This document is a Vortx™ Damper Placement Recommendation from Preformed Line Products for High Energy Inc.'s Liberty-Van Buren Rebuild project. The recommendation provides detailed specifications for installing Spiral Vibration Dampers (SVDs) on a transmission line with specific parameters: Grackle - ACSR cable type, compression dead-end, and armor grip suspension, located in an undulating or foothills terrain.
The document includes comprehensive placement guidelines for two types of dampers - Standard and Hi Mass Spiral Vibration Dampers - with detailed tables specifying damper placements, span lengths, ruling spans, initial and final tensions, and recommended catalog numbers. Key technical details include recommendations for different span lengths (ranging from 0-4800 feet), notes on damper installation (such as not placing more than 3 SVDs together in a subset), and specifications for water/canyon crossings. The recommended products have catalog numbers VSD-4040 and VSD-4061, with a quantity of 171 units, and the placement recommendation is dated 2019-08-16.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX I
Vibration Damper Reports and Details
All vibration dampers used on this project shall conform and be purchased in accordance with these specifications. Vibration damper type and placement shall conform to the following reports and details.
P.O. Box 91129 • Cleveland, Ohio 44101 l 440.461.5200 l www.preformed.com
SVD General Placement Recommendations
The following table contains the general recommendations for using PLP Spiral Vibration Dampers (SVDs):
Total Number of SVDs Recommended Per Span
Span Length (ft)
Standard Application
Standard Application With Final Tensions > 20% of RBS/UTS OR Crossing*
Span Application
Crossing* Span Application With Final
Tensions > 20% of RBS/UTS
0 – 800 2 4 6
801 – 1600 4 6 10
1601 – 2400 6 10 16
2401 – 3200 8 12 18
3201 – 4000 10 16 24
4001 – 4800 12 18 28
*For “Crossing” line applications that span water, canyons, highways, or other vibration inducing terrain.
Notes:
1. Tension values should correspond to the Average Annual Minimum Temperature or AAMT Final
Tensions.
2. SVDs may be subset together in sets of up to 3 SVDs apiece; Do not place more than 3 SVDs together in a subset as doing so may cause the SVDs to bind somewhat and reduce their overall effectiveness.
3. SVDs have the advantage of being placement independent and may be placed at either end of the span, or on both ends if so desired. However, SVDs are designed to be placed directly on the conductor or shield wire. Thus as a general recommendation, place SVDs on the bare conductor or shield wire approximately one hand’s width away from suspension rods, dead-end rods, ties, etc
6-7
Transmission: Section
(440) 461-5200 • inquiries@preformed.com • www.preformed.com • EN-CA-1014-2
S piral V ibration D am per
Spiral Vibration Damper
1. This product may be reused if in good condition.
2. This product is intended for use by trained craftspeople only. This product SHOULD NOT BE USED by anyone who is not familiar with and trained in the use of it.
3. When working in the area of energized lines with this product, EXTRA CARE should be taken to prevent accidental electrical contact.
Damping devices are designed for the single purpose of reducing vibration. This single function is entirely different from that of protecting against (1) stress concentrations,
(2) fretting or abrasion, and (3) arc-over burning. Because of this, damping devices should be considered only as supplemental to WRAPLOCK® Tie, Armor Rod, Side Tie, Spool Tie, or other hardware at tangent supports. Dampers are also used as supplemental protection at Dead-ends.
The degree of protection needed on a specific line depends upon a number of factors such as line design, temperature, tension, exposure to wind flow, and vibration history on similar construction in the same area.
Spiral Vibration Dampers are also effective on certain size overhead shield wires and OPGW. Consult PLP® for specifics.
For damper applications on ADSS cable, refer to the FIBERLIGN® Fiber Optic Products catalog under motion control.
Consult your PREFORMED™ Sales Representative for placement and installation guidelines.
MATERIAL. The solid polyvinyl chloride helical rod material is noncorrosive and has a surface hardness which does not abrade the conductor.
GENERAL RECOMMENDATIONS
SAFETY CONSIDERATIONS
Length: Assists in identification of conductor size, corresponding to tabular information appearing on following page.
Damping Section: Helically scaled for interplay of damper and conductor, to provide the action/reaction motion that opposes the natural vibration wave.
Note: Water/Canyon Crossings – due to the increased potential of laminar wind flow, an additional 50% more dampers per span should be added to the standard rec-ommendations above for adequate protection.
In areas that are prone to high levels of vibration or conductor tension is in excess of 20% RBS, consult Preformed Line Products for specific recommendations.
NOMENCLATURE
4. For PROPER PERFORMANCE AND PERSONAL SAFETY be sure to select the proper size PREFORMED Spiral Vibration Damper before application.
5. PREFORMED Spiral Vibration Dampers are precision devices. To insure proper performance, they should be stored in cartons under cover and handled carefully.
APPLICATION-INSPECTION. The Gripping Section should be installed approximately one hand's width from the ends of Armor Rod or other hardware. It is not neces-sary to make engineering calculations as to placement.
Usage Recommendations for Spiral Vibration Dampers on Bare Conductor, Shield Wire and OPGW.
Gripping Section: Has a smaller helix designed to the grip conductor.
Span Length 0-800' 801'-1600' 1601'-2400'
Standard 2 4 6
Hi Mass 1 2 3
Number of SVDs Per Span
Thermal Rating (Continuous) 125°C
6-8
(440) 461-5200 • inquiries@preformed.com • www.preformed.com • EN-CA-1014-2
Spiral Vibration Damper (Standard)
For use on:
Bare Conductors, Shield Wires and OPGW
Catalog Number
Diameter Range (Inches)
Units Wt./Lbs. Length (Inches)Min. Max.
5050102 .174 .249 50 29 46
5050103 .250 .326 50 31 49
5050104 .327 .461 50 34 51
5050105 .462 .563 50 36 53
5050106 .564 .760 25 50 65
EXPLANATORY NOTES:
(1) Up to three SVDs can be subset together in one location where the cable diameter is 0.461" and below.
(2) On the cables with diameters above 0.461", only two SVDs should be subset for optimal damping performance.
6-9
Transmission: Section
(440) 461-5200 • inquiries@preformed.com • www.preformed.com • EN-CA-1014-2
Spiral Vibration Damper (Hi Mass) S piral V ibration D am per
CONSTRUCTION
The Hi Mass Spiral Vibration Damper (HMSVD) has a damping section close to double that of the standard SVD. By extending the length of the damping section, one Hi Mass SVD provides the effectiveness of two standard SVDs.
BENEFITS
• Fewer points of installation.
• Fewer components on the line.
For use on:
Bare Conductors, Shield Wires and OPGW
Catalog Number
Diameter Range (Inches)
Units Wt./Lbs. Length (Inches)Min. Max.
5050200 .250 .326 50 55 87
5050201 .327 .461 50 60 91
5050202 .462 .563 50 65 94
5050203 .564 .760 15 55 97
EXPLANATORY NOTES:
(1) Up to three SVDs can be subset together in one location where the cable diameter is 0.461" and below.
(2) On the cables with diameters above 0.461", only two SVDs should be subset for optimal damping performance.