complies Does Not Not Observable Not Applicable

C408.2.5.

[FI30]1

Final commissioning report due to building owner within 90 days of receipt of certificate of occupancy.

Complies Does Not Not Observable Not Applicable

Additional Comments/Assumptions:

1 High Impact (Tier 1) 2 Medium Impact (Tier 2) 3 Low Impact (Tier 3)

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

1110 ofPage

Project Title:

Data filename:

American Fork Armory Lartrine Remodel I:\PROJECTS\2025 Projects\2025-121.00 UTNG American Fork Armory Remodel\Energy\Energy Code-COMCheck-Models\UNG American Fork COMcheck.cck

03/05/26Report date:

1111 ofPage

File details come from the government source that posted it. Updated .