This document package includes construction drawings and specifications for the Construct Bismarck O&M Service Center Vehicle Storage Building No. 4 project. The project involves constructing a new vehicle storage building at the Bismarck Operations and Maintenance Service Center in Bismarck, North Dakota. The construction drawings provide details for site work, foundations, concrete slabs, structural steel framing, and miscellaneous site elements. Specifications address requirements for excavation, backfill, concrete, reinforcement, pre-engineered metal building systems, grouting, vapor barriers, and joint fillers. The solicitation is seeking bids for the construction of the new building in accordance with the drawings and specifications provided by the Department of Energy Western Area Power Administration.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E
A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
ROUNDED CONC TOP
6" DIA STD
WEIGHT STEEL
PIPE, CONCRETE
FILLED, FINISH
COLOR SAFETY
YELLOW
CONCRETE
EMBEDMENT
1'-6"
DIA
BOLLARD
NOT TO SCALE
C500
FINISHED GRADE
(MATCH EXISTING)
TOOLED EDGE
3/4" RESILIENT FILLER
7" PCC
T/3" TOOLED OR GREEN SAW JOINT
SLAB OR
FOUNDATION
3/4" RESILIENT FILLER
T/2
T/2
T/2
7" PCC
7" PCC
6" NDDOT CLASS 5
AGGREGATE BASE
6" NDDOT CLASS 5
AGGREGATE BASE
6" NDDOT CLASS 5
AGGREGATE BASE
EXPANSION JOINT AT SLAB DETAIL
NOT TO SCALE
CU501
EXPANSION JOINT DETAIL
NOT TO SCALE
C500
PCC PAVING WITH JOINT DETAIL
NOT TO SCALE
C500
5' MAX
M
A X
VARIES SEE PLAN
4" TROWEL FINISH (TYP.)
BROOM
1/8"
1/2"
SAWED
JOINTS
(TYP)
EXPANSION JOINTS
@ 25' CTRS MAX
T
Y P
SAWCUT
PLAN
4" P.C.C.
4" NDDOT
CLASS 4
AGGREGATE
BASE COURSE
SECTION A
1/2" RADIUS (TYP.)
1. BROOM FINISH SHALL BE APPLIED NORMAL TO
DIRECTION OF TRAFFIC.
2. SIDEWALK SHALL BE CONSTRUCTED IN ACCORDANCE
WITH CITY OF BISMARCK STANDARDS.
SAW JOINT
NOTES:
EXPANSION JOINT
NOTES:
PRE-FORMED EXP.
JOINT MATERIAL
1/8" RAD 1/8" RAD
A
B
EXPANSION JOINT
SECTION B
6 X 6 - W1.4 X W1.4
COMPACTED SUBGRADE
4" NDDOT CLASS 4
AGGREGATE BASE COURSE
4" P.C.C.
1. SAW JOINTS TO BE LOCATED TO MAINTAIN AN APPROXIMATE
SQUARE SLAB AS INDICATED ON PLANS.
2. EXPANSION JOINTS TO BE LOCATED WHERE WALK ABUTS
CONCRETE CURBS, DRIVES, STRUCTURES AND WHERE WALK
CHANGES DIRECTION.
TYPICAL SIDEWALK DETAIL
NOT TO SCALE
C500
TYPICAL SIDEWALK JOINT DETAIL
NOT TO SCALE
C500
COMPACTED SUBGRADE
ISOLATION JOINT DETAIL
NOT TO SCALE
C500
(COVERS & RINGS REMOVED)
TOP VIEW
SIDE SECTION VIEW
OPERATING CAPACITY: 500 GALLONS.
DESIGN LOAD: H-20 TRAFFIC WITH DRY SOIL CONDITIONS
(WATER LEVEL BELOW TANK) AND 1'-6' EARTH COVER.
SUITABLE SUB-BASE BEDDED WITH GRANULAR MATERIAL SHALL BE
PREPARED TO HANDLE ANTICIPATED LOADS.
FOR COMPLETE DESIGN AND PRODUCT INFORMATION
CONTACT JENSEN PRECAST.
THIS DETAIL IS FROM JENSEN PRECAST. ITEM OF EQUAL SIZE AND
QUALITY IS ALSO ACCEPTABLE.
6'-0"
24"
T
O
500 GALLON SAND-OIL INTERCEPTOR
NOT TO SCALE
C500
4" PIPE AND
FITTINGS
STANDARD-TEE
OR ELBOW PER
CODE
24" CAST IRON FRAMES
AND COVERS WITH GASKET
(GASTIGHT) 2 TOTAL
3", 6" AND 12" GR2432
GRADE RINGS AS
REQUIRED AT EXTRA COST
2.0' 2.0'
4.0'
C L
P
A N
FINISHED SURFACE
#4 @ 18" O.C., EACH WAY
12" SCARIFIED & COMPACTED SUBGRADE
6" NDDOT CLASS 5 AGGREGATE BASE
CONCRETE DRAINAGE PAN
NOT TO SCALE
C500
T
NON-EXTRUDING PREFORMED
COMPRESSIBLE MATERIAL
C500
NT
CIVIL SITE DETAILS I
ACG
07/02/2020
B 06/23/20 90% DESIGN REVIEW
0 07/02/20 ISSUED FOR CONSTRUCTION
NO. 4 BARS,
18" O.C., EACH WAY
NO. 4 BARS,
18" O.C., EACH WAY
NO. 4 BARS,
18" O.C., EACH WAY
INLET
INVERT
1662.66
OUTLET
INVERT
1662.40
PVC SPIGOTS
PVC FITTING
THREADED PVC
PVC RISERS
PLUGS AT GRADE
4" OR 6"
SERVICE
LATERALS
DOUBLE CLEANOUT DETAIL
NOT TO SCALE
C500
12" SCARIFIED AND
COMPACTED SUBGRADE
12" SCARIFIED AND
COMPACTED SUBGRADE
12" SCARIFIED AND
COMPACTED SUBGRADE
1 08/28/20 REV 1
8/25/2020
AMENDMENT 0003
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E
A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
ROAD BASE SECTION
NOT TO SCALE
C501
6" NDDOT CLASS 5
AGGREGATE BASE
12" SCARIFIED AND
COMPACTED SUBGRADE
MATCH
EXIST
SEE PLAN
MATCH
EXISTING
MATCH
EXIST
MATCH
EXISTING
IN STREET
T R
E N
C H
Z
O N
E
P I P
E
O
D
L I M
I T
S
O
F
B E
D D
I N
G
BEDDING TO BE
ASTM C33 N0 67
NEW
PAVEMENT
SURFACE
UNIFORM CUT LINE
ASPHALT/CONCRETE
EXISTING
PAVEMENT
SURFACE
EXISTING BASE
COURSE
NEW BASE
COURSE
COMPACTED
BACKFILL
WIDTH PER
SPECIFICATIONS
IN OPEN FIELD
UTILITY TRENCH
NOT TO SCALE
C501
H
V
M
A
X
12"
DEMO & REPLACE
PAVEMENT 1'
BEYOND TRENCH
B c
4"
1/4 Bc
Bc + 8"
BEDDING TO BE
ASTM C33 NO 67
PLAIN OR REINFORCED
CONCRETE 2,000 PSI MIN.
CONCRETE CRADLE SECTION
NOTES:
1. TRENCHES
TRENCHES SHALL BE BRACED OR SHEETED AS NECESSARY FOR THE SAFETY OF THE WORKMEN AND FOR THE PROTECTION OF EXISTING UTILITIES IN
ACCORDANCE WITH APPLICABLE LOCAL, STATE AND FEDERAL SAFETY REGULATIONS. PVC PIPE TRENCH WIDTHS SHALL BE IN ACCORDANCE WITH
THE UNI-BELL HANDBOOK OF PVC PIPE, LATEST EDITION. DUCTILE IRON PIPE TRENCH WIDTHS AT THE TOP OF PIPE SHALL BE IN ACCORDANCE WITH
AWWA C-600 LATEST EDITION. SHOULD TRENCHES BE EXCAVATED WIDER THAN ALLOWED, THE CONTRACTOR MAY REQUIRE THAT A CONCRETE
CRADLE BE PLACED AROUND THE PIPE IN CONFORMANCE WITH THE SPECIAL BEDDING DETAIL. SUPPORT PIPE FROM WALL TO FIRST JOINT WITH
CONCRETE CRADLE STRUCTURALLY CONTINUOUS WITH BASE SLAB OR FOOTING.
2. BEDDING
CONTRACTOR SHALL SUBMIT BEDDING GRADATION TEST RESULTS FOR REVIEW, PRIOR TO DELIVERING ANY MATERIAL TO THE PROJECT SITE. SEE
SPECIFICATIONS FOR BEDDING GRADATION REQUIREMENTS. BEDDING LIMITS SHALL EXTEND FROM SIX INCHES UNDER THE PIPE TO SIX INCHES
ABOVE THE PIPE. THE LIMITS OF BEDDING DEFINE THE "PIPE ZONE". CLASS B BEDDING MATERIAL SHALL BE USED AS PIPE BEDDING. WHERE COVER
EXCEEDS 22 FEET, THE CONTRACTOR SHALL REVIEW THE INSTALLATION AND RECOMMEND BEDDING MATERIAL AND PIPE CLASS.
3. COMPACTION
PIPE ZONE (BEDDING) COMPACTION SHALL BE 90% STANDARD PROCTOR DENSITY OR EQUIVALENT RELATIVE DENSITY. TRENCH ZONE COMPACTION
SHALL BE; 95% STANDARD OR MODIFIED PROCTOR DENSITY OR EQUIVALENT RELATIVE DENSITY INSIDE STREET RIGHTS-OF-WAY; AND 90% STANDARD
OR MODIFIED PROCTOR DENSITY OR EQUIVALENT RELATIVE DENSITY OUTSIDE STREET RIGHTS-OF-WAY UNLESS SPECIFIED OTHERWISE.
GATE VALVE
THRUST
BLOCK
FINISH GRADE
VALVE
BOX
SERVICE LINE
(SIZE VARIES)
CENTER LINE MAIN
BACKFILL AS
SPECIFIED
CRUSHED
ROCK DRAIN
BED
ISOLATION VALVE
NOT TO SCALE
C501
4.5" ASPHALT BASE
6" NDDOT CLASS 5 AGGREGATE BASE
12" SCARIFIED & COMPACTED SUBGRADE
ASPHALT PAVEMENT DETAIL
NOT TO SCALE
C501
BISMARCK SANITARY SEWER MANHOLE
NOT TO SCALE
C501
FOUNDATION
WALL
8" DIA.
45° BEND
FACE OF BUILDING
3"x3" DOWNSPOUT
3"X3" TO 8" PVC
BOOT TRANSITION
PACK BOOT WITH OAKUM.
FILL WITH NON-SHRINK GROUT.
FINISH
GRADE
M I N
I M
U M
F
R O
S T
D
E P
T H
45° BEND
1. DIAMETER OF BOOT SHALL BE 1/2" GREATER THAN DOWNSPOUT'S LARGEST DIMENSION.
2. BOOT MATERIAL SHALL BE PVC. ALL ELSE SHALL BE PVC UNLESS OTHERWISE INDICATED.
NOTES:
CLEANOUT (TEE W/ PLUG)
EXTEND TO DAYLIGHT
AT DITCH. SEE SHEET
CU001 FOR ROUTING.
DOWNSPOUT AND UNDERDRAIN DETAIL
NOT TO SCALE
C501 C501
NT
CIVIL SITE DETAILS II
ACG
07/02/2020
B 06/23/20 90% DESIGN REVIEW
0 07/02/20 ISSUED FOR CONSTRUCTION
7"
1"
NOTES:
1. PLACE 3/4" EXPANSION JOINTS WITH 24" DOWELS AT RADIUS POINTS OR A
MAXIMUM OF 60' ON STRAIGHT SECTIONS. THESE DOWELS SHALL BE
GREASED AND WRAPPED ON ONE END WITH EXPANSION TUBES.
2. INSTALL 1 1/2" DEEP CONTRACTION JOINTS AT APPROXIMATELY 15' INTERVALS.
THESE JOINTS SHALL PASS THROUGH THE ENTIRE CURB SECTION.
3. FORM NOT REQUIRED BELOW GRADE.
#5 x 24" SMOOTH
DOWELS (SEE NOTES)
5' SIDEWALK
EXPANSION JOINT
6" VERTICAL CURB
SLOPED CONC PAVEMENT
6" VERTICAL CURB AND TAPERED END DETAIL
NOT TO SCALE
C501
SIDEWALK
2.0" ASPHALT SURFACE
NOTE:
1. ASPHALT SHALL FOLLOW NDDOT SUPERPAVE FAA41.
COMPACTED SUBGRADE
1 08/28/20 REV 1
8/25/2020
AA - ALUMINUM ASSOCIATION
AB - ANCHOR BOLT
ABT - ABOUT
ACI - AMERICAN CONCRETE
INSTITUTE
ADH - ADHESIVE
AGGR - AGGREGATE
AHR - ANCHOR
AISI - AMERICAN IRON AND
STEEL INSTITUTE
AISC - AMERICAN INSTITUTE OF
STEEL CONSTRUCTION
AL, ALUM - ALUMINUM
ALTN - ALTERNATE
ANSI - AMERICAN NATIONAL
STANDARDS INSTITUTE
ARCH - ARCHITECT
ASTM - AMERICAN SOCIETY FOR
TESTING OF MATERIALS
AWS - AMERICAN WELDING
SOCIETY
(B) - BOTTOM
BC - BOLT CIRCLE
BETW - BETWEEN
BLDG - BUILDING
BM - BEAM
BO - BOTTOM OF
BOC - BOTTOM OF CONCRETE
BOS - BOTTOM OF STEEL
BOT - BOTTOM
B/P - BASE OF PIER
BRG - BEARING
BRKT - BRACKET
C/C - CENTER TO CENTER
CL - CENTER LINE
CF - CUBIC FEET
CHKR - CHECKER
CIR - CIRCLE
CJ - CONSTRUCTION JOINT
CLR - CLEAR
CLJ - CONTROL JOINT
CMU - CONCRETE MASONRY UNIT
CO - CONCRETE OPENING
CONC - CONCRETE
CONT - CONTINUOUS
COL - COLUMN
COTR - CONTRACTING OFFICER
COR - CORNER
COORD - COORDINATE
CRSI - CONCRETE REINFORCING
STEEL INSTITUTE
CTR - CENTER
CTRD - CENTERED
CY - CUBIC YARD
DBL - DOUBLE
DET - DETAIL
DIAG - DIAGONAL
DIA - DIAMETER
DIM - DIMENSION
DK - DECKING
DL - DEAD LOAD
DN - DOWN
DWL - DOWEL
DWG - DRAWING
E - EAST
EA - EACH
EF - EACH FACE
EJ - EXPANSION JOINT
EL - ELEVATION
ELEC - ELECTRICAL
EMBED - EMBEDMENT
EQ - EQUAL
EQUIV - EQUIVALENT
EQ SP - EQUALLY SPACED
EQUIP - EQUIPMENT
EXIST - EXISTING
EW - EACH WAY
FD - FLOOR DRAIN
FDN - FOUNDATION
FTG - FOOTING
FF - FAR FACE
FL - FLOOR
FNSH - FINISH
FS - FAR SIDE
FT - FEET
GA - GAGE
GALV - GALVANIZE
GB - GRADE BEAM
GND - GROUND
GR - GRADE
GRTG - GRATING
HG - HIGH
HR - HANDRAIL
HPT - HIGH POINT
HORIZ - HORIZONTAL
HS - HIGH STRENGTH
IBC - INTERNATIONAL BLDG CODE
ID - INSIDE DIAMETER
IF - INSIDE FACE
IJ - ISOLATION JOINT
IN - INCHES
JT - JOINT
KSI - KIPS PER SQUARE INCH
L - ANGLE
LB - POUND
LD - DEVELOPMENT LENGTH
LG - LONG
LL - LIVE LOAD
LLH - LONG LEG HORIZONTAL
LLO - LONG LEG OUTSTANDING
LLV - LONG LEG VERTICAL
LONG - LONGITUDINAL
LPT - LOW POINT
LS - LAP SPLICE
MATL - MATERIAL
MAX - MAXIMUM
MC - MOMENT CONNECTION
MECH - MECHANICAL
MFR - MANUFACTURER
MH - MANHOLE
MIN - MINIMUM
MISC - MISCELLANEOUS
MK - MARK
NA - NOT APPLICABLE
NF - NEAR FACE
NOM - NOMINAL
NIC - NOT IN CONTRACT
NTS - NOT TO SCALE
NO - NUMBER
NS - NEAR SIDE
OC - ON CENTER
OD - OUTSIDE DIAMETER
OF - OUTSIDE FACE
OPNG - OPENING
OPP - OPPOSITE
OSHA - OCCUPATIONAL SAFETY
AND HEALTH ADMINISTRATION
OZ - OUNCE
PCF - POUNDS PER CUBIC FOOT
PED - PEDESTAL
PEMB - PRE-ENGINEERED METAL
BUILDING
PERP - PERPENDICULAR
PL - PLATE
PLC - PLACES
PLF - POUNDS PER LINEAR FOOT
PREFAB - PREFABRICATED
PS - PIPE SUPPORT
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PVC - POLYVINYL CHLORIDE
RD - ROOF DRAIN
REF - REFERENCE
REINF - REINFORCE
REQD - REQUIRED
REV - REVISION
RM - ROOM
S - SOUTH
SB - SHEAR BAR
SCHED - SCHEDULE
SIM - SIMILAR
SLP - SLOPE
SOG - SLAB ON GRADE
SP - SPACE
SPEC - SPECIFICATION
SQ - SQUARE
SST - STAINLESS STEEL
STD - STANDARD
STL - STEEL
STIF - STIFFENER
STR - STRAIGHT
STRL - STRUCTURAL
STRUC - STRUCTURE
TEMP - TEMPORARY
THK - THICK
THRU - THROUGH
(T) - TOP
T/ - TOP OF
TOA - TOP OF ALUMINUM
TOB - TOP OF BOLT
TOC - TOP OF CONCRETE
TOG - TOP OF GRATING
TOM - TOP OF MASONRY
TOS - TOP OF STEEL
T/P - TOP OF PIER
T&B - TOP AND BOTTOM
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VAR - VARIES
VERT - VERTICAL
VEF - VERTICAL EACH FACE
WD - WIDE
W/ - WITH
W/O - WITHOUT
WP - WORK POINT
WS - WATERSTOP
WT - WEIGHT
WWF - WELDED WIRE FABRIC
@ - AT
& - AND
# - POUNDS OR NUMBER
% - PERCENT
STANDARD ABBREVIATIONS
EARTH
MATERIAL LEGEND
COMPACTED FILL
ROCK
GRANULAR FILL
SAND
CONCRETE
GROUT
CONCRETE
MASONRY UNITS
(PLAN/SECTION)
BRICK (COMMON/FACE)
WATER
STEEL (LARGE SCALE)
GRATING
ALUMINUM
CHECKERED PLATE
STRUCTURAL STEEL
(SMALL SCALE)
CONCRETE W/
REINFORCING BAR
ADHESIVE/EPOXY
ANCHOR
EXPANSION
ANCHOR
C L J T
TYPICAL BOND
BEAM
CONTINUOUS BOND
BEAM
CONCRETE
MASONRY UNIT
(ELEVATION)
VOID FORM
GENERAL NOTES
1. CONTRACTOR SHALL COORDINATE ALL STRUCTURAL WORK WITH
WORK SHOWN ON ALL OTHER DRAWINGS.
2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS OF EXISTING
CONSTRUCTION AND REPORT ANY DISCREPANCIES FROM THE
CONTRACT OR REFERENCE DRAWINGS TO THE ENGINEER PRIOR TO
COMMENCING WITH WORK. IN NO CASE SHALL WORKING
DIMENSIONS BE SCALED FROM THE STRUCTURAL DRAWINGS.
3. THE CONTRACT DRAWINGS AND SPECIFICATIONS REPRESENT THE
FINISHED STRUCTURE. CONTRACTOR SHALL BE RESPONSIBLE FOR
MEANS AND METHODS OF CONSTRUCTION INCLUDING, BUT NOT
LIMITED TO, SHORING AND TEMPORARY BRACING TO PROVIDE
STRUCTURAL STABILITY DURING CONSTRUCTION.
4. IF CERTAIN FEATURES ARE NOT FULLY SHOWN OR CALLED FOR ON
THE CONTRACT DRAWINGS OR SPECIFICATIONS, THEIR
CONSTRUCTION SHALL BE OF THE SAME CHARACTER AS FOR
SIMILAR CONDITIONS THAT ARE SHOWN OR CALLED FOR, WITH THE
APPROVAL OF THE ENGINEER. WHERE SECTIONS VARY,
CONTRACTOR SHALL PROVIDE FOR SMOOTH TRANSITIONS BETWEEN
THEM, UNLESS NOTED OTHERWISE.
5. ALL PRODUCTS SHALL BE INSTALLED IN ACCORDANCE WITH THE
MANUFACTURERS WRITTEN INSTRUCTIONS AND
RECOMMENDATIONS, UNLESS NOTED OTHERWISE.
CONCRETE AND REINFORCING
1. SEE DRAWINGS S004 - S006 FOR CONCRETE AND CONCRETE
REINFORCING DETAILS AND DESIGN NOTES.
FOUNDATION EXCAVATION
1. ALL INFORMATION CONTAINED ON THE FOUNDATION DRAWINGS IS
BASED ON A REPORT TITLED "GEOTECHNICAL ENGINEERING REPORT,
WAPA VEHICLE MAINTENANCE FACILITY" PREPARED BY TERRACON
CONSULTANTS, INC PROJECT NO. M2205057, AUGUST 2020. THE
MENTIONED DOCUMENT IS NOT PART OF THE CONTRACT. IN THE
EVENT OF DISCREPANCIES BETWEEN THE ABOVE DOCUMENT AND
THE FOUNDATION DRAWINGS, THE FOUNDATION DRAWINGS SHALL
GOVERN.
2. FLOOR SLAB EXCAVATION: SLAB EXCAVATION SHALL EXTEND TO A
MINIMUM ELEVATION OF 1662'. ALL INTERIOR SLABS ON GRADE SHALL
BE PLACED OVER 6 INCHES OF FREE-DRAINING (LESS THAN 8%
PASSING THE U.S. NO 200 SIEVE) CRUSHED AGGREGATE OR SAND,
COMPACTED TO AT LEAST 95% OF MAXIMUM DENSITY.
3. FOUNDATION EXCAVATION: FOUNDATION EXCAVATION SHALL EXTEND
TO A MINIMUM ELEVATION OF 1660'. ALL OTHER FOUNDATIONS SHALL
BE PLACED ON STRUCTURAL FILL COMPACTED TO AT LEAST 95% OF
MAXIMUM DENSITY.
4. MAXIMUM SOIL LIFT THICKNESS SHALL BE 6 INCHES WHEN USING
HAND-GUIDED EQUIPMENT AND 9 INCHES WHEN HEAVY, SELF-
PROPELLED COMPACTION EQUIPMENT IS USED.
5. ON-SITE MATERIALS ARE SUITABLE FOR RESUSE AS A STRUCTURAL
FILL PROVIDED THEY MEET THE COMPACTION CRITERIA OUTLINED
ABOVE AND ARE FREE OF VEGETATION, ORGANIC MATTER AND
OTHER DELETERIOUS MATERIALS.
MISCELLANEOUS MATERIALS
1. GROUT FOR EQUIPMENT BASE PLATES SHALL BE NON-SHRINK NON-
METALLIC HIGH STRENGTH GROUT. GROUT SHALL BE FIVE STAR
GROUT BY U.S. GROUT CORPORATION OR APPROVED EQUAL. ALL
GROUTING REQUIRES CURING THE EXPOSED SURFACE WITH CURING
AND SEALING COMPOUND IMMEDIATELY AFTER INSTALLATION.
2. BONDING AGENT SHALL BE SIKADUR 32, HI-MOD BY SIKA
CORPORATION OR APPROVED EQUAL.
3. PROVIDE VAPOR RETARDER FOR INTERIOR FLOOR SLABS BENEATH
GRANULAR FILL MATERIAL WHEN SPECIFIED ON PROJECT-SPECIFIC
DOCUMENTS. MATERIAL SHALL CONFORM TO E1745 CLASS A, HAVE A
MAXIMUM PERM RATING OF 0.018, A MINIMUM MIL THICKNESS OF 15,
MINIMUM TENSILE STRENGTH OF 84 LB/IN, AND MINIMUM PUNCTURE
RESISTANCE OF 4135 GRAMS. MATERIAL SHALL BE EQUAL TO W.R.
MEADOWS PERMINATOR 15 MIL UNDERSLAB VAPOR RETARDER (HIGH
PUNCTURE RESISTANCE). ALL JOINTS/SEAMS, BOTH SIDE AND END,
SHALL BE OVERLAPPED 6" MINIMUM, AND TAPED USING W.R.
MEADOWS 4" WIDE PERIMETER TAPE (OR EQUAL); USE SAME
MATERIAL FOR ATTACHMENT TO FOUNDATION WALLS. ALL REPAIRS
SHALL BE MADE USING ORIGINAL MATERIALS.
PRE-ENGINEERED METAL BUILDING
1. THE FOUNDATION AND ANCHOR BOLT LAYOUT SHOWN IS BASED ON
PRELIMINARY COLUMN REACTIONS BASED ON THE LOAD CRITERIA
SHOWN ON THIS SHEET.
2. BUILDING COLUMN REACTIONS TO BE DETERMINED AFTER PEMB
CONTRACT IS AWARDED. FOUNDATION DESIGN AND ANCHOR BOLT
DESIGN SHALL BE CONFIRMED UPON RECEPT OF COLUMN REACTIONS
FROM PEMB MANUFACTURER.
DESIGN NOTES:
A. STRUCTURAL DESIGN WAS PREPARED USING THE FOLLOWING
CODES AND DATA:
1. INTERNATIONAL BUILDING CODE, 2018 EDITION
2. ACI 318 BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE
3. ASCE 7 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER
STRUCTURES, 2016 EDITION
B. LIVE LOADS:
1. GARAGES - TRUCKS AND BUSES (16,000 LB OVER A 20" X 10"
TIRE CONTACT AREA)
2. ROOF LIVE LOAD - 20 PSF
C. SNOW LOADS:
1. GROUND SNOW LOAD (Pg) - 35 PSF
2. FLAT-ROOF SNOW LOAD (Pf) - 24.3 PSF
3. SNOW EXPOSURE FACTOR (Ce) - 0.9
4. SNOW LOAD IMPORTANCE FACTOR (Is) - 1.10
5. THERMAL FACTOR (Ct) - 1.0
6. SLOPE FACTOR (Cs) - 1.0
7. DRIFT SURCHARGE LOADS (Pd) - N/A
D. WIND DESIGN DATA:
1. BASIC DESIGN WIND SPEED (V) - 121 MPH
2. NOMINAL DESIGN WIND SPEED (Vasd) - 94 MPH
3. RISK CATEGORY III
4. EXPOSURE CATEGORY C
5. INTERNAL PRESSURE COEFFICIENT - ±0.18
E. SEISMIC DESIGN DATA:
1. RISK CATEGORY III
2. SEISMIC IMPORTANCE FACTOR (Ie) - 1.25
3. MAPPED SPECTRAL RESPONSE PARAMETERS:
a. SS = 0.054
b. S1 = 0.023
4. SOIL SITE CLASS E
5. DESIGN SPECTRAL RESPONSE PARAMETERS:
a. SDS = 0.086
b. SD1 = 0.063
6. SEISMIC DESIGN CATEGORY A
7. BASIC SEISMIC FORCE RESISTING SYSTEM(S):
a. STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE, EXCLUDING CANTILEVER COLUMN
SYSTEMS
8. DESIGN BASE SHEARS(S): 9.35 KIPS
9. SEISMIC RESPONSE COEFFICIENT(S) (CS) - 0.036
10. RESPONSE MODIFICATION COEFFICIENT(S) (R) - 3.0
11. ANALYSIS PROCEDURE USED: EQUIVALENT LATERAL FORCE
METHOD
F. GEOTECHNICAL INFORMATION & SOIL PROPERTIES:
a. SOIL ALLOWABLE BEARING PRESSURE (UNO): 1,500 PSF
DEFERRED SUBMITTALS:
SUBMITTAL DOCUMENTS FOR DEFERRED SUBMITTAL
ITEMS SHALL BE SUBMITTED TO THE ARCHITECT AND
ENGINEER OF RECORD, WHO SHALL REVIEW THEM AND
FORWARD THEM TO THE BUILDING OFFICIAL WITH A
NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
DOCUMENTS HAVE BEEN REVIEWED AND THAT THEY
HAVE BEEN FOUND TO BE IN GENERAL CONFORMANCE
WITH THE DESIGN OF THE BUILDING. THE DEFERRED
SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL
THEIR DESIGN AND SUBMITTAL DOCUMENTS HAVE BEEN
APPROVED BY THE BUILDING OFFICIAL.
AS A MINIMUM, ITEMS REQUIRING DEFERRED
SUBMITTALS ARE AS FOLLOWS:
1. PRE-ENGINEERED METAL BUILDING SYSTEM -
INCLUDES ALL STEEL FRAMING AND ANCHOR BOLT
LOADING.
NON STRUCTURAL ITEMS NOT SPECIFICALLY IDENTIFIED
ABOVE AND NOT INCLUDED IN THESE STRUCTURAL
DRAWINGS SHOULD ALSO BE CONSIDERED DEFERRED
SUBMITTALS.
THE ABOVE LISTED SUBMITTAL DOCUMENTS SHALL BE
STAMPED AND SIGNED BY A REGISTERED
PROFESSIONAL ENGINEER IN THE APPROPRIATE STATE.
SEE STRUCTURAL SPECIFICATIONS FOR ADDITIONAL
SUBMITTAL REQUIREMENTS.
BSM
HEADQUARTERS - LAKEWOOD, COLORADO
BISMARCK O & M SERVICE CENTER
VEHICLE STORAGE BLDG N0.4
NORTH DAKOTA
UNITED STATES DEPARTMENT OF ENERGY
APPROVED
E A
C
DESIGNED
WESTERN AREA POWER ADMINISTRATION
S00105/29/20
GENERAL NOTES SHEET I
N. WITHERS U. PANDEY
BOLSTER SUPPORTS FOR REBAR:
1. GENERAL: TOP SURFACE OF COMPACTED BASE GRANULAR FILL
MATERIAL SHALL NOT BE CONSIDERED EQUIVALENT TO A
FORMED SURFACE REGARDING CLEARANCES ABOVE EARTH.
REBAR LOCATION SHALL BE AS SPECIFIED AND SHOWN IN
DETAILS; AND SHALL BE AS MEASURED FROM BOTTOM SURFACE
OF CONCRETE SLAB. ALL SLAB REINFORCEMENT SHALL BE
POSITIVELY SUPPORTED AT CORRECT POSITION USING BOLSTER
SYSTEM PRIOR TO CONCRETE PLACEMENT; VIOLATION OF THIS
PROVISION WILL RESULT IN REJECTION WITHOUT EXCEPTION.
UNDER NO CIRCUMSTANCES WILL IT BE ACCEPTABLE TO "PULL"
REBAR INTO POSITION DURING CONCRETE PLACEMENT;
VIOLATION WILL RESULT IN REJECTION WITHOUT EXCEPTION.
2. MAIN 8" SLAB-ON-GRADE SECTIONS (UNLESS SPECIFIED
OTHERWISE) : EQUAL TO DAYTON SUPERIOR 3-1/2" TALL x 5'
LONG CONTINUOUS HIGH CHAIR WITH PLATE (CHCP-TYPE, PART
NUMBER 74924) WITH CONTINUOUS 5' LONG TOP WIRE AND (2) 1"
WIDE x 5' LONG CONTINUOUS STEEL BASE PLATES (1 PER LEG);
SPACE SUPPORTS AT 24" MAXIMUM.
3. PERIMETER 12" DEEP TURN DOWN SECTIONS IN EXTERIOR
APRONS, SIDEWALKS, ENTRY AND EQUIPMENT SLABS-ON-
GRADE: EQUAL TO DAYTON SUPERIOR 9-1/2" TALL x 5' LONG
CONTINUOUS HIGH CHAIR (CHC-TYPE, PART NUMBER 121104)
WITH CONTINUOUS 5' LONG TOP WIRES.
PREFORMED JOINT FILLER MATERIALS AND SEALANTS:
1. EXTERIOR: MATERIAL EQUAL TO W.R. MEADOWS
ASPHALT EXPANSION / CONTRACTION JOINT FILLER
CONFORMING TO ASTM D994, THICKNESS AS SHOWN
ON DRAWINGS.
2. INTERIOR VEHICLE BAYS: MATERIAL EQUAL TO W.R.
MEADOWS FIBRE EXPANSION / CONTRACTION JOINT
FILLER CONFORMING TO ASTM D 1751, THICKNESS AS
SHOWN ON DRAWINGS. HOLD PRODUCT DOWN TO
LEAVE ROOM FOR COMPATIBLE SEALANT.
3. JOINT SEALANT SHALL BE COMPATIBLE WITH
SPECIFIED JOINT FILLER MATERIALS, AND SHALL BE
INTERIOR OR EXTERIOR GRADE CONSISTENT WITH
SPECIFIED LOCATIONS.
GEOTEXTILE FABRIC:
1. PROVIDE GEOTEXTILE FABRIC WHEN SPECIFIED ON
PROJECT-SPECIFIC DOCUMENTS. GEOTEXTILE FABRIC
SHALL BE WOVEN, BLACK POLYPROPYLENE FABRIC
AND HAVE A FILL TENSILE STRENGTH NOT LESS THAN
200 POUNDS, FILL ELONGATION NOT MORE THAN 20
PERCENT, BURST STRENGTH NOT LESS THAN 450 PSI,
AND PUNCTURE STRENGTH NOT LESS THAN 75
POUNDS. INSTALL GEOTEXTILE FABRIC IN
ACCORDANCE WITH MANUFACTURER'S INSTRUCTION.
A 06/02/20 30% DESIGN REVIEW
B 06/23/20 90% DESIGN REVIEW
0 07/02/20 ISSUED FOR CONSTRUCTION
1 08/28/20 REV 1