Appendix D - OPGW and Fiber Optic Cable.pdf
PDF 9 MB Posted
- Solicitation number
- 89503625RSW000052
About this file
The provided documents are a collection of technical specification sheets, installation instructions, and product details for Optical Ground Wire (OPGW) cables and fiber optic cables from AFL. The primary documents include:
-
OPGW Specification Sheets (DNO-3091 and DNO-10211) for AlumaCore Optical Ground Wire cables, detailing technical specifications such as cable construction, fiber type (Corning Singlemode), component details, and mechanical/electrical characteristics. The cables are designed for overhead power transmission lines, with specifications including fiber count (12 and 36 fibers), cable diameter (14.00 mm and 16.70 mm), and breaking load (7,313 kg and 9,175 kg).
-
Installation instructions for OPGW cable installation, splice enclosure preparation, and fiber splicing, providing detailed guidance on cable handling, stringing procedures, sagging methods, dead ending, and splice tray management. The instructions cover critical aspects like cable preparation, optical unit routing, fiber splicing techniques, and enclosure sealing, with specific steps for different cable designs including ADSS, Loose Tube, and Stainless Steel Tube cables.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPENDIX D
OPGW & FIBER OPTIC CABLE
• OPGW Specification Sheet, DNO-3091 AC-25/49/551
• OPGW Specification Sheet, DNO-10211-AC-49/59/657
• AFL OPGW Installation Instructions
• AFL Reel Handling & Storage
• AFL AlumnaCore OPGW in SB01 Splice Enclosure
• Substation Fiber Specification Sheet, Corning Optical Fiber Cable 036EUZ-T4101D2N
Specification DNO-3091
AlumaCore Optical Ground Wire
PO Box 3127
Spartanburg, SC 29304
1 800 235 3423
1 864 433 5560
Tel:
Fax:
Component Details
Standards
AC-25/49/551
#Component OD Area
CENTER
Aluminum Pipe 1 inmm8.40 0.3307 mm²34.99 in²0.0542
LAYER 1 - LEFT HAND LAY
Aluminum Clad Steel (20.3% IACS) 8 inmm2.80 0.1102 mm²49.26 in²0.0764
Aluminum Alloy 6201 4 inmm2.80 0.1102 mm²24.63 in²0.0382
* - Cross Section drawing shown is representative.
Designed and Manufactured in accordance with the following:
Fiber Corning® Singlemode: ITU-T G.652D/G.657.A1ꞏ Cable IEEE 1138, IEC 60794-4ꞏ Color Code ANSI/EIA 359-A, TIA 598-C, IEC 60304ꞏ Aluminum Alloy Wires ASTM B398, IEC 60104Aꞏ Aluminum Clad Steel Wires ASTM B415ꞏ
12 Corning® Singlemode
DNO-3091 8/27/2002 Version 30.3 Page 1 - 5
Printed on 12/19/2018 AFL Confidential
Mechanical / Electrical Details
Optical Details
18 Fiber Tight Structure Design (3 - 6 fiber units)
Unit Fiber Type Fiber Count
Corning® SinglemodeBlue 6
Corning® SinglemodeOrange 6
Filler N/A
12Total Fiber Count
Installation and cable preparation procedures are outlined in the AFL documents listed below. Contact AFL to request copies.
Installation and Handling Recommendations
Recommended Installation Procedures for Composite Optical Ground Wire
Installation Instructions for Installing Optical Ground Wire in an AFL Splice Enclosure
Fiber Optic Cable Receiving, Handling and Storage. Document ACS-WI-809
7,313 16,123 lbskg
14.00 0.551 inmm
507 1,798 lbs/milekg/kmApproximate Cable Weight
10,781 15,333
1.61E-05 8.96E-06 kpsi
1/°F kg/mm²
1/°C
1-1440
0.4024 0.6476Ohms/km Ohms/mile
96 (kA)²•sec
Short Circuit Duration 1 sec 9.8 kA9.8 kA
96 (kA)²•sec
1-1440
40 °C °F104
108.88 0.1688mm² in²
Calculated Breaking Load
Approximate Cable Diameter
Total Cross-Sectional Area
Modulus of Elasticity
Coefficient of Linear Expansion
Sag10™ Chart Number
Calculated DC Resistance (20°C)
Short Circuit Rating
Short Circuit Ambient Temperature
Attenuation Characteristics for Corning® Singlemode Fiber
0.35 dB/km 1310 nm
0.22 dB/km 1550 nm
Max Individual
1 2 3 4 5 6 7 8 9 10 11 12
Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua
Standard Fiber Color Code
Designs with more than 12 fibers per tube will use the standard color code and binders for identification of the fibers.
Fiber
Color
DNO-3091 8/27/2002 Version 30.3 Page 2 - 5
Quick Reference Installation Notes
Shipping Reels
1,463 3,225 lbskg
98 39 incm
56 22 incm
21 9 incm
28 11 incm
3.8 1.5 incm
8.0 incm Buffer Tube
3.0
14.00 0.551 inmm
Approximate Cable Diameter
Maximum Stringing Tension (at tensioner)*
Minimum Bull Wheel Diameter
Stringing Sheave Diameter**
Minimum Bending Radius
Cable
Fiber
Static (No load)
Dynamic (under tension)
Static (No load)
Static (No load)
The stringing tension is always measured at the tensioner side. In general the maximum stringing tension should be approximately half of the maximum sagging tension and should never exceed 20% RBS of the OPT-GW.
The value indicated is for the first and last structures of the pull and is based on 40 times the diameter of the OPT-GW. Smaller diameters can be used at tangent structures. Reference AFL's installation instructions for more details.
Reference AFL's "Recommended Installation Procedures for Composite Optical Ground Wire" for detailed installation instructions.
FL TR DR
(meters)(cm) (in) (feet)
OW FL TR DR OW
(kgs) (lbs)
Reel Type
CapacityTareTare
60Wood 152 3691 3691 42107 245 15,2504,650540
66Wood 168 3691 3691 42107 260 21,3206,500573
72Wood 183 3691 3691 42107 300 22,9607,000662
72Wood 183 48122 42107 55140 363 22,9607,000800
84Wood 213 3486 3589 41104 385 22,9607,000849
60Steel 152 3281 3281 3897 156 15,6804,780344
72Steel 183 3691 40102 42107 245 22,9607,000540
84Steel 213 45114 42107 51130 351 22,9607,000774
Wood: 3-1/8in (7.9cm) Steel: 3-1/4in (8.2cm)
FL - Flange Diameter; TR - Inside Traverse Width; DR - Drum Diameter; OW - Outside Overall Width Minimum Arbor Hole Diameter:
Maximum lengths shown are the longest lengths that AFL offers. Longer lengths may be possible.
Ordered lengths should include a distribution of lengths, i.e., all reels cannot be ordered at the maximum. A typical reel length distribution is as follows:
6000m – 7000m ~ 15% of reels 4500m – 6000m ~ 55% of reels 2500m – 4500m ~ 25% of reels <2500m ~ 5% of reels
Wood reels with flex-wrap covering are standard. Non-returnable steel reels and/or wood lagging are available upon request. Additional reel sizes may be available upon request.
Steel reels are recommended for long term storage. Reference AFL's "Fiber Optic Cable Receiving, Handling and Storage" document for additional information.
Reel dimensions are typical and subject to availability at the time of shipment.
DNO-3091 8/27/2002 Version 30.3 Page 3 - 5
Electrical Characteristics
(°C) (Ohms/mile)(Ohms/km) (Ohms/mile)(Ohms/km)(°F)
0.0179
0.4883
0.1119 feet
Ohms/mile
MOhmsꞏmile
0.3034 Ohms/km
0.1801 MOhmsꞏkm
0.55 cm
0.00364
0.6476 Ohms/mile0.4024 Ohms/km
0.4069 Ohms/mile0.2528 Ohms/km
0.1343 MOhmsꞏmile0.2162 MOhmsꞏkm
(1/°C)
Composite DC Resistance [20°C]
Geometric Mean Radius
Inductive Reactance [60 Hz frequency]
[one foot (0.3048 meter) spacing]
[50 Hz frequency]
Capacitive Reactance [60 Hz frequency]
[one foot (0.3048 meter) spacing]
[50 Hz frequency]
Composite Coefficient of Thermal Resistance
Temperature DC Resistance AC Resistance
20 0.6476 0.66060.4024 0.410568
25 0.6594 0.67260.4098 0.418077
30 0.6712 0.68470.4171 0.425486
35 0.6830 0.69670.4244 0.432995
40 0.6948 0.70870.4318 0.4404104
45 0.7067 0.72080.4391 0.4479113
50 0.7185 0.73280.4464 0.4554122
55 0.7303 0.74490.4538 0.4628131
60 0.7421 0.75690.4611 0.4703140
65 0.7539 0.76890.4684 0.4778149
70 0.7657 0.78100.4758 0.4853158
75 0.7775 0.79300.4831 0.4928167
80 0.7893 0.80500.4904 0.5002176
85 0.8011 0.81710.4978 0.5077185
90 0.8129 0.82910.5051 0.5152194
95 0.8247 0.84120.5124 0.5227203
100 0.8365 0.85320.5198 0.5302212
105 0.8483 0.86520.5271 0.5376221
110 0.8601 0.87730.5344 0.5451230
115 0.8719 0.88930.5418 0.5526239
120 0.8837 0.90130.5491 0.5601248
125 0.8955 0.91340.5564 0.5676257
130 0.9073 0.92540.5638 0.5750266
135 0.9191 0.93750.5711 0.5825275
140 0.9309 0.94950.5784 0.5900284
145 0.9427 0.96150.5858 0.5975293
150 0.9545 0.97360.5931 0.6050302
DNO-3091 8/27/2002 Version 30.3 Page 4 - 5
PLS-CADD Inputs
Name
Description
Cross section area
Outside diameter
Temperature at which strand data below obtained
0.1688
0.551
AFL OPGW DNO-3091 AC-25/49/551
Unit weight
Ultimate tension
0.341
16,123
Use simplified elastic cable model (no creep, no coefficient)
Number of independent wires 1
(above should be 1 unless cables are separated by spacers)
(in^2)
(in)
(lbs/ft)
(lbs)
(deg F)
Outer Strands
Final Modulus of elasticity
Thermal expansion coeff.
152500
0.000920
Core Strands (if different from outer strands)
Final Modulus of elasticity
Thermal expansion coeff.
Polynomial coefficients (all strains in %) Polynomial coefficients (all strains in %)
-1202.2Stress-strain
A0
138124.1
A1
-39455.6
A2
-83364
A3
65244
A4
Stress-strain
244Creep 61047.3 309368.4 -702084 452245 Creep
A0 A1 A2 A3 A4
(psi/100)
(/100 deg F)
(psi/100)
(/100 deg F)
Thermal Rating Properties
Resistance at two different temperatures
Resistance 0.6594
Resistance 0.7775 at 77
167at
Emissivity coefficient
Solar absorption coefficient
Core heat capacity
0.5
0.5
Outer strands heat capacity
Generate Coefficients from points on stress-strain curve OK Cancel
* These two fields do not need to be entered for OPGW - intentionally left blank.
(Ohms/mile)
(Ohms/mile)
(deg F)
(deg F) (Watt-s/ft-deg F)
(Watt-s/ft-deg F)
DNO-3091 8/27/2002 Version 30.3 Page 5 - 5
Specification DNO-10211
AlumaCore Optical Ground Wire
PO Box 3127
Spartanburg, SC 29304
1 800 235 3423
1 864 433 5560
Tel:
Fax:
Component Details
Standards
AC-49/59/657
#Component OD Area
CENTER
Aluminum Pipe 1 inmm9.60 0.3780 mm²42.68 in²0.0661
LAYER 1 - LEFT HAND LAY
Aluminum Clad Steel (20.3% IACS) 6 inmm3.55 0.1398 mm²59.39 in²0.0921
Aluminum Alloy 6201 5 inmm3.55 0.1398 mm²49.49 in²0.0767
* - Cross Section drawing shown is representative.
Designed and Manufactured in accordance with the following:
Fiber Corning® Singlemode: ITU-T G.652D/G.657.A1· Cable IEEE 1138, IEC 60794-4· Color Code ANSI/EIA 359-A, TIA 598-C, IEC 60304· Aluminum Alloy Wires ASTM B398, IEC 60104A· Aluminum Clad Steel Wires ASTM B415·
36 Corning® Singlemode
DNO-10211 5/22/2014 Version 30.3 Page 1 - 5
Printed on 8/28/2018 AFL Confidential
Mechanical / Electrical Details
Optical Details
36 Fiber Tight Structure Design (3 - 12 fiber units)
Unit Fiber Type Fiber Count
Corning® SinglemodeBlue 12
Corning® SinglemodeOrange 12
Corning® SinglemodeGreen 12
36Total Fiber Count
Installation and cable preparation procedures are outlined in the AFL documents listed below. Contact AFL to request copies.
Installation and Handling Recommendations
Recommended Installation Procedures for Composite Optical Ground Wire
Installation Instructions for Installing Optical Ground Wire in an AFL Splice Enclosure
Fiber Optic Cable Receiving, Handling and Storage. Document ACS-WI-809
9,175 20,226 lbskg
16.70 0.657 inmm
674 2,391 lbs/milekg/kmApproximate Cable Weight
10,036 14,275
1.67E-05 9.30E-06 kpsi
1/°F kg/mm²
1/°C
1-1455
0.2785 0.4482Ohms/km Ohms/mile
191 (kA)²•sec
Short Circuit Duration 1 sec 13.8 kA13.8 kA
191 (kA)²•sec
1-1455
40 °C °F104
151.55 0.2349mm² in²
Calculated Breaking Load
Approximate Cable Diameter
Total Cross-Sectional Area
Modulus of Elasticity
Coefficient of Linear Expansion
Sag10™ Chart Number
Calculated DC Resistance (20°C)
Short Circuit Rating
Short Circuit Ambient Temperature
Attenuation Characteristics for Corning® Singlemode Fiber
0.35 dB/km 1310 nm
0.25 dB/km 1550 nm
Max Individual
1 2 3 4 5 6 7 8 9 10 11 12
Blue Orange Green Brown Slate White Red Black Yellow Violet Rose Aqua
Standard Fiber Color Code
Designs with more than 12 fibers per tube will use the standard color code and binders for identification of the fibers.
Fiber
Color
DNO-10211 5/22/2014 Version 30.3 Page 2 - 5
Quick Reference Installation Notes
Shipping Reels
1,835 4,045 lbskg
117 46 incm
67 27 incm
25 10 incm
34 14 incm
3.8 1.5 incm
8.0 incm Buffer Tube
3.0
16.70 0.657 inmm
Approximate Cable Diameter
Maximum Stringing Tension (at tensioner)*
Minimum Bull Wheel Diameter
Stringing Sheave Diameter**
Minimum Bending Radius
Cable
Fiber
Static (No load)
Dynamic (under tension)
Static (No load)
Static (No load)
The stringing tension is always measured at the tensioner side. In general the maximum stringing tension should be approximately half of the maximum sagging tension and should never exceed 20% RBS of the OPT-GW.
The value indicated is for the first and last structures of the pull and is based on 40 times the diameter of the OPT-GW. Smaller diameters can be used at tangent structures. Reference AFL's installation instructions for more details.
Reference AFL's "Recommended Installation Procedures for Composite Optical Ground Wire" for detailed installation instructions.
FL TR DR
(meters)(cm) (in) (feet)
OW FL TR DR OW
(kgs) (lbs)
Reel Type
CapacityTareTare
60Wood 152 3691 3691 42107 245 10,6603,250540
66Wood 168 3691 3691 42107 260 14,8904,540573
72Wood 183 3691 3691 42107 300 17,6505,380662
84Wood 213 3486 3589 41104 385 17,6505,380849
60Steel 152 3281 3281 3897 156 10,9503,340344
72Steel 183 3691 40102 42107 245 17,7105,400540
84Steel 213 45114 42107 51130 351 19,6105,980774
Wood: 3-1/8in (7.9cm) Steel: 3-1/4in (8.2cm)
FL - Flange Diameter; TR - Inside Traverse Width; DR - Drum Diameter; OW - Outside Overall Width Minimum Arbor Hole Diameter:
Maximum lengths shown are the longest lengths that AFL offers. Longer lengths may be possible.
Ordered lengths should include a distribution of lengths, i.e., all reels cannot be ordered at the maximum. A typical reel length distribution is as follows:
6000m – 7000m ~ 15% of reels 4500m – 6000m ~ 55% of reels 2500m – 4500m ~ 25% of reels <2500m ~ 5% of reels
Wood reels with flex-wrap covering are standard. Non-returnable steel reels and/or wood lagging are available upon request. Additional reel sizes may be available upon request.
Steel reels are recommended for long term storage. Reference AFL's "Fiber Optic Cable Receiving, Handling and Storage" document for additional information.
Reel dimensions are typical and subject to availability at the time of shipment.
DNO-10211 5/22/2014 Version 30.3 Page 3 - 5
Electrical Characteristics
(°C) (Ohms/mile)(Ohms/km) (Ohms/mile)(Ohms/km)(°F)
0.0213
0.4669
0.1067 feet
Ohms/mile
MOhms·mile
0.2901 Ohms/km
0.1717 MOhms·km
0.65 cm
0.00362
0.4482 Ohms/mile0.2785 Ohms/km
0.3890 Ohms/mile0.2417 Ohms/km
0.1280 MOhms·mile0.2061 MOhms·km
(1/°C)
Composite DC Resistance [20°C]
Geometric Mean Radius
Inductive Reactance [60 Hz frequency]
[one foot (0.3048 meter) spacing]
[50 Hz frequency]
Capacitive Reactance [60 Hz frequency]
[one foot (0.3048 meter) spacing]
[50 Hz frequency]
Composite Coefficient of Thermal Resistance
Temperature DC Resistance AC Resistance
20 0.4482 0.45720.2785 0.284168
25 0.4563 0.46540.2835 0.289277
30 0.4644 0.47370.2886 0.294486
35 0.4725 0.48200.2936 0.299595
40 0.4807 0.49030.2987 0.3046104
45 0.4888 0.49860.3037 0.3098113
50 0.4969 0.50680.3088 0.3149122
55 0.5050 0.51510.3138 0.3201131
60 0.5131 0.52340.3188 0.3252140
65 0.5212 0.53170.3239 0.3304149
70 0.5294 0.53990.3289 0.3355158
75 0.5375 0.54820.3340 0.3407167
80 0.5456 0.55650.3390 0.3458176
85 0.5537 0.56480.3441 0.3509185
90 0.5618 0.57310.3491 0.3561194
95 0.5699 0.58130.3542 0.3612203
100 0.5781 0.58960.3592 0.3664212
105 0.5862 0.59790.3642 0.3715221
110 0.5943 0.60620.3693 0.3767230
115 0.6024 0.61450.3743 0.3818239
120 0.6105 0.62270.3794 0.3870248
125 0.6187 0.63100.3844 0.3921257
130 0.6268 0.63930.3895 0.3972266
135 0.6349 0.64760.3945 0.4024275
140 0.6430 0.65590.3995 0.4075284
145 0.6511 0.66410.4046 0.4127293
150 0.6592 0.67240.4096 0.4178302
DNO-10211 5/22/2014 Version 30.3 Page 4 - 5
PLS-CADD Inputs
Name
Description
Cross section area
Outside diameter
Temperature at which strand data below obtained
0.2349
0.657
AFL OPGW DNO-10211 AC-49/59/657
Unit weight
Ultimate tension
0.453
20,226
Use simplified elastic cable model (no creep, no coefficient)
Number of independent wires 1
(above should be 1 unless cables are separated by spacers)
(in^2)
(in)
(lbs/ft)
(lbs)
(deg F)
Outer Strands
Final Modulus of elasticity
Thermal expansion coeff.
124000
0.000880
Core Strands (if different from outer strands)
Final Modulus of elasticity
Thermal expansion coeff.
Polynomial coefficients (all strains in %) Polynomial coefficients (all strains in %)
-1114.5Stress-strain
A0
137270.3
A1
-16623.3
A2
-113531
A3
78251
A4
Stress-strain
709.2Creep 78505.3 59189 -132936 73913 Creep
A0 A1 A2 A3 A4
(psi/100)
(/100 deg F)
(psi/100)
(/100 deg F)
Thermal Rating Properties
Resistance at two different temperatures
Resistance 0.4563
Resistance 0.5375 at 77
167at
Emissivity coefficient
Solar absorption coefficient
Core heat capacity
0.5
0.5
Outer strands heat capacity
Generate Coefficients from points on stress-strain OK Cancel
* These two fields do not need to be entered for OPGW - intentionally left blank.
(Ohms/mile)
(Ohms/mile)
(deg F)
(deg F) (Watt-s/ft-deg F)
(Watt-s/ft-deg F)
DNO-10211 5/22/2014 Version 30.3 Page 5 - 5 www.AFLglobal.com or 800-890-8878
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
Installation Instructions
AFL Optical Ground Wire (OPGW)
(Stainless Steel Tube and Aluminum Pipe Cable Designs)
NOTE:
EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT, THESE DRAWINGS AND/OR SPECIFICATIONS ARE THE PROPERTY OF AFL TELECOMMUNICATIONS LLC, ARE ISSUED IN STRICT CONFIDENCE, AND SHALL NOT BE REPRODUCED OR COPIED OR USED AS THE BASIS FOR MANUFACTURE OR SALE OF PRODUCT WITHOUT PERMISSION.
CERTAIN INFORMATION SUCH AS THE DATA, OPINIONS OR RECOMMENDATIONS SET FORTH HEREIN OR GIVEN BY AFL REPRESENTATIVES, IS INTENDED AS A GENERAL GUIDE ONLY. EACH INSTALLATION OF OVERHEAD ELECTRICAL CONDUCTOR, UNDERGROUND ELECTRICAL CONDUCTOR, AND/OR CONDUCTOR ACCESSORIES INVOLVES SPECIAL CONDITIONS CREATING PROBLEMS THAT REQUIRE INDIVIDUAL SOLUTIONS AND, THEREFORE, THE RECIPIENT OF THIS INFORMATION HAS THE SOLE RESPONSIBILITY IN CONNECTION WITH THE USE OF THE INFORMATION. AFL
DOES NOT ASSUME ANY LIABILITY IN CONNECTION WITH SUCH INFORMATION.
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
TABLE OF CONTENTS
CONTENTS PAGE NO.
General Information 3
Precautions 3
Cable Installation 3
Stringing Procedures 4
Sagging Methods 7
Dead Ending and Clipping In 8
Splice Points 10
Anchoring the Optical Units in the Splice Enclosure 11
Reference A 12
Ratio of Sheave Diameter/Cable Diameter Chart 14
Anti-Rotational Device Examples 15, 16
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
1.0 General Information
Composite Optical Ground Wire (OPGW) was developed to provide a large capacity telecommunications system utilizing overhead power transmission lines. Serving the additional purpose of an overhead ground wire, the OPGW is constructed of aluminum clad steel strands and aluminum alloy strands stranded with stainless steel tubes or surrounding a fiber unit (core) which contains optical fibers. OPGW can be installed using the basic stringing methods currently employed for overhead ground wires, with minor variations.
This document outlines basic installation methods applicable for existing and newly constructed transmission lines. The installer should be thoroughly familiar with the installation of conventional overhead ground wire and conductors. Additional information can be obtained from the latest revision of IEEE Guide to Installation of Overhead Transmission Line Conductors, IEEE Std 524.
2.0 Precautions
Care must be taken to avoid damaging the OPGW during handling and stringing operations. Avoid sharp bends to the cable and take precautions to prevent crushing the OPGW during placement. The transmission quality of the optical fibers can potentially be degraded if the OPGW is subjected to excessive pulling tensions or excessively small bend diameters.
Always observe the recommended values for Maximum Stringing Tensions and Minimum Bend Radius. More information about these values is contained on the following pages.
OPGW is normally supplied on non-returnable wooden reels. The cable is packaged with a flex wrap or wooden lagging to provide additional protection during transportation. If the cable is not to be installed for a period of over four months from the delivery date, it is recommended that the cable be requested and shipped on steel reels rather than wood reels. Please contact AFL for more details or to request shipment on steel reels.
OPGW cable reels should always be transported and handled in an upright position. Never lay a reel of cable on its side. It is recommended that each reel of OPGW be tested prior to and after installation to ensure that fiber damage has not occurred during shipping and/or stringing operations. All cable protective packaging (wood lagging or flex wrap) must remain in place on all reels until placed on a pay-out rack and the rack is in position for cable stringing.
Above all, be familiar with and observe all of your company’s safety rules when working with overhead transmission lines. These installation recommendations should not supersede any established safety practices.
3.0 Cable Installation
Reel Preparation Prior to Beginning a Pull
AFL ships the cable reels with the inner tail securely connected to the outside of the reel flange. This connection should be loosened, but not removed, prior to stringing. This allows the inner layers of cable to adjust themselves to the varying tensions seen during installation.
As the cable makes these adjustments, the inner tail may lengthen, or “grow,” requiring periodic attention to ensure that the cable continues to be in a state where it can “grow” out.
The wooden reel will have through bolts connecting the two flanges. During shipment, these bolts can loosen. Prior to stringing, the bolts should be tightened to help prevent any issues while paying off the cable.
AFL recommends using the controlled tension stringing method of installation. Ordinary stringing equipment can be utilized as if installing standard overhead ground wire provided all of the minimum block sizes and other requirements of these instructions are followed.
Suitable equipment includes pullers, tensioners, reel winders, and stringing blocks.
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
Figure 1 illustrates a typical stringing setup.
Table 1—Temperature Ranges Storage -50°C to +85°C (-58°F to +185°F)
Installation -30°C to +85°C (-22°F to +185°F)
Operation -40°C to +85°C (-40°F to +185°F)
There is one primary difference between installing OPGW and conventional overhead ground wires. Standard ground wires are typically spliced using compression type connectors and locations of the splices are relatively flexible. The splice locations of the OPGW cable must be planned to allow for splicing of the optical fibers. The reel lengths will be engineered to locate the cable splices at predetermined towers on each end of a stringing section.
After installing dead ends, the free ends of the OPGW are trained down the towers to the an additional 75 feet (23 meters) to accommodate the splicing. After stringing, this cable length is typically coiled and temporarily stored at the tower until the splicing occurs.
The OPGW will also use special attachment hardware, including dead ends, suspension clamps, and wire fittings such as grounding clamps. The hardware is designed to provide the necessary holding strengths and prevent deformation of the fiber unit which could potentially damage the optical fibers.
PAYOUT
REEL
TENSIONER
15’ 300’
100’
OPGW CABLE
ANTI-ROTATIONAL
DEVICE
STRINGING BLOCK
100’
PULLING
LINE
PULLING
MACHINE
300’DISTANCE TO STRINGING EQUIPMENT FROM
TOWER IS THREE TIMES BLOCK HEIGHT
Figure 1—Typical Stringing Setup
4.0 Stringing Procedures
Stranded wire pulling lines are generally used, although nylon ropes have also been employed. In either case, the line must be rated strong enough to withstand the required stringing tensions. The pulling line should have the same direction lay as the OPGW to help resist the tendency to rotate under stringing load.
If an existing overhead ground wire is to be removed, it can potentially be used as a pulling line for the OPGW. A visual inspection should be made of the existing ground wire to be sure it is in suitable condition. If there is any concern about the existing wire’s ability to withstand the stringing tensions, it should be pulled out and replaced with a pulling line.
It is recommended to use a bull-wheel type tensioner with round (not “V” type) polyurethane lined contact grooves. The tensioner should have two bull-wheels, each with multiple grooves to minimize cable damage. The tensioner should be capable of maintaining the required tensions at various pulling speeds. Positive braking systems are necessary for pullers and tensioners to maintain the tension when pulling is stopped. Minimum diameter of the bull wheels should not be less that 70 x D (diameter of the OPGW). For cable diameters greater than 0.787” (20 mm), please contact AFL.
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
The OPGW must be reeved (threaded) through the bull-wheel tensioner properly. Left hand lay OPGW (typical USA) is reeved from right to left, as shown in Figure 2. Right hand lay OPGW (typical International), is reeved from left to right. A thorough explanation of the reeving process can be found in the latest revision of IEEE Std 524. This arrangement is necessary to avoid any tendency to loosen the outer layer of strands and to avoid induced torque during installation.
The reel shall be placed directly in line with the tensioner. The distance from the reel to the tensioner should be at least 25 feet (7.5 meters). The OPGW shall not be permitted to scrape the reel flanges while being pulled.
The OPGW cable reels are not designed to withstand the braking forces present during stringing. Direct tensioning of the OPGW from the cable reel is not recommended. Back tension on the reel should only be enough to keep the cable properly seated in the tensioner grooves and to prevent overshooting and bird-caging.
Two basic types of pulling machines are recommended for tension stringing. These are either drum type or bull wheel type pullers. Positive braking systems are required in either case. On a drum type puller, the pulling line is taken up directly onto the drum. On the bull wheel type, the line is threaded onto two bull wheels, much like the tensioner, and onto a self winding drum.
Stringing blocks, sometimes called travelers or sheaves, are mounted on the structure at the OPGW attaching point in the normal manner.
Please refer to Reference A, OPGW Diameters and Bending Radius, for information on blocks diameters.
The stringing blocks should have neoprene lined grooves. The linings should be in good condition and adhering to the block. Minor rough areas can be sanded out to ensure the lining is smooth.
“Radius Blocks,” “Banana Blocks” or “Array Travelers” as shown below in Figures 3A-C are strictly prohibited during the installation of OPGW. The decreased surface area in contact with the OPGW is sufficient to damage the OPGW at typical stringing tensions.
Figure 2—Reeving direction for Left Hand Lay OPGW cable, typical in North America.
A
Figures 3A-C—These types of array installation blocks should NOT be used to string OPGW.
B C
Uplift rollers (which attach to the installation sheave wheel) or hold-down blocks (which are separate blocks) need to be placed where uplift of the pulling line is likely to occur (due to its higher tension/weight ratio than the conductor). This will typically occur going up inclines or at a low point in a section. These devices should also have a break away feature in the event of fouling or incorrect installation.
The size of the uplift rollers should follow the same guidelines as the installation sheaves shown in Reference A.
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
The tensioner and puller should be positioned for a 3:1 ratio to the stringing block on the first structure adjacent to the equipment.
See Figure 1. The tensioner should be placed in line with the first two structures (or first span) of the pull. Likewise, the puller should be placed in line with the last two structures (or last span) of the pull. Doing so minimizes the line angle change seen by the cable during the installation process.
This minimum stringing block diameter and distance to the tensioner (3:1) are recommended to help prevent deformation of the fiber unit (aluminum pipe, stainless steel tube or slotted core), which protect the optical fibers in the OPGW.
The use of an Anti-Rotational Device (see sample drawings on pages 15 and 16) depends largely upon the construction of the optical ground wire. Such a device is used to prevent the OPGW from twisting while being pulled. Variations of these devices have been successfully used.
Please consult AFL for any inquiries regarding a particular form of anti-rotation device.
For cables with helically stranded stainless steel tubes, an anti-rotational device may or may not be required. To confirm whether one is needed for your particular application, contact AFL. When in doubt, the conservative approach is to conduct the installation with the use of an anti-rotational device. For cables constructed with an un-stranded stainless steel tube in the center of the cable or single layer cables, an anti-rotational device is always a requirement. (See Appendix 2 on page 15 and Appendix 3 on page 16.)
If the anti-rotational device is not preventing the cable rotation or if the anti-rotational device is wrapping around the OPGW, a stiffer or heavier device is required. The weight and length of the ARD will depend upon the construction of the optical ground wire.
The anti-rotational device attaches to the OPGW with a Kellum type grip. The grip must be appropriately sized for the OPGW diameter and pulling tensions.
Normally, the OPGW should be kept under constant stringing tension during the stringing process to keep the line clear of both the ground and other obstacles that could cause damage to the cable.
Do not cut the OPGW with ratchet cutters or other types of tools that could crush or crimp the optical core.
The use of a hacksaw will ensure the fiber optic units are free to move within the pipe. During stringing, the optical fiber core (design dependent) may pull back into the cable, requiring a few feet to be cut away upon splicing on the leading end to expose the optical core.
It is important to monitor the tensions and ensure that excessive tension is not applied as the OPGW passes from the reel to the tensioner.
Table 2 on the following page show the recommended values for safe OPGW installation.
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
5.0 Sagging Methods
The methods and procedures for sagging the OPGW are the same as those for normal overhead ground wires. For determining sags, the installer should use the sag-tension design information provided by the utility or AFL. Sagging and tensioning should be conducted from dead end to dead end. Care should be taken to avoid sagging the cable around angles greater than 30 degrees.
A temporary grip is installed on the OPGW for tensioning. The grip must be designed to aluminum pipe. AFL can provide a come-along, sometimes called a pocketbook grip, that can be attached anywhere along the length of an OPGW. Figure 4 illustrates a satisfactory come-along design.
Table 2—Recommended Values for Safe OPGW Installation
PARAMETER VALUE
Minimum Bull Wheel Diameter 70 x OPGW diameter
For larger diameter OPGW cables where 70 x OD exceeds 60" (~1.5 m), a 60" (~1.5 m) bull wheel may be used.
Please consult AFL in such cases.
Recommended Block Diameter for first and last structure
40 x D
Smaller diameters can be used at tangent structures. See Reference A.
Minimum Cable Bend Radius During Installation (Dynamic): 20 x OPGW diameter
After Installation (Static): 15 x OPGW diameter
Maximum Stringing Tension 20% of the Rated Breaking Strength of OPGW
The stringing tension is always measured at the tensioner side. In general, the maximum stringing tension should be a half of the maximum sagging tension and never should exceed 20% RBS of the OPGW.
Pulling Speed 60 meters (195 feet) per minute OR 3.6 km (2.2 miles ) per hour
Minimum Distance from Puller and Tensioner to the Stringing Block
3:1 Ratio
Total Number of Spans in Each Stringing Section
Typically 20 to 30*
* The maximum number of spans is included as a reference only; since this will vary considerably due to differences in terrain, span lengths, line angles, etc.
Figure 4—Come-along (Pocketbook Grip)
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
Some types of gripping devices that might induce crushing damage to the OPGW such as Chicago grip or Kito grip are strictly prohibited to use for OPGW, as shown in Figures 5A and B.
Certain types of formed guy grips can also be used successfully, but their use in stringing applications should be checked with the grip’s manufacturer.
6.0 Dead Ending and Clipping In
Dead Ends are installed on OPGW spans that terminate at splicing towers or ends of the system. Dead Ends are also used at angle structures when the angles are too great to use suspension clamps. Suspension clamps are normally used at the remaining towers. These types of hardware (dead end and single suspension) are illustrated in Figures 6 and 7.
In general, the rule for hardware use is the following:
| • | Single Suspension to be used at structures with line angles between 0 and 30 degrees. |
| • | Double Suspension to be used at structures with line angles between 30 and 60 degrees. |
| • | Double Dead End to be used at structures with line angles over 60 degrees. |
Dead ends can be used starting from line angles of 30 degrees in lieu of double suspensions.
In order to diminish the probability of motion-induced damages and creep rate change, AFL recommends that tensioning and anchoring of the OPGW to the structure and removal of the stringing blocks be completed no later than 48 hours after pulling in the cable.
Figures 5A and 5B—Types of prohibited grips used to tension OPGW.
Chicago grip (prohibited)Kito Grip (prohibited)
Figure 6—OPGW Dead end (Bolted Type) Figure 7—OPGW Suspension Unit
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
OPGW is installed using stringing blocks. If left in the stringing blocks for extended periods of time, the potential for motion induced damage (aeolian vibration) increases. Also, the creep of the cable is affected due to the change in the initial condition on the cable. In order to diminish the probability of motion induced damages and creep rate change, AFL recommends that tensioning and anchoring of the OPGW to the structure and removal of the stringing blocks be completed no later than 48 hours after pulling in the cable.
There are several ways to lift the OPGW from the stringing blocks in order to install the hardware. A come-along is attached on both sides of the block and a coffin hoist is placed over the tower arm. The hooks of the coffin hoist are attached to the come-along and jacked up to form a small loop in the OPGW. The block can then be removed and the armor rods can be placed on the OPGW then attached to the structure. Alternately, certain types of preformed wire grips can be used instead of come-along. The preformed grip can be used once as a come-along and then used permanently in the next span.
If vibration dampers are required for this span, these should be placed on the OPGW immediately after clipping in. Dampers may not be required at every structure; their locations will be specified by the utility or AFL. A drawing of an AFL Stockbridge damper is shown in Figure 8.
Figure 8—Stockbridge Damper
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
7.0 Splice Points
Splice points will be located at the beginning and end of each OPGW reel. After completion of sagging and clipping, the surplus OPGW should be coiled and attached temporarily to the tower. Coils should be approximately 3.5 to 5 feet (1 to 1.5 meters) in diameter. The coils should be fixed on the tower to prevent any damage to the OPGW prior to splicing.
The exposed ends of the OPGW should be re-sealed to prevent moisture from entering the fiber units. The cable reel may be supplied with a pair of plastic caps for sealing the cable ends. Electrical tape, RTV silicone, or other means can also be used for this purpose.
The OPGW will be trained down the tower and to the ground for splicing. Do not cut off any excess length of the OPGW at this time.
To facilitate splicing, the OPGW should extend a minimum of 75 feet (23 meters) beyond the bottom of the tower. The length of OPGW running down the tower should be attached to the structure using appropriate guide clamps, spaced every 6 to 8 feet (1.8 to 2.4 meters) of running length. Several types of guide clamps are illustrated in Figure 9.
Figure 9—OPGW Guide Clamps and Bonding Clamps
Tower Bonding ClampTower Guide Clamp
The splice enclosure will typically be installed on the structure between 15 and 20 feet (4.5 to 6 meters) above the ground. In most cases, it will be desirable to store extra cable on the tower. This will allow the splice box to be removed and lowered to the ground if it is ever necessary. This can be accomplished with a simple loop of OPGW below the splice box or by permanently storing a coil of OPGW higher on the tower.
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
8.0 Anchoring the Optical Units in the Splice Enclosure
The following is an example of anchoring the optical units when installing AFL Loose Tube OPGW (Aluminum pipe designs) in an AFL SB01-72 Splice Enclosure (See Figure 10).
| • | Once the pipe is removed, the fiber core should be cut to length and the binders removed. |
| • | Unwind the optical units and set aside the aramid yarn in the center of the unit. |
| • | Wind the optical units back into their original position and use electrical tape every 15 inches to secure the units. Leave the end of the |
units free of tape so that the units can be prepped for splicing.
| • | Remove any excess aramid yarn, leaving at least 14-18 inches to tie off into the box. |
| • | Secure the yarn to the eye bolt in the enclosure. (See Figure 10) |
| • | Tape the units (duct tape is recommended) to the top outside radius of the box (See Figure 10). This will help support the units and |
prevent damage of the units at the bushing.
| • | Tighten the retaining nut of the connector kit so that the bushing is sealed around the pipe. |
| • | Repeat the previous steps for the remaining OPGW cable(s). |
A similar procedure is available for AFL Tight Structure, HexaCore and CentraCore OPGW and AFL Opti-Guard Splice Enclosure.
** Ensuring that the optical core is “tied off” within the chosen splice enclosure (whether AFL splice enclosures or not) is a must. If not, the optical core may work its way back into the cable over time, damaging the splice box contents and potentially affecting the optical continuity. **
30 ft. (to free end of cable)
Route Optical Units Behind Yarn
Entry Bushing Seals Around the Pipe
Tie Off Yarn
Duct Tape
Remove Binder Tape at this point
Figure 10—Anchoring the Optical Units in the AFL SB01 Splice Enclosure
NOTE: There should be 30 ft of optical unit (s) prepped for each individual OPGW cable that is to be inserted into the Splice Box. The 30 ft of optical unit (s) is divided two sections:
| 1: | 20 ft from box to ground, and |
| 2: | 10 ft for storing and splicing. Should the Splice Box be mounted at a different height, |
then adjust the amount of OPGW cable to be prepped, stored and spliced.
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
Table 3—Recommended Values for Stringing and Handling OPGW
PARAMETER VALUE
Maximum OPGW Stringing Tension 20% (at tensioner) of the rated breaking strength
Minimum Bull Wheel Diameter for Tensioners
70 x OD of OPGW
For larger diameter OPGW cables where 70 x OD exceeds 60" (~1.5 m), a 60” (~1.5 m) bull wheel may be used.
Please consult AFL in such cases.
Stringing Sheave (Root) Diameter
40 x OD of OPGW
Based on a sheave through angle of 45° and maximum stringing tension (at tensioner) of 20% of the rated strength of the OPGW.
NOTE: Refer to Table 4 for additional information on minimum diameters of the stringing blocks for other conditions.
Minimum Cable Bending Radius
After Installation (Static): 15 x OD of OPGW
During Installation (Dynamic): 20 x OD of OPGW
NOTE: Based on actual OPGW size, etc., care must be taken when bending the OPGW to avoid kinking the strands and damaging the optical fibers contained within the central pipe.
Minimum Permanent Bending Radius
OPGW: 15 x OD of OPGW
Stainless Steel Tube: 45 x OD of stainless steel tube
Plastic Buffer Tubes: 3 in. (8 cm)
Optical Fibers: 1.5 in. (3.8 cm)
Swinging Angle of Stringing Block
Shall be controlled corresponding to the swinging angle of the OPGW stringing plane to help prevent the cable from riding out of the traveler or excessive twisting during installation.
The cable should travel through the lowest part of the groove.
At angle structures, this is done by tying a support rope to the sheave to keep it suspended as shown in Figure 11.
REFERENCE A
Stringing and Handling OPGW Diameters and Bending Radius
The following guides apply to AFL OPGW Cable.
Figure 11—Tying a support rope to the sheave keeps it suspended to the stringing block.
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.
Installation Instructions WI-0298 Rev 1
Table 4—Sheave Sizes for Different Stringing Angles
STRINGING OR LINE ANGLE SHEAVE SIZE (x OPGW OD)
Bull Wheel Diameter 70x
First and Last Structures 40x
Tangent Structures
Θ < 20° Stringing Angle 30x
20° < Θ < 45° Stringing Angle 40x
45° < Θ < 60° Stringing Angle 50x
60° < Θ < 90° Stringing Angle 60x
90° < Θ Stringing Angle No Go
The following are minimum diameters of stringing blocks at:
Sheave Size Recommendations
The following sheave diameters are recommended for their respective stringing angles in Table 4. These sizes are considered satisfactory if the pulling line slope is at least three horizontal to one vertical from the traveler to the site and the stringing tension does not exceed 20% of the OPGW’s rated breaking strength.
Tower
Stringing Block
OPGW
Stringing Plane δ θ/2 θ/2
Figure 12—Stringing angles and sheave size diagram
© 2012, AFL, all rights reserved. Revision 4, 2.7.19 Specifications are subject to change without notice.www.AFLglobal.com or 800-890-8878
Ratio (Sheave Diameter/Cable Diameter):Ds/Dc
0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00
10.00 11.00 12.00 13.00 14.00 15.00 16.00 17.00 18.00 19.00 20.00 21.00 22.00 23.00 24.00 25.00 26.00 27.00 28.00 29.00 30.00 31.00 32.00 33.00 34.00 35.00 36.00 37.00 38.00
5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90
Sheave Through Angle [deg]
A x ia l Lo a d
R B
S
Ds/Dc=25
Ds/Dc=28
Ds/Dc=31
Ds/Dc=34
Ds/Dc=37
Ds/Dc=40
Ds/Dc=43
Ds/Dc=46
Ds/Dc=49
Ds/Dc=52
Ds/Dc=55
Ds/Dc=58
Ds/Dc=61
Ds/Dc=64
Ds/Dc=67
Ds/Dc=70
Ds/Dc=73
Ds/Dc=76
Ds/Dc=79
Ds/Dc=82
Ds/Dc=85
Ds/Dc=88
Ds/Dc=22
22 25 28 31 34 37
Appendix 1 Sheave Size Based on Line Angle and Installation Tension
Specifications are subject to change without notice.www.AFLglobal.com or 800-890-8878
WEIGHT
DETAIL B
DETAIL A
SWIVEL GUY
WIRE
CONNICAL
FERRULE
DETAIL C
8.00
B
WEIGHT
CONNICAL
FERRULE
GUY
WIRESWIVEL
A
DIRECTION OF PULL
29.00 FT
APPROX.
C
Appendix 2 Anti-Rotational Device Example (Attached in Front of the OPGW)
Specifications are subject to change without notice.www.AFLglobal.com or 800-890-8878
7/8” WIRE ROPE
PUNCH LOK CLAMPS
OPGW
1-1/2” OD STEEL REINFORCED
HYDRAULIC HOSE
8’
2.44 m
PULLING
LINE
ROTATING SWIVEL
KELLEM GRIP
APPLY HEAVY LAYER
OF ELECTRICAL TAPE
OPGW
APPLY HEAVY LAYER
OF ELECTRICAL TAPE
APPLY HEAVY LAYER
OF ELECTRICAL TAPE
APPLY HEAVY LAYER
OF ELECTRICAL TAPE
APPLY HEAVY LAYER
OF ELECTRICAL TAPE
1’ 1’
0.30 m 0.30 m4.6 m
15’1’ 1’
0.30 m 0.30 m4.6 m
15’1’ 1’
0.15 m 0.30 m
6”
8’
2.44 m
8’
2.44 m
Appendix 3 Anti-Rotational Device Example (Attached Directly to the OPGW)
WI-0189 REV. 0
Legacy Document Number: ACS-WI-809
Effective Date: Jun 14, 2013
AFL Proprietary Page 1 of 5
Fiber Optic Cable Receiving, Handling and Storage
NOTE: EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT, THESE
DRAWINGS AND/OR SPECIFICATIONS ARE THE PROPERTY OF AFL, ARE ISSUED
IN STRICT CONFIDENCE, AND SHALL NOT BE REPRODUCED OR COPIED OR
USED AS THE BASIS FOR MANUFACTURE OR SALE OF PRODUCT WITHOUT
PERMISSION.
CERTAIN INFORMATION SUCH AS THE DATA, OPINIONS OR RECOMMENDATIONS
SET FORTH HEREIN OR GIVEN BY AFL REPRESENTATIVES, IS INTENDED AS A
GENERAL GUIDE ONLY. EACH INSTALLATION OF OVERHEAD ELECTRICAL
CONDUCTOR, UNDERGROUND ELECTRICAL CONDUCTOR, AND/OR CONDUCTOR
ACCESSORIES INVOLVES SPECIAL CONDITIONS CREATING PROBLEMS THAT
REQUIRE INDIVIDUAL SOLUTIONS AND, THEREFORE, THE RECIPIENT OF THIS
INFORMATION HAS THE SOLE RESPONSIBILITY IN CONNECTION WITH THE USE
OF THE INFORMATION. AFL DOES NOT ASSUME ANY LIABILITY IN CONNECTION
WITH SUCH INFORMATION.
AFL Proprietary Page 2 of 5
FIBER OPTIC CABLE
RECEIVING, HANDLING, AND STORAGE
Contents Section
Receipt of Cables Reels 1.0 Handling of Cable Reels 2.0 Storage Cable Reels 3.0
1.0 RECEIPT OF CABLE REELS
Upon receiving the shipment, the purchaser should conduct an acceptance inspection. A cable acceptance inspection should include several simple and inexpensive steps including but not limited to the following:
1.1. Visual Inspection For Damage During Shipment
Visually inspect all reels for any damage that may have occurred during transit. Be particularly alert for damage if:
a) A reel is laying flat on its side (flange).
b) Reels are stacked on top of each other.
c) Other freight is stacked on the reel.
d) Nails have been driven into the flange or lagging to secure blocking.
e) A reel flange is damaged or lagging is damaged.
f) The end seals of the cable have been removed or damaged, allowing potential moisture ingress into the cable.
1.2. Inspection Of Reel Tags
Visually inspect all reels to ensure that it has the proper tags and labels. Unless otherwise specified by the purchaser, the reel tag will contain the following information:
a) Manufacturer’s name (AFL).
b) Customer purchase order number.
c) AFL order number.
d) Cable size.
e) Length of cable.
f) Reel number.
g) Lot number.
h) Gross weight and net weight.
Verify that the cable description, reel size, and length are consistent with what has been ordered. The cable manufacturer should be immediately notified of any missing information or discrepancies.
AFL Proprietary Page 3 of 5
1.3. Check Cable Dimensions
The purchaser should take simple measurements of the basic cable dimensions on at least one reel of each size of cable in a shipment to verify that the cable’s dimensions meet specification requirements.
2.0 HANDLING OF CABLE REELS
When moving cable reels, care should be taken to ensure that material handling equipment does not come into contact with the cable surface.
UNDER NO CIRCUMSTANCE SHOULD CABLE REELS BE DROPPED
FROM ANY HEIGHT OR ALLOWED TO ROLL UNCONTROLLED
Whenever possible, cable reels should be moved or lifted using the following methods:
2.1. For cranes, booms, or other overhead lifting equipment, a heavy steel arbor or suitable heavy rod or pipe should be inserted through the reel hubs allowing the cable reel to be lifted by slings utilizing spreader bars or a lifting yoke. This method will minimize the sling pressure against the reel flanges and reduce the risk of the reel tipping.
2.2. When lifting reels with fork truck type equipment, reels should be lifted facing the flange with fork blades that are long enough to reach beneath both flanges. This method will ensure that the lift pressure is equally distributed on both flanges. Whenever possible, reels should be lifted with the flange that includes the cable “test tail” facing away from the fork truck. Do NOT lift the reel with the fork blades resting on the cable.
2.3. Cable reels may be moved short distances by rolling, keeping in mind that reels should always be rolled in the direction indicated by the arrows painted on the outside of the reel flanges. This will prevent loosening of the cable on the reel which may cause problems during installation.
The path over which the cable reels are to be rolled must be clear of any debris that might damage the cable. Cable reels that are unloaded down ramps should be rolled, in a controlled manner, in the direction of arrows painted on the reel flanges. The ramps must be of a gradual incline, spaced parallel, and wide enough to ensure contact at all times with both reel flanges during unloading.
AFL Proprietary Page 4 of 5
AFL Proprietary Page 5 of 5
3.0 STORAGE OF CABLE REELS
All reels should be stored in such a manner to allow easy access for lifting and moving. The reels should be stored away from construction activities, falling or flying objects, sources of high heat, open flames, chemicals or petroleum products that may come into contact with and cause damage to the cable or reel.
The cable ends must remain sealed during storage to prevent the ingress of moisture. End seals removed during acceptance testing/inspection should be replaced immediately upon completion of testing. Loose cable ends on the reels must be securely re-fastened to the reel flange. Do not allow cable ends to lie on the ground. The use of fencing or other barriers to protect the cable and reels against damage by vehicles or other equipment as well as vandalism is highly recommended.
Optical ground wire should not be exposed to storage temperatures less than -40°C or greater than 55°C, or a relative humidity greater than 98%. Dielectric cables should not be exposed to storage temperatures less than -40°C or greater than 75°C.
Ideally, fiber optic cables should be stored indoors on a hard, dry surface to prevent deterioration of the reels and possible moisture ingress into the cable. If outdoor storage is necessary, the reels must be supported off the ground and covered with a suitable weatherproof material. The reel supports should be long enough to provide an adequate load-bearing surface (to prevent sinking) and high enough to prevent the reel from sitting in free standing water (in the event of heavy rainfall).
3.1. Short-term Storage
For short-term storage, which is defined loosely as four months or less, steel or wood reels are suitable. The short-term storage period may vary depending on local conditions such as humidity, temperature fluctuations, etc.
3.2. Long-term Storage
When long-term storage is a possibility or anticipated (i.e., spare reels), steel reels should be used.
CABLE REELS SHOULD NEVER BE STACKED OR LAID ON THEIR SIDES
www.AFLglobal.com or 800-866-7385
© 2011, AFL, all rights reserved. Revision 1, 10.29.14 Specifications are subject to change without notice.
Installation Instructions
INS-ACA034
Instructions for Preparing
ALUMACORE OPTICAL GROUND WIRE
IN THE SB01 SPLICE ENCLOSURE
NOTE:
EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT, THESE DRAWINGS AND/OR
SPECIFICATIONS ARE THE PROPERTY OF AFL, ARE ISSUED IN STRICT CONFIDENCE, AND
SHALL NOT BE REPRODUCED OR COPIED…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .